Home
        UPS Selection, Installation, and Maintenance
         Contents
1.                        Figure 4 6   Multipoint grounding example   Reproduced from Federal Information Processing Standards Publications  FIPS pub  94     25 feet is considered adequate in most applications  Also  a suppression plate attached to the  junction box located in the computer room for connecting the incoming power cable to the local  distribution panel can be used to attenuate the radio frequency  RF  noise which may propagate  along the incoming power cable     f  Noise and noise reduction methods  Noise is unwanted current and or potential induced in  the signal cables by adjacent sources  Noise can be induced in the signal cable in the following  two modes  Differential mode  where the induced noise causes the potential of one side of the  signal path to change relative to the other side  Common mode  where the induced noise appears  between both signal leads and the common signal reference ground and causes the potential of  both sides of the signal path to change simultaneously and by the same amount relative to the  common reference ground  Noise is generally induced by electromagnetic coupling  electrostatic  coupling  and ground potential differences  Noise reduction methods are highly specialized and  are specific to the application  They also depend on the installation configuration  the proximity  and nature of sources of interference  frequency of the interference signals  etc  However  noise  can generally be reduced by providing proper grounding  avoi
2.      overload   and  UPS  operating abnormality   In a location where the UPS is in a dedicated room  the periodic  monitoring records of the UPS system would be provided by maintenance personnel  Computer  room operating personnel would only record battery cycling  time  discharge  overload  and  abnormality and advise maintenance personnel at the time of an alarm indication of the problem  displayed      5  Major system inspections  These should be performed at least annually on small to  medium systems and semiannually on large to very large systems  By performing this type of  maintenance on a scheduled basis  it is possible to find and remedy potential problems before the  system s operation is affected  Table 5 1 provides general guidance for the major system  inspection  however  the manufacturer s recommendations should be strictly followed      6  Minor system inspections  Minor system inspections should be provided either after 5  months from an annual major inspection or after 3 months from a semiannual major inspection  unless a more frequent requirement is recommended by the manufacturer  Minor system  inspections should include at least the first four items listed under major inspections  Off line  load testing is required if major component replacements are required     Table 5 1  Major system inspection general       Perform visual checks and operational tests of all UPS equipment and associated switchgear        Review maintenance logs and log all alarm opera
3.    0 s  Make before break   120  of rated full load current  1000  for 1 cycle       Table 3 7  Typical environmental ratings          ambient temperature range  relative humidity range  operating Altitude   audible noise       0   to 40  C   0 to 95  non condensing  0 to 1200 meters    lt 67 dB A  at 1 5 meters                   TM 5 693    Single phase loads    pj  1000    where  V is the system voltage in volts  Iis the measured current in amperes    Three phase loads    kVA 1 73        1000    where  V is the phase to phase voltage in volts  Lis the highest measured phase current in amperes    In cases where the load current cannot be measured or when the installation is in the planning  stage  the load KVA should be calculated  Calculating the kVA requires obtaining the individual  load kVAs from equipment manufacturers  data  The total load kVA is then obtained by  vectorially adding the individual load kVAs  However  when an individual load power factor is  not available  it can be estimated from the data in table 3 8  Also  an approximate but  conservative estimate of the load kVA may be obtained by arithmetically adding the individual  load kVAs     Table 3 8  Typical load power factors and inrush requirements                      Type of Load Power Factor   Inrush   Duration  Induction motor or MG set 0 75 500 800 1 30 sec   Computer central processor unit 0 9 0 85 600 1000 2 6 cycles  Computer peripherals 0 8 500 800 1 30 sec   Process instruments  amp  controls 0 
4.   2 x E  1  x 1 7 x 0 75 kV  where E is the rated voltage in kV    The standard duration of the test is between 1 to 5 minutes  The dc acceptance test voltage is  applied to each winding separately with the other windings grounded  The voltage is applied in  steps  First  one third of the dc acceptance test voltage is applied  Leakage current readings are  taken at 1 minute intervals for a maximum of 10 minutes  Then the voltage is increased in 1 kV  intervals recording the leakage current at each step  Sufficient time shall be allowed between  steps for the leakage current to stabilize  The data shall be plotted  Any sudden changes in the  curve characteristics are an indication of impending winding failure      e  No load test  This test will determine whether a problem exists in the generator or  regulator system  The theory behind this test is as follows  The output voltage of a generator is  dependent on its speed  design  load  and exciter input current  If the speed and exciter input are  known  the output voltage at no load can be measured and compared to the design value  To  conduct the test  verify that the generator is shut down and connect a voltmeter to the generator  output  With no load on the generator  main breakers open  run the generator at rated speed and  measure the generator output voltage  Shut the generator down and compare the voltage reading  with the design value  if they match  the regulator is functioning properly      f  Load test  Following th
5.   997 1005    Brecht  William B      Life Expectancy of VRLA Batteries     Batteries International  July 1994  pp  40 41    Bulik  Vince     Sizing a UPS System for Non Linear Loads     1993 Power Distribution Conference  Solid  State Controls  October 26  1993    DOE HDBK  1084 95     Primer on Lead acid Storage Batteries     U S  Department of Energy  Washington  D C   1995    Feder  Dr  David O      VRLA Cell Failures   The 60   s Revisited     Batteries International  July 1994  pp  44 48    Harville  A      Choosing a Secondary Battery Technology     Powertechnics  March 1991  pp  31 35    Herritty  Robert     A Primer on Batteries     EC amp M  February 1991  pp  20 21    Hussain  A  J   and John Sears     UPS Semiconductor Technologies     Power Quality  March April 1997    Ittner  David  D      Selecting and Maintaining UPS Battery Systems     Power Quality Assurance   January February 1994  pp  19 26    Kamran  Farrukh     A Novel On Line UPS with Universal Filtering Capabilities     IEEE Transactions on Power  Electronics  Vol  13  No  3  May 1998  pp  410 418    Key  Thomas  Lai  Jih Sheng     Costs and Benefits of Harmonic Current Reduction for Switch Mode Power Supplies in a  Commercial Office Building     IEEE  Inc   New York  NY  1995    Li  H H   M  Trivedi  and K  Shenai     Dynamics of IGBT Performance in Hard  and Soft Switching Converts     IEEE  October 1995   pp  1006 1009    McLatcher     Specifying Nickel Cadmium Batteries     Powertechnics  February 1
6.   TM 5 693    In an AGM cell  the electrolyte is absorbed and held in place with a microfibrous silica glass mat  sandwiched between the plates  The electrolyte is and remains liquid for the entire battery life   The glass mat is only about 90 percent saturated with electrolyte  therefore  oxygen produced    during charge can readily migrate to the negative plate and recombine into water  This    recombination mechanism  along with charge voltage control  substantially eliminates water loss     making the AGM batteries as non spillable and maintenance free as possible  Properly    supported  AGM batteries with absorbed electrolyte can be installed and operated on their side     G 3    TM 5 693    Active Redundancy   see Redundancy  active      Alternate Power Source   see Power Source  alternate       Availability   In its simplest definition  availability is uptime divided by downtime  In terms of reliability   MTBF or MTBD  and maintainability  MTTR or MDT   inherent and operational availability  are defined as          ade    MTBF  Inherent availability   Ai                  _  MTBF   MTTR    PESE MTBD  Operational availability   Ao    MTBD  MDT    Backup Time   Time during which the UPS can supply the rated load with nominal quality power while the  mains are down  This time depends on the battery and the efficiency of the UPS  Typical backup  ranges from five minutes to several hours     Battery   A device that converts chemical energy into electrical energy by means of 
7.   UPS component that draws on the mains the power required to supply the inverter and to float  charge or recharge the battery  The alternating input current is rectified and then distributed to  the inverter and the battery     Redundancy  active    Parallel UPS configuration in which several UPS units with equal outputs are parallel connected  and share the load  In the event one UPS unit fails  the other units pick up its share without any  interruption in the supply of power to the load     G 13    TM 5 693    Redundancy  standby    UPS configuration in which one or several UPS units operate on standby  with no load or only a  partial load  and can immediately back up a faulty UPS unit by no break transfer of the load   carried out by a static switch     Reliability   The probability that an item will perform as intended for a specified period of time under a stated  set of conditions  Usually measured as a probability  a failure rate  or a mean time between  failures     Reliability   Probability that a device will accomplish a required function under given conditions over a given  period of time  RMS value of ac with harmonics  The RMS value Yrms of a non sinusoidal ac  may be determined on the basis of the individual harmonic currents  where Y is the RMS value of  the fundamental     Reliability Centered Maintenance  RCM   A maintenance program established to maximize the equipment reliability     Rotary UPS   see UPS  Rotary     RS232C  recommended standard RS232C    
8.   current   Battery room temperature   Battery design versus actual load  Battery  system ground          Breaker trip Battery   system short  System overload          a  Use of maintenance personnel  Maintenance personnel should be able to recognize that a  failure condition exists from observation of the display  alarm  diagnostics aids  and  manufacturer s support  Simple failures such as blown fuses  defective fans  normal electrical   mechanical deficiencies  and electronic failures  i e   printed circuit boards  PCB   should not be  beyond the repair or replacement capability of on site maintenance personnel  Repair of the  PCBs should be performed by the manufacturer     b  Use of diagnostics  Display  alarm  and diagnostic equipment are generally provided in  proportion to the cost and complexity of the UPS system  Whether personnel can repair  equipment based on the diagnostics will depend on their training  All operating and maintenance  personnel should be familiar with their display  alarm  and diagnostics aids to the extent that they    4 20          TM 5 693    indicate proper operation  the need for local repair  the need for manufacturer provided repair or  consultation  and the requirement to observe and record trends indicating a need for preventive    maintenance     Table 4 4  Inverter static switch corrective action          Inverters  Static Switch Areas to Check  No output voltage  current Input voltage  breaker  SCR or diode    Static switch  Constant 
9.   due to the  absence of feedback regulating circuits in inverters with a ferroresonant transformer  the transient  response is slower than that of inverters with pulse width or pulse width modulation  PWM   control techniques  SCRs have a limited overload capability  Also  heavy load currents may  cause commutation failures  Therefore  the rectifier and inverter are designed to be self protected  from overloads  The self protection circuit reduces the output voltage at currents exceeding the  full load current  Normally  the inverter is designed to reduce the output voltage to zero at  overloads of 115 to 135 percent rated load  The value of overcurrent at which the voltage is  reduced to zero is termed  current limit     The inverter may reach the current limit condition  when energizing a load with a high inrush current or during a load branch circuit fault     e  Basic static UPS system without a dedicated battery  The basic system discussed above    utilizes a dedicated battery as a backup source  The UPS system is provided with a controlled  rectifier to supply the inverter and float equalize charge the battery  In other applications  a large    2 5    TM 5 693    battery bank may be available for supplying the UPS system as well as other loads  In such  applications  a separate battery charger is provided to supply the connected load and  float equalize the battery  In this case  the UPS system is provided with a rectifier that only  supplies the inverter and is isolat
10.   largely up to the manufacturer to meet the performance requirements      4  Flywheel  A flywheel is used in a rotary UPS system as an energy storage device  The  flywheel is coupled to the M G shaft and supplies stored energy to drive the generator upon  momentary loss of the motor output  In addition  it acts to stabilize the generator frequency by  maintaining the rotational speed following transient frequency variations at the motor power  supply or sudden load changes  The flywheel may be considered an analog to a storage battery   with a very short protection time  in static UPS systems      5  Induction coupling  Induction coupling occurs when using an asynchronous motor and  a synchronous generator  The induction coupling provides kinetic energy lasting approximately 2  seconds after loss of normal ac power to allow transfer to backup power  During this time a  backup diesel generator may be brought on line to provide power  This kinetic energy is supplied  from the rotor  Energy storage is achieved when the rotor of a three phase  two pole  asynchronous machine is accelerated to 3600 rpm  The stator of the same machine is  mechanically connected with the rotor of the synchronous machine  running at 1800 rpm  The  squirrel cage rotor of the asynchronous machine will run at 5400 rpm  1800 plus 3600 rpm   To  retrieve energy from the squirrel cage  at the moment of power interruption  a controlled dc field  is provided through an additional dc stator winding in the asy
11.   or oversight of any initial conditions  could result in the selection of a system that is  not capable of meeting the needs of the facility  costly budget overruns  and delays in completing  the project  In addition  there is usually significant growth in the number of UPS loads as a  manufacturing plant is developed  This must be accounted for in the sizing of the UPS  Figure 3   3 outlines the process of determining the required power capacity  The first question to answer is  how much power is needed  Power requirements can be divided into two categories  critical and  non critical  Critical power can be thought of as power for items such as emergency lighting for  evacuation of personnel  security systems  central computing systems  signaling systems  medical  equipment  and other functions that could cause loss of productivity  or result in injury or a life  threatening situation  Non critical power is used for functions such as general lighting   escalators  coffee makers  etc  Once the power requirements are defined  the next step is to  determine how much  if any  to oversize the unit  Oversizing serves two purposes  First  it  provides the capability to efficiently and effectively handle surges in power requirements due to  peak demands caused by starting machinery  switching power supplies  etc  Secondly  it provides  for growth  Over time  power demands may rise due to the addition of equipment or personnel   increases in productivity  and other reasons  Oversizi
12.   standards and    laws    Maintain conditions to prevent malfunctions in data processing system  Prevent damage    to equipment and storage media  Continue normal activity     Prevent malfunctions in data processing system and damage to equipment Continue  normal activity    Comply with local  state  and federal codes  standards  and laws  Lower insurance rates   Minimize damage to life and property    Comply local  state  and federal codes  standards  and laws  Lower insurance rates     Minimize damage to life and property     Service fire pump engine should it fail to start  Provide visual guidance for fire fighting    personnel     Maintain exposure quality  Ensure availability in emergencies     Comply with local  state  and federal codes  standards  and laws  Prevent interruption to  operation and operating needs   Maintain life  Prevent interruption of treatment or surgery  Continue normal activity   Comply with local  state  and federal codes  standards  and laws    Maintain blood  plasma  and related stored material at recommended temperature and in  prime condition    Maintain customer services  Maintain production control and warehousing  Continue  normal communication to prevent economic loss   Continue normal activity and control    Continue sales  Meet contractual obligations   Maintain security  Continue production     Continue sales  Meet contractual obligations   Maintain security  Continue production   Provide evacuation instructions  Direct activities durin
13.  12 volts  Battery cabinets are supplied  prewired with all inter connections factory made  The use of battery cabinets is common for  lead acid batteries in smaller systems and for nickel cadmium  ni cad  batteries  Lead acid  batteries for larger installations are normally mounted on open racks  In open rack installations   the individual battery cells are mounted on a rack or group of racks specially constructed for this  purpose  The racks are constructed of steel rails  frames  and braces  The battery cells rest on  plastic channels  The rack is factory painted with acid resistant paints  The racks may be of a  variety of configurations as shown in figure 4 2  The battery rack configuration is usually  determined by the cell dimensions  the number of cells  and the space available  Lead acid cells  are connected by specially designed inter cell connectors made of lead plated flat copper  Ni cad  cells can be connected by specially designed inter cell connectors made of flat steel  Inter tier   inter rack  and inter row connectors are also specially fabricated for the cell and rack type used     b  Installation requirements  The static UPS system should be located indoors in a clean  dust  free  low humidity location  The charger inverter cabinets may be located in the same room with    4 1    TM 5 693    the battery  However  for larger systems  it is preferable to locate the battery in a separate room  for additional safety  The charger inverter cabinets should be locat
14.  18  2 20  2 33  2 34  2 36  3 16  3 18  4 8   static UPS  1 1  1 2  2 1  2 6  2 14  2 20  2 22  2 25  2 26  2 31  2 32  2 33  2 35  2 36  2 39  2   40  3 13  3 15  3 16  3 17  3 18  4 1  4 2  4 7  5 5   synchronous motor  2 29  2 37  4 6   system rating  1 1  3 18    T  testing  1 3  1 4  4 1  4 11  4 13  4 15  4 16  5 5  5 6  three phase uncontrolled rectifiers  2 8  transistors  2 6  2 7  2 8  2 15  troubleshooting  1 1  3 11  4 23  5 4  5 5  5 16   U  unbalanced load  2 32    I 3    TM 5 693    Vv    valve regulated lead acid batteries  VRLA   2 21  voltage tapping  2 23    W    walk in time  2 5    zero crossing increases  2 28    I 4    TM 5 693    The proponent agency of this publication is the Chief of Engineers  United States Army   Users are invited to send comments and suggested improvements on DA Form 2028   Recommended Changes to Publications and Blank Forms  directly to HQUSACE   ATTN   CEMP SP   Washington  DC 20314 1000     By Order of the Secretary of the Army     ERIC K  SHINSEKI    General  United States Army  Official     Z    Chief of Staff    JOEL B  HUDSON  Administrative Assistant to the  Secretary of the Army    Distribution     To be distributed in accordance with Initial Distribution Number  IDN  344743   requirements for non equipment TM 5 693     PIN  077447 000    
15.  G al OAD  TATT j N F   Fi  SYNCH  SEMERATOR  MOTOR    i  t     HARGEF INVERTER       SaTTERY       Figure 2 31  Battery supported M G set    f  Rotary systems with a transfer switch to a bypass source  Like static UPS systems  rotary  systems can be provided with a transfer switch to transfer the load to an alternate source upon  loss of the generator output  However  unlike the static UPS inverter  it is not practical or  economical to synchronize the generator to the alternate source  Therefore  the transfer may    2 39       TM 5 693    occur in  out of synch  mode and may subject the connected loads to undesirable transient  overvoltages  Therefore  although the addition of a transfer switch can increase the availability of  power supply  live transfer is not recommended in rotary systems  Also  less costly  electromechanical switches may be adequate for this purpose     g  Paralleling of redundant rotary systems  Redundant rotary systems may be connected in  parallel to provide higher capacity and or to increase the reliability as was discussed in paragraph  2 3c for static UPS systems  However  due to the difficulty of synchronizing the generators to  one another  switching the individual generators for parallel operation should be performed  without the loads being connected to avoid subjecting sensitive equipment to high voltage  transients during switching     2 40    TM 5 693    CHAPTER 3    DESIGN AND SELECTION OF UNINTERRUPTIBLE  POWER SUPPLY  UPS     3 1  Select
16.  Technologies     4 3    TM 5 693    to remove the heat load generated by the UPS system and maintain the required room  temperature  The approximate heat load generated by the UPS in BTU hr is     1500 x UPS kVA for systems rated up to 20 kVA  1000 x UPS kVA for systems rated above 20 kVA    The need for a ventilation system should be determined on a case by case basis  Consideration  should be given to the load carrying capacity of the floor where the charger inverter cabinets are  to be installed  Also  the availability of freight elevators with adequate capacity for moving large  systems in office buildings should be ensured      2  Batteries and racks for larger systems  The battery racks should be located to allow access to  the cells for periodic maintenance  It is recommended that the battery be installed in a clean  cool  dry  location  Cells should not be exposed to heating units  strip heaters  radiators  steam pipes  or sunlight   Any of these conditions can cause a serious electrolyte temperature variation among cells within a  battery  In large battery installations  whenever possible  a floor drain with acid or alkaline proof piping  to a collection tank  depending on the cell type used  should be located near the rack to permit draining  any electrolyte that may spill accidentally  However  it may be desirable to use a pan directly underneath  the batteries  Due to the excessive weight of lead acid batteries  it should be ascertained that the battery  room flo
17.  _    kWx10      WK    oS lw  fe     where  kW   generator rated power  kW   n   generator rated rotational speed  r min     The inertia constant  H  is determined based on the required ride through time and minimum  frequency as follows     2  H t 1   Sa          TM 5 693    where  t   required ride through time  s   Fmin   minimum frequency required at the end of the ride through time  Hz   f     generator rated frequency  Hz     Theoretically  a flywheel can be selected to provide any ride through time  However  practical  and economical considerations limit the ride through time to around 0 5 second  High flywheel  inertia causes a long motor starting time  During the starting time  the motor s high starting  current can cause unacceptable or excessive motor heating  Also  due to the flywheel s heavy  weight and the long starting time  special bearings and lubrication methods may be required     d  Rotary UPS system selection criteria  Selection of a rotary UPS system should be in  accordance with certain criteria  The system output voltage and frequency shall be as required by  the loads  The output should preferably be three phase except for small systems  5 kVA and  smaller  where single phase systems may be used  The system output voltage and frequency  regulation and transient response shall meet the requirements of the most power sensitive load s    The system rated kVA at the specific site shall be equal to the load KVA plus a 10 to 15 percent  margin  The system s
18.  a make before break transfer   The addition of the alternate source increases the reliability of this configuration over the  comparable redundant system  In addition  the static switches make this configuration capable of  supplying high in rush currents by transferring to the alternate source  As with all systems with a  static transfer switch to an alternate ac source  a regulating transformer connected to the alternate  ac source is commonly used     2 4  Rotary UPS system configurations  The main building blocks of rotary UPS systems are the synchronous motor  ac generator  and  flywheel  In addition to the main building blocks  induction motors  eddy current clutches     batteries  dc M Gs  and static rectifier inverters are also used in rotary UPS systems  The  building blocks can be assembled in numerous configurations to meet reliability and or economic    2 36    TM 5 693    considerations  The most common rotary UPS configurations are the inertia driven ride through  system with a synchronous motor  the inertia driven ride  through system with an induction  motor  inertia driven ride through system with an induction motor and an eddy current clutch   battery supported inertia system with a dc motor  and battery supported inertia system with a  backup inverter        ALTERMATE _ TATE  f  J  AC SOURCE 4 F TaN     NORMAL             Figure 2 27  Dual redundant static UPS system with static transfer switches    a  Inertia driven ride through system with a synchronous 
19.  and power transistors can be turned off by gate pulses supplied by low  power gating circuits  Commutation circuits are relatively complex and their principles of  operation are beyond the scope of this manual  The second point is that in the circuit shown  the  load is directly connected to the dc source through the SCRs  This subjects the load to transients  generated within the dc system  For this reason  the load is normally isolated from the dc source  through the use of an output transformer  Also  the inverter output wave shape is a square wave   This wave shape is not suitable for supplying power sensitive equipment  Therefore  some means  are required to condition the inverter output to a sinusoidal waveform      2  Inverter voltage control  The common methods of inverter output voltage control are  pulse width control  PWM  and use of a ferroresonant transformer  Any of these methods may be  used for output voltage control  In some designs a combination of pulse width control and  modulation is used  However  a ferroresonant transformer is never used in combination with  either of the other two methods  The pulse width control technique has become less common    2 15    TM 5 693    than the PWM technique and the use of ferroresonant transformers  Also  some manufacturers  advocate the use of PWM while others favor the use of ferroresonant transformers  Although  each method may have some advantages over the others  the voltage control method is normally  not specif
20.  and system faults and records power disturbances  The  contained isolation transformer in a computer power center isolates noise that may be produced in  the power cable from the UPS output and allows establishing an effective single point grounding  system  Additionally  the output cables have specially fabricated grounding wires which tie the  equipment enclosures to the single point ground through plug in connectors  There should be no  other grounds on the neutral conductors which must be insulated for their entire length  including  the wiring in the equipment supplied by the branch circuits     d  Shielding  Low level signal cables to instruments should never be run in the same raceway  as power cables  While signal  or instrumentation  cables are usually shielded and or twisted to  reduce noise pickup  it is practically impossible to provide shielding of power cables to eliminate  transmission of low frequency energy  Using grounded metal enclosures  such as conduit or solid  tray  for all the distribution circuits will eliminate most of the higher frequency energy radiated by  the power cables     e  Radio frequency interference  RFI   Shielding as described in paragraph 4 3d  above  effectively eliminates the RFI that may be caused by harmonics in the UPS output  The RFI  effects that may be caused by radiated noise from the UPS components can be minimized by  maintaining adequate space between the UPS and susceptible equipment  A spacing at    4 10       TM 5 693  
21.  attempt at troubleshooting by qualified personnel  Obtain the manufacturer s  troubleshooting guide that applies to the specific system needing repair     f  Spare parts availability  A spare parts inventory for the UPS equipment should have been  provided at the time of installation  Normally  the inventory level should satisfy maintenance  requirements for at least a one year period based on the level of servicing capability of  maintenance personnel      1  Spare parts levels  The basic level includes typical user replacement items such as  fuses  capacitors  power semiconductors  and other items that may be useful at the time of  installation  Another level may include the basic level plus essential electronic control modules  and printed circuit boards  Additional items which are less frequently replaced or not as essential  to the uninterrupted operation of the UPS may also be included  The baking soda or boric acid  neutralizing agents and distilled water required for the battery electrolyte should also be available   Spare batteries having a short shelf life  6 months  should be ordered on need      2  Training levels  There are two training levels  basic  that is preventive and  troubleshooting  and advanced  that is corrective or remedial  Every user s manual will be    5 4       TM 5 693    structured differently  An understanding of what user personnel are permitted to do and what  requires a service representative will be different  Always refer to the user s ma
22.  capable of transferring and carrying the full load current continuously   In some designs  particularly larger ratings  a static transfer switch with short time rating is used  in conjunction with a circuit breaker connected in parallel at the bypass source  In this  arrangement the static transfer switch is not rated to carry the load current continuously  it can  carry the full load current for a duration of less than one second  The static switch is used to affect  fast transfer and to carry the load current for the duration required to close the motor operated  circuit breaker which is in the order of several cycles  Once the circuit breaker closes  it carries  the load current and relieves the static transfer switch  This configuration is comparable to the  fully rated static transfer switch  However  it has a lower reliability due to the higher failure rate  of motor operated circuit breakers  It is used mainly for economic reasons in lower cost systems     j  Batteries  A battery is used in a static UPS system to provide reliable emergency dc power  instantaneously to the inverter when the normal power fails or degrades  Of the many available  battery types  the following two basic types are generally used in static UPS systems  namely  the  lead acid and the nickel cadmium  ni cad  batteries      1  Lead acid batteries  A lead acid battery cell consists basically of a sponge lead  negative electrode  a lead dioxide positive electrode  and a sulfuric acid solution as 
23.  diode  conducts every half cycle when the anode voltage is positive relative to the cathode  In the bridge  configuration a pair of diodes conducts every half cycle when their anode voltage is positive  relative to the cathode  Comparison of the output voltage  Ea  and current wave shapes of the  two configurations indicates that they are identical  However  a major difference between the two  configurations is that for the same kW output  the center tap configuration requires a transformer  with a higher kVA than the bridge configuration and is more costly  For this and other reasons   the center tap configuration is used mainly in ratings of less than one kW  Examining the output  voltage wave shape for the two configurations indicates that it contains two pulses every cycle   This causes the output voltage  which is the average of these two pulses  to have a high ripple  content  Also  comparison of the output current  Ig  wave shape for resistive and inductive loads  indicates that with an inductive load  the output current is essentially constant throughout the  cycle  Therefore  connecting a large inductor in series with the rectifier output smoothes the  output current and minimizes the current ripples      2  Three phase uncontrolled rectifiers  There are numerous possible configurations of  three phase rectifiers  However  the basic building blocks of these configurations are the three   phase single way and the three phase bridge rectifier configurations shown in f
24.  discharged state  before the charger output is restored  A system shutdown may be initiated manually or  automatically by a dc undervoltage sensing device     2 1    TM 5 693     2  Restoration of power  Upon restoration of the ac supply after extended outage while  the battery has been discharged  the rectifier output voltage is set at the equalizing voltage to  recharge the battery  This can be done manually or automatically  The charger will also supply  the inverter while recharging the battery  At the end of the battery recharging time  the battery  charger returns to the floating mode and the system returns to normal operation      3  Momentary loss of power  During momentary ac power interruptions or when the ac  supply voltage sags below acceptable limits  the battery maintains the dc supply to the inverter   Under this condition  the inverter continues to supply the connected loads with regulated power  without interruption     b  Bypass mode  The static UPS systems may have three bypass switching arrangements  the  UPS static switch  SS   the UPS static switch circuit breaker  SS CB   and the maintenance  circuit breaker      1  UPS static switch  When an UPS equipment problem occurs  the load is automatically  transferred by the static switch bypass to an alternate power source to prevent power interruption  to the loads  The static switch is also useful in clearing load faults downstream of the UPS  The  static switch will transfer to the alternate power source o
25.  disclaims any responsibility of liability resulting from the placement and  use in the described manner     Technical Manual    No  5 693    TM 5 693    HEADQUARTERS    DEPARTMENT OF THE ARMY  Washington  DC  31 May 2002          APPROVED FOR PUBLIC RELEASE  DISTRIBUTION IS UNLIMITED       Uninterruptible Power Supply System Selection  Installation  and  Maintenance for Command  Control  Communications  Computer   Intelligence  Surveillance  and Reconnaissance  C4ISR  Facilities    CHAPTER 1    CHAPTER 2    CHAPTER 3    CHAPTER 4    CHAPTER 5    APPENDIX A    INTRODUCTION   Purpose   Scope   References   Principles and configurations  Design criteria and selection  Installation and testing  Maintenance    PRINCIPLES AND CONFIGURATIONS OF UNINTERRUPTIBLE  POWER SUPPLY  UPS  SYSTEMS   Principles of static UPS systems   Principles of rotary UPS systems   Common static UPS system configurations   Rotary UPS system configurations    DESIGN AND SELECTION OF UNINTERRUPTIBLE POWER  SUPPLY  UPS    Selecting an UPS   Static UPS system ratings and size selection   Rotary UPS system ratings and size selection    INSTALLATION AND TESTING OF UNINTERRUPTIBLE  POWER SUPPLY  UPS    Construction and installation of static UPS systems  Construction and installation of rotary UPS systems   Power distribution and equipment grounding and shielding  requirements   Testing and start up   Test equipment    UNINTERRUPTIBLE POWER SUPPLY  UPS  SYSTEMS  MAINTENANCE PROCEDURES   Maintenance for UPS syste
26.  for material  handling  Power for escalators    Power for alarms and    annunciators    Land based aircraft   railroad  and ship  warning systems  Water  cooling and   general use     Provide water   drinking  amp  sanitary   Provide boiler  power  Power pumps for  water  sanitation   and production  fluids    Up to 10s  preferably not  more than 3s    10s    From 10 s up to 2 or 3 min    1 s to indefinite depending on  available light  Indefinite  depends on  analysis and evaluation  Up to 10s  NFPA 99 1996   ANSI NFPA 101 1994    allow 10s for alternate power  source to start and transfer  power    0 1 sto lh    3s    15s to 1 min  15s to 1 min  15s to no requirement for    power  1 10s    Is to 1 min    1 min to no requirement  0 1s    10s to no requirement    2h    10 12 h during all dark  hours    Until prime power restored    Until repairs completed  and power restored  Indefinite  depends on  analysis and evaluation  Until prime power restored    10 min to several hours    Until prime power restored    Until prime power restored    1 h  Until prime power  restored   1 h  Until prime power  restored   Zero to until prime power  restored  Until prime power restored    Until prime power restored    Yh  Until prime power    restored     Indefinite until evaluated    1 h  Until prime power    restored   Indefinite until evaluated    X    Prevent panic  injury  loss of life  Comply with building codes and local  state  and  federal laws  Lower insurance rates  Prevent prope
27.  for their batteries  All have maintenance instructions for their cells and  some will conduct maintenance seminars or presentations  Be familiar with IEEE 450 and IEEE  1106 covering maintenance  testing  and replacement of storage batteries for lead acid and ni cad  types  respectively  Battery record  figure F 11 in National Fire Protection Association  NFPA   70B is an example form to use      1  Maintenance program  The maintenance program selected should address the specific  needs of the battery installed and should be both consistent and regular  Recommended  maintenance intervals should never be longer than those required by the manufacturer to satisfy  the requirements of their warranty  In addition  critical load requirements may dictate more  frequent maintenance based upon the importance of the installation and the consequences of a  failure of the battery when it is required to serve its load  Proper maintenance will ensure  optimum battery life assuming the battery has been properly sized and installed  Wherever  practicable  tests should be carried out in a manner that accomplishes one or more objectives at  once  a capacity test also can check for high connection resistance      2  Battery specifics  A maintenance program must address the specific battery installed   Although the tests and frequency of maintenance may be the same  there are subtle differences  between batteries  For example  the nominal float voltage will vary between lead antimony and  lead 
28.  for ventilation and access to maintenance panels  Static UPSs require environments with a  controlled atmosphere where the temperature  humidity  and dust levels are carefully maintained   The batteries of the UPS require ventilation of the room to prevent hydrogen buildup  Rotary  UPSs are suitable for placement in industrial environments     c  Protection  The UPS power distribution system shall be designed to provide short circuit  protection  isolate branch faults  and isolate critical loads from sources of harmonics  surges  and  spikes  This is achieved using panelboards  circuit breakers  and fuses  The UPS system is  grounded to ensure the safety of the operating personnel  Shielding of the control cables shall be  achieved by running power cables in bonded metal enclosures separately from the control cable   s  enclosures     d  Testing and startup  Testing and startup shall be performed to ensure the component   s  operation once energized  Acceptance testing should be performed on all equipment  Testing  records on test forms should be kept for comparison to later routine maintenance tests  The  possible failures of the equipment drawn out from the test results should be discussed and  corrective action implemented  Test equipment used should be in accordance with the  manufacturer   s recommendation     1 7  Maintenance    Maintenance of the UPS consists of preventive and corrective maintenance  Preventive  maintenance consists of a scheduled list of activities  
29.  found for UPS systems  but  the user should be aware of their effects on specific gravity requirements  A higher specific  gravity electrolyte is provided when ambient temperatures are extremely low  This increases cell  performance as well as serving to lower the freezing point of the electrolyte  Similarly  in high  ambients  normally above 90  F   a lower specific gravity electrolyte is provided to reduce losses  and maintain expected life      b  Comparisons  The measured specific gravity should be corrected to the reference  temperature and compared to previous data  Readings should be uniform  with a minimum  difference between the high and low readings  Where specific gravities vary considerably over  the battery  they are termed  ragged  and corrective action is required as covered in IEEE 450 and  IEEE 1106      6  Voltage readings  The open circuit voltage of a lead acid cell is a direct function of  specific gravity and can be approximated by equation 6 1  This relationship holds for cells that  are truly open circuited  i e   no current flowing through the cell  and have been off charge for  more than 16 hours with a well mixed electrolyte  A problem may be indicated if a voltage check  indicates a voltage below that expected by the following equation     5 12    TM 5 693    Open circuit voltage   specific gravity   0 84     a  Float and equalize voltages  Float voltages are directly related to cell type and  plate alloy as well as to the specific gravity of the 
30.  indicate deterioration without being destructive  The following paragraph discusses the  acceptance testing  The routine and special maintenance testing is discussed in chapter 5   Acceptance testing is a system verification and functional performance test which should be  performed on the UPS system  These tests will include installation inspections  individual  component testing  testing on wiring  control and interlock functional checks  equipment  energization and system operating measurements  and functional checks     a  Installation inspection  Field inspection and installation checks include the inspection of  the component nameplates  inspection of components for damage and cleanliness  inspection of  insulators for cracking  inspection of anchorage and grounding  sizing check of fuses and  breakers  alignment and adjustment checks  mechanical operation and interlock checks     4 12    TM 5 693    lubrication application  verification of insulating liquid or gas level or pressure  and verification  that local safety equipment is in place      1  UPS  The UPS system shall be inspected for completeness of assembly  verification of  nameplate  sizes and settings against drawings  loose parts and insulation damage  and proper  settings      2  Battery  The battery should be inspected for completeness of assembly  verification of  nameplate  sizes and connection against drawings  loose parts  leaks or damage  electrolyte level   flooded batteries   and vents sealed and p
31.  is used in rotary UPS applications  The relevant  characteristics of a cage motor are as follows  The motor speed is essentially proportional to the  power supply frequency  The motor speed is dependent on the load level  For a motor with 5  percent slip  the speed may increase by up to 5 percent of the rated speed from rated load to no  load  The speed variations are lower for low slip motors  When energized  the motor draws a  starting current as high as 6 5 times the rated current for a duration of 2 to 10 seconds or longer  depending on the load inertia  The induction motor power factor is approximately 0 8 lagging      2  Synchronous motors  The relevant characteristics of a three phase synchronous motor  are as follows  The motor speed is independent of the load and is directly proportional to the  power supply frequency  The starting current and starting duration of a synchronous motor are  slightly less than those of a comparable induction motor  A synchronous motor can be either self   excited or externally excited  see paragraph 2 2b 3  for exciter types   The synchronous motor  power factor can be changed from lagging to unity to leading by adjusting the field or exciting  current      3  DC motors  DC motors are classified according to the method of excitation used as  shunt excited  series excited  and compound excited  The shunt excited dc motor is the most  suitable in rotary UPS applications and has the following characteristics  The motor speed is  dependent
32.  logic  After shutdown  all UPS systems should be load tested off line   Approximately 85 percent of system failures occur after maintenance shutdowns which were not    2 3    TM 5 693             AC  CRTC AL  AC LINE hy LOAD  SS CB SCRA OUTPLUT CB     ora     i     CONTROL  i   FIRING    Logie  i UFS CE SCRI  RECTIFIER a ae ze  CHARGER INVERTER   SORI  Cat  BATTERY  MPE CB  s h  SCR O G  P SCR OPERATING LEGEND   H SCR OFF LINE _   PETES  MEF   MAINTENANCE BYPASS SAITOH  SS   STATIC SWITCH  UFS   UMNTERRUPTIELE POWER SLIPPLY  CE   CIRCUIT BREAKER                Figure 2 3  SCR switching transfer with UPS isolation    off line load tested to assure proper operation  In order to shut down the complete UPS system   the load must be transferred to a line which is isolated electrically from the power and logic  circuitry of the entire UPS installation      b  Operation of maintenance bypass switch  Close the UPS static bypass  which  automatically opens the UPS module output circuit breaker  UPS CB   allowing closing of the  maintenance bypass circuit breaker  MBP CB  before opening the UPS output circuit breaker   OUTPUT CB   A closed transition has been made to an alternate supply for input to the critical  load with no interruption  Now the UPS system as a whole can be de energized for maintenance  and off line load testing  This is the basis for the interlocking requirements shown on figure 2 5     c  Test mode  Off line load testing of UPS systems after installation and sched
33.  may require strengthening of the floor to support their weight  Large UPSs may  require the construction of a separate building to house the unit  A rotary UPS or engine  generator used in a cold climate will probably require thermostatically controlled lubricating oil   coolant heaters  and radiator louvers  All equipment manufacturers specify the temperature  extremes  humidity  and other conditions for which the UPS was designed  Operating and  support costs of the UPS are usually secondary to the costs of purchasing and installation   However  they can be substantial and should be included as a factor in the final selection   Operating and support costs include cost of fuel  maintenance  replacement parts  and taxes   Finally  when an UPS reaches the end of its life  disposal costs will be incurred  Disposal may  simply consist of dismantling the UPS and selling the parts to a recycling company or dumping it  at an approved refuse site  For UPSs containing dangerous or environmentally unsafe chemicals  or materials  disposal is much more complicated and expensive  For example  disposal of lead   acid batteries must be performed according to all federal  state  and local regulations  Lead acid  batteries should be reclaimed to avoid the regulatory requirements for hazardous waste treatment  and disposal facilities  Reclamation may be included as part of a procurement contract for  replacement batteries or contracts may be placed with a permitted reclaiming facility  In  d
34.  motor and a generator   These items are individually listed      2  Battery chargers  A battery charger is an electronic device that converts ac power to dc  power  The charger supplies this dc power to the battery  As with all electronic devices  this  device should not be megger tested  A visual inspection should be performed to verify the  correctness of installations  supports  grounding  and wiring  The rating nameplate should be  checked to ensure that both the ac supply to the charger and the battery to be connected  corresponds to the charger   s parameters  Check to ensure all shipping and other debris in and  around the charger cabinet are removed  Check settings of the charger and calibrate per  manufacturer   s manual to match the battery  float and equalizing levels   If the battery charger  has been factory set  check the charger float and equalizing voltage levels against drawings and  specifications  If not  set the charger float and equalizing voltage levels to those listed on  drawings and specifications  Before connecting to the battery  measure the output voltage  provided by the charger and record  Verify that all charger functions and alarms operate  correctly  Verification that the battery is connected to the battery charger properly is extremely  important  The negative wire from the negative terminal of the battery must be connected to the  negative terminal of the charger  Similarly  the positive wire from the positive terminal of the  battery must 
35.  number  the greater the capacity to resist  First digit  O to 6   capacity to resist penetration by  solid objects  Second digit  0 to 7   capacity to resist penetration by liquids  Third digit  0  1  2   3 5  7  9   mechanical strength     Pulse Width Modulation  PWM    Inverter high frequency chopping technique using a means of regulation enabling rapid  modification of pulse widths over a single period  This makes it possible to maintain the inverter  output within tolerances even for non linear loads     Radio Frequency Interference  RFI   An unwanted electromagnetic signal that degrades the performance of the electronic device     Rated Output   see Output  rated      Reactance   Relative measurement  percent  of the internal impedance of an ac generator during harmonic  phenomena  This reactance  also called the longitudinal subtransient reactance of the generator  is  sometimes identified as X   d  For most common generators  the value ranges between 15 and 20  percent  It can drop to 12 percent for optimized systems and to 6 percent for special devices     Recombinant Battery   A battery in which the cells are sealed with pressure relief valves that confine any gases produced  during cell operation  These gases are then recombined back into water  substantially eliminating  the loss of water from the cells and the need for water replenishment     Recombination Battery   see Battery  recombination      Rectifier  A device for converting ac to dc     Rectifier charger 
36.  of 120 to 180 percent of the installed battery per cell cost   These battery maintenance costs may appear high  but  compared to the cost of an unplanned  critical load outage  they are relatively small     b  Maintenance access  Redundant UPS systems having a separate but inter tied battery per  UPS module can be maintained without taking the entire UPS system off line  A single system  battery requires an UPS system shutdown on not less than a quarterly basis  Shutdown should be  done in conjunction with the maintenance shutdown for the UPS equipment  While some battery    5 5    TM 5 693    maintenance service companies indicate that battery maintenance which does not require testing  can be performed without UPS shutdown  they also indicate that the battery disconnect switch  should be open  It is recommended that site maintenance personnel not provide quarterly  maintenance to the battery without an UPS shutdown     c  Preventive maintenance  Institute of Electrical and Electronics Engineers  IEEE  450 and  IEEE 1106 recommend monthly  quarterly  and yearly inspections  Some manufacturers  recommend weekly inspections  The National Electrical Code  NEC  requires periodic testing on  a schedule acceptable to the authority having jurisdiction  Periodic maintenance is required and  written records of tests and maintenance must be kept  A typical lead acid battery inspection  procedure shown in table 5 2      1  Testing  Do not overtest  Frequent testing will shorten the se
37.  on the load level  The speed may decrease by up to 5 percent of the rated speed from  no load to rated load  The motor speed can be easily adjusted by varying the shunt field current  through the use of a rheostat  The motor can be operated as a generator by applying mechanical  input to the shaft     b  Generator types and characteristics  In a rotary UPS system a synchronous generator is  used to convert the motor mechanical energy or the mechanical energy stored in a flywheel to ac  electrical energy with regulated voltage  In rotary systems with a storage battery a dc motor or  inverter is provided for driving the generator during a loss of ac power  When ac power is  available  the dc motor is operated as a dc generator to charge the battery  Newer rotary system    2 30    TM 5 693    designs may also utilize a back up inverter and a dc battery to supply the driving motor upon loss  of the normal ac power  In the following paragraphs  only the generator characteristics relevant  to rotary UPS applications will be discussed      1  Synchronous generators  The relevant characteristics of a three phase synchronous  generator are as follows  The generator frequency is directly proportional to the prime mover  speed  Controlling the output frequency is accomplished by controlling the prime mover speed   The output voltage can be regulated by varying the field current  i e   excitation level  The  generator rated power factor is normally 0 8 lagging  The generator has a limit
38.  operations  1 1    I 2    TM 5 693    P    power  1 1  1 2  1 3  1 4  2 1  2 2  2 3  2 4  2 6  2 7  2 8  2 9  2 14  2 15  2 18  2 20  2 21  2 22   2 23  2 25  2 26  2 27  2 28  2 29  2 30  2 31  2 32  2 33  2 34  2 35  2 36  2 37  2 38  2 39  2   40  3 1  3 2  3 6  3 7  3 8  3 9  3 10  3 13  3 15  3 16  3 17  3 18  3 19  3 20  4 1  4 2  4 6  4 7   4 8  4 9  4 10  4 11  4 12  4 13  4 14  4 15  4 16  4 17  4 21  5 1  5 3  5 4  5 5  5 13   power diodes  2 9   power requirements  3 6   preventive maintenance  1 4  5 1  5 5   probability  3 8  5 2   protective devices  1 3  3 16  4 7  4 8  4 9   pulse width modulation  PWM   2 5  2 15  2 16  2 17    R    rectification  2 8   rectifier  1 1  2 1  2 2  2 5  2 6  2 8  2 9  2 10  2 11  2 12  2 25  2 26  2 29  2 32  2 33  2 35  2   36  2 39  4 3  4 17  4 20  4 22  5 3  5 4  5 6  5 8  5 9  5 10  5 13  5 15  5 16   reliability  2 20  2 21  2 28  2 33  2 34  2 35  2 36  2 37  2 38  2 39  2 40  3 1  3 7  3 8  3 9  3   10  3 11  3 20  5 1  5 2  5 8   ripple currents  2 25   rotary UPS  1 1  1 2  1 4  2 29  2 30  2 31  2 32  2 33  2 36  2 37  3 13  3 18  3 20  4 6  4 7  4   13  5 5    S    safety  3 6  4 22  4 23  5 1  5 5  5 15  5 16   SCR  2 1  2 3  2 4  2 6  2 7  2 14  2 15  2 16  2 17  2 18  2 19  4 20  4 21   shielding  1 4  4 7  4 10   single phase uncontrolled rectifiers  2 8   sizing selection  1 1   standby power  1 1  3 1  3 6   static switch  1 2  2 1  2 2  2 20  2 33  2 35  2 36  2 39  4 8  4 17  4 19   static transfer switch  2
39.  referred to as the load factor  Phase shift filter  see Filter  phase shift       Power Factor   The power factor is the mathematical relationship between apparent or effective power  measured  in kVA  and real or average power  measured in kW  When the current and voltage are in phase   purely resistive load  the power factor is 1  In a purely reactive load in which voltage and current  are 90   out of phase  the power factor is 0     Power factor  1   Ratio between the active power P supplied to a load and the apparent power S supplied to said  load by an ac power supply     Power Source  alternate   Backup source used in the event of a mains failure  The connection time and the duration of the  source depend on the type of source used     Power Source  safety   Power source for loads defined as critical by applicable safety regulations  This supply must not  be affected by a mains failure and is generally separate from other supplies     Primary Cell or Battery  A cell or battery that is not intended to be recharged and is discarded at the end of its useful life     TM 5 693    Prime Power  The normal source of power used continuously day and night  Usually supplied by an electric  power utility but can be supplied by base loaded user generation     Protection Index  IP    Index indicating the capacity of an electrical device to resist environment conditions  It is made  up of three digits  e g   IP 205   each corresponding to a type of environmental risk  The higher  the
40.  sediment hills reach the plate bottoms  Dark or chocolate brown  sediment hills beneath the positive plates indicate continuous overcharge  A gray deposit in hills  beneath the negative plates indicates continuous undercharge  Excessive but somewhat mixed  sediment hills showing both positive and negative materials indicate the battery has probably  undergone random periods of undercharge and overcharge  Examine cells for mossing where  excessive sediment is noted  Cells should be watered when inspection reveals electrolyte levels  below the high level line  The manufacturer should be consulted immediately about cells where  the electrolyte level is below the plate tops  Water should not be added to these cells until the  manufacturer has agreed that this is the proper action or has inspected the cells and recommended  filling  Electrolyte levels below the plate tops can cause permanent cell damage  and the cell may  need to be replaced  A record of the amount of water added to each cell should be kept and  checked with the battery manufacturer s normal cell water consumption requirement  Lead   antimony batteries normally experience an increase in water consumption with age  Water  consumption in excess of the manufacturer s requirement is an indication of overcharging  A cell  that has been recently moved or transported should not have water added until it has been placed  back on charge for a period of time as recommended by the manufacturer  If the plates were  exposed w
41.  solid state system relying solely on battery power as an  emergency source  A static UPS consists of a rectifier  inverter  and an energy storage device   i e   one or more batteries  The inverter in the static UPS also includes components for power  conditioning  Modern static UPS systems are constructed with ratings ranging from about 220  VA to over 1 MVA  Static UPSs ranging from 220 VA to 1 MVA are constructed without  paralleling internal components  UPS with output higher than 1 MVA are built with some  parallel internal components  which result in decreasing reliability  Figure 1 1 shows a simple    1 1    TM 5 693    static UPS  Design  installation  and maintenance requirements should follow the latest version  of applicable codes and standards from recognized industry and commercial groups                                                                                   UPS UNIT       MANUAL  NORMAL  AC    RECTIFIER INVERTER 3 Bite BYPASS            o LOAD  SOURCE     SWITCH       BAT TERY    ALTERNATE  AC SOURCE             Figure 1 1  Simple version of a static UPS    b  Rotary UPS  A rotary UPS is a system that uses a motor generator  M G  set in its design   Figure 1 2 illustrates a simple rotary UPS  Unlike static units  the basic parts may vary between  manufacturers for rotary units  Rotary units are mainly designed for large applications  125 kVA  or higher  Some reasons for selecting a rotary UPS over a static UPS are to provide higher  efficiency  superi
42.  t      Load  non linear    Load  generally with a switched mode power supply  generating major harmonic currents   Current wave form is different from voltage wave form  Ohm   s law is not applicable  It can be  used only with each harmonic     Load Power  Apparent power Pu that the UPS inverter supplies under given load conditions  It is less than or  equal to the rated output Pn  The ratio Pu Pn defines the percent load of the inverter     Load Shedding  The process of deliberately removing pre selected loads from a power system in response to an  abnormal condition to maintain the system   s integrity     Maintainability   Relative ease and economy of time and resources with which an item is retained in  or restored to   a specific condition when maintenance is performed by personnel having specified skill levels   using prescribed procedures and resources  at each prescribed level of maintenance and repair   Measures include probability to repair within a given time  repair rate  and mean time to repair     Manual Bypass   see Bypass  manual      Mean Downtime  MDT   The mean time during which an item is not available for operation for any reason  including  active maintenance  lack of parts  lack of maintenance personnel  etc     Mean Time Between Demand  MTBD    A measure of reliability that addresses all reasons for support  Demands can result from inherent  failures of the item  failures caused by operators or maintenance personnel  induced failures    preventive mai
43.  test equipment list for troubleshooting an UPS module  Major system inspection general   Weekly battery inspection   Monthly battery inspection   Quarterly battery inspection   Annual battery inspection    LIST OF FIGURES  Title    Simple version of a static UPS   Rotary UPS  shown with primary power on   Basic static UPS system   SCR static switching transfer   SCR switching transfer with UPS isolation    B 1    I 1    Page    2 23  2 26    3 3   3 9   3 11  3 14  3 14  3 14  3 14  3 15  3 18  4 19  4 20  4 20  4 21  4 21  4 22  4 22  4 22  4 23  5 3   5 6   5 6    5 8    Page    1 2  1 2  2 1  2 3  2 4    Figure    Figure 2 4   Figure 2 5   Figure 2 6   Figure 2 7   Figure 2 8   Figure 2 9   Figure 2 10  Figure 2 11  Figure 2 12  Figure 2 13  Figure 2 14  Figure 2 15  Figure 2 16  Figure 2 17  Figure 2 18  Figure 2 19  Figure 2 20  Figure 2 21  Figure 2 22  Figure 2 23  Figure 2 24    Figure 2 25  Figure 2 26  Figure 2 27  Figure 2 28  Figure 2 29    Figure 2 30  Figure 2 31  Figure 3 1  Figure 3 2  Figure 3 3  Figure 3 4  Figure 3 5  Figure 3 6  Figure 4 1  Figure 4 2  Figure 4 3  Figure 4 4    Figure 4 5  Figure 4 6    Figure 4 7    TM 5 693    LIST OF FIGURES  continued     Title    Static switching transfer with circuit breaker   UPS maintenance bypass switching   Half wave diode rectifier with resistive load   Half wave SCR rectifier with resistive load   Center tap full wave uncontrolled rectifier   Full wave bridge uncontrolled rectifier   Three phase uncontrolled s
44.  those for flooded cells  but charging voltage must be monitored more closely   Normally  the cells operate on float charge without need for periodic equalizing charges   Recharge times are relatively short when recharges are required  Temperature compensation of    5 14    TM 5 693    float voltage is more critical than for flooded cells  and a temperature compensated rectifier  charger should be utilized      3  Temperature  Failure to temperature compensate float voltage can cause premature  cell failure  A recommended float voltage of 2 25 volts per cell at 77  F must be increased to 2 33  volts per cell if the ambient temperature is 55  F and must be decreased to 2 18 volts per cell if the  ambient temperature is 95  F  consult manufacturers for specific values for their cells   Ripple  content of the rectifier charger output must also be considered  Ripple voltage limits are specified  by some battery manufacturers on their cell data sheets  Excess ripple may reduce the expected  life of the battery  particularly when the battery has a low internal resistance     h  Ni cad cells  In general  all of the procedures and tests described for flooded lead acid cells  are valid for ni cad batteries  except for specific gravity  The ni cad electrolyte is a solution of  potassium hydroxide in water with a specific gravity between 1 180 and 1 200  depending upon  the manufacturer  The electrolyte does not enter into the reaction of the ni cad cell and is  therefore not an indicat
45.  to crystallize and be shed from the plate  To prevent this  an   equalizing  charge is given for a selected time period to provide a complete recharge on all cells   However  excessive equalizing charges will have an adverse effect on battery life  Automatic  equalizing after a discharge may require less maintenance time but may affect battery life   Equalizing charges on a periodic basis are not recommended but should follow the manufacturer s  guidelines  Equalizing charging should be considered a corrective action rather than routine  maintenance  Periodic equalizing charges can be considered as treating a possible problem before  determining that there is a problem      d  Ni cad cells  The usual recommended float voltage for UPS applications is 1 38 to  1 47 volts per cell depending upon the manufacturer s recommendation  Overcharge  as such   may cause no harm to the battery although there will be water loss  The current rate used for  charging  though  could produce a damaging heating effect during any appreciable overcharge   Equalizing is not as important for this type of battery  but may be recommended to assist in  electrolyte mixing after addition of water     2 24    TM 5 693     4  Ripple currents  UPS applications can place unusual load conditions on a battery  and  one condition that increases the rate of battery breakdown is ripple current  Ripple current is  caused by the ripple voltage of the battery charger output and by the pulsating current  requirement
46.  to inverter A  Close inverters A and B input breakers  measure inverters A and  B output voltage and read meters  and verify inverters A and B outputs are in phase  Verify static  switch is in inverter A position  open inverter A incoming breaker and verify static switch  switches to inverter B  Measure voltage and ensure a bumpless transfer is made  Close inverter  A incoming breaker and verify static switch switches to inverter A  Measure voltage and ensure a  bumpless transfer is made  Open rectifier battery charger output breakers and battery breaker and  verify that inverts A and B trip on low voltage     4 17    TM 5 693             Rectifier   Battery  Charger  l1 CB     495 VDC  Battery    Static  Transfer  Switch    J  6004       UPS Switchboard  120 206  3 Phase       200A 200A   eo  200A h           UFPE Distribution Panels             Figure 4 7  UPS distribution panels     2  Loading UPS  Verify UPS is energized through static switch and all UPS loads are  connected properly and ready to start  Close the incoming breaker to the UPS bus  Close the  load breakers on the UPS bus sequentially  Measure voltage and read UPS meters at each step   and add load until the UPS reaches normal design load      3  Utility trip test  Verify the UPS is loaded and connected to the utility  Manually open  the feeder breaker and verify the battery picks up load  Measure the current  Verify the transfer    4 18    TM 5 693    switch transfers to diesel generator  the diesel generat
47.  transistors which are not latching devices  The other drawbacks to the  commutation circuit are that it adds more equipment to the circuit  adds audible noise to the unit   and consumes power        A K    w    THYRISTOR    Ia             0 a T 2r 2nta 3n    wt    gt              Figure 2 7  Half wave SCR rectifier with resistive load     3  Bipolar transistors  Bipolar transistors permit current to flow through the circuit when  current is applied to the base  The flow of the power through the device is proportional to the  current applied to the base  Unlike SCRs  transistors are not latching  Upon removing the current  from the base  the circuit will be turned off  This allows for much quicker switching time than  the SCRs  However  bipolar transistors experience high saturation losses during power  conduction which requires drive circuits to minimize switching losses      4  FET  FETs are turned on and off by applying voltage to the gate  This is more    efficient than applying current to the base as done with the bipolar transistors  The FETs  experience saturation losses and require drive circuits to minimize the switching losses     2 7    TM 5 693    Moreover  the high resistance characteristics of the power conducting portion make this device  inefficient and undesirable for large applications      5  IGBT  The IGBT combines the desirable characteristics of the bipolar transistor and  the FET  Voltage is applied to the base to turn the device on and off and the coll
48.  user s manual should always be consulted as to specific maintenance requirements  and troubleshooting diagnostics guidelines     a  Safety  Do not rely on memory  Follow the user s manual guidelines  Such guidelines  should provide safety precautions  If your user s manual limits the maintenance that can be  provided by the user  follow the manual s instructions unless general instructions are  supplemented with additional guidance  Physical maintenance or troubleshooting should only be  performed by personnel trained on the system  Operating personnel not instructed in UPS  maintenance must limit their efforts to identifying the symptoms of a fault  Always be aware of  the DANGER  as voltages within the UPS modules and associated switchgear are lethal  Lethal  voltages are present even when the output circuit breaker in the UPS is open  It is necessary to  open the circuit breaker in the distribution panel feeding the UPS and the UPS bypass circuit  breaker  plus opening the direct current  dc  link connection to the battery  before all dangerous  voltages within the UPS are eliminated  Capacitors may need to be discharged of their stored  energy  Use CAUTION when operating UPS equipment to prevent serious injury or death     b  Preventive maintenance  Periodic maintenance is required to maintain the integrity and  lifetime of the battery  Power electronic equipment also requires scheduled maintenance even  though solid state devices are used  Preventive maintenance may req
49.  x In     High Frequency Interference   see Interference  high frequency      G 8    TM 5 693    Hybrid UPS   see UPS  Hybrid     Individual Distortion   see Distortion  individual      Inrush Current   See Current  inrush      Insulated Gate Bipolar Transistor  IGBT   The IGBT is a minority carrier device and is fundamentally different in operation than a  MOSFET  although they are similar in cross section     Interference  high frequency   High frequency parasitic current that is either conducted  electrostatic origin  or radiated  EM  origin  by a device     International Electrotechnical Commission  IEC   Advisory organization that draws up international standards in the electrotechnical field     Inverter  A device for converting dc to ac current     Inverter   UPS subassembly that recomposes a sine wave output  regulated and without breaks  using the  dc current supplied by the rectifier charger or the battery  The primary elements of the inverter  are the dc ac converter  a regulation system  and an output filter     Inverter  off line or stand by    UPS configuration in which the inverter is parallel mounted to the load supply line and backs up  the mains  This configuration offers a substantial cost reduction but is applicable only to low  outputs  under 3 KVA  because it results in an interruption lasting up to 10 milliseconds  ms   during transfer and does not filter inrush currents     Inverter  on line    UPS configuration in which the inverter is in series mount
50. 85 300 500 2 6 cycles  Fluorescent lights  corrected type  0 95 300 600 1 cycle  Incandescent lights 1 0 600 1500 2 6 cycles  Regulated DC power supply  or battery charger  0 6 0 8 600 1000 2 6 cycles  Unregulated DC power supply 0 9 600 1000 2 6 cycles  Transformer Same as load 1000 1 cycle  Magnetic line regulators  auto transformer  0 6 0 8 200 300 1 cycle  Ferroresonant type line 0 5 lead   regulators  CVT  to 0 5 lag 600 1000 1 3 cycles  Solenoids  Relays and Contactors 0 5 1000 2 3 cycles        2  Determining load power factor  In existing installations  the load power factor should  be determined by actual measurements using a power factor meter  In cases where actual  measurements cannot be taken or when the installation is in the planning stage  the load power  factors should be calculated  To calculate the load power factor  the kVA and power factor of the  individual loads should be obtained from the equipment manufacturers    data  When a load power  factor is not available  it can be estimated from the data in table 3 8  The total load power factor  can then be calculated  Estimating the load power factor is necessary since the kVA rating and  performance parameters of most static UPS system designs are guaranteed only at a power factor    TM 5 693    range of 0 8 lagging to unity  The static UPS system kVA capacity and performance parameters  are affected at other power factors      3  Determining load inrush kVA  Determination of the load inrush kVA is particu
51. 9  2 30  2 31  2 32  2 36  2 37  2 38  3 18  3 19  3 20    I 1    TM 5 693    G    generator  1 2  2 26  2 28  2 29  2 30  2 31  2 32  2 33  2 36  2 37  2 38  2 39  3 6  3 13  3 18  3   19  3 20  4 6  4 13  4 16  4 17  4 19  4 21  4 22  grounding  1 1  4 7  4 9    H    harmonic correction techniques  2 28  harmonic distortion  1 1  2 25  3 14  harmonics  2 1  2 17  2 26  2 27  2 28  4 10    induction coupling  2 31   induction motors  2 30  3 19   inrush current  2 4  2 5  2 25  2 33  3 16  3 18  4    installation  1 1  2 4  2 28  2 33  3 1  3 6  3 10  3 11   11  4 12  4 14  4 15  4 17  5 4  5 5  5 7  5 8  5 9  5    insulated gate bipolar transistor  IGBT   2 6  2 8  2 14   inversion  2 14   inverter  1 1  2 1  2 2  2 5  2 6  2 7  2 14  2 15  2 16  2 17  2 18  2 20  2 25  2 29  2 30  2 32  2   33  2 34  2 35  2 37  2 39  3 16  3 17  4 1  4 2  4 3  4 4  4 7  4 8  4 14  5 3    8  11  3 12  3 13  3 15  3 16  3 17  3 19  4 7  4   8 13  5 15    2     K  kinetic battery  2 29   L  latching devices  2 7  lead acid batteries  2 20  lower power factor  2 27   M    maintenance  1 1  1 3  1 4  2 3  2 4  3 11  4 1  4 20  4 22  5 1  5 2  5 4  5 5  5 7  5 8  5 9  5 12   5 14   maintenance bypass switch  2 3   memory effect  2 25   motor  1 2  2 20  2 29  2 30  2 31  2 32  2 36  2 37  2 38  2 39  3 15  3 18  3 19  3 20  4 6  4 13   4 15  4 16  4 19    N  neutral harmonic behavior  2 27  nickel cadmium batteries  2 20  2 22  5 6  5 15  noise feedback  2 28  nonlinear loads  2 25  2 32   O   
52. 990  pp  37 40    TM 5 693    Migliaro  Marco     Considerations for Selecting and Sizing Batteries     IEEE Transactions on Industry  Applications  Vol  IA 23  No  1  January February 1987  pp  134 143    Migliaro  Marco     Maintaining Station Batteries     IEEE Transactions on Industry Applications  Vol   A 23  No   4 July August 1987  pp  765 772    Motto  Eric R   John F  Donlon  Stashi Mori  and Takhiko Iida     New Process Technologies Improve IGBT Efficiency     IEEE  October 1995  pp  991 996    Reeves  Mark     IGBTs     Power Technics  August 1990  pp  12 16    Sammuli  Lynn     Harmonics Can Affect a UPS     Electrical Design and Installation  June 1991  pp  18 23    Santini  John     Specifying Power Supplies     Powertechnics  January 1991  pp  25     Smith  K M      Intelligent Magnetic Amplifier Controlled Soft Switching Method for Amplifiers and  Inverters     IEEE Transactions on Power Electronics  Vol  13  No  1  January 1998  pp  84 92    VanDee  Dawn     Rounding Up Rotary UPS Features     EC amp M  March 1999  pp  54 55    VanDee  Dawn     Understanding UPS Techno Babble     EC amp M  November 1998  pp  80 87    Windhorn  Allen     A Hybrid Static Rotary UPS System     IEEE Transactions on Industry Applications  Vol  28   No  3  May June 1992  pp  541 545    Yarpezeshkan  Hassan     Selecting the Battery for UPS Applications     Powertechnics  October 1989  pp38 42    A 5    TM 5 693    APPENDIX B    SELECTING AN UNINTERRUPTIBLE POWER SUPPLY  UPS   AN  E
53. ANSI   1430 Broadway  New York  NY 10018    ANSI C57 110  Recommended Practice for Establishing Transformer Capability when Supplying Non   sinusoidal Load Currents  1998   cited in paragraph 2 1n 4      ANSI TEEE 519  Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems    1992   cited in table 2 2     ANSI NEMA MG 1  Motors and Generators   1978   cited in paragraph 3 3b     Institute of Electrical and Electronic Engineers  IEEE   445 Hoes Lane  P  O  Box 1331  Piscataway  NJ 08855 1331    IEEE 446  Orange Book  Emergency and Standby Power Systems for Industrial and Commercial  Applications   1996   cited in paragraph 2 3  Table 3 1     TEEE 450   Recommended Practice for Maintenance  Testing  and Replacement of Vented Lead Acid  Batteries for Stationary Applications   1995   cited in paragraphs 3 2b 2   5 2c  5 2c 1   5   2c 2  k   5 2f 4   5 2   5  6      TEEE 500   IEEE Guide to the Collection and Presentation of Electrical  Electronic  Sensing Component   and Mechanical Equipment Data for Nuclear Power Generating Stations   1984   cited in  paragraph 3 1f 1      TM 5 693    IEEE 1106   Recommended Practice for Installation  Maintenance  Testing  and Replacement of Vented  Nickel Cadmium Batteries for Stationary Applications   1995   cited in paragraphs 5 2c 1   5   2c  5 2c 2   5 2d  5 2f 5  b      National Fire Protection Association  NFPA   One Batterymarch Park  P  O  Box 9101  Quincy  MA 02269 9101    NFPA 70  National Electrical C
54. Figure 4 3  Double ended substation connected in secondary selective configuration       TM 5 693    4 2  Construction and installation of rotary UPS systems  The construction and installation of the UPS are critical to its proper operation     a  Construction features of rotary systems  There are several construction features about the  UPS that contribute to the system as a whole      1  Motor generators  M G  and controls for rotary systems  The M Gs used in rotary  UPS systems are normally of the horizontal type  The M Gs can be built into a single frame or in  separate frames coupled together and mounted on a common base  The M G can be mounted  without enclosures or enclosed in a sheet metal cabinet  In constructions without an enclosure   the control and monitoring devices are installed in one or more small cabinets mounted on the  M G frame s   In constructions with an enclosure  the control and monitoring devices are  normally mounted in a free standing cabinet attached to the M G enclosure  An inertia driven  ride through system with a synchronous motor rotary UPS with a power range of 200 to 10 000  kVA is shown in figure 4 4  In addition to the M G  various protective and control devices may  be used on rotary systems including a thermal magnetic circuit breaker at the ac motor input       Figure 4 4  Rotary UPS system 200 to 10 000 kVA  courtesy of HITEC Power Protection      with indicating lights to indicate the breaker open close position   an ac contactor use
55. ITEC Power  Protection    Single point grounding example  reproduced from Federal Information  Processing Standards Publications  FIPS pub  94    Multi point grounding example  reproduced from Federal Information  Processing Standards Publications  FIPS pub  94    UPS distribution panels    iii    Page    2 5   2 6   2 7   2 7   2 9   2 10  2 11  2 12  2 13  2 14  2 15  2 16  2 17  2 18  2 19  2 20  2 29  2 30  2 33  2 34  2 34    2 35  2 36  2 37  2 38  2 38    2 39  2 39  3 1  3 2  3 7  3 9  3 10  3 12  4 2  4 3  4 5  4 6    4 10    4 11    4 18    TM 5 693    CHAPTER 1    INTRODUCTION       1 1  Purpose    The purpose of this publication is to provide guidance for facilities engineers in selecting   installing  and maintaining an uninterruptible power supply  UPS  system after the decision has  been made to install it  This technical manual  TM  TM 5 693 has been prepared to provide  generic guidance to agencies responsible for the selection  installation  and maintenance of UPS  systems at Command  Control  Communications  Computer  Intelligence  Surveillance  and  Reconnaissance  C4ISR  facilities  Although it is written mainly for C4ISR facilities  which  require a higher level of reliability  it could also be utilized as a reference in similar applications     1 2  Scope    The process for identifying the need for an UPS system  selecting  installing  and maintaining the  UPS system are covered  Covered are  theory and principles of static and rotary UPS systems   desi
56. MBP  MAINTEMANCE BYPASS SWITCH  CE   CIRCUIT BREAKER                Figure 2 2  SCR static switching transfer     3  Maintenance bypass circuit breaker  A bypass circuit breaker is provided to bypass the  complete UPS system when maintenance of the UPS system is required  The UPS bypass line  provides power continuity during UPS module malfunction periods  If the malfunction is such as  to require UPS maintenance  then the load must be shifted to a maintenance bypass line  as shown  on figure 2 5  An explanation as to why such a transfer is needed and the how such a transfer is  configured is basic to comprehending UPS maintenance procedures      a  Purpose of maintenance bypass switch  It is unsafe to work on an energized UPS  system  The complete system must be isolated from ac inputs  ac outputs  and the dc link  whenever maintenance requires that the cabinet doors be opened and or protective panels be  removed  There are lethal voltages present in UPS cabinetry  resulting from the ac power applied  to the converter or the dc power available from the battery  When energized  these circuits  provide high voltage  Any portions of the system providing a redundant path  such as more than  one UPS module or the static bypass  are tied together by the system logic so partial system  shutdown for maintenance is not acceptable  Shutting off the battery for maintenance and  running the UPS portion as a power conditioner should not be attempted since this also impacts  on the system
57. OR             Figure 2 30  Battery supported inertia system    e  Battery supported M G set  The battery supported M G system with a backup inverter is  shown in figure 2 31  It is made up of a synchronous M G set with the addition of a  rectifier inverter  batteries  and a static switch  During normal operation  the static switch is  conducting and 95 percent of the required power is supplied to the motor from the ac source  The  remaining 5 percent power is supplied through the rectifier inverter while the battery is float  charged  The inverter is kept operational at this low power level to ensure that it remains  operational and can supply full power in the event of degradation or loss of the ac source  Upon  loss of the ac source or deviation of its frequency and or voltage from acceptable limits required  to maintain the generator output  the static switch is automatically blocked and power is supplied  from the battery to the motor through the inverter  Upon restoration of the ac source  the static  switch automatically conducts and the system reverts to normal operation  This configuration  provides conditioned  isolated  and uninterrupted power  In addition  it has a higher reliability  and requires less maintenance than a comparable rotary system with a dc motor  DC machines in    general require more frequent maintenance due to wear in brushes and wear and pitting in the  commutator ring            STAHL BS     1         STATE SIGMAL f 4   ai  ray i   j al    eee 
58. Performing these activities keeps the UPS  in good working order and helps to prevent failures  Corrective maintenance is performed as a  result of a failure  Corrective maintenance fixes the problem and gets the unit working again   Maintenance is covered in chapter 5     TM 5 693    CHAPTER 2    PRINCIPLES AND CONFIGURATIONS OF UNINTERRUPTIBLE  POWER SUPPLY  UPS  SYSTEMS       2 1  Principles of static UPS systems    The basic static UPS system consists of a rectifier charger  inverter  static switch  and battery as  shown in figure 2 1  The rectifier receives the normal alternating current  ac  power supply   provides direct current  dc  power to the inverter  and charges the battery  The inverter converts  the dc power to ac power to supply the intended loads  The dc power will normally be provided  from the rectifier  and from the battery upon failure of the primary ac power source or the  rectifier  The inverter will supply the loads under normal conditions  In the event of the failure  of the inverter  the static switch transfers the load to an alternate ac source                                                                                      UPS UNIT       MANUAL  NORMA  RECTIFIER INVERTER   erate BYPASS           o LOAD  E k l   SWITCH       BATTERY  ALTERNATE  lt    AC SOURCE          Figure 2 1  Basic static UPS system    a  Normal operation  During normal operation  the rectifier converts the ac input power to dc  power with regulated voltage  The rectifier o
59. Standard defining the communication circuits between devices for synchronous and asynchronous  transmissions on the following types of lines  two wire  four wire  point to point  telephone lines   and local links with short cables  Though the standard covers only transmissions over distances  up to 15 meters  it is often possible to ensure correct transmission over greater distances using  high quality shielded cable in a reasonably satisfactory electrical environment  Most terminals  and devices on the market can implement this transmission standard     RS422A  Recommended standard RS422A    Standard RS232C is sufficient for transmissions in a normal environment  For transmissions in a  disturbed environment or over long distances  standard RS422A offers a differential operation  option  with a balanced voltage  ensuring far superior performance  What is more  it can be used  for multipoint links  with generally up to ten connection points  one sender and up to ten  receivers      RS485  recommended standard RS485    This standard is similar to RS422A except that the number of possible links is greater and up to  32 senders may be interconnected to as many receivers  This system is particularly designed for  local area networks     Safety Installation   Installation supplying electrical equipment which may have a direct effect on the safety of users  and must therefore remain energized even in the event of a main failure  In general   characteristics concerning the power sup
60. TM 5 693    TECHNICAL MANUAL    UNINTERRUPTIBLE POWER  SUPPLY SYSTEM SELECTION   INSTALLATION  AND  MAINTENANCE FOR COMMAND   CONTROL  COMMUNICATIONS   COMPUTER  INTELLIGENCE   SURVEILLANCE  AND  RECONNAISSANCE  C4ISR   FACILITIES          APPROVED FOR PUBLIC RELEASE  DISTRIBUTION IS UNLIMITED       HEADQUARTERS  DEPARTMENT OF THE ARMY  31 MAY 2002       TM 5 693    REPRODUCTION AUTHORIZATION RESTRICTIONS    This manual has been prepared by or for the Government and  except to  the extent indicated below  is public property and not subject to  copyright     Reprint or republication of this manual should include a credit  substantially     Department of the Army  TM 5 693  Uninterruptible  Power Supply System Selection  Installation  and Maintenance for  Command  Control  Communications  Computer  Intelligence   Surveillance  and Reconnaissance  C4ISR  Facilities  31 May 2002        Table 2 2  Harmonic currents present in input current to a typical  rectifier in per unit of the fundamental current reprinted with permission  from IEEE Std  519 1981    IEEE Guide for Harmonic Control and  Reactive Compensation of Static Power Converters     copyright    1981  by IEEE  The IEEE disclaims any responsibility of liability resulting  from the placement and use in the described manner     Table 3 1  IEEE table 3 2 reprinted with permission from IEEE Orange  Book     Emergency and Standby Power Systems for Industrial and  Commercial Applications    Copyright    1996  by IEEE  The IEEE 
61. Table 4 6  Motor engine corrective action       Engine Problem    Areas to Check       Will not start    Starter  Battery  and connections  Fuel system  level  pump  injectors   internal engine  valves  tappets  pistons   Ignition system  gas engines   Control system interlocks permissives          Poor Performance   Will not handle load       Fuel System and cleanliness  injectors or carburetor  internal engine   control and ignition system  System kW requirements       Table 4 7  Generator corrective action       Generator Problem    Areas to Check       No Output Voltage   Current    Check Stator and Rotor Continuity  Fluid diode pack  voltage regulator   Control System and interlocks       Generator Breakers will not close    Control Circuitry operation  Auto manual sync system  generator  control system       Generator will not pick up load or  stalls trips    Engine fuel and control system  generator voltage regulator  generator  control system  auto manual sync system  protective device settings       Generators don   t share load    Paralleling control system          Main switchgear breaker won   t re close on  diesel generator powered system       Generator sync system  breaker sync check relay  breaker control  circuitry        Table 4 8  Suggested test accessory list for battery maintenance          Item Disposition  Battery capacity test set Special  Battery conductance impedance tester Special  Battery lifter Special  Metering of dc  located on the rectifier cha
62. VRLA  batteries  The VRLA batteries are sealed with a  valve allowing venting on excessive internal pressure  These cells provide a means for  recombination of the internally generated oxygen and suppression of hydrogen gas evolution to  reduce the need for adding water  This design does not require the maintenance of checking the  specific gravity and adding electrolyte as does the flooded lead acid batteries  These batteries  have a lifetime of approximately 5 to 6 years  This is substantially shorter than the 20 year  lifetime of the flooded lead acid and the ni cad designs  These batteries would need to replaced 3  to 4 times to provide the same service of the flooded lead acid and ni cad designs  These units  sometimes experience failures called    sudden death failures    where deposits form on the plates  causing a short  This type of failure is difficult to detect and makes this battery less reliable than  the flooded lead acid design and the ni cad design  The VRLA batteries cost approximately half  of the price of the flooded lead acid batteries and one fourth of the price of the ni cad batteries   These units are well suited for UPS systems providing back up to computer systems because of  their low maintenance  low cost  and low emissions  For industrial applications requiring greater  reliability and longer life the flooded lead acid and ni cad designs are preferred      2  Ni cad batteries  Stationary ni cad batteries designed for emergency power  applications a
63. XAMPLE       The following example illustrates the use of the selection process described in this handbook   Please note that no one example can serve as the model or template for every possible case  Each  case in which an UPS is being selected for a specific facility is unique and the specifics of the  process will vary  All figures are for purposes of the example and should not be considered  indicative of actual costs     John Public  who will be the facility manager for the new Eastville plant  now in planning  of ABC   Inc   is selecting the UPS to be installed in the plant  With the aid of his engineering staff  Mr   Public has gone through each of the steps of the process  Following is a summary of how each  step was accomplished     1  Determine the need for UPS  Mr  Public knows that many of the electrical loads are critical  and even a lapse in power of 5 seconds could result in damage to very expensive processing  equipment and could lead to injuries to operators  He is also aware of governmental regulations  that require that lighting for evacuations and for other functions must be available in the event of  a loss of power  Clearly  an UPS is needed     2  Determine the purpose of UPS  Based on discussions with his engineers and production  personnel  the following purposes were identified for the UPS     e Power lighting for evacuation  security  and facilitate orderly shutdown    e Continue heating  ventilation  and air conditioning  HVAC  functions for select
64. ad acid batteries  A lead acid battery operated on a high   ripple current input at an elevated temperature can have its operating life reduced to one quarter  of what would normally be expected      5  Memory effect  Ni cad cells charged at very low rates are subject to a condition known  as a  memory effect   Shallow cycling repeated to approximately the same depth of discharge  leads to continual low rate charging  The result is a battery action which has reduced the  effective reserve time of the UPS system  An affected cell can have the memory effect erased by  providing a complete discharge followed by a full charge with constant current which breaks up  the crystalline growth on the plates     m  Effects of loads on static UPS systems  Linear loads present a constant load impedance to  the power source  This type of load results in a constant voltage drop  However  non linear loads  draw non sinusoidal current resulting in a non sinusoidal voltage drop  Non linear loads and  loads with high inrush current demand could adversely affect the static UPS system performance      1  Non linear loads  Non linear loads are loads whose current is not proportional to the  supply voltage such as loads with ferroresonant transformers or regulating transformers and solid   state power supplies  Non linear loads distort the inverter output voltage wave shape and cause  the output voltage to contain high harmonic content  This effect can be more pronounced in  inverters with high impe
65. an electrochemical  reaction  Usually defined as consisting of two or more cells  but commonly used to refer to one  cell     Battery  flooded cell   An electrolyte filled vented cell     Battery  recombination   Battery with a gas recombination rate at least equal to 95 percent  i e   no water need be added  over battery life  Usually called    maintenance free        Battery  tier mounted   Battery cell installation system whereby the cells are placed on tiers made of insulating material     Battery  vented cell   The battery cells are equipped with a filling port for distilled  demineralized water used to top up  the free electrolyte     Battery Cells  The interconnected battery elements that supply electrical power created by electrolytic reaction     Battery Circuit Breaker   see Circuit Breaker  battery      Battery Monitor   Battery monitoring and protection system developed and patented by MGE UPS SYSTEMS for  UPS systems  It incorporates software to calculate the real available backup time  predicts when  batteries need replacement  and is a protection system against excessive discharges     G 4    TM 5 693    Battery on Shelves  Battery cell installation system whereby the cells are placed on several vertically stacked shelves  or racks made of insulating material     BEM  Building and Energy Management  System   System used for control monitoring of all building utilities and systems  It is generally composed  of sensors  actuators  and programmable controllers con
66. an electrolyte   As the cell discharges  the active materials of both positive and negative electrodes are converted  to lead sulphate and the electrolyte produces water  On charge  the reverse action takes place  At  the end of the charging process  water electrolysis occurs producing hydrogen at the negative  electrode and oxygen at the positive electrode     2 20    TM 5 693     a  Lead acid design  The most common design of lead acid batteries is the lead   calcium cell construction where the active material for each electrode is prepared as a paste  spread onto a lead calcium alloy grid  The grid provides the electrical conductivity and structure  to hold the active materials  The resultant plates are soldered to connecting straps to form  positive and negative groups which are interleaved  Separators are placed between the plates and  the assembly is placed in a container or jar  These batteries can survive more short duration   shallow cycles than long duration  deep discharge cycles      b  Voltage  The nominal voltage of a lead acid cell is 2 volts while the open circuit  voltage is approximately 2 05 volts  A commonly used end or discharged voltage is 1 75 volts   However  lower end voltages are also possible  The electrolyte specific gravity with the cell fully  charged can range from a nominal 1 210 to 1 300 at a temperature of 25  C  77  F       c  Rate design  The batteries may be of the high rate  medium rate  or low rate  design  The high rate batteries are de
67. and expensive equipment are required  When highly skilled  personnel are required  the cost of maintenance increases  obviously  However  the consequences  go beyond the cost of actual repairs  Training costs also increase  Ideally  personnel will need  only low to moderate skills and a minimum of training  initial and recurring   Special  qualifications for UPS maintenance personnel can include fundamentals of electrical and  electronic design of UPSs  UPS testing and maintenance practices  specific maintenance training  on identical or similar equipment  UPS safety precautions  and facility specific procedures for  operation  surveillance  and maintenance  Economical support is also difficult to achieve if many  different pieces of expensive test equipment and tools are needed to support the UPS  Ideally  the  only tools required will be common hand tools normally found in a facility maintenance shop and  the number and cost of test equipment will be minimal     g  Determine if the selected UPS is maintainable  Maintenance determines much of the  operating cost of an UPS  Done correctly  maintenance can ensure that the UPS stays reliable   Poorly done  maintenance can compromise reliability and safety  A system may be inherently  maintainable  i e   good access  good diagnostics  etc    but other factors can determine whether or  not the system can be maintained  These factors include availability of trained personnel   availability of spares and parts  and location of repa
68. ange of temperatures of 5   to 40   C while operating  and  20   to 80   C while not  operating  However  when batteries are installed in the same room  a lower room temperature   approximately 77  F  is desirable  The need for a ventilation system should be determined on a  case by case basis  Consideration should be given to the load carrying capacity of the floor  where the rotary UPS is to be installed  Also  the availability of freight elevators with adequate  capacity for moving large systems in office buildings should be ensured      2  Battery and rack installation for rotary systems  Installation of rotary UPS system  batteries and racks is the same as the static UPS system batteries discussed in paragraph 4 1b 2      4 3  Power distribution and equipment grounding and shielding requirements    An UPS system  whether static or rotary  single phase or three phase  has a single output  The  UPS system  however  usually supplies a variety of loads  each of which should be independently  protected so that a fault on one circuit will not cause loss of all others     a  Power distribution equipment  There are three critical functions of a well designed UPS ac  distribution system  First  short circuit protection of all underground conductors  second   isolation of panel pull down during a branch fault  and third  isolation of the critical loads from  electrical noise coupled through the static bypass  The power distribution system will usually  consist of a panelboard  wit
69. ar 5 20years 150  Ni cad  flooded electrolyte 20 25 years 25 years 1 000 1 200           1  Voltage tapping  Sometimes the UPS system will require one dc voltage level while  electrical operation of circuit breakers will require another dc voltage level  Tapping off of the  higher voltage battery is not permitted  Unequal loads on the battery will reduce the battery s life  since it causes one portion of the battery to be undercharged while the other portion is  overcharged  Battery and UPS manufacturers both often indicate that such practices invalidate  their warranties      2  Cycling effects  A cycle service is defined as a battery discharge followed by a  complete recharge  A deep or full cycle discharge recharge consists of the removal and  replacement of 80 percent or more of the cell s design capacity  Cycling itself is the repeated  charge discharge actions of the battery  A momentary loss of power can transfer the UPS to the  battery system and impose a discharge on the battery for the time period needed by the UPS to  determine whether the ac power input has returned to acceptability  As we see an increase in  non linear loads  we may expect to see more frequent cycling  As indicated in table 2 1  the  ability of flooded lead acid batteries utilizing a lead antimony alloy to provide the greatest  number of full discharges  Ni cad batteries have a good cycle life  but their increased cost does  not encourage their use in large installations  Valve regulated batterie
70. ause loss of revenue     Ferroresonant  An interactive UPS configuration in which a ferroresonant transformer is used to magnetically  couple the ac input to the load     Field Effect Transistor  FET   A solid state device in which current is controlled between source and drain terminals by voltage  applied to a non conducting gate terminal     TM 5 693    Filter  phase shift    Filter used to reduce  if necessary  the overall distortion due to the current harmonics injected into  the mains upstream of an UPS by its rectifier charger  Filtering is superior to that of a traditional  filter of the L or C type     Float Charge   Commonly used for applications in which the battery is only infrequently discharged  charging  conducted with the charger  battery  and load in parallel  The charger operates off the normal  power supply     Float Current   see Current  float       Floating Voltage   see Voltage  float      Fourier Theorem   Theorem stating that any non sinusoidal periodic function  frequency f  may be represented as a  sum of terms  series  made up of a sinusoidal term with frequency f  called the fundamental  frequency  n sinusoidal terms with frequencies that are whole multiples of the fundamental  frequency   harmonics   and a possible dc component  Where n is a whole number  n   1  corresponds to the fundamental  n  gt  1 to the harmonic of the nth order     Gell Cell   Refers to a battery in which the electrolyte consists of a mixture of finely divided silica or sa
71. be connected to the positive terminal of the charger  As with the interconnections    4 13    TM 5 693    for all other equipment  the cables used should be megger tested as described in the paragraph 4   4 a      3  Inverter  The inverter is similar in construction to the charger  It converts dc power to  ac power using solid state electronics and should generally be tested using the same methods   Therefore  this device also should not be megger tested      4  Static switch  The inverter is similar in construction to the charger and inverter  It is  constructed of solid state electronics and should generally be tested using the same methods   Therefore  this device also should not be megger tested      5  Battery testing  The individual cell condition check includes visual inspection of cell  integrity investigating evidence of corrosion at terminals  connections  racks  or cabinet  The  general appearance and cleanliness of the battery  the battery rack or cabinet  and battery area  including accessibility should be observed  The cells should be checked for cracks in cell or  leakage of electrolyte as well as the integrity of the cover  Electrolyte should be added to any cell  in which the electrolyte level is below the top of the plates  If the battery cells are not delivered  filled  it is recommended that they be filled according to manufacturer    s recommendations before  installation on racks  Before installation  the voltage of each cell should be measured  The  vol
72. be exposed to the hazard  Also  the test procedures  used should be designed to ensure that no intentional damage to equipment will result from the  testing process  There are four categories of tests for electrical equipment  factory  acceptance   routine maintenance  and special maintenance  Factory tests are performed at the factory to prove  the equipment was manufactured properly and meets specific design parameters  Acceptance  tests are also proof tests performed on new equipment and systems usually after installation and  before energization  They are run to determine whether the equipment is in compliance with  specifications  to establish benchmarks for future tests  to determine the equipment was installed  without damage  and to verify whether the equipment meets its intended design operation and  limits  Routine and special maintenance tests are run after the equipment has been in service for a  certain amount of time to determine the degree of deterioration of certain equipment physical  parameters as operating time increases  Routine tests are performed on a periodic basis and  special tests are performed on defective equipment to help determine the cause of a failure and or  the extent of the damage  The same type of tests and measurements are performed for all of the  categories using different voltage values  The acceptance tests are usually run at 80 percent and  the maintenance tests are usually run at 60 percent of the factory test voltage values to help 
73. bed in paragraph 3 2 for determining a static UPS system rating  The maximum permissible  frequency deviation and required ride through time is required for sizing the flywheel inertia as will  be described in the following paragraph  The maximum permissible frequency deviation should  be the maximum deviation tolerated by the most sensitive load  The required ride through time depends    TM 5 693    largely on the nature of the power supply source  It should be longer than the longest momentary  interruption experienced or expected at the particular installation  The longest momentary interruption  time is usually the duration of reclosing operations on the power supply distribution feeders  In  addition  the nature and percentage of non linear loads should be determined  This is necessary  to insure that the system s level of voltage distortion when supplying such loads is acceptable     b  Motor and generator ratings  Motor and generator ratings and performance characteristics  are standardized by the National Electrical Manufacturers Association  NEMA  in ANSI NEMA  Publication MG 1  1978      1  Synchronous motors  The NEMA rating structure of continuous duty synchronous  motors is based on horsepower output  maximum ambient temperature for which motor is  designed  speed at full load  frequency  number of phases  voltage  full load current  field current   excitation voltage  power factor  and locked rotor  starting  KVA      2  Induction motors  The NEMA rating structu
74. calcium cells  In addition  the total float voltage  terminal voltage  will be different for a    5 7       TM 5 693    188 cell UPS battery than for a 192 cell UPS battery  since the number of cells varies even  though the voltage per cell may be the same  Another consideration is that the float voltage used  will vary with the nominal specific gravity of the cell     Table 5 5  Annual battery inspection          Check and record the overall float voltage at the battery terminals  not at the rectifier charger    Measure the pilot cell voltage   Make a visual cell and rack check as to general appearance  cleanliness  cracks in cells  electrolyte leakage  or evidence of corrosion   Check rectifier   Check rectifier charger output current and voltage   Check electrolyte levels   Check ambient temperature and condition of ventilating equipment   Check pilot cell voltage  specific gravity of flooded lead acid pilot cells  electrolyte temperature of flooded pilot cells r and terminal  temperatures of valve regulated pilot cells   Check all cell voltages  specific gravities of all flooded lead acid cells and all terminal temperatures of valve regulated batteries   Check total battery voltage    Check 10 percent of inter cell connection resistances chosen at random    Clean and provide corrosion protection of cells terminals  and racks  and add water to adjust electrolyte levels as necessary    Provide an equalizing charge if cells are unbalanced    Analyze records and report any re
75. ce  inter cell resistance   and load cycles  With the installation of one of these systems  system reliability will increase due  to the constant monitoring of the system  Also  maintenance cost will be reduced  by minimizing  the required maintenance man hours     e  Maintaining flooded lead acid cells  Visual checks  various measurements  and certain  tests are used to optimize the life and performance of battery systems  Visual checks will indicate  when cleaning is necessary or when there are other problems that need to be corrected   Measurements of voltage and specific gravity identify the condition of each cell  Battery capacity  tests and measurements are made of inter cell connection and terminal connection resistances are  made to determine the battery system s condition  Measurements and tests are often performed  on pilot cells instead of the entire battery     f  Maintenance considerations  Specifics of maintenance requirements will vary because of  the battery type  the construction  and the manufacturer s requirements  However  general    5 8       TM 5 693    maintenance considerations are the same  except that electrolyte levels and specific gravity  requirements do not apply to valve regulated batteries and specific gravity variations do not affect  the performance of ni cad cells  Maintenance of a battery begins at the time of the battery  installation  The tests and data taken at that time form the base set of values for the battery to  which all future da
76. cell  so that the higher the specific gravity  the  higher the minimum float voltage must be  This ensures sufficient charging current is available to  overcome the increased local action  Too high a float voltage will result in overcharging and  therefore reduce battery life  A slightly higher float voltage is sometimes selected to reduce or  even eliminate the need for periodic equalizing charges for maintenance purposes  Equalizing  voltages are normally limited by system design considerations when batteries are selected and  sized      b  Voltage records  Correction should be made for the electrolyte temperature and no  voltage readings should be taken within 72 hours of an equalizing charge  Voltages should also  be uniform rather than ragged  with minimum spread between the high and low readings   Measure the terminal voltage of a battery  at the battery terminals  Measurements at the rectifier  charger are not acceptable  since the voltage drop in the cables to the battery may result in low  voltage at the battery terminals  with resultant undercharging of the battery      7  Capacity tests  The only true indication of battery condition and capacity is a discharge  test  Stationary cells designed for float operation should have no more than two deep discharges  per year  and the duration of these tests  test setup  personnel requirements  etc   make frequent  testing impractical  One must also consider that the battery is not available to serve its load  during a capac
77. commendations    Provide a detailed visual inspection of each cell   Check all bolt connections per IEEE 450 or IEEE 1106 to see if retorquing is required and retorque to the manufacturer s  specifications as required    Check inter cell  inter tier  and battery terminal connection resistances    Check integrity of the battery racks    Record the AC ripple voltage going to the battery and ensure that the rectifier charger filtering circuits are maintaining a ripple  output that meets the battery manufacturers  requirements on both a continuous and intermittent  spikes  transients  basis         a  Battery system replacement  When a battery is replaced  the new battery often  continues to be maintained in the same manner as the old ones  However  the new battery may be  of a different alloy or nominal specific gravity or may contain a different number of cells   Maintenance personnel may not recognize the differences  which can lead to irreversible damage      b  Battery condition  Battery condition can be assessed based upon comparisons of  current data with past data  Data collected during maintenance must always be corrected to the  standard temperature reference so that meaningful comparisons between data can be made      3  Remote battery monitoring systems  Battery monitoring may be performed remotely  with the installation of a battery monitoring system  These systems are able to monitor overall  string voltage  cell voltages  ambient temperature  internal cell resistan
78. comparable static system and hence has a lower  failure rate  It has a low output impedance which makes its output voltage less susceptible to  harmonic distortion as may be caused by non linear loads      2  Disadvantages  While there are several advantages to the rotary UPS  it does have  some short comings  Some of them are that they operate at high sound levels unless equipped  with special silencing enclosures  They require more maintenance and long repair times  Also   they require special foundations  Their installation is more complex  They do not easily lend  themselves to future expansion  paralleling  or reconfiguration  Their performance requirements  and configurations are not commonly standardized  Fewer manufacturers produce rotary UPS  systems as compared to static UPS systems  The rotary UPS has a short backup time and requires  either a battery or backup diesel generator for longer backup power     2 3  Common static UPS system configurations    The building blocks of a static UPS system are rectifier charger  inverter  battery  and static switch   These building blocks can be assembled in many configurations as required to meet reliability and or  economic considerations  However  some specific configurations have been in common use and are  standardized in Institute of Electrical and Electronic Engineers  IEEE  446  The most common of these  configurations in ascending order of reliability are a non redundant system  a system with static bypass  switch  a 
79. ctor  or to a  ground rod driven into earth  The connection between the equipment enclosure and the ground  point should be as short as possible to achieve the maximum in noise reduction  particularly at the  higher frequencies      3  Single point grounding  In addition to grounding the system neutral to facilitate ground  fault isolation and grounding the equipment enclosures to avoid the hazard of electrical shocks   the grounding system should minimize the generation of unwanted noise  The generation of  unwanted noise can be minimized by equalizing the voltage to ground of all the system  components  This is done by establishing single point grounding  The single point grounding is  established by connecting the grounding conductors of all the system component enclosures to  the power source neutral grounding point as shown in figure 4 5  For the single point grounding  system to be effective  the equipment grounding conductors should be as short as possible  This  requires that the UPS system be located adjacent to or in the same room with the supplied  equipment  In installations where this cannot be accomplished and the UPS system is located  away from the loads  an isolation transformer should be used  The isolation transformer is  interposed between the UPS output and the loads and should be located in the same room with the  supplied loads  The isolation transformer grounded secondary neutral is used as the grounding  point to connect all the equipment grounding co
80. d  No ox id is a soft  wax based rust preventive lubricant  It contains a small amount of solvent for  ease of application with a brush  It is non drying and retains its properties indefinitely        Off Line Inverter   see Inverter     Off Line or Standby   An off line  or standby  UPS is switched on to power the load only when the primary power  source is lost or fails  The interval of time from when the utility power is lost and the UPS picks  up the load can range from 2 to 20 ms     On Line  An UPS that continuously powers the load from the inverter     TM 5 693    On Line Inverter   see Inverter     Output  rated   Apparent power Pn that the UPS can deliver under given load conditions  power factor   0 8      Overall Distortion   see Distortion  overall      Oversizing   Increasing the capacity of an UPS beyond that required to exactly meet the needed power  requirements  Oversizing allows an UPS to efficiently and effectively handle surges and provides  for growth in the power requirements     Overvoltage  Sudden increases in voltage on one or more phases of ac power caused by large changes in the  electrical load or from utility power switching     Parallel UPS Cubicle   see Cubicle  parallel UPS unit      Parallel UPS with Redundancy   see UPS  parallel with redundancy      Parallel UPS without Redundancy   see UPS  parallel without redundancy      Percent Load  Ratio between the power Pu drawn by the load and the rated output Pn of an UPS system  Pu Pn    Sometimes
81. d along  with the input circuit breaker  a thermal magnetic circuit breaker with ac contactor and indicating  lights at the generator output  and a dc contactor at the dc motor input in systems with a dc motor  and a backup battery  Relays to detect and alarm loss of ac input output and loss of dc input in  systems with a backup battery may also be provided  The control cabinets are normally designed  for front access  All components can be operated  inspected  or removed from the front of the  cabinet by opening a hinged door  Meters  indicating lights  control switches or pushbuttons  and  adjustment potentiometers may be located inside the cabinet or mounted on the hinged door  The  cabinet doors are provided with screened filtered openings for cooling  Cooling is normally by  natural convection  Enclosure mounted cabinets are normally designed to allow power and  control cables to enter from the top  Free standing cabinets are designed to allow the power and  control cables to enter from either the top or the bottom  In some designs the motor and generator    4 6    TM 5 693    are vertically mounted on a common vertical shaft to reduce the required floor space  Reducing  the floor space may also be accomplished by stacking the motor and generator and coupling their  horizontal shafts using pulleys and belts  Some designs are also available with a common motor  and generator in one rotor to optimize the machine size      2  Batteries and racks for rotary systems  Construc
82. d be obtained from the manufacturer  Note that the test discharge current  is equal to the rated discharge current divided by the temperature correction factor for the initial  electrolyte temperature  Set up a load and the necessary instrumentation to maintain the test  discharge rate determined above  Disconnect the charging source  connect the load to the battery   start the timing  and continue to maintain the selected discharge rate  If the charging source  cannot be disconnected  the current being drawn by the load has to be increased to compensate  for the current being supplied by the charging source to the battery  Read and record the  individual cell voltages and the battery terminal voltage  The readings should be taken while the  load is applied at the beginning and at the completion of the test and at specified intervals  There  should be a minimum of three sets of readings  Individual cell voltage readings should be taken  between respective posts of like polarity of adjacent cells so as to include the voltage drop of the  inter cell connectors  Maintain the discharge rate and record the elapsed time at the point when  the battery terminal voltage decreases to a value equal to the minimum average voltage per cell as  specified by the design of the installation times the number of cells      b  Capacity check  The capacity of the battery is checked using the following  equation     Percent capacity at the test rate at 25   C  77   F         t   x 100    Where  ta
83. d for UPS Determine Purpose for Determine Power  UPS Requirements    Select Type of UPS                       Is Availability of  Selected UPS Acceptable       Is Selected UPS  Maintainable    Is Selected UPS    Is Safety of Selected Affordable       UPS Acceptable                     Figure 3 1  Determine the general need for an UPS    a  Determine the general need for an UPS  The assessment process for determining the need  for a facility UPS is shown in figure 3 2  Determining the need for an UPS is mainly a matter of  evaluating the way in which a facility is used  as well as knowing whether local  state  or federal  laws mandate the incorporation of an UPS  The number of regulations mandating an alternate  power source to ensure safety of personnel and to prevent pollution of the environment continues  to increase  Consequently  enforcement agencies should be consulted to determine if an UPS is  mandated  They should also be consulted during design and installation to make sure that the  UPS is designed and installed in accordance with current applicable regulations     3 1       TM 5 693    i Is the  Is the facility facility used  inhabited at night         Are all areas lit  by day by ambient  lighting  1    Are critical  functions     involved    Are critical  functions   involved    s emergency  power required  by law   UPS probably not required  Is emergency   However  determine if periodic power required   maintenance or other   requirements dictate an UPS    UPS p
84. d is the most  reliable  This is shown through the following equations  The reliability where two of three units  are required to supply 100 percent of the needed power  is given by the following equation     3 8    TM 5 693    Ou    Iipui tpat    Relisbility  MTBF  is 3500 hours  Foran For the system to fail  ie  mo outpat   beth units   exponential distribution of failures  this is must fail  The probability of system failure is   equivalent to a fathure raie  A  of 002 fotlores  miven by  l t  l h Fort 1  the   every hour  The sysiem reliability is piven by probability of system failure 1 2992  The   at  Foris 1  Reliability   99200199 fysiem relbihty s ibeere        HON    Ra ati DIL       Figure 3 4  Redundancy improves system reliability    Reliability   R t    3e   2e        where  A is the failure rate of each unit and the units fail exponentially  t is the time over which the system must operate    The reliability where one of two units is needed to supply 100 percent of the power  the reliability is  given by the following equation     Reliability   R t    2e    e       Table 3 2 shows the reliability for various values of t and        Where f h is failures per hour and h is hours   Table 3 2  Comparison of reliability of parallel redundant and parallel configurations    CONFIGURATION  Parallel Redundant   1 of 2   2 of 3           TM 5 693    Redundancy is the duplication of elements in a system or installation for the purpose of  enhancing the reliability of the s
85. d on while SCRs 2 and 3 are off  a dc voltage appears across  the load with the polarity shown in figure 2 14a  After some time interval  if SCRs 1 and 4 are  turned off and SCRs 2 and 3 are turned on  a dc voltage appears across the load with opposite  polarity as shown in figure 2 14b  If SCRs 2 and 3 are allowed to conduct for the same time  interval as SCRs 1 and 4 and then turned off while SCRs 1 and 4 are turned on and the process is    2 14    TM 5 693    A  SCR   s 1 AND 4 CONDUCTING   B  SCR   s 2 AND 3 CONDUCTING    C  OUTPUT VOLTAGE WAVEFORM       Figure 2 14  Simple single phase inverter    repeated  an alternating voltage will appear across the load  The wave form of this alternating  voltage is as shown in figure 2 14c  Two points must be taken into consideration to make the  simple circuit in figure 2 14 of practical importance  As discussed before  once a SCR is turned  on it remains conducting until the current drops to nearly zero  In the circuit shown in figure 2   14  once the SCR is turned on  load current flows with magnitude larger than zero  Therefore   some external means are required to cause the current to drop to near zero in order to turn off the  SCR  Such means is called a commutating circuit  Generally  all inverters with SCRs require  commutation means and normally charged capacitors are used to effect the commutation process   However  when gate turn off  GTO  SCRs or power transistors are used  no commutation circuits  are required  GTO SCRs
86. d testing and repair equipment to do it independently  except for occasional  telephone consultations with the manufacturer s service group  They should have a complete  knowledge of the UPS system s operation  be able to order and install replacement components   and have completed the UPS manufacturer s advanced training course  Topics will expand on  those of the basic course and include corrective maintenance  testing and repair equipment   schematics analysis  flowcharts  troubleshooting charts  and printed circuit assembly repair     5 2  UPS battery maintenance    The basic component that differentiates an UPS system from a power conditioner is the battery   If the batteries fail before the backup generators come on line  the critical power goes down   Improperly installed  poorly maintained  and inadequately tested batteries are common  happenings  Only the fact that the backup generators are highly reliable and come on line in a  few seconds prevents many UPS battery banks from failing long before their rated design life   Maintenance costs and maintenance access generally are the greatest contributing factors to  poorly maintained battery systems     a  Maintenance costs  An UPS equipment installation cost will run  750 to  2500 per kVA   Annual maintenance cost will run 3 to 8 percent of the installed cost for a static UPS and 1 to 2  percent of the installed cost for a rotary UPS  An UPS battery per cell installed cost is about  10  with an annual maintenance cost
87. dance is commonly called the short circuit voltage because it is measured during a short   circuit test  shorted secondary winding subjected to a current set to In   For most common three   phase transformers  this value ranges between 3 and 6 percent     Transients   Disturbances to electrical power lasting less than one cycle  1 60  of a second for 60 cycle ac    Also referred to as voltage spikes  Can be caused by lightning strikes  sudden load shedding on  the primary power system  shutdown of equipment that was drawing an extremely large amount  of power  or a general rise in voltage on the primary power system after use by a large number of  consumers  Voltage spikes can blow fuses or trigger circuit breakers  destroy electronic circuitry   and corrupt stored data     Underwriters Laboratories  UL    UL is a non governmental  non profit certification organization in the United States in which not  only government authorities are represented  but also consumer groups     export    services   research  etc  Following certification  a product may bear the UL label     Uninterruptible Power Supply  UPS    An electrical device providing an interface between the mains power supply and sensitive loads   computer systems  instrumentation  etc    The UPS supplies sinusoidal ac power free of  disturbances and within strict amplitude and frequency tolerances  It is generally made up of a  rectifier charger and an inverter together with a battery for backup power in the event of a 
88. dance such as inverters with pulse width control technique and inverters  with a ferroresonant output transformer      2  Loads with high inrush current  Loads such as motors  transformers  incandescent  lamps  etc   draw a high initial current when energized  The high initial current for such loads  could be as high as 10 times the normal full load current  Therefore  loads with high inrush  current requirements should not be energized simultaneously otherwise the inverter may reach the  current limit point     n  Effect of static UPS system on power supply system  The battery charger within the static  UPS is a controlled rectifier which draws non sinusoidal currents from the power source  The ac  line current drawn is basically a square wave or a stepped wave depending on the charger design   This square or stepped wave can be analyzed into an equivalent sinusoidal wave of the power    2 25    TM 5 693    frequency  i e   the fundamental component  plus other sinusoidal waves of higher frequencies or  harmonics  These harmonic currents cause harmonic voltage drops in the power source  impedance  This results in power source voltage distortion and the flow of harmonic currents in  the power system components and loads  The degree of power source voltage distortion increases  with the static UPS system capacity as well as the power source equivalent impedance  The flow  of harmonic currents in the power system can cause resonance and additional losses and heating  in the pow
89. dicative of problems like  deterioration of insulation or dirty equipment  A test program will commence after completion of  installation and will usually include field inspection and installation checks  de energized  component testing  verify instrument and relay operation and calibration  visual check of all  wiring  continuity checking of control circuits  energized functional testing of control circuits   megger testing of power circuits  test of power circuit phasing  energizing of equipment  and  service testing  If problems are found during the testing  an analysis should be performed  and a  repair and retest should be performed that is approved by the manufacturer  engineer  and system  operator  Many of these initial tests will be repeated periodically as part of the system  maintenance program depending on the load conditions  duty cycle  environmental conditions   and the critical nature of the equipment  Because of this  the completeness and clarity of the test  reports is important as they supply baseline data for comparison with the results of the  maintenance tests  Many tests on electrical equipment involve the use of high voltages and  currents that are dangerous  both from the standpoint of being life hazards to personnel and  because they are capable of damaging or destroying the equipment under test  Adequate safety  rules should be instituted and practiced to prevent injury to personnel  both personnel who are  performing the tests and others who might 
90. ding ground loops  providing  electrostatic and electromagnetic shielding of signal circuits  and providing separation of circuits     4 4  Testing and start up    The purpose of electrical testing on systems and their components is two fold  The first is to  check the installation of the equipment and perform component and systems tests to ensure that   when energized  the system will function properly  The second is to develop a set of baseline test  results for comparison in future testing to identify equipment deterioration  The system should be  initially checked for damage  deterioration  and component failures using specific component    4 11    TM 5 693    checks  inspections  and tests defined by the equipment manufacturer  Then the interconnection  of the system components should be checked  using de energized and energized methods  to  verify the proper interconnection and operation of the components  including on off control   system process interlocks  and protective relaying functions  Once the above tests are complete   the system can be energized and operational tests and measurements should be performed  All  steps and results of the testing should be carefully documented for review and for use in the  future for comparison with the results of future tests  Many of the same component tests initially  run will be performed at regular intervals as part of a maintenance program  The new results will  be compared to the initial results  where variations may be in
91. dual harmonic frequency  distortions  UPS manufacturers typically guarantee that this distortion holds when the UPS  supplies linear loads  A UPS sized for the addition of future loads may be in trouble if the future  loads have high harmonic contents  All manufacturers of electronic equipment install line filters    2 26    TM 5 693    to meet the Federal Communications Commission s  FCC  requirements for radio frequency  limits  They do not necessarily provide them for reducing power line harmonics since this adds  to equipment costs  Electronic load induced distortion beyond the UPS limitations can be  deduced if adverse effects occur under maximum loads but not under lesser loads  As the UPS  impedance increases in relation to the lower loads  this may reduce the distortion to limits which  can be handled by the UPS  Experience has shown that while distortion in excess of the UPS  manufacturer s specified limits may not operate protective circuitry  such excess distortion will  probably result in increased heating and possible reduction in equipment life      2  Problems from harmonics  Harmonic voltages and currents resulting from non linear  loads have caused operating problems  equipment failures  and fires  Harmonics cause increased  heating  lower the power factor  change crest factors  increase zero crossing points  provide noise  feedback  and influence inductive and capacitive reactance  An understanding of harmonic  behavior helps to recognize actions which adver
92. due to operating the energized system at 100 percent  capacity as compared to operating each of the systems of a two parallel redundant configuration  at 50 percent capacity  Another advantage of this configuration over the redundant system is that  the two basic systems are not susceptible to a single failure        SYNCHROM ZING                                                    GAAL STATI  E  WITCH  LE  i   i E ALIER E k NVERTER  MORAL CHARGER  ac SOURCE T       BATTERY   g Loo  BLIERTMGTE _        C SOLE     z    a EAI TER L k ERTER    CHARGER  a  a    Pr  Sy MICHRIOMIZINIG  JERAI                Figure 2 26  Cold standby redundant static UPS system    e  Dual redundant system with static transfer switches  The configuration of the dual  redundant static UPS system with static transfer switches is shown in figure 2 27  Like the  redundant system configuration  it is made up of two normally energized 100 percent capacity  basic systems connected in parallel with one common battery  Each of the two basic systems is  synchronized to the alternate source  The static switch provided at the output of each system  serves the functions of a static interrupter as in the redundant system configuration  and a switch   Operation of this configuration is similar to the redundant system  In addition  upon loss of both  systems or deviation of the output voltage beyond acceptable limits  the static switches disconnect  the load from the inverters and connect it to the alternate source in
93. e no load test  perform a load test turning the generator off  and attaching an ammeter to the output  Turn on the generator and add load until generator rated  power is reached  Run the generator at full load for four hours  and check the temperature to  ensure the unit is not overheating     c  Visual and electrical wiring inspections  The termination of each cable  shown on the  cable block and wiring diagrams  should be checked to insure each conductor matches the wiring  and schematic diagrams  This is performed by yellow lining each connection from the schematic  to the wiring diagram  visually inspecting each connection for cable number  wire number color   and terminal  and checking point to point continuity or    ringing out    each wire from end to end  including grounds     d  Energizing and test of the UPS system  After installation and component testing  individual  components of the UPS system should be sequentially energized from the source through the  loads  As each item is energized  control functions  interlocks  and alarms should be checked for  proper operation  Voltage  phasing  and current measurements should be made at each step  See  figure 4 7      1  UPS  inverter static switch   Verify the UPS is operational through the rectifier battery  charger and battery  and verify the battery is charged and on float  Measure the float voltage   Verify the UPS bus incoming breaker is open  inverters A and B breakers are open  and the static  switch is switched
94. e utility breaker  close the diesel generator breaker  and  return to auto start mode  Verify the battery is on float and charging  and measure the current   Verify when the battery is fully charged and record time to charge     e  Test forms  Component and system test forms for the UPS  battery  UPS switchboard   motor  generator  UPS loading  utility trip  inverter transfer  and battery discharge test should be  completed for each component and the system     f  Possible failures and corrective actions  For general assistance in resolving equipment  failures of the UPS  tables 4 1 to 4 7 may be referenced  Specific troubleshooting guides of    equipment are provided by the manufacturer     Table 4 1  Circuit breaker corrective action                Circuit Breaker Problem Areas to Check  Breakers will not close trip Mechanical alignment  Interlocks  Relay and protective device settings and operation  Breaker trips inadvertently Ground on cable or system  Relay and protective device settings and operation  System overload          4 5  Test equipment    The amount of test equipment available should be appropriate to the amount of local use and  should meet safety requirements  The user in some cases may have had some control over the  amount of diagnostic and monitoring equipment  plus the special tools specified for UPS systems   In other cases  off the shelf equipment might have been installed  The maintenance personnel  may be primarily electrically oriented  Such personn
95. ead acid pilot cells  electrolyte temperature of flooded pilot cells r  and terminal temperatures of valve regulated pilot cells   Check for evidence of voltage leaks to ground   Check rectifier charger output current and voltage   Check electrolyte levels   Check ambient temperature and condition of ventilating equipment   Check pilot cell voltage  specific gravity of flooded lead acid pilot cells  electrolyte temperature of flooded pilot cells r  and terminal temperatures of valve regulated pilot cells   Check for evidence of voltage leaks to ground   Check all cell voltages  specific gravities of all flooded lead acid cells and all terminal temperatures of valve regulated  batteries   Check total battery voltage   Check 10 percent of inter cell connection resistances chosen at random   Clean and provide corrosion protection of cells terminals  and racks  and add water to adjust electrolyte levels as  necessary   Provide an equalizing charge if cells are unbalanced   Analyze records and report any recommendations        3  Special inspections  A special inspection should be made whenever a battery  experiences an abnormal condition  such as a severe discharge or overcharge  to assure that the  battery has not been damaged  This inspection should include all the quarterly tests     d  Maintenance procedures  Always follow the battery manufacturer s procedures and check  warranty requirements  Manufacturers will normally provide assistance in developing a  maintenance program
96. ector emitter has  low resistance  IGBTs have a greater tolerance to temperature fluctuations than the FETs  The  IGBTs have the drawback of saturation losses and switching losses like all of the other  transistors  These must be taken into consideration in the designing of the UPS  Overall  the  IGBT is more efficient and easier to control than the other power semiconductors     g  Rectification  Rectification is the conversion of ac power to dc power  Rectification is  accomplished by using unidirectional devices such as SCRs or IGBTs  Rectifiers can be built to  convert single phase or three phase ac power to controlled or uncontrolled dc power  Ina  controlled rectifier  the output de voltage can be continuously maintained at any desired level  whereas in an uncontrolled rectifier the output dc voltage  at no load  is a fixed ratio of the input  ac voltage  Moreover  the output dc voltage of an uncontrolled rectifier varies with the load level  due to voltage drops in the various circuit elements  Generally  single phase rectifiers may be  used in ratings up to 5 kilowatt  kW  whereas three phase rectifiers are used in higher ratings   When controlled de voltage is required  SCRs are normally used      1  Single phase uncontrolled rectifiers  The two most common configurations of single   phase uncontrolled rectifiers are the center tap full wave rectifier shown in figure 2 8 and the  single phase bridge rectifier shown in figure 2 9  In the center tap configuration  each
97. ed  equipment to facilitate orderly shutdown  Shutdown of the entire plant could take as  much as 2 3 hours    e Provide power to critical processing functions and controls until orderly shutdown  can be completed    e Continue fire protection in the event of a loss of power    e Provide communications  paging within plant      3  Determine the power requirements  Mr  Public   s engineers have calculated the total power  requirements for the UPS to be 1000 kVA  But Mr  Public is concerned about growth  He  decides to add a 12 5 percent    cushion    to allow for growth  The engineers endorse this approach  to cover overvoltages and other anomalies  So the total power required is 1250 kVA  At a power  factor of  80  this is equivalent to 1000 kilowatt  kW      4  Select the type of UPS  A diesel generator is selected for the UPS  Diesels start quickly   are reliable  can provide the needed power for as long as necessary  and are easy to maintain  The  UPS should be on line  Based on discussions with his staff  Mr  Public knows that an on line  system is the best choice for providing the maximum possible protection for critical loads  The  efficiency of the diesel generator is about 93 percent  Mr  Public was advised by his staff that a  high efficiency means less heat will be generated by the UPS  The result will be increased battery  life  higher reliability  and decreased cooling requirements     B 1    TM 5 693    5  Is safety of selected UPS acceptable  The diesel generato
98. ed as close as practical to the  battery to minimize the voltage drop in the battery leads  Personnel access should be limited to  the battery and charger inverter  The manufacturer   s instructions and National Electrical Code   NEC  instructions shall be consulted for access and arrangements  The UPS cabinets should not  be located directly adjacent to office space and work areas unless provided with acoustically  treated enclosures  Although the noise level of static UPS systems is low  the humming caused  by the electromagnetic components  transformers and reactors  may be irritating  Finally  since  the static UPS system causes power supply source voltage distortion  the effect of distortion on  other equipment supplied from the same bus as the UPS system should be taken into  consideration  To eliminate the effect of voltage distortion on other equipment  it is advisable to  supply larger UPS systems by a dedicated distribution transformer whenever possible  When the  use of a dedicated transformer is not feasible and a double ended substation is available  the loads  should be distributed between the two buses as shown in figure 4 3 to minimize the effect of  voltage distortion  By this arrangement  when the UPS goes to bypass  the loads are supplied  from a distortion free source through the transfer switch        Figure 4 1  Static UPS system 150 to 750 kVA  courtesy of Liebert      1  Charger inverter cabinets  The charger and inverter cabinet assemblies shall be  i
99. ed between the mains and the load  All  power drawn by the load passes via the inverter  This is the only configuration used for high  outputs     IP  protection index    see Protection index  IP      ISO 9000   Standard defining procedures and systems used to attain an internationally recognized level of  production quality  ISO 9000 certification is proof that the quality system effectively complies  with the standard  Certification is carried out by an official organization  AFAQ   unaffiliated  with either clients or suppliers or the company itself  and is valid for a three year period with  yearly audits and checks     G 9    TM 5 693    Kilo Volt Amperes  kVA   The product of the voltage and the amperes expressed in units of thousands  The resultant is total  system power     Kilowatt  kW   The product of the voltage and the amperes and the power factor expressed in units of thousands   The resultant is    real    system power     Life Cycle Cost  LCC    The total costs incurred in the acquisition  operation and maintenance  and disposal of an item   For an UPS  from a customer perspective  life cycle cost includes the purchase price  installation  costs  operating and support costs  and disposal costs     Line Interactive  An UPS configuration in which line power is fed directly into the load through a series inductor  or transformer     Load  linear   Load for which voltage form and current form are similar  Voltage and current are related by  Ohm   s law U t    Z x I
100. ed from the battery and other loads by a blocking diode  The  blocking diode allows current to flow from the battery to the inverter while blocking the flow of  current from the rectifier to the battery  Upon failure of the ac input power  the battery supplies  the inverter as discussed above        mito    BLH   SP SET ce T   TERTARER  LEGER             Figure 2 5  UPS maintenance bypass switching    f  Principles of rectifiers and inverters  UPS systems use power semiconductors in the  construction of the rectifiers  inverters  and static switches  These solid state devices control the  direction of power flow and switch on and off very rapidly allowing for the conversion of power  from ac to dc and dc to ac      1  Power semiconductor characteristics  A power semiconductor is an electronic device  consisting of two layers of silicon wafer with different impurities forming a junction made by  diffusion  The joining of these two wafers provides control of the current flow  Referring to  figure 2 6  the power semiconductor permits the current to flow in one direction from the anode  A to the cathode K  whenever the anode voltage is positive relative to the cathode  When the  anode voltage is negative relative to the cathode  the power diode blocks the flow of current from  the cathode to the anode  The power semiconductors may be either SCR or transistors  The types  of transistors are bipolar transistors  field effect transistors  FET   and insulated gate bipolar  transistor
101. ed load unbalance  capability  severe unbalance can result in overheating  The generator can supply a maximum  current of 6 to 7 times rated RMS current for a few cycles and 3 to 4 times rated RMS current for  a few seconds  The output voltage harmonic content is typically less than 5 percent      2  DC generators  Similar to dc motors  dc generators are classified as shunt excited   series excited  and compound excited  The relevant characteristics of dc generators are as  follows  The generator output is essentially ripple free power  The output voltage can be  precisely held at any desired value from zero to rated by controlling the excitation level  The  generator can be operated as a motor by applying dc power to its armature      3  Exciters  Exciters are used to create the magnetic field on the generator  They can be  broadly classified as static and rotary  In a static exciter all components are stationary and are  mounted outside of the machine frame  The synchronous machine field coils are connected to  commutator rings  and brushes are used to connect the field coils to the excitation power source   In a rotary exciter  some of the components are rotating and are mounted either on the  synchronous machine shaft or externally  Also  in a rotary exciter a commutator ring and brushes  may be required or the system may be brushless  Brushless type exciters are more commonly  used now due to their lower maintenance requirements  However  selection of the exciter type is
102. el may have had some training on UPS  systems maintenance at one time  In some cases  highly qualified electronically oriented  technicians may be available because of the need to service computer equipment  Because of the  variations in UPS equipment and maintenance capability  a hard and fast list of recommended    4 19       TM 5 693    tools and test equipment cannot be given  Some general guidance is provided covering use of  diagnostics  maintenance personnel  and ownership of equipment  Suggested checklists on  maintenance test equipment are advisory only     Table 4 2  Rectifier battery charger corrective action       Rectifier  Battery Charger Areas to Check       No output voltage  current Input voltage  breaker   Rectifier  SCR  and rectifier fuse  Input transformer   Control board       Low output voltage Dead input phase   Rectifier  SCR  and rectifier fuse  Voltage control settings or potential  Control board       High output voltage Input voltage high  Voltage control settings or potential  Control board       Output voltage not adjustable Voltage control potential  Control board       High output current System overload  short  Current limit setting  Control board          Low output current Current limit setting  Control board          Table 4 3  Battery corrective action          Battery Areas to Check   Low battery voltage  current  capacity Battery and cell connections  Electrolyte level  Cell voltage    Cell condition  cleanliness  and age  Float voltage
103. ended Practice for Monitoring Electric Power Quality   1995     IEEE 1184  Guide for the Selection and Sizing of Batteries for Uninterruptible Power Systems   1995     IEEE 1187  Recommended Practice for Installation Design and Installation of Valve Regulated Lead Acid   VRLA  Batteries for Stationary Applications   1996     IEEE 1188  Recommended Practice for Maintenance  Testing  and Replacement of Valve Regulated Lead   Acid  VRLA  Batteries for Stationary Applications   1996     IEEE 1189  Guide for the Selection of Valve Regulated Lead Acid  VRLA  Batteries for Stationary  Applications   1996     National Electrical Manufacturer   s Association  NEMA   2101 L Street  NW  Suite 300  Washington  DC 20037    NEMA PE 1  Uninterruptible Power Systems   1993     NEMA PE 5  Utility Type Battery Chargers   1986     National Fire Protection Association  NFPA   One Batterymarch Park  P  O  Box 9101  Quincy  MA 02269 9101    NFPA 70B  Recommended Practice for Electrical Equipment Maintenance   1996     NFPA 110  Emergency and Standby Power Systems   1996     A 3    TM 5 693    Other Publications    Baliga  B J   M S  Adler  R P  Love  P V  Gray  and N D  Zommer     The Insulated Gate Transistor  A New Three Terminal MOS Controlled Bipolar Power  Device     IEEE Transactions on Electronic Devices  Vol  ED 31  pp  821 828  1984    Blaabjerg  Fred  John K  Pedersen  and Ulrik Jaeger     Evaluation of Modern IGBT Modules for Hard Switched AC DC AC Converters     IEEE   October 1995  pp
104. ending problems  Operating personnel as well as maintenance personnel  should be made aware of the conditions which lead to problems and the clues which may point to  the beginning of troubles  Any time the environmental requirements are compromised there will  be a potential for damage  Maintenance personnel should be called to check equipment that has  not been kept clean  dry  tight  and friction free     e  Troubleshooting  Troubleshooting procedures covered by the user s manual address the  most common alarm conditions and assume that spare parts are available for replacement of  defective components  If following the procedure does not lead to the correction of an alarm  condition  contact the manufacturer s local service representative or field service office  Each  manufacturer has a particular system to guide the troubleshooter in the definition of a fault or the  action necessary to remove a fault condition  Fault free recognition systems or fault charts all list   yes  or  no  steps leading to some recommended action  Troubleshooting procedures may be  provided for problems such as overvoltage trip  undervoltage trip  battery discharge  battery  ground  battery undervoltage  clock failed  frequency failed  fuse cleared  inverter leg fuse blown   inverter overload  inverter rectifier overtemperature  logic failed  power supply failed  or rectifier  fuse blown  This guide is reproduced to illustrate the type and depth of information that must be  on hand prior to any
105. er control program  Maintain production   Prevent safety hazards from developing  Prevent out of tolerance products    Prevent personnel hazards  product or property damage  Lower insurance rates   Continue normal activities  Prevent loss of computer function    Prevent personnel hazards  product or property damage  Continue normal activities     Lower insurance rates  Comply with local  state  and federal codes  standards  and laws     Prevent loss of computer functions  Maintain normal operations and tests  Prevent  hazards   Prevent static electric charge and associated hazards  Continue normal production        Prevent loss due to freezing Maintenance of personnel efficiency  Continue normal    activities     Reduce health hazards  Comply with local  state  and federal codes  standards  and  laws  Reduce pollution   Reduce explosion hazard  Prevent property damage  Lower insurance rates  Comply  with local  state  and federal codes  standards  and laws  Lower hazard of fire  Reduce  hazards to personnel   Maintain personnel efficiency  Provide make up air in building    Provide purging operation to allow safe shutdown or startup  Reduce hazards to  personnel and property  Meet requirements of insurance company  Comply with local   state  and federal codes  standards  and laws               panujuod  SdQ uv fo asodind   y  suiuimisajap AOf D1431149 JDAIUIDH   T  QPL      69 S WL    s           Power Needed  For Purpose  Space Non critical  Conditioning ventilation   contin
106. er source s components and loads  Normally  a static UPS system does not have  detrimental effects on the power supply system  However  when the static UPS system capacity  is close to 20 percent of the supply system capacity  the harmonic effects should be analyzed    The effect of the UPS generated harmonics on the power source and other supplied equipment  can be minimized when necessary  The use of a 12   or more  pulse rectifier reduces the  harmonic currents generated  The harmonic currents present in input current to a typical rectifier  in per unit of the fundamental current are as shown in table 2 2  However  the rectifier number of  pulses is an equipment specific design parameter that is not normally specified by the user   Should the UPS generated harmonics become a problem and affect other loads supplied from the  same bus as the UPS  harmonic filters at the UPS input may be used  Harmonic filters filter out  the harmonic currents and minimize the voltage distortion and its effects on harmonic susceptible  equipment     Table 2 2  Harmonic currents present in input current to a typical rectifier in per unit of the fundamental  current          Converter Harmonic Order   Pulses 5 7 11 13 17 19 23 25  6 0 175 0 11 0 045 0 029 0 015 0 010 0 009 0 008  12 0 026 0 016 0 045 0 029 0 002 0 001 0 009 0 008  18 0 026 0 016 0 007 0 004 0 015 0 010 0 001 0 001  24 0 026 0 016 0 007 0 004 0 002 0 001 0 009 0 008          From IEEE Std 519 1981  Copyright    1981 IEEE  All ri
107. er switch total    TM 5 693    transfer time  normally 4 milliseconds  msec  or less  shall be less than the time the most critical  load can tolerate a loss of power     b  Grounding  The usual electrical power system utilizes two grounding methods  their  purposes are quite different  System grounding is the intentional grounding of the neutral point of  devices to provide equipment protection by suppressing transient and sustained overvoltages  caused by fault conditions  Equipment grounding is provided as protection against accidental  grounds by interconnecting a low impedance path from all noncurrent carrying metallic parts   thus minimizing potential gradients while ensuring sufficient fault current to trip protective  devices      1  System grounding  The neutral of a single phase  three wire system and of a three   phase four wire system should always be grounded  As explained in paragraph 4 3a 4   the  neutrals of the UPS and of the bypass source should be grounded and not the neutral bar in the  distribution panel board      2  Equipment grounding  For safety reasons  all electrical equipment enclosures   including metallic conduits  must be effectively grounded per the NEC  Although all raceways  and enclosures are bonded together to form a continuous ground path  grounding of enclosures to  the nearest ground point is recommended  The ground point may be a structural member which is  part of a bonded and grounded network of steel beams and columns  a ground condu
108. ercent capacity and for a three parallel system  each system  should be rated for 50 percent capacity  etc  In this configuration  all the parallel systems are  normally energized and share the load equally  It is also used where very high reliability is  required  Should one system fail  the remaining systems supply the load without interruption   installations  400 kVA and larger  where the load exceeds the rating of available systems  This  configuration is also commonly used in very large configuration is more costly than other  configurations to purchase and install  In addition  it has a lower overall efficiency since all the  parallel systems have to be operated continuously at part load where the efficiency is lower than  at full load  However  this configuration is desirable where very high reliability is essential and  the reliability of the ac power supply is questionable  It should be noted that C4ISR facilities  require a system reliability level of 99 9999 percent                F ETE k    NTESSUPT  4 HAGMZH  Hi   hah Al  z   j    i J Biwi z           E y li   j    HTESRUPT       P       SY NCHROMEING  F ni pn      a                      Figure 2 25  Redundant static UPS system    d  Cold standby redundant system  The cold standby redundant static UPS system  configuration is shown in figure 2 26  Itis made up of two basic systems with one common  battery  Each of the two basic systems is rated at 100 percent capacity  During normal operation  one system is de e
109. es when remaking the connection      c  Battery vent caps  Flame arrestor vent caps should be cleaned periodically by  thoroughly rinsing in clean  clear water  No solvents or detergents should be used      3  Pilot cells for voltage and specific gravity measurements  One or more pilot cells may  be chosen to reduce the time necessary to perform inspections and tests while still affording the  user some degree of confidence in the battery s condition  One cell per rack section should be  chosen so that all levels are represented  otherwise  the selection is arbitrary  Some users select  pilot cells after complete sets of quarterly voltages and specific gravities are taken  Criteria for  selection include cells with the lowest specific gravity  lowest voltage  highest specific gravity   highest voltage  or combinations of both  Pilot cells should be rotated periodically  usually on a  quarterly basis  One reason for this is to limit electrolyte loss  Whenever a cell s specific gravity  is read  some small amount of electrolyte will remain in the hydrometer after the electrolyte  which was removed from the cell for the specific gravity reading is again returned to the cell  For  the more frequently read pilot cell  this loss of electrolyte  although very small  could ultimately  affect the cell over a long period of time  which is the reason for pilot cell rotation      4  Temperature readings  Electrolyte temperatures should be read and be recorded any  time specific gravity o
110. f a load supplied with ac power at a given frequency     TM 5 693    Cos phil  A measure of the phase shift between the fundamental current wave and the fundamental voltage  wave observed at the terminals of a non linear load      Crest Factor  Fc   Ratio between the peak current value to the root mean square  RMS  current value     Cubicle  parallel UPS unit   Cubicle containing a rectifier charger and an inverter  It is connected to one or several other  identical cubicles and a bypass cubicle to make up a parallel UPS     Cubicle  single UPS unit   Cubicle containing a rectifier charger  an inverter  and a bypass  Connected to a battery  it  operates alone  forming a single UPS  Compare with cubicle  parallel UPS unit      Current  float   DC current that maintains the battery at nominal charge  corresponding the float voltage  This  current compensates open circuit losses     Current  inrush    Temporary current observed in a network when electrical devices are energized  generally due to  the magnetic circuits of the devices  The effect is measured by the current   s maximum peak  value and the RMS current value it generates     Current Harmonics   see Harmonics  current and voltage      Current Loop  20 mA    Transmission system used on certain devices and offering better performance than the RS232C   It provides a high degree of immunity to interference and is easy to implement  but has not been  standardized     Cycle  A battery discharge followed by a complete rechar
111. g  or cracking of plates  Shining a light source on the plates  may detect sulphation by reflections from any sulphate crystals on the plate edges  If visible   inspect the connections between the plates  straps  i e   bus bar connecting the plates to the post    and posts for obvious abnormalities  In areas of high seismic activity  this connection sometimes  fails if acceptance seismic testing was not properly performed  Check for electrolyte spillage   evidence of corrosion  and vent cap damage  and correct any problems  Examine cables  connecting the battery to the rectifier charger and those cables used as inter cell or inter tier  connectors to be sure they are putting no strain on the cell posts      b  Excessive gassing  Although gassing on recharge is normal  excessive gassing can  indicate overcharging  so gassing should always be noted  Lead acid batteries begin to gas when  cell voltage reaches approximately 2 30 volts  Outgassing  when a cell is on open circuit or on  float charge  may be an indication of high local action and undercharging  The gas coming from  the negative plate is not generated but is squeezed out of the expanding active plate material by  the sulphate formed as the cell discharges  Most local action takes place at the negative plates   and the positive plates may remain well charged  The specific gravity drop will not be as great as  for uniformly discharged positive and negative plates  and so using specific gravity readings may  not detect 
112. g emergency  Continue normal  activities  Maintain security    Locate responsible persons concerned with power outage  Provide evacuation    instructions  Prevent panic            P3AI  SI SSH IV HAHI 9661    MSHAdOD yoog esueiQ AAAI   panuyuor  SqjQ uv fo sasodind   y  Sumumuajap AOf D14INAI JOAIUAH   T F AQDI      69 S NL    TM 5 693    to assist in determining the purposes of a backup power system  diesel generator  UPS  or  combination of diesel may vary  Note that the terms emergency power and standby power are used in  the table  An emergency power system can be defined as an independent reserve source of electric  energy that  upon failure of the primary source  automatically provides reliable electric power within a  specified time to critical devices and equipment which  if they fail to operate satisfactorily  would  jeopardize the health and safety of personnel  result in property damage  or cause loss of revenue  A  standby power system is an independent reserve source of electric energy that  upon failure or outage of  the prime source  provides electric power of acceptable quality so that the user   s facility ies  may  continue operation in a satisfactory manner     c  Determine the power requirements  After determining the specific purpose s  for an UPS   the next step is to determine the facility power requirements  This task is often laborious but is  essential because it sets the stage for the remainder of the selection process  Undefined power  requirements
113. ge  A deep  or full  cycle is described as the  removal and replacement of 80 percent or more of the cell   s design capacity     Cycling  The repeated charge discharge cycle of a storage battery  Some batteries are rated by their ability  to withstand repeated  deep discharge cycles     Diagnostics  Manual  automated  and semi automatic methods and procedures for identifying and isolating a  failure in an item     Discharge Rate  The rate at which a cell or battery delivers current  e g   200 amperes over 10 hours is a rate of 20    amperes per hour      Distortion  individual   Ratio between the RMS value of an nth order harmonic and the RMS value of the fundamental     G 6    TM 5 693    Distortion  total    Ratio between the RMS value of all harmonics of a non sinusoidal alternating periodic value and  that of the fundamental  This value may also be expressed as a function of the individual  distortion of each harmonic   Hn   Yn  Y1     Earthing System  System for the interconnection and earthing of exposed conductive parts and neutral  There are  three types of neutral systems  IT  TN  TT     Earthing System IT   Earthing system in which the neutral is isolated from the earth or connected to the earth via a high  impedance and the various exposed conductive parts are connected to the earth via individual  earthing circuits  An alarm must signal the appearance of a first insulation fault  The installation  must be de energized immediately in the event of a second insulati
114. ghts reserved      1  Magnitude of harmonic effects  Systems with low impedances such as a large power  system will be less sensitive to the harmonic distortion from the non linear UPS load than an  engine generator source whose rating is close to that of the UPS  Sources with a high impedance  in relation to the load are known as  soft  power sources when they are unable to absorb the  generated distortion of their critical load  that is  the source voltage waveform can be greatly  deformed by the critical load waveform  It is difficult for the UPS to attenuate load produced  noise  A very noisy or extremely non linear load may reflect current distortions via the UPS  input onto the source  Any interposed soft source may interact with this load to increase rather  than reduce critical load power disturbances  So non linear loads on the UPS can actually distort  the  clean  power the UPS is designed to provide by their load induced current harmonics  Most  UPSs provide an input current distortion which meets or is less than the Information Technology  Industry Council  ITIC   formerly called Computer Business Equipment Manufacturers  Association  CBEMA   recommendations  To maintain required power quality to other loads  served by the UPS source  ITIC advocates an input having a total reflected current harmonic  distortion  THD  of 5 percent or less of line to line distortion with a maximum of 3 percent for  any one harmonic order  Total distortion is the vector sum of indivi
115. gn and selection of UPS  installation and testing of UPS  maintenance and operation of UPS  systems  principles of static and rotary UPS  UPS system rating and sizing selection   operations maintenance  batteries  troubleshooting  harmonic distortions  grounding  checklists   and acceptance testing     1 3  References    A complete list of references is contained in appendix A  The design  installation  and  maintenance of UPS systems should follow the latest industry and commercial codes and  standards as detailed in the references     1 4  Principles and configurations    An UPS system is an alternate or backup source of power with the electric utility company being  the primary source  The UPS provides protection of load against line frequency variations   elimination of power line noise and voltage transients  voltage regulation  and uninterruptible  power for critical loads during failures of normal utility source  An UPS can be considered a  source of standby power or emergency power depending on the nature of the critical loads  The  amount of power that the UPS must supply also depends on these specific needs  These needs  can include emergency lighting for evacuation  emergency perimeter lighting for security  orderly  shut down of manufacturing or computer operations  continued operation of life support or  critical medical equipment  safe operation of equipment during sags and brownouts  and a  combination of the preceding needs     a  Static UPS  A static UPS is a
116. h circuit breakers or fuses to protect the individual branch circuit  conductors which will usually be run in conduits dedicated to these uninterruptible circuits      1  Panelboards  A panelboard consists of a sheet steel housing containing a set of bus  bars  enclosed in a molded insulated housing  which also provides mounting for the branch circuit  protective devices  A single phase UPS will require two bus bars while a three phase UPS will  require three  A neutral bar  insulated from the enclosure but otherwise bare  will be provided in    4 7    TM 5 693    both single phase and three phase boards  A front panel  usually screwed to the enclosure   contains a door for access to the protective devices while completely enclosing the wiring and  terminals      2  Circuit breakers  Molded case circuit breakers are either plugged into or bolted onto  auxiliary bus bars attached at right angles to the main bus bars  Circuit breakers may be single   pole or two pole in single phase boards  three phase boards may in addition contain three pole  breakers  Manual switching as well as automatic overcurrent tripping of the various branch  circuits is provided by the circuit breaker  which disconnects all ungrounded circuit conductors  simultaneously      3  Fused switches  As an alternative to circuit breakers  fused switches may be used  The  switch provides for manual control and the fuse provides automatic overcurrent protection   Switches may have one  two  or three poles as wi
117. hall be capable of supplying the load inrush demand without voltage and  frequency deviations beyond the required tolerances  The inertia driven ride through  configuration should be considered at sites where the power distribution system has a high  reliability and long duration interruptions are not frequently experienced  The battery supported  inertia configuration should be considered at sites with frequent long duration power  interruptions  The battery protection time shall not be less than one minute and shall not exceed  the maximum time the load can be operated with the loss of the environmental support  equipment     3 20    TM 5 693    CHAPTER 4    INSTALLATION AND TESTING OF UNINTERRUPTIBLE POWER  SUPPLY  UPS  SYSTEMS       4 1    Construction and installation of static UPS systems  The construction and installation of the UPS are critical to its proper operation     a  Construction features of static systems  There are several construction features about the  UPS that contribute to the system as a whole      1  Charger inverter  In addition to the basic components of the charger inverter  an input  transformer is normally connected at the charger for isolating the charger components from the  power source  Also  surge suppression devices are used at the input to protect the charger  components from high transient voltages  Various protective and control devices may be used on  static UPS systems including a thermal magnetic circuit breaker at the system alternat
118. he battery following discharge  In stationary applications such as static UPS  systems  the battery is continually connected to the charger and the load and the battery is float  charged  During float charging the battery charger maintains a constant dc voltage that feeds  enough current through the battery cells  while supplying the continuous load  to replenish local  losses and to replace discharge losses taken by load pulses exceeding the charger s current rating   Periodically the charger voltage is set at a level 10 percent higher than the floating voltage to  restore equal state of charge at the individual  lead acid  cells  This mode of charging is called     equalizing charge    and the charger voltage level during this mode is the equalizing voltage   Following the battery discharge  the charger is set at the equalizing voltage to recharge the  battery  The charger is set at this higher voltage to drive a higher charging current to recharge the  battery in a reasonably short time and to restore it to the fully charged state  Although a periodic    2 22    TM 5 693    equalizing charge is not required for equalizing ni cad cells  a charger with float equalize mode is  required  At the floating voltage level  the ni cad cell cannot be charged over 85 percent of its  full capacity  Therefore  the equalizing voltage level is required to fully recharge the cell after  successive discharges     l  Service life influences  Service life as reported by battery manufacturers 
119. he rectifier charger        Measure the pilot cell voltage          Make a visual cell and rack check as to general appearance  cleanliness  cracks in cells  electrolyte leakage  or evidence of corrosion        Table 5 3  Monthly battery inspection          Check and record the overall float voltage at the battery terminals  not at the rectifier charger    Measure the pilot cell voltage   Make a visual cell and rack check as to general appearance  cleanliness  cracks in cells  electrolyte leakage  or evidence of corrosion   Check rectifier   Check rectifier charger output current and voltage   Check electrolyte levels   Check ambient temperature and condition of ventilating equipment   Check pilot cell voltage  specific gravity of flooded lead acid pilot cells  electrolyte temperature of flooded pilot cells r and terminal  temperatures of valve regulated pilot cells   Check for evidence of voltage leaks to ground       5 6          TM 5 693    Table 5 4  Quarterly battery inspection          Check and record the overall float voltage at the battery terminals  not at the rectifier charger    Measure the pilot cell voltage   Make a visual cell and rack check as to general appearance  cleanliness  cracks in cell  electrolyte leakage  or evidence  of corrosion    Check rectifier   Check rectifier charger output current and voltage   Check electrolyte levels   Check ambient temperature and condition of ventilating equipment   Check pilot cell voltage  specific gravity of flooded l
120. hile moving cells  consult the manufacturer for recommended action  Vibration  occurring as a cell is moved will tend to free hydrogen bubbles attached to the plates and the loss  of these bubbles will cause a decrease in the electrolyte level  Once the cell is installed  the  bubbles will reappear  and the electrolyte level will increase  Never add acid  or alkali  to a cell   nor add any additive which claims to rejuvenate cells      e  Vibration  Check the surface of the electrolyte for indication of any battery  vibration  Battery life will be reduced in proportion to the length of time and action of any severe  systematic vibration  Excess sediment when there is no apparent reason for that sediment  such  as the battery has not experienced overcharging or undercharging  can indicate recurrent  vibration  Where signs indicate vibration  reexamine the battery supporting restraining system  and eliminate this source of damaging activity      f  Hydration  Overdischarge of a lead acid battery without immediate recharge can  cause hydration  This could happen if the rectifier charger is shut down or if a lead acid battery is  kept in storage for an extended period without recharging  The cell must be replaced if  irreversible damage is indicated  for example  by a whitish  bathtub ring  visible approximately  halfway up a clear jar  The lead and lead compounds in the cell dissolve in the water released on  overdischarge and form lead hydrate which is deposited on the separato
121. hould be determined by  measuring the current with all equipment operating  In three phase installations  the load current  should be measured at each phase  The load kVA can then be estimated as follows     Table 3 4  Typical rectifier charger ratings          a  Input  Voltage    Frequency   Power Factor  typical   b  Output  Nominal Voltage       208  220  240  380  415  or 480 V    10   3 phase    120 220 V    10   Iphase   50 or 60 Hz    0 5    0 8    110 VDC  220 VDC nominal  130VDC  260 VDC nominal   5  adjustment             Equalize Voltage 140 VDC  280 VDC   5  adjustment  Ripple Voltage  lt 2  RMS with batteries  Equalize Timer 1 100 hours  manual start  auto reset  Capacity Sized to recharge the battery in 8 to 10 hours  Table 3 5  Typical inverter ratings   a  Input   Voltage  range  120  220 V   20   b  Output   Voltage 120 V  single phase 280 V or 480 V  3 phase     Voltage Regulation    Sync range  Load Power factor  Transient Recovery    Harmonic Distortion  Frequency    Overload Capacity  Crest factor    3 or 4 wire            2  for balanced load     3  for 100  unbalanced loads  3 phase only    0 5 Hz   0 8 to 1 0     3  within 10 milliseconds     1  within 30 milliseconds   3  maximum single harmonic   5  THD maximum up to crest factor 2  3  THD maximum for linear loads   50 or 60 Hz  0 1    500  for 1 cycle  120  continuous  3 1 at full load       Table 3 6  Typical static switch ratings          Transfer Time  Overcurrent Transfer  Overload Capacity    
122. ich can differ from the room  ambient  Optimum battery performance is obtained when electrolyte temperature is maintained at  TTF      5  Specific gravity readings  Specific gravity is a good indication of state of charge of  lead acid cells  Corrections for electrolyte temperature and level must be applied to adjust the  specific gravity readings to a standard reference temperature  Level corrections can vary for each  cell type and should be obtained from the manufacturer  Note that specific gravity readings  should not be taken within 72 hours of the termination of an equalizing charge or a water  addition  Specific gravity readings can be inaccurate where the water addition has not been  properly mixed with the existing electrolyte solution and stratification occurs      a  Differences in specific gravity  Lead antimony or lead calcium batteries do not  always have the same nominal specific gravities even if the plate alloy is the same  Maintenance  personnel should be alerted when a battery replacement provides a different specific gravity  requirement  New high performance stationary cells for UPS service may have nominal specific  gravities as high as 1 300  In similar cells  higher specific gravities mean higher float voltage  requirements  increased local action  and higher water consumption  Some application  considerations may also cause a manufacturer to vary the nominal 1 215 specific gravity for  stationary cells  High or low ambient temperatures are not usually
123. ied when specifying UPS systems  Either type may be used provided it meets the  performance requirements      a  Pulse width control  To illustrate this technique  the circuit in figure 2 14 is  redrawn in figure 2 15  Referring to this figure  when each of the two SCR pairs  1  4 and 2  3  is  gated for a time interval equal to a half cycle without the two pairs conducting simultaneously   the output voltage waveform is as in figure 2 15b  If the gating of SCR pair 2  3 is retarded by a       Figure 2 15  Voltage control using pulse width control    quarter of a cycle  the output voltage waveform is as in figure 2 15c  Therefore  the inverter  output voltage can be continuously adjusted by retarding the firing signal of one pair of SCRs  with respect to the other  The magnitude of the fundamental component of the output voltage  depends on the pulse width and is higher for a wider pulse  The maximum output voltage is    2 16    TM 5 693    obtained with no retard  zero voltage is obtained when the firing signal is retarded by a half cycle   The voltage control is accomplished by a feedback control loop which senses the output voltage  and adjusts the SCRs  firing angles to increase or reduce the output voltage level  With the pulse  width control technique  the output voltage harmonic content is high and a harmonic filtering  means is required      b  PWM  In this technique  the inverter SCR pairs are switched on and off many  times every half cycle to provide a train of pul
124. igures 2 10 and 2   11 respectively  Comparison of the output voltage and output current wave shapes indicates that  the bridge rectifier output wave shape contains six pulses while the wave shape for the single way  rectifier contains three pulses  This makes the ripple content of the bridge rectifier output less  than that of the single way rectifier  Another important difference is that the required transformer  kVA in the single way configuration is approximately 1 5 times that in the bridge configuration  for the same kW output due to the low power factor of the single way configuration  Normally  three phase rectifiers are used in ratings higher than 5 kW although it may also be used in lower ratings   The bridge rectifier configuration is commonly used in high power applications while the single way  configuration is mostly used in lower ratings  Generally  the selection of one configuration or another is  up to the equipment designer and is based on cost considerations     TM 5 693          i an te     2 1p2    ae aE    E    0 r 2r 0 7 2r  RESISTIVE LOAD 5 INDUCTIVE LOAD             Figure 2 8  Center tap full wave uncontrolled rectifier     3  Controlled rectifiers  In applications where a continuously adjustable dc voltage is  desired  controlled rectifiers are used  Controlled rectifiers like the uncontrolled rectifiers can be  single phase or three phase  The controlled rectifier configurations are identical to the  uncontrolled rectifiers  however  in order to co
125. il prime power restored  Indefinite until evaluated   normally for time for  orderly shutdown  or until  prime power restored    Until prime power restored    Until prime power restored    Indefinite until evaluated    Until prime power restored  or until orderly shutdown    Until prime power restored    1 min or until prime power  restored   1 min or until prime power  restored   Until prime power restored    Until prime power restored  Until prime power restored  Until prime power restored  or orderly shut down   Until prime power restored    or orderly shutdown    Until prime power restored  Until prime power restored       or orderly shutdown    Type of Auxiliary Power       Justification for UPS  Maintain boiler operation  Provide venting and purging of gas fired units    Maintain  cooling and heating functions for buildings and production     Prevent loss of sales and profit  Prevent spoilage of in process preparation   Prevent in process production damage  Prevent property damage  Continue production   Prevent payment to workers during no production  Lower insurance rates    Prevent equipment or product damage     Prevent loss of stored material     Prevent loss of stored material   Lower insurance rates     Prevent product and equipment damage  Continue normal production  Reduce payment  to workers on guaranteed wages during nonproductive period  Lower insurance rates   Prevent prolonged shutdown due to non orderly shutdown   Prevent loss of machine and process comput
126. ill cost  250 000  So the total acquisition cost is  310 000  Operating and  maintenance costs are estimated by Mr  Public   s staff to be  30 000 over 15 years  This estimate  is based on an MTBM of 200 hours  fuel consumption of 70 gallons per hour  labor costs of  25  per hour  and a conservative forecast of 20 operating hours per year  All figures are in constant  calendar year 1998 dollars  Of the total budget for constructing and outfitting the new plant    350 000 was allocated for the UPS  therefore  the total acquisition cost is acceptable  Mr  Public  knows that similar plants within ABC  Inc   spent about  25 000 last year on all maintenance  He  estimates that maintenance for the new plant  excluding the UPS  will take about  22 500 per  year  That would mean the total cost per year with the UPS operating and maintenance costs  included would be about  24 500  Disposal costs are considered negligible  since some of the  costs can be recouped through sale of the UPS for parts and scrap  Mr  Public is concerned about  the estimate because it only has  500 of    wiggle room     He decides to a look at an alternate  UPS  Back to step 4     B 2    TM 5 693    GLOSSARY       Section I  Abbreviations    ac  Alternating Current    AGM  Absorbed  or Absorptive  glass mat    ANSI  American National Standards Institute    C4ISR   Uninterruptible Power Supply System Selection  Installation  and Maintenance for Command   Control  Communications  Computer  Intelligence  Surveil
127. ilovolts  kV  plus 1 megohm for the stator winding  for example  5 16 megohms for 4 16 kV  winding  and 1 megohm for the rotor winding  While this is a guideline  the manufacturer s test  manual shall include acceptance criteria for the test  Megger test are    go no go    tests      c  Motor polarization index test  The polarization index test is an insulation    resistance test that lasts for 10 minutes  The insulation resistance is recorded after 1 minute  then  again after 10 minutes  The polarization index is the quotient of the 10 minute and 1 minute    4 15    TM 5 693    readings  After insulation resistance readings have been made  the test voltage is returned to zero  and the insulation is discharged      d  Motor overpotential testing  Hi Pot   This test assesses the dielectric strength of  the insulation of a generator  The dc over potential test is performed by applying a voltage and  measuring the leakage current  The voltage applied during the acceptance test is a function of the  equipment voltage rating as shown by the following equation     de acceptance test voltage    2 x E  1  x 1 7 x 0 75 kV  where E is the rated voltage in kV    The standard duration of the test is between 1 to 5 minutes  The dc acceptance test voltage is  applied to each winding separately with the other windings grounded  The voltage is applied in  steps  First  one third of the dc acceptance test voltage is applied  Leakage current readings are  taken at 1 minute intervals for a maxi
128. in figure 2 28 except for replacing  the synchronous motor with an induction motor  In this configuration  the induction motor must  be with low slip characteristics   typically less than 0 5 percent slip  With 0 5 percent slip  characteristic  the generator output frequency  for a 60 Hz system  can vary from 59 7 Hz at rated  load to near 60 Hz at no load  This configuration has the same limitation as the configuration  with a synchronous motor  In addition  it is mostly suitable for supplying loads with higher  tolerance to frequency variations  However  due to the lower cost of an induction motor as  compared to a comparable synchronous motor  this configuration is less costly     2 37    TM 5 693       FLYWHEEL  Fa wN Fa x  AC l N at  SOURCE                     G joto D  MOTOR GENERATOR             Figure 2 28  Inertia driven ride through system with a synchronous motor    c  Inertia driven ride through system with an induction motor and an eddy current clutch   This configuration shown in figure 2 29 consists of an induction motor which drives a flywheel  and an eddy current clutch at a speed essentially proportional to the supply frequency  The  generator rotates at a constant speed lower than the motor speed by controlling the slip of the  eddy current clutch  The generator output frequency can be maintained at 60 hertz  0 25 hertz   On loss of the ac input power  the generator receives energy stored in the flywheel  As the  flywheel slows down  the slip of the eddy cu
129. ing an UPS    The process for selecting an UPS consists of eight steps  These steps are  determining the need  for an UPS  determining the purpose s  of the UPS  determining the power requirements   selecting the type of UPS  determining if the safety of the selected UPS is acceptable   determining if the availability of the selected UPS is acceptable  determining if the selected UPS  is maintainable  and determining if the selected UPS is affordable  The last four steps may  require repeating if the UPS does not meet all of the requirements  This process does not and  cannot provide a    cookbook solution     Each facility has unique requirements for emergency and  standby power  These requirements include the reliability of the prime power source  the nature  of the work done  local and state regulations governing emergency power  etc  The process does  not give a single solution that is applicable to all cases  It is hoped  however  that it provides the  framework for selecting an UPS for any facility  Figure 3 1 illustrates this process  To help  illustrate how the selection procedure can be used  an example is provided in appendix B  This  example is completely fictitious and should not be considered as    the    model for how the  selection process would be used in every case  It does  however  illustrate the many factors that  go into the decision process and the need for a good staff to assist the facility manager in making  the UPS selection             Determine Nee
130. ing current   ac  inputs  with indicating lights to indicate the breaker open close position   devices to detect  and alarm loss of ac input  and devices to detect and alarm low high charger output direct current   dc  voltage  The power and control components are normally mounted in one or more free  standing  sheet metal cabinets  One cabinet may be adequate for smaller systems  The cabinets  are normally designed for front access  All components can be inspected or removed from the  front of the cabinet by opening a hinged door  Meters  indicating lights  control switches or  pushbuttons  and adjustment potentiometers may be located inside the cabinet or mounted on the  hinged door  A static UPS with a power range of 150 to 750 kVA is shown in figure 4 1   Electronic control components are normally assembled in a modular construction with drawout  removable modules  The cabinet doors are provided with screened filtered openings for cooling   Cooling may be either by natural convection or by fans  Fans are typically used in larger  systems  The cabinets are normally designed to allow power and control cables to enter from  either the top or bottom      2  Batteries and racks for smaller systems  Batteries for smaller systems  50 kVA and  smaller  may be mounted in cabinets or on open racks  Batteries used in cabinets are normally  the valve regulated  VRLA  type sometimes referred to as  maintenance free    type  Also  the  individual units normally have a voltage rating of
131. ing normal operation the motor drives the flywheel and the synchronous generator at  constant speed proportional to the power supply frequency  The generator output voltage is  regulated by the voltage regulator and the frequency is constant and proportional to the motor  power supply frequency  When input power is momentarily lost or degrades  the flywheel  supplies its stored energy to the generator and the frequency is maintained within the required  tolerance for a duration depending on the flywheel inertia  The time interval for which the  frequency can be maintained within tolerance is proportional to the ratio of flywheel inertia to the       FLYWHEEL   a k1 Pa    AC   hi   iad ttn PI   G   olosad  SOURCE _ f I o      eal  Ma a w a3 i  A TOR BENERA TUR             Figure 2 20  Inertia driven ride through system    load for a given speed  To keep the system weight low  high speed is required  However  to keep  the noise level low  low speed is desirable  Therefore  the system is commonly operated at a  speed of 1800 revolutions per minute  rpm  as a trade off  In this system  a synchronous motor is  used to maintain a constant speed independent of the load level  However  an induction motor  with very low slip may also be used as discussed in paragraph 2 2a 1   In newer designs an  asynchronous motor is coupled with a synchronous generator  This technology uses induction  coupling rather than a flywheel for the ride through inertia  Other designs use a battery  The  bat
132. ingle way rectifier   Three phase uncontrolled bridge rectifier   Single phase controlled bridge rectifier   Three phase controlled bridge rectifier   Simple single phase inverter   Voltage control using pulse width control   Pulse width modulation  PWM    Ferroresonant transformer   Three phase inverter   Single phase static transfer switch   Inertia driven ride through system   Battery supported motor generator  M G  set   Nonredundant static UPS system   Static UPS system with static transfer switch   Static UPS system with static transfer switch and an alternate source  regulating transformer   Redundant static UPS system   Cold standby redundant static UPS system   Dual redundant static UPS system with static transfer switches  Inertia driven ride through system with a synchronous motor  Inertia driven ride through system with an induction motor and an eddy  current clutch   Battery supported inertia system   Battery supported M G set   Determine the general need for an UPS   Determine the facility need for an UPS   Determine the required power is a key step in the UPS selection process  Redundancy improves system reliability   Basic redundant UPS designs   Determining affordability requires that all costs be considered   Static UPS system 150 to 750 kVA  courtesy of Liebert    Various battery rack configurations  courtesy of Excide Electronics   Double ended substation connected in secondary selective configuration  Rotary UPS system 200 kVA to 10 000 kVA  courtesy of H
133. ion  production  fire protection   space conditioning  data processing  communication  life support  or signal circuits  Some  facilities need an UPS for more than one purpose  It is important to determine the acceptable  delay between loss of primary power and availability of UPS power  the length of time that  emergency or backup power is required  and the criticality of the load that the UPS must bear    All of these factors play into the sizing of the UPS and the selection of the type of the UPS     b  Determine safety  It must be determined if the safety of the selected UPS is acceptable   The UPS may have safety issues such as hydrogen accumulation from batteries  or noise pollution  from solid state equipment or rotating equipment  These issues may be addressed through proper  precautions or may require a selection of a different UPS     c  Determine availability  The availability of the selected UPS must be acceptable  The  criticality of the loads will determine the necessary availability of the UPS  The availability of an  UPS may be improved by using different configurations to provide redundancy  It should be  noted that the C4ISR facilities require a reliability level of 99 9999 percent     d  Determine maintainability  The selected UPS must be maintainable  Maintenance of the  unit is important in assuring the unit   s availability  If the unit is not properly cared for  the unit  will be more likely to fail  Therefore  it is necessary that the maintenance be pe
134. ion of state of charge  thus  specific gravity readings are not part of  normal routine maintenance  The electrolyte in a ni cad cell will start to freeze  slush  at  approximately  40  F  Occasionally  grayish white deposits of potassium carbonate may be seen  on the cell tops  these deposits form the electrolyte entrained in the escaping gas reacts with the  carbon dioxide in the air  This deposit is not corrosive but is a conductor when damp  and needs  to be removed from the battery      1  Parameters  The flooded lead acid material data discussed previously can be used for  maintaining ni cad cells by changing parameters appropriate for alkaline cells  Float voltages for  ni cad cells are significantly different from those for lead acid cell  Although the battery terminal  voltage may be the same  the number of cells will be different since a lead acid cell is a nominal  2 volts per cell with a ni cad battery is a nominal 1 2 volts per cell      2  Neutralizing agent  Use a boric acid solution of 7 ounces of boric acid to one gallon of  water     i  Safety  Every UPS battery installation presents safety hazards and safety precautions  cannot be ignored  The three major hazards are from the electrolyte in the battery  the gases  emitted by the battery  and the potential electrical hazard available from the stored energy of the  battery  Most persons trained in an electrical environment are aware that batteries are dangerous   but need to be warned and advised again as to 
135. ir facilities for removed components   Availability of personnel is a function of the total number of maintenance personnel  the hours of  facility operation  dictates the number of shifts during which maintenance personnel may be  required   and training schedules  Availability of spares  to replace removed components  and  parts  to repair in place or removed components  depends on the total number initially procured   Replacement and repair then depends on the rate spares and parts are purchased and the rate at  which the spares and parts become obsolete  Location of repair facilities is important because if    3 11       TM 5 693    they are located a significant distance from the UPS  transportation may increase the time  and  the cost  to restore the UPS to operation  In many cases  the facility manager may choose to do  only that maintenance performed directly on the UPS  i e   in place repair and removal and  replacement  with internal resources  All other maintenance  i e   repair of removed components   would be done by the UPS manufacturer or a third party  Alternatively  the manager may  contract out all of the maintenance  This decision should be made primarily on the basis of cost  and availability  The cost of hiring and training personnel should be compared to that of  contracting out all or some of the maintenance  The expected number of repairs should be  considered  A study of high failure rate components and the stock levels needed to minimize  down time i
136. is a  specially designed transformer which can maintain its output voltage with limited deviations in  input voltage  In addition  it can attenuate voltage surges and spikes originating in the power  supply source                 REGULATING a    a a ei SYNCHRONIZING  TRANSFORMER   SIGNAL  ALTERNATE do he f  AC a sata af j  SOURCE    gt  f  __ L n   Co  STAIR m    a  SWITCH ae  MORMAL  Te BATTER VERTER  AC o CHARGER   INVERTER  S  LRCE          BAT TERYT          Figure 2 24  Static UPS system with static transfer switch and an alternate source regulating transformer    2 34    TM 5 693    c  Redundant system  The redundant static UPS system configuration is shown in figure 2 25   This configuration is made up of two or more normally energized basic systems connected in  parallel and synchronized with one another  The static interrupters used in this configuration are  solid state devices which serve to isolate a faulty inverter from the connected loads and to prevent  the other inverters from supplying high fault currents to the faulted inverter  In this  configuration  although the rectifier inverter combinations are duplicated for higher reliability   only one common battery is used  This is due to the extremely high reliability of batteries  The  rating of each of the parallel basic systems should be such that if one system fails  the remaining  systems are capable of supplying the connected load  Therefore  for a two parallel system  each  system should be rated for 100 p
137. is greatly  influenced by temperature considerations  Battery manufacturers are finding that the type and  number of discharge cycles can reduce life expectancy when installed for the high current  short  period  full discharges of UPS applications  Characteristics of expected life and full discharge  capabilities of various types of UPS batteries are given in table 2 1  An explanation of the  relationship of battery life to battery capacity  of the basis for battery sizing  and of the effects of  battery cycling is considered necessary to impress on maintenance personnel why continual  maintenance  data reporting is so important in fulfilling warranty policy requirements  Operating  characteristics of the overall system such as charging discharging considerations  ripple current  contribution  and memory effect also can lead to a diminishment in expected battery performance     Table 2 1  Characteristics of UPS battery types             Approximate  Typical Typical Number of  Warranty Expected Full   Battery Type Period Life Discharges  Lead acid antimony  flooded electrolyte 15 years 15 years 1 000  12 000  Lead acid calcium  flooded electrolyte 20 years 20 years 100  Lead acid calcium gelled electrolyte  valve regulated 2 years 5 years 100  Lead acid calcium suspended electrolyte  valve regulated 1   10 years 5 12 years 100 200  Lead acid special alloy suspended electrolyte  valve regulated 14 years 14 years 200 300  Lead acid pure starved electrolyte  valve regulated 1 ye
138. is the actual time of the test to specified terminal voltage as corrected for  temperatures    t  is the rated time to specified terminal voltage     6  Motor testing  Testing of motors will vary based on the size of the motor  Small size  motors  less than 200 HP require mechanical testing and insulation resistance testing  megger    Medium size motors  between 200 and 5000 HP require mechanical testing  insulation resistance  testing  megger   and polarization index testing  Large size motors  greater than 5000 HP require  mechanical testing  insulation resistance testing  megger   polarization index testing  and  overpotential testing  Hi Pot       a  Motor mechanical test  A mechanical test of the motor should be performed to  check that the motor is free from interference  This is accomplished by first uncoupling the  motor from the driven machinery  The motor shaft is then manually rotated  The shaft should  rotate freely      b  Motor insulation resistance test  megger   This test is performed to ensure the  insulation has no weaknesses  The test is performed utilizing a megohmmeter  either hand or  power operated  with a voltage output of at least 1000 volts  The test should be conducted phase   to phase and phase to ground  Test duration should be one minute  The insulation resistance is  variable with temperature  thus the measured value should be corrected to the standard  temperature as required  The recommended minimum values of insulation resistance are rated  k
139. isposing of spent batteries  the facility manager must ensure that batteries meet all radioactive  contamination requirements for uncontrolled release  A variety of UPS types and configurations  can be selected  The costs can vary widely depending on the specific type and configuration  selected  It is impractical to provide an all inclusive cost comparison of all possible combinations  of types and configurations     3 2  Static UPS system ratings and size selection    Presently  there are no standard ratings and performance characteristics for static UPS systems   However  the typical performance specifications from various manufacturers are indicated in  tables 3 4  3 5  and 3 6  The performance specifications are normally based on operating the  static UPS system under typical environmental conditions as shown in table 3 7  These ratings  only provide a general listing of typical ratings  The manufacturer s ratings shall be used to  determine if the UPS will perform in the specified environment  It may be necessary to derate the  equipment where the manufacturer s performance specifications are exceeded     a  Determining static UPS system rating  In order to properly size and select a static UPS  system  the load kVA  load power factor  inrush kVA or current  load voltage  number of phases  and frequency  and required battery protection time should be determined for the load to be  served     TM 5 693     1  Determining load kVA  In existing installations  the load KVA s
140. itch  The methodology used in this computation sheet can be used to develop    TM 5 693    computation sheets for other system configurations  For example  for a three phase system  the  step by step procedure should be followed for each phase  The system kVA rating should be  three times the largest single phase kVA obtained  For systems without a static transfer switch   the maximum inrush current obtained should be below the value at which the system reaches the  current limit mode     d  Static UPS system selection criteria  Selection of a static UPS system should be in  accordance with certain criteria  The system output voltage and frequency shall be as required by  the loads  The output shall be three phase when any of the loads is a three phase load  otherwise  a single phase system should be used for ratings up to 75 kVA  The system output voltage and  frequency regulation and transient response shall meet the requirements of the most power   sensitive load s   The system rated kVA at the specific site shall be equal to the load KVA plus a  25 to 30 percent margin  The system shall be capable of supplying the load inrush demand  without reaching the current limit mode  The battery protection time shall not be less than one  minute and shall not exceed the maximum time the load can be operated with the loss of the  environmental support equipment as specified by the equipment manufacturer  normally in the  range of 1 to 15 minutes      3 3  Rotary UPS system ratings a
141. ity test  and so an UPS shutdown must occur or a redundant replacement battery  will need to be provided  For these reasons  voltage and specific gravity are used to periodically  monitor the battery condition  Recognize that these readings indicate state of charge  but do not  indicate the capacity of the battery      a  Use of capacity tests  The results of a capacity test can be used to determine the  need for a replacement battery  Currently  battery test sets are available from a number of  manufacturers  or the user can fabricate a load bank  sometimes actual loads can be used   Three  types of battery capacity tests are described in the standards  namely  acceptance  performance   and service tests  Of these  the last two are required for normal maintenance testing      b  Comparison of results  The key again is to compare the results to prior test data to  establish a trend  Battery capacity may be less than 100 percent of nameplate rating during the  first few years of operation  unless 100 percent capacity at delivery was required by the purchase  specification  The capacity  normally 90 to 95 percent of nameplate  of a new battery will rise to  its rated value after several charge discharge cycles or after several years of float operation      8  Connection resistance  This check is very important but is often neglected  even  though it can be conducted with the battery in service  The instruments normally used are those  which are used to measure a power circuit b
142. lance  and Reconnaissance  C4ISR   Facilities    CBEMA  Computer Business Equipment Manufacturers Association    dc  Direct Current    EM  Electromagnetic    FCC  Federal Communications Commission    FET  Field Effect Transistors    GTO  Gate Turn Off    HVAC  Heating  Ventilation  and Air Conditioning    IEC  International Electrotechnical Commission    IEEE  Institute of Electrical and Electronic Engineers    IGBT  Insulated Gate Bipolar Transistors    G 1    TM 5 693    IITRI  IIT Research Institute    ITIC  Information Technology Industry Council    kW  Kilowatt    MDT  Mean Downtime    M G  Motor Generator    MOSFET  Metal Oxide Field Effect Transistor    ms  Millisecond    MTBD  Mean Time Between Demand    MTBF  Mean Time Between Failure    MTTF  Mean Time To Failure    MTTR  Mean Time To Repair    MVA  Mega Volt Amperes    NEC  National Electrical Code    NEMA  National Electrical Manufacturer   s Association    NFPA  National Fire Protection Association       Ni Cad  Nickel Cadmium       PCB  Printed Circuit Board    G 2    PWM  Pulse Width Modulation    RF  Radio Frequency    RFI  Radio Frequency Interference    RMS  Root Mean Square    rpm  Revolutions Per Minute    SCR  Silicon Controlled Rectifier    SLA  Sealed Lead Acid  also see VRLA     THD  Total Harmonic Distortion         Technical Manual    UL  Underwriters Laboratories    UPS  Uninterruptible Power Supply    VRLA  Valve Regulated Lead Acid    Section II  Terms    Absorbed  or Absorptive  Glass Mat  AGM   
143. larly  important for static UPS configurations without a static transfer switch and bypass capability  In  these configurations  if the load inrush kVA requirements exceed the inverter capability  the  inverter will reach the    current limit    mode causing the output voltage to drop  In configurations  with a static transfer switch and bypass capability  determining the load inrush current  requirements is required for proper selection of overcurrent protective devices for the transfer  switch and coordination with other overcurrent protective devices  The load inrush KVA or  current in existing installations should be determined by actual measurement using a high speed  storage oscilloscope or oscillograph  Since all loads are not normally started simultaneously  the  inrush kVA or current requirements should be determined by energizing the load with the highest  inrush kVA while all other loads are connected  In cases where measurements cannot be taken or  when the installation is in the planning stage  the load inrush requirements should be calculated   Data on individual load inrush kVA and duration should be obtained from equipment  manufacturers or estimated from the data in table 3 8  The maximum inrush current and effective  inrush current can be calculated      4  Load voltage  number of phases  and frequency  The load voltage and frequency  requirements determine the UPS system output voltage and frequency  Three phase loads require  a system with three phase outp
144. ld be given to those that have been approved by the  governmental authority having jurisdiction  Batteries pose special safety concerns for the facility  manager  Safety problems associated with lead acid batteries include spills of sulfuric acid   potential explosions from the generation of hydrogen and oxygen  and the generation of toxic    TM 5 693    gasses such as arsine  AsH   and stibine  SbH3   All of these problems can be satisfactorily  handled with the proper safety precautions  National Fire Protection Association  NFPA  70   National Electrical Code  NEC   provides guidance on battery room ventilation  Wearing face  shields and plastic rubber aprons and gloves when handling acid is recommended to avoid  chemical burns from sulfuric acid  Precautions must be routinely practiced to prevent explosions  from ignition of the flammable gas mixture of hydrogen and oxygen formed during overcharge of  lead acid cells  The gas mixture is explosive when hydrogen in air exceeds 4 percent by volume   A standard practice is to set warning devices to alarm at 20 to 25 percent of this lower explosive  level  Hydrogen accumulation is usually not a problem if good air circulation around a battery is  present  If relatively large batteries are confined in a small room  an exhaust fan s  should be  used to constantly vent the room or should start automatically when hydrogen accumulation  exceeds 20 percent of the lower explosive limit  Finally  the materials used in the battery  con
145. least 95 percent of the complete storage capacity is  replaced within an acceptable time period  This recharge time may range from 5 to 24 times the  reserve period  for a 15 minute reserve period with a 10 times recharge capability the recharge  period would be 2 5 hours       b  Voltage action  Providing the precise amount of charge on each and every cell for  each and every recharge is impracticable for a continuously floating battery operation  The float   voltage point should just overcome the battery s self discharge rate and cause the least amount of  corrosion and gassing  Ambient temperature differences will affect the charging ability of the  selected float voltage level  Overcharge  undercharge  and float voltage levels differ  depending  upon the type of cell used      c  Lead acid cells  The usual recommended float voltage for UPS applications is 2 20  to 2 30 volts per cell depending upon the electrolyte s specific gravity  The excess energy of  higher float voltages results in loss of water  cell gassing  accelerated corrosion  and shorter cell  life  To eliminate such actions  the charge is stopped slightly short of a fully charged condition  on daily or frequent discharges  However  permissible cell manufacturing tolerances and ambient  temperature effects will cause individual cell charge variations  Sulphation will take place and  not be reconverted upon recharge  since the charge is insufficient to draw all the acid from the  plates  The sulphate may start
146. lugs installed  if applicable       3  UPS switchboard  The UPS switchboard should be inspected for completeness of  assembly  verification of nameplate  sizes and settings against drawings  and loose parts and  insulation damage      4  Motor inspection  The motors should be inspected for completeness of assembly   verification of nameplate  sizes and connection against drawings  loose parts  foreign materials or  damage  check insulation type  and alignment of motor with generator      5  Generator inspection  The generators should be inspected for completeness of  assembly  verification of nameplate  sizes and connection against drawings  loose parts  foreign  materials or damage  proper mounting and grounding  and alignment of motor with generator     b  Individual component testing  De energized component testing typically includes megger  and insulation resistance testing of equipment and connections including grounds  turns ratio  measurements  polarity tests  power factor or dissipation factor tests  overpotential tests  contact  resistance measurements  operation time travel analysis  battery and cell voltage measurements   charger UPS generator current and voltage measurements  and equipment systems impedance or  resistance tests  The following components of the UPS system will be tested as follows      1  UPS systems  The static UPS system consists of the battery charger  inverter  battery   and static switch  In addition to these items the rotary UPS consists of a
147. mains  failure     Uninterruptible Power System  UPS    Also used as the abbreviation for uninterruptible power supply  The latter is most often used for  static  battery  backup power supplies for personal computers and other equipment with similar  power requirements  UPSs include uninterruptible power supplies as well as more complex  systems  e g   rotary  hybrid  etc       UPS  parallel with redundancy    An UPS made up of several parallel connected UPS units with equal output ratings  P  and each  equipped with its battery  If one unit fails  one or several of the others pick up the resulting  excess load  If an UPS has a rated output n x P and is made up of n  k units  k is the level of  redundancy for the entire set of n   k units     UPS  parallel without redundancy    An UPS made up of several  n  parallel connected UPS units with equal output ratings  P  and  each equipped with its battery  for large loads  The total output is equal to the number of units  multiplied by their individual output  n x P   In this configuration  no UPS unit is redundant     UPS  single   An UPS made up of one single UPS unit  rectifier charger  inverter  and bypass  and a battery     G 16    TM 5 693    UPS  Hybrid  An UPS that combines the features of both a static and rotary UPS     UPS  Multiple Unit  An UPS in which two or more units share the load but neither can carry 100 percent of the load     UPS  Parallel Redundant  An UPS in which two or more units are arranged in parallel a
148. mal safety procedures  When working around batteries  all normal safety  procedures should be followed  including the use of protective equipment and tools with insulated  handles  Generally  a ground detector is provided as part of the dc system  most often in the  rectifier charger  Be certain to check the ground detector before starting work  If an  unintentional ground exists  it should be cleared before work begins     j  Troubleshooting  Questionable battery system performance means that all the service  checks required under annual inspections will need to be made  Generally  any cell which  demonstrates conditions beyond the manufacturer s recommended parameters should be replaced  and the system rechecked to ensure all suspect cells have been removed  Where widespread  premature battery failures are encountered  the battery manufacturer s service department should  be contacted for further instructions  If low or high float voltages  temperature variations  visual  deviations or bulges  low open circuit voltages  and low 10 second full load voltages all exceed  the manufacturer s parameters  the cells are probably irreparably damaged     5 16    TM 5 693    APPENDIX A    REFERENCES       Required Publications  Government Publications  Department of Commerce    Federal Information Processing Standards  FIPS  pub 94  Guideline of Electrical Power for ADP Installations  cited in figures 4 5  4 6      Non Government Publications    American National Standards Institute  
149. mean time between failure  a measure of reliability   MTTR is mean time to repair  a measure of maintainability     Reliability is the probability that the item will perform as intended for a specified period of time   under a stated set of conditions  It can be expressed in terms of the number of failures in a given  time  the failure rate   or as the time between failures  for repairable items   or time to failure  for     one shot    or non repairable items  Maintainability is defined as the relative ease and economy  of time and resources with which an item can be retained in  or restored to  a specific condition   This assumes maintenance is performed by personnel having the specified skill levels  using  prescribed procedures and resources  at each prescribed level of maintenance and repair  It can  be expressed as the probability that an item can be restored to operational condition in a stated  time  the number of repairs that can be made in a specific time  repair rate   or the MTTR  From  the equation for A   it is obvious that availability can be increased by increasing MTBF or  reducing MTTR  For example  assume the MTBF and the MTTR of a single UPS unit are 500  hours and 20 hours  respectively  The inherent availability of a single unit configuration would  be     Rie  oe Lge   A 500  20      The inherent availability of a two unit configuration where only one unit is required would be   A  A    Ap  A  x A2  0 999  The inherent availability of a two unit configu
150. motor  The inertia driven ride   through system with a synchronous motor shown in figure 2 28 is the basic inertia driven ride   through system described in paragraph 2 2  The main limitation in this configuration is that the  ride through time is normally limited to 0 5 seconds  This makes this configuration suitable only  at locations where the power supply has a high reliability and long term interruptions are unlikely  as in large metropolitan areas  This configuration is also widely used in frequency changer  applications to convert the power supply frequency to another frequency such as 420 Hz  In this  application the synchronous motor drives the generator at a constant speed proportional to the  power supply frequency  The ratio of the generator number of poles to the motor number of poles  should be the same as the ratio of the desired frequency to the power supply frequency  This  configuration is becoming less common and it is not available from many manufacturers   However  newer technologies provide an induction coupling system for the inertia ride through  rather than the flywheel as discussed in paragraph 2 2b 5   This system is used with an  asynchronous motor and a synchronous diesel generator  The induction coupling allows for  approximately 2 seconds of ride through while the diesel generator comes on line     b  Inertia driven ride through system with an induction motor  The inertia driven ride   through system with an induction motor is the same as shown 
151. ms   UPS battery maintenance    REFERENCES    Paragraph    1 1  1 2  1 3  1 4  1 5  1 6  1 7    2 1  2 2  2 3  2 4    4 1  4 2  4 3    4 4  4 5       TM 5 693    APPENDIX B    GLOSSARY    INDEX    Table    Table 2 1  Table 2 2    Table 3 1  Table 3 2  Table 3 3  Table 3 4  Table 3 5  Table 3 6  Table 3 7  Table 3 8  Table 3 9  Table 4 1  Table 4 2  Table 4 3  Table 4 4  Table 4 5  Table 4 6  Table 4 7  Table 4 8  Table 4 9  Table 5 1  Table 5 2  Table 5 3  Table 5 4  Table 5 5    Figure    Figure 1 1  Figure 1 2  Figure 2 1  Figure 2 2  Figure 2 3    ii    SELECTING AN UNINTERRUPTIBLE POWER SUPPLY  UPS    AN EXAMPLE    LIST OF TABLES  Title    Characteristics of UPS battery types   Harmonic currents present in input current to a typical rectifier in per unit of  the fandamental current   General criteria for determining the purposes of an UPS  Comparison of reliability of parallel redundant and parallel configurations  Criteria for evaluating UPS battery   Typical rectifier charger ratings   Typical inverter ratings   Typical static switch ratings   Typical environmental ratings   Typical load power factors and inrush requirements   Updated typical rotary UPS ratings   Circuit breaker corrective action   Rectifier battery charger corrective action   Battery corrective action   Inverter static switch corrective action   UPS system corrective action   Motor engine corrective action   Generator corrective action   Suggested test accessory list for battery maintenance   Suggested
152. mum of 10 minutes  Then the voltage is increased in 1 kV  intervals recording the leakage current at each step  Sufficient time shall be allowed between  steps for the leakage current to stabilize  The data shall be plotted  Any sudden changes in the  curve characteristics are an indication of impending winding failure      7  Generator testing  Testing of generators will vary based on the size of the generator   Small size generators  less than 200 HP  require mechanical testing  insulation resistance testing   megger   no load testing  and load testing  Medium size generators  between 200 and 5000 HP   require mechanical testing  insulation resistance testing  megger   polarization index testing  no  load testing  and load testing  Large size generators  greater than 5000 HP  require mechanical  testing  insulation resistance testing  megger   polarization index testing  overpotential testing  Hi  Pot   no load testing  and load testing      a  Generator mechanical test  The clearance in the generator and exciter air gap  should be checked  Uncouple the motor from the generator  Make sure the generator set turns  over freely  Rotate the generator rotor by hand at least two revolutions to be sure there is no  interference and it turns freely  Do not apply any mechanical force to generator fan when rotating  generator rotor      b  Generator polarization index test  The polarization index test is an insulation  resistance test that lasts for 10 minutes  The insulation resista
153. n a setting of 110 to 125 percent of rated  load  Without this feature  the inverter would be driven to current limit on a fault  The inverter  would not supply sufficient current to trip the breaker and would continue to feed the fault  causing a potential hazard  The transfer of the fault to the alternate power source by the static  switch allows full short circuit current to pass through  thus tripping the circuit breaker  The  static switch will then transfer back to the UPS for normal operation  Because the circuit cannot  differentiate between an inrush and a fault current  it is common for the initial energization of a  load to cause a temporary transfer to the alternate source power  When the inverter logic drops  below a predetermined value  the bypass SCRs are gated on by the static switch logic board and  the UPS bypass line will supply the load  Retransfer to the UPS module can occur automatically  when the logic senses that the UPS output problem has been eliminated  The logic system  circuitry maintains the inverter output in synchronization with the UPS bypass power  The  configuration of figure 2 2 does not provide the isolation capability of the figure 2 3 system   Reverse parallel SCRs can also be used as UPS power interrupters  that is  as an on off switch to  isolate a failed inverter occurring in a redundant UPS configuration      2  UPS static switch with circuit breaker  SS CB   A hybrid UPS system uses an  electromechanical switch in the inverter outpu
154. nce is recorded after 1 minute  then  again after 10 minutes  The polarization index is the quotient of the 10 minute and 1 minute  readings  After insulation resistance readings have been made  the test voltage is returned to zero  and the insulation is discharged      c  Generator insulation resistance test  megger   This test is performed to ensure the  insulation has no weaknesses  The test is performed utilizing a megohmmeter  either hand or  power operated  with a voltage output of at least 1000 volts  The test should be conducted phase   to phase and phase to ground  Test duration should be 1 minute  The insulation resistance is  variable with temperature  thus the measured value shall be corrected to the standard temperature  as required  The recommended minimum values of insulation resistance are rated kV plus 1  megohm for the stator winding  for example  5 16 megohms for 4 16 kV winding  and 1 megohm  for the rotor winding  While this is a guideline  the manufacturer s test manual shall include  acceptance criteria for the test  Megger test are    go no go    tests      d  Generator over potential test  Hi Pot   This test assesses the dielectric strength of  the insulation of a generator  The dc over potential test is performed by applying a voltage and    4 16    TM 5 693    measuring the leakage current  The voltage applied during the acceptance test is a function of the  equipment voltage rating as shown by the following equation     de acceptance test voltage  
155. nchronous machine  The magnetic  field created in this way brakes the speed of the free running inner rotor  so that energy is  released  This energy is used to keep the rotor running at 1800 rpm  while the generator comes  on line     2 31    TM 5 693     6  Kinetic battery  The kinetic battery may be used in place of regular flooded lead acid  or ni cad batteries in the battery backed M G configuration as shown in figure 2 21  The energy  for the kinetic battery comes from a flywheel coupled with a M G set  The energy from the  flywheel is driven by a small pony motor using normal ac power  Upon loss of normal power  the  flywheel continues to put out energy through the generator which provides input ac power to the  rectifier  The rectifier and inverter filters the ac power and provides ac power to the primary M G  set  The ac power must be filtered to prevent the load from seeing the degradation of the  frequency as received from the flywheel generator source  This system allows for approximately  15 to 30 seconds of ride through while waiting for the diesel generator to start     c  Affect of loads on rotary UPS systems  Various types of loads may affect the UPSs ability  to perform  Some of these load types are non linear loads  loads with high inrush current  and  unbalanced loads      1  Non linear loads  Non linear loads as discussed in paragraph 2 1m 1  will distort the  synchronous generator output voltage wave shape and cause the output voltage to contain high  ha
156. nd  mixed with a sulfuric acid solution  The gelled electrolyte is highly viscous and during charge  and discharge can develop voids or cracks that impede acid flow and result in loss of battery  capacity     Harmonic   Sinusoidal term of the Fourier series expansion of a periodic function  The harmonic  or  harmonic component  of the nth order is characterized by  Yn is the root mean square  RMS   value of the given harmonic component  w is the angular frequency of the fundamental  related to  frequency by  w   2 f  phin is the phase angle of the given harmonic component at t   0     Harmonics   Distortions of the sine wave that characterizes normal ac current  Harmonics are transmitted into  an ac line by non linear loads  i e   loads that do not draw power in regular sine waves   such as  computers  copiers  FAX machines  and variable speed motors  Harmonics can cause  communication errors and equipment damage  In three phase systems  they can cause  transformers and neutral conductors to overheat creating a possible fire hazard     Harmonics  current and voltage    All ac which is not absolutely sinusoidal is made up of a fundamental and a certain number of  current harmonics which are the cause of its deformation  distortion  when compared to the  theoretical sine wave  For each current harmonic of order n and an RMS value In  there is a  voltage harmonic with a RMS value Un  If Zsn is the voltage source output impedance for the  harmonic of the nth order  then  Un   Zsn
157. nd each can carry 100 percent of the  load        UPS  Parallel Unit  An UPS in which two or more units are arranged in parallel and not all units are required to carry  100 percent of the load     UPS  Rotary  An UPS in which a M G set is used     UPS  Single Unit  An UPS in which one unit carries 100 percent of the load     URS  Static  A solid state UPS relying solely on battery power     Useful Life  battery   The time over which a battery can deliver a useful  normally defined as 80 percent or more of the  battery   s capacity  amount of power     UTE  Union Technique de     Electricit     French electrotechnical standards organization     VDE  German electrotechnical standards organization     Vented Battery   see Battery  vented       Voltage  equalize   The voltage applied during an equalizing charge  This voltage is sufficiently high to ensure that  the local action of all cells is overcome     Voltage  float   DC voltage applied to the battery to maintain its charge level  This voltage depends on the type  of battery  the number of cells  and the manufacturer   s recommendations     Volt Amperes  VA   The product of the voltage and the amperes  The resultant is total system power     Voltage Harmonics   see Harmonics  current and voltage      TM 5 693    Valve Regulated Lead Acid  VRLA    A    sealed    battery in which the electrolyte is immobilized  a relief valve opens when the internal  pressure  caused by oxygen and hydrogen generation  exceeds a predetermined 
158. nd economic loss     Continue production  Prevent damage to equipment  Provide fire protection     Provide customer service  Maintain personnel performance     Prevent loss of electric generation and steam  Maintain production  Prevent damage to  equipment    Prevent flooding  Maintain cooling facilities  Provide sanitation   Continue production   Maintain boiler operation           Sd  uv fo sasodind ayy suunusajap AOf DIAAUD  DAIUADH        AGPI      69 S NL    v              Power Needed  For  Mechanical  Utility  Systems   continued   Heating    Refrigeration    Production    Space  Conditioning    Purpose  Power fans  amp  blowers  for ventilation  amp   heating    Prepare food    Sustain process    Power special  equipment or  devices having  critical warm up   cryogenics   Power critical  depositories  e g    blood bank   Power non critical  depositories  e g    meat  produce    Power critical    process    Process control  power  Control critical  temperatures  Control critical  pressures   Control critical  humidity  Control static  charge  Control building  heating and  cooling  Ventilate for toxic  fumes  Ventilate for  explosive atmosphere    General ventilation    Ventilation for special    equipment    Maximum Tolerable Power  Failure Duration  0 1s to until prime power  restored    5 min  10s per NFPA 99   1996     2h    Up to 1 min    10s    1 min    1 min    10s or less    30 min    Recommended Minimum  Auxiliary Supply Time  Indefinite until evaluated    Unt
159. nd size selection    Similar to static UPS systems  there are no standard ratings and performance characteristics for  rotary UPS systems  Also  since the use of rotary UPS systems is much less common  the  number of manufacturers offering rotary UPS systems is limited  Each rotary UPS system  configuration may have unique performance characteristics  Performance characteristics of  typical configurations are shown in table 3 9     Table 3 9  Updated typical rotary UPS ratings                   Induction Motor Asynchronous motor  Generator  Kinetic Battery   generator  induction coupling  Protection Time 12s 2s  Voltage Regulation  1  t1   Voltage Drop or Rise for 50  Load Step  3    1 0 pf  6   Change from Full Load  4    0 8 pf  Voltage Transient Recovery Time 150 ms to  2  250 ms  Frequency Regulation  0 5 Hz  0 5 Hz  Frequency Transient Recovery Time 0 5 s 0 5s  Phase Angles  Unbalanced Loads up to 120     1   120     1    20 Percent  Harmonic Voltage 1 5   THD  Ph Ph  4  max   2 5   THD  Ph Ph        a  Determining rotary UPS system rating  In order to properly size and select a rotary UPS  system  the load kVA  load power factor  inrush kVA or current  load voltage  number of phases  and frequency  required battery protection time  if battery supported UPS   maximum permissible  frequency deviation  if inertia driven UPS   and required ride through time  if inertia ride   through UPS  should be determined  This information can be determined in the same manner as  descri
160. nductors      4  Ground loops and multipoint grounding  The single point grounding system should be  used whenever feasible  However  within very large systems the use of a single point grounding  may not be practical  The system may be made of subsystems each supplied from different  power sources with separate central grounding points  This situation is often in installations  where data terminals and remotely located printers are located outside the computer room  In  such installations the different central ground points may have different potential to ground and  ground loops are established as shown in figure 4 6  Such ground loops can create a path for    4 9    TM 5 693                Figure 4 5  Single point grounding example   Reproduced from Federal Information Processing Standards Publications  FIPS pub  94     unwanted noise through the data links between the different components  Ground conductors of  low resistance interconnecting the separate central grounding points shunts some of the noise  current away from the data cable as shown in figure 4 6     c  Computer power centers  A computer power center is a self contained unit which can be  located in a computer room to distribute the power from the UPS system to the loads  It contains  an isolation stepdown transformer  output circuit breakers  and terminations for main input power  cable and output cables  A computer power center may also contain a power monitoring panel  which monitors the input output power
161. nected to a central computer or several  computers  equipped with specific software     Brownout  Conditions under which power is available but not sufficient to fully meet the needs  voltage   current  of the load     BS  British Standard   Label used to indicate compliance with British standards     Bypass  The use of parallel units in an UPS to increase capacity or for redundancy     Bypass  automatic   In the event of an overload or an unlikely UPS problem  your application is still powered thanks  to the automatic bypass module     Bypass  manual   Manually operated switch used to supply the load via direct connection to utility power during  servicing of the UPS system     Capacity  battery   The number of ampere hours  Ah  a fully charged cell or battery can deliver under specified  conditions of discharge     Cell  The basic electrochemical element of a battery     Charge  equalizing   An extended charge to a measured end point that is given to a storage battery to insure the  complete restoration of the active materials in all the plates of the cells     Charger   Device associated with the rectifier and used to supply the battery with the electrical power   direct current  dc   required to recharge and or float charge the battery  thus ensuring the rated  backup time     Circuit Breaker  battery   DC circuit breaker that protects the battery of an UPS     Cos phi  A measure of the phase shift between the current wave and the voltage wave observed at the  terminals o
162. nergized and the other system is energized to supply the load through a  manually operated circuit breaker  Upon loss of the inverter output  the static switch  automatically connects the load to the alternate source without interruption  The second system s  static switch is then closed manually  also connecting the load to the alternate source  To transfer  the load to the second system  the static switch of the failed system is manually opened  Next the  second system s breaker is manually closed  its static switch is opened  and the load is supplied  from the system s inverter  During the transfer operations  the load is continuously supplied from    2 35    TM 5 693    the alternate source without interruption until it is switched to the second system  In this  configuration the two inverters are not intended for operation in parallel and their output circuit  breakers are interlocked to prevent this condition  One disadvantage of this configuration  when  compared to the redundant system  is that the load is supplied from the unregulated alternate  source for a short duration before the transfer is completed  Also  the transfer from one system to  the other is manually accomplished and requires an operator s action  This makes the use of this  configuration undesirable in locations where the alternate power source has a low reliability   However  this configuration has a higher efficiency than a comparable two parallel redundant  configuration  The higher efficiency is 
163. ng the UPS ensures it will have the capacity  to handle the increased load without the expense of retrofitting the system  which is more costly  in the long run  A general rule of thumb in oversizing is to increase the initial power requirement  by 30 percent  If oversizing cannot be justified  the UPS should be selected and the installation  designed such that future expansion can be accommodated at the least possible cost     d  Select the Type of UPS  Selecting a particular type and configuration of an UPS depends  on many factors that must be considered and weighted according to a facility   s particular  requirements  These factors include the purpose of the UPS  the required power  cost  safety   environmental  availability  and maintenance  Note that the selection process  see figure 3 1  is  iterative  The type and configuration of the UPS initially selected is based on the purpose and  power required  If the selected UPS is not acceptable based on one or more of the remaining  factors  another type or configuration must be selected and the evaluation repeated     e  Determine if the safety of the selected UPS is acceptable  Safety is an overriding concern  of any UPS design and installation  Safety is basically governed by the electrical codes and  standards as adopted by government and commercial agencies  and good judgment on the part of  the design and installation team  In cases where more than one performance or safety design  alternative exists  preference shou
164. nitude but the line to line voltages may be extremely unbalanced  However  PWM  technique can also be used as in the case of single phase inverters     i  Static transfer switch  A static transfer switch  like an electromechanical transfer switch  is  used to transfer loads from one power source to another  manually or automatically  However   unlike an electromechanical transfer switch  the static transfer switch total transfer time is in the  order of one fourth of a cycle which will provide power to the loads without interruption      1  Design  As shown in figure 2 19  a single phase static transfer switch consists of two  pairs of SCRs  Each pair is connected in antiparallel arrangement  i e   the anode of one SCR is  connected to the cathode of the other  By this arrangement  each SCR in the pair can be made to  conduct every other half cycle  One pair of SCRs is connected between the load and each of the  two sources  The logic circuit applies firing signals to either pair of SCRs      a  Operation  Applying a firing signal to source No  1 SCRs causes them to conduct  and power flows from source No  1 through the SCRs to the load  To transfer the load to source    2 18    TM 5 693        lt     PHASE A      _        PHASE B    gt        PHASE C            Figure 2 18  Three phase inverter    No  2  the firing signals are transferred from source No  1 SCRs to source No  2 SCRs  This  causes source No  2 SCRs to conduct and source No  1 SCRs to block when the SCR anode  
165. nstalled on a level surface  The assemblies may be bolted to the floor if required by the  manufacturer  The cabinets should be in a convenient location for periodic inspection with  sufficient front clearance for front door opening and access to the cabinet internals  Sufficient    4 2    TM 5 693    rear and overhead clearances should also be maintained for removing rear panels when necessary  and for ventilation  The minimum clearances should be as recommended by the manufacturer   The charger inverter cabinets are normally factory wired  The field wiring consists of connecting the ac  input to the rectifier charger  the alternate ac source to the bypass equipment when used  the battery  leads  and the connections to the output distribution panel  The positive and negative battery leads  should preferably be run in separate non metallic conduits  The cables from the normal and the  alternate ac sources should also be run in separate conduits to avoid common failures  The room  temperature should be maintained below 104  F for maximum equipment life  However  when  batteries are installed in the same room as the rectifier inverter cabinets  a lower room  temperature  approximately 77  F  is desirable  A ventilation system may be required          SINGLE ROW   1 TIER                                        SINGLE ROW   2 TER   SINGLE ROW   3 TER                                  SINGLE ROW   3 STEP             Figure 4 2  Various battery rack configurations  courtesy of Excide
166. ntenance requirements  etc     G 10    TM 5 693    Mean Time Between Failure  MTBF   A measure of reliability  Usually denotes the time between inherent failures  1 e   failures caused  by a physical or chemical phenomena within the item      Mean Time To Failure  MTTF    Mathematical calculation of the duration of normal operation of a non reparable device  i e   for  which a MTBF is not possible  The product  expressed in hours  is an indication on the reliability  of the device     Mean Time To Repair  MTTR   A measure of maintainability  Mathematical calculation  or statistical average if available  of the  time required to repair a device     Mega Volt Amperes  MVA   The product of the voltage and the amperes expressed in units of millions  The resultant is total  system power     Micro Outage  Total loss in the supply of power for 10 ms     Monitor  system interface    User interface on the Galaxy range of UPS systems  This interface includes an LCD  alphanumeric display with two lines of 20 characters each and is used in conjunction with the  Signal 4 interface     Motor Generator  M G    Power systems that use a rotating ac generator to generate the needed output power  A motor   generator that is powered by a battery or a diesel or gas powered engine when utility power is  lost  constitutes a rotary or hybrid UPS     Noise level  Acoustical decibel level of a source of noise  measured according to the applicable ISO standard     Non Linear Load   see Load     No Ox I
167. ntly and cooler   and require less frequent retorquing than do lead posts  How the batteries are tested at the plant Cells should be tested together  Capacity at which the batteries are shipped   Anything less than 100  makes it debatable whether 100   from the factory can ever be achieved  Tolerance to temperatures above 77  F The higher  the better  Frequency at which a boost charge is   Less frequent is better  needed  Frequency at which testing is required Less often for short times is better        a  Diagnostics  Identifying what has caused a system failure requires a diagnostics  capability  This capability can consist of built in test  manual troubleshooting procedures  or  troubleshooting using external test equipment      b  Accessibility  Once the component s  that caused the system to fail are identified  through the diagnostic capability available for the system  maintenance personnel must gain  access to those components   Access may also be an issue in performing the troubleshooting of  the system failure   To some extent  the accessibility is determined by the installation as well as  the system design  Access to certain areas of an UPS installed in a very limited space may make  repair very difficult even though the UPS design is very maintainable      c  Skills and resources  Even a system that has the most reliable and thorough  diagnostics and is designed for total accessibility will not be economical to maintain if highly  skilled personnel and extensive 
168. ntrol the output de voltage  SCRs are used in place  of the power diodes  The output dc voltage can be controlled at any desired level by changing the  firing angle  amp  as discussed in paragraph 2 1f 2   Control by changing the firing angle is termed     phase control   The voltage is controlled by a feedback loop which senses the output voltage  and adjusts the SCRs firing angles to maintain the output at the desired level  The configurations  of single phase and three phase controlled bridge rectifiers and their wave forms are shown in  figures 2 12 and 2 13 respectively  The output dc voltage of rectifiers with resistive inductive or  non linear loads and the effect of the firing angle  amp  can be determined by circuit analysis  techniques for each specific load  The effect of the firing angle  amp  on the magnitude of the output  dc voltage is as follows      a  Single phase bridge rectifier with a resistive load  The following equation models  the voltage output of the single phase bridge rectifier with a resistive load      1  cos      Eu  a   Ex 2    2 9    TM 5 693             me  rs    i Ini  Ips    Tp2  Ibs  Eg ly    0 T 2r  RESISTIVE LOAD          Ivi  Iba    ane Goo    Inz  Ibs    Ey    0   2r    INDUCTIVE LOAD       Figure 2 9  Full wave bridge uncontrolled rectifier     b  Single phase bridge rectifier with an inductive load  The following equation    models the voltage output of the single phase bridge rectifier with an inductive load     2 10    E  Q   E  c
169. nual for specific  directions      a  Qualifications  Maintenance electricians should be specifically qualified for their  assignments  Responsible supervisors should know the capabilities and limitations of their  personnel and the equipment to be maintained and should not attempt maintenance or repair  activities for which they are not completely staffed or adequately equipped  It is important that  personnel who are to be responsible for the operation and maintenance of the complex UPS  system equipment be trained to a level at which they are comfortable with the equipment   Without this training there is a tendency for personnel to become very apprehensive about  operating controls or opening cabinet doors if necessary      b  Basic training  Personnel should be able to perform preventive maintenance  checks and first level troubleshooting  order spare parts  and have a knowledge of the UPS  system operation  after having completed the UPS manufacturer s basic training course  Training  topics include start up procedures  theory of operation  block diagram level   system description   demonstration of the UPS in operation  operational characteristics  calibration and alignment  procedures  preventive maintenance  basic troubleshooting procedures  safety  and battery  maintenance      c  Advanced training  This training may not be available from all manufacturers   Personnel should be able to perform their own remedial maintenance and be fully equipped with  spare parts an
170. ny ampere hours of  capacity for an 8 hour period  Battery voltage is not constant  so if the load requires a constant  power output  which most UPS applications do  the current must increase as the voltage  decreases  Consequently  the battery is sized to supply a specific kW rate  usually the maximum  inverter kW requirement without recharging  for a specific period of time  usually 5 to 15  minutes  to a minimum specific end voltage and  for lead acid types  at a maximum specific  gravity  measured at 77  F       a  Lead acid cells  A nominal system design may utilize minimum end voltage of  1 67 to 1 75 volts per cell and a maximum specific gravity of 1 215 at 77  F  The actual end  voltage should be the voltage which the UPS manufacturer  battery manufacturer  or the system  design requires  whichever is higher  In some cases  designs provide higher end voltages to meet  design concerns  A higher specific gravity may result in a battery installation needing less space   but results in shorter life spans and higher cell losses and float voltages  The lower end voltage  that manufacturers recommend may cause the UPS to go to static bypass or  by overstressing  battery plates  shorten the life of the battery      b  Nickel cadmium  ni cad  cells  A nominal system design for ni cad units will be to  a minimum end voltage of 1 14 volts at 77  F with the actual end voltage to meet both  manufacturers    and system design requirements  The specific gravity of a new cell will va
171. ode   1999   cited in paragraphs 2 1n 3   3 le  5 2d     RELATED PUBLICATIONS  Government Publications  Department of the Army    TM 5 682  Facilities Engineering Electrical Facilities Safety  November 1983    TM 5 683  NAVFAC MO 116 AFJMAN 32 1083  Facilities Engineering Electrical Interior Facilities   November 1995    TM 5 684  NAVFAC MO 200 AFJMAN 32 1082  Facilities Engineering Electrical Exterior Facilities   November 1996    TM 5 685 NAVFAC MO 912  Operation  Maintenance and Repair of Auxiliary Generators  August 1996    TM 5 686  Power Transformer Maintenance and Acceptance Testing  November 1998       TM 5 811 2 AFM 88 9 Chap  2  Electrical Design Interior Electrical System  September 1983    Non Government Publications       Institute of Electrical and Electronic Engineers  IEEE   445 Hoes Lane  P  O  Box 1331  Piscataway  NJ 08855 1331    TEEE 241  Gray Book  Recommended Practice for Electric Power Systems in Commercial Buildings    1990     TEEE 484    Recommended Practice for Installation Design and Installation of Vented Lead Acid Batteries  for Stationary Applications   1996     A 2    TM 5 693    ANSI TEEE 944  Recommended Practice for the Application and Testing of Uninterruptible Power Supplies for  Power Generating Stations   1986     IEEE 1100  Recommended Practice for Powering and Grounding Sensitive Electronic Equipment   1992     TEEE 1115  Recommended Practice for Sizing Nickel Cadmium Batteries for Stationary Applications    1992     IEEE 1159  Recomm
172. ommended  For battery strings rated under 250 volts  batteries having rubber jars  must be sectionalized into groups rated at 150 volts or less  Vented alkaline type batteries in conductive  material jars cannot be installed with more than 20 cells  24 volts  in any one tray  For safety  an  eyewash and quick drench facilities shall be located nearby     4 4    TM 5 693                        lt  DUAL UTILITY    POWER SOURCES  NOTE 1 _  OPTIONAL STANDBY  ALAJ GENERATORS ALL   2       2  NOTE 2 NOTE 3     NON TECH    BUS 480V EN 480V    NON TECH    BUS BLDG BUS  NORMALLY    J EEE   J Joo a             A C    480V UPS BUS    CLET Oe  AAN SIN    120 208V       NON REDUNDANT  SOLID STATE          UPS    J             STATIC BYPASS CIRCUIT                                 AOIN                   COMPUTER LOADS ONLY    LIGHTS OTHER BLDG  TENANTS LOADS   5 120 208V   RECEPTACLES OTHER   TECHNICAL     LOADS  1e0 208V  NOTES       1  Utility source is double ended substation connected in secondary selective  configuration with either BUS capable of carryingthe entire load     2     NON TECH    Bus feeds large cyclic motor loads or harmonic CUPS rectifier   loads     3     TECH    Bus feeds non cyclic loads  light receptacles and other techincal  loads     4  Computer loads of different types or manufacturers are isolated utilizing    Computer Power Distribution Centers equipped with shielded transformers   transient supressed branch circuit breakers and meterings     DNT Ups tm 1       
173. on disc watt hour meters  when used for billing  may result in    2 27    TM 5 693    bills which are usually too high rather than too low  True RMS sensing is practical but requires  microprocessor based technology  The use of other than true RMS sensing meters  relays  and  circuit breaker trip units may contribute to system operating problems      7  Zero crossing increases  Controls such as generator voltage regulators which use the  zero crossing point of a voltage or current wave can start hunting where harmonic contents result  in more zero crossings than there are naturally in a 60 Hz system  Instability in speed and  frequency can result  causing generator paralleling problems  An inaccurate measurement of  RMS values can prevent proper load sharing of paralleled units  These are important  considerations when generating capacity requirements are changed  Generator manufacturers  should be contacted when existing units are used to supply non linear loads in order to ensure  compatible interfacing      8  Noise feedback  Power line harmonics at audio and even radio frequencies can be  interposed on telephone  communication  and data systems by inductive or capacitive coupling  and by radiation  FCC has set maximum power line conduction and radiation standards for many  types of electric equipment  Unfortunately  not all harmonic generating non linear loads come  under FCC standards  and improperly shielded and filtered equipment can conduct or radiate  noise  which ma
174. on fault     Earthing System TN   Earthing system in which the exposed conductive parts are interconnected and connected to the  neutral  The neutral is connected to the earth  The installation must be de energized immediately  in the event of an insulation fault     Earthing System TT  Earthing system in which the neutral and the exposed conductive parts are directly earthed  The  installation must be de energized immediately in the event of an insulation fault     Electrode  The electrical connector and the associated active materials at which an electrochemical reaction  occurs  Also referred to as the positive and negative plates in a secondary cell     Electrolyte   The medium that provides the ion transport function between the positive and negative electrodes  of a cell  In lead acid batteries  the electrolyte is a mixture of water and sulfuric acid  A nickel   cadmium  ni cad  cell uses a dilute alkaline mixture of potassium hydroxide in water     Electromagnetic  EM  Compatibility  Possibility of a device to operate normally when installed near other devices  given the  disturbances emitted by each device and their mutual sensitivities     Emergency Power   An independent reserve source of electric energy that  upon failure or loss of the primary source   provides reliable power within a specified time to critical devices and equipment which  if they  fail to operate satisfactorily  would jeopardize the health and safety of personnel  result in  property damage  or c
175. onents can be  obtained by contacting the manufacturer or  if the information is not available  by referencing the  Institute of Electrical and Electronics Engineers  IEEE  500  Due to the nature of their critical  loads  C4ISR systems are desired to maintain a reliability level of 99 9999  commonly known as  the six nine rule   This should be taken into account as one attempts to design or select an UPS  system  The selected UPS system  in combination with the overall system  should maintain  reliability level of 99 9999 or higher  Therefore  it might be necessary to design and select a  system with greater redundancy  in order to achieve the  six nine    goal      2  Maintainability  As already shown by the availability equation  reducing the time to  restore a system after it has failed is another way to increase availability  Major factors  determining the ease and economy with which maintenance can be performed are means for  identifying the component s  that caused the system to fail  i e   diagnostics   accessibility of  components  and skills and resources needed to repair the system  through in place repair of the  failed component s  or by removing and replacing them      TM 5 693    Table 3 3  Criteria for evaluating UPS battery                                  CRITERION FOR RELIABLE PERFORMANCE  amp  LONGER LIFE  The thickness of the positive plate Thicker is better for durability   The material used for the battery posts Copper inserted posts operate more efficie
176. ons like refrigeration  heating  and cooling may tolerate loss of power for  several minutes  or longer  without any adverse effects  For data processing equipment  it may  be necessary to maintain power until the equipment can be shut down in an orderly manner  This  process may take only a few minutes  Alternatively  life support  safety  communications and  security equipment  and other applications may require continuous power until primary power is  restored  Restoration of primary power could take hours or even days  A survey of commercial  power outages may be necessary to determine this information  If commercial power outages are  historically infrequent and last only a few minutes or hours  it may not make economical sense to  install an UPS capable of supplying power for several days  Table 3 1 lists some general criteria          Power Needed Maximum Tolerable Power Recommended Minimum Type of Auxiliary Power    Failure Duration Auxiliary Supply Time Emergency Standby Justification for UPS               For Purpose          Lighting    Startup Power    Startup Power   continued     Transportation    Signal  Circuits    Mechanical  Utility  Systems    Evacuate Personnel    Illuminate  perimeter  amp  for  security  Provide warning    Restore normal  power system  Provide general  lighting  Provide power to  hospitals and  medical areas    Facilitate orderly  shut down  Startup power for  boilers    Startup power for    air  compressors  Power for elevators    Power
177. or fault clearing capability  capability of supplying currents for high inrush  loads  and isolation from harmonic distortion generated by non linear loads in the line  Rotary  UPS bearings must be replaced periodically  Although this might make reliability between the  two types debatable  bearing failure is highly predictable with stringent routine testing  Rotary  units produce more heat than do static units due to their M G sets  They are more costly for small  capacities but become competitive with static units around 300 kVA  Rotary units provide  complete electrical isolation where the static UPS is limited by the static switch  Extremely high  voltages or rapidly rising voltages can pass through the static switch and damage critical loads        Control  AC Input Panel          from prim ary power  Solr ce   O Engine Generator    AC Output   to load         Motor   G ener ator             Figure 1 2  Rotary UPS  shown with primary power on     1 2    TM 5 693    1 5  Design criteria and selection    The UPS selection process involves several steps as discussed briefly here  These steps are  discussed in further detail in chapter 3     a  Determine need  Prior to selecting the UPS it is necessary to determine the need  The  types of loads may determine whether local  state  or federal laws mandate the incorporation of an  UPS  An UPS may be needed for a variety of purposes such as lighting  startup power   transportation  mechanical utility systems  heating  refrigerat
178. or has a weight carrying capacity that exceeds the load of the batteries and racks  The battery  room should be provided with sufficient ventilation to prevent hydrogen gas accumulation in the room  air  The ventilation equipment should be such that the battery room air is changed 2 5 times each hour   The objective of the room ventilation is to keep the hydrogen concentration in the room air to less than 1  percent by volume  If it is required to establish that the ventilation of the battery room is adequate  then  it is necessary to calculate the rate of evolution of hydrogen gas in the room  The following method is  used     C22 ee          X   xKxN  1000 100  on     0 01  Where  C   Cubic feet of hydrogen per hour   FC   Float current  in milliamperes per 100 AH  temperature compensated   AH   Ampere hours  K   Constant      1 AH   0 016 cubic feet of hydrogen  N   Number of cells  A   New air required  0 01   1 percent maximum concentration of hydrogen    It is also important to maintain the average ambient room temperature at around 77  F  Higher  average ambient temperatures substantially shorten the life expectancy of lead calcium batteries   An average ambient temperature of 95  F shortens the life expectancy by about 50 percent  The  NEC insulation restrictions require that battery strings rated over 250 volts be installed in groups having  a total nominal voltage of not over 250 volts on any one rack  Sectionalizing protection for each 250  volt group is highly rec
179. or starts and picks up load  and the battery  returns to float mode  Measure voltage and current at UPS and ensure a bumpless transfer is  made  Close the utility breaker  Verify the transfer switch transfers to the utility  the battery  picks up load during transfer  the diesel generator stops  and the battery returns to float after the  utility picks up load  Measure voltage and current at UPS bus and ensure a bumpless transfer is  made      4  Inverter A to inverter B loaded transfer test  Verify the UPS is loaded and connected  to the utility  Open inverter A incoming breaker and verify the static switch switches to inverter  B  Measure voltage and current at UPS bus and ensure a bumpless transfer is made  Close  inverter A incoming breaker and verify that the static switch switches to inverter A  Measure  voltage and current at the UPS bus and ensure a bumpless transfer is made      5  Battery discharge test  Verify the UPS is loaded and connected to the utility  and  notify the plant of pending UPS trip  Open the diesel generator breaker and block auto and  manual start  Open the utility breaker  Verify the battery picks up load and measure battery  voltage and current  Measure the UPS voltage and current and ensure a bumpless transfer is  made  Operate the UPS from the battery until the battery minimum voltage is recorded  1 to 4  hours   Verify inverters A and B trip when the batteries reach minimum voltage  Notify the plant  of pending UPS re energization  reclose th
180. ors will probably cause problems  especially for generators supplying more than a 25   percent non linear load  Provide line filters to suppress the harmonics emanating from the power  source  Increase power source capacities so as to lower output impedance and minimize voltage  distortion  Use UPS outputs which have no neutrals  Where neutral voltages are required   provide isolation transformers as close to their loads as possible to shorten oversized neutral  installations  Use true RMS sensing for circuit breaker trip units  relays  meters  and instruments     o  Advantages and disadvantages of static UPS systems  Static UPS systems have several  advantages  They provide disturbance free uninterrupted power  operate at low sound levels  have  high reliability and short repair times  require minimal maintenance  simple installation  and lend  themselves to future expansion and reconfiguration  However  they also have some  disadvantages  Some of the disadvantages are that they introduce harmonics into the power  supply system  have a high initial cost to purchase  require large space  require regulated    2 28    TM 5 693    environment  require skilled technicians for trouble shooting and repairs  and have a somewhat  low efficiency     2 2  Principles of rotary UPS systems    The most basic UPS system is the inertia driven ride through system  This system consists of a  synchronous motor driving a synchronous generator with a large flywheel as shown in figure 2   20  Dur
181. osa       TM 5 693                   Figure 2 10  Three phase uncontrolled single way rectifier     c  Three phase bridge rectifier with a resistive load  The following equation models  the voltage output of the three phase bridge rectifier with a resistive load     II  Ex      E  1 sin  ea     TM 5 693          wl   N  3    T  3        gt  wt             Figure 2 11  Three phase uncontrolled bridge rectifier     d  Three phase bridge rectifier with an inductive load  The following equation  models the voltage output of the three phase bridge rectifier with an inductive load     E     E   cosa    2 12    TM 5 693    where  Eao   average dc voltage at no load without phase control  neglecting the  voltage drop in the circuit elements   Ego Q    average dc voltage at no load with phase control at firing angle a   neglecting the voltage drop in the circuit elements         Figure 2 12  Single phase controlled bridge rectifier    TM 5 693       Figure 2 13  Three phase controlled bridge rectifier    h  Inversion  Inversion is the conversion of dc power to ac power  Inversion can be  accomplished using SCRs or IGBTs  In high power applications  IGBTs have been used   Inverters for static UPS systems can be single phase or three phase  Single phase inverters are  used in ratings up to approximately 75 kVA  at higher ratings three phase inverters are used      1  Inverter principles  The basic elements of a single phase inverter are shown in figure  2 14  When SCRs 1 and 4 are turne
182. ounded  so touching a live part will  not result in a shock  The real hazard exists when an accidental ground is already present and a  person touches a live part  In this case  the person completes the circuit to ground and current  will flow through the person  Sometimes personnel may recognize that the hazard exists but do  not seem concerned because the cell voltage is only 1 2 to 2 volts per cell nominal  Another  hazard is when an accidental connection between positive and negative points is such as to cause  a dangerous potential gradient      a  Possible effects  Batteries used for large UPS systems often contain 188 or 192  individual cells connected in series  to form a string  representing approximately 500 volts  In  addition  multiple strings may be connected in parallel to serve an UPS system  Another fact to  consider is the short circuit current a battery can deliver  The short circuit capability of any  battery can be obtained from the manufacturer  For example  a battery of one manufacturer that  provides backup for a 500 kVA UPS for 15 minutes is capable of delivering approximately  23 000 amperes into a zero resistance short circuit      b  Accidental grounds  It is not uncommon to find that a ground does exist on a  battery  One way in which this occurs is that electrolyte on top of a cell will track across the  cover  down the plastic jar  and contact a metallic part of the rack  The electrolyte  being  conductive  establishes the ground path      c  Nor
183. ply and conditions for transfer to the safety source for  such electrical equipment are covered by applicable regulations     Safety Power Source   see Power Source  safety       TM 5 693    Sag   A low voltage condition in which the voltage on one or more phases of ac power falls below 80  to 85 percent of the nominal value for more than one cycle  1 60  of a second for 60 cycle ac    Can be caused by ground faults  starting large loads  inadequate power supply  utility switching   utility equipment failure  and lightning  Can cause computer crashes and damage equipment     Secondary Battery   A battery that may be restored to its charged state after discharge by passing an electrical current  through the cell in the opposite direction to that of discharge  Also called a storage or  rechargeable battery     Single UPS   see UPS  single      Single UPS Cubicle  see Cubicle    single UPS  unit     Standby Power   An independent reserve source of electric energy that  upon failure or loss of the prime source   provides electric power of acceptable quality so that the facility may continue operation in a  satisfactory manner  which could include an orderly shutdown      Standby Redundancy   see Redundancy  standby      Static Bypass Switch   Power electronics device that can be used to switch from one source to another without  interruption in the supply of power  In an UPS  transfer is from Mains 1 to Mains 2 and back   Transfer without interruption is possible due to the fact 
184. pment should be verified  After  completion of the above inspections the battery is ready for charging  After charging  measure  each cell voltage and total battery voltage  with charger in float mode of operation   ac ripple  current  specific gravity  electrolyte temperature  visually check fill level   overall float voltage at  the battery terminals  charger output current and voltage  and ambient temperature  Also check  the condition of ventilation and monitoring equipment and the temperature of the negative  terminal of each cell of the battery  When the battery is charged  use a voltmeter to check the  polarity of the series connections  The total voltage should be measured both across the battery  and between adjacent cells and should be compared to the specified voltage  The total voltage  should approximately be the resultant of the quantity of cells multiplied by the typical cell  voltage  A variation is an indication that the battery may be improperly assembled      a  Discharge test  For the acceptance test the discharge rate should be at a constant  current or constant power load equal to the manufacturer   s rating of the battery  The charging  method used as a basis for published data is an important factor  For a stationary float  application  data based on prolonged constant potential charging should be used  If constant  current charging has been used to establish the published data  appropriate float charging    4 14    TM 5 693    correction factors shoul
185. r voltage readings are taken  Normally  only a representative sample of  cells is checked for electrolyte temperature  IEEE 450 recommends checking every sixth cell   even when each cell s voltage and specific gravity are read  These readings are used to correct  specific gravity  along with the electrolyte level correction  and voltage to a standard reference  temperature in accordance with instructions in IEEE 450  The standard reference temperature    5 11    TM 5 693    and correction for batteries not manufactured in the United States should follow the  manufacturer s recommendations  Operation of a battery on a higher or lower reference  electrolyte temperature will affect that battery s performance and life      a  Differential temperature  Differential temperatures between cells can be a  problem  if the electrolyte temperature differential between any two cells is greater than 5  F   This problem normally occurs when one portion of a battery is located near a localized heat  source such as a window that allows the sun to shine on a portion of the battery  or when a battery  rack with more than two steps or tiers is used  A battery temperature differential will cause some  cells to be overcharged and some cells to be undercharged      b  Ambient temperature  Ambient temperature of the battery area should be read and  recorded periodically even where the room or area is environmentally conditioned  Battery  performance is based upon the cell electrolyte temperature  wh
186. r will be located outside of the  main plant  Personnel will be isolated from the noise of the diesel  Separate HVAC will ensure  that exhaust and battery fumes  the battery is vented  are properly vented and that the battery will  not be operated at temperatures above 25  C  The engine is a proven design  used for many years  in similar applications  and has a good safety record     6  Is selected UPS availability acceptable  The UPS can start  come up to speed  and take up  the load within 3 seconds  The reliability of the UPS in previous applications is equivalent to  about a 200 hour mean time between maintenance  MTBM   Preventive maintenance procedures  were developed using a reliability centered maintenance  RCM  approach and allows  maintenance personnel to keep the unit in    like new    condition with a minimum of expense  The  average time to repair a failure is less than 5 hours  so the availability is  9756     7  Is selected UPS maintainable  As already stated  the diesel generator has a proven record  of low maintenance and has excellent preventive maintenance procedures  Since ABC  Inc    operates and maintains its own fleet of diesel powered trucks  and will operate and maintain  many alternating current  AC  motors in the plant  Mr  Public feels that maintenance can be done  internally  Major repairs  such as overhauls  will be outsourced     8  Is cost of UPS acceptable  The price of the diesel generator is  60 000 and construction of  a separate building w
187. ration where both units are required would be   Ai  Ay X A2   0 925    The availability could be increased by increasing the reliability or reducing the MTTR  The reliability  could be increased by selecting a more reliable unit  derating the unit  i e   use a unit capable of providing  more power than needed   when used  it will be operating below its capacity thereby reducing stresses    or use redundancy  see 3 1f   MTTR could be decreased by selecting an inherently more maintainable  system or perhaps by improving diagnostics  training  or procedures      1  UPS reliability  Reliability is a function of the design of the UPS  the configuration  selected  and the parts used  The environment that the UPS is installed in also plays a role in the  reliability of the UPS  Environmental factors such as excessive heat  cold  humidity  and or dust  can all have a significant effect on the UPS reliability  Another significant factor in UPS reliability  is the configuration  The different UPS configurations were discussed in paragraphs 2 3 and 2 4   Redundancy reduces the overall failure rate of the UPS because one failure does not cause the UPS to  fail  The example in figure 3 4 illustrates why this so     As discussed in paragraph 2 3c  two units may be placed in parallel where each is capable of  supplying 100 percent of the load or three units may be placed in parallel where each is capable  of carrying 50 percent of the load  The earlier case where one of two units is require
188. re being used in static UPS systems  These batteries have a long lifetime of 25    2 21    TM 5 693    years  However  because of their initial cost their use is not as common as the flooded lead acid  type      a  Ni cad design  The ni cad battery cell consists basically of a nickel hydroxide  positive electrode  a cadmium hydroxide negative electrode  and a potassium hydroxide solution  as an electrolyte  As the cell discharges  the nickel oxide of the negative electrode is changed to a  different form of oxide and the nickel of the positive electrode is oxidized  On charge the reverse  action takes place  Also  hydrogen and oxygen are evolved by the positive and negative  electrodes  respectively  as the cell reaches full charge  However there is little or no change in the  electrolyte s specific gravity      b  Ni cad voltage  The nominal voltage of a ni cad cell is 1 2 volts while the open  circuit voltage is 1 4 volts  The electrolyte specific gravity is approximately 1 180 at a  temperature of 25  C  77  F       c  Ni cad rate design  Ni cad batteries are also available in one of three designs of  high  medium  or low rate power delivery  The high rate batteries are the most commonly used in  the application of UPS systems      d  Advantages  These batteries are resistant to mechanical and electrical abuse  They  operate well over a wide temperature range of    20  C to 50  C  Also  they can tolerate a complete  discharge with little damage to the capacity of the batte
189. re of continuous duty induction motors is  based on horsepower output  maximum ambient temperature for which motor is designed  speed  at full load  frequency  number of phases  voltage  full load current  and lock rotor  starting  KVA      3  DC motors  The NEMA rating structure of continuous duty dc motors is based on  horsepower output at base speed  maximum ambient temperature for which the motor is designed   base speed at rated load  armature voltage  field voltage  armature load current at base speed  and  winding type   shunt  series  or compound      4  Synchronous generators  The NEMA rating structure at synchronous generators is  based on kVA output  output power  kW   power factor  maximum ambient temperature for  which the generator is designed  speed  voltage  full load current  number of phases  frequency   excitation current  and excitation voltage     c  Flywheel sizing  The flywheel inertia is selected such that the stored energy is sufficient to  supply the generator while operating at rated power for a duration not exceeding 0 5 second while  keeping the speed from falling to maintain the frequency drop to a maximum of 0 5 Hz  The  flywheel inertia plus the inertia of the coupled motor s  and generator make up the total inertia of  a rotary UPS system  The flywheel inertia is usually more than 95 percent of the total inertia and  the motor s and generator s inertias can be neglected  The required flywheel inertia  WK     can be  calculated as follows      
190. reaker s contact resistance by passing a moderate to  high current through the connection under test and measuring the voltage drop which is converted  at the meter output to microohms  These measurements are difficult to perform  especially when  the cells have multiple posts per cell and multiple inter cell connectors per post  In these cases   multiple measurements per cell must be made or there will be significant errors in the  measurement  The test  performed at the initial installation  should be repeated periodically and  the results compared  High connection resistance  if not detected  can cause severe damage in a  stationary cell required to discharge at a high current rate for a period of time  as in an UPS  application  High connection resistance can actually melt battery posts     5 13    TM 5 693     9  Battery rack  Battery racks should be checked during visual inspections  Included are  checks for structural integrity  corrosion  and proper grounding      a  Corrosion  The check should include an inspection of the corrosion resistant  covers  e g   plastic channels  normally installed on the rack materials where the jars rest  Clean  any corrosion found and recoat the rack using a chemical resistant coating  in accordance with the  manufacturer s instructions  Replace cracked or broken corrosion resistant covers      b  Seismic  Additional checks of the rails and spacers must be made  if the battery  rack is a seismic type that is designed for use in installa
191. redundant system  a cold standby redundant system  and a dual redundant system with static  transfer switches     a  Non redundant system  The non redundant static UPS system shown in figure 2 22 is the  basic system described in paragraph 2 1  One major limitation in this configuration is that failure  of the inverter leads to the loss of power to the supplied loads  This limitation makes this  configuration undesirable except for supplying redundant loads where the loss of one load group  does not impact operation  Another limitation is that due to the limited overload capability of the  inverter elements  it is not suitable for supplying loads with high inrush current requirements       nea i S a OER INVERTER y LOAD  oe ee as ie      BATTERY       Figure 2 22  Non redundant static UPS system    b  System with static bypass switch  The static UPS system with a static transfer switch is  shown in figure 2 23  It is made up of the basic system with the addition of a static transfer  switch to transfer to an alternate ac source  Normal operation of this system is basically the same  as the basic system as described in paragraph 2 1  In addition  the static transfer switch sensing  and logic circuit continuously monitors the inverter output voltage and initiates a load transfer to    2 33    TM 5 693       ALTERNA IE  A e a              URLE SYNCHRONENG  SIGNAL E  SIGNAL STATIC    ian  SWITCH Shere  NORMAL kirE  O o elas INVERTER  SOURCE it    BATTERY             Figure 2 23  S
192. rformed as  required  If the skills and resources required for the maintenance of the unit are not available  it  may be necessary to select a unit requiring less maintenance     e  Determine if affordable  The selected UPS must be affordable  While this is the most  limiting factor in the selection process  cost cannot be identified without knowing the other  parameters  The pricing of the unit consists of the equipment cost as well as the operating and  maintenance costs  Disposal costs of the unit should also be considered for when the unit reaches  the end of its life     f   Re evaluate steps  If these criteria are not met  another UPS system must be selected and  these steps re evaluated     1 6  Installation and testing    The installation and testing of the UPS is critical to its proper operation  These items are  discussed in greater detail in chapter 4     a  Features  The UPS shall be installed with all necessary features  Features such as alarms   indicators  control devices  and protective devices are installed to assist in the safe operation of  the unit  Power and control components such as meters  indicating lights  control switches  push  buttons  and potentiometers are typically located in a nearby cabinet  Batteries are typically  installed on battery racks  The design of the racks varies based on the available space and  number of batteries     1 3    TM 5 693    b  Location  The UPS shall be installed on a level surface with sufficient clearance to allow 
193. rger  Normal  Hydrometer set Normal  Microohmmeter Normal  Portable infrared temperature measuring device Normal  Terminal protective grease Normal  Thermometer set Normal  Torque wrench Normal  Chemical resistant gloves Safety  Goggles and face shield Safety  Protective aprons or suits and shoes Safety  Rubber matting Safety          4 22             TM 5 693    Table 4 9  Suggested test equipment list for troubleshooting an UPS module          Item   Analog multimeter   Digital multimeter   Dual trace oscilloscope   Load bank   Phase rotation meter   Portable ammeter   Portable clamp on current transformer   Portable infrared temperature measuring device  Built in test equipment board   Diagnostic printed circuit board  PCB  and all related parts  Extender cable kit   Capacitor shorting device   Rubber matting       Disposition  Normal  Normal  Normal  Normal  Normal  Normal  Normal  Normal   Manufacturer   Manufacturer   Manufacturer  Safety  Safety       4 23       TM 5 693    CHAPTER 5    UNINTERRUPTIBLE POWER SUPPLY  UPS  SYSTEMS  MAINTENANCE PROCEDURES    5 1    Maintenance for UPS systems    A general guide for the maintenance requirements of the UPS systems modules  static switches   and controls is provided  Although electronic components are not subject to wear in the same  degree as electromagnetic  EM  components  they do require systematic maintenance  A  standard maintenance procedure cannot be developed for all types and sizes of UPS units  The  manufacturer s
194. rmonic content  The harmonic currents generated can also cause additional losses and heating  in the generator  This may require derating the generator if the harmonic content of the load  current is excessive  The generator manufacturer should provide the derating recommendations  which are based on the nature as well as the level of the non linear loads      2  Loads with high inrush current  Unlike a static UPS system  a rotary UPS system is  capable of supplying high inrush currents at reduced voltages  The level of voltage reduction is  more gradual than for the static inverter and depends on the generator transient reactance      3  Unbalanced loads  The unbalanced load capability of a rotary system is less than that  of a comparable static UPS system  A synchronous generator has a very limited negative  sequence current capability  Highly unbalanced loads produce high negative sequence currents  which cause severe overheating     d  Affect of the rotary UPS system on the power supply system  Due to the high starting  current required by ac motors  a rotary UPS system may cause the reduction of the power supply  system voltage during startup  The duration of the voltage reduction is dependent on the motor  type and the system inertia  It could be as long as 10 or 15 seconds  The power factor of a  system with a synchronous motor can be made leading by adjusting the motor excitation level   This means that the motor can be made to supply reactive power to the power suppl
195. robably not needed     A critical function is defined as one requiring electrical power and for However  determine if  which a power outage of some specified duration is unacceptable ambient light always  due to safety or financial considerations sufficient during facility use       Figure 3 2  Determine the facility need for an UPS    b  Determine the purpose of the UPS  An UPS may be needed for a variety of purposes   These include emergency lighting for evacuation  emergency perimeter lighting for security  shut  down or continued operation of manufacturing equipment or computer operations  continued  operation of life support or critical medical equipment  continued operation of communications   and safe operation of equipment during sags and brownouts  Some facilities need an UPS for  more than one purpose  In any case  the purpose s  must be known before proceeding because it  determines many factors that will drive the amount of power required and the type of UPS that  will be needed  These factors are the acceptable delay between loss of primary power and  availability of UPS power  the length of time that emergency or backup power is required  and the  criticality of the load that the UPS must bear  Applications such as hospital life support and  safety  aircraft tracking and landing  and certain production process controls and data processing  cannot tolerate any loss of power  no matter how short the period of time  without loss of life or  revenue  Other applicati
196. rrent clutch is reduced so as to maintain the generator  frequency at 60 Hz  The generator frequency can be maintained above 59 5 Hz for up to 15  seconds after loss of ac input power  This configuration is most suitable where a backup power  source such as a diesel generator or gas turbine is available  The rotary system can supply the  loads until the backup source is started and operated to supply the motor  However  the use of  this configuration is becoming less common and it is not available from many manufacturers        FLYWHEEL    EDOY CURRENT          CLUTCH  AC    i ha      sauet     ar steseececedl EENES    4    oLOaAL        AC GENERATOR    FREQUENCY  CONTROLLER              Figure 2 29  Inertia driven ride through system with an induction motor and an eddy current clutch    d  Battery supported inertia system with a dc motor  The battery supported inertia system  with a dc motor is shown in figure 2 30  The ac motor may be a synchronous or a low slip  induction motor  The frequency regulation of systems using an induction motor is the same as  the inertia driven ride through system described in paragraph 2 2  This configuration is required  at installations where the power supply is of low reliability and long term interruptions are  common  This type is no longer manufactured  however  there may be some still in use     2 38    TM 5 693       BAT TRY  A t i h 5 H ki l k f   i SAD  soarce    A p A mel G J    aloa  i a inau knu r  SYNCH oo AC  MOTOR MOTOR GENERAT
197. rs  Thousands of short  circuits between the positive and negative plates will occur when the battery is recharged after  hydration  Hydration can also occur when a dry charged battery is mistakenly filled with water  instead of the electrolyte solution      g  Frozen electrolyte  In the required environment  it is very unlikely that the  electrolyte will freeze since nominal 1 200 specific gravity lead acid electrolyte only starts  forming slush at approximately  20  F  But  during discharge  a lead acid cell s specific gravity  decreases  and there is a resultant increase in the temperature at which slush could form  freezing  would then begin at 16  F if the specific gravity decreased to 1 100  Irreparable damage occurs  when ice crystals form within the battery  even though damage may not be visible  In essence     5 10    TM 5 693    the frozen electrolyte will cause the active materials to expand and lose contact with the grid   The frozen electrolyte can also cause structural damage to the jar      2  Cleaning  It is recommended that batteries be kept clean at all times  The battery cells   battery connections  and battery vent caps shall be kept clean and free of corrosion to maximize  the battery lifetime      a  Battery cells  Jars or covers should be wiped with a clean lint free cloth or wiper  moistened with clean water  The cloth should be moistened to clean any electrolyte spilled on the  cover or jar with a suitable neutralizing agent  Wipe with a clean dry clo
198. rty damage  Lessen losses due to  legal suits    Lower losses from theft and property damage  Lower insurance rates  Prevent injury     Prevent or reduce property loss  Comply with building codes and local  state  and  federal laws  Prevent injury and loss of life   Reduce risk of extended power and light outage due to a longer repair time     Prevent loss of sales  Reduce production losses Lower risk of theft  Lower insurance  rates    Facilitate continuous patient care by surgeons  medical doctors  nurses  and aids   Comply with all codes  standards  and laws  Prevent injury or loss of life  Lessen losses  due to legal suits     Prevent injury  loss of life  and property loss by a more orderly and rapid shutdown of  critical systems  Lower risk of theft  Lower insurance rates    Restore production  Prevent property damage due to freezing  Provide required electric  power    Restore production  Power instrumentation     Safeguard personnel  Evacuate building  Continue normal activity    Complete production run  Permit orderly shutdown  Continue normal activity   Evacuate building  Continue normal activity    Prevent loss from theft  arson  or riot  Maintain security systems  Comply with codes   standards  and laws  Lower insurance rates  Alert operators to critical out of tolerance  temperature  pressure  water level  and other hazardous or dangerous conditions   Comply with local  state  and federal codes  standards  and laws  Prevent personnel    injury  Prevent property a
199. rvice life  IEEE 450 and  IEEE 1106 require a performance test  a current capacity test which discharges a battery to a  designated terminal voltage to detect any change in the capacity determined by the initial test   within the first 2 years of service and then recommends performance tests at 5 year intervals until  the battery shows signs of degradation or has reached 85 percent of the service life expected   Degradation of lead acid batteries is indicated when the battery capacity drops more than 10  percent of rated capacity from its capacity on a previous performance test or is below 90 percent  of the manufacturer s rating  Degradation of nickel cadmium  ni cad  batteries or extensive  capacity loss is indicated when the battery capacity drops more than an average of 1 5 percent per  year of rated capacity from its previous performance test capacity  Then annual performance  tests must be provided  Perform tests in accordance with IEEE 450 or IEEE 1106 requirements      2  Inspections  Inspections should be made under normal conditions and performed on a  regularly scheduled basis  Tables 5 2 through 5 5 provide general checklists to be performed on  a weekly  monthly  quarterly  and annual basis  Refer to the appendices of IEEE 450 and IEEE  1106 for more information  The inspections recommended in this manual are in excess of IEEE  requirements     Table 5 2  Weekly battery inspection       Check and record the overall float voltage at the battery terminals  not at t
200. ry      3  Lead acid vs  ni cad batteries  Lead acid batteries are about 50 percent less expensive  than an equivalent ni cad battery  the ni cad batteries exhibit a longer life and a more rugged  construction  Also the ni cad battery requires less maintenance than a lead calcium battery   However  a ni cad battery requires approximately 53 percent more cells than a lead acid battery  at the same voltage  Lead acid batteries are more susceptible to high temperature than ni cad  batteries  The life of a lead acid battery is reduced by 50 percent for every 15  F increase in  electrolyte temperature while a ni cad battery loses approximately 15 percent of its life  It should  also be noted that lead acid batteries release more hydrogen during recharging than ni cad  batteries     k  Battery charging  During initial operation  the battery requires charging  During normal  operation  local chemical reactions within the cell plates cause losses that reduce the battery  capacity if not replenished  Also  these local chemical reactions within the different cells occur at  varying rates  In lead acid batteries these local reactions over long periods of time cause unequal  state of charge at the different cells  In addition  it is required to recharge the battery following a  discharge  Therefore  the battery charger should provide the initial charge  replenish the local  losses to maintain the battery capacity  equalize the individual  lead acid  cells state of charge   and recharge t
201. ry  between 1 160 and 1 190 at 77  F  depending upon the manufacturer  Lower specific gravities are  generally used in cells with larger electrolyte reserves  Higher specific gravities are typically  used for low temperature applications  The specific gravity will decrease slowly over the years  because of evaporation and other effects  even though the surface of the electrolyte is probably  covered with a protective layer of oil  Renewal will be necessary if the specific gravity decreases  to 1 130 to 1 160  depending upon the manufacturer s instructions      c  Temperature correction  Ratings are at 77  F  25  C   Therefore  to determine  specific gravity  which is temperature sensitive  a temperature correction factor must be applied   For both lead acid and ni cad batteries  add one point   001  to the hydrometer reading for every  3  F above 77  F and subtract one point for every 3  F below 77  F      4  Ambient temperature  The usual controlled environment provided for batteries should  eliminate temperature correction while a 100 percent UPS inverter capacity normally allows an  adequate kW design margin  The life of a battery in comparison with an UPS system  which may  be outdated and replaced in much less time  may mean that the aging factor is not of such great  importance     c  Computation sheets  The typical computation sheet in appendix B is intended for  calculating the kVA rating and inrush capability of a single phase static UPS system with static  bypass sw
202. s  IGBT   The devices most commonly used are the SCRs and the IGBTs  The IGBTs  are relatively new and have been gaining in popularity  The IGBTs are significantly more  efficient and easier to control than the other power semiconductors  The use of IGBTs has  allowed for static UPS as large as 750 KVA without paralleling units      2  Single phase SCR characteristics  An SCR allows for forward flow of current through    the device similar to a diode  The SCR differs from a diode in that the SCR will not conduct until  a current pulse is received at the gate  Once the SCR is conducting  it will only turn off with the    2 6    TM 5 693       Legend    A   anode  K   cathode   d  amp    Source  d   diode                Figure 2 6  Half wave diode rectifier with resistive load    current falling to zero or through a reverse current being applied  Referring to figure 2 7  the  anode voltage is positive relative to the cathode between wt   o and wt   q  the SCR begins  conducting when a firing pulse is applied at wt   a  Here     is called the firing angle  Also  the  SCR blocks at wt  gt  7 when the anode voltage becomes negative relative to the cathode  The SCR  does not conduct again until a firing pulse is reapplied at wt   27       While turning on the SCR  is very efficient  the SCRs require a commutation circuit to turn it off  It is necessary to be able  to turn off the device for use in the inverter to generate the ac wave  The turn off time is slow in  comparison to the
203. s also important  Another party might be able to maintain the required stock levels at  a lower cost and might be able to make repairs in a shorter time  On the other hand  many  contractors require time  typically 24 hours  to respond to a problem  This additional time may  result in large losses of revenue  Even if internal repair is more expensive  the added cost may be  more than offset by the savings in revenue     h  Determine if the selected UPS is affordable  Although discussed as the last step in the  selection process  affordability is often a limiting factor in the selection of an UPS  It is placed  last because the pricing of the UPS can only be done when the type  configuration  and sizing are  known  These parameters cannot be known until the steps in paragraph 3 1 have been completed   When considering the cost of an UPS  or any product  for that matter   it is best to consider the  total cost  or life cycle cost  that will be incurred   See figure 3 6 that describes the process for  determining affordability   For an UPS  the total cost includes the purchase price  installation  cost  operating and support costs  and disposal costs  The acquisition and installation of the    Develop Cost l    Acquisition Cost Purchase Price                 Initially  selected UPS        Projected maintenance costs        Projected disposal costs             s Another Type of UPS  unctionally Acceptable        Take Management Action       Reassess items requiring UPS    Reasses
204. s duration of UPS    Increase budget             Figure 3 6  Determining affordability requires that all costs be considered    TM 5 693    UPS typically constitute the greatest portion of the life cycle cost  A static UPS will cost between   100 and  250 000 while the cost of a rotary ranges between  5000 and  1 000 000 for single  units  The cost of any needed auxiliary equipment must also be considered  At a minimum  a  manual bypass switch is required to disengage the UPS from the input power and load during  maintenance or repair  These switches are typically integrated into a static UPS but are stand   alone items with rotaries  In the latter case  the switches require additional cabling and support  hardware  More sophisticated systems having automatic monitoring  switching  and control  functions requiring additional components  adding to the complexity and cost of the system s    As part of the installation costs  the costs associated with needed facility modifications should  also be considered  If the UPS is operated under adverse conditions  availability will suffer   Specific precautions must be taken for dirty  hot  cold  corrosive  explosive  tropical and other  adverse conditions  Additional air conditioning might be required for the UPS  or for the facility  due to heat loads from the UPS   Rotary units may require additional or special ventilation  equipment to purge toxic fumes from working areas  Floor units  usually static UPS for computer  system backup 
205. s have low cycle  capabilities because each recharge means a possibility of some gassing  resulting in the ultimate  failure of the cell when it eventually dries out     2 23    TM 5 693     3  Charging discharging considerations  A battery cannot function without a charger to  provide its original and replacement energy  A well designed charger will act to charge a  discharged battery by maintaining the correct balance between overcharging and undercharging  so as not to damage the battery  Additionally  the charger must assure that battery discharging is  limited to the point where the cells approach exhaustion or where the voltage falls below a useful  level  usually about 80 percent of the battery s rated capacity   Overcharging results in increased  water use  and over discharging tends to raise the temperature  which may cause permanent  damage if done frequently      a  Current flow  Batteries are connected to the charger so that the two voltages  oppose each other  positive of battery to positive of charger and negative to negative  Battery  current flow is the result of the difference between the battery and the charger voltages and the  battery s extremely low opposing resistance  The voltage of the battery rises during charging   further opposing current flow  Chargers are designed to limit starting charging currents to values  that keep equipment within a reasonable size and cost  They must also maintain a sufficiently  high current throughout charging so that at 
206. s of the inverter  The UPS battery design strives for excellent short term  high rate   current characteristics and this demands the lowest possible internal cell resistance  This low  resistance can serve as a better short circuit path for the ripple voltages coming out of the rectifier  stage of the UPS than can the filter capacitors in the output rectifier  Also  the inverter stage of  the UPS demands large instantaneous dc currents as it builds ac power from the parallel  rectifier battery combination  If the UPS is located some distance from the commercial ac power  source  the short term instantaneous currents must then come from the battery  These factors can  result in a relatively high ac component in the UPS battery  The relative detrimental effects of  ripple current on the battery are mainly a function of the design of the UPS  the comparative size  of the battery as compared to the UPS rating  and the battery type  Ripple current tends to heat  the batteries and is equivalent to constantly discharging and recharging the battery a tiny amount   Ni cad cells can be adversely affected by ripple currents although they provide a very good  filtering capability  Lead  being much softer than nickel  requires different plate construction  techniques which make lead acid batteries even more susceptible to harmful effects from ripple  currents  Usually ripple currents of less than 5 percent over the allowable continuous input range  of the battery will not be harmful to le
207. s than weekly checks  Personnel  involved in status monitoring should be those most concerned with the equipment s proper  functioning      a  UPS systems in computer rooms  Computer room operating personnel should  become familiar with the equipment and its various operating indications  They should maintain  records on all findings or occurrences during preventive maintenance  The operating personnel  shall check all lamps on mimic bus and alarm status indicators  They shall have maintenance    5 2    TM 5 693    personnel replace inoperative bulbs  Also  they shall check input  output  and bypass voltages  and currents and all other system status readings and compare them to the required specifications   A copy of the requirements which must be met  exceeded  or not exceeded should be included as  a part of the inspection checklist  Maintenance personnel shall be called to apply troubleshooting  procedures if abnormal values are indicated  Operating personnel may also ensure adequate  ventilation and cooling by checking that all fans are operational  ensure all doors  drawers  and  covers are secured  and check for unusual noises and odors      b  UPS system in dedicated UPS rooms  These systems will normally have remote  displays and alarms  Display panels usually indicate problems only to the extent that they affect  computer operations  Summary alarms keep the information simple and easy to understand  A  usual system would include  on battery    battery near discharge 
208. sely influence the overall electrical systems      3  Neutral harmonic behavior  Harmonics are integral multiples of the fundamental  power  60 hertz  Hz   frequency  Odd order harmonics are additive in the common neutral of a  three phase system  For pulsed loads  even order harmonics may be additive if the pulses occur  in each phase at a different time so that they do not cancel in the neutral  This results in  overloaded neutrals and becomes a fire safety concern  ITIC recommends providing double   capacity neutrals  Section 310 4 of the National Electrical Code  NEC  suggests installing  parallel conductors to alleviate overheating of the neutral in existing installations where there is  high harmonic content  Balanced neutral current buildup due to harmonics can be as high as 1 73  times the phase current  Under unbalanced conditions  neutral current can be as much as three  times the phase current for worst case  pulsed loads  Oversized  that is per normal linear load  applications  neutrals should be a requirement wherever solid state equipment is installed      4  Harmonics and equipment ratings  Transformers  motors  and generators are rated on  the heating effects of an undistorted 60 Hz sine wave  At higher frequencies  hysteresis and eddy  current losses are increased  and the conductor s skin effect decreases its ampacity  Substantial  harmonic currents therefore will result in substantial heating effects  which means that the  equipment loads must be decreased 
209. ses of constant amplitude and different widths  The  output voltage is synthesized from this train of pulses as shown in figure 2 16  The output  voltage level can be controlled by varying the width of the pulses  By this technique the output  voltage wave shape can be made to closely approximate a sine wave  Also  it is feasible to  eliminate all harmonics by the use of this technique  This eliminates the use of output filters   Inverters using this technique have lower impedance and faster transient response  The control is  accomplished by feedback control as in the pulse width control technique        Figure 2 16  Pulse width modulation  PWM      c  Use of a ferroresonant transformer  A ferroresonant transformer connected across  the inverter s output can be used to regulate the output voltage and reduce its harmonic content   The ferroresonant transformer is basically a two winding transformer with an additional small  secondary compensating winding and a series low pass filter connected across part of the main  secondary winding as shown in figure 2 17  The filter presents a low impedance to the lower  order harmonics and reduces their amplitude in the output to a low acceptable value  The  compensating winding voltage is added to the secondary output voltage 180   out of phase thus  maintaining the output voltage within a narrow regulation band  However  with the use of a  ferroresonant transformer  the output voltage is not continuously adjustable as in the previous  
210. signed to deliver a large amount of current over a short  amount of time of approximately 15 minutes  This is achieved by designing the batteries with  thin plates  This design is most common for UPS applications  The medium rate batteries are  designed for general use  They deliver a medium amount of current over a medium amount of  time of approximately 1 to 3 hours  The design consists of medium width plates  This design is  most common with switchgear and control applications  The low rate batteries are designed for  delivery of power over a long amount of time of approximately 8 hours  The battery design  consists of thicker plates  This design is most common for applications such as emergency  lighting and telecommunications      d  Vented  flooded  lead acid battery  Vented  flooded  lead acid cells are  constructed with the liquid electrolyte completely covering the closely spaced plates  The  electrolyte maintains uniform contact with the plates  These batteries require regular  maintenance of checking the specific gravity of the electrolyte and adding water  These batteries  are well suited for industrial applications due to the long lifetime  20 years  and high reliability  with the proper maintenance  Without the proper maintenance  the lifetime of the battery could  be greatly reduced  These batteries are approximately half the cost of ni cad batteries  These are  the most commonly used batteries for industrial application UPSs      e  Valve regulated lead acid  
211. st and  performance of equipment are retained  the maintenance program will be defeated  Unless  records are updated at each succeeding test period  valuable information is lost  Comparative test  data materially assists an UPS specialist in defining problems  especially when test results differ  from manufacturers    recommended settings or actual factory test data  Significant changes in  comparative test data can  in general  be related to the equipment s condition      3  Scheduling  Scheduling of UPS and battery maintenance is normally based on the  manufacturers    recommendations  Since an UPS system is vital to the operation of critical loads   it may be considered advisable to provide more inspections than those the manufacturer  recommends  Certain items on the UPS should be inspected daily or weekly  This inspection can  be done by operating personnel  but data should be recorded and sent to the appropriate  maintenance point not more than 5 days after being recorded  Battery maintenance should be  done by maintenance personnel  Visual monitoring data should be recorded daily for the UPS   and if recorded for the battery  the recorded data should be handled and sent on to the  maintenance department on a weekly basis      4  Periodic system status checks  The continued monitoring of the operating status of any  electronic equipment greatly enhances the probability that failure of that equipment will be  prevented  Daily observation is advised but do not provide les
212. st inverter input power required to produce rated output at minimum input dc voltage  The  end of discharge voltage should be equal to or higher than the minimum dc input voltage required  by the inverter to maintain rated performance  The minimum dc voltage required by the inverter  is normally published by the manufacturer  The maximum dc power required by the inverter can  be obtained from the manufacturer or can be calculated  In addition  it is recommended to  include a margin of 30 percent for the required capacity to account for load growth and battery    aging     TM 5 693     2  Lifetime  The expected lifetime of batteries on UPS duty is usually stated in terms of  years of service on continuous charge to an end of life defined as the failure to be able to deliver a  certain percentage of rated capacity  Initial capacity  unless specified as 100 percent capacity  is  usually in the range of 90 to 95 percent of rated capacity  This will rise to 100 percent capacity in  normal service after several charge discharge cycles  IEEE 450 recommends that a battery be  replaced when its actual capacity drops to 80 percent of rated capacity  however  some  manufacturers rate  end of life  at 50 percent of rated capacity  Obviously  the user needs to  check the initial capacity rating  the service life period  and the aging characteristics given in the  battery guarantee so as not to be unpleasantly surprised      3  End of discharge voltage  UPS batteries are not sized on so ma
213. stems determined to be of poor quality  misapplied  or marginal for  the application      c  Inspection check list  This list should provide necessary and pertinent information  on points to be checked and establish the recommended recurring dates when these checks should  be made  Since shutdown may require a sliding window period  the amount of time for which  this request must precede the shutdown window should also be stated      d  Periodic maintenance schedule  This schedule provides a complete listing of the  day to day  weekly  monthly  and annual duties which should be reviewed on the same periodic  time basis so that potential trouble situations can be investigated and corrected as soon as  possible      e  Maintenance inspection and repair records  These necessary and vital documents  should be completed in detail by the inspector or an assigned individual in the maintenance  department  Maintenance personnel usually report their findings and corrective action on  assignment sheets or job cards  Permanent records are a useful guide to each UPS system s  general condition and reliability  It is important to know the frequency and type of repair and  how often there is a need for a complete overhaul      2  Use of records  These records provide for a workable preventive maintenance  program  The information obtained from the necessary periodic inspections can be quickly lost   This is particularly true when test results are required  Unless records and data on the te
214. t with the reverse parallel SCRs provided only in  the UPS bypass line  With an UPS output malfunction  the UPS bypass static switch will be  turned on before the inverter output circuit breaker automatically opens  This type of hybrid  switching will need only a short term static switch current carrying  heat  rating and provides a  normally reliable configuration if there are no problems with the circuit breaker closing in the  static switch s 300 milliseconds  ms  rating  Figure 2 4 shows a SS CB configuration where  circuit breaker SS CB closes after the UPS bypass static switch closes  The circuit breaker SS   CB provides a bypass for the static switch and therefore allows for the use of a short term static  switch current carrying  heat  rating  To prevent any damage to the static switch the circuit  breaker must be able to close within the static switch s short time rating  There have been  problems even though manufacturers quote a 450 000 hour mean time before failure  so this  system cannot be considered as reliable as a fully rated UPS bypass static switch  Hybrid  switching is used as a method of combining the merits of both a static switch and a circuit  breaker  that is  both speed and economy     2 2    TM 5 693       AC   SEN i CRMCAL   Ful LINE     f LOAD  LES BYPASS OUTPUT       a                         CONTROL  FIRING  LOH    RECTIFIER l Frij  CHARGER     sR    WPS OUTEUT  OC  BATTERY          MAINTENANCE BYPASS  a SCR OPERATING LEGEND  CA SCR OFF LINE    
215. ta must be referenced for later inspections      1  Visual inspections  Visual inspections afford the opportunity to check cells for damage  or evidence of improper charging or other mishandling  A flashlight or other localized  unsparking light source is essential in inspecting cell components and connections and checking  for evidence of excessive gassing  mossing  sediment  and low electrolyte levels  Vibration may  be a problem  Although hydration and frozen electrolytes should not be problems  under  abnormal operating conditions such unlikely events can cause irreparable damage      a  Cell inspections  The jars  plates  and connections should be closely inspected on  each cell  Jars  covers  and cover to jar and cover to post seals should be checked for cracks or  other structural damage  Failure of any seal will cause the electrolyte to seep out  A light source  can be directed through clear jars as an aid in locating cracks or structural damage to the jar or  cover and their seals  such defects should be noted  and the manufacturer should be consulted as  to remedial action  Unwrapped plates in a clear jar should be examined  as they show the  battery s condition  The color of the positive plate of a lead acid cell will vary from light to deep  chocolate brown  and the darker the color the more likely the battery has been overcharged  The  negative plate will be gray in color  with a tendency to darken with age  Check and note any  buckling  warping  scaling  swellin
216. tage measured should be equal to or less than 0 05 volts below the manufacturer   s open circuit  voltage  If it is not  the manufacturer should be contacted to determine the next course of action   The cell polarity for positive to negative connections should be checked  The battery should be  assembled as shown on drawings  Each battery cell is then checked to ensure the electrolyte level  is at the maximum level  The interconnection of the battery cells should be checked for polarity   The connector bolts should be checked to ensure that they have been tightened to the  manufacturer   s recommended torque values  The cell internal ohmic values and the inter cell  connection resistances are then measured  This is accomplished by applying a load across the  battery and measuring the step change in voltage and current for each cell taken between the  positive and negative terminal posts of adjacent cells as well as the battery as a whole  The  ohmic value is the change in voltage divided by the change in current  The resistance values for  each cell should be averaged and any interconnection that varies more than 10 percent or 5 yQ  over the average should be remade and then rechecked for its resistance value  These values shall  become baseline values for comparison in future tests  The presence of flame arrestors  adequacy  of battery support racks  mounting  anchorage  grounding  and clearances  ventilation of battery  room enclosure  and existence of suitable eyewash equi
217. tainer should be fire retardant     Identify electrically  Determine type  3 phase AQ Determine total amount o  powered equipment DC  etc   and amount of power required  requiring auxiliary power power required for each    60Hz 400H4 Othe 60HE  400Hz Ojha    For each type of Physical   From spec  From spec ae Table 1  lighting or equipment count dags  etc    dags  etc  analysis  soromast     11  1     To calculate the total power required  other factors mst be  considered  These inchide      Overvoltages and Spikes   Transients    Future Expansion  oversizing        Figure 3 3  Determine the required power is a key step in the UPS selection process    f  Determine if the availability of the selected UPS is acceptable  In managing a facility  the  availability of equipment and systems is of the utmost concern  Simply stated  availability is the  amount of time a piece of equipment is available to perform its function divided by the total time  the equipment is needed  It is also defined as    uptime    divided by    total time     Thus  if an air  conditioner is required 12 hours each day  the availability would be 90 percent if it is out of  commission an average of 1 2 hours each day  Normally  the required availability for UPS is 98  percent  Availability is a function of reliability and maintainability  The inherent or designed in  availability is usually expressed as follows     _ MTBF  MTBF   MTTR       i    3 7    TM 5 693    where  Aj is inherent availability  MTBF is 
218. tatic UPS system with static transfer switch    the alternate source during a loss of inverter output or a deviation of the inverter output voltage  beyond the allowable tolerance due to malfunctions  high inrush demand  or a load branch circuit  fault  In order to minimize disturbances to the connected loads during transfers  the inverter is  synchronized to the alternate ac source  During normal operation the inverter frequency is  controlled by the alternate source s frequency  In this mode  the inverter s internal oscillator  provided for controlling the inverter frequency is bypassed  However  should the alternate source  frequency deviate beyond the allowable tolerance  the inverter automatically reverts to its internal  oscillator for frequency control and maintains the frequency within tolerance  The static transfer  switch is commonly designed to automatically retransfer the loads back to the inverter when its  output voltage recovers to within tolerance  However  the automatic retransfer feature can be  inhibited if desired to allow for manual retransfer only  The addition of the static transfer switch  to the basic system configuration increases the system reliability by connecting the loads to an  alternate source upon loss of the inverter output  In addition  this configuration facilitates  supplying loads with high inrush demands  One common improvement to this system is the  addition of a regulating transformer as shown in figure 2 24  A regulating transformer 
219. techniques      3  Three phase inverters  Three phase inverters are commonly made up of three single   phase inverters connected to the same dc supply  as shown in figure 2 18  The secondaries of the  three single phase inverter output transformers are connected in wye configuration  To generate a  three phase output  the firing signals for phase B inverter SCRs are delayed 120   from those of  phase A inverter  Similarly the firing signals for phase C inverter SCRs are delayed 120   from    TM 5 693       INPUT WDG 1        OUTPUT       Q  I  N    CH1    we SS ae eee       1 FILTER             Figure 2  17  Ferroresonant transformer    those of phase B inverter  The resulting phase to neutral voltages for 180   pulses and the line to   line secondary voltages are shown in figure 2 18  where     Ea p   Ean   EB n  Ep c   Ep n   Ec n    Ec a   Econ   Ean    In this case as with the single phase inverter  the output wave shape is a square wave and means  for conditioning the output to a sinusoidal waveform is required  The three phase inverter output  voltage control can be accomplished by the same techniques used for single phase inverters  However   the use of ferroresonant transformers is not feasible in many three phase applications  This is due to the  fact that a slight load current unbalance can cause substantial phase shifts in the ferroresonant  transformers output voltages  With substantial voltage phase shift  the three line to neutral voltages may  have the same mag
220. tery supported inertia rotary UPS system consists of a synchronous motor driving a  synchronous generator  with a rectifier  inverter  and storage battery added  The system  configuration is shown in figure 2 21  During normal operation  the synchronous motor drives  the synchronous generator and provides filtered power  Upon loss of the ac input power to the  motor  the battery supplies power to the motor through the inverter which drives the generator   The batteries provide energy to the system during the transition from normal to emergency  operation  This system may also use a kinetic battery in place of the standard lead acid and ni   cad batteries  see paragraph 2 2b 6       2 29    TM 5 693        gt  PHA LM    arc l Siya i       some         i   4   e  iiin    S Sey el  _k   SYNCH 3ENERATOR    WITOR  EAT TER    i    INVERTER  CHARGER    BATTER             Figure 2 21  Battery supported motor generator  M G  set    a  Motor types and characteristics  In a rotary UPS system an ac motor is used to convert  electrical energy to mechanical energy for driving an ac generator and a flywheel  Both  synchronous and induction motor types may be used  DC motors are also used in rotary systems  with a storage battery for back up power  In the following paragraphs  only the motor  characteristics relevant to rotary UPS applications are addressed      1  Induction motors  Induction motors are of the squirrel cage or the wound rotor type  It  is the three phase cage motor type that
221. th circuit breakers      4  Neutral bus  An UPS system will usually supply at least some line to neutral loads   and a neutral bus will be provided  This bus contains provision for both a main neutral conductor  and a grounding conductor  as well as terminations for the branch circuit neutral conductors  The  neutral bus must not be grounded to the enclosure  either accidentally or intentionally  in spite of  the provision of a grounding terminal  The neutral ground is applied at the UPS and at the bypass  source and must not be duplicated at the panelboard  Also  in a three phase UPS system with a  transfer switch  the neutral conductor should not be opened with the transfer switch      5  Coordination of protection  When a fault  or short circuit  occurs on a branch circuit   the branch circuit breaker or fuse must isolate the fault before the UPS protective devices operate  and trip the entire system  When this condition is fulfilled  the protection system is said to be  coordinated  Fuses of different ratings can be coordinated  so a main panelboard may supply a  downstream panel if necessary  however  it rarely is necessary and should be avoided  Molded   case circuit breakers are instantaneous in action at currents above 8 to 10 times their continuous  current rating  Since the UPS has limited output current  additional power for clearing fault  currents rapidly may be provided from an alternate high power source by the use of a static  switch  When a fault occurs on an
222. th or wiper once  cleaning is finished  Never use solvents  detergents  oils  waxes  polishes  or ammonia to clean  the jars  as this may cause permanent damage to the jar  Use an acid neutralizing agent consisting  of soda solution  one pound of bicarbonate of soda to one gallon of water   Other neutralizing  agents may damage the jar      b  Battery connections  Terminal posts and connections should be cleaned with a  clean lint free cloth or wiper moistened with a suitable neutralizing agent  followed by a clean  cloth moistened with water  and finally by a dry cloth  Cleaning charged batteries could present a  safety hazard in the case of heavy corrosion  Corroded connections should be unbolted and  cleaned  Suitable means to continue service  e g   installing jumper cells  should be arranged for  batteries which must remain in service  Normally  loss of the voltage jumpered out by removal of  the cells will not degrade the ability of the battery to supply the UPS if the number jumpered out  is in accordance with the UPS manufacturer s recommendations  Cleaning of heavily corroded  posts and connectors should follow the manufacturer s directions  Do not clean the surfaces so  rigorously that the plating is removed  A plastic bristle brush can be used  Once the connection  is clean  a thin coating of an approved corrosion inhibitor such as No Ox Id should be applied   Never use anti corrosion sprays in aerosol containers  Observe the manufacturer s recommended  torque valu
223. that there are no mechanical parts and the  ultra fast switching capabilities of the electronic components     Static UPS   see UPS  static      Subtransient Reactance of Generator   see Reactance      Surge   A high voltage condition in which the voltage on one or more phases of ac power exceeds 100  percent of the nominal value for more than one cycle  1 60  of a second for 60 cycle ac   Can be  caused by a rapid load reduction or switching  and can damage equipment     Thermal Runaway  A condition that is caused by a battery charging current that produces more internal heat than the  battery can dissipate  This condition ultimately causes cell venting and premature failure     Thevenin Generator   For a given load  it is possible to consider the power supply as a voltage generator  referred to as  a Thevenin generator  made up of a perfect voltage Uo generator  in series with an internal  impedance Zs  n Uo is the voltage measured across the load terminals  given that the load is to be  disconnected  load terminals forming an open circuit   n Zs is the equivalent impedance as seen    TM 5 693    from the load terminals  again considered an open circuit   obtained by short circuiting the  upstream voltage generator s      Tolerance in Percent  Limit for allowable variations for a given quantity  expressed as a percent of the rated value     Transformer Short Circuit Voltage   Relative measurement  percent  of the internal impedance of a transformer  This short circuit  impe
224. the extent of the hazards posed by UPS battery  systems both large and small  flooded  and valve regulated      1  Warnings  All batteries contain an acid or alkaline solution  While the gases from a ni   cad electrolyte are not toxic  the ni cad electrolyte is corrosive as is the dilute sulfuric acid  electrolyte of lead acid batteries  All batteries are capable of out gassing      2  Electrolyte hazard  Battery rooms are required by OSHA to provide quick drenching  facilities for the eyes and body within 25 feet of the work area for emergency use  Where  emergency eyewash and showers are not provided  there are many portable devices which can be  brought into a computer room  Squeeze bottles can substitute for eyewash fountains and canisters  that look much like fire extinguishers can be fitted to provide eyewash or quick drench  When  using these devices  be sure to change the water as recommended  This prevents the growth of  bacteria  Squeeze bottles are date coded and should be replaced before the expiration date  The  canister units should be exercised periodically to prevent clogging of the head so that a good flow  of water is available when it s really needed     5 15    TM 5 693     3  Explosive gas hazard  All batteries present a potentially deadly shock hazard and  produce hydrogen gas  which is explosive in the right concentration  Therefore  there is a need  for removal of possible explosive gas buildup      4  Electrical hazard  An UPS battery is operated ungr
225. this action  Cells which do not gas during charge may indicate problems such as  undercharge  short circuits in the cell  or impurities in the electrolyte      c  Mossing  Mossing of lead acid cells is caused by overcharging or charging at  excessively high rates  Moss shield protection may be provided by the manufacturer on the top of  the plates for some cell constructions  Mossing results from the accumulation of a sponge like  material on top of the negative plates or straps  The material is shed predominantly from the  positive plates and is carried off by gassing  where  if deposited on the positive plates  gassing  simply washes it off again  however  if the material is deposited on the negative plates it will  adhere to these plates  Over time  the negative plates build up a deposit sufficient to bridge and  make contact with positive plates  causing partial shorts  If mossing is found during an  inspection  expect to find excessive sediment as well     5 9    TM 5 693     d  Sediment  Observing quantity and color of sediment in clear lead acid battery jars  also indicate the battery s condition  Excessive sediment usually indicates overcharge or charge  at excessively high rates  The sediment from a well maintained cell may look like a layer of dust  on the bottom of the jar  The sediment from a poorly maintained cell may completely fill the  space provided under the plates and will be in the form of hills under the plates  Partial short  circuits will occur when the
226. tion of rotary UPS system batteries  and racks is the same as the static UPS system batteries discussed in paragraph 4 1a 2      b  Installation requirements for rotary systems  The rotary UPS system can tolerate a larger  range of environmental conditions than the static UPS  The room may range from temperatures  of 5   to 40   C while operating   20   to 80   C while not operating  The humidity may range from  0 to 95 percent non condensing for all temperatures mentioned  The UPS is suitable for  installation in industrial electrical environments  Where applicable  the charger inverter cabinets  should be located as close as practical to the battery to minimize the voltage drop in the battery  leads  Also  the UPS shall be close to the protected load if possible  The UPS cabinets should  not be located directly adjacent to office space and work areas unless provided with acoustically  treated enclosures      1  M G and controls installation  The M G and cabinet assemblies shall be installed on a  level surface  The assemblies may be bolted to the floor if required by the manufacturer  The  cabinets should be in a convenient location for periodic inspection with sufficient front clearance  for front door opening and access to the cabinet internals  Sufficient rear and overhead clearances  should also be maintained for removing rear panels when necessary and for ventilation  The  minimum clearances should be as recommended by the manufacturer  The rotary UPS can  tolerate a r
227. tions and output       Complete a functional checkout and test of the UPS diagnostic systems        Check environment  temperature  dust  moisture  room vents  etc        Clean and tighten all power connections at the input and output terminals  at all circuit breakers  and at the terminal  posts and fuses on the rectifier and inverter legs  During the inspection  check all power cabling for abrasions and burn  spots  Visually check components for signs of overheating  swelling  leaking  etc   Visually check printed circuit board  alignments        Replace air filters at regular intervals  Site conditions will determine how often the filters should be replaced  but  generally  they will need to be replaced at least every 6 months in clean environments  If more frequent replacement is  required  the cleanliness of the environment should be upgraded        Check and calibrate each system  to include switchgear and circuit breakers  meters  and alarm levels for frequency   voltage  current  transfer  trip  alarm  etc        Perform system and component functional tests on all UPS equipment to insure proper functioning within specified parameters        Run all UPS system diagnostics  and correct all diagnosed problems        Resolve any previous outstanding problems  review operation with user personnel  and report any power enhancement  or equipment operation recommended changes           Replace control batteries at least every 2 years  If the control batteries have been used 
228. tions requiring earthquake protection   Seismic racks use rails and spacers to prevent movement of cells during an earthquake and the  spacers function to prevent adjacent cells from knocking together  The side rails are covered by a  corrosion resistant cover  such as a plastic channel  where they touch the jars  Check to ensure  all side rails  end rails  and spacers are in place  and bolts are properly torqued  Occasionally   portions of the seismic equipment for the rack may be disassembled to allow maintenance to be  performed on the battery or for cell replacement  The ability of the rack to protect the battery  during an earthquake will be impaired if rack reassembly is not properly done  Consult the  manufacturer if replacement spacers are required  Spacers must be corrosion resistant and non   swelling  such as using a styrofoam like material  Swelling of spacers can damage the battery  jars  Recheck and retorque all rack bolts and anchoring bolts  steel plates  and welds  Note any  deficiencies and correct in accordance with the manufacturer s recommendations drawings      10  Water quality  Use of distilled or deionized water is recommended so as to eliminate  the addition of foreign contaminants which reduce cell life and performance  Otherwise  a water  quality test is necessary  This can be performed by the user or by the battery manufacturer who  will provide information on the maximum allowable impurities in the water to be used for  maintaining electrolyte le
229. to prevent overheating  Equipment loaded to less than 70  percent of its nameplate rating has been shut down because of harmonic overheating   Unfortunately  there is only one standard on how to derate equipment  American National  Standards Institute  ANSI  C57 110 covers transformers  but a measured harmonic distribution of  the load current is probably not available to most users  Equipment capability must be checked  then by observation based on the temperature rise of the affected equipment      5  Lower power factor  Many non linear loads have an uncorrected low power factor  because expensive power factor and harmonic line distortion correction has not been provided   Any decrease in system power factor may indicate a load change has been made  which has  increased harmonic distortion      6  Crest value changes  Measurements for currents and voltages are based on average or  peak values  which are calibrated to read root mean square    or effective values  For a sine  wave  the crest factor or ratio of the peak to the root mean square  RMS  value is 1 414  Crest  values of non sinusoidal waveforms can be greater than this value  so that normal measuring  instruments do not provide correct readings  It is the effective value which is a measure of the  true amount of heat from a resistance  Inaccurate measurements  low for average sensing and  high for peak sensing instruments  can lead to protective device actions such as premature  tripping or failure to trip  Inducti
230. ued     Control air    pollution    Data Power CPU memory  Processing tape disk storage   peripherals  Control humidity and  temperature  Fire Annunciator    Protection alarms    Fire Pumps    Auxiliary lighting    Life Support X ray  and life  safety  systems   Medical Light  offices   Hospitals  Critical to life  clinics  etc   machines and services  Refrigeration  Communication Teletypewriter  Systems  Inner building  Television  CCTV  amp   commercial   Radio systems    Intercom systems    Paging systems    Maximum Tolerable Power  Failure Duration    1 min    y cycle    5 15 min  1 min for water   cooled equipment    Is    Milliseconds to several hours    Milliseconds to several hours    Y cycle to 10s    5 min    5 min    Recommended Minimum Type of Auxiliary Power    Auxiliary Supply Time Emergency Standby    Optional X    Indefinite until evaluated    compliance or shutdowns  are options   Until prime power restored    or orderly shutdown    Until prime power restored  or orderly shutdown    Until prime power restored       Until prime power restored  5 min or until prime power  restored  From no requirement to  until prime power restored    as evaluated  prime power restored  prime power restored  power restored    power restored    power restored    power restored       prime power restored    prime power restored           2h    Justification for UPS    Maintain comfort  Prevent loss of tests    Continue normal operation  Comply with local  state  and federal codes
231. uire that the UPS system be  shut down  A transfer of the critical load which may not provide the power enhancement  capabilities of an UPS system is something that the user must tolerate in order to obtain  maximum reliability and minimize downtime and repair costs      1  Records  Preventive maintenance is systematic maintenance  The objective is to  minimize equipment operating problems and prevent failures by making minor or necessary  repairs before major operating difficulties occur  The general condition of the equipment needs  to be evaluated periodically  and records need to be maintained for comparison at subsequent  inspections  Recorded information is more reliable than a maintenance technician s memory   Records should be concise but completely describe equipment conditions  Inspection records  should provide complete information on the following topics  preferably on separate record  sheets      a  Equipment record  This record should list the basic information on the equipment  itself  e g   manufacturer s identification  style  serial  size  location  etc   and incorporate  inventory control data for spare parts  Warranty requirements covering uninterruptible operating  conditions should be abstracted from the user s manual     5 1    TM 5 693     b  Repair cost record  This record should provide a history of repair and associated  costs of maintenance for the UPS system  It is an essential diagnostic record for avoiding future  difficulties  especially for sy
232. uled  maintenance is always necessary  A permanent load test tap or a circuit breaker and interlocking  circuitry may be provided as part of the installation  Otherwise a temporary connection must be  provided     d  Characteristics and limitations  To avoid drawing heavy inrush currents from the power    source upon initial energization  the battery charger is designed to assume the load gradually   Normally  the start up current is limited to a maximum of 25 percent of the full load current  The    2 4    TM 5 693            AC  can   CRIMCAL  AC LINE   LOAD    OUTPLT CE    RECTFIER RAE    be SCR OPERATING LEG    gt  SCR OFF LINE   a MBP   MAINTENANCE BYPASS SWITH  SE   STATIC SWITCH  UPS   UNNTERRUPTIELE POWER SUPPLY  CE  GROUT BREAKER                Figure 2 4  Static switching transfer with circuit breaker    current is then automatically increased gradually to the full load value in 15 to 30 seconds  this  time is termed the  walk in  time  For this reason all loads cannot be switched simultaneously if  the battery has been fully discharged  Upon sudden application or removal of a load  the  inverter s output voltage will drop or rise beyond the steady state level  The voltage then returns  to the steady state condition after some short time which depends on the inverter s voltage control  circuit design  These voltage variations are termed  transient voltage response  and the time  required to return to steady state conditions is termed the  recovery time     Generally
233. ut regardless of the kVA rating required  However  when all loads  are single phase  a system with single phase output is preferable up to a rating of 75 kVA  When  the single phase loads are higher than 75 kVA  a system with three phase output is normally  used  In such a case  the loads should be distributed among the three phases to minimize the  phase unbalance effects on the inverter      5  Battery protection time  Battery protection time depends on the load type and  functions  Generally  a battery with a minimum protection time of one minute is necessary for  the initial operation of the inverter without support from the power supply source  i e   during the  walk in time  There is no upper limit for the protection time  However  other considerations may  limit the length of battery protection time  Examples are the loss of the environmental control  support  which could limit the length of a computer operation time with power loss to 5  10  or 15  minutes  In such a case  there is no need to select a battery protection time which can extend  computer operating time beyond the time for which a computer system can operate before it must  shutdown due to overheating     b  Battery sizing  In order to properly size the battery  required discharge rate in kilowatt   kW  cell  required protection time  end of discharge voltage  and ambient temperature should be  determined      1  Discharge rate  For an UPS system battery  the discharge rate should correspond to the  highe
234. utput is normally set at the battery float voltage to  charge the battery while supplying dc power to the inverter  The rectifier output voltage is  periodically set at the battery equalize voltage to maintain the battery capacity  The dc filter   inductor  is provided for smoothing out the rectifier output current to reduce the current ripple  content  The battery acts as a capacitor and in conjunction with the filter  smoothes out the output  voltage and reduces the dc voltage ripple content  The inverter converts the dc power to ac power  with regulated voltage and frequency  An internal oscillator maintains the inverter frequency by  controlling the timing of the silicon controlled rectifier  SCR  firing signals and matches the ac  input frequency  The filters at the output transformer secondary are provided to filter out the  harmonics in the inverter output  Tuned L C filters are used   when required   to filter out the 5   and 7  harmonics while a capacitor is adequate for filtering out the higher order harmonics      1  Loss of normal power  Upon loss of ac power supply or upon failure of the rectifier   the battery maintains the dc supply to the inverter  The battery can maintain the dc supply to the  inverter until the ac supply is restored or to the end of the battery duty cycle  Under this  condition  the inverter continues to supply the connected loads without interruption  This mode  of operation continues until the system is shut down if the battery reaches the
235. value  VRLA  provide a means of recombination of internally generated oxygen and suppression of hydrogen  gas evolution to limit water consumption  The electrolyte is immobilized by using an absorbent  separator  e g   AGM  or a gelling agent     Walk In  The slow transfer of power from the battery back to the utility over a 10 20 second interval     G 18    TM 5 693    INDEX       acceptance test  4 12   acceptance testing  1 1   asynchronous motor  2 29   availability  1 3  2 40  3 1  3 2  3 6  3 7  3 8  3 10  3 12  3 13  4 4  4 7    B    batteries  1 1  1 3  2 20  2 22  2 24  3 6  4 1  4 4  4 7  4 14  5 16   battery  1 1  1 3  2 1  2 2  2 3  2 4  2 5  2 20  2 21  2 22  2 23  2 24  2 25  2 29  2 30  2 31  2 32   2 33  2 35  2 36  2 38  2 39  3 7  3 10  3 11  3 13  3 14  3 15  3 16  3 17  3 18  3 20  4 1  4 2   4 3  4 4  4 6  4 7  4 13  4 14  4 15  4 17  4 18  4 19  4 20  4 21  5 1  5 2  5 3  5 4  5 5  5 6  5   7  5 8  5 9  5 10  5 11  5 12  5 13  5 14  5 15  5 16   battery charging  2 22   battery sizing  3 16   bipolar transistors  2 6  2 7   blocking diode  2 6    checklists  1 1   controlled rectifiers  2 9   corrective maintenance  1 4  5 4   crest value changes  2 27   current limit  2 5  2 25  3 16  3 18  4 8  cycling effects  2 23    DC generators  2 31  DC motors  2 30  2 31  3 19    emergency power  1 1  2 22  3 1  3 6  exciters  2 31    ferroresonant transformer  2 5  2 15  2 17   field effect transistors  FET   2 6  2 7  2 8   filtered power  2 29   flywheel  2 2
236. vels  Water should be stored in chemically inert  nonmetallic  containers      11  Test equipment  Test equipment used in battery maintenance is covered in paragraph  4 5  Periodically  recalibrate all devices as necessary  A number of new instruments are  available which can continuously monitor a battery  These are often provided for systems serving  very critical loads  One final caution is that instruments which are inserted into the electrolyte  should not be used for different battery types  For example  a hydrometer used on a lead   antimony battery should never be used on a lead calcium or a ni cad battery  Such use of  equipment will cause cell contamination     g  Maintaining valve regulated lead acid cells  All the requirements given for flooded lead   acid cells apply except the requirements for electrolyte level and specific gravity      1  Differences  The valve regulated sealed lead acid cells differ from traditional cells in  that they are not in transparent jars  thus  plates cannot be seen  and the cell s electrolyte is not  accessible  Do not expect to install these cells and forget about them for their expected life   Maintenance inspections are still required  Gelled electrolyte cells are normally operated in a  vertical orientation  however  some manufacturers can produce a cell which can be operated  horizontally  A seal leak may require cell replacement      2  Charging  Charging considerations for valve regulated sealed lead acid cells are  similar to
237. voltage reaches zero  By causing source No  2 SCRs to conduct and source No  1 SCRs to block   power flows from source No  2 through the SCRs to the load during the transfer  the two sources  are paralleled momentarily until source No  1 SCRs reach the blocking state and the transfer is in  a  make before break  mode      b  Initiation  The transfer process can be initiated manually or automatically through  the sensing and logic circuit  This circuit senses the voltage and frequency of both sources and  checks their synchronism  When the connected source voltage and or frequency deviate from the  required level  the sensing and logic circuit initiates transfer to the other source provided its  voltage and frequency are within allowable tolerances  The transfer is normally initiated after a  short time delay to avoid unnecessary transfers during transients     2 19    TM 5 693       SOURCE  1 SOURCE  2        4      SENSING  amp          LOAD             Figure 2 19  Single phase static transfer switch     c  Three phase static switch  A three phase static transfer switch consists of three  single phase switches  However  only one common sensing and logic circuit is used to monitor  the frequency and voltages of the three phases  A voltage deviation in any phase initiates the  transfer  Otherwise  operation is the same as the single phase switch operation      2  Static transfer switches with short time rating  The static transfer switch discussed in  paragraph 2 1i  above is
238. voltage transformer  Control boards       Low output voltage    Input voltage  System overload  System frequency  Control board       High Low output frequency    Input voltage   Alternate source  Frequency control setting  Control board          No transfer from Inverter A to Inverter B       Primary Alternate source  Static switch  Synchronizing circuit  Control board       Table 4 5  UPS system corrective action       System    Areas to Check       No output voltage  current    Incoming voltage  Circuit breakers  System components       No transfer to Diesel generator    Diesel generator equipment  breaker  Transfer switch       Low high output voltage  current    Incoming voltage  System components  Battery sizing  capacity  System sizing  capacity       Transfers not bumpless    Battery connection  Static switch  Control board          Inadequate UPS capacity       UPS sizing  capacity  Battery sizing  capacity       c  Suggested lists of test equipment and accessories  A list of test accessories for an UPS  battery is given in table 4 8  and a list of UPS module or power converter test equipment for a  500 kVA module is given in table 4 9  Special equipment may be available or may be rented   dependent upon the site s maintenance capabilities  Normal and safety equipment should already  be available as a part of the electrical maintenance equipment  Manufacturer s equipment should  be provided with the UPS equipment by the UPS manufacturer     4 21          TM 5 693    
239. without inverter or bypass AC  power  they may need replacement sooner           TM 5 693    Table 5 1  Major system inspection general  Continued         Open all doors  drawers  and covers  Perform a thorough inspection of all cabinets for foreign objects  Perform a thorough  dusting and vacuuming of all cabinet interiors  Use only rubber or plastic vacuum attachments to clean drawers and cabinets   Except for vacuuming  never attempt to clean the UPS subassemblies  Accumulated dust or grime should only be cleaned by the  manufacturer s service representative  The exterior panels can be cleaned with a mild cleaning solution  Transparent panels  should be cleaned with a mild soap and water solution only  Restore all doors and covers to their secured condition        Off line load test the UPS system to ensure that the system is completely functional           Return the UPS to service following the manufacturer s recommended start up procedures  Make sure that no damage  to the UPS equipment or shutdown will occur because of inrush currents        c  Corrective maintenance  All UPSs have some degree of diagnostic capability which  usually includes some degree of battery monitoring  This diagnostic ability  along with a  systematic tracking of preventive maintenance data  will aid in locating possible internal faults  and may even help in tracking external faults  A good preventive maintenance program should  minimize the need for corrective maintenance     d  Recognizing imp
240. y branch circuit  the inverter reaches the current limit condition  and the bus voltage falls almost to zero  thus depriving all branch circuit loads of power  The  permissible duration of this loss of power must be longer than the clearing time of the breaker  plus the transfer switching time in the UPS if the coordination is to be obtained      a  Branch circuit breakers  Branch circuit breakers are selected based upon the  voltage rating  the normal full load current of each branch circuit load  continuous and  intermittent loads   the inrush current and its duration for each branch circuit load  the maximum  time each connected load can tolerate a loss of voltage without failure  time for failure   and the  available short circuit current at the uninterruptible ac main bus through the inverter or the by   pass circuit when a static transfer switch is used  to be obtained from the UPS system vendor or  calculated       b  Fuses  Like circuit breakers fuses must have adequate voltage rating  Select the  fuse ampere rating for each branch circuit to be as close as possible to the full load current of the  connected load  Check from the fuse melting curve that the fuse melting time at a current equal  to the connected load inrush current is longer than the duration of the load inrush current  If this  condition is not satisfied  increase the fuse size as required  The branch circuit fuse with the  largest rating shall have a clearing time which when added to the static transf
241. y cause problems even many miles from their source      9  Inductive and capacitive influences  High harmonic content can cause resonant circuits  at one or more of the harmonic frequencies  resulting in voltages and currents that are higher than  equipment ratings  Insulation breakdown  overheated equipment  and eventually equipment  failure will result  Additionally  capacitors added for surge suppression or power factor  correction may have such a low reactance at higher harmonic frequencies as to cause a short  circuit and failure of the capacitor      10  Harmonic correction techniques  The measurements of harmonic currents and  voltages require special techniques  The inductive and capacitive impedance is variable because  of harmonic variations  therefore  its effects are usually unpredictable  More and more the power  system is becoming susceptible to the operation of the sensitive electronic equipment  as much as  or more than the sensitive electronic device is susceptible to the power source  If harmonic  problems have been identified as causing problems  certain procedures are recommended  The  following are some of the procedures  Provide oversized neutral conductors  Derate  transformers  generators  motors  and UPS if necessary  Insure all controls  especially those  involving generator speed and paralleling  are properly shielded and filtered and are designed to  respond as quickly as is necessary  Use of unfiltered voltage regulators and non electronic  govern
242. y system and  improve its overall power factor  Improving the overall power factor can improve the supply  system voltage regulation  On the other hand  systems with an induction motor have a power  factor of approximately 0 8 lagging  Such a system requires reactive kVA from the power supply  system which may cause a voltage reduction on the supply system  AC motors contribute  currents during system faults  A large rotary UPS system may appreciably increase the system  short circuit capability     e  Advantages and disadvantages of rotary UPS systems  The rotary UPS system has both  advantages and disadvantages that should be considered at the time of selection      1  Rotary advantages  There are many advantages to a rotary UPS system  The rotary  system low output impedance makes it able to supply higher fault currents to operate a circuit  breaker during fault conditions  They provide total isolation of sensitive loads from power supply  system transients  They provide disturbance free uninterrupted power  Systems without storage  batteries have a low initial cost  Efficiency is higher than comparable static UPS systems  The    2 32    TM 5 693    rotary UPS systems have higher tolerance to adverse environments  Some require small space   especially systems without a storage battery  They do not cause power supply system voltage  distortion  High ratings  e g   above 1000 KVA can be built in the rotary UPS design  A rotary  system has a lower number of components than a 
243. ystem or installation  The two most common redundant designs  are the isolated parallel and parallel redundant systems  See figure 3 5     Isolated Parallel Redundant System Parallel Redundant System       Figure 3 5  Basic redundant UPS designs    Isolated and parallel redundant systems involve paralleling multiple power conversion modules   The designs are termed redundant because they contain at least one more unit than is required to  support the load  The basis for this arrangement is that if one of the power   conversion modules  fails or must be taken off line for service  the remaining unit s  is able to support the load  This  approach can provide significant improvement to the systems reliability  but must be designed  and installed properly in order to achieve its full potential  Parallel redundant systems can  actually be less reliable if the power conversion units are not tolerant of disturbances and  overloads on their outputs  Although redundancy improves the system level reliability  it actually  increases the total number of failures that will occur  The reason the number of failures increases  is that the number of operating modules  subsystems  or components has increased and nothing  has been done to reduce their basic failure rate  The reliability of the UPS is certainly affected by  the battery selected  In choosing an UPS  criteria that the buyer might use in evaluating the  batteries are shown in table 3 3  Reliability and availability data on UPS comp
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  Atto EPCI-ESTR-000 storage software  カタログ  飼い主主様への説明をサポートし 高真客満足度の向上に貢献します  А) В) ITALIANO ENGLISH А) В) ESPAÑOL  Frequenzumrichter Comfort FU-C    Copyright © All rights reserved. 
   Failed to retrieve file