1. JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 12 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON TS id AX 4 6 CT The CT option sets the current ratio 172000 and secondary current CT2 1A or 5A of the current transformer CT that wires to the meter From the Set up menu use ES and ES buttons to select the CT option The screen will show the current CT primary current value Secondary CT setting Press to enter the CT secondary current selection routine 5 1 Set CT Ratio Value Press to enter the CT Ratio The range is from 0001 2000 For example if set the ratio to be 100 that means the primary current is secondary current x100 4 7 PT The PT option sets the primary voltage PTratio100 500000V and secondary voltage PT2 100 500V of the Voltage transformer PT that wires to the meter The default value is 230V for both primary and From the Set up menu use EN and ES buttons to select the PT option The screen will show the voltage PT primary voltage secondary voltage value JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 13 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON TLS id AX
2. Q 8 5 gem Nt 2 96 00 96 00 16 a 7 Wiring diagram E voltage output 7 8 0 11111 Power output fornext meter FAST BLOW FUSE LOAD single phase two wire JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD oe TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON 7 RLS ed aX Si L3 L2 E LOAD 0 131415 19 2021222324 1A FAST BLOW FUSE 1 L2 A ne LOAD Li three phase three wire L3 L2 LOAD L1 13141518 i718 19 20 21 22 2324 current input SO output vonage votage output 221193456 78 8 101112 Power output QOQQOQOQOOQOOOOQl fornextmeter 1 FAST AAAA BLOW FUSE I D d TL M ia LOAD L3 N three phase four wire JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD sale TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON AGIS is dx Annex label in the back of the meter JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 28 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan R
3. 0 001 0 01 0 1 1 10 100kWh kVarh per pulse buttons to choose pulse rate JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 15 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON AK IB iid AX On Completion of the entry procedure press to confirm the setting and press EN to return to the main set up menu 4 8 2 Pulse Duration The energy monitored can be active or reactive and the pulse width can be selected as 200 100 or 60ms he shows pulse width of 200ms From the Set up menu use ES and ES buttons to select the Pulse width option On Completion of the entry procedure press to confirm the setting and press EN to return to the main set up menu JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 16 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON There is a RS485 port can be used for communication using Modbus RTU protocol For Modbus RTU 4 9 Communication parameters are selected from Front panel 4 9 1 RS485 Address address ranges from 1 to 247 4 9 2 Baud Rate From the Set up menu use ES and ES buttons to select the Baud Rate option Press to enter the selection routine The Baud Rate setting
4. EASTRON 27 MULTIFUNCTION POWER MINITOR SMARTconnect X835 USER MANUAL 2013 V2 0 EASTRON S THEIR Installation and Operation Instructions Important Safety Information is contained in the Maintenance section Familiarise yourself with this information before attempting installation or other procedures Symbols used in this document Risk of Danger These instructions contain important safety information Read them before starting installation or servicing of the equipment Caution Risk of Electric Shock JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 1 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON EU 1 Introduction The multifunction panel meter SMARTconenct X835 is a top new generation intelligent panel meter used not only in the electricity transmission and power distribution system but also in the power consumption measurement and analysis in high voltage intelligent power grid This document provides operating maintenance and installation instructions for the Eastron SMARTconenct X835 The unit measures and displays the characteristics of single phase two wires and three phase four wires supplies including voltage frequency current power and active and reactive energy imported or exported Energy is measured in terms of kWh kVarh Maximum demand current
5. Secondary PT setting The setting method is same as Primary voltage setting PT1 Max PT2 value is 500V Set PT Ratio Value Press to enter the PT Ratio The range is from 0001 2000 For example if set the ratio to be 100 that means the primary current is secondary current x100 4 8 Pulse output This option allows you to configure the pulse output The output can be set to provide a pulse for a defined amount of energy active or reactive Use this section to set up the relay pulse output Units kWh kVarh From the Set up menu use EN and ES buttons to select the Pulse output option Press to enter the selection routine The unit symbol will flash JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 14 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON AX Use ES and buttons to choose kWh or kVarh On Completion of the entry procedure press to confirm the setting and press to return to the main set up menu 4 8 1 Pulse rate Use this to set the energy represented by each pulse Rate can be set to 1 pulse per 0 001Wh 0 01kWh 0 1kWh 1kWh 10kWh 100kWh It shows 1 impulse 1Wh kVarh From the Set up menu use ES and ES buttons to select the Pulse Rate option Press to enter the selection routine The current setting will flash
6. will flash Use ES and ES buttons to choose Baud rate 2 4k 4 8k 9 6k 19 2k 38 4k JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 17 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON id AX From the Set up menu use ES and ES buttons to select the Parity option 4 9 3 Parity Press E to enter the selection routine The current setting will flash Use EN and FS buttons to choose Parity EVEN ODD NONE 4 9 4 Stop bits From the Set up menu use EN and ES buttons to select the Stop Bit option JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 18 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON iil dx 4 10 CLR 4 10 1 CLR kWh From the Set up menu use EN and ES buttons to select the reset option Press to enter the selection routine The yes will flash 3 r Press to confirm the setting and press to return to the main set up menu JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 19 TEL 0086 5 73 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 53h EASTRON
7. 4 4 DIT Demand Integration Time This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement The options are off 5 10 15 30 60 minutes 1 From the set up menu use ES buttons to select the dIT option The screen will show the currently selected integration time Press to enter the selection routine The current time interval will flash 3 Use EN and ES buttons to select the time required Press to confirm the selection SET indicator will appear KS Press to exit the dIT selection routine and return to the menu JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 11 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON TS id AX 4 5 Supply System Use this section to set the type of power supply being monitored From the Set up menu use ES and ES buttons to select the System option The screen will show the currently selected power supply Press to enter the selection routine The current selection will flash Use ES and ES buttons to select the required system option 3BPAW 3P3W 1P2W Press to confirm the selection SET indicator will appear Press to exit the system selection routine and return to the menu SET will disappear and you will be returned to the main Set up Menu
8. EET EE From the Set up menu use ES and ES buttons to select the reset option 4 10 2 CLR KVarh Press E to enter the selection routine The yes will flash to confirm the setting and press to return to the main set up menu From the Set up menu use EN and ES buttons to select the reset option Press to enter the selection routine The yes will flash 3 to confirm the setting and press to return to the main set up menu JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 20 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON 4 11 reverse connected current inputs correction setting 1 From the Set up menu use ES and ES buttons to select page SET sys cont Press to enter Phase A the default is frd forward 3 use ES and ES buttons to Phase B or C setting pages 4 to confirm the setting and press to return to the main set up menu 4 11 2 how to operate if phase A is reversely connected Go to phase A setting page JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 21 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON TS iil dx Press 4 to enter the selection routine
9. The Frd will flash Use ES button to change Frd to rEV On Completion of the entry procedure press to confirm the setting and press ES to return to the main set up menu 4 12 setting auto scroll display interval Use the EN and ES to choose the change Round of the significant time option Press the to enter the change password routine The new Round of the significant time screen will appear with the first digit flashing Use ES and ES to set the first digit and press Oe confirm your selection The next digit will flash JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 22 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON Repeat the procedure for the remaining three digits After setting the last digit SET will show i Press to exit the number setting routine and return to the Set up menu SET will be removed After setting you still need to active the auto scroll display function by keep pressing the button ESC If you want exit from auto scroll display mode you can pressing the ESC button to get out 5 Specifications 5 1 Measured Parameters The unit can monitor and display the following parameters of a single phase 3 phase 3 wire or 3 phase 4 wire supply 5 1 1 Voltage and Current Phase to neutral voltages 100 to 289V a c not for 3p3w supplie
10. and Power factor screens In Set up Mode this is the Up button Select the Power screens In Set up Mode this is the Down button Select the Energy display screens In Set up mode this is the Enter or Right button 3 1 Voltage and Current Each successive pressing of the Hm selects a new range Phase to neutral voltages Current on each phase JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON TS id AX EASTRON iil dx Phase to neutral voltage THD Current THD for each phase 3 2 Frequency and Power Factor and Demand EN Each successive pressing of the EN button selects a new range Total kW Frequency Power factor total Power factor of each phase JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 5 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON iil dx Max Power demand Max Current demand 3 3 Power FS Each successive pressing of the FS button select a new range Instantaneous active power kW Instantaneous reactive power kVar JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 6 TEL 0086 573 83698881 83
11. 698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 Instantaneous Volt amps KVA Total kW kVarh kVA 3 4 Energy Measurements Each successive pressing of the button selects new range Imported active energy in kWh Exported active energy in kWh Imported reactive energy in kVarh Exported reactive energy in kVarh Total active energy in kWh Total reactive energy in kVAh JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON iil dx EASTRON iil dx 4 Set up To enter set up mode pressing the for 3 seconds until the password screen appears Setting up is password protected so you must enter the correct password default 1000 before processing If an incorrect password is entered the display will show PASS Err To exit setting up mode _ repeatedly until the measurement screen is restored 4 1 Set up Menu Structure Change password nnnn 4 digit number default 1000 Set the ratio of the CT nnnn 4 digit number 000172000 set the ratio of PT Nnnn 4 digit number 000172000 This is the period in minutes over which the current and power readings are integrate
12. TRONIC INSTRUMENTS CO LTD 2 TEL 0086 573 83698881 83698882 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 EASTRON PRLS ied dx 1 3 RS485 Serial Modbus RTU This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the SMARTconnect X835 Set up screens are provided for setting up the RS485 port See section 4 8 1 4 Pulse output This provides 2 pulse outputs those clocks up measured active and reactive energy The constant for reactive energy is 5000imp kVarh The pulse width for active energy be set from the Set up menu 2 Start up Screens The first screen lights all display segments and can be used as a display check The second screen indicates the firmware installed in the unit and its build number Next the unit performs a self test and indicates if the test passes After a short delay the screen will display active energy measurements JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 3 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 3 Measurements The buttons operate as follows Selects the Voltage and Current display screens In Set up Mode this is the Left or Back button Select the Frequency
13. can be measured over preset periods of up to 60minutes In order to measure energy the unit requires voltage and current inputs in addition to the supply required to power the product The requisite current input s are obtained via current transformers CT The SMARTconenct X835 can be configured to work with a wide range of CTs giving the unit a wide range of operation Built in interfaces provide pulse and RS485 Modbus RTU outputs Configuration is password protected 1 1 Unit Characteristics The SMARTconenct X835 can measure and display Line voltage and THD total harmonic distortion of all phases Line Frequency Currents Current demands and current THD of all phases Power maximum power demand and power factor Active energy imported and exported Reactive energy imported and exported The unit has password protected set up screens for Changing password Supply system selection 1phase2wire 3phase 4wires CT Ratio and secondary current PT Ratio and secondary voltage Demand Interval time Reset for demand measurements Pulse output duration A pulse output indicates real time energy measurement An RS485 output allows remote monitoring from another display or a computer 1 2 Current Transformer Current ratio The unit can be configured to operate with CT ratio between primary and secondary current is 1 and 2000 Maximum CT primary current corresponds to a maximum input current to the unit of 1 5A JIAXING EASTRON ELEC
14. d for maximum DIT Demand Integration Time JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 8 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON V TRG 4x demand measurement Options are off 5 10 15 30 and 60minutes 4 2 Set up Entry Methods Some menu items such as password and CT require a four digit number entry while others such as supply system require selection from a number of menu options 4 2 1 Menu Option Selection i 1 Use the ii and M buttons to select the required item from the menu shown in section 4 1 selection does not roll over between bottom and top of list 2 Press Mi to confirm your selection 3 if an item flashes then it be adjusted by the ii and M buttons If not there maybe a further layer 4 Having selected an option from the current layer press to confirm your selection The SET indicator will appear 5 Having completed a parameter setting press EN to return to a higher menu level The SET indicator i will be removed and you will be able to use the li and M buttons for further menu selection 6 On completion of all setting up press zt repeatedly until the measurement screen is restored 4 2 2 Number Entry Procedure When Setting up the unit some screens require the entering of a number In particular on entry to th
15. e setting up section a password must be entered Digits are set individually from left to right The procedure is as follows e 1 the current digit be set flashes and is set using the ii and M buttons 2 Press Mi to confirm each digit setting The SET indicator appears after the last digit has been set 4 3 After setting the last digit press EN to exit the number setting routine The SET indicator will be removed JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 9 TEL 0086 573 83698881 83698882 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON id 4x ES and ES to choose the change password option 4 3 Change Password Press the E to enter the change password routine The new password screen will appear with the first digit flashing Use ES and ES to set the first digit and press confirm your selection The next digit will flash Repeat the procedure for the remaining three digits After setting the last digit SET will show JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 10 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON iil dx li E _ to exit the number setting routine and return to the Set up menu SET will be removed
16. h VArh 0 1 100 Wh VArh 1 1kWh kVArh 10 10 kWh kVArh 100 100 kWh kVArh Pulse width 200 100 60 ms Relay Rating 240V ac 50mA 5 5 2 RS485 Output for Modbus RTU For Modbus RTU the following RS485 communication parameters can be configured from the Set up menu Baud rate 2400 4800 9600 19200 38400 Parity none odd even Stop bits 1 or 2 RS485 network address nnn 3 digit number 1 to 247 Modbus Word order Hi Lo byte order is set automatically to normal or reverse It cannot be configured from the set up menu 5 6 Reference Conditions of Influence Quantities Influence Quantities are variables that affect measurement errors to a minor degree Accuracy is verified under nominal value within the specified tolerance of these conditions Sinusoidal distortion factor 0 005 Auxiliary supply voltage Nominal 1 Auxiliary supply frequency Nominal 1 Auxiliary supply waveform if AC Sinusoidal distortion factor 0 05 Magnetic field of external origin Terrestrial flux 5 7 Environment Operating temperature Relative humidity Maximum operating and storage temperatures are in the context of typical daily and seasonal variation JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD s29 TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON TS id 4x 6 Dimensions O
17. oad Nanhu Jiaxing Zhejiang China 314001
18. s Voltages between phases 173 to 500V a c 3p supplies only Percentage total voltage harmonic distortion THD96 for each phase to N not for 3p3w supplies Percentage voltage THD96 between phases three phase supplies only Current on each phase 1 to 9999A range set by external current transformer s CTs Current THD 6 for each phase 5 1 2 Power factor and Frequency and Max Demand Frequency in Hz Power to 999MW Reactive Power to 999MVAr Volt amps 0 to 999 MVA Maximum demanded power since last Demand reset Power factor Maximum neutral demand current since the last Demand reset three phase supplies only JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD ds TEL 0086 573 83698881 83698882 FAX 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON 5 1 3 Energy Measurements Imported active energy to 9999999 9 kWh Exported active energy to 9999999 9 kWh Imported reactive energy 0 to 9999999 9 kVArh Exported reactive energy 0 to 9999999 9 kVArh Total active energy to 9999999 9 kWh Total reactive energy to 9999999 9 kVArh 5 2 Measured Inputs Voltage inputs through 4 way fixed connector with 2 5mm2 stranded wire capacity 3 Phase 3 and 4 wire and Single phase 2 wire unbalanced Line frequency measured from L1 voltage or L3 voltage Three current inputs six physical terminals with 2 5mm2 stranded
19. wire capacity for connection of external CTs Nominal rated input current 5A or 1A a c Rms 5 3 Accuracy 0 5 of range maximum 2 of range maximum 1 of range maximum Class 1 IEC 62053 21 2 of range maximum 1 up to 31st harmonic Temperature co efficient Voltage and current 0 013 C typical Active energy 0 01896 C typical Response time to step input 1s typical to gt 99 of final reading at 50 Hz 5 4 Auxiliary Supply Two way fixed connector with 2 5mm2 stranded wire capacity 85 to 275V a c 50 60Hz 10 or 120V to 380V d c 20 Consumption 10W 5 5 Interfaces for External Monitoring Three interfaces are provided anRS 485 communication channel that can be programmed for Modbus RTU protocol anrelay output indicating real time measured energy configurable anpulse output 5000imp kWh not configurable The Modbus configuration Baud rate etc and the pulse relay output assignments kW kVArh import export etc are configured through the Set up screens JIAXING EASTRON ELECTRONIC INSTRUMENTS CO LTD 24 TEL 0086 573 83698881 83698882 0086 573 83698883 WEB www eastrongroup com Email sales eastrongroup com Add No 1369 Chengnan Road Nanhu Jiaxing Zhejiang China 314001 EASTRON S7 TUE TAX 5 5 1 Pulse Relay Output The pulse relay output can be set to generate pulses to represent kWh or kVArh Rate can be set to generate 1 pulse per 0 001 1Wh VArh 0 01 10 W
Download Pdf Manuals
Related Search
Related Contents
TG-1工一郎 取扱説明書 PV-10072015 PowerTracker VII User Manual INSTALLATION MANUAL Cassette Type Series 12360 ACH550 brochure REV E_68295378.indd GeoPocket_Manual. (EDI) User`s Manual - the Illinois Law Enforcement Training and POWER TROWEL POWER TROWEL Descargar - Documentación técnica Contents Chapter 1 - Introduction ....................................................... Copyright © All rights reserved.