1. MODBUS Queries are Q1 01020000000A S02 Q2 Undefined Q3 Undefined Q4 Undefined Q5 Undefined gt To setauthentication numbers 123A XX XX MANES media converters Where XX is authentication number Maximum length can be 14 digits for each number E g 123A 910123456789 919876543210 will configure 919871045611 as first authentication number and 919871045501 as second authentication number Unit will send acknowledgement SMS as following Command 123A 910123456789 919876543210 Acknowledgement Authentication numbers are 910123456789 919876543210 NOTE Authentication numbers must be stored along with country code Maximum of 2 authentication numbers can be stored SMS FORMATS TO READ CONFIGURATION For reading the configuration SMS can be sent from any number i e it is not necessary that it should be authentication number only The SMS formats are mentioned below gt To read authentication numbers When unit receives this SMS it will reply with an SMS as follows Command 123RA Acknowledgement Authentication numbers are 910123456789 919876543210 gt To read the currently configured SMS reporting numbers When unit receives this SMS it will reply with an SMS as follows Assuming only 02 reporting numbers are configured Command 123R1 Acknowledgement SMS Nos 910123456789 919876543210 gt To read configured SMS text Read channel 1 Alarm text mess
2. Reporting text for channel 1 Alarm on channel 1 Set channel 2 Alarm text message Command 123M2 Alarm on channel 2 Acknowledgement Reporting text for channel 2 Alarm on channel 2 Set channel 3 Alarm text message Command 123M3 Alarm on channel 3 Acknowledgement Reporting text for channel 3 Alarm on channel 3 Set channel 4 Alarm text message Command 123M4 Alarm on channel 4 Acknowledgement Reporting text for channel 4 Alarm on channel 4 MANES media converters Set analog channel 1 Alarm text message Command 123M5 Alarm on Analog 1 Acknowledgment Reporting text for Analog 1 Alarm on Analog 1 Set analog channel 2 Alarm text message Command 123M6 Alarm on Analog 2 Acknowledgment Reporting text for Analog 2 Alarm on Analog 2 To set confiqurable text to be added with periodic reporting SMS 123M7 Text Where Text is the text message which will be the part of periodic reporting SMS and will specify device information such as serial number location etc configured by user Please note that and should not be part of the text Maximum text length can be of 50 characters Default text for reporting text would be Device Id 023456 Unit will send acknowledgement SMS as following Command 123M7 Device ID 0123456 Acknowledgement Reporting text for Device Device ID 0123456 To set NO NC status of inputs 1234 XXXX AA BB CC HDD Where X 0 means NO 1 means NC and
3. AA BB CC DD are delays in seconds which can be set for input channels 1 4 respectively These can take value from 00 to 99 seconds If unit is configured as NO there will be alarm SMS if change of state is detected for specified delay period for particular channel For NO configuration SMS format is Command 1234 0000 90 90 90 90 Acknowledgement Configuration of input channels is 0000 Delays set to 90 90 90 90 MANES media converters In below message format input 1 amp 2 is set to NC and input 3 amp 4 is set to NO If this message format is set each input channel will report alarm state if corresponding channel has retained it s changed state for 90 seconds Command 1234 1 100 90 90 90 90 Acknowledgement Configuration of input channels is 1100 Delays set to 90 90 90 90 If unit is configured to bi state there will be alarm SMS if input goes from high to low or from low to high within specified delay period for particular channel For bi state configuration SMS format is Command 1234 2222 00 00 00 00 Acknowledgement Configuration of input channels is 2222 Delays set to 00 00 00 00 So if this message format is set each input channel will report alarm state immediately To set analog input levels Analog channel 1 and channel 2 high and low levels can be set using below SMS command If analog channel value goes above below set levels then unit will send alert SMS
4. Command 1236 Al1L 08 0 AI1H 75 0 Al2L 10 5 AI2H 85 5 Acknowledgement Analog levels are set to AI1LOW 08 0 AI1HIGH 75 0 Al2LOW 10 5 AI2HIGH 85 5 To set periodic status reporting time 123HXX XX in the above format represents hours which can take values from 01 to 24 MANES media converters The status of input channels is sent periodically to reporting numbers e g 123H01 will set periodic reporting time to 1 hour So when this time is set through SMS unit will send status message after every one hour Unit will send acknowledgement SMS as described below Command 123H01 Acknowledgement Periodic Reporting hours are set to 01 Note 123H00 will disable the periodic status reporting To set output status 1235 XY Where X means output number and X means NO NC status Used only for SA42 model X 1 means output 1 and X 2 means output 2 and so on up to output number 6 Y 0 means NO and Y 1 means NC When common C terminal is connected to NO LED corresponding to that output is ON otherwise OFF E g If C1 connected to NO1 then O1 LED will be ON Unit will send acknowledgement SMS as following Command 1235 10 Acknowledgement C1 is connected to NO1 Command 1235 21 Acknowledgement C2 is connected to NC2 Command 1235 30 Acknowledgement C3 is connected to NO3 Command 1235 41 Acknowledgement C4 is connected to NC4 Command 1235 50 Acknowledgement C5 is
5. is in normal state DI4 ON Input 4 is in alarm state OFF Input 4 is in normal state Alt ON Analog Input 1 is in alarm state OFF Analog Input 1 is in normal state Al2 ON Analog Input 2 is in alarm state OFF Analog Input 2 is in normal state O1 ON C1 is connected to NO1 OFF C1 is connected to NC1 02 ON C2 is connected to NO2 OFF C2 is conncted to NC2 O03 ON C3 is connected to NO3 OFF C3 is conncted to NC3 12 media converters 04 ON C4 is connected to NO4 OFF C4 is connected to NC4 O ON C5 is connected to NO5 OFF C5 is conncted to NC5 5 O6 ON C6 is connected to NO6 OFF C6 is conncted to NC6 RANGE Indicates unit range 1 LED ON Low rage 2 LEDs ON Medium range 3 LEDs ON Good range CONNECTOR DETAILS 9 Pin Howder connector for analog amp digital inputs CONNECTOR NAME DETAILS DIt Digital Input channel 1 Common GND terminal Digital Input channel 2 Digital Input channel 3 Common GND terminal DI4 Digital Input channel 4 Ali Analog Input channel 1 Common GND terminal Analog Input channel 2 2 Pin Howder connector for Modbus communication CONNECTOR NAME DETAILS D RS485 D Tx D RS485 D Tx 4 Pin Howder connector for output 1 amp 2 connection CONNECTOR NAME DETAILS C1 Comman 1 NO1 NO for output 1 NO for output 2 MANES media converters 4 Pin Howder connector for o
6. MANES media converters USER MANUAL for Smart Alert VE SA 246M INTRODUCTION SMART ALERT SA is used for obtaining quick SMS alerts from field inputs VE SA 246M allows up to 4 Potential free inputs to be sensed For every input unique separate SMS is sent to multiple reporting numbers Maximum up to 10 different persons could be notified with the alert VE SA 246M allows 6 potential free outputs to be controlled remotely via SMS VE SA 246M allows 2 analog inputs for 4 20 mA signals and also can poll Modbus slave devices through RS 485 interface and send an SMS containing Modbus data FEATURES gt 12 V 2A DC power supply gt 4 number digital potential free alarm inputs with common ground pin gt 2 analog inputs for 4 20 mA signals gt 6 number NO NC outputs gt Built in GSM modem gt Storage of total 10 reporting telephone numbers Each with 14 digits max gt Modbus protocol over RS485 interface supported gt Buzzer for audible status gt Configuration via preformatted SMS gt Dimensions 106 x 63 x 45 mm Excluding connectors and antenna INSTALLING THE UNIT Inserting Removing the SIM Card To insert or remove the SIM Card it is necessary to press the yellow SIM holder ejector button with Sharp edged object like a pen or a needle When this is done the SIM holder comes out a little then pull it out and insert or remove the SIM Card It is very important that the SIM is placed in the right direction for prop
7. age Command 123RM1 Acknowledgement Reporting text for channel 1 Alarm on channel 1 9 MANES media converters Read channel 2 Alarm text message Command 123RM2 Acknowledgement Reporting text for channel 2 Alarm on channel 2 Read channel 3 Alarm text message Command 123RM3 Acknowledgement Reporting text for channel 3 Alarm on channel 3 Read channel 4 Alarm text message Command 123RM4 Acknowledgement Reporting text for channel 4 Alarm on channel 4 Read reporting text for analog channel 1 Command 123RM5 Acknowledgment Reporting text for Analog 1 Alarm on Analog 1 Read reporting text for analog channel 2 Command 123RM6 Acknowledgment Reporting text for Analog 2 Alarm on Analog 2 Read Device Information text message Command 123RM7 Acknowledgement Reporting text for Device Device ID 0123456 To read current NO NC status of inputs Command 123R4 Acknowledgement Configuration of input channels is 2222 Delays set to 00 00 00 00 To read current status of outputs Command 123R5 Acknowledgement C1 is connected to NO1 C2 is connected to NC2 C3 is connected to NO3 10 MANES media converters C4 is connected to NC4 C5 is connected to NO5 C6 is connected to NC6 To read analog input levels Command 123R6 Acknowledgement Analog threshold values are set to AI1LOW 08 0 AI1HIGH 75 0 Al2LOW 10 5 AI2HIGH 85 5 To read periodic sta
8. connected to NO5 Command 1235 61 Acknowledgement C6 is connected to NC6 MANES media converters gt To link Output with inputs In VE SA 246M outputs can be used by 2 methods One using directly SMS specified in above 1235 format and second one is based on input channels alarm condition If output is linked to the input channels then that particular output is connected to NO when any one the input goes into alarm state This output will restore to NC after set time format explained in pulsed configuration below Command to link outputs to inputs 1238 XXXXXX where X 1 or 0 E g 1238 101010 will link outputs 1 3 5 to the inputs and outputs 2 4 6 to be operated as independent output on SMS Whenever any one of the 4 digital inputs goes into alarm output 1 3 5 will be connected to NO and will restore automatically to NC depending on next Latch Pulsed configurations Unit will send acknowledgement SMS as following Command 1238 101010 Acknowledgement Output linked to inputs OP1 Y OP2 N OP3 Y OP4 N OP5 Y OP6 N gt To set time out for output auto restoral Each output can be restored to NC after setting time period through following SMS format 1237 XAA HX AA X AA XAA X AAFXAA Where X S seconds M Minutes H hours A Any digit between 0 9 e g 1237 S60 M30 HO5 S99 M99 H24 will configure output 1 to be connected to NO1 for 60 Seconds output 2 to be connected
9. en SMS to activate output is received it changes the output state VE SA 246M has 4 inputs DI1 Dl4 and two common GND terminals The four potential free contacts must be connected to these inputs The inputs are configurable as NO Normally Open or NC Normally closed or bi state inputs in normal condition When any input changes its state SMS for that input is sent to the configured reporting numbers All numbers are reported one after another The unit can send 4 different SMS messages for each input and the English text is also configurable SMS text can be maximum 120 characters VE SA 246M supports two analog inputs Al1 and Al2 with one common GND terminal Analog inputs can be set to indicate alarm on crossing low or high levels set in Two alarms can be set Lo alarm and Hi alarm When input to that analog channel goes below low level or goes above high level alarm SMS corresponding to that analog input is sent to reporting numbers The status of each input channel is sent periodically to the reporting numbers along with data received from Modbus slave device Also status message of input channels are sent indicating channel is in alarm or in normal state The period of reporting is also configurable from 01 24 hours If this value is set to zero periodic status reporting is disabled The instantaneous status can also be obtained on demand by user by sending a SMS to the unit Any configuration of unit can be done through two aut
10. er working Connecting External Antenna Connect the external SMA antenna to the male antenna connector of the unit The frequency of the antenna should be GSM 850 900 1800 1900 The right Antenna should be used with the specified frequency otherwise it can affect the communication Power Supply Screw type connector with 12V DC 2A supply Digital Inputs For SA246 connect the potential free contact wires to DI1 Dl4 terminals of unit The other end of contact can be connected to common GND terminal provided MANES media converters Analog Inputs Ali and Al2 are provided for analog inputs The 4 20mA sensor output should be connected to Al1 or Al2 terminal and other end is to be connected to GND Digital Outputs SA246 supports6 digital outputs with two potential free NO NC contacts for each output The contact rating is 230V 15A So appropriate capacity load can be switched using these outputs Whenever unit is powered off DO status falls back to NC status and is restored to last condition upon resumption of power OPERATION At power on unit beeps twice and power LED glows steady The unit checks for range and range LED 1 blinks while the unit gets the range When the range is found LEDs become steady In good range all 3 LEDs glow In medium range only 2 LEDs will glow and in low range only 1 LED will glow Unit then starts scanning inputs and report alarm as and when it detects change of input state Wh
11. henticated numbers only These numbers can be changed at site At factory shipping time default number is configured as per user request blank When unit receives pre formatted SMS messages it acts per the message command The configuration can be changed only through authenticated numbers whereas general status read can be done through any number Device continuously poll Modbus data and will send an SMS automatically when there is change of data and also at periodic time interval configured by user to receive periodic status Total of 5 Modbus queries can be preconfigured 2 MANES media converters SMS FORMATS FOR CONFIGURATION gt To set SMS reporting numbers 1231 XX XX XX XX XX XX XX XX XX XX Where XX is dialing number Maximum length can be 14 digits for each number Unit will send acknowledgement SMS as following Assuming 2 numbers are configured Command 1231 910123456789 919876543210 Acknowledgement SMS Nos 910123456789 919876543210 gt To set SMS text for each channel 123MX Text Where Text is the text message for each of 1 4 inputs respectively and X is channel number Please note characters and should not be part of SMS alert text Maximum text length can be 120 characters Default text is Alarm on Channel X for input X Unit will send acknowledgement SMS for respective commands as follows Set channel 1 Alarm text message Command 123M1 Alarm on channel 1 Acknowledgement
12. o network congestion or peak network traffic it takes more than 1 minute for SMS reception 4 If you still do not receive the SMS then kindly return the device MANES media converters gt keep receiving INVALID COMMAND SMS from unit 1 Kindly send SMS 123RA 2 Read the authentication numbers set 3 Ensure you are sending SMS from one of the two authentication numbers set 4 If authentication number is being used to send SMS then kindly ensure the command being sent is syntactically correct gt Input LED s keep turning ON and OFF in cyclic fashion 1 Kindly return the device
13. to NO2 for 30 Minutes Output 3 to be connected to NO3 for 5 Hours and so on If output is linked with input output timing must be a non zero value If configured zero it will set to 5 seconds automatically MANES media converters If output is not linked with input and timing is configured to 00 then it will not restore the output to NC Each reporting number will receive SMS after output is restored automatically Note Output 2 is configured to be ON for 30 minutes But user can restore the output to NC by sending SMS as 1235 X1 before 30 minutes are over SMS override is allowed Where X 1 2 3 4 5 6 i e output number Unit will send acknowledgement SMS as following Command 1237 S60 M30 HO5 S99 MI9 H24 Acknowledgement OP1 ON for 60 Sec OP2 ON for 30 Min OP3 ON for 05 Hrs OP4 ON for 99 Sec OP5 ON for 99 Min OP6 ON for 24 Hrs gt Toset MODBUS query frame 123QX YYYYYYYYYYYY ABC Where X Number of Queries Maximum of 5 queries Y MODBUS Query frame in HEX without check sum A S M or H indicating Seconds Minutes Hours and B C Numberic value between 0 to 9 E g 123Q1 010300E80003 S05 will configure 010300E80003 as MODBUS query where 01 is device ID 03 is function code OOE8 is modbus address and 0003 is length to be read S05 will indicate Query response timeout If no response in this time is received device will poll next query Command 123Q1 01020000000A S02 Acknowledgement
14. tus reporting hours Command 123RH Acknowledgement Periodic Reporting hours are set to 01 To read current status of inputs Command 123RS Acknowledgement CH1 NO ALERT CH2 NO NORMAL CH3 NO NORMAL CH4 NO NORMAL Al1 NORMAL Al2 ALERT Device ID 0123456 This message tells all input channls are configured as NO Channel 2 3 amp 4 inputs and analog chanel 1 are in their normal state and Digital input 1 and analog input 2 is in alarm state Also the message configured by user using M7 command will be added towards the end of periodic reporting to indicate device ID location Serial Number To read auto restoral output timeout Command 123R7 Acknowledgement OP1 ON for 60 Sec OP2 ON for 30 Min OP3 ON for 05 Hrs OP4 ON for 99 Sec OP5 ON for 99 Min OP6 ON for 24 Hrs MANES media converters gt To read output linked with input or not Command 123R8 Acknowledgement Output linked to inputs OP1 Y OP2 N OP3 Y OP4 N OP5 Y OP6 N gt To read MODBUS Query set Command 123RQ Acknowledgement MODBUS Queries are Q1 01020000000A S02 Q2 Undefined Q3 Undefined Q4 Undefined Q5 Undefined LED INDICATIONS LED Meaning NAME PWR ON Unit is powered on Dit ON Input 1 is in alarm state OFF Input 1 is in normal state DI2 ON Input 2 is in alarm state OFF Input 2 is in normal state DI3 ON Input 3 is in alarm state OFF Input 3
15. utput 3 amp 4 connection CONNECTOR NAME DETAILS C3 Comman 3 NO3 NO for output 3 C4 Common 4 NO4 NO for output 4 4 Pin Howder connector for output 5 amp 6 connection CONNECTOR NAME DETAILS C5 Comman 5 NO for output 5 Common 6 NO for output 6 TROUBLESHOOTING gt Unit doesn t power ON 1 Verify input voltage supply connections with their polarity 2 Check the supply 12 VDC with the help of Digital Multi Meter gt Not receiving SMS from SA40 SA42 unit 1 Ensure device has range Range LEDs are constant If range LED s are blinking then device has poor range Check antenna connections or check if SIM card is present and if present then make sure it is inserted properly 2 If device range indications LEDs are constant then make sure the SIM card has enough balance to send an SMS and or is SMS service enabled Before inserting new SIM card in the device it is advised to check the new SIM card on a mobile device for SMS functionality and balance check 3 If Range LEDs are constant and device SIM is inserted properly and has sufficient balance then send any configuration read command such as 123R1 or 123RH and check if device makes a long beep This indicates device has received SMS Now closely follow the device device will again give 2 short beeps this indicates device has acknowledged the received SMS command NOTE Kindly be patient sometimes due t