        REGARD Profibus-DP Gateway User documentation
         Contents
1.    Note    A configuration by using the software Wingate   which comes as a standard accessory is  not required and only in case of maintenace or service it   s necessary to do this      In case of maintenance or service the gateway has to be brought to the configuration mode  For  this the switches S4 and S5 have to be set to position    F    and the switch    Interface    has to be  set to position  RS232   Next a connection to the PC serial port has to be established and the  gateway has to be started once more  The program Wingate   automatically selects the  interface parameters correctly  For the operation of Wingate   please take a look at the  Wingate   Online help     5 4 1  Profibus DP configuration parameter    The configuration parameter of the gateway for the Profibus DP master connection can be load  via the GSD file which comes on disk as a standard accessory     e Configuration data  in acc  with GSD file  module    DRAEGER  REGARD Vers  20  3E 10A       DRAEGER  REGARD Vers  21  3E 10A   starting with serial number 28540259   e Diagnostic data  max  8 byte   e Baud rate  automatic detection up to 12 MBaud   e Sync  supported   e Freeze  supported   e Ident  No  0x2079    5 4 2  Serial interface parameter RS232 RS485  The following parameters for the serial interface to the REGARD Control System are already    preconfigured and only in case of maintenance or service the parameters must be reconfigured  by using the software Wingate   which comes on disk as a s
2.  S d  3 B Non inverting input output signal from Profibus  4    E  5 M5 DGND   data reference potential  6 P5 5V supply voltage  7 E    8 A Inverting input output signal from Profibus  9    25    Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA          User documentation REGARD Profibus DP Gateway    9 3  Connection diagram    Connection to the Profibus DP         E                  MAA g    E  BIS BIG   u P  nen  4205716 Issue 1  FAULT A3   of    Connections  Gerti  Ei D 5  TT   EE  Ei pc SSRLY3 NO     Bs Ei 5 a ov  AE  s   UNIGATE   3             l  Soe e ai chi6e chi5e chi4e ch13 0 ch12 0 chite  Profibus DP       IP         Deutschmann Automation  GmbH    Termination Interface  On CE OM 232 CH aes    vvs ng ee vv ome    15         EE DANGER        Picture 2  Connection to the internal REGARD system bus    Power supply    Note     Please make sure  that the connection between the gateway and the REGARD Control   System is correct  otherwise a communication error accures within the Control System    Gateway RS485 A  Pin No  4   gt  REGARD system bus  RS485 A    Gateway RS485 B  Pin No  3   gt  REGARD system bus  RS485 B     26  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    9 4  Hexadecimal table                                                          Hex Decimal Binary  0 0 0000  1 1 0001  2 2 
3.  distinction can be made between two error categories    Serious errors  1 5   In this case  the gateway must be switched off and switched back on again   If the error occurs again  the gateway modul must be exchanged and returned for repair   Warnings  6 15   These warnings are displayed for one minute simply for information purpose  and are then automatically reset  If such warnings accure frequently  please inform the  Dr  gerService     In the configuration mode these displays are not valid and only meant for internal use                                                                             LED8  LED4  LED2  LED1 Error no   Error descrition  resp  ID   0 0 0 0 0 Reserved  0 0 0 1 1 Initialisation error of the RS485 RS232 interface  0 0 1 0 2 EEROM error  0 0 1 1 3 Stack error  0 1 0 0 4 Hardware fault of the fieldbus ASIC  0 1 0 1 5 Configuration error of the gateways  unknown   protocol   0 1 1 0 6 Reserved  0 1 1 1 7 RS485 RS232 transmit buffer overflow  1 0 0 0 8 RS485 RS232 receive buffers overflow  1 0 0 1 9 Timeout on reception RS485 RS232 interface  1 0 1 0 10 Transmit error of the RS485 RS232 interface  1 0 1 1 11 Receive error of the RS485 RS232 interface  1 1 0 0 12 Adressing error of the RS485 RS232 interface  1 1 0 1 13 Configuration error by the Profibus Master  1 1 1 0 14 General error of the RS485 RS232 interface  1 1 1 1 15 Internal error  Table 1  Error handling   22    REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    D
4.  master  e g  a PLC DCS  can interrogate  only information from one channel card at a time  In order to achieve this the Profibus DP master  has to transmit first a channel card number to the gateway  There upon the gateway places the  requested information of the selected channel card from the buffer into the data output register  and the Profibus DP master can read in the data now by a query     In addition to the data for status and gas concentration also the channel card number is supplied  by the gateway  Thus the Profibus DP master is put into the position to determine whether the  information of the selected channel is already present  valid   or whether the gateway still  provides information for a channel out of a query taken place before  data validation      In order to enter the data of all channels cards in a REGARD Control System  the attached  Profibus DP master must query all channel cards cyclically     Up to 32 users  transmitter and receiver  can be summarized on the Profibus in a line structure   Thus there is the possibility to setup a very complex distributed system with the REGARD  Profibus DP Gateway that consist  e g  of a PLC DCS as a Profibus DP master and a  connection of up to 31 separate REGARD Control Systems with up to 99 REGARD channels   theoretical upper limit      There is also the possibility to integrate a REGARD Control System with attached REGARD  Profibus DP Gateway into an already existing Profibus fieldbus network     2 3  Note    Th
5.  r   0 1  gt  reset flag    new status       q   0 1  gt  alarm acknowledge    c   0 1  gt  command mode and alarm inhibit without lock  up to 10  minutes        0 1   command mode and alarm inhibit with lock  permanent    e   0 1  gt  end command mode and alarm inhibit        3  Byte           0000 Odef       f   0 1   maintenance password for command mode   e   0 1   gt  configuration password for command mode   d   0 1  gt  service password for command mode          All flags in the 3rd byte can be set optional with flags    c    and    I    in the 2nd byte      Description     1  Byte  Selection of the REGARD channel card by the channel card number  1 up to max  99  for  querying of status and gas concentration  see Item 3 2 output data   In the 2nd and 3rd  byte additional flags can be set  which will activate functions at the selected channel    card     Functions for the Master card shall be activated by selecting card number 100  for Extra   Master cards 101 to 109 and for all cards  channel cards  Master  and Extra Master  cards  by 127  This selection will only return the card number in the 1st byte in the  output data  The flag    t    for timeout in the 7st byte is only relevant for the Master card   All other flags in the output data will be set to    0        Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA       User documentation REGARD Profibus DP Gateway    2  Byte  Flag    r      Reset flag    
6.  un acknowledged   111   100 110  gt  Alarm 1  A1  acknowledged  but still activ        4  Byte 0000 0222 222   000 010  gt  Alarm 2  A2  off   222   001 011 101 111  gt  Alarm 2  A2  un acknowledged   222   100 110  gt  Alarm 2  A2  acknowledged  but still activ        5  Byte 0000 0333 333   000 010  gt  Alarm 3  A3  off   333   001 011 101 111  gt  Alarm 3  A3  un acknowledged   333   100 110  gt  Alarm 3  A3  acknowledged  but still activ        6  Byte 0000 Offf fff   000 010  gt  Fault  FLT  off   fff   001 011 101 111  gt  Fault  FLT  un acknowledged   fff   100 110  gt  Fault  FLT  acknowledged  but still activ        7  Byte 0000 tcih h   0 1  gt  Transmitter  Measuring head calibration  H cal     i  0 1  gt  Alarm inhibit    c   0 1  gt  critical failure    t   0 1   Timeout        8  Byte  00mm mmmm   00mmmmmm  High byte for gas concentration       9  Byte  nnnn nnnn nnnnnnnn  Low byte for gas concentration       10  Byte  0000 sfdd dd   00 01 10 11   0 1 2 3 decimal places   f   0 1   gt  measuring range exceeded   s  0 1  gt  negative sign                     Byte 8 and byte 9 can also read in by the Profibus DP Master as    Word    value      Description     1  Byte  Channel card number  1 to max  99  for the available data in bytes 2 to 10 for status and  gas concentration  With the channel card number it s possible for the Profibus DP  master to determine whether the information of the selected channel is already present   valid   or whether the gateway still 
7. 0010  3 3 0011  4 4 0100  5 5 0101  6 6 0110  7 7 0111  8 8 1000  9 9 1001  A 10 1010  B 11 1011  C 12 1100  D 13 1101  E 14 1110  F 15 1111                27  Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    Draeger Ltd   Kitty Brewster Industrial Estate  Blyth   Northumberland   NE24 4RG   England   T  44 1670 352891   Fax  44 1670 356266    Dr  ger Safety AG  amp  Co  KGaA  Revalstra  e 1   D 23560 L  beck   Germany   Z  49 451 882 2794   Fax  49 451 882 4991    Draeger Industrie S A    3c  route de la F  d  ration  F 67025 Strasbourg Cedex  France      33 388 407676   Fax  33 388 407667    Draeger Safety  Inc   P O  Box 120  Pittsburgh  PA 15 230  U S A       1412 787 8383  Fax  1 412 787 2207    Draeger South East Asia Pte  Ltd   67  Ayer Rajah Crescent  06 03  SGP 0513 Singapore   Singapore      658729288   Fax  65 773 20 33    http   www draeger com    28  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    Beijing Fortune Draeger Safety  Equipment Co  Ltd    Jixiang Lu  B Area   Beijing Tianzhu Airport Industrial Zone  Houshayu  Shunyi County   Beijing 101300  P R  China      86 10 69498000   Fax  86 10 69498006    
8. Dr  ger    REGARD Profibus DP Gateway  User documentation       REGARD Profibus DP Gateway  Part Number  AG00485    Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA  Revalstra  e 1   23560 L  beck  Germany   Telefon  49  451  882 4147  Telefax  49  451  882 4991       User documentation REGARD Profibus DP Gateway    CONTENTS  A Nee NO AT 4  2   IPIUF   CU CU   T  da 5  2 1  Intended Us iii ie aa 5  2 23 RE lee E 5  235 Noti A San ee ah ee tare 6  Y  Data transmission    aos 7  3 1  MPU ata  Aa a Ad ibi 7  3 2  Qutp  t d  ta isa en 9  DES e ehe niederen nennen 11  4  Installation    ee id 13  4 1  Control cabinet installation    seinen een ann  13  4 2  Equipotential bonding CONNECTION ENEE 14  43    POWEr SUPPLY EE 14  4 4  REGARD Control System CONNeCtlON scsi 14  4 5  Profibus DP CONNECTION EEN 15  4 6  Shielding Connection cima nen 15  4 7  SGORMECHON Cla GEA  dde 16  5     Configuration    teilen aa ian ivan Rasta 17  5 1  Profibus DP u  iii 17  5 1 1  Rotary coding switch    Profibus ID High and LOW  seen 17  5 1 2  Slide switch    Termination Profibus    AAA 17  5 2  Serial interface RS232 RS485 sniene nna a n a iT 17  5 2 1  Rotary coding switch    S4   S5  RS485 ID  kee 18  5 2 2  Slide switch    Interface  RS485 RS232           nemnnneensnnennennnnnnnnnnnnennnnnnnnannnnnarnn 18  5 2 3  Slide switch    Termination  RS485 ON OFF   nee 18  5 3  REGARD Control System           cccccsscsssssscsssscsscsesssscssssseesesaesesacsesessesecessesensesesaesessesese
9. Gateway operates only as a Slave on the internal serial REGARD  system bus and even thus it can not read or send data direct to REGARD channel cards  This  function is taken over by the REGARD Master card in a REGARD Control System     The Master card queries cyclically all channel cards for status  alarms  faults  maintenance  messages and critical failures  and the current gas concentrations  For a REGARD Control   System the cycle time to query 99 channnels for status is approx  2 2 sec  and approx  10 sec   for the gas concentration    The gateway analyses all information about status and gas concentrations of the channel cards  and stores the data accordingly sorted to the channel card number in a internal buffer  With each  renewing query of the Master card the data already available in the buffer are updated     Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    After every query cycle for the status of the channel cards  so after 2 2 sec  the Master card  queries also the gateway for data  alarm acknowledge  command mode and alarm inhibit  for  overtaking into the REGARD Control system  H data is available  it will be overtaken by the  Master card and passed on to the channel card  which will then execute the function     On the Profibus DP fieldbus the REGARD Profibus DP Gateway behaves likewise only as a  Slave  An attached standard conformal Profibus DP
10. P fieldbus coupling for the  REGARD Control System of Dr  ger Safety AG  amp  Co  KGaA and enables the access to  informations about the current status of alarms  faults  maintenance messages and critical  failures as well as the current gas concentrations of all REGARD channel cards  e g  4 20mA    SE EX   HART  cards      for a REGARD Control System    In addition to that the gateway provides the possibility to acknowledge alarms and faults for a  single or all cards as well as putting single or all cards into command mode to inhibit alarms   For the proper operation of the REGARD Profibus DP Gateway a REGARD Master card is  necessary     2 2  Description    As a base for the REGARD Profibus DP Gateway the universal fieldbus gateway UNIGATE   of  the company Deutschmann Automation GmbH was selected  In the standard version this  gateway adapts a serial interface RS232 RS485 to the Profibus DP according to the standard  EN 50170  In this version the data are transferred transparenctly     In order to consider the special protocol characteristics of the REGARD Control System and   at the same time to ensure a significant figure of the transferred information on the Profibus DP  field bus  the software of the gateway was redesigned by the manufacturer following the  specifications of the Dr  ger Safety AG  amp  Co  KGaA     REGARD Control Systems with up to 99 REGARD channels are supported by a REGARD  Profibus DP Gateway using the REGARD Master card    The REGARD Profibus DP 
11. REGARD Profibus DP Gateway    3 2  Data exchange    The following flowchart shows in a simple form the cyclically data exchange between a Profibus   DP Master and the REGARD Profibus DP Gateway  The activation of functions for all channel  cards  Master cards or Extra Master cards is not included in this flowchart     Initialising    MaxChannelCards   99   ChannelCard   1            Alarm                  acknowledge  Command  ment   mode    R End  command  mode         initialising gateway input data   channel card  alarm acknowledge     flag    q         1  initialising Gateway input data     channel card  command mode and  alarm inhibit   flag    c    or flag    l         1       initialising Gateway input data   channel card  end command mode and  alarm inhibit   flag    e       1     send gateway input data    read gateway output data    evaluate measuring value  of gas concentration     high  and low byte  decimal places   measring range exceeded  sign    CES       11    Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway            new status  flag    n     lt  1     evaluate status   A1  A2  AS  fault  calibration  alarm  inhibit  critical failure  timeout    initialising gateway input data   reset flag    n    of output data with  flag    r         1    of input data     send gateway input data    initialising gateway input data   new status  alarm acknowledg
12. e   command mode and alarm inhibit     password  all flags      O        send gateway input data       ChannelCard   lt MaxChannel   cards            ChannelCard   ChannelCard  1 ChannelCard   1    12    REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    4  Installation    mi    UNIGATE  Profibus DP    Protibuz 1D   On CR Op  Tarm nation  BusPower     BusState       BusErrar    Deutschmann Automation  GmbH   Termination Interface   On CR OM 238 CR 483    Error No   Seloct ID  TES    OUE  ec   ODN  Per       Picture 1    4 1  Control cabinet installation    The gateway has been developed for use in a control cabinet use  IP20  and therefore it must be  mounted on a standard top hat rail  deep top hat rail according to EN 50022      e Engage the gateway modul from the top in the top hat rail and swivel it down until the module  engages in position   e Above and below the gateway modul must be at least 5 cm clearance for heat dissipation     13  Regard Profibus DP Gateway  User documentation   Issue 4     13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    4 2  Equipotential bonding connection    e Connect the standard top hat rail  deep top hat rail according to EN 50022  with as low  impedance as possible to the equipotential bonding strip of the control cabinet  see Item  4 7 Picture 2   Use a flexible earthing 
13. e available operating manual to the REGARD Profibus DP Gateway describes all substantial  functions of the gateway and deals in particular with the installation  the configuration and the  operation of the gateway with the REGARD Control System    If you should need further information about the universal field bus gateway UNIGATE    please  refer to the provided original user manual of the company Deutschmann Automation GmbH     REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    3  Data transmission    By an attached Profibus DP master the current status of the alarms A1  A2  A3 and Fault   Transmitter Measuring head calibration  alarm inhibit  critical failure  timeout and the current gas  concentration with sign  decimal places and measuring range exceeding of each channel card  can be queried   Additionally a Profibus DP master is able to acknowledge alarms and faults of single or all  channel cards as well as activating the command mode  If the command mode is activated  automatically alarms will be inhibit     The complete functionality of the gateway is linked to the Profibus DP with 3 byte input data and  10 byte output data     3 1  Inputdata       1  Byte    Osss ssss    Card number 1 to 99 for channel cards  100 for Master card  101 to  109 for Extra Master cards or 127 for all channel cards  Master  and  Extra Master cards        2  Byte    000e Icqr   
14. ference signal      gt  Difference signal       Transmission method    Master   Slave    Master   Slave       Number of users      32 Transmitters  32 Receivers    1 REGARD Control System with  REGARD Master card and up to  99 REGARD channels        Bus topology    Line    Line       Data rate    Max   12 MBits s   Standard  9 6 kBits s  19 6 kBits s   93 75 kBits s  187 5 kBits s    500 kBits s 1 5 MBits s  3 MBits s   6 MBits s  12 MBits s    4 8 kBits s          Cable length       Max   1200m   Baud rate dependent   93 75kBd   gt  1200m   500 kBd   gt  500m    gt  1 5 MBd   gt  100m       1200m       REGARD Profibus DP Gateway    24    User documentation   Issue 4   13 February 2007      Dr  ger Safety AG  amp  Co  KGaA       User documentation REGARD Profibus DP Gateway    9  Appendix    9 1  REGARD Control System connection    Pin assignment  5 pin screw type plug connector       Pin No    REGARD Profibus DP Gateway    Function    REGARD Control System       Power supply 24V DC    Power supply    Power supply 24V DC       Power supply OV    Power supply    Power supply OV       RX   RS485   RS485 B     Receive signal    Internal Bus RS485 B       TX   RS485   RS485 A     Transmit signal    Internal Bus RS485 A             a PRoOMN        GND  connection to Pin No  2        Reference for Pin 3   4          9 2  Profibus DP connection    Pin assignment  9 pin Sub D socket connector                                              Pin No    Name Function  1  Shield  Schield   2
15. he 2nd byte of the input register will remain in this status and they must be  reset to    O    after the function is executed to activate a specific function again     3  Byte  Flag    f      gt  The command mode will be activated with maintenance password   Flag e   gt  The command mode will be activated with configuration password   Flag    d      gt  The command mode will be activated with service password     Note     All flags in the 3rd byte are optional parameters for the activating of the command mode  with flag    c    and    I    in the 2nd byte    If there is more then one flag set  only the flag with the highest priority will be considered  where flag    f    has the highest priority and flag    d    has the lowest priority    All flags in the 3nd byte of the input register will remain in this status and they must be  reset to    O    after the function is executed to activate a specific function again     REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    3 2  Output data       1  Byte Osss ssss Card number 1 to 99 for channel cards  100 for Master card 101  to 109 for Extra Master or 127 for all cards        2  Byte 0000 000n n   0 1  gt  new status  A1  A2  A3  fault  Transmitter Measuring  head calibration  alarm inhibit  critical card fault  timeout         3  Byte 0000 0111 111   000 010   Alarm1  A1  off   111   001 011 101 111  gt  Alarm 1  A1 
16. he Profibus ID and the Bus Termination                    Rotary coding switch  Profibus ID High Profibus DP ID  High byte   Rotary coding switch  Profibus ID Low Profibus DP ID  Low byte   Slide switch    Termination    Switchable Profibus DP termination resistor       5 1 1  Rotary coding switch    Profibus ID High und Low       These two switches are used to set the Profibus ID  00  7D  of the gateways in hexadecimal  notation  A conversion table from decimal to hexadecimal can be found in the appendix  This  value is read only once when the gateway is activated and cannot be changed via the Profibus   In case of changing the position of the rotary coding switches the gateway must be switched off  and switched back on again     5 1 2  Slide switch    Termination Profibus       If the gateway is operating as the first or last physical device in the Profibus DP  there must be a  bus termination at the gateway  In order to do this  either a bus terminating resistor must be  activated in the connector or the resistor  22002  integrated in the gateway must be activated  In  order to do this  move the slide switch to position    ON     In all other cases  the slide switch must  remain in the position    OFF     For further information on the subject of bus termination please  refer to the general Profibus literature     5 2  RS232 RS485 interface    The gateway features 4 switches to set the RS232 RS485 interface  the RS485 ID and the Bus   Termination                          R
17. ipotential  bonding  next to the gateway module  see also Item 4 7 Picture 2      14  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA       User documentation REGARD Profibus DP Gateway    4 5  Profibus DP connection  The connection of the REGARD Profibus DP Gateway to the Profibus DP is routed via the 9 pin  Sub D socket  see also Item 4 7 Picture 2   Use only cable which is certified for Profibus DP    applications     Pin assignment  9pin Sub D socket                                           Pin No   Name Function   1  Shield  Shield    2   E   3 B Non inverting input output signal from Profibus  4   A   5 M5 DGND   data reference potential   6 P5 5V supply voltage   7       8 A Inverting input output signal from Profibus   9   z         The shield of the Profibus cable is connected to the equipotential bonding system via an RC   network  This guarantees higher interference immunity of the gateway module since the cable  shield current which may be up to a few Amperes owing to potential differences between two  bus users is not discharged via the device     4 6  Shield connection    The shield signal for the electronic circuitry is connected to the DIN rail via the integrated  earthing connection in the left part of the device    The shield of the Profibus cable must be directly linked up to the 9 pin Sub D socket connector   see also Item 4 5  and is connected to the equipotential bonding system via an RC ne
18. n     new status  in the 2nd byte of the output data    Flag    q      gt  Acknowledge alarms    Flag    c      Activates the command mode and the alarm inhibit without lock   The cards will return into the normal operation mode automatically after  10 minutes  The cards can also be reset to normal operation mode before  expiration of 10 minutes by setting flag    e      Optional the command mode can be activated with password for  maintenance  configuration and service  To do this one of the flags    f        e     or    d    must be set  If the command mode is activated without password all  configuration parameters of the card can only be read    Flag    l      Activates the command mode and the alarm inhibit with lock   The cards will not return into the normal operation mode automatically and  must be reset by setting flag  e      Optional the command mode can be activated with password for  maintenance  configuration and service  To do this one of the flags    f        e     or    d    must be set  If the command mode is activated without password all  configuration parameters of the cards can only be read    Flag e   gt  Exits the command mode and the alarm inhibit     Note     In the 2nd byte all flags only triggers functions  if they are changing from    O    to    1     If  there is more then one flag set  only the flag with the highest priority will be considered  where flag    r    has the highest priority and flag    e    has the lowest priority    All flags in t
19. nsesas 18  5 4  Select REGARD protocol             cccccsssscsssscsesscsessssesecsescseceessesesesscseseesesecseesasesecesessesavensas 19  5 4 1  Profibus DP configuration data een 19  5 4 2  Serial interface data RS232 RS485         nnnnsnnnnnnennnnnnnnnnennnnnnnnnnnnnnnnnannnnnannnanan 19  6 2  V  sualiindie  tion iii iaa Den ea aa 20  6 1 2 LED Be EE de 20  0 27 PED Re EE 20  6 3  LED  BUS State    nahen 20  6 4  ILED   PowWer    EEN 20  60 LEDO SIS  anadir ASA AA A da 21  66 RTE 21  TETONA e RE 22  8   Technical data    ida 23  Sul     Device dal u    ei seen essen in Dr ete diab es 23  9 2    Interface data  ee Seed geet ee 24    REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    CONTENTS   Di AD PET  I E E T Dti 25  9 1  REGARD Control System connection    ussnenssnrerennunnnerennnensereneneensnennnonnnnarsrarennananerens 25  9 2  Profibus DP Connections anne Blunt 25  9 3  Connection ACE AINE sr iia EEE 27  9 4  Ee EI EE 28    Regard Profibus DP Gateway  User documentation   Issue 4     13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    1  For your safety    The law for governing technical work equipment  equipment safety law  requires to point out the  following points il    Strictly follow the Instructions for Use  Any use of the REGARD Profibus DP Gateway requires full understanding and strict observa
20. otary coding switch S4 RS485 ID  High byte   Rotary coding switch S5 RS485 ID  Low byte   Slide switch  Interface  Switch to select RS485 or RS232 interface  Slide switch    Termination    Switchable RS485 termination resistor  17    Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA          User documentation REGARD Profibus DP Gateway    5 2 1  Rotary coding switch    S4   S5  RS485 ID        These two switches are used to set the RS485 ID of the gateway in hexadecimal notation   Operating the gateway with the REGARD Control System switch    S4    and    S5    must be set to  position    0       In case of maintenance  see also ltem 5 4  the gateway has to be brought to the configuration  mode by setting the switches   54  and    S5    to the position    F     The setting is read in only once  when the gateway is activated  In case of changing the position of the rotary coding switches the  gateway must be switched off and switched on again     5 2 2  Slide switch    Interface  RS485 RS232        This switch is used to select whether the gateway is running with the REGARD Control System  or in the configuration mode in case of maintenance  see also ltem 5 4   Running the gateway  with the REGARD Control System the switch    Interface    must be set to position  RS485     For running the configuration mode to position  RS232      5 2 3  Slide switch    Termination  RS485 ON OFF      If the gateway is operated as 
21. provides information for a channel card of a query  taken place before  data validation   For card number 100 only the flag    t    for timeout in  the 7st byte is relevant  All other flags in the output data will be set to    0        2  Byte  Flag    n      The status in the byte 3 to 7 has changed against the last query of this  channel card  If this flag is set  then all flags in byte 3 to byte 7 has to be  evaluated again  This flag remains in it   s status until it   s reset with flag    r     in the 2nd byte of the input data     9    Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    3  Byte  Flags    111      With 3 flags the status of the 1st alarm  A1  will be shown   Depending on the alarm configuration of the channel card different  flags will be set for an identical alarm status      4  Byte  Flags  222    With 3 flags the status of the 2st alarm  A2  will be shown   Depending on the alarm configuration of the channel card different  flags will be set for an identical alarm status      5  Byte  Flags  333   gt  With 3 flags the status of the 3st alarm  A3  will be shown   Depending on the alarm configuration of the channel card different  flags will be set for an identical alarm status      6  Byte  Flags    fff      gt  With 3 flags the status of the fault  FLT  will be shown   Depending on the alarm configuration of the channel card different  flag
22. r  ger Safety AG  amp  Co  KGaA       User documentation REGARD Profibus DP Gateway    8  Technical data    8 1  Device data       Device data        Location     Control cabinet  Top hat rail mounting  35mm        External power supply    10 8 to 30V DC  24V DC nominal        Current consumption    at 24V DC  typ  120 mA  max  150 mA   at 10 8V DC   typ  350 mA       Power supply at the Profibus interface    SV DC   max  50 mA       Protection    Reverse voltage protection  short circuit protection   overload protection       Environment conditions  Temperature     Atmospheric pressure     Relative humidity     O bis  60  C with forced convection    O bis  40  C without forced convection   795 bis 1080 hPa during operation    660 bis 1080 hPa during storage and transport  5  bis 80     no condensation  no corrosive                   atmosphere  Enclosure IP 20  Housing size 90 x 127 x 55 mm  WxHxD    5x 7 x 6   WxHxD   Weight 0 3 Kg  Approvals CE mark  elektromagnetic compatibility        Profibus certification       Regard Profibus DP Gateway  User documentation   Issue 4     13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    23       8 2  Interface data    User documentation REGARD Profibus DP Gateway       Interface data                 Interface designation Profibus DP REGARD  Physical interface RS 485 RS 485  Standard ElA Standard ElA Standard  Transmission mode Symmetrical Symmetrical  Asynchronous Asynchronous  serial Serial  half duplex half duplex      gt  Dif
23. s will be set for an identical alarm status      7  Byte  Flag    h      gt  The transmitter measuring head connected to the channel card has  turned into calibration mode    Flag    i      gt  The channel card is turned into the status alarm inhibit  Alarms will be  inhibit  if the transmitter measuring head connected to the channel card is  turned into command mode or a fault alarm is triggered    Flag    c     gt  A critical failure has occurred at the channel card  For critical failures also  a fault  FLT  occures    Flag    t      gt  A timeout has occured for the selected channel or Master card  No current  data for status and gas concentration is available  because the channel  card is not connected to the control system or the card is not configurated  correctly  With Master cards the card is not connected to the control  system or the card is not configurated correctly     8  Byte  High byte for measuring value ofthe gas concentration   9  Byte  Low byte for measuring value ofthe gas concentration     Note    Byte 8 and byte 9 can also read in by the Profibus DP Master as    Word    value      10  Byte  Flags    dd     gt  Shows the decimal places for the measurement of the gas  concentration   Flag    f     gt  Measuring range exceded has occured   Flag    s     gt  The measurement of the gas concentration has a negative sign     10  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation 
24. tandard accessory  see Item 5 4      e Start bit  1  e Data bits  8  e Stop bit  1    e Parity  None  e Baud rate  4800 Baud   19  Regard Profibus DP Gateway    User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    6 1  Visual indication    The gateway features 9 LEDs with the following significance                                LED Bus Error red Profibus error   LED Bus Power green Profibus supply voltage   LED Bus State red green  Interface status  Profibus DP   LED Power green RS485 RS232 supply voltage   LED State red green  Interface status  RS485 RS232   LED Error No   Select ID   yellow Binary display of the connection to the REGARD  channel number  address   error number       Note    In the configuration mode these displays are not valid and only meant for internal use     6 1  LED    Bus Error       These LED is activated directly by the Profibus ASIC and signals that the Profibus is not in     DATA EXCHANGE    status     6 2  LED    Bus Power       This LED is directly connected to the electrically isolated supply voltage of the Profibus end     6 3  LED    Bus State                      Lights green Profibus in Data Exchange status   Flashes green Gateway waiting for Profibus configuration data  Flashes green red Gateway waiting for Profibus parameter data  Lights red General Profibus error          6 4  LED    Power       This LED is directly connected to the  optionally also elec
25. the first or last physical device in the internal RS485 bus of the  REGARD Control System  there must be a bus termination at this gateway  In order to do this   either a bus terminating resistor in the connector or the resistor integrated in the gateway   1500  must be activated  To activate the integrated resistor the slide switch    Termination    must  be set to position    ON       In all other cases  the slide switch must remain in position    OFF     For further information on the  subject of bus termination please refer to the general RS485 literature    If the integrated resistor is used  please consider that this automatically activates a pull down  resistor  3900  to ground and a pull up resistor  3900  to VCC     5 3  REGARD Control System    On all cards of the REGARD Control System the communication checksum has to be configured  to    CRC     For further information on this subject please refer to the user documentation for the  REGARD Control System     18  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    5 4  Select REGARD protocol    On delivery the protocol software  see also Item 2 2  for the REGARD Control System  adapted  by the company Deutschmann Automation GmbH  is already loaded into the REGARD Profibus   DP Gateway and the parameters for the serial interface to the REGARD Control System are  already preconfigured  see also Item 5 4 2   
26. tion  of these instructions  The gateway is only to be used for the purposes specified hereunder     Maintenance  At regularly time intervals a function test must be performed by qualified personnel  with log    Only qualified personnel is permitted to make any modifications     Use in hazadous areas  The Regard Profibus DP Gateway is not designed or certified to be installed or to be operated in  hazardous areas     Liability for proper functioning or damage   The liability for the proper function of the REGARD Profibus DP Gateway is irrevocably  transferred to the owner or operator to the extent that the gateway is serviced or repaired by  personnel not employed or authorized by Dr  gerService or if the gateway is used in a manner  not conforming to its specified use    Dr  ger Safety AG  amp  Co  KGaA doesn t take any liability for damages caused due to ignoration  of the above mentioned advises    The warranty and liability provisions of the terms of the sale and delivery of Dr  ger Safety AG  amp   Co  KGaA are likewise not modified by the recommendations given above     Dr  ger Safety AG  amp  Co  KGaA    DAIL references to laws  regulations and standards apply to the legal system of the Federal  Republic of Germany     REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    2  Introduction  2 1  Intended Use    The REGARD Profibus DP Gateway provides a Profibus D
27. trically isolated  supply voltage of the  RS485 RS232 end     20  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA          User documentation REGARD Profibus DP Gateway    6 5  LED    State          Lights green    Data exchange active via RS485 RS232       Flashes green    RS485 RS232 ok  but no permanent data exchange       Flashes green red    No data exchange since switching on       Lights red    General gateway error  see LED s Error No            Flashes red       Gateway is in configuration mode       6 6  LED    Error No    Select ID       If these 4 LEDs flash and LED    State    simultaneously lights red  the error number is displayed in  binary notation  conversion table  see appendix  in accordance with the table of Chapter  Error  handling   Otherwise  the card number with which communication is currently operating via the  RS232 RS485 interface is displayed also in binary notation     Regard Profibus DP Gateway    21    User documentation   Issue 4   13  February 2007      Dr  ger Safety AG  amp  Co  KGaA       User documentation REGARD Profibus DP Gateway    7  Error handling    If the gateway modul detects an error  the error is signalled by the red lighting    State    LED and  simultaneously the error number being indicated by means of    Error No     LEDs as shown in the  table below  In addition  this error number is transfered as an external diagnostic byte via the  Profibus to the Master  A
28. twork   This guarantees higher interference immunity of the gateway module since the cable shield  current which may be up to a few Amperes owing to potential differences between two bus  users is not discharged via the device     15  Regard Profibus DP Gateway  User documentation   Issue 4   13  February 2007    Dr  ger Safety AG  amp  Co  KGaA       User documentation REGARD Profibus DP Gateway    4 7  Connection diagram    Connection to the Profibus DP         E                  sera SE  BIS BIG   u P  nen  4205716 Issue 1  FAULT A3   of    Connections  Gerti  Ei D 5  TT  gt  lt   gt     Re    SSRLY3 NO  Bs Ei 5 a ov  AE  s   UNIGATE   3             l  Soe e ai chi6e chi5e chi4e ch13 0 ch12 0 chite  Profibus DP          IP         Deutschmann Automation  GmbH    Termination Interface  On CE OM 232 CH aes    vvs ng ee vv ome    15         EE DANGER        Picture 2  Connection to the internal REGARD system bus    Power supply    Note     Please make sure  that the connection between the gateway and the REGARD Control   System is correct  otherwise a communication error occures within the Contro  System    Gateway RS485 A  Pin No  4   gt  REGARD system bus  RS485 A    Gateway RS485 B  Pin No  3   gt  REGARD system bus  RS485 B     16  REGARD Profibus DP Gateway  User documentation   Issue 4   13 February 2007    Dr  ger Safety AG  amp  Co  KGaA    User documentation REGARD Profibus DP Gateway    5  Configuration    5 1  Profibus DP    The gateway features 3 switches to set t
29. wire with a cross section of at least 10mm  for this    e Fit an earthing terminal to the top hat rail directly next to the gateway module  The earthing  terminal automatically establishes an electrical connection to the top hat rail    e The gateway connection to the equipotential bonding is automatically established via the  integrated earthing connection in the left part of the device when it is put on the DIN rail     4 3  Power supply   The gateway operates with a supply voltage of 10 8V 30V DC  nominal 24V DC   The  connection of the supply voltage is routed via the 5 pin screw type plug connector  see also Item  4 4 and Item 4 7  Picture 2     4 4  REGARD Control System connection   The serial interface connection of the REGARD Profibus DP Gateway to the internal REGARD  system bus is routed via the 5 pin screw type plug connector  see also Item 4 7 Picture 2   Use    a flexible shielded cable with at least 3 wires  for example LiYCY 3x0 25  for this     Pin assignment  5 pin screw type plug connector                         Pin No    REGARD Profibus DP Gateway   Function REGARD Control System  1 Power supply 24V DC Power supply Power supply 24V DC   2 Power supply OV Power supply Power supply OV   3 RX   RS485   RS485 B  Receive signal Internal Bus RS485 B   4 TX   RS485   RS485 A  Transmit signal Internal Bus RS485 A   5 GND  connection to Pin No  2   Reference for Pin 3 4 In                The cable shield has to be connected to the earthing connection terminal  equ
    