         Contents
1.       3 13  Autotest    3 13 1  CCT  Cumulated Current Test    o Menu  gt  Management  gt  Diagnostics  gt  CCT     Cumulated Current Test    CCT     Cumulated Current Test is a mechanism monitoring the value of cumulated current for each phase   Monitoring consists in adding measured each breaking current to the sum of the former ones  Breaker state  report is available via communication ports and user interface  In case the sum of breaking currents exceeds a  warning level indicating that the CB wear may cause a failure a warning is generated to carry out service  inspection or its replacement     IU M710P MANUAL 05i00 ENG Strona 29 z 36     MuUPASZ  710 plus User manual    3 13 2  CBCT   Circuit Breaker Control Test    Q Menu  gt  Management  gt  Diagnostics  gt  CBCT     Circuit Breaker Control Test    CBCT   Circuit Breaker Continuity Test checks the continuity of the control lines of the breaker coils and  auxiliary voltage  Lack of continuity is indicated by a message on the LCD display  the LED diode and the relay  UP output  memorized signalization   Signaling can be reset by pressing UP button on the operator panel     The CBCT can be blocked in the device settings independently for opening and closing circuits     3 13 3  HVT  High Voltage Test          Menu  gt  Management  gt  Settings  gt  Settings X  gt Autotest  gt  HVT    HVT     High Voltage Test checks the cable insulation  using external high voltage generator  It allows testing  cable insulation and verif
2.   amp    confirms edited value        G amp G   results in leaving the window without saving changes     Edition of a NUMBER parameter    Characteristic    OeNormally dependent IEC  O Very dependent IEC    O Extremely dependent IEC  O Dependent with long time          consists in entering the number in accordance with the format and within allowable range    The name of the edited parameter is displayed in the  window header line  Allowable range of the parameter   min  max  is displayed below    Edition of number is carried out by means of the following  keys    O     increment or decrement one digit     o   lt         gt    position change     fox    confirms edited value         results in leaving the window without saving changes     Changed parameters are displayed in red     Save     used for storing all protection parameters  After  its pressing a   write    message appears   Pressing the     key results in leaving the    gt  IDMT  1   window without memorizing the edited parameters        Strona 22 z 36       Ir  In   min  0  10  max  25 00    oifflo    I  gt  IDMT  1     Options        Direction  None  Characteristic  Steep  Ir  InjJ  1 10    Active events         Logging In    IU M710P MANUAL 0O5i00 ENG    User manual MuPASZ EATI    3 9 2  Supervision    3 9 2 1  User manager  UM     A Q Menu  gt Management gt  Supervision  gt  Users    The application controls and identifies access by 14 users to device functions  e g   changing set points   editing configuration p
3.   following types of wiring of communication ports are used     Lor    baad      RS485 B2     RS485 A2    RS485 Bl       55    Type I  2 wire              GNDI               Fig  4 2 1  Intermediate position of the device in 2 wire communication network    Type II  2 wire        Fig  4 2 2  Extreme position of the device in 2 wire communication network    It is recommended that shielded twisted pair is used  with characteristic impedance 120 Q and low wire to   wire capacity  with additional wire equalizing potentials of individual transmission modules  One end of  shielding wire should be connected with protective potential of the system     IU M710P MANUAL 05i00 ENG Strona 33 z 36    User manual  4 3  Twisted Pair RJ Ethernet Modem    The device may be fitted with an optional Ethernet module with MODBUS TCP and IEC 61850 protocols     n c  Pin 4 Pin 5 n c   TD  Pin3 Pin6 TD   RD  Pin 2 Pin 7 n c   RD  Pin 1 Pin 8 n c        Fig 4 3 1  RJ 45 female connector     4 4  ST Optical Fibre    Connection of optical signals consists in plugging ST plugs in relevant sockets paying particular attention to  proper matching Tx and Rx transmission directions    During transportation and when cables are not connected optical sockets should be protected with sealing  caps  If the optical sockets get dirty or covered with dust they should be cleaned with compressed air before  connecting ST plugs     Name Function  Tx Optical signal transmit output  to the Rx socket in the cooperating devic
4.   protection set to opening of the main switch       Tripping    selected in Options   Execution of an algorithm  e g  protection set to lock      Lock    or  Temporary  lock    selected in Options    Tripping  Lock    Executed Execution of an algorithm  e g  protection    OAT OL    3 6  Measurements    Q Menu  gt  Measurements         Measurements    The resource stores and provides access to all  measurements carried out by the device  Measurements Measurements  have flags assigned to them that represent their state and   lt lu 12  Vv     validity status  see table below     lt  u23  V     By pressing the Oa   Selected keys either all available or I lt JI1  A    0  only user selected measurements will be displayed    lt JI2  A   0    I lt JI3  A    0      x f  Hz        Pressing the      Clearing key opens the window for clearing      Clearing  counters  e g  work time or energy counters     Cumulated current counters  Energy counters    Counter of    aa time       Configuration of Selected measurements is also possible via the ELF software tool     Strona 16 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MUPASZ Palys    Table 3 6 1 Flags of measurements    Symbol Flags of measurements Description    Only used with measurements of resistance  Means opening in measured    ID  circuit    Above the range Measured value exceeds upper measuring limit  Not available No measurement  e g  no measurement channel    Below the range Measured value exceeds lower measuring limit    Measu
5.  4 7 and PN EN 61000 4 30  standards  It provides the THD value and the harmonic  content  up to the 40th  of phase voltages and currents   The THD and harmonic content values are used in  harmonic protections  that enable selective localization of  faults  e g  bearings damage in motor drives  increase in  transformer core magnetization    The PQA     Power Quality Analyzer window displays the  averaged values  harmonic content and THD coefficient     Mean values  Harmonics  Mean value harmonics       3 11 5  SLOG     System Log    o Menu  gt  Management  gt  Extensions  gt  SLOG   System Log       System log stores information with date and time stamp  referring to logins of individual users  last change in  set points  last cancelling of signalization  changes in profiles  bay view  parameters of communication ports   user commands  The log is accessible via SCADA system and ELF software tool     IU_M710P_MANUAL_05i00_ENG Strona 27 z 36    User manual  3 11 6  UPS    Uninterruptible Power Supply       The UPS system will maintain the full functionality of the device for 60 seconds after power failure or 200  seconds when the display backlight is turned off  The most common use of these system is in devices which  are away from the position of dispatcher  in tight spaces or in hazardous areas  The system is used very often  in facilities that do not have a guaranteed supply  It immunizes the device from short power outages which  allows to keep continuity of information abo
6.  e    circuit breaker   contactor   load switch   disconnecting switch  disconnecting earthing switch  truck   earthing switch  short circuiting switch    local remote  user interface  transmission  binary inputs  switches  open  close  insertion  withdrawal   cancelling      failures AW   TRIP     signaling UP   ALARM       lock   LOCK   binary and analog outputs   user commands    Automatic functions    AACF     Automatic Active Component Forcing   ACCB     Automatic Connection of Capacitor Battery  CBF   Circuit Breaker Failure   AUELS   Automatic Under Frequency Load Shedding  ARF   Automatic Reclosing Function   ATC   Automatic Transfer Control   Synchrocheck v1     external synchronizer  Synchrocheck v2   integrated synchronizer   BPF   Busbar Protection Function    Protections    current protection  I gt    gt  gt   I gt IDMT  dI gt   dl gt  gt   I2f gt   I lt    autonomous current protection  Al gt  gt  gt    zero sequence overcurrent protection  10 gt   IO gt IDMT  lO gt dir  YO  gt    voltage protection  U lt   U gt   U2 gt   U0 gt    frequency protection  f gt   f lt   df dt   motor protection  ItR  gt   ItA  gt   ItU  gt   NfR  gt   ItS  gt   U123  Cos d   Om gt   Rwir  lt   power protection  P gt   P lt O   technological protection  Tech   temperature protection  Temp   special protections  Harm  Arc    IU M710P MANUAL 05i00 ENG    Strona 5z 36     MuUPASZ  710 plus User manual    Options of protections  e operation based on RMS or 1 harmonic  e directional actio
7. 10 00       Logging in Settings    Fig  3 1 1 Main window    In the main window of fig 3 1 1 there are presented elements shown in most user interface windows    1  The upper line contains the window caption  i e  the name of relevant branch or window the user is  watching at    2  On the right hand side of the caption icons are located which inform about alarms  locks and emergency  CB opening    3  Position of the cursor  line number  or number of the screen  e g  in the Log  is located between the  header line and the scrollbar    4  Inthe lower line functions of the context keys are displayed    5  The central part of the display is used for presenting numbers  texts or graphic     Strona 12 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MUPASZ EATI    3 2  Menu    The Q    and o    keys are used to navigate around the device menu  In order to reach destination one    should navigate using the Q   keys  The Q key is used to accept entering the selected branch  The    key  allows moving one level up in the menu tree     For quick moving to selected windows or branches the      context keys are used  Their current meaning id  displayed in the bottom line   For example in order to move from the main window to the Logging window the following path should be    followed  Menu  gt  Management  gt  Monitoring  gt  Logging or to use the      Logging context key     LEDs descriptic  Event log  Measurements  Alarms   Control  Management  Identification    14 10 00       Logging in S
8. 422  two  or four wire    2 x RS 485  two  wire    e RJ45 Ethernet  twisted pair    These interfaces are used to transfer data  in accordance with selected transmission protocol   Depending on the transmission protocol  the data sent may contain the following information   e states of switches in the bay   e measurements   e event log   e counters   e states of binary inputs and outputs  and may allow to   e control the switches   e issue signaling cancel commands   e modify device configuration   e modify set points of protection and automatic functions   e activate device functions   e transfer inter bay lock messages   e synchronize internal clocks with system clock   e transmit content of recorders   e reprogramming of the device     Each version of the device is accompanied by documentation which allows to design visualization and  to control objects in the power system     4 1  Modem RS 485  2 wire  4 wire connection     Depending on the connection point of the device within the network  following types of connections are  used    Type I     intermediate position     without RT resistor matching wave impedance of the line    Type II     extreme position     with RT resistor matching wave impedance of the line   Above connection types are implemented in the by means of suitable wiring of 10 pin WAGO type 734 110  connector     Depending on device position in RS 485 network  following types of wiring of communication ports are used     Type    2 wire                     R
9. AC     Manual Algorithms Check    MAC     Manual Algorithm Check window allows to check  the correctness of algorithm operation  using simulated  measurement values  Execution of specified algorithm test  consists of programming selected analog values  needed to  assess the correctness of algorithm  forcing the test and  analysis of the records in the event log  After test start   analog values are transferred to the algorithms  which  results in generation of algorithms response in accordance  with protection configuration  tripping  signaling  lock   event recording   Validation of the test result is user   s  responsibility        3 12 3  CBD   Circuit Breaker Diagnostics    Q Menu  gt  Management  gt  Diagnostics  gt  CBD     Circuit breaker diagnostics    The CBD     Circuit breaker diagnostics determines the  circuit breaker parameters during normal exploitation  without disconnecting it from the network  Basing on the  acquired information the comprehensive breaker Serre  diagnostics is carried out including its wear and possible Sper  future malfunction  The CB state report is available through Cammands  the communication channels and user interface   Items analyzed    e CB opening events number irrespective of the  cause and value of current in the disconnecting circuit    e CB opening events number caused by the over  current protection    e mean opening time from the last 10 opening   cycles   e maximal opening time     CBD   Circuit br  di      State of operation 
10. EN ENEI O E A OE E A A A A TA 19  3 9  MandgemeMN i erriren enaner EEE aE 20  3 9 1  ENS E E E EET er er ease 20  3 9 2  UPV SION ee ED anton darnunte sgh muaiuaieteio gad anesp gation gatmcctada EEEE EEEO EOE 23  3 9 3  OU UN AO siatace cctecesacwnate ceveruniaansauptese tena seaosonstaccseuesa aesiedtapantesteamantdonpiaceraneeeasoonoserses  24  SOs NCEE ON sieges A T raisins ith AE A N 26  Bg PONO SE ES ES geen oc taptaoreaas E E nieevent econ ennneans 26  3 11 1  Al  gt  gt  gt    Autonomous independent overcurrent protection              ccccsccsseceeeceeeeeeeceeenees 26  3 11 2  DAR   Fault recorder          essesseseesssssesseseeresroseesroseesessessesscsresresroseossoseoseesessesscsresreseeseese 26  3113  DAR CHEF OR ier OF 0 ON piscis rE dnn an EE EEE TEE SA 27  3 11 4  PQA     Power Quality Analyzer        sesssssesssessessesscssesessesscsscsreseoseeseosseseosessessesscsreseeseeseesee 27  SB SLOG  Sy Lem LOE sirrin eE AE O EEEE 27  3 11 6  UPS  Uninterruptible Power Supply       ssssssessessesseseeseeseoseseeseoseeseoseoseosessessesscseeseeseeseesee 28  3 11 7  RPS     Redundant Power Supply      sessssssssssssesssssesseseosessesscsreseossessoseoseoseesessesscsreseeseeseesee 28  L PREO IG a E E E EO sensor ans A E AAAA AE AEE ESS 28  Ihe SS E ae is pate seein O E E A 28  3 12 2  MAC   Manual Algorithms Check             ccccccsccssccesccssecseceecceeccesececseeeceeeseeeseeeueeeseeeenees 29  3 12 3  CBD   Circuit Breaker Diagnostics              snnsensessessesersess
11. LE ES AE A EA A an A E A A A E ET E SEERE E 36  5 6  BEVIS N E E E N E E E E E E T 36    IU_M710P_MANUAL_05i00_ENG Strona 3 z 36    MUPASZ EATI User manual    1  General    1 1  Designated use    MUPASZ 710 plus is designated for operation as a multi function bay control device in MV grids   with grounded or insulated neutral point  and in compensated grids     Y Pole Silnikowe    11 A  401    h   I2  A   403     13  A    399  U12 V   6001  U23 V   5999    19 24     Sterowanie  E diod               Fig  1 1 1 The view of MUPASZ 710 plus     The device can work in grids with frequency 50 or 60 Hz     The MUPASZ 710 plus bay controller may have up to 8 bay types  profiles  implemented  which may be freely modified and adapted to the user   s requirements  Logic function  simulator is included  The user may also redesign implemented bay views and usage of 16  three colour signaling diodes     MUPASZ 710 plus works with ELF application used to design individual bay operation logic   parameterization of protections  to configuration  to read measurements and events  and       to control device operation in service mode     The regular 36 months warranty period may be extended to 60 or 120 months        Strona 4 z 36 IU_M710P_MANUAL_05i00_ENG    1 2     User manual    Features    Operation in    Capacitor battery bay  incoming outgoing feeder  generator bay   line bay   busbar coupling bay  measurement bay   motor bay   transformer bay   feeder bay    Connector types    Control  e 
12. O Energetyka    Bay control unit       ox smart  energy  management    User manual    Document version  05i00  Update  2015 01 22       energetyka itr org pl    We reserve the right to modify the device     Tele  and Radio Research Institute  ICT and Electronics Centre   03 450 Warsaw  ul  Ratuszowa 11  tel  faks    48 22 619 73 14   e mail  energetyka itr org pl   www  energetyka org pl    User manual MUPASZ RATE    Contents    1  CBO GIO elation SEE SEE ERE ES odia ssn cet A sereaasacnreoa nase A EAO ES 4  1 1  VSS ON WSS A E eran sean sing E E AOO E A E E E E 4  12 FE EU SS SEE E A NEEE E AEA E E A E 5  1 3  Functional and accessors maa EDEN E SER 8   2  EEA EE E E A EE E E A EAE EE aeons 10  2 1  FORCO TE erase n EA A E EEEN E EE E EES 10   2 1 1  COUT  keypa ar Oesen a EAEE 11  2 1 2  SIC ell NOC CS E A E E E E A E E EE E A E A se 11   3  Bo EA EE EAA EE AEE ASAA E E A OA A N A A eee 12  3 1  WIGO N ea N Ea R A A AE 12  3 2  TO a E E A E A 13  5 3  BAY AOW R  RER SERENE ENE SESESS SENSE SENE gests E E TEE FED SEJRE 14  3 4  Modeen E nase auseeainsy pov anuu oun E R E E AEE O E 15  3 5  ENN OD rE EEE EE E AOE A R 15  3 6  Mea Urme aer EE E E ET 16  3 7  Alarms     cancelling the signaling              sccsscssscosssosssosccesecsssosstessessseusecesecessosstesstessessseuseeesess 17  3 8  COTO  MOE eeoa Ennen RE EEEE r EEEE EEEE TREERE 18   3 8 1  SEE OR Of COMO  MMOG C irois ED EE 18  3 8 2  BESS COA A a A RESET SEER   RER TEDE SE EROBRERE BES SER EEDER 18  3 8 3  SCG AE P
13. PASZ Pale    User interface  e three languages  Polish  English  Russian  e upto 12 users  e colour display 320 x 240 pixels  e 7 signal diodes  Emergency trip  Alarm  Lock  Local  Remote  Power supply  Device failure  e 16 freely configurable tricolour diodes  e configuration of displayed measurements and event counters  e bay view editing   over 120 elements of synoptic available  switches  electrical symbols  lines  nodes   e texts  measurements  clock  states of binary inputs and outputs  events  messages  signaling  operational states    Other functions  e 4 sets of set points  e event log capacity 1000 events  e filtering of events displayed  e system log  e each defined event has 16 bit counter assigned  e power outputs  relay semiconductor type   e auto logging  e editing selected texts  e g  names of protections  connectors and signal diodes  e algorithm operational status registers  e user registers for free assignment of analog digital signals    IU_M710P_MANUAL_05i00_ENG Strona 7 z 36     MuUPASZ  710 plus User manual    1 3     Functionality and accessories       B       To       a m  oo  co    d  N  IN          BA         Logic   Used to edit operational logic of the device  utilizes  protections  automatic functions  logic  gates  comparators  timers  flip flops  registers  event blocks  etc  Available via ELF program     Simulator   Used to carry out simulations of designed logic and preview analog digital signals in the  profile schematics  Forcing of input s
14. S422 485 B  RS422 485 A      2  D i    WHhUADN 0000          Fig  4 1 1  Intermediate position of the device in 2 wire communication network    IU M710P MANUAL 0O5i00 ENG Strona 31 z 36    MUPASZ EAI User manual    Type II  2 wire            RS422 485 RT  i            Fig  4 1 2  Extreme position of the device in 2 wire communication network    It is also possible to connect devices to 4 wire RS 485 communication network  In this case pins 2  3  4 of  WAGO connector refer to direction of data transmission  pins 5  6  7 direction of data reception by the device   Recommendations concerning wiring method for communication ports of devices installed at various  locations of communication network  are the same as for 2 wire version     Type I  4 wire                 RS422 485 Y        BPNWAUAN WOH       Fig  4 1 3  Intermediate position of the device in 4 wire communication network    Type II  4 wire        oO       RS422 485 RT    RS422 485_Y         RS422 485 B       FPNWAUAN WOWOH       Fig  4 1 4  Extreme position of the device in 4 wire communication network    It is recommended that shielded twisted pair is used  with characteristic impedance 120 Q and low wire to   wire capacity  with additional wire equalizing potentials of individual transmission modules  One end of  shielding wire should be connected with protective potential of the system     Strona 32 z 36 IU_M710P_MANUAL_05i00_ENG    User manual  4 2  Modem 2 x RS 485    Depending on device position in RS 485 network
15. alues are grouped  in separate menu branches     Z rol gr  Autotest  Current  Voltage   Motor  Technological  Locks and alarm    Logging in Factory    After pressing the  e  Factory context key all parameters in  a given set of settings may be restored to factory values   The Cancel command opens again the window with  configuration of settings in the edited set  The Factory  command will be executed or information displayed that  the command cannot be executed  Additionally  a relevant  event will be logged in the Event log     Factory       Strona 20 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MUuPASZ Palys    An exemplary window with current protections  implemented in device profile being edited contains  Current  e Two instances of    gt   e One instance of I  gt  gt   e One instance of    gt  IDMT  e One instance of EFD  gt  I  gt  IDMT f 1     e One instance of I lt  EFB   Taf 1        Cogaging in    If more than one instance of a given algorithm may be implemented in the device than the number of  the instance is displayed in round brackets     An exemplary window with the I  gt  IDMT  1    Parameters  depending on their type  are edited as in the I  gt  IDMT  1   examples below  Options and Active events are multilist  type  Direction and Characteristic are monolist type  Ir and    Direction  None  T are number type     Characteristic  Normally depe     Ir  InJ  1 10   T  s   5 00   Active events            Logging In       When starting edition of settings one sho
16. arameters  controlling switches  operating fault recorder  etc    Currently logged in user is displayed In red    The device Has 5 access levels with different user       privileges     e User not logged in siesta bert   88 i ser 1  e 10 users to be defined Administrator  e Administrator Service  e Service Producer    User manager  Auto login  Passwords activity time    e Producer         Return     opens the window in which    Logging in was    lately used  Return       Producer and Service users have privileges allowing servicing of the devices  these privileges are not  granted to the operating personnel     i  Activation of the Auto login function results in keeping the latest logged in user in memory and thus the  user is not changed after device restart     i  If the Autologging function is not active the user is logged in for Password activity time  h m   after that  time automatic logging out takes place  switching to User not logged in      Administrator may grant privileges  see figure  to defined  users  also to not logged in user   Permissions    Change control mode  i User interface  User may be defined in the User manager window by MyProfile a  granting him a password  This operation results in adding    Communication  the new user to the list in the Users window         Applications    _  Configuration  Control       Password change       IU_M710P_MANUAL_05i00_ENG Strona 23 z 36    MUPASZ EAI User manual    Each user may log in by entering a 4 digit password de
17. ay   2  Colour graphic 320x240 pixels display    3  Emergency opening signalization cancelling key   TRIP    4  Alarm cancelling key   UP    5  Active circuit breaker lock cancelling key   LOCK    6  Menu navigation keys    7  Context keys    8  Control key     OPEN    9  Control key     CLOSE    10  USB mini B service connection port     Strona 10 z 36 IU_M710P_MANUAL_05i00_ENG    2 1 1  Control keyboard    User manual MuPASZ EAJ    Control keyboard of the device has 12 navigation  function  control and context keys  Navigation and context  keys are used to navigate around the display MENU and to review and edit parameters     Table 2 1 1 Control keyboard       Przycisk       ooeeceooceoe    Opis    navigation key   UP arrow   navigation key   DOWN arrow   navigation function key ESC   cancel return   navigation function key OK   acceptance   function key  function description is displayed   function key TRIP used to cancel signalization of emergency opening of the main switch  function key ALARM used to cancel UP signalization of bay damage   function key LOCK used to cancel active locks   function key CLOSE used to issue the   close    command to the main switch    function key OPEN used to issue the  open    command to the main switch    The function keys    OPEN and ap CLOSE allow issuing commands to the main switch  The    open     command is always executable  For the   close    command to be executed the Local or Local and remote mode  must be active  Additionally  ac
18. cess to the   close    command may be restricted for some users  see Part 3 9 2 1    User Manager      2 1 2  Signal diodes    In addition to graphic display and control keyboard  device front panel has 23 signal LEDs  16 of them are  programmable  They signal the most important states of device operation  resulting from operation of  algorithms  or existing situation  such as establishing a lock  emergency CB opening  ALARM signalization  UP   bay damage   local or remote control mode     Table 2 1 2 Meanings of predefined diodes    Diode Color    Q       green       i    re  e    TRIP red       ALARM yellow  LOCK yellow    L yellow  yellow    IU M710P MANUAL 05i00 ENG    Meaning  Signals feeding of correct supply voltage to the device Continuous light     Signals action of SC Self Check mechanism  Continuous light    Signals opening of the CB caused by tripping of protection set to  disconnection or disconnection with lock  Continuous light    Signals protection tripping the signalization  Flashing continuous light   Signals that the device is locked following activation of any lock   Continuous light    Signals the possibility of local control  Continuous light    Signals the possibility of remote control  Continuous light     Strona 11 z 36     MuUPASZ  710 plus User manual    3  Operation manual    The below show views may differ for different device specification     3 1  Window    Menu    Event log  Measurements    Alarms  5   Contral  Management  Identification    14 
19. e   Rx Optical signal receive input  to the Tx socket in the cooperating device   Tx  Rx    Fig 4 4 1  ST fibre optic connector desription     Strona 34 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MUPASZ EAJ    5  Remarks of manufacturer    5 1  Maintenance  inspections  repairs    The device implements programmed operation of protection  control and automatic functions algorithms   and it was fitted with autotest systems responding to internal damage during device operation   The manufacturer recommends that correctness of device operation is verified   a  each time   during commissioning   b  atleast once a year   in mine face installations   c  atleast once every 5 years in installations other than front face   The following are subject to periodic inspections  if used    e correct operation of measurement channels of phase currents and voltages  earth fault currents  and voltages  at rated values   e correct operation of control circuits   e correct operation of measurement channels of PT100 temperature sensor  one point check may be  carried out  with an external 100 O 0 1  resistor indicated temperature should be 0  C   e correct operation of 4   20 mA measurement channels  verification check can be carried out at one  point  with preset measuring current  e g  10 mA   e correct operation of communication channels  in line with the implemented protocol   e integrity of device protection earthing   It is recommended that the internal battery is replaced at least once e
20. er interface menu branch allows modification of the  device menu appearance  selection of language and setting User interface  display blanking time  Particular parameters are edited in  accordance with their type  as in the edition examples     Compositions  green   Language POL ENG RUS  Englis     Backlight off after  him   05 00  Font  Normal    See chapter 3 9 1 1 Edition of parameters        3 9 3 3  Date and time    N    Menu  gt  Management  gt  Configuration  gt  Clock    W Menu  gt  Management  gt  Configuration  gt  Clock options    After entering the Clock window in the first line current  date and time is displayed  and in the second line date and  time to edit     2015 01 14 14 10 00    205 01 14 14 10 00  See chapter 3 9 1 1 Edition of parameters       Confirmation of date and time results in automatic zeroing of milliseconds     In the Clock options window Automatic time change  option may be activated  it results in automatic change Clock options  between standard and summer time   The second option    i i Automatic time change  allows to log time change event in the Event log  tomatic time chang        Change time event       IU M710P MANUAL 05i00 ENG Strona 25 z 36    User manual  3 10  Identification    w LOK  Menu  gt  Identification       In the exemplary Identification window there are displayed        all parameters identifying device hardware and software  Identification  e name    MUPASZ 710 plus     e serial number   35 MUPASZ 710 plus  e software ve
21. erials  or materials that can be processed again or disposed  of in environmentally sound manner  Decommissioned devices can be collected for recycling  provided that  their condition is that of normal wear and tear  All components that are not recyclable shall be disposed of  in environmentally sound manner     5 5  Guarantee       Regular 36 month guarantee period  may be extended to 60 or 120 months  Had the sale been preceded  by execution of an Agreement between the Buyer and the Seller  provisions of such Agreement shall apply   Guarantee covers remedying of defects  free of charge  provided that instructions specified in the  Warranty Card are adhered to  Detailed guarantee conditions may be found at energetyka itr org pl in the  w    Sale Regulations       e The guarantee period is counted from the date of sale    e The warranty is extended by a period of residence of the product in the repair    e Unauthorized tampering with the product will void the warranty    e Warranty does not cover damage resulting from improper use of the product     5 6  Service    Servicing includes   e guarantee and after guarantee inspections   e assistance in commissioning MUPASZ 710 plus devices or switchgears with MUPASZ 710 plus  devices both in the country and abroad   e device configuration  if requested by the customer      algorithms set points     communication ports     fault recorder     criterion fault recorder   e training courses covering operating skills and programming of t
22. erification of correct  operation of an algorithm     CBD   Circuit breaker diagnostics is used to determine critical parameters of circuit breaker contactor  during its operation     O Seg OH       CCT   Cumulated Current Test monitors the value of cumulated current for each phase   CBCT   Circuit Breaker Control Test monitors the integrity of coil control circuits and auxiliary voltage     HVT   High Voltage Test monitors the condition of cable insulation  using high voltage  before  energizing the cable     B9 BBH    PAT   Protections and Automatic Functions Test verifies correct operation of protections and  automatic functions  using external testing systems     Accessories    Communication and arc detection fibre optic cables  sealing caps  fixing elements  hardware access  key  grounding copper braid  mini USB cable    Accessories available for MUPASZ devices can be found on the website energetyka itr org pl   Availability of individual elements varies by device family and technical specification             IU_M710P_MANUAL_05i00_ENG Strona 9 z 36    MUPASZ EATI User manual    2  User interface    2 1  Front panel    The front panel hosts   e 320x240 pixel backlit graphic display   e control keyboard of the device   e LED signal diodes   e USB service port for communication with ELF software tool     Mupasz Palys    wore     ees      ieee     Om      energetyka itr org pl       Fig  2 1 1 Front panel    1  Freely programmable diodes  diode descriptions on graphic displ
23. essing the       key the Control window opens in which required switching Seah   Operations may be selected from the list and confirmed Breaker  1   with the    key    After selection of the required operation it will be executed Open   or    not available    message displayed  Close           The switches may be operated also in the Switches window or by means of a User command     Strona 14 z 36 IU_M710P_MANUAL_05i00_ENG    User manual    3 4  Diode description    Q Menu  gt  Diode description  oOo Diode description    LED       Device MUPASZ 710 plus is fitted out with the set of freely  programmable signal LEDs installed on device front panel   Diodes are configured by means of ELF program  in the tab  Logic  configuration consists in assigning a signal from the  system  algorithm or automatic function to specific LED   Active state of the signal results in illumination of LED   Descriptions of signalization diodes are defined by editing  the text assigned to given diode and are shown on the  display  The mark in front of the description text  corresponds with the diode colour illumination          LED 1 8 9 16     allows moving to the widow with  descriptions of the other diodes     3 5  Event log    he    Menu  gt  Event log         oOo Event log    The Event log holds events generated in the device and   allows their viewing  Any recorded event is characterized   by    1  type     see table below    2  date and time     the events are tagged with 1 ms  resolution time 
24. essrsresersrrsrrsresrrsrosessessesseserserseesee 29  sA AU T E E T OTOA EEEO 29  3 13 1  CCT   Cumulated Current Test              nsesensessessessesersessessrssrsersrrsrrsrrserseesessessesseserserseesee 29  3 13 2  CBCT   Circuit Breaker Control Test             nsnnsessnssnsenssrsessesresersrrserserserseosessessessrserserseesee 30  3 13 3     HV   High Voltage TEST vessssscssensundonacsincmnncdonaneanacaetanndcncauneistocrameemsarnnaainaseeasecaaedatongaess 30  3 13 4  PAT   Protection and Automation Test             cccccseccsscceecceeeceeceecceeeceeeceeeeseeeueeeseeeeeeeeenees 30   4  Description of COMMUNICATION INTEFFACES            ccecccsccseccsecceeececcencceucceucceeceseceeeeesecsuceeueeeeeees 31  4 1  Modem RS 485  2 wire  4 wire CONNECTION            cccccccccceeccceseceeececeuecsceesseueceeeneeeeueceeeneeeanees 31  4 2  Modem 2X 9 Osea tesseaGacusscmsteaccuammansacistenoponesenetdedeine E ESER 33  4 3  Twisted Pair RJ Ethernet Modem              ccscccseccsecceeecsccseceeeeceeceseeaseeeeeeeuceeeeeeeeeeeeeeeeaaeeeeegseees 34  4 4  STOPU FO ater sinc ase cate carers oe sass ea cars asteiosaitie strate nous viesisounaeeeonuenmeenancauceaunon eee 34   5  Remarks of manufacturer sesser ER Ene Tse 35  Sd  Maintenance  inspections  repairs            s sssssesssssrsrsrsrsorsrsrsssrsrsrorsrorsrsrseserererererererererereeesereo 35  5 2  Storage and rans DON 5 oe E E E 35  5 3  Place of MISES IAL OWN reescrito eE EEEE OEE OOOO 35  5 4  DEPO na A E TE ERE TEROR 36  5 5  CIU
25. ettings    The context key in the main window are used for     the left one     moving to the user Logging window     the Middle one   moving to the parameter Configuration window      the right one   moving to the Bay view window     i    The right hand side context key is used for navigating through all widows listed in the main menu  starting from the Bay view window and ending in the Identification window     IU_M710P_MANUAL_05i00_ENG Strona 13 z 36     MuUPASZ  710 plus User manual    3 3  Bay view    LOK  Menu  gt  Bay view       Bay view    ELF software tool allows configuration of the bay view   customized to user   s needs  There is no need therefore to    visualize the whole bay  only its individual components    lt  l 1 LA    0 0  such as state of the CB  Bear in mind  however  that   lt  12  A    0 0  inserting in the bay view of e g  earthing switch that is not   lt  I3  A    0 0  there in the actual bay  shall result in displaying it as not   lt  10  A    0 0    monitored    lt  u 12        0 0    lt  U23  V    0 0    16 31       Control         Control activates the mechanism of switch control   Activation of this option marks the main switch     Another switch may be selected with the J Q keys   lt 11 A      0 0   lt  I2  A    0 0   lt  I3  A    0 0   lt   IO  A    0 0    lt JU12 V    0 0    The switches which cannot be controlled may not be   lt  U23  vV    0 0  selected and marked           14 06       anal       After selection of the required switch and pr
26. ew measurements  along with their status   UM     User Manager controls and identifies users access to functions of the device     RALG   Algorithm register   used to preview  in textual and graphical form  of algorithm operating  states  of e g  protections  automatic functions  switches     Service   Group of service parameters available to users with service privilege     Strona 8 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MUPASZ EAJ    Al gt  gt  gt    Autonomous independent overcurrent protection protects objects against consequences of  short circuits in the absence of device supply voltage                   DAR   Fault recorder used to record analog digital signals with sampling frequency 2 kHz   CDAR   Criterion recorder used to record analog digital signals with sampling frequency 50 Hz   PQA   Power quality analyzer used to assess the quality of energy at the protected facility     SLOG   System log  Stores time and date stamped device operation logs i a  user logging  last  modification of set points  control commands     UPS   Ensures sustaining full functionality of the device for 60 s following voltage decay or up to  200 s with display backlight off     RPS  The solution that allows installation of two independent power supply units in the bay  controller  making up redundant power supply system             Diagnostic    SC     Self check  monitoring of internal states of the device     MAC     Manual algorithm check simulates measurement values and allows v
27. fined  by the Administrator  Administrator    The password is entered by means of the O Q          lt  and       gt  keys  in the same way as the NUMBER  parameter    In order to log in the correct password must be entered    Get password        W key pressed  ger       Factory password of the Administrator  1111    3 9 2 2  Digital inputs and outputs    ofi        N   Menu  gt  Control  gt Supervision gt  Digital Inputs outputs       In this window current states of device binary inputs and    outputs are displayed  Digital Inputs outputs  High state of input output is marked with the E symbol     low state with the _ symbol  Inputs Outputs    1234567890 1234567890       3 9 3  Configuration    3 9 3 1  Communication       Ww Menu  gt  Management  gt  Configuration  gt  Communication       Window is used for configuration of transmission  parameters for particular Communications ports   Configuration parameters displayed in the window depend    FOTO O       ol ww     T 1      on transmission protocol available for the given COM port  Sere FE  Particular parameters are edited in accordance with their Lenght of data  bit  8  type  as in the edition examples  Parity bit  None    Stop bit  1  Adress  1     See chapter 3 9 1 1 Edition of parameters  Timeout  s   10 00       Logging In    Save   Parsee    Strona 24 z 36 IU M710P MANUAL 05i00 ENG    User manual MuPasz EAIA    3 9 3 2  Interfejs uzytkownika    w    Menu  gt  Management  gt  Configuration  gt  User interface       Us
28. he devices  in the manufacurer s  site in Warsaw  Poland  e designing logical schemes based on documentation delivered by the customer   The engineers team of Tele and Radio Research Institute  with long professional experience in the field of  power protection relays  will answer questions regarding operation of the bay controllers  communication  and implemented algorithms        Tele  and Radio Research Institute  ICT and Electronics Centre   03 450 Warsaw  ul  Ratuszowa 11  tel  faks    48 22 619 73 14   e mail  energetyka itr org pl   www  energetyka org pl    Strona 36 z 36 IU_M710P_MANUAL_05i00_ENG    
29. ignals and measurement values can be carried out using data  saved in COMTRADE format  Available via ELF program     Bay view     Allows editing graphic representation of bay schematics  visible in the device  via ELF  program     Freely programmable diodes   16 freely programmable tricolour diodes  The Elf program allows their  editing  assignment of functions to be signaled  signaling order  description  colours and display  mode     Set points   Used to preview and edit parameters  nominal values  protections  automatic functions   control and monitoring systems  autodiagnostics  grouped into sets of set points     Texts   Used to preview texts predefined in the device  in supported languages  and to edit editable  texts  Available via ELF program     Selected counters   Used to configure Selected Event Counters window   Selected measurements   Used to configure Selected Measurements window     Selected MODBUS records   Used to map MODBUS registers     iii 673    d  N  AN        BGO E       Configuration   Used to preview and edit configuration parameters of the device  i a  system clock   communication ports  user interface     Log   Used to preview events logged in the device   Event counters   Each event defined in the device has a16 bit counter assigned  Used to preview  their values in Event Counter window     States   Used to preview system states  digital inputs and outputs  signal diodes  communication  ports  user login information     Measurements   Used to previ
30. lues of Settings   analog signals   Recorder trig   The DAR   Fault recorder window allows the user to  manage the work of a recorder  In particular it allows to  trigger the recorder from the user interface    For details  refer to the    Fault Recorder User Manual        State of the recorder       Logging in    Strona 26 z 36 IU M710P MANUAL 05i00 ENG    User manual MUuPASZ Palys    3 11 3  CDAR  Criterion recorder    Q Menu  gt  Management  gt  Extensions  gt  CDAR     Criterion recorder    The criterion recorder application is used to record slowly changing signals in the protected object  e g  motor  start up sequence  It saves analog values  RMS  and digital signals with sampling frequency 50 Hz  The user  can configure the number of registered signals  recording time before triggering  cause of the start of  recording  binary inputs  binary outputs  digital signals from algorithms or programmable logic and increasing  or decreasing values of analog signals     The window Criterion recorder allows the user to manage the work of a recorder  In particular it allows to  trigger the criterion recorder from the user interface    For details  refer to the    Criterion Recorder User Manual        3 11 4  PQA     Power Quality Analyzer     HR Q Menu  gt  Management  gt  Extensions  gt  PQA     Power Quality Analyzer    The application is intended for energy quality analysis in  the object that is being protected according to PN EN PQA   Power qualit     50160 2002  PN EN 61000
31. mote     via device interface   Of ocal and remote  communication system  O Autonomous control    e Autonomous control     control without  participation of the device  CB is controlled by external  devices      i         See chapter 3 9 1 1 Edition of parameters           Before setting the control mode one should check if the intended mode is allowed in settings    Menu  gt   Management  gt  Settings  gt  Settings X  gt  Control group  gt  Selection of control     If in the bay operation logic scheme the control mode selection is done via binary inputs then selection  of the control mode via the user interface is disabled     3 8 2  User commands    D Q Menu  gt  Control  gt  User commands    ELF software tool allows the user to define own  commands which activate logic functions from the User commands  device menu level    Commands are configured by means of ELF program  in  the tab Logic  configuration consists in entering the Control i   CMD_USER block and connecting its output signal to the No control inspection  block of the function it is to activate  Selecting the  command from device menu shall activate the  instruction resulting from the logic        a    User commands may be used to control the switches  cancel signaling  activation of algorithms or  execution of any user designed function present on the device logic scheme     Strona 18 z 36 IU_M710P_MANUAL_05i00_ENG    User manual    3 8 3  Switches       RW Menu  gt  Control  gt  Switches    In this window all 
32. n  e operation in CBF mode  e operation in BPF mode  e cooperation with ARF  e voltage stabilization  e frequency stabilization  e harmonic stabilization  e  acceleration deceleration of protection action    Measurements  e current  11  12  13  10  e voltage  U1  U2  U3  U12  U32  U13  UO  e frequency  f  e power  P  Q  S  cos     e energy  EC   EB   EC    EB   e angle between current signals and voltage signals  e temperature  Om  calculated from thermal model   Temp 1   6  PT100   e diagnostics  THD  up to 40 harm   Tp  bay working time   2    cumulated current    e resistance  Rrotor  Rhvt    Measurements  set two  e current  2 11  2 12  2 13  e voltage  2 U1  2 U2  2 U3  2 U12  2 U32  2 013  e frequency  2 f    Diagnostic   e SC   Selfcheck  e voltage  supply  reference  battery  e memory  program and data  e correctness of internal module to module communication  e calibration factors of measurement channels   e device set points   e MAC   Manual Algorithm Check   e CBD  Circuit Breaker Diagnostics    Autotest  e CCT   Cumulated Current Test  e CBCT   Circuit Breaker Control Test  e HVT   High Voltage Test  e PAT   Protection and Automation Test    Extensions  e Al  gt  gt  gt   Autonomous independent overcurrent protection  e DAR      Fault recorder  e  CDAR     Criterion recorder  e PQA      Power Quality Analyzer  e SLOG     System Log  e RPS    Redundant Power Supply  e UPS      Uninterruptible Power Supply    Strona 6 z 36 IU_M710P_MANUAL_05i00_ENG    User manual Mu
33. rement value is calculated basing on incomplete information  e g     Unsure    the power is calculated for two phase currents    WAles     3 7  Alarms     cancelling the signaling    Q Menu  gt  Alarms    Alarms       MUPASZ 710 plus implements a series of switch bay  protection algorithms  In order to facilitate reading of Alarms  operating state of algorithms  the software of MUPASZ  710plus device is fitted with the function of displaying FYRE Breaker   1    aggregated information on states of all algorithms Earthing disconnector     implemented in the active profile  Breaker control   In the Alarms window aggregated information on alarms   locks and tripping is displayed        DELETE    The      DELETE key deletes all signaling and displays    Alarms  a relevant message     If the cause of signaling is still active it will not be  cancelled  First the cause should be removed and then the  signaling cancelled        Control       Signaling may be selectively cancelled by means of the            An adequate User command on the logic scheme may be used to cancel signalization after adaptation     IU M710P MANUAL 05i00 ENG Strona 17 z 36     MuUPASZ  710 plus User manual    3 8  Control mode    3 8 1  Selection of control mode    Q Menu  gt  Control  gt  Selection of control    One of four control modes may be selected in the Selection    of control window  Control selection   e Local  via device interface  OL     e Remote     via communication system     aa   e Local and re
34. rsion    S_M710P_A0_01     Device serial Na     In succeeding windows aggregated information relating bay Software S M7 10P_4A0_ 01  state is displayed  such as main switch state  control mode   active set of settings and address data        3 11  Extensions    3 11 1  Al gt  gt  gt   Autonomous independent overcurrent protection    Q Menu  gt  Management  gt  Settings  gt  Settings X  gt  Current  gt  Al  gt  gt  gt     Al  gt  gt  gt  is an independent circuit for    protection of objects against current faults when the protective device  is not powered   Energy for powering the circuit is harvested from the current transformers  Al  gt  gt  gt   cooperates with low voltage CB trip coils  what ensures CB opening even when no auxiliary supply is available  in the switchgear  Breaking current is also monitored and in case the maximum allowable local switch  breaking current is exceeded the open command is issued to the CB in the upper switchgear    More information in  U_M710P_ALGORITHMS_XXiXX     3 11 2  DAR     Fault recorder    Q Menu  gt  Management  gt  Extensions  gt  DAR     Fault recorder    The fault recorder application is used to record analog and  digital signals with sampling frequency 2 kHz  The user can DAR   Fault recorder  configure the number of registered signals  recording time  before triggering  cause of the start of recording  binary TET ETE  inputs  binary outputs  digital signals from algorithms or e  programmable logic and increasing or decreasing va
35. switches included in the device active    profile and their states are displayed  After selection of a  particular switch and pressing the nd key the Control    window opens        In case the selected switch is not intended for control  via the interface the message Lack of control is displayed     If the selected operation is allowable it will be executed  and the Switches window will return  Additionally   a relevant event will be logged in the Event log        Switches    Breake   Failure  Not armed  Earthing disconnector  1 Opened    Logging In    Control       In order for the operation selected from the Switches submenu to be executed the control mode Local or    Local and remote must be selected     IU M710P MANUAL 0O5i00 ENG    Strona 19 z 36    MUPASZ Baye User manual    3 9  Management    3 9 1  Settings    The Settings submenu allows selecting active bay type   profile   active set of settings and reviewing and editing settings  parameters in one of four sets of settings        Menu  gt  Control  gt  Settings    Profile  Active set Settings 1  Settings 1  Settings 2  Settings 3  Settings may be modified by a user with adequate Settings 4    level of privileges  see chapter 3 9 2 1  User Manager         Logging In       Modified parameters are memorized in the set of settings being edited     Menus of all sets of settings for a given profile are identical   Algorithms of protections and automatic functions  control Settings 1  and monitoring functions and nominal v
36. tags    3  descriptive text     displayed in one or two lines    4  up to 5 parameters  e g  current value at protection  stripping  the parameters may be accessed by selecting    the      Details context key     The logged events may be filtered for displaying in regard  of their types  Having selected the Filter context key a  window opens in which event types to be displayed may be  selected     By means of the      Select context key required positions  may be selected or deselected  After confirmation your    choice with the  ox key and returning to the Event log  window only the event types selected in the Filter window  will be displayed     IU_M710P_MANUAL_05i00_ENG       LEDs descriptions    gt     I gt  inverse   10 gt    l gt  directional   ItA current unbalance    BOBOHOOHOUOHA    Event log    Event log    20 14 12 10 14   Breaker control  Alarm    1jo14 127 10 14   Tech  2    Trivping PI   O  2014 12 10 14  Tech  2    Executed    Filter    Normal   3   amp   tart   O   Alarm   A C  Release  BE Tripping   Al  Interlock  OC  Executed    Strona 15 z 36    MUuPASZ hayes User manual    Table 3 5 1 Event types    Symbol Event type Description       Normal Standard event type  such as user login     Activation Activation of an algorithm  e g  protection    Execution of algorithm  e g  protection set to UP signalization    UP    Alarm   a      signalization    item selected in Options    Release Deactivation of an algorithm  e g  protection    Execution of algorithm  e g
37. uld first set the nominal values  Bay settings  gt  Nomindls   because their values may influence the way the protections and automatic functions operate and their  operating ranges     3 9 1 1  Edition of parameters    Below a method of editing monolists  multilists and numbers is presented for an exemplary protection  I  gt  IDMT  1      Edition of a MULTILIST parameter  consists in selecting any combination of elements from the list  The name of the edited parameter is displayed in the    window header line  Elements of the list and the selection  J amp iuscelil   symbols are displayed underneath  o       not selected element  oa    D  selected element   Edition of the multilist is carried out by means of the     Interlock  following keys      Temporary interlock     change of element Interlock at start    i     Operation on hi      select   element select or deselect  C  Control breaker failure    Q   confirms edited value          results in leaving the window without saving changes        IU M710P MANUAL 05i00 ENG Strona 21 z 36    MUPASZ kal ITS User manual    Edition of a MULTILIST parameter  consists in selecting single element from the list  The name of the edited parameter is displayed in the  window header line  Elements of the list and the selection  symbols are displayed underneath       not selected element      selected element   Edition of the monolist is carried out by means of the  following keys       Q   change of element   o Select     element select    
38. ut the state of the power facility  In case of a power failure  the  device  for the guaranteed time  can perform switching operations and send complete information about the  state of the bay to the SCADA system  which significantly soeeds up the analysis of the situation  The system  reaches full capacity after 10 minutes of charging     3 11 7  RPS     Redundant Power Supply       RPS solution consists of two independent power supplies  The default power supply for the controller is  power supply No  1  Make before break switching to the power supply No  2 follows after detection of too  low supply voltage by the power supply No  1  Information about switching to the power supply No  2 is  logged in the Event Log  The redundant power supply is essential for important facilities where reliable  operation is paramount     3 12  Diagnostic    3 12 1  SC  Self check    Subject to self check are  voltages  supply  reference  battery   memory  program and data   correctness of  internal module to module communication  calibration factors of measurement channels and device set  points  Following detection of damage that could pose threat to safe operation of the switchgear  device  operation is stopped  AL relay contacts are opened  optical signalization on the front panel is activated  Such  a state requires servicing     Strona 28 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MUPASZ EATI    3 12 2  MAC   Manual Algorithms Check  o    Menu  gt  Management  gt  Diagnostics  gt  M
39. very 10 years  The battery should be  replaced by service personnel as indicated by manufacturer   Differences observed during checks  or in measurement readings  or in device operation  should be notified  to the service center as indicated by manufacturer   Also inspections resulting from branch regulations should be undertaken   Changes in protections set points during operation do not require verification of their correctness     5 2  Storage and transport    Devices are packed in transport packages and secured against damage during transport and storage  Devices  should be stored in transport packages  indoors  in places free from vibrations and direct effects of weather  conditions  dry  well ventilated  free from harmful vapors and gases  Ambient air temperature should be  between    55  C and  70  C  and relative humidity should not exceed 80   All shipped devices are attached  with complete set of connectors  grounding braid  warranty card and quality certificate     5 3  Place of installation  MUPASZ 710 plus series is designed for erection in switchgears  acc  to drawings in IU_M710P_SPECIFICATION     Length of single cable connected to device sockets cannot exceed 50 m     Connection of MUPASZ 710 plus device earthing pin with metallic section of the switching bay should  be executed with WAD_6140 grounding braid  delivered with the device     IU M710P MANUAL 05i00 ENG Strona 35 z 36    User manual  5 4  Disposal    K    Devices are made mostly from recyclable mat
40. y the operation of the  generator using an external test resistor  HVT can work TETEE nnetic  in manual and automatic modes  In the manual mode  R  kOQ   350   the test is triggered by operator request  In the T  s   8 00  automatic mode  it is possible to test the generator at Active events       the request of the operator  and the test runs  automatically before each closing of the circuit breaker        Logging in    3 13 4  PAT   Protection and Automation Test       Menu  gt  Management  gt  Settings  gt  Settings X  gt Autotest  gt  PAT    PAT      Protections and Automation Test check  operation of the protections and the automatic functions  using external testers  It allows to check protections and    automatic functions including inputs circuits  measuring ON hour i  06 00  and digital inputs  used by the algorithm  PAT requires ON hour 2  06 00  the test signal generators that are attached to the inputs TifsJ  0 50   of the bay controller  After the start  test signals are T2  s   0 05  attached to inputs and PAT checks the response to the Active events         signals  PAT can work in manual and automatic modes  In  the manual mode test are initiated by an operator while  in the automatic mode tests run periodically at preset Logging in  hours            Strona 30 z 36 IU_M710P_MANUAL_05i00_ENG    User manual MuPASZ EAJ    4  Description of communication interfaces    MUPASZ 710 plus may be fitted with the following interfaces   e ST type optical fibre   RS 485   
    