1. A DELTA http www delta com tw industrialautomation l lil 5011627202 SXE2 Multi function Built in Analog DVP SX O Multiple Commands PLC Instruction Sheet WARNING This Instruction Sheet only provides descriptions for electrical specifications general specifications installation amp wiring troubleshooting and peripherals Other detail infromation about programming and commands is compatible with SA SC SX series please see PLC Application Manual For more information about the optional peripherals please see individual product manual This is an OPEN TYPE PLC The PLC should be kept in an enclosure away from airborne dust humidity electric shock risk and vibration Also it is equipped with protective methods such as some special tools or keys to open the enclosure so as to avoid the hazard to users and the damage to the PLC Never connect the AC main circuit power supply to any of the input output terminals as it will damage the PLC Check all the wiring prior to power up To avoid any electromagnetic noise make sure the PLC is properly grounded Do NOT touch terminals when power on INTRODUCTION 2 1 Model Name Explanation and Peripherals Thank you for choosing DELTA s PLC DVP series TheDVP SX series is a 10 point 4DI 2DO 2Al 2A0O special main processing unit Besides the same commands and functions as DVP SA SX SC series 2 CH 12 bit analog voltage current input and 2 CH
2. 4 Status indicator POWER RUN ERROR BAT LOW RUN STOP switch 2 digital 7 segment display Digital I O terminal DIN rail clip Analog I O terminals I O point indicators COM1 RS 232 Rx indicator COM2 RS 485 Tx indicator COM1 RS 232 Communication port Slave 11 Nameplate O O lOINIO OA R W NM 12 Expansion port 13 Mounting hold of the expansion unit 14 DIN rail 35mm 15 Expansion unit clip 46 COM2 RS 485 Communication port 17 DC Power input 18 2 pin removable terminal standard accessory 21 Battery socket connection 19 Power input cable standard accessory 22 Battery mount 20 Battery Cover FUNCTION SPECIFICATIONS O y Control Method Stored program cyclic scan system Batch processing method when END command is executed e a Program language _ s amp Commands Ladder aie SFC marie the Sie commands saa Battery 32 Basic sequential commands including STL RET 68 Application commands External input relay X0 X177 octal number system 128 points Total Conecrond to external input point 256 External output relay Y0 Y177 octal number system 128 points points Total Auxiliary tched 4096 Contacts can switch to On Off in Relay points Program TO T199 200 points 1 100ms Tota When the timer that set by TMR T250 T255 6 points Accumulative 4 256 command reaches the preset T200 T239 40 points 2 points value the T contact with the same number wi
3. 12 bit analog voltage current output are all bipolar There is built in 2 digit 7 segment display corresponds to internal register directly to display PLC station or user defined code a Model Name DVP10 SX 11 R Series Name NO Points 6DI 2DO 2AI 2A0 SX Series R Relay T Transistor DC Power Input E Peripherals DVPHPP02 Handheld Programming panel E Nameplate Explanation PLC Model gt MODEL DVP10SX11R Input Power Supply Spec gt POWERINPUT 24Vdc 6W Output Module Spec gt OUTPUT MODULE 2 0A 250Vac 50 60Hz RES LOAD Barcode and Serial Number gt CPU Version gt V1 00 E TT TATU 10SX11R0T4020001 DELTA ELECTRONICS INC MADE IN XXXXXX a Serial Number 10SX11RO T 4020001 a Production number Production week Production Year 2004 Production factory Version type Production model WPLSoft Windows Ladder Logic Programming Software DVPACAB115 1 5M Cable HPP PLC included in DVPHPP0O2 DVPACAB215 1 5M Cable PC DB9 DB25 PLC DVPACAB230 3 0M Cable PC DB9 DB25 PLC DVPACAB2A30 3 0M Cable PC DB9 PLC 2 2 Product Profile and Outline Units mm X Battery replacement Please change the battery within 3 minutes or the internal data of the PLC including the program area RTC and latched registers could be lost or destroyed
4. pilot indicator Emergency stop The machinery must provide a quick manual method disconnecting all system power Circuit isolation device System Power Disconnect Utilize the electromagnetic contactor and the relay to be the isolation unit of the power circuit to prevent the possible instability of the system when the power is supplied on and off DVP PLC MPU main processing unit Grounding Power supply AC 100 240VAC 50 60Hz DC 24VDC Input Point Wiring The input signal of the input point is the DC power DC input There are two types of DC type wiring SINK and SOURCE defined as follows There are two types of DC type wiring SINK and SOURCE defined as follows Sink Current flows into the common terminal S S Source Current flows out of common terminal S S sis zr 1 CMa t Dj O e 0i lt a 7 li ilde Loop Equivalent Circuit of Input Point Wiring Loop DC Type DC Signal IN Sink Type SINK Mode Loop Equivalent Circuit of Input Point Wiring Loop DC Signal IN 24VDC Source Type Output Point Wiring DVP 11 R There are two kinds of DVP SX Series PLC output modules LOAD Relay and Transistor For relevant electrical specification please refer to the function specification AC POWER Be careful with the connection of the common terminals when wiring outputs For example when wiring DVP12SX11R output te
5. the DELTA PLC Technique Application Manual for relevant basic commands and application commands 2 The DVPHPP handheld programming panel and the WPLSoft the Windows version editing program of the ladder diagram are both good for use with the DELTA DVP PLC Also the PLC could connect with the DVP12SX MPU through specific transmission wire to execute the program transmission the MPU control and the program monitoring Judge the errors by the indicators on the front panel When errors occurred on DVP PLC please check xt POWER LED There is a POWER LED at the front of the MPU When the MPU is powered On the green LED light will be on If the indicator is not on when the MPU is powered up and with the input power being normal it is an indication that the PLC is out of order Please have this machine replaced or have it repaired at a dealer near you 3 PLC RUN LED Identify the status of the PLC When the PLC is in operation this light will be on and users could thus use HPP or the editing program of the ladder diagram to give commands to make the PLC RUN or STOP 37 ERROR LED If incorrect programs are input to the MPU or that the commands and the components exceed the allowable range the indicator will blink At this moment the user should check both the error codes saved in the MPU data register D1004 and the Error Code Table below to correct the programs The address that the error occurs will
6. 20 Time ms could be selected through D1020 and D1021 YO and Y1 are specified points for high speed pulse MODEL NAME amp I O CONFIGURATION E E E a 20 20mA 20 20mA Sinkcor range 1000 1000 range 2000 2000 Source 10 10V 10 10V DVP10SX11T range 2000 2000 races range 2000 2000 INSTALLATION amp WIRING DVP 1 overosxnie 1R 24VDC Relay DC24V 5 mA 7 1 PLC Mounting Arrangements and Wiring Notes Installation of the DIN rail The DVP PLC can be secured to a cabinet by using the DIN rail that is 35mm high with a depth of 7 5mm When mounting the PLC on the DIN rail be sure to use the end bracket to stop any side to side motion of the PLC thus to reduce the chance of the wires being pulled loose At the bottom of the PLC is a small retaining clip To secure the PLC to the DIN rail place it onto the rail and gently push up the clip To remove it pull down the retaining clip and gently pull the PLC away from the DIN rail As shown on the right When installing the DVP series PLC make sure that it is installed in an enclosure with sufficient space as shown below to its surroundings so as to allow heat dissipation SS Wiring oo 1eawe Notes i 1 Please use 22 16AWG 1 5mm wiring either single or multiple core for I O wiring terminals The specification for the terminals is as shown on the left E oo F PLC terminal screws should be tightened to between 1 95 kg cm 1 7 in
7. File File register Unchanged BUILT IN ANALOG I OAND 7 SEGMENT DISPLAY Built in 2 CH 12 bit A D and 2 CH 12 bit D A are bipolar It can read A D converted digital value and get designated analog output by reading special D or writing into special D Refer following table for corresponding special D This built in display corresponds to special D directly User can use it to display error code or station when executing PLC LINK It is great convenience for system maintenance Refer following table for corresponding special D 2 digital 7 t displ M1196 Number system setting for display Off Decimal On Hexadecimal M1197 The decimal point setting between the middle and the right most numbers The decimal point setting after the right most Present value of AD card D1056 channel 0 CHO Present value of AD card channel 1 CH1 Average value of AD card channel 0 CHO Average value of AD card channel 1 CH1 D1057 D1110 D1111 D1116 DA card channel 0 CHO D1117 DA card channel 1 CH1 number D1118 ral Salmplirig time D1196 Display content ELECTRICAL SPECIFICATIONS Model DVP10SX11R T DVPO8SM11N Item DVPO08SN11R T DVPOBSPTIRIT DVPIGSPHRIT MPU 24VDC 15 20 with DC input reverse polarity protection Expansion Unit supplied by the MPU 2AT250vA OSOCSCS SSCSC C CSCSTTTC C Power Consumption Insulation Resistance gt 5 MQ at 500 VDC Between al
8. Input LED The On Off signals of the input point could be displayed through the Input LED or the status of the input point could be monitored through the device monitoring function of HPP x Output LED Output LED indicates if the output signals are On or Off Please check the following items when the LED On Off indication does not correspond to the commands 1 Output contacts may be melted and stuck together due to a short circuit or current overload 2 Check wiring and verify that the screws are tight
9. be stored in data register D1137 the address saved in D1137 is invalid in case of common loop error When the ERROR LED is on not blinking users should make a judgment from the special relay M1008 of the MPU If it is On it indicates that the execution time of the program loop has exceeded the time out setting set by D1000 Please turn the PLC RUN STOP switch to STOP and find out the address of the time out program by special data register D1008 WDT instruction can be used to solve the problem Once program modification is completed user can re download the program of PLC and the ERROR LED will be off If the ERROR LED is still keep on please turn off the power and check if there s any noise or any conductive invader inside the PLC 37 BAT LOW LED When the battery voltage is low the BAT LOW LED will be on and the battery should be replaced as soon as possible otherwise the user program and the data in latched area will be lost On the unplugged PLC please change the battery within 3 minutes to retain the PLC s internal user programs and data Choose lithium battery TDRTL 2150 S Please refer to the following table for battery life information Battery life Fme o e 50 70 Life Years 9 8 6 5 Precision of calendar timer At 0 C 32 F less than 117 seconds error per month At 25 C 77 F less than 52 seconds error per month At 55 C 131 F less than 132 seconds error per month x4
10. l inputs outputs and earth ESD 8KV Air Discharge EFT Power Line 2KV Digital I O 1KV Analog amp Communication I O 250V Damped Oscillatory Wave Power Line 1KV Digital I O 1KV RS 26MHz 1GHz 10V m Groundin The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N g All DVP units should be grounded directly to the ground pole Operation 0 C 55 C Temperature 50 95 Humidity Pollution degree 2 Storage 25 C 70 C Temperature 5 95 Humidity D A output operation 0 C 50 C Temperature Standard IEC1131 2 IEC 68 2 6 TEST Fc IEC1131 2 amp IEC 68 2 27 TEST Ea 154 146 141 136 Power supply voltage Noise Immunity Environment Vibration Shock Resistance Weight approx g 162 154 Approvals Electrical N of Input Point Electrical Specification of Output Point Input Type DC SINK or SOURCE Output Type Relay R Current 1 5A 1 point 0 3A 1 point 40 C When the output of YO Specification p and Y1 is high speed pulse YO and Y1 5A COM 30mA T Voltage Below 250VAC Off On above16VDC ae 30VDC On gt Off below 14 4VDC 75VA Inductive Inductive When the output of YO and Y1 is high speed pulse YO 90 W Resistive 9W 1 point and Y1 0 9W YO 32kHz Y1 10kHz Responding About 10 ms A pine On gt Off 30us Input Current 24VDC 5mA Active Level Maximum About 10ms An Poading Responding adjustment range of 0
11. lbs oe Emm 2 I O signal wires or power supply should not run through the same multi wire cable or conduit Use Copper Conductor Only 60 75 C 7 2 Wiring Notes Power Input Wiring DVP SX series input power supply is DC input Please take a note of listed items when operating DVP SX Series 1 Please make sure the power is at terminals 24VDC and OV power range is 20 4VDC 28 8VDC When voltage is lower than 20 4VDC PLC will stop operating all outputs will turn Off and ERROR LED will flash continuously 2 If the power off time is less than 10ms the PLC still operates unaffectedly If the power off time is too long or the power voltage drops the PLC will stop operating and all the outputs will be Off Once the power is restored the PLC will return to operate automatically There are latched auxiliary relays and registers inside of the PLC please be aware when programming DC Input Type 20 4V 28 8V eel Safety Wiring Since the PLC is in control of numerous devices motion of either one device could affect the motion of other devices therefore the breakdown of either one device would consequently be detrimental to the whole auto control system and danger will thus be resulted Please use the recommended wiring below for the power input Power supply for AC loads Power Circuit Protection Fuse 3A Power On
12. ll be On T246 T249 4 points Accumulative 4 C0 C95 96 points 1 ee 32 bit count Total When the counter that set by CNT C Counter up down 7a et UA cer area Fs dinte preset value the C contact with the 32b higtrepeea 25 225 phase 1 input Spo poit iame number wite On count up down 4 C251 C254 2 phase 2 inputs 3 points 3 Initial step point SO S9 10 points 1 Zero point reset S10 S19 10 points use with IST command 1 Total Sep 20 S511 492 points 1 I O Processing Method I O refresh command is available Program Capacity 7920 STEPS Correspond to external output point Relay bit mode Usage device of step ladder diagram SFC points Start D1214 K512 512 S895 384 points 3 S 896 S1023 124 points 3 End D1215 K895 When the timer reaches the preset T Current value of the timer TO T255 256 points a the contact of timer will be On When the counter reaches the ICO C199 16 bit counter 200 points ssid C199 16 bit counter 200 ICO C199 16 bit counter 200 points ssid t val f th t C Current value of the counter C200 C254 32 bit counter 50 points ta nae the contact of counter General DO D199 200 points Latched D200 D999 800 eye D2000 D4999 3000 saints 3 D1000 D1999 1000 points OWES FO F3 8 points 1 01599 1600 points 4 For master control nested NO N7 8 points Control point of master control N loop nested
13. loop P For CJ CALL commands _ P0 P255 256 points The location point of CJ CALL 1001 X0 1101 X1 1201 X2 1301 X3 1401 X4 1501 X5 6 points all are rising edge trigger Total Can be memory area for storing 5000 data E and F can be used as the points special purpose of index indication Expansion register for storing data Register WORD data External interrupt The location pointer of interrupt subroutine Interrupt Service K 32 768 K32 767 16 bit operation K 2 147 483 648 K2 147 483 647 32 bit operation 6 H0000 HFFFF 16 bit operation HO0000000 HFFFFFFFF 32 bit operation Programming port COM1 RS 232 COM2 RS 485 Master Slave They can be used at the same time Analog Volume RTC MPU built in bipolar 2 CH A D D A 12 bits 2 digital 7 segment display built in RTC Special Expansion Module Use the same modules AD DA PT TC XA RT of SS series Max 8 Expansion Unit points 1 The non latched area is fixed and can t be changed 2 The non latched area can be changed to a latched area with parameter setting 3 The latched area can be changed to a non latched area with parameter setting 4 The latched area is fixed and can t be changed General Latched Special auxiliary relay M MO M511 M512 M999 M1000 M1999 M2000 M4095 Auxiliary Latched default 5 aedade La
14. of the MPU or the Expansion Units will be lit in green if the power is on If the indicator is not on when the MPU is powered up it means that the 24V DC power supply of the PLC is overloaded It is thus necessary to remove the wiring on terminals 24V and 24G and to use a 24VDC power supply instead If the ERROR LED is blinking swiftly it suggests that the 24V power supply of the PLC is insufficient xt Low Voltage Indication The LOW V LED on the Expansion Unit is an indication that the input power voltage is insufficient thus all outputs of the expansion unit should be turned off xt Low Battery Voltage Indication There is also a BAT LOW LED at the front of the MPU When the LED is on it indicates that the battery voltage is insufficient Please change the batter within 3 minutes as soon as possible otherwise the user programs and the data in latched area may be lost Preparation 1 Prior to applying power please verify that the power lines and the input output wiring are correct And be advised not to supply AC110V or AC220V into the I O terminals or it might short circuit the wiring and would cause direct damage to the PLC 2 After using the peripheral devices to write the program into the MPU and that the ERROR LED of the MPU is not on it means that the program in use is legitimate and it is now waiting for the user to give the RUN command 3 Use HPP to execute the forced On Off test of the output contac
15. rminal YO uses one common terminal CO Y1 uses C1 as shown below RELAY OUTPUT DVP 41 T coYyoc1yY1 Action indication When the output point is active the corresponding indicator at the front will be on Isolated circuit The optical coupler is used to isolate signals between PLC internal circuits and input modules Voltage input 10V 10V CHO Note 1 Please isolate analog input and other power wiring Note 2 If input signal is in current please short out between V and I terminals Current input 20mA 20mA CH1 Note 3 If the noise interference from loaded input wiring terminal is significant please connect a capacitor with 0 1 0 47uF 25V for noise filtering voltage output E TT Note 4 Please isolate analog output and other power wiring Note 5 If the noise interference from loaded AC drive recorder scale valve input wiring terminal is significant please connect a capacitor with 0 1 0 47uF 25V for noise filtering Note 6 Please connect power module current output 20mA 20mA CH oe P EET terminal and analog output module scale valve terminal to system earth point and make system earth point be grounded terminal of power module or connects to machine cover DC DC converter Warning DO NOT wire to the No function terminal class 3 grounding 100Q or less x lt Power Indication The POWER LED at the front
16. t Operation amp Test If the ERROR LED of the MPU is not blinking use RUN STOP switch or the peripheral devices HPP or WPLSoft to give the RUN command and the RUN indicator will then be on If the RUN LED is not on it indicates that there is no program inside the PLC HPP could be utilized to monitor the settings and the registered values of the timer T the counter C and the data register D during operation and moreover to force the output contacts to conduct the On Off action If the ERROR LED is on but not blinking it means that the setting of the user s program has exceeded the preset time out limit At this case please turn the PLC RUN STOP switch to STOP and find out the address of the time out program by special data register D1008 WDT instruction can be used to solve the problem PLC Input Output Reaction Time The total reaction time from the input signal to the output operation is calculated as follows Reaction Time input delay time program scan time output delay time inputdelaytine Factory setting 10 ms Please refer to the usage of special P register D1020 1021 Please refer to the usage of special register D1010 Output delay time Relay module 10ms Transistor module 20 30us Basic Commands and Application Commands of the PLC 1 The basic commands and the application commands of the MPU of this series are totally applicable to the DELTA DVP PLC SA SX SC Series MPU Refer to
17. tched default Relay Non latched fixed Start D1200 K512 ome See changed Start D1202 K2000 End D1201 K999 End D1203 K4095 i TO T199 T200 1239 T246 1249 T250 1255 anes Non latched fixed Non latched fixed Accumulative Latched fixed 16 bit count up 32 bit count up down 32 bit high speed count up down C C0 C95 C96 C199 C200 C215 C216 C234 C235 C245 C246 C255 Counter Latched default Latched default Latched default Start D1208 K96 Start D1210 K216 Start D1212 K235 End D1209 K199 End D1211 K234 End D1213 K255 Non latched fixed Non latched fixed Special register S0 S9 510 519 520 5511 5512 5895 896 S1023 Factory setting is latched ey Start D1214 K512 End D1215 K895 It is fixed to be non latched It is fixed to be latched General Latched Special registers Latched D DO D199 D200 D999 D1000 D1999 D2000 D4999 Register Factory setting is latched Factory setting is latched latch t Non latched fixed Start D1216 K200 a Aen i i Start D1218 K2000 End D1217 K999 End D1219 K4999 File Register KO K1599 Latched fixed X When switching between power On Off or MPU RUN STOP modes POWER Clear all M1031 Clear all M1032 Factory M1033 0ff clear Nomietoned latched Clear Unchanged M103 On unchanged Clear Unchanged Unchanged Unchanged a PPEcALM pect Initial value Unchanged Unchanged nite Index Eo lt