Thyristor power controllers TE10A Phase angle operation Control of

image

Contents

1. Eurotherm certifies that TE10A Phase Angle fired products installed and used in compliance with their manual meet the following EMC standards and enable the system which incorporates them to comply with the EMC Directive as far as those TE10A products are concerned EMC STAN DARDS Immunity Generic standard EN 50082 2 Test standards EN 61000 4 2 EN 61000 4 4 ENV 50140 ENV 50141 ENV 50204 Emission Generic standard EN 50081 2 Test standard EN 55011 with external filter for conducted emissions Product standard IEC 1800 3 without filter EXTERNAL EMC FILTERS To reduce conducted emissions in accordance with standard EN50081 2 a series of EMC filters is used 16A and 25A ratings filter code FILTER MON 25A 00 40A and 250A ratings filter code FILTER MON 63A 00 Eurotherm can supply these external filters To mount the filters on DIN rails use a BA175552 mounting plate TE10A PA User manual 5 VALIDATION BY INDEPENDENT BODY Eurotherm has validated the compliance of these TE10A controllers with the Low Voltage Directive mentioned above and with EMC standards through product design and laboratory testing The controls carried out on TE10A products are listed in a Technical Construction File validated by the LCIE Central Laboratory for the Electrical Industries a Recognised Competent Body PERSONNEL The installation configuration commissioning and maintenance of the power unit should only be carried out by pers
2. Thyristor power controllers TE10A Phase angle operation Control of all types of load up to 25kW constant resistance short wave infrared elements transformer primaries inductors User M anual Copyright Eurotherm Automation 1997 All rights reserved All reproduction or transmission in any form or using any procedure without written authorisation from EUROTHERM AUTOMATION is strictly prohibited TE10A PA User manual HA175548ENG Issue 1 0 06 97 1 Before installation please read this manual thoroughly Eurotherm cannot be held responsible for any damage to persons or property or for any financial loss or costs arising from incorrect use of the product or failure to observe the instructions given in this manual In order to maintain its leading edge Eurotherm may have to make changes to its specifications without advance notice For any further information or if in doubt please contact Eurotherm Controls where qualified staff are available to advise or assist you with the commissioning of your installation Guarantee Two years for parts and labour return to factory 2 TE10A PA User manual TE1OA Industrial thyristor power controller Phase angle operation CONTENTS SAFETY DURING INSTALLATION AND USE 4 EUROPEAN DIRECTIVES 0 5 TECHNICAL SPECIFICATION 7 PRODUCT CODE 0 000 9 INSTALLATION AND DIMENSIONAL DETAILS 10 FRONT FACIA suser eee
3. 11 TERMINALS AND CONNECTORS 12 WIRING sihes eee eeey leben sl ses ere sone 14 Control of TE10A by temperature controller 14 Local control by potentiometer 15 Local control by contacts 15 Auxiliary power supply option 16 INPUT SIGNAL 0 0 0 0 eee eee 17 LAYOUT OF CONFIGURATION COFFEE BEANS osi ce egces ee ee ee ded 18 THYRISTOR FIRING MODE 19 CURRENT LIMIT OPTION 20 Operation aa EA SSD ee Oe ea fe 84 20 ACUStMENE er ii oe Seles eee ae teas 21 POWER CONTROL 0 00000 b ee eee 22 COMPENSATION FOR SUPPLY VARIATIONS 22 CURRENT DERATING 205 23 TE10A PA User manual SAFETY DURING INSTALLATION AND USE This symbol means that failure to take note of the information given in this manual may have serious consequences for the safety of personnel and may even result in electrocution DANGER Units must be installed in fan cooled electrical cabinets to ensure that condensation and pollution are excluded The cabinet must be closed and bonded to the safety earth in accordance with Standards NFC15 100 IEC 364 or current national Standards It is the responsibility of the user to install and wire the installation in accordance with current professional practice Before any connection or disconnection make sure that power and control cables and leads are isolated from voltage sources
4. table enables the user to check the signal configuration or to re configure the TE10A if required In this table the x denotes the corresponding solder link Coffee bean Signal type Solder links Coffee beans GR1 GR2 GR3 0 10V 0 5V X 4 20mA X X X Local control X TE10A PA User manual 17 LAYOUT OF CONFIGURATION COFFEE BEANS Factory configured Soldered LED firing indicator Configuration of input type adana DOGRES pr z Not soldered Soldered Control _ connector Layout of Coffee beans on circuit board solder side view GR8 and GR9 Coffee beans are configured in the factory GR6 and GR7 Coffee beans are soldered GR4 and GRS Coffee beans are not soldered 18 TE10A PA User manual THYRISTOR FIRING MODE In phase angle thyristor firing mode the power transmitted to the load is controlled by firing the thyristors over part of the supply voltage half cycles Load voltage in phase angle firing mode 0 thyristor firing angle TE10A PA User manual 19 CURRENT LIMIT OPTION Operation The TE10A controller features an adjustable rms load current limit This function enables the user to limit the load current to a desired value independent of variation in load resistance The current limit threshold can be set from 30 to 100 of the nominal current of the controller using t
5. 10V 14 TE1OA PA User manual Local control by potentiometer The input must be configured as 0 to 5V code 0V5 Ron aca External potentiometer wiring example view from below Local control by contacts The input must be configured as 0 to 5V code 0V5 Front aca te am e raout PRR ESE TS Control contact wiring example view from below TE10A PA User manual 15 Auxiliary power supply option In the case of non standard mains the auxiliary power supply must be in phase or in anti phase with the power supply voltage Sonne of horestandard 0 54 anti surge fuse 1 2 Power protection teminals 3 4 Load teminals Auxiliary power supply connector Example of auxiliary power supply wiring with non standard mains 16 TE10A PA User manual INPUT SIGNAL External control The TE10A is controlled by a DC analogue signal Signal type voltage 0 to 5V or 0 to 10V or current 4 to 20mA Input impedance voltage 100kQ in current 250Q Local control Local control is possible using a 10k potentiometer analogue operation or via dry contacts logic operation A 5V User voltage output terminal 7 is provided for these control modes see wiring diagrams page 15 Configuration The signal type voltage or current and the signal level are configured in the factory by the Coffee beans located on the circuit board see page 18 The following
6. Automatic compensation for supply variations is effective in the voltage range from 10 to 10 of the nominal voltage of the controller Control with compensation of mains variations enables constant output power to be maintained for a constant load despite variations in supply voltage Without compensation for supply variations a reduction for example of 10 in supply voltage would result in a reduction of 20 in load power This variation is less than 2 in the TE10A controller 22 TE10A PA User manual CURRENT DERATING le 4 20 25 30 35 40 45 SO 55 60 Operating temperature C Current derating curves as a function of ambient temperature IN nominal current at 45 C Dotted line limit of recommended fuse With Current limit option load current may not exceed around 110 of nominal current of controller TE1OA PA User manual 23 EUROTHERM CONTROLS LIMITED UK SALES OFFICE Eurotherm Controls Limited Faraday Close Durrington W orthing W est Sussex BN 13 3PL Telephone Sales 01903 695888 Technical 01903 695777 Service 01903 695444 Fax 01903 695666 Sales and support in over 30 countries worldwide For countries not listed overleaf enquiries orders to Eurotherm Controls Limited Export Dept Faraday Close Durrington Worthing W est Sussex BN 13 3PL Telephone 01903 268500 Fax 01903 265982 Telex 87114 EUROWG G
7. The safety earth must be connected before any other connection is made during wiring and should be the last cable to be disconnected Thyristors are not isolating devices The high speed fuse recommended is used only to protect the thyristors under no circumstances can it be used to protect the installation For this reason it is very important to fit a suitable device guaranteeing protection for and electrical isolation of the installation in compliance with current practice Access to the internal components of the product is prohibited to users Disconnect the TE10A completely before dismantling The temperature of the heatsink fins may exceed 100 C Avoid all contact even occasional with the heatsink while the TE10A is operational The heatsink remains hot for approximately 15mins after the TE10A has been switched off 4 TE10A PA User manual C EUROPEAN DIRECTIVES CE MARKING TE10A products carry the CE mark in compliance with the essential requirements of the Low Voltage Directive 73 23EC of 19 2 73 amended by the Directive 93 68 EC of 22 7 93 For safety reasons TE10A products installed and used in compliance with this user manual meet the essential requirements of the European Directives mentioned above CE DECLARATION OF CONFORMITY A CE Declaration of conformity is available on request ELECTROMAGNETIC COMPATIBILITY EMC For an industrial environment only not to be used in domestic environments
8. he potentiometer labelled I LIMIT on the front facia 20 TE10A PA User manual Adjustment Current limit adjustment is possible if the rms load current is greater than or equal to 30 of the nominal current For this adjustment use a true rms ammeter in order to minimise errors which could otherwise amount to as much as 50 of the value of the current For current limit adjustment proceed as follows Check that the load circuit is connected Turn the potentiometer labelled I LIMIT on the front facia 25 complete turns in an anti clockwise direction minimum position Apply 0 setpoint to the controller input With an Auxiliary power supply option apply volts to the electronics supply Connect the power circuit The voltage at the load terminals must be zero Set the input signal to 100 The load voltage is minimal Turn the current limit potentiometer slowly in a clockwise direction and check that the current increases Adjust the potentiometer in order to attain the maximum current permitted in the load TE10A PA User manual 21 POWER CONTROL TEI10A PA controls on the square of the rms load voltage Control precision is guaranteed to 2 of the maximum voltage The power controlled varies linearly from 0 to 100 of maximum power for an input signal variation from 4 to 96 of full scale Linearity is better than 2 of full scale COMPENSATION FOR SUPPLY VARIATIONS
9. in control connector TE10A PA User manual 11 TERMINALS AND CONNECTORS POWER Terminal Function Terminal Cable Stripping Tightening designation type torque 1 Mains Controlled phase Cage 1 5mm 16mm 1 2 Nm 2 Mains Direct phase Neutral to 16mm 3 Load Controlled phase 4 Load Direct phase Neutral al Safety earth M5 screw Same 10mm 2 Nm E gauge as power CONTROL Terminal Function Connector Cable Stripping Tightening designation type torque 5 OV of control signal Plug in 0 5mm 7mm 0 4Nm 6 of control signal to i 7 User 5V 1 5mm 8 amp 10 Auxiliary power supply Plug in 0 5mm 7mm 0 25 Nm option to 1 5mm 9 Not used 12 TE10A PA User manual VIEW FROM BELOW Power terminals load connection 5 Plug in control connector Shipped cable outine Plug in awiliary 8 power supply zonnector option qg TE1OA PA User manual 13 WIRING Control of TE10A by temperature controller 2000 Series Eurotherm Temperaure Controller Line protection circuit breaker installed by user EUROTHERM 2408 1A fuse Controlled phase 3 Neutral Thyristor protection fusi Thermocouple input Current limit adjustment option Analogue output Fixing indicator Analogue input TE10A wiring example 230V supply input 0 to
10. le Load power variation from 0 to 100 of the nominal power Green LED on front facia Analogue DC voltage or current 0 5V 0 10V or 4 20mA Voltage 100KQ Current 250Q 10KQ external potentiometer Dry contact logic operation all or nothing A 5V user voltage is available A phase angle ramp allows progressive variation in power applied to the load TE10A PA User manual Environment Operating temperature Operating atmosphere Humidity Pollution Thyristor protection Protection degree Insulation 1 minute test Cooling Mounting Dimensions mm Weight g 0 to 60 C see Derating Curves at maximum altitude of 2000m Storage 10 to 70 C Non conductive non explosive and non corrosive RH 5 to 95 non condensing nor streaming Pollution degree 2 permissible IEC 664 External fuse internal MOV varistor and RC snubber IP20 in accordance with IEC 529 11 4 table 5 Isolation distances according to IEC 664 2000Vac between power and earth 3600Vac between power and control inputs Natural convection Vertical on DIN rail Height 115 depth 92 5 Width 52 5 16A 70 25A 105 40A and 122 5 50A 550 16A 700 25A 900 40A 1200 50A TE10A PA User manual PRODUCT CODE Controller Model Current Voltage Input Firing Option 00 TE10A 16A 100V Phase angle Current limit 25A 115V PA CL 40A 200V Auxiliary 50A 230V power s
11. onnel qualified and trained to work with low voltage electrical equipment in an industrial environment INDEPENDENT SAFETY DEVICE Given the value of the equipment controlled by TE10A it is the responsibility of the user and it is highly recommended that an independent safety device alarm should be installed This alarm must be tested regularly Eurotherm can supply suitable equipment ELECTROMAGNETIC COMPATIBILITY INSTALLATION GUIDE In order to help you reduce the effects of electromagnetic interference depending on the product installation Eurotherm can supply you with the Electromagnetic Compatibility Installation Guide ref HA025464 6 TE1OA PA User manual TECHNICAL SPECIFICATION Power Nominal current at 45 C Nominal voltage Supply frequency Current in off state Load Regulation Type of regulation Linearity Stability Firing mode Firing indicator Control Inputs External signal type Input impedance Local control Soft start 16 25 40A or 50A 100Vac to 500Vac 10 15 50 and 60Hz nominal 2Hz Below 30mA typically Constant resistance short wave infrared elements transformer primaries inductors Load voltage squared The load power is proportional to the control input Better than 2 of the full range Automatic compensation for supply variations from 10 of the nominal voltage Stability better than 2 of the full range on constant resistance Phase ang
12. u 240V MSV or BN OV 271V 380V 400V 415V 440V 480V 500V Options Auxiliary power supply 115Vac or 230Vac used in the case of non standard mains or if independent power supply required The auxiliary supply must be in phase with load supply Current limit Rms load current limit threshold adjustable by potentiometer on front facia from 30 to 100 Fuses Thyristor protection except for short wave infrared application Current Rating Code Fuse amp fuse holder Dimensions mm 16A 20A FU1038 16A 00 81 x 17 5 x 68 25A 32A FU1038 25A 00 81 x 17 5 x 68 40A 50A FU1451 40A 00 95 x 26 x 86 50A 63A FU2258 50A 00 140 x 35 x 90 TE10A PA User manua 9 INSTALLATION AND DIMENSIONAL DETAILS Minimum spacing between two TEIOA units 10mm up to 45 C 17 5mm over 45 C ane bi rail adapter ee BD173730 Pa 115 Dimensions gt et fee in mm 52 5 164 70 254 105 404 122 5 50A 11N Lal cup IMUULILL EN 50022 35x7 5 and 35x15 Ground continuity For EMC reasons ensure that the DIN rail of the TE10A installation is electrically bonded to the reference ground panel or bulkhead 10 TE1OA PA User manual FRONT FACIA Norninal voltage and currert Power terminals 1to4 User label Cur ent limit potentiometer option Green LED thyristor firing indcator Firing mode indcator Phase angle Plug