User Manual - ONLINE 6K/10K RACK
Contents
1. ENGLISH C PRO TOWER AND RACK UPS USER MANUAL DOUBLE CONVERSION UPS BATTERY CABINET User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH TABLE OF CONTENTS 1 SAFETY 2 AVAILABLE MODELS 3 UPS INSTALLATION SITE PLANING SITE INSPECTION amp INSTALLATION CONDITIONS RACK UPS INSTALLATION TOWER UPS INSTALLATION EXTERNAL CIRCUIT BREAKERS SELECTION WIRING SELECTION 4 UPS INSTALLATION SINGLE UPS TERMINAL BLOCK UPS AC LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION 5 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION 6 START UP SINGLE UPS INSPECTION BEFORE START UP SINGLE UPS START UP PROCEDURE 7 START UP PARALLEL UPS REQUIREMENTS FOR PARALLEL UPS SYSTEMS INSPECTION BEFORE START UP PARALLL UPS START UP PROCEDURE 8 OPERATION INTERFACE FRONT PANEL PUSH BUTTONS LEDS LCD 9 OPERATION SINGLE UPS 10 OPERATION PARALLEL UPS REMOVING UPS FROM PARALLEL SYSTEM ADDING UPS TO PARALLEL SYSTEM 11 UPS CONFIGUIRATION 12 ERROR CODES ALARMS amp TROUBLESHOOTING 13 TECHNICAL SPECIFICATIONS 14 WARRANTY 20150105 Tower Rack 6K 10K ISOTX 2 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 1 GENERAL SAFETY INSTRUCTIONS N WARNING It is required to read and understand this manual Follow all instructions given in this manual for sta
2. Tierra Salida Tierra Entrada O I O Input Ground Each isolated output only offers 50 of total UPS capacity in Watts 110 115 120Vac 110 115 120 Cada salida aislada SOLO ofrece el 50 50 total Watts 50 total Watts 208 220 230 240Vac de la capacidad total en Watts del UPS N N L1 NM L2 N2 L N 2 ONE 110Vac output Output Power 100 UPS Total Capacity ISOTX MODELS MODELOS ISOTX One isolated 110V Output Salida Unica aislada 110V Isolated Output 1 Isolated Output 2 AC INPUT Salida Aislada 1 Salida Aislada 2 Entrada CA Output Ground Input Ground Tierra Salida Tierra Entrada N N N L2 N2 L Special Note Nota Especial y y 1 1 Output 1 amp 2 are connected parallel for JUN Vac iso 10096 watis one TT Vac maleated output 105075 watts 110 115 120Vac Pa Salidas 1 y 2 conectadas en paralelo para 100 total Watts una salida aislada de 110Vac 100 watts 3 ONE 220Vac Isolated Output Output Power 100 UPS Total Capacity ISOTX MODELS MODELOS ISOTX One 220V isolated Output Salida Unica aislada 220V N NO Aislado Salida Aislada 1 Salida Aislada 2 Entrada CA Input Ground Output Ground Tierra Salida Tierra Entrada O 444 N L1 N1 L2 N2 L y 11 Special Note Nota Especial Output 1 and Output 2 are connected in series for an unique isolated 220V output 208 220 230 240Vac Las salidas 1 y
3. OLED OFF 20150105 Tower Rack 6K 10K ISOTX 25 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH UPS FRONT PANEL LCD This UPS has a sophisticated LCD able to display all important information related to input line UPS status and values operation mode and error and alarm messages It is a powerful information tool to know what is happening at any moment LCD is also the configuration interface for all configurable parameters QIS 1 BATTERY INFORMATION In this section is displayed battery charging level and battery alarms error icons 2 ELAPSED TIMER When UPS switches to battery mode elapsed time during battery mode is displayed in Hours Minutes Seconds 3 ERROR ALARM CODE In case of alarm or error 2 digits code is displayed in this section to describe the kind of error or alarm Revise error and alarm codes tables in this manual 4 BEEP STATUS It shows if audible alarm buzzer is active or muted 5 LOAD INFORMATION In this section is displayed load value connected to UPS by 4 segments displays 0 25 2590 5090 5090 7590 and 7590 10090 It also shows error and alarm icons related to UPS output 6 UPS MODE All possible UPS modes are indicated by this section in graphic way 7 INPUT OUTPUT VALUES Input and output voltage and frequency values can be monitored in this LCD section In battery mode this section shows battery DC voltage 20150105 Tower Rack 6K 10K ISOTX 26 User M
4. factory set value is OV WE STRONGLY RECOMMEND TO NOT CHANGE THIS FACTORY SET VALUE 14 BATTERY CHARGER ADJUSTMENT i gt Parameter 2 Select Add or Sub for adjusting battery charger voltage Add lt lt Y or Reduce m Parameter 3 available adjustment value is from OV a 9 9V Factory set value hdd Udo is OVdc NOTE Before changing this value batteries must be disconnected from UPS so that charger output voltage can be measured without batteries interference WE STRONGLY RECOMMEND TO NOT CHANGE THIS FACTORY SET VALUE Parameter 2 Select Add or for adjusting battery charger voltage Add or Reduce Parameter 3 available adjustment value is from OV a 6 4V Factory set value is OV 20150105 Tower Rack 6K 10K ISOTX 34 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 12 ERROR CODES ALARMS amp TROUBLESHOOTING ERROR FAILURE CODES ON LCD When a failure or alarm is detected by the UPS an alarm or error code is presented in front panel LCD This code or symbol will allow to identify the problem In case of failure or alarm service center must revise the problem ERROR CODE ERROR DESCRIPTION ICON BEEP ALARM Ts alar 74 Bus Unbalanced SSCS 5 711 72 713 L 14 Inverter output short creut f SHORT Continous 1A Nega
5. 11 FAN ISOTX Ventilaci n para ISOTX 5 Parallel Port for parallel UPS para UPS paralelas 12 Terminal block cover Tapa Regleta Conexiones 6 SNMP 13 EXBATT connector Conector Bater as Externas 15 AC INPUT ENTRADA AC 18 Isolated Output 1 Salida Aislada No 1 120V 19 Isolated Output 2 Salida Aislada No 2 120V 20 NON Isolated Neutral Neutro NO Aislado gt hl 8 M Hid ad idi n Perry 20150105 Tower Rack 6K 10K ISOTX 7 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH RACK RACK 6KEX 10KEX UPS MODULE Terminal Block Cover RS 232 TB AC output USB DC Connector for external batteries EPO Emergency Power Off TB AC Input Share Current Port for parallel function TB Ground Parallel Port for parallel function SNMP Intelligent Slot BATTERY MODULE Cooling Fans 16 DC Connectors External Bypass Switch port MBS port 19 DC Breaker Main AC Input Breaker cmo UPS MODULE ISOTX MODULE 20150105 Tower Rack 6K 10K ISOTX 8 User Manual ONLINE 6k 10K RACK TOWER ISOTX UPS ENGLISH 3 UPS INSTALLATION SITE PLANING SAFETY INSTRUCTIONS N WARNING Before revising this section you must read and understand very well section 1 of this manual GENERAL SAFETY INSTRUCTIONS WARNINGS RECOMMENDATIONS AND LIABILITY LIMITATION REA
6. 3 IMPORTANT AC input breakers activation must be done in one by one and not at same time First for UPS No 1 then for UPS No 2 and finally for UPS No 3 if you have a parallel system with 3 UPS If AC input breakers are activated all at same time warning message 3F could be activated If it occurs reinitiate procedure sequentially Warning 3F message must be previously reset according to warning and error section in this manual 8 When rear panel AC breaker is set to ON This UPS recognizes all other UPS previously powered ON in the parallel system and will get its own parallel identification as PAR 00 where X is the position according to power on sequence 001 for 1st UPS powered on PAR 002 for 2nd and PAR 003 for 3rd UPS This message is only indicated in UPS manufactured after Dec 2011 If UPs is before Dec 2011 continue without waiting for PAR 00X message PHI 00 A E Ou im te tel li 9 At this moment all UPS LCDs must turn on to indicate internal circuitry in UPS is been powered If bypass mode is allowed all UPS will go to bypass mode If bypass mode is not allowed by configuration all UPS will go to a kind of stand by mode with outputs open and powered off waiting until ON command is selected in UPS front panel 10 At this moment configuration menu in each UPS LCD must be revised to select desired configuration It is mandatory to use same configuration in all configuration pa
7. INSTALLATION SITE CONSIDERATIONS This product has been designed to be used indoors protected from water direct sun light dust and extreme temperature Install the UPS in well ventilated location or air conditioned room Temperature must be always in acceptable range according to technical specifications table of this manual It is strongly recommendable controlled room temperature between 21 to 24 for longer battery and UPS life There must be minimum 1 meter free room distance between UPS and any wall or object It will allow better ventilation and it will allow service UPS when required Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation 100cm min 40 min 100cm min 100 40 ELECTRICAL REQUIREMENTS MANDATORY All Power lines must be protected by magneto thermal protection devices against over current breakers with capacity and technology appropriate to effectively accomplish its function as indicated in this manual Moreover installation grounding must be correct This UPS must be connected to appropriate electrical service according to selected model Technical specs sticker in the UPS shows the UPS power ratings DO NOT connect this UPS to any of its own power outlets this could damage the unit permanently Connect only computer related equipments to this UPS DO NOT connect medical equipments or critic
8. If it is used in different application some considerations fo avoiding interferences could be necessary Z l 8w N D 20150105 Tower Rack 6K 10K ISOTX 4 User Manual ONLINE 6k 10K RACK TOWER ISOTX UPS ENGLISH 2 AVAILABLE MODELS UPS TOWER 6K EX amp 10K EX UPS with internal batteries and connection for external battery cabinets to increase backup time UPS TOWER 6KEX amp 10KEX with ISO TX Models with isolation transformer to provide galvanic isolation between input and output as well as Dual Output 110Vac 220Vac 2 isolated phases of 110Vac each L1 N1 L2 N2 UPS RACK RACK 6K EX amp 10K EX UPS for rack mounting with external battery connection capabilities to increase backup time Optional Accessory Isolation Transformer ISOTX for RACK UPS 6K EX amp 10K EX ISOTX for RACK UPS is an optional external module can be connected at any moment to the UPS Model ER E Ext connecter LI 6KEX 10KEX Rack eKEX 10KEX in module Note A ISOTX module for Rack UPS is an accessory available in a separate MEUM M 3U height module EXTERNAL BATTERIES EX model ups also supports additional external battery cabinets to increase backup time External Battery Cabinet for Tower type 6K EX amp 10K EX Model EX BAT T6 T10 Batteries 40 pieces 2 groups connected in parallel 20 batteries of 12V 9AH in each group DC Voltage 240Vdc External Battery Cabinet for
9. Rack type Rack 6K EX amp 10K EX Model EX BAT R6 T10 Batteries 20 pieces 1 group of 12V 9AH DC Voltage 240Vdc NOTE 6K 10K Rack Models are supplied in 2 separate modules 1 for UPS electronic and 1 for Main Batterv Module 20 pieces x 12V batteries 20150105 Tower Rack 6K 10K ISOTX 5 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH TOWER 6K EX 10K EX 1 RS232 7 FAN ventilaci n Forzada 2 USB 9 MBS Bypass Switch Interruptor Bypass 3 EPO Emergency Stop Parada Emergencia 0 AC Input Breaker Breaker Entrada AC 5 Parallel Port for parallel UPS para UPS paralelas 12 Terminal block cover Tapa Regleta Conexiones 6 SNMP 13 EXBATT connector Conector Bater as Externas 15 AC INPUT ENTRADA AC 16 AC Output 1 Salida AC No 1 Standard 17 AC Output 2 Salida AC No 2 Programable 1 4 Share Current for parallel UPS para UPS paralelas 11 FAN ISOTX Ventilaci n para ISOTX El EIJE LE IUE JEJEJE I OC aR Mi 27177174 20150105 Tower Rack 6 10 ISOTX 6 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH TOWER 6K EX 10K EX with ISO TX 1 RS232 7 FAN ventilaci n Forzada 2 USB 9 MBS Bypass Switch Interruptor Bypass 3 EPO Emergency Stop Parada Emergencia 10 AC Input Breaker Breaker Entrada AC 4 Share Current for parallel UPS para UPS paralelas
10. UPS parallel system is powering your system in NORMAL Online mode 20150105 Tower Rack 6K 10K ISOTX 24 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 8 OPERATION INTERFACE UPS FRONT PANEL PUSH BUTTON FUNCTION DISPLAY BYPASS LIne BATTERY FALLT OFF ESC TEST UP MUTE DOWN ON ENTER d EA de Y Des RACK FRONT PANEL TOWER FRONT PANEL Both Rack and Tower type UPS offer same 4 function buttons as described below ON ENTER POWER Keep selected during 1 second to power UPS ENTER It Works as ENTER or confirmation function when LCD is in configuration menu mode OFF ESCAPE POWER OFF Keep selected to turn UPS OFF ESCAPE It Works as ESCAPE key when LCD is in configuration menu mode EST UP BATTERY TEST When UPS is in normal mode by selecting TEST key UPS enters into battery test mode during 10s UP It Works as UP key when LCD is in configuration menu mode MUTE DOWN ALARM MUTE It mutes alarm beep in progress DOWN Works as DOWN key when LCD is in configuration menu mode TEST MUTE DOWNI Simultaneous Activation CONFIGURATION MODE UPS enters into configuration menu when these 2 keys are activated at same time during 1s UPS FRONT PANEL LED INDICATOR LIGHTS There are 4 LED indication lights in front panel located below LCD These 4 LEDs describe UPS condition as follow BYPASS Mode NORMAL Mode ECO Mode Activated UPS in Failure
11. User Manual ONLINE 6k 10K RACK TOWER ISOTX UPS ENGLISH 6 START UP SINGLE UPS INSPECTION BEFORE START UP 1 5 Make sure all wires are tightly connected to terminal block Any loose connection will produce overheating failures and damage to UPS Make sure all instructions of sections 3 and 4 have been performed correctly Put the terminal block cover back in its position to avoid access to wiring Check EPO connections e EPO Port closed Wired EPO function disabled e EPO port connected to an emergency switch EPO function available by activation of Emergency Switch which must be Normally Closed type in order to guarantee that UPS will shut down when circuit opens Check Maintenance Bypass Switch MBS located in UPS rear panel is in UPS position and its cover is duly installed Make sure all external protection devices in input and output lines are in open OFF position SINGLE UPS START UP PROCEDURE 1 10 Make sure all equipments connected to UPS are off Power AC input at electrical panel board by setting input AC Lines Circuit Breaker to ON Put Battery Bank breaker to ON Only for Ex Models If using external battery pack Put AC INPUT Breaker to ON in UPS rear panel LCD in front panel starts to show bypass mode UPS Outputs are powered although UPS is off because it is on By Pass mode At this moment output power is being supplied by AC Input Power Line Start up the UPS by pressing On
12. and unplugged of power line There are dangerous voltages in DC Direct Current Capacitors Please Check Capacitor location in Figure 8 4 1 Wait at least 10 minutes after turning off UPS before opening it to access inside DANGER Power off UPS and unplugged it from AC Line before opening it to Access inside this unit CAUTION Before starting the opening procedure remove all jewelry and metallic objects such as Rings Watches Bracelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electrical risks Transportation and Storage Warnings and Recommendations N This UPS must be transported only in its original package to be properly protected This equipment must be storage in dry and ventilated site in upright position Before storage this UPS batteries must be recharged for 8 to 10 hours During long term storage UPS must be recharged periodically according to this manual ARNING EQUIPMENT DISPOSAL N Out of service units It is strongly recommended to dispose this piece of equipment according to valid directives in your country At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials to be recycled Batteries Do not throw it to fire risk of explosion Do not open the batteries there are dangerous liquids inside W
13. more humid one some condensation could be generated Leave the UPS for at least 2 hours to climate to new installation site e Do not install the UPS outdoors or near water sources nor in wet environment e Do not install the UPS in sites exposed to sun light or heat sources Temperature at operation site should never rise over 35 Batteries life shortens over 25 e Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru the ventilation system Fan e Do not block UPS ventilations UPS INPUT AND OUTPUT POWER LINES PROTECTION AC LINES PROTECTIONS DEVICES All UPS Inputs and outputs must be protected by circuit breakers and current leak protections Protection capacity and type must fulfill local regulations as well as directives from this manual Grounding must be according to local directives as well DC PROTECTIONS DEVICES For Ex models with external batteries there must be also DC Circuit Breakers between UPS and battery bank Some Models include a DC breaker on the rear panel for external battery pack protection otherwise an external DC Circuit breaker must be installed MATERIALS AND ELECTRICAL DEVICES Verify that all electrical lines involved in installation are open circuits and free of dangerous voltages before starting inspection tasks All switches related to these electrical lines must be in OFF position before star
14. or to final user INTEGRA is not responsible for damage that occurs as a result of your failure to follow the instructions intended for this hardware product USA Headquarters SPAIN Headquarters Latin America Headquarters 10540 NW 26th St Ave Can Bordoll 60 Nave 4 Zona Ind San Vicente II Calle A11 Doral FL 33172 Sabadell 08202 Maracay Tel 1 305 406 3664 Tel 34 93 745 9694 Tel 58 243 551 7023 20150105 Tower Rack 6K 10K ISOTX 39
15. when circuit opens 5 Check Maintenance Bypass Switch MBS located in UPS rear panel is in UPS position and its cover is duly installed 6 Make sure all external protection devices in input and output lines are in open OFF position 7 Check control parallel cables are connected according to section 5 of this manual 20150105 Tower Rack 6K 10K ISOTX 23 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH START UP FOR PARALLEL UPS SYSTEM WARNING Make sure all requirements and previous inspection have been revised and complied before initiating start up procedure If not please do not try to continue with start up procedure 1 Make sure all equipments to be protected and connected to UPS output are in OFF condition 2 Check AC input breaker located in UPS rear panels is in OFF position in all UPS of the system 3 Power on external main AC input in electrical panel Set to ON position all external AC input breakers 4 f UPS are using external battery packs set to ON all DC breakers to connect external DC packs to UPS 5 For UPS No 1 Set to ON AC input breaker located in rear panel of UPS No 1 Wait until UPS No 1 completes auto checking and Bypass LED lights continuously 6 For UPS No 2 Set to ON AC input breaker located in rear panel of UPS No 2 Wait until UPS No 2 completes auto checking and Bypass LED lights continuously 7 In case of having UPS in the system proceed in similar manner with UPS No
16. 05 Tower Rack 6K 10K ISOTX 27 User Manual ONLINE RACK TOWER ISOTX UPS ENGLISH FUNCTION DISPLAY ACCORDING TO OPERATION MODE UPS ON Input AC source OK UPS output generated by inverter ONLINE FREQUENCY CONVERTER FUNCTION CF BATTERY MODE BYPASS FAULT STATUS UPS in ON ECO mode activated Input AC source is OK UPS output feed from AC input to save energy UPS in ON ECO mode activated Input AC source out of acceptable range UPS output generated by inverter I Le t am E CF function enable to generate output frequency as selected IMPORTANT NOTE When is activated bypass mode is automatically disable and maximum power output is de rated to 60 of standard maximum power output When AC input source is out of range Ups goes to battery mode to supply output from taking energy from batteries If UPS is overloaded by big consuming load connected at UPS output UPS changes to BYPASS mode feeding outlets from input AC source This mode can be set also by front panel by selecting ON MUTE SELECT at same time When UPS detects a failure output will be powered off and error code will be displayed on LCD Example code 43 20150105 Tower Rack 6K 10K ISOTX 28 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 10 OPERATION PARALLEL UPS UPS operation modes for UPS in parallel are basically same than de
17. 2 se conectan en serie 100 total Watts 208 220 230 240Vac para una salida nica aislada de 220Vac 20150105 Tower Rack 6K 10K ISOTX 15 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH RACK TYPE UPS 6 10K RACK UPS 6 10K T BLOCK REGLETA OUTPUT INTPUT SALIDA ENTRADA CAE C UE dI L GL N Optional ISOTX Module for RACK UPS 6 10K ISOTX module is optional accessory rack module UPS AC output must be connected to ISOTX input as indicated ISOTX outputs can be configured as tower UPS models RACK UPS 6 10K with External ISOTX OUTPUT INTPUT SALIDA E ENTRADA Isolated Output 1 Isolated Output 2 AC INPUT Salida Aislada 1 Salida Aislada 2 Entrada CA 110 115 120Vac 110 115 120Vac 208 220 230 240Vac 20150105 Tower Rack 6K 10K ISOTX 16 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH EXTERNAL BATTERY CABINETS CONNECTION PROCEDURE UPS Tower type 1 Check all DC breakers are in OFF position 2 Remove all DC connector covers in UPS and EXBATT cabinets 3 Using appropriate cable supplied with the EXBATT connect UPS with EXBATT 1 In case of more than 1 EXBATT connect EXBATT 1 with EXBATT 2 and so on until last EXBATT 4 Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries EXBATT 1 EXBATT 2 UPS RACK type EXBATT 1 EXBATT 2 20150105 Tower
18. 300Vac 3 50 load 40 70 Hz 1 Phase Ground 1 Fase Tierra gt 0 99 10096load lt 5 0 100 load 1 Hz s 1 phase L1 N1 208 220 230 240Vac Dual Isolated Outputs 2 phases L1 N1 L2 N2 104 110 115 120Vac 1 Mode Modo Bater a 1 Mode Modo Bater a 50 Hz 0 1 Hz 60 Hz 0 1 Hz 50 Hz 0 1 Hz 60 Hz 0 1 Hz 3 1 100 load 3 1 100 load lt 3 Linear Load Carga Lineal lt 5 No Linear Load Carga no Lineal 0 ms 0 ms Sine Wave Sinusoidal Pura Sine Wave Sinusoidal Pura Terminal Block Regleta de Conexi n Terminal Block Regleta de Conexi n 10096 11096 10m 11096 13096 1m 213095 1s 10096 11096 30s 11070 13090 10s gt 130 1s 96 192 EX ISO 90 186 EX ISO 88 184 EX ISO 96 92 EX ISO 90 186 EX ISO 88 184 EX ISO Separate Cabinet Separate Cabinet 12VITAH x 20 pcs 12V 9AH x 20 pcs 12V 7AH x 20 pcs 12V 9AH x 20 pcs 12V 9AH x 40 pcs 12V 7 AH x 20 pcs 12V 9AH x 20 pcs 3 5 h 90 4 h 90 3 5 h 90 4 h 9090 Depending on external battery configuration depende de cantidad de bater as externas 2 0 A Max 2 0 A Max 273 0 VDC 273 0 VDC Charging Voltage Voltaje del cargador 20150105 Tower Rack 6K 10K ISOTX 37 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH UPS 6K 10K 6K EX amp ISOTX 10 EX amp ISOTX 6K RACK 10K RACK INDICATORS INDICADORES Estado del UPS Consumo Baterias Voltaje Entra
19. ARNING BATTERIES MAINTENANCE N e Batteries capacity in general of all kinds decrease with time and use e Our products contain high quality batteries only e Batteries useful life in our UPS is between 4 and 5 years considering environment temperature under 25 C and optimal operational conditions This time can be dramatically reduced by high temperature and other adverse operation condition e X Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipments connected to UPS e Batteries should be periodically tested to check capacity and assure and appropriate back up e Toenlarge batteries life expectancy it is recommendable to fully discharge UPS one every 2 to 3 months e During UPS storage recharge batteries according to the following table Storage Temperature Recharging Frequency Recharging Time 25 a 30 C Every 4 months During 6 hours 30 C a 45 C Every 2 months During 6 hours 20150105 Tower Rack 6K 10K ISOTX 3 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH SAFETY STANDARDS SAFETY IEC EN 62040 1 EMI Radiated IEC EN 62040 2 Cat 3 EMS Power Frequency Magnetic Field EMS Low Freq Signals EMS ESD IEC EN 61000 4 2 Level 4 EMS RS EMS SURGE IEC EN 61000 4 5 Level 4 EMS CS IEC EN 61000 4 6 Level 3 This product has been designed to operate in industrial and commercial applications
20. CH AND LIABILITY LIMITATION The preparation of the site wiring and all protection devices must be supplied by end user and it will not be responsibility neither the UPS distributor nor the UPS technician in charge of the start up The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical requirements This manual describes minimal conditions and technical requirements with which the site must accomplish Directives and requirements described in this manual do not pretend to substitute in any way local electrical directives or normative In some cases local directives or regulations might be more exigent than UPS technical requirements described by this manual In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives WARNING Power lines must be protected by protection devices against over current breakers or leak currents with capacity and technology appropriate to effectively accomplish its function Moreover installation grounding must be correct WARNING Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures WARNING Do not connect to UPS equipments or devices that exceed its capacity this would overload the UPS WARNING This product has been designed to be used indoors protected from water direct sun light dust and extreme temperatur
21. LLEL SYSTEM UPS ISOTX PARALELO Input Neutral Input Line AC Ground Tierra AC Output 2 Neutral gt Output 2 Line Output 1 Neutral Output 1 Line gt Non isolated Neutral 20150105 Tower Rack 6K 10K ISOTX 20 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH PARALLEL UPS CONTROL WIRES CONNECTION 2 UPS Parallel System Control Wiring Parallel Cables O apo EE om Gee ku mm d FI i p S am m e T EA ft E E E E E 72 gt al i b Uc Shared E Jy JJ i G ajn dL A mdi Aa Cables P H a O a _ A d a E A CN b if Ath Py 2 3 MA IFA A ff Hl l MA LS AL IH var Par g if Fi A 1 iP i E uc rai g ey 5 kl Parallel Cables n J i e D O ppe T O em gt pam me Rm nn ee m mM Asiae ee XC EI 7 UE Shared cul UB Shared Current POZA Cables gt ki IZA Cables 20150105 Tower Rack 6K 10K ISOTX 21
22. Parallel System e For adding a new UPS to an operating system all UPS must be turned off and all equipments must be disconnected from UPS outputs Total UPS quantity must be 3 or lower Firmware of all UPS must be compatible for allowing parallel functionality New UPs must be configured with similar LCD configuration menu than current UPS of the system Follow the procedure explained in Installation Section of this manual 20150105 Tower Rack 6K 10K ISOTX 29 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 11 UPS CONFIGUIRATION u m m umm Li NE LA n dl LI Co Ci CO This menu is activated by simultaneous selection of Test Up Mute Down keys during 1 second or longer when UPS is in OFF or BYPASS mode Configurable functions according to UPS mode NN Bypass AC 1 Output Voltage OH Output Frequency 3 Voltage Range for BYPASS Frequency Range for BYPASS ECO Mode Enable and Disable 6 Voltage Range for ECO mode Frequency Range ECO mode BYPASS mode 9 Battery Backup Security Time Programmable Output note 1 Programmable Output Settings note 1 NO Battery startup function Battery Voltage adjustment Battery Charger Voltage adjustment UPS output voltage adjustment configurable parameter according to each UPS working mode note 1 In ISOTX models function 10 and 11 are not availa
23. Por ejemplo para un UPS de 10KVa se reduce a 6KVA If output voltage is set to 208Vac output power is reduced to 90 For example for a 10KVA UPS power output will be reduced to 9KVA Si el voltaje de salida se ajusta a 208Vac la potencia de salida se reduce al 90 de la potencia original Para un 10KVA potencia se reduce 9KVA 20150105 Tower Rack 6K 10K ISOTX 38 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 14 LIMITED WARRANTY Support If a failure or problem is detected please check troubleshooting section in user manual If problem cannot be solved please contact authorized service center or authorized dealer Batteries Rechargeable batteries can be charged and discharged hundreds of times However they will eventually wear out This is not a defect or failure so that batteries wear out is not covered by this warranty Battery lifetime will depend of operative conditions like working temperature type and frequency of discharging cycles Higher the temperature shorter will be the lifetime Frequent and deep discharging cycles also will short lifetime For critical applications batteries should be revised and replaced periodically Long storage longer than 6 months without required recharging will wear out batteries This situation is not covered by this limited warranty since this is not considered as a defect Check recharging instructions on user manual Warranted Products EPRO series 1K to 10KVA 1 phase or 2 phases m
24. Rack 6K 10K ISOTX 17 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 5 UPS INSTALLATION PARALLEL UPS TERMINAL BLOCK GENERAL COMMENTS FOR PARALLEL SYSTEMS 6K y 10KVA models allow installation of up to 3 units in parallel Units to work in parallel must be connected as indicated in this section Parallel system must be configured and started up according to instructions given dedicated section of this manual Any mistake in connection configuration or starting up procedure could produce permanent damage UPS PARALLEL UPS CONNECTION h e Make sure the UPS is Off before starting the installation e Remember to check all wires to be connected including external batteries are not powered before manipulating them UPS TERMINAL BLOCK PREPARATION Remove cover of terminal block at the UPS rear panel identified as 12 in rear panel section of this manual DO NOT use a wall power outlet to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected directly to electric panel board UPS INPUT AND OUTPUT CONNECTIONS Connect input and output ground wires to proper place on the UPS chassis on both sides of terminal blocks Ground wires must be FIRST to be connected and LAST to be disconnected Refer to Figures 3A and 3B Grounding Wires Connect AC Input and Output ground of both UPS according to figures b AC Input Wires AC Input wires must come fro
25. ace on the UPS chassis on both sides of terminal blocks Ground wires must be FIRST to be connected and LAST to be disconnected Connect UPS input and output wires according to your UPS model or configuration as described in following figures TOWER TYPE 6 10K TERMINAL BLOCK REGLETA 6KEX 10KEX Tower Type Tipo Torre OUTPUT 1 OUTPUT 2 AC INPUT SALIDA 1 SALIDA 2 Entrada CA Output Ground Input Ground Tierra Salida i E Tierra Entrada O cs tn atan sms tanos O M L2 N2 L N yy y y 11 208 220 230 240Vac 208 220 230 240Vac 208 220 230 240Vac TOWER TYPE 6K 10K ISO WITH INTERNAL ISO TX Output Ground Input Ground Tierra Salida Tierra Entrada N N L1 M L2 N2 L N INT BLOCK DIAGRAM UPS 6K 10K L Inverter Output N LI NI L2 N2 110 110 e Output 1 Output with Galvanic Isolation 110Vac between phase and Neutral with 50 of total UPS capacity e Output 2 Output with Galvanic Isolation 110Vac between phase and Neutral with 50 of total UPS capacity 20150105 Tower Rack 6K 10K ISOTX 14 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH ISO TX UPS MODEL CAN BE CONFIGURED IN 3 DIFFERENT MANNERS 1 TWO separate 110Vac isolated outputs Each 5090 of total UPS capacity ISOTX MODELS MODELOS ISOTX 2 isolated 110V Outputs 2 Salidas aisladas 110V N NO Aislado Salida Aislada 1 Salida Aislada 2 Entrada CA Output Ground
26. al availability equipments to this UPS DO NOT connect AC motor based equipments DO NOT connect home appliances ovens vacuum cleaners refrigerators etc to this UPS 20150105 Tower Rack 6K 10K ISOTX 12 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH CIRCUIT BREAKERS SELECTION UPS Input 220VAC Single phase Neutral UPS Output 220VAC Single phase Neutral MODEL Input 220Vac Output 220Vac External eo 40 Amps 40 Amps 50 Amps 63 Amps 63 Amps 50 Amps KVA a ISOTX MODEL UPS Input 220VAC Single phase Neutral UPS Dual Output 110 220Vac Includes Galvanic Isolation Transformer 2 x 110VAC isolated outputs Phase Neutral 2 Individual One Total 110Vac MODEL Input 220Vac 110 Outputs Output O 3 Note 1 Note 2 Dual Output curve D curve D curve D curve C Dual Output curve D curve D curve D curve C Note 1 When using two 110Vac outputs independently each output phase 110Vac Line Neutral must have electrical protection with ratings and capacity according to table IMPORTANT Each individual output manages half of total UPS capacity Note 2 When connecting two 110Vac outputs in parallel as shown in Figure 3 2 3 B to offer one single 110Vac output with 100 UPS capacity electric protection circuit breakers must be as shown in the table One Total 110Vac Output Note 3 If external battery cabinets are connected to UPS it is necessary to inst
27. all one DC breaker between UPS and each external battery cabinet WIRES TYPE AND GAUGE Section or Gauge of the wires used in the installation must be rated to manage current values as indicated in below table WIRE SELECTION ISOTX MODELS 220Vac MODELS Two 120Vac Outputs OUTPUT UNIQUE EXTERNAL UPS MODEL INPUT OUTPUT 1 OUTPUT 2 OUTPUT BATTERIES 220Vac 220Vac 110Vac 110Vac 110Vac 240VDC 40 Amp 40 Amp ag 40 40 80 eee AC AC AC 63 63 wx 63 63 125 Values in Amps AC Alternate Current DC Direct Current WARNING The correct wire gauge or section is strongly affected by diverse factors such as Operation temperature wire length type of wire and kind of installation UPS user and or his electrical contractor must assure an appropriate selection for wire and other devices for complying with local regulations and directives for electrical installations NOTE 1 Wires for 6K 6K y 6KEX models with 208 240 VAC should be able to manage 40 Amps NOTE 2 Wires for 6K 6K y models with 208 240 VAC should be able to manage 63 Amps NOTE 3 Models with Dual Outputs with isolation transformer Each independent 110VAC line manages just half of total UPS power For ISO TX models When connecting two individual 110VAC outputs together see figure in section 3 2 3 take into conside
28. anual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 9 OPERATION SINGLE UPS This is a True On Line Double Conversion UPS and it is designed to offer clean bump less and highest quality power to your computer related equipments protecting also your valuable data Power delivered by UPS is 100 sine wave as main line According to AC Line status the UPS may operate in following modes ONLINE NORMAL Mode When UPS is turned off by selecting ON push button in front panel and AC Line is normal it enters into ONLINE NORMAL mode Under this mode UPS Inverter powers outputs and the energy is taken from DC voltage coming from AC DC converter Batteries are charged by AC Line if required BATTERY Mode Also known Inverter Mode Under ONLINE NORMAL mode when UPS detects a problem in AC input Line or black out it enters in battery mode Under this mode UPS takes energy from its batteries to power outputs There are no transfers neither micro cuts on UPS outputs as inverter was already working the only difference is that energy for outputs is now coming from batteries Transfer time is actually Zero 0 ms UPS also can enter in battery mode when it is turned on without an acceptable AC input ECO Mode There is an energy saving function that makes UPS to power its outputs with AC Line directly If Under this mode UPS detects AC input is out of acceptable range it enters into Normal Online mode If an AC failure occurs under ECO mode the UPS s inverter st
29. arts working draining energy from batteries There is a transfer time of 4 ms typical This mode is configured and activated from LCD panel There is specific input voltage range and input frequency range to configure for ECO mode BY PASS Mode Under BYPASS mode UPS outputs are powered by AC Line UPS is out of the circuit This nodes can be caused by operator by means of the maintenance switch on the rear panel or from LCD panel when OFF button is activated but it may also happen automatically by UPS malfunction or overload detected at UPS outputs FREQUENCY CONVERSION Function This UPS offers a very sophisticated function named frequency conversion CF that allows UPS to generate power output at determined frequency value 50Hz or 60Hz no matter input frequency value UPs will be able to generate output at 50Hz even input source is at 60Hz or generate 60Hz even if connected to 50Hz source This function can be configured and activated by LCD Revise configuration section of this manual IMPORTANT NOTES 1 Under CF mode UPS will disable BYPASS mode Since UPS has been configured to generate output with frequency value different to input frequency BYPASS mode is disable to avoid a not acceptable frequency value at output 2 When CF function is activated maximum power output is de rated to 6090 of maximum nominal capacity For example for a 10KVA 8KW model when CF is activated maximum output is decreased to 6KVA 4 8KW 201501
30. ble ECO CVCF Battery Test Configuration menu texts ADD Add A adir ATO Auto Autom tico BAT Battey Bateta ENA Enable Hiablitado mode Modo Convertidor de Frecuencia CF CVCF mode Modo Convertidor de Frecuencia NCF Normal mode not CVCF mode ON JO OPN Allow Permitido Parallel Paralelo Reserved Reservado SUB 20150105 Tower Rack 6K 10K ISOTX 30 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH Configuration menu functions and screens e 01 Output Voltage Configuration mai Parameter 3 Output Voltage Value DU Bi Output can be selected from following choices 208 208Vac Important Note 220 220Vac 230 230Vac l 240 240Vac UT IMPORTANT NOTE If output voltage is to 208Vac maximum power output is de rated 10 For example for 10KVA UPS maximum power output will be 9KVA e 02 Output Frequency 60 Hz CVCF mode Parameter 2 Output Frequency m gt Output can be selected from following choices c N 50 0Hz 50 0Hz r 60 0Hz 60 0Hz ATO Automatic Under this mode output frequency is selected according to input frequency 50Hz if input is 46Hz y 54Hz and 60Hz if input is 56Hz y 64Hz ATO mode is factory default value LLLI A 50 Hz Normal mode HS Parameter 3 Frequency Mode Adjusting parameter 3 can be selected Mode which is
31. da Salida Tiempo Descarga Diagnostico LCD Pantalla de Cristal Liquido LCD Fall allas ALARM ALARMAS For Battery Mode Low battery Overload UPS Failure Acoustic Beep Alarm Alarma sonora l 7 Modo Bater a Baja bater a Sobrecargas Falla PRODUCT SIZE amp WEIGHT DIMENSIONES Y PESOS DEL EQUIPO DxWxH Prof X Ancho X Altura UPS 6KEX amp 10KEX 592x250x576 592x250x576 580x438x133 mm 3U 668x438x133 mm 3U UPS 6KEX ISOTX amp 10KEX ISOT X 592x250x826 592x250x826 X External batt cabinet Gabinete Externo Bater as 592x250x576 592x250x576 580x438x133 mm 30 668x438x133 mm 30 ISOT X Module for RACK Modulo RACK ISOT X X X 580x438x133 mm 3U 668x438x133 mm 3U Net Weight Peso Neto kgs UPS 6KEX amp 10KEX 81 03 21 23 UPS 6KEX ISOT X amp 10KEX ISOT X 117 142 X X External batt cabinet Gabinete Externo 119 optional 119 optional 57 65 ISOT X Module for RACK Modulo RACK ISOT X X X 55 75 PACKING EMPAQUE DxWxH Individual UPS GKEX amp 10KEX Small Pallet 73x39x82 3 cm Carton 87x58x25 cm Individual UPS GKEX ISOT X 8 10KEX ISOT X Small Pallet 73x39x107 4 cm X Individual External Battery Cabinet Small Pallet 73x39x82 3 cm Carton 87x58x25 cm ISOT X Module for RACK Modulo ISOT X RACK X Carton 87x58x25 cm Gross Weight Peso Bruto kgs UPS 6KEX amp 10KEX 81 83 23 25 UPS 6KEX ISOT X amp 10KEX ISOT X 117 142 X X External Battery Cabinet 124 124 59 67 ISOT X Module fo
32. e WARNING Do not put any object on the UPS do not apply any force over UPS Do not cover UPS ventilation WARNING This UPS must be connected to appropriate electrical service according to selected model Technical specs sticker in the UPS shows the UPS power ratings DO NOT connect this UPS to any of its own power outlets this could damage the unit permanently WARNING Do not connect AC motor based equipments without a careful sizing of the UPS based on inrush current instead of average current Inrush current typical of motor based system could overload this UPS 20150105 Tower Rack 6K 10K ISOTX 9 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH SITE INSPECTION AND INSTALLATION CONDITIONS REGULATIONS AND LEGAL DIRECTIVES It is necessary to check that installation site wiring and power protection in the installation supplied by end user fulfill technical parameters required by UPS particular installation might accomplish with UPS requirements but not with local directives and regulations The end user and or electrical contractor will be responsible of watching for complying with electrical regulations and normative during electrical installation managed by end user Inspection performed by installation technician is not intended to confirm regulations and directives accomplishing but only with technical needs for optimal UPS operation SITE INSPECTION e During transport of this UPS from a cold place to a warmer and
33. frequency converter mode or np NCF in NON converter mode 5 IIL CF This mode allows fixing a fixed output frequency in parameter 2 NCF This mode allows output frequency was selected according to the input meanwhile input frequency is inside allowed range If input frequency is out of range UPS will go to battery mode ATO Rta 600 IMPORTANT NOTE ABOUT FREQUENCY CONVERSION FUNCTION When CF function is enable to generate an output with a different frequency value than input bypass mode will be automatically disable When CF function is activated maximum power output is de rated to 60 of standard power output For example for 10KVA UPS when CF is activated max output power is 6KVA 20150105 Tower Rack 6K 10K ISOTX 31 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH e 03 BYPASS Input Voltage Range Parameter 2 It adjusts low acceptable input voltage in bypass mode between 110V to 209V Parameter 3 It adjusts high acceptable input voltage in bypass mode between 231V 276V 04 BYPASS Input Frequency Range LCD 1 Parameter 2 It adjusts low acceptable input frequency in bypass mode In 50 Hz systems from 46 0Hz to 49 0Hz In 60 Hz systems from 56 0Hz a 59 0Hz Parameter 3 It adjusts high acceptable input frequency in bypass mode In 50 Hz systems from 51 0Hz to 54 0Hz In 60 Hz systems from 54 0Hz a 64 0Hz Parameter 3 Enable or Disable ECO Mode DIS Disable ECO
34. l be used until reaching very low level WE STRONGLY RECOMMEND TO KEEP FACTORY SET VALUE 990 Parameter 3 It configures programmable outputs according to available options ON Programmable outputs are supplied without time restrictions OFF This option turns programmable outputs OFF ATO This option allows programmable outputs to turn off when timer value is reached or very low voltage level whatever occurs first Parameter 2 001 Menu for timer setting Parameter 3 Shutdown time in minutes Timer can be set from 0 to 300 min Parameter 2 002 Menu for minimum battery voltage level setting Parameter 3 Shutdown voltage in V Minimum voltage can be set from 11 2Vdc 13 6 Vdc Programmable outlets are turned off when minimum voltage value is reached gt Parameter 2 HS H Enable or disable Hot standby function You may choose following two options in G m y 6 Parameter 3 YES Hot standby function is enabled It means the UPS is to restart after AC recovery even without battery connected NO Hot standby function is disabled The UPS is running at normal mode and can t restart without battery io ME L 20150105 Tower Rack 6K 10K ISOTX 33 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 13 BATTERY VOLTAGE ADJUSTMENT Parameter 2 Select Add or Sub for adjusting battery voltage Add or Reduce Parameter 3 available adjustment value is from OVdc to 5 7Vdc
35. m individual electrical circuit breakers on electrical panel board before being connected to UPS terminal block c Output Wires AC output wires must be connected directly to external circuit breakers of bigger capacity d IfUPS is EX model external battery banks must be connected to dedicated connector located in rear panel of UPS e Control Cables for Parallel Connection Connect Parallel Cable and shared current according to figures WARNING EXTERNAL BATTERIES N If UPS to be connected in parallel have external batteries it is mandatorv each UPS counts with its own batterv pack Parallel connection cannot be performed if one of two or two or three UPS have external batteries Permanent damages will be produced in UPS if this warning is not followed 20150105 Tower Rack 6K 10K ISOTX 18 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH MODEL 6K 10KEX PARALLEL UPS AC LINES CONNECTION UPS IN PARALLEL SYSTEM UPS EN PARALELO M Input Neutral gao Input Line ga en sol fmc _ fs Ground a Tierra AC Ground Tierra AC 3h om e c sb b Output 2 Neutral 38 as gt Output 2 Line 5o gt Output 1 Neutral 52 gt Output 1 Line 20150105 Tower Rack 6K 10K ISOTX 19 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH MODEL 6K 10K ISOTX PARALLEL UPS AC LINES CONNECTION UPS ISOTX IN PARA
36. mode ENA Enable ECO mode We recommend to know very well how this function works before trying to enable it If ECO mode is disable next programs 06 and 07 don t need to be configured n i Parameter 2 Sets acceptable low voltage limit LI zz Parameter 3 Sets acceptable low voltage limit CUT cai Parameter 2 lt sets low frequency acceptable value in ECO mode For 50 Hz system 46 0Hz 48 0Hz For 60 Hz system 56 0Hz 58 0Hz Parameter 3 It sets high frequency acceptable value in ECO mode For 50 Hz system 46 0Hz 48 0Hz For 60 Hz system 56 0Hz 58 0Hz Parameter 2 OPN Bypass ALLOWED It allows Bypass mode according to Parameter 3 configuration FBD Bypass NOT ALLOWED Under this mode Bypass mode is prohibited and UPS never will go to bypass mode no matter the situation Parameter 3 ENA Bypass enabled Enables BYPASS mode when necessary manual by LCD or automatic DIS Bypass disabled It disables manual bypass mode selection by LCD panel When OFF push button is selected UPS turn OFF Only automatic bypass mode can be performed when internal failure or overload is detected by the UPS 20150105 Tower Rack 6K 10K ISOTX 32 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH e 09 BATTERY BACKUP MAXIMUM TIME Parameter 3 000 999 t sets maximum backup time from Omin to 999min UPS will turn OFF to protect batteries when time is reached DIS IT disables this function and batteries wil
37. n normal mode AN EP UPS cannot be powered on even AC input is OK ON push button is not been selected Push ON button during 2 seconds or properly longer 1 beep s alarm is active and LCD shows Internal or external batteries are not Check battery connection E properly connected Code 27 Very high voltage at batteries or charger Batteries and charger must Active BATT FAULT failure inspected by qualified personnel Continuous beep Code 28 Very low voltage at batteries or charger Batteries and charger must be Active BATT FAULT failure inspected by qualified personnel Continuous beep UPS overloaded Disconnect devices from UPS outlets Intermittent OVER LOAD until solving overload 2 beeps per second Intermittent OVER LOAD OVER LOAD BYPASS mode to avoid internal damage until solving overload 2 beeps per second After repetitive small overloads UPS has Disconnect devices from UPS until By Pass activated solving overload Then power off UPS and re star Code 43 UPS has been automatically powered off Disconnect devices from UPS outlets Continuous beep Active UPS has been automatically powered off Check short circuit problem in devices Parallel communication lost Check parallel cables and PAR 00X tant EP text on each LCD If problem 15 solved 1 beep s reset alarm with UP and DOWN simultaneous key selection Any of the error codes activated Probable internal UPS failu
38. nstallation Input fuse or breaker reset or replacement is not covered by this warranty 10 This warranty does not cover damages produced during transportation from user to technical service caused by improper packing of the product by user 11 This warranty does not cover product failures caused by installations modifications or repair performed by non authorized person If product is open by not authorized technician warranty will be considered void 12 Warranty time could be extended as an option depending on market or products Contact your authorized dealer or www integra ups com for additional information about official warranty extension plans 13 Warranty terms and conditions cannot be modified or extended by third parties without written approval of INTEGRA Limited Warranty PRO11 INTEGRA does not warrant that the operation of this product will be uninterrupted or error free during its lifetime If product fails to work the maximum liability of INTEGRA under this limited warranty is expressly limited to the lesser of the price you have paid for the product or the cost of repairing or replacement of any hardware components that malfunction in conditions of normal use In no event will INTEGRA be liable for any damages caused by the product or the failure of the product to perform including any lost profits or savings or special incidental or consequential damages INTEGRA is not liable for any claim made by a third party to INTEGRA
39. odels Conditions Limited Warranty PRO11 1 Subject to the conditions of this limited warranty this product is warranted to be free from defects in materials and workmanship at the time of its original purchase by end user In Europe Warranty time is 2 years on electronic parts and 2 years on batteries In America warranty time is 1 year on electronic parts and 1 year on internal batteries Standard warranty times could vary depending on country region or extended by purchasing warranty options Please check warranty conditions by country region in our web www integra ups com 2 If during the warranty period this product fails to operate under normal use and service due to defects in materials or workmanship authorized distributor or service center will at their option either repair or replace the product in accordance with terms and conditions stipulated herein Transportation expenses are not covered by this limited warranty 3 Warranty is valid only if the original purchasing document issued to original purchaser by authorized distributor or dealer specifying date of purchase serial number and name of the dealer is presented with the product to be revised INTEGRA and authorized partners reserve the right to refuse warranty service if any of this information has been removed changed or missing in original purchasing document 4 If product is repaired or replaced repaired or replaced product will be warranted for the remaining
40. push button in front panel until beep is heard and ON message displayed on top of the LCD Few seconds after the UPS leaves By Pass mode to enter in Normal Online Mode also known as Mode Power on sequentially each protected equipments The front panel LCD should show the load increase as equipments start Once all equipments are on the total power consumption load should not exceed UPS capacity At this moment UPS working under NORMAL AC MODE and the system is supplied by UPS NOTE 1 If any error or warning message in indicated in LCD please revise Troubleshooting section of this manual NOTE 2 UPS batteries maybe are not fully charged UPS could require about 4 to 6 hours to recharge batteries up to 100 of their capacity 20150105 Tower Rack 6K 10K ISOTX 22 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH 7 START UP PARALLEL UPS REQUIREMENTS FOR PARALLEL SYSTEM WARNING Before starting up this parallel UPS system is mandatory to comply with all below requirements 1 Maximum quantity of UPS to be connected in parallel is 3 Do not try to connect more than 3 units in parallel 2 All UPS to be connected in parallel system must be same model all 6K or all 10K with same firmware version Please ask your distributor to confirm firmware is the same in case of doubts UPS belonging to same manufacturing batch have same firmware version 3 UPS configuration configuration parameters of LCD menu must be the
41. r RACK Modulo ISOT X RACK X X 57 77 OPERATING AMBIENTALES Humidity Humedad 95 non condensing no condensante Temperature T emperatura 0 40 C Noise Level Ruido Producido 55dB 1m COMMUNICATION COMUNICACION Smart RS 232 amp USB ports Windows 98 2000 2003 XPMsta 2008 Windows 7 Linux and MAC Intelligent Port SNMP Optional LAN card Comunicaci n LAN Ethernet opcional AS400 optional interface board Interfaz 5400 opcional Specifications can be modified to comply with special project requirements Las especificaciones pueden modificarse para adaptarse a proyectos especiales Specificaions may change without further notice Por motivos comerciales o t cnicos las especificaciones pueden cambiar sin previo aviso Available Product Models Modelos Disponibles EX Single Output 220Vac with extended backup capabilities Salida Mono 220Vac con bater as internas y opci n de bater as externas SOTX Dual Isolated Outputs 2 phases of 110Vac with EX capabilities Modelo EX con transformador de aislamiento interno salida dual 2x110Vac Rack 6K 10K 2 Cabs UPS Battery 3rd optional cab for ISOTX Rack 6K 10K 2 gabinetes UPS Bater as 3er por opci n Transf ISO opcional If CF function is activated maximum power output is de rated to 60 For example for 10KVA UPS total power output will be 6KVA in CF mode Si se activa la funci n CF la potencia m xima se ve reducida al 60 de la potencia maxima
42. rameters for all UPS of the system 11 Once configuration has been selected and verified all UPS can be started up by selecting ON push button in front panel Please press ON push button for each UPS One long beep will be generated ON message will be displayed on top side of LCD 12 All UPS will go to NORMAL Online mode at same time 13 Before setting to ON all external output breakers please revise AC voltage output on each UPS Please measure AC output voltage using a digital multi meter and confirm all output voltages are similar Maximum acceptable deviation should be 3Vac or lower Typically 1Vac f output voltage values are higher than 3Vac we suggest to adjust them by function 15 You can reduce Sub or increase Add voltage output voltage for each UPS as required LA Add 816 14 If AC output voltages are as expected please set to ON external output breakers for all UPS progressively Start with UPS N 1 then UPS N 2 etc After that all UPS outputs are connected in parallel 15 Check to confirm there are no error or alarm messages on LCDs At this moment all UPS are working in NORMAL Online mode and connected in parallel 16 It is time to power on equipments connected to UPS output Power on progressively one by one Check on UPS LCDs how power output rises meanwhile equipments are powered on Once all output load is connected check power output is below 100 At this moment
43. ration that total current will be twice the single phase current Keep this in mind for selecting the appropriate wire size For model 6K output cable must be rated to manage 80Amps AC For 10K model output cable must be rated to manage 125Amps AC NOTE 4 Wiring colors must be selected according to local directives and regulations LEAK CURRENT PROTECTION In many countries now a day it is legally required to install protections against current leakage to protect human beings in cases of leaks o discharges to ground It is responsibility of the end user and or electrical contractor selecting and including these protection devices in the electrical circuit of the UPS 20150105 Tower Rack 6K 10K ISOTX 13 User Manual ONLINE RACK TOWER ISOTX UPS ENGLISH 4 UPS INSTALLATION SINGLE UPS TERMINAL BLOCK AC LINES CONNECTION PROCEDURE N e Make sure the UPS is Off before starting the installation e Remember to check all wires to be connected are not powered including external batteries UPS terminal block preparation Remove cover of terminal block at the UPS rear panel identified as 12 in rear panel section of this manual DO NOT use wall power outlet to plug UPS to AC Line as usually ratings of this kind of outlets are not enough to power 6KVA UPS UPS Input wire must be connected by breaker protected line to electric panel board UPS Input and Output Connection Connect input and output ground wires to proper pl
44. re Contact service center 20150105 Tower Rack 6K 10K ISOTX 36 User Manual ONLINE RACK TOWER ISOTX UPS ENGLISH 13 TECHNICAL SPECIFICATIONS UPS 6K 10K 6K EX amp ISOTX EX amp ISOTX 6K RACK 10K RACK Capacity Capacidad INPUT ENTRADA Input Voltage Voltaje de Entrada Input Range Rango de Entrada Frequency Range Rango de Frecuencia Phase Fases Power Factor Factor de Potencia THDi Slew Rate Segumiento de Frecuencia OUTPUT SALIDA Model Modelo EX Model Modelo ISO TX Voltage Regulation Regulaci n de Salida Frequency Frecuencia Batt Mode Current Crest Ratio Factor de Cresta THDv Transfer Times Tiempos Transferencia Waveform Forma de Onda Power Outlets Salidas OVERLOAD SOBRECARGA AC Mode Modo Normal Battery Mode Modo Bater a EFFICIENCY EFICIENCIA Eco Mode Modo ECO AC Mode Modo AC Battery Mode Modo Bater a BATTERIES BATERIAS Type and Qty Tipo y Cantidad Internal Battery Pack bater as Internas External batt cabinets Gabinetes Externos Typical Recharge T T de Recarga Internal Battery Pack bater as Internas External batt cabinet Gabinete Externo Charging Amps Corriente de Carga 6 000VA 4 800W 10 000VA 8 000W 6 000VA 4 800W 10 000VA 8 000W 220Vac single phase L N ground L N Tierra Rated Input Entrada Nominal 208 220 230 240 Vac 176Vac 300Vac 3 100 load 110Vac
45. rting up and operating this product Only qualified technician must start up operate and maintain this product Keep manuals as a guide for future consults WARNING This product operates with dangerous voltages lt must be installed operated and maintained ONLY by qualified technicians trained for this kind of products Service personnel MUST know and understand very well all electric risks related to this product UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent practices at the moment of install starting up or maintain this product UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation WARNING If you are not qualified technician do not try to install operate or repair this product WARNING Do not try to install operate or repair this product if you are not accompanied by another qualified person able to offer first aid support in case of emergency or accidents WARNING Internal area of this product is locked by screws Do not try to access inside the UPS unless you are a qualified technician UPS must be checked repaired and maintained by qualified personnel only CAUTION There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power lind ICAUTION Inside this equipment due to internal batteries there are ALWAYS dangerous voltages thought the UPS is OFF
46. same for all UPS 4 All MBS Maintenance Bypass Switch located in rear panels must be in UPS position and switch covers must be properly installed 5 In case of using external battery packs each UPS must has same external battery packs quantity and type 6 All control parallel cables parallel cables and current share cables must be properly connected in UPS rear panels as indicated in section 5 of this manual 7 Make sure total available capacity in Watts of all UPS to be connected in parallel is higher than load to be connected to UPS system lt is recommendable total UPS power is at least 25 higher to total load If UPS system will work as n 1 redundant system make sure total UPS capacity after removing one UPS is higher than maximum load to be connected If not remaining UPS will not be able to support connected load when one of the units was removed INSPECTION BEFORE START UP 1 Make sure all wires are tightly connected to terminal block Any loose connection will produce overheating failures and damage to UPS 2 Make sure all instructions of sections 3 and 5 have been performed correctly 3 Put the terminal block cover back in its position to avoid access to wiring 4 Check EPO connections e Port closed Wired EPO function disabled e EPO port connected to an emergency switch EPO function available by activation of Emergency Switch which must be Normally Closed type in order to guarantee that UPS will shut down
47. scribed for single UPS However it is important to remark all UPS in parallel system must work under same mode at same time Parallel function does not allow different operation modes between UPS of the system Removing an UPS from a Parallel System There are 2 procedures to isolate and remove one UPs from operative parallel system A Total Power Off Powering off all UPS of the system This is the less risky procedure B Keeping Parallel system in ONLINE mode First check all below requirements are complied before trying to follow this procedure Requirements for removing one UPS in operative UPS 1 This operation must be performed only by qualified and trained personnel 2 This operation must be coordinated with the system administrator System administrator must know about the related risks of this procedure since the system could be shut down during operation because external reasons like If during this operation occurs a failure in main AC line battery backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 There must be a detailed plan to perform this procedure identifying all maintenance activities to be performed on removed unit before reconnecting it 4 Remaining UPS must be able to support the power system after selected unit is removed 5 Each UPS must have their own external protections
48. time of the original warranty or for 90 days on repaired part from date of repair whichever is longer 5 INTEGRA or their distribution service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out of warranty a reparation proposal will be sent to the user for his approval If proposal is not accepted service center will keep product available for the user during 60 continuous days After this period product would be disposed and user will not be able to rise any claim 7 Rechargeable batteries like included in this product will definitively wear out even under normal operation This is not a defect or failure so it is not covered by this warranty This warranty does not cover batteries wear out caused by improper or long storage over 6 months without required recharging indicated in product manual Even performing recharging procedure this product cannot be storage longer than 18 months Problems on batteries caused by this kind of long storage are not covered by this warranty 8 This warranty does not cover failure caused by inadequate installation or maintenance misuse accidents fire or floods In these cases warranty will be considered void 9 This product can include protection devices like input fuse or input breaker Activation of this kind of devices is not a failure it is caused by an improper product i
49. ting UPS installation After disconnecting power from electrical lines involved in installation check again with a digital voltmeter that are free of dangerous voltages IMPORTANT Warning label must be placed on primary involved circuit breakers to alert there are maintenance personnel working on these circuits to avoid accidental actuation on involved breakers 20150105 Tower Rack 6K 10K ISOTX 10 User Manual ONLINE 6k 10K RACK TOWER ISOTX UPS ENGLISH RACK UPS INSTALLATION Rack UPS must be installed using L Shape type guides for supporting UPS weight Usually this kind of supports is provided with rack cabinets If not UPS distributor can provide original telescopic guides as optional accessory Small black handles included with the UPS are only for locking purposes UPS cannot be supported only by these handles Figure 1 Rack cabinet must include L shape guide to support UPS Figure 2 UPS must be installed on L shape guides Figure 3 Handles included with UPS are only for locking UPS to the cabinet but not for supporting UPS weight Figure 4 Original telescopic guides can be provided as optional accessory if it is required Figure 1 gt g 0 Q Q D 0 g B Figure 2 l 49 0 91 L m Q 10 Q Figure 3 Figure 4 20150105 Tower Rack 6K 10K ISOTX 11 User Manual ONLINE 6k 10K RACK TOWER ISOTX UPS ENGLISH TOWER UPS
50. tive Voltage 2 34 28 Battery connection problem BATI FAULT 35 Parallel Communication problem O 36 42 cPUcommuiceonpoblem 43 JUPSOubutOvebad OVERLORD ALARM CODES ON LCD FLASHING ALARM DESCRIPTION BEEP Sec load High tion in Watts at i OVER LOAD UPS Overload High power consumption in Watts a 2 beep s UPS output m Battery Overload 1 5 Some alarms can block UPS avoiding normal operation of UPS until they are reset Technician must revise original error cause has been solved and then alarm must be reset by simultaneous selection of UP and keys in front panel meanwhile UPS is in BYPASS mode connected to AC source previous to select ON command 20150105 Tower Rack 6K 10K ISOTX 35 User Manual ONLINE 6K 10K RACK TOWER ISOTX UPS ENGLISH TROUBLESHOOTING PROBLEM DESCRIPTION PROBABLEROOTCAUSE ROOT CAUSE SUGGESTED ACTION ACTION LCD does not show input voltage value _ power cord is not connected EO Lc MEN input power cord connection AC input failure alarm active 1 beep 4s however AC input source is OK ii i Input power cord is connected into UPS Check input power cord connection outlet UPS cannot be powered on even AC input is OK EPO function is active Re establish emergency power off Beep alarm is active beep s amp LCD shows switch and set UPS i
51. to allow total electrical isolation 6 There must be enough physical room to allow comfortable access to all UPS of the system Note if any of the above requirements cannot be complied below procedure must not be performed In case all requirements can be complied proceed as follow 1 Power off selected UPS by OFF button in front panel Note OFF button must be selected twice If OFF is selected only one time UPS will not respond Once UPS is turned off it will shut down its outputs but remaining LCD on This UPS will not go to bypass mode since it is working in UPS system with other UPS generating their output from their inverters At this moment any failure in AC main line must be supported by operative UPS 2 Set AC input breaker located in rear panel of the selected UPS to OFF position 3 Set external output breakers of selected UPS to OFF position 4 Set external input breakers of selected UPS to OFF position 5 Once LCD is turned Off in selected UPS to be isolated disconnect control parallel cables parallel cables and current share cables from its rear panel Other operative UPS must keep their control parallel cables connected NOTE If you disconnect parallel control cables in any of the operative UPS of the system a communication problem will occur and the parallel system will be shut down At this moment selected UPS is currently powered off and isolated so that it can be serviced or simply removed Adding an UPS to a