Home

Notifier ID50-60 User Manual

image

Contents

1. TEST DELAYS ACTIVE The DISABLEMENT and relevant ZONE FAULT DISABLE TEST LEDs illuminate indicating that the selected zone s are now disabled The LCD returns to the Disable Enable menu To enable a Full Zone Ore minn FIRE DISABLEMENT TEST DELAYS ACTIVE The DISABLEMENT and relevant ZONE FAULT DISABLE TEST LEDS extinguish b APartial Zone Press the 0 button on the numeric keypad to select the Device in Zone option aO win zone Tie 5 To select individual devices use the Q0 QO buttons to display the required device s Confirm selection of each by pressing the 0 button RR e 9 FIRE DISABLEMENT TEST DELAYS ACTIVE 29 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Repeat until all devices are in the required state either disabled or enabled The DISABLEMENT LED remains illuminated if one or more devices are disabled It is extinguished when all devices have been enabled The relevant ZONE FAULT DISABLE TEST LED is illuminated when all devices in that zone have been disabled Disablement of ALL devices is confirmed by the Fully Disabled LCD message 6 Pressthe 9 button to return to the Disable Enable menu E 4 an a gt N cn per S lt x ho _ Da Q O 997 264 000 11 Issue 11 30 October 2010 ID50 Seri
2. PRE ALARM POWER indicates status of power POWER FRE contRoL oP FAULT DISABLED supply SYSTEM FAULT indicates the CPU has reset ora system fault has occurred EARTH FAULT indicates an earth fault has occurred PLANT ALARM indicates a fault or warning from a plant monitoring device FIRE CONTROL O P FAULT DISABLED indicates a fire control output fault or disablement FIRE OUTPUT FAULT DISABLED indicates a fire output fault or disablement SOUNDER FAULT DISABLED indicates a sounder circuit fault or disablement POWER SUPPLY FAULT indicates an unsatisfactory power supply to the panel This LED is also configurable as SOUNDERS SILENCED 2 This LED can be configured as FAULT O P FAULT DISABLED Visible Audible Indicators e Liquid Crystal Display LCD Section 4 1 1 e Internal Buzzer Section 4 1 2 997 264 000 11 Issue 11 4 October 2010 TEST DELAYS ACTIVE OOO FIRE OUTPUT FAULT DISABLED TEST DELAYS ACTIVE FIRE OUTPUT FAULT DISABLED ID50 Series Panel Operating Manual DISPLAYED ALARM CONDITION CONDITIONS ALARM CONDITION 3 3 1 Automatic Alarms What to do Before any automatic alarms have been sounded the panel only operates in display mode quiescent state The user must then turn the keyswitch to the right or enter a Level 2 access code to enable the panel s pushbutt
3. S pallina iii Press the B button to exit the Walk Test menu and return to the Test Zones menu b For all zond om the 1 More option YO press the B button on the numeric keypad to select the Stop All menu EE an Simse sone lt p om A Oo kai cn 4 To exit the Test Zones menu press the Y button Continue pressing this button until the required menu or the Status NORMAL message is displayed Checking the Devices Use the following methods to check devices during a walk test i Test sensors by applying smoke or heat as gz appropriate or by operating the device s internal test ot switch by means of a magnet ii Test Manual Call Points by using a test key cia For each device the panel will record the event in the log sound its internal buzzer illuminate the appropriate ZONE FIRE LED and if a CLIP protocol device turn on the LED at the device that initiated the alarm For OPAL protocol devices the longer green LED flash duration is replaced after testing by the normal poll flash Note A maximum of ten devices LEDs can be illuminated during the test Further device testing functions normally in all other respects LEDs will not light again until after the removal of the walk test condition and manually resetting the panel After a few seconds the panel will automatically return to Test Mode and the device LED will be turned off The panel is then ready to test the next devic
4. an _ oQ e O pen S lt n Pr ho Q ID50 Series Panel Operating Manual 4 5 SILENCE RESOUND Pushbutton The term silence as used throughout this manual describes a temporary state the panel enters whenever the SILENCE RESOUND pushbutton is pressed to stop the sounders operating While the panel is in this state a new fire alarm operating the SILENCE RESOUND pushbutton again or operation of the END DELAY EVACUATE pushbutton will re sound all previously silenced sounders You can suspend all sounder output delays and silence all sounder outputs which are operating as a result of a FIRE alarm or an EVACUATE operation Provided that the pushbuttons have been enabled for Level 1 operation and delays are active proceed as follows 1 1 Press the SILENCE RESOUND pushbutton The D me following are not switched off by this operation A a The internal FIRE buzzer b Any output modules configured in the CBE Rules during commissioning NOT to be silenced by the SILENCE RESOUND pushbutton p 2 To start the sounders again in the same pattern as ESSA they were previously operating and reactivate any programmed delays press the SILENCE RESOUND pushbutton 3 3 The panel may have been configured during SILENCE e commissioning to illuminate the SOUNDERS RESCUND SILENCED LED when the SILENCE RESOUND pushbutton is pressed non defaul
5. User Option 34 4 11 1 Time User Option 35 4 11 2 Date User Option 36 4 12 VIEW MODE User Option 37 4 12 1 Log User Option 38 4 12 2 Devices User Option 39 4 12 3 Faults User Option 41 4 12 4 Input Events User Option 42 4 12 5 Disabled User Option 43 4 12 6 Alarm Count User Option 43 LD 4 12 7 Voltages User Option 44 end 4 12 8 Version User Option 45 a 4 13 Commissioning 45 4 14 Print 45 5 Appendix 1 Log Book A1 1 Appendix 2 Maintenance A2 1 Appendix 3 ID60 Single Loop Panel Differences A3 1 997 264 000 11 Issue 11 ii October 2010 ID50 Series Panel Operating Manual ID50 Series Panel i ZONE FAULT gt 9 DI DISABLEMENT POWER SUPPLY FAULT EARTH FAULT SYSTEM FAULT SOUNDER FAULT DISABLED DELAYS ACTIVE FIRE OUTPUT FAULT DISABLED FIRE OUTPUT ACTIVE DISABLEMENT l oju re DELAYS ACTIVE __FIRE OUTPUT FAULT DISABLED __FIRE OUTPUT ACTIVE L POWER FIRE CONTROL O P FAULT DISABLED ID50 Series Panel 0 NO TIFIER iii 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 1 1 1 1 2 Introduction This manual contains operating instructions for the ID50 and ID60 Series Fire Detection Panels Differences between the ID50 and ID60 panels are given in Appendix 3 Users of this manual are assumed to be working with a panel that has already been installed and configured appropriately for
6. as to are not turned on indicate that all loop powered devices under test are operating Select In Only to perform test correctly This percentage value may go down if a device with loop powered only from the starts reporting incorrectly or becomes de activated Loop Out end Select Out Only to perform test with op powered only from 4 Pressthe pushbuttons to select the other Loop me Loop oend Booster options In Only or Out Only 5 To perform a loop test without loop booster support you can turn off individual LBMs while testing that loop powered sounders are still able to operate correctly 6 Pressthe d button to cancel the test and return to the Test Menu Note If the test is not cancelled manually it is cancelled automatically 4 hours after the last panel keystroke 997 264 000 11 Issue 11 26 October 2010 ID50 Series Panel Operating Manual 4 9 6 Buzzer User Option The Buzzer User Option selected from the Test Menu tests the internal buzzer Proceed as follows 1 Using the numeric keypad press Q to display the TEST menu E 2 Press the pushbuttons to display the next screen options To test the buzzer press the Q button on the numeric keypad 3 The buzzer sounds with a 2 1 mark space ratio and the LCD flashes the message below Press the Q button to cancel the test and return to the Test Menu 4 9 7 Keyboard User Option The sta
7. is recommended Daily Check the panel to ascertain that it indicates normal operation If any fault is indicated check that it has been recorded in the log book and that the appropriate actions have been taken e g informing the maintaining company Weekly Test at least one sensor or call point to confirm the operation of the panel and the audible alarms Test a different zone each week and if possible a different device Keep a record of the device and zone tested each week Record and report any malfunction Quarterly The responsible person should ensure that every three months the system is checked by a competent person who shall Check the log book entries and any action taken Check the standby batteries and the charger voltage Test at least one device in each zone to check the panel functions Check the operation of the audible alarm and any link to a remote manned centre Central Station etc Carry out a visual inspection of the installation to check for alterations or obstructions and issue a certificate of testing Oo G a LI N La ce cd Q Q lt x Annually The responsible person should ensure that in addition to the quarterly checks each device on the system is tested and that a visual inspection is made of the cable fittings and equipment A2 2 Batteries As a minimum replace the batteries every four years The battery units should always be disposed o
8. Channel B Module Address Channel C Sub address Values Explained Sensors the first value indicates the sensor status i e fire pre alarm etc used by the panel The next values before the semi colon are internal to the sensor and therefore are of no concern to the user Modules the first value is interpreted by the panel as an indication of the module s health status The next values represent the status where appropriate of the sub addresses inputs and or output circuits In either case the last value after the semi colon shows the status of the internal isolator if fitted 224 isolator closed 96 isolator open For devices without an internal isolator this value 0 39 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 3 Press the e button to view additional device information For CLIP protocol devices Note Three percentage values are displayed this is the device s alarm level status e g 100 default is equivalent to alarm The value on the left is the current alarm status level The other percentage values are historical the previous two alarm status percentages are displayed the one on the left being the more recent For OPAL protocol devices the device data displayed is for reference purposes only 4 Pressthe Q button to return to the View Mode menu AWACS Devices ID60 only The ID60 panel allows the configuration of all sensor types except HEAT sensors
9. Tools menu to allow event or device data to be retrieved from the panel and saved on the PC 6 To print the disablements press the button at the Print screen A 7 Select the appropriate option using the numeric keypad If disabled device data is available the print screen changes to advise that printing is taking place For example if option 2 Zone is selected the following information is displayed 8 To print the maintenance log ID60 only press the O button The display changes to indicate that printing is in progress as below Note The Maintenance log can hold up to 100 log entries Newer entries replace the oldest in the log 9 Pressthe Ka Y button to cancel printing and return to the Print menu 997 264 000 11 Issue 11 46 October 2010 ID50 Series Panel Operating Manual Appendix 1 Log Book In accordance with EN54 part 14 it is the user s responsibility to maintain a log book and to record all events resulting from or affecting the system The log book should be kept in a place accessible to authorised persons preferably near the control panel One or more identifiable individuals should be appointed to oversee or carry out all entries in the log book The names of these persons and any changes of responsible person should be recorded All events should be properly recorded events include real and false fire alarms faults pre alarm warnings tests temporary disconnections
10. _ oQ ON G O pann S lt da e sf pes 17 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 7 Numeric Keys When using any numeric key each operation is confirmed by a sharp audible bleep At Access Level 1 the numeric buttons have NO function until an alarm condition occurs The alarm condition enables the 9 and buttons allowing the user to view each alarm in turn At Access Level 2 the function remains identical to the Level 1 function The J cancel confirm 90 to next option buttons are enabled Numeric entry used in conjunction with the D shift button is also enabled a Use the and buttons to scroll through fire alarms fault conditions and warning conditions or to view the More menu list when available b Press the button to confirm an option Press and hold the D c Press the Bi Shift button to enable number entry Shift pushbutton while Following the input of a number approx 1 sec later entering numbers a second audible bleep indicates that number entry is no longer enabled 4 7 1 Cancellation Termination Button To cancel or terminate configuration data entry press the button The LCD returns to the previous menu To cancel access rights press the button until the Status NORMAL message is displayed 4 7 2 Level 2 Options Men
11. and return to the Clock menu 90000040 Ii EE onou lo eye Dee Note The date MUST be entered in the same format as indicated on the LCD Only date entries between 2000 and 2063 are valid eeeeeeqt e If an invalid date is entered for example 222222 22 22 22 the LCD displays an error message and then re displays the Clock menu n l ae lo ee E AT Q an E oQ a ce O pran S lt ho sed dhe Q 997 264 000 11 Issue 11 36 October 2010 ID50 Series Panel Operating Manual 4 12 View Mode User Option The VIEW MODE User Option allows the user to view the following system parameters Log Devices on the loop a b c Faults d Input Events e Disablements on the loop f Maintenance Log ID60 only requires access level 3 g Alarm Count h Voltages i Version system and loop software To display the View Mode menu 1 From the Status NORMAL message press the 0 button The LCD prompts for a Level 2 3 access code Note If an incorrect access code is entered the LCD displays ERROR INCORRECT PASSCODE l After one minute the LCD returns to the Status NORMAL message 2 Either turn the keyswitch or using the numeric keypad enter the correct Level 2 access code and confirm using the Q button The Level 2 menu is displayed with the user number U0 to U9 in the top left hand corner 3 Using the nu
12. initiates the fire investigation period refer to Section 3 1 1 Fire in Delayed Mode The DELAY ACTIVE LED remains illuminated until the delay timer expires 14 ID50 Series Panel Operating Manual 4 4 END DELAY EVACUATE Pushbutton END DELAY EVACUATE END DELAY e EVACUATE 3 i The END DELAY EVACUATE pushbutton is used to initiate the Evacuate procedure If this pushbutton is operated while a delay is active all delays are cancelled and all sounders designated in the pre configured Evacuate rule are activated Fire Alarm Condition Providing the pushbuttons have been enabled for Level 1 operation and delays are active the following occurs 1 Press the END DELAY EVACUATE pushbutton The following is typically displayed 2 Nofurtheraction is needed until it is required to silence the sounders in which case the SILENCE RESOUND pushbutton should be pressed see Section 4 5 Silence Resound pushbutton Note If the pushbuttons are enabled to operate at Level 2 enterthe Level 2 passcode in the manner described in the RESET pushbutton procedure Section 4 6 No Alarm Condition In quiescent mode pressing the END DELAY EVACUATE pushbutton immediately sounds the internal buzzer operates all outputs configured in accordance with the CBE rules configured at time system was commissioned and the LCD displays the EVACUATE message WI 15 997 264 000 11 Issue 11 October 2010 cd iy
13. this terminates access Level 2 Alternatively tum the keyswitch to the right and and then back to normal to exit all user menus Menus willrevertto the panel status display automatically five minutes after the last key press Press the O button to toggle between the menus and top level display Note To exit the Level 3 Commissioning menu press the numeric button 12 FIRE DISABLEMENT FAULT TEST POWER SUPPLY FAULT DELAYS ACTIVE EARTH FAULT FIRE OUTPUT FAULT DISABLED SYSTEM FAULT FIRE OUTPUT ACTIVE SOUNDER FAULT DISABLED PLANT ALARM PRE ALARM POWER 00000000 FIRE CONTROL O P FAULT DISABLED 9 6 gt Se 000 00 e po ID50 Series Panel Operating Manual Operations within this manual require Level 2 access code or keyswitch although a Level 3 access code may be entered Throughout this manual a U accompanied by a _ number represents a Level 2 access code e 4 1 2 Internal Buzzer The panel has an internal buzzer which gives a local warning when any of the following is detected a Fire condition b Pre alarm condition c Fault condition 4 1 3 Access Codes With the exception of the Loop Booster Output Test option the actions described in this manual require access Level 2 which is invoked either
14. to the panel s Control by Event CBE Rules configured during the Commissioning stage 5 997 264 000 11 Issue 11 October 2010 ENS4 2 7 6 1 7 8 8 7 1 Ensure ENS4 compliance ID50 Series Panel Operating Manual 9 1 2 for access to controls 1 MUTE BUZZER 3 END DELAY UP 8 Last to first 9 DOWN 2 Firstto last 5 l RESOUND SILENCE e RESOUND e RESET 997 264 000 11 Issue 11 October 2010 Recommended operator actions Note In the recommended operator actions described below only MUTE BUZZER and END DELAY are selectable atAccess Level 1 The operation of EXTEND DELAY EVACUATE SILENCE RESOUND and RESET must only be possible at access Level 2 in accordance with the requirements of EN54 Part 2 1 Operate the MUTE BUZZER pushbutton to silence the panel s internal buzzer 2 Follow prescribed instructions for evacuation of premises notification of Fire Brigade and investigation of source of fire 3 If additional sounder operations are required to achieve a complete and immediate evacuation of the premises press the END DELAY EVACUATE pushbutton needs access level 2 This will cause the internal buzzer to resound so press the MUTE BUZZER pushbutton to silence 4 When more than one fire Alarm condition is present it is possible to manually scroll through all logged Fire Alarm conditions using the arrows Note With mu
15. to use the AWACS multi sensing algorithm For these devices an additional screen is available which displays the current percentage values for alarm and pre alarm E i gt an _ oQ v cn O p S lt n sed Q O 997 264 000 11 Issue 11 40 October 2010 ID50 Series Panel Operating Manual 4 12 3 Faults User Option This menu option allows the user to view active faults while the normal active fault display has been overridden by a higher priority display alarms To view Faults from the View Mode menu 1 Onthenumeric keypad press the button to select the Faults display 2 The LCD automatically displays the last recorded event first Viewing commences from this point Press the QQ buttons to scroll through the faults Note Press the Q button to view additional zone text information To return to the fault message press any numeric cursor key Alternatively if no key is pressed within ten 10 seconds the display reverts to the fault message Example fault displays are given below m mn O TI a Fault condition b Fault currently displayed c Total number of faults logged d Text description of fault e Zone Number f Device Address g h Device Type Time fault was logged Note If no faults are recorded on the system the following message is displayed 3 Press the B button to return to the View Mode menu 41 997 264 000 1
16. which is used to determine if a fault condition exists Ideally this value should be between 250 and 8002 FAULT ow POWER SUPPLY FAULT EARTH FAULT SOUNDER FAULT DISABLED POWER SUPPLY FAULT POWER SUPPLY FAULT 997 264 000 11 Issue 11 October 2010 4 12 7 Voltages User Option The Voltages User Option allows the user to view the Voltages mV of various parts of the system For sounder circuits configured as a transmission device TxD a resistance value 9 is displayed see note at left To view these Voltage resistance values from the View Mode menu 1 Using the numeric keypad press the Q button to select the Voltages menu ID60 Panels only 2 The Battery Volts window is automatically displayed Press the QQ buttons to display the previous next system voltage BATTERY WIRING TEST The last battery load test result is displayed in mQ If the value displayed is 9999 either the battery load test has not been run yet or the test has been suspended The range is 220 to 570 Any value outside this range will generate a fault Note The voltage displayed for each system should be within a given range Mains supply present a battery voltage value greater than 15V means that batteries are connected battery voltage is low if greater than 15V but less than 18 9V No mains supply present a value of less than 22
17. 010 E i gt an _ oQ v cn O p S lt ho sed 1 cs Q O Disabled Enabled MN EXTEND TEST DELAYS ACTIVE FIRE OUTPUT FAULT DISABLED 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual MUTE BUZZER EXTEND DELAY END DELAY EVACUATE SILENCE RESOUND RESET 000 DELAY 5 O j ZE a p 4 1 4 Keyswitch 4 2 4 3 The panel is fitted with a keyswitch which provides an alternative to the Level 2 access code If the keyswitch is in the enabled position it overrides the requirement for a Level 2 access code Therefore if an alarm condition occurs the keyswitch enables the immediate operation of the control keys With the keyswitch in the enabled position the Level 2 menus are accessible by pressing the O button MUTE BUZZER Pushbutton Operating the MUTE BUZZER pushbutton when an alarm or fault has occurred silences the internal buzzer If the Primary Delay is active during an alarm condition this pushbutton will also terminate this delay and start the Extend Delay time The internal buzzer remains silent until the system is RESET or the panel detects another alarm condition EXTEND DELAY Pushbutton With the occurrence of an alarm and with the Primary Delay active pressing the EXTEND DELAY pushbutton cancels the initial response time and
18. 1 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 12 4 Input Events User Option The Input Events menu option allows the user to view active input events plant alarms while the normal active input events plant alarms display has been overridden by a higher priority display alarms To view Plant Alarms from the VIEW Mode menu 1 Using the numeric keypad press the button to select the Input Events display e rete L 2 TheLCD automatically displays either a The first input event or ada b The No Warnings message if there are no current input events recorded on the system 3 If a number of input events are present press the buttons to scroll through the entries Plant Alarm condition Alarm currently displayed Number of alarms Zone Number Device Address Device Type Time alarm was logged if any Note Plant alarms for Hold Switch and Abort Switch inputs are entered as AUX events in the Fault list These input events are not processed by any CBE rules H 7a 0000 4 Press the Q button to return to the View Mode menu 997 264 000 11 Issue 11 42 October 2010 ID50 Series Panel Operating Manual 4 12 5 Disabled User Option The Disablement User Option allows the user to view all current loop based input disablements recorded on the system To view each disablement in turn from the VIEW Mode menu 1 Using the numeric keypad press
19. 1 1 Time User Option The Time User Option allows the user to enter or edit the current time displayed on the LCD To edit the time proceed as follows 1 Press the pushbutton on the numeric keypad to select the Time option O 4 Ea 2 The LCD displays the Enter New Time prompt Using the numeric keypad enter the numbers directly All digits are automatically entered into position from left to right on the display After entering the last digit press the Q to confirm and return to the CLOCK menu 000040 geyen L Syme arme ne Note The entered time must be in the 24 hour clock via format e g for 07 11 pm enter 1911 If an invalid time is entered the LCD displays an error message and then re displays the Clock menu 35 997 264 000 11 Issue 11 October 2010 cd i gt an _ ON O pan lt n Pr cs Q ID50 Series Panel Operating Manual 4 11 2 Date User Option The Date User Option allows the user to enter or edit the current date displayed on the LCD To enter or edit the date proceed as follows 1 Using the numeric keypad press the 0 button to select the Date option o e 2 The LCD prompts for entry ofa new date Using the numeric keypad enter the numbers directly All digits are automatically entered into position from left to right on the display After entering the last digit press the to confirm
20. 263 ID50 Series Panel Installation Commissioning amp Configuration Manual Sections 4 and 5 4 14 Print The RS232 Protocol option has to be set to Printer for this option to become available If available the panel s event log and disablements can be printed using an external printer or displayed on a terminal or saved as a file on a PC connected to the RS232 port To print the event log og TnL tad Tae 1 Fromthe top level menu press the e button to select the Print option The following options are displayed a We 1 ID60 option only a 2 Press the pushbutton to select the Print Log option 45 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 7 3 Select the appropriate print option from the Log menu lie Moio ase using the appropriate numeric key You are prompted or a selected print to enter the dates of the event log period you wish to option the option will print Use the numeric keypad to enter the dates press not be selectable the to confirm the date entered If you make a mistake edit the date using the button and then press the button 4 The display now changes to indicate that printing is taking place as follows 5 If the event log is being printed to a PC the data can be saved as a csv comma separated values Excel file for archiving purposes Note The ID5x 6x Series offline configuration tool has an option under the
21. NOTIFIER by Honeywell operating manual 1D50 60 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Contents 1 Introduction 1 1 1 Associated Documents 1 1 2 The ID50 ID60 Series Panel 1 1 2 1 Device Type Abbreviations 2 1 3 Cleaning 2 2 Panel Controls and Indicators 3 2 1 Controls 3 2 2 Indicators 4 3 Automatic Alarms What to do 5 3 1 Fire 5 3 1 1 Fire in Delayed Mode 7 3 2 Pre alarm 8 3 3 Fault 9 3 2 1 Power Fail 10 n 3 3 Plant Alarm 11 nd jen 4 Operator Actions at Panel 12 io 4 1 Introduction 12 4 1 1 Liquid Crystal Display 12 O 4 1 2 Internal Buzzer 13 O 4 1 3 Access Codes 13 4 1 4 Keyswitch 14 4 2 MUTE BUZZER Pushbutton 14 4 3 EXTEND DELAY Pushbutton 14 4 4 END DELAYS EVACUATE Pushbutton 15 4 5 SILENCE RESOUND Pushbutton 16 4 6 RESET Pushbutton 17 4 7 Numeric Keys 18 4 7 1 Cancellation Termination Button 18 4 7 2 Level 2 Options Menu Button 18 4 8 Level 2 Option Menus 19 4 9 TEST User Option 20 4 9 1 LEDs User Option 21 4 9 2 LCD User Option 21 4 9 3 Zones User Option 22 4 9 4 Auto High Test User Option 24 4 9 5 Outputs User Option 24 i 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 9 6 Buzzer User Option 27 4 9 7 Keyboard User Option 27 4 10 DISABLE ENABLE User Option 28 4 10 1 Zones User Option 28 4 10 2 Outputs User Option 31 4 10 3 Day Mode User Option 32 4 10 4 Delays User Option 33 4 11 CLOCK
22. V means an imminent deep discharge a value less than 21 V indicates deep discharge of the batteries An Earth Fault is indicated when the displayed value is less than 175 or greater than 450 A fault is generated if the panel detects either a series resistance is too high or parallel resistance is too low The values are for service engineer use only Amains failure is detected when the AC voltage drops below 193Vac This fault will remain until the AC voltage rises above 205Vac The Charger is faulty if a value less than 24V is displayed 3 Pressthe B button to cancel and return to the View Mode menu 44 ID50 Series Panel Operating Manual 4 12 8 Version User Option The Version User Option allows the user to view the System and Loop part numbers and revision levels used in the system To view the Versions from the View Mode menu 1 Using the numeric keypad press the Q button to select the Versions display Mo Te ovan Hie ID60 panel only 2 The LCD automatically displays the following Press the Oo button to cancel and return to the View Mode menu Revision Level Part Number 4 13 Commissioning The Commissioning User Option is available to Level 3 users only i e the Level 3 access code must be entered The Commissioning menu allows the engineer to configure the system in preparation for handover For details concerning commissioning and configuring the system refer to 997
23. a general pre alarm condition at the panel refer to Section 5 7 Control by Event Rules Recommended operator actions 1 Operate the MUTE buzzer pushbutton to silence the panel s internal buzzer 2 Check condition of sensor indicated and check area for possible fire If the cause cannot be determined notify authorised servicing company ID50 Series Panel Operating Manual 3 3 Fault Automatic panel actions 0000 si oli occurs the panel automatically does the 6646 ollowing a Operates the internal buzzer 2 sec on 1 sec off b Flashes the appropriate FAULT LEDs including numbered ZONE FAULT DISABLE TEST LED s if appropriate Sa Sha Q FIRE 3 DISABLEMENT O FAULT O TEST POWER SUPPLY FAULT EARTH FAULT SYSTEM FAULT SOUNDER FAULT DISABLED PRE ALARM FIRE CONTROL O P FAULT DISABLED c Operates any control outputs which are associated in the Control by Event Rules with fault events Recommended operator actions 1 A fault message typically displays information as follows not all items apply to all types of fault 0000000 a Fault condition Fault number currently displayed Total number of faults logged A text message describing the fault Zone Number Fe ao Device Address g Device Type h Time fault was logged Depending upon the fault message either A B C D E F G H i Ifthe fault message relates to a specifi
24. able menu or b When Digital UE Input 1 is operated if this input is configured during commissioning for Day Mode Start These delays will be deactivated when Day Mode is ended either automatically at the end of the configured Day Mode period or by one of the following 0O0000000 a Using the Disable Enable menu b When the Digital UE Input 1 is operated c Delays are disabled using the Disable Enable menu 33 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 11 Clock User Option The CLOCK User Option allows the user to enter or edit the following a Time b Date To edit the CLOCK User Option 1 At the Status NORMAL message press the O button The LCD prompts for a Level 2 3 access code Note lf an incorrect access code is entered the LCD displays an ERROR INCORRECT PASSCODE l After one minute the LCD returns to the Status NORMAL message 2 Either turn the keyswitch or using the numeric keypad enter the correct Level 2 access code and confirm using the button The Level 2 menu is displayed with the user number U0 to U9 in the top left hand corner 3 Press the button on the numeric keypad to select the Clock menu E wo an _ oQ v O pran S lt Dm sed Q O 997 264 000 11 Issue 11 34 October 2010 ID50 Series Panel Operating Manual 4 1
25. an c Total number of faults logged TEST O POWER SUPPLY FAULT d Time fault was logged DELAYS ACTIVE O EARTH FAULT FIRE OUTPUT FAULT DISABLED O SYSTEM FAULT e A text message describing the fault FIRE OUTPUT ACTIVE O SOUNDER FAULT DISABLED PLANT ALARM O PRE ALARM POWER e FIRE CONTROL O P FAULT DISABLED O A B C D A battery fault is shown on the LCD as follows 2 Ifa service contact number has been configured the LCD alternates between the power fault message and the service contact number Note Press the MUTE BUZZER pushbutton to silence the panel s internal buzzer 3 When the cause of the fault has been cleared press the RESET pushbutton RESET 997 264 000 11 Issue 11 October 2010 gt gt EZRA 10 ID50 Series Panel Operating Manual 3 4 Plant Alarm A Plant Alarm indication is the default configuration setting for ID50 Series fire control panels In this configuration the panel operates as follows A Plant Alarm message is displayed if the panel detects a non fire input AUX configured in zones 17 to 32 When a non fire event occurs the Plant Alarm LED is illuminated except for Hold Switch and Abort Switch AUX inputs and the LCD displays the following information Plant Alarm condition Alarm number currently displayed a b c Number of alarms d Zone number e Device address f Device type Time of logged message g
26. and service visits A brief note of any work carried out or outstanding should be made Sample pages of the log book are provided here and can be photocopied to produce a log book that conforms to EN54 14 The sample below is for the reference data eg the name of the responsible person while the sample on the next page is for the entry of event data REFERENCE DATA Name and address Responsible person This system was installed by and is maintained under contract by Telephone number should be contacted if service is required A1 1 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Event Data Date Completed Action Required A1 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Event Data Date Completed Action Required October 2010 997 264 000 11 Issue 11 A1 ID50 Series Panel Operating Manual Event Data Date Completed Action Required A1 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Appendix 2 Maintenance Create a log book see Appendix 1 in accordance with the recommendations of EN54 Part 14 This log book should be used and maintained for recording events as described below A2 1 Routine Testing In order to ensure that the system is fully operational and to comply with the requirements of EN54 Part 14 and BS 5839 Part 1 1988 the following routine attention
27. by turning the keyswitch or by entry of an access code The access code is a sequence of numbers configured in the panel during commissioning The panel has two levels of access codes 7 Level 2 and Level 3 Level 3 is required for testing the loop booster output and for panel configuration and commissioning procedures The panel has a maximum of ten 10 Level 2 access codes each defined by the user identification number UO U9 in the top left hand corner Entering a Level 2 access code allows access to all functional controls and some system operation parameters Operating the keyswitch to enter Level 2 always displays U9 Note When the panel is at Level 3 S1 is displayed in place of the user identification number 1 Press the button at the Status NORMAL message to prompt for a Level 2 3 access code as shown below 2 Press and hold the D button while pressing the appropriate 4 digit Level 2 access code will appear on the LCD as the numbers are entered 3 Press the 0 button to confirm the entered code The Level 2 Options are then displayed 4 The procedure to cancel Level 2 and thus prevent any other person accessing Level 2 options is given in Section 4 1 1 Note If an incorrect access code is entered the following is displayed Press the button or wait for approximately one minute to return to the Status NORMAL message 13 997 264 000 11 Issue 11 October 2
28. c loop device investigate whether the cause of the fault is immediately apparent and can be corrected pann Note Press the button to view additional zone text information To return to the fault message press any numeric cursor key if no key is pressed within ten 10 seconds the display automatically returns to the fault message ii Ifthe fault message relates to a system fault condition as displayed below note the full description of the fault and notify the authorised servicing company Note Items e f and g are not applicable A B Cc H 9 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 2 Ifa service contact number has been entered during panel commissioning the LCD alternates between the fault message s and the following A B C D Note Press the MUTE BUZZER pushbutton to silence the panel s internal buzzer 3 When the cause of the fault has been cleared press the RESET pushbutton RESET gt gt PIA 3 3 1 Power Fail 1 The loss of a power supply causes the panel to enter a Power Fail condition The POWER SUPPLY FAULT and general FAULT LEDs illuminate and the internal buzzer operates The LCD displays If both the AC and Battery power fail the indicators and LCD are non operational a Fault condition b Fault number currently displayed a O Z
29. e Note Up to one minute must be allowed for smoke sensors to clear 23 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual VAAN 997 264 000 11 Issue 11 October 2010 ap SI If a fire alarm signal is received from a zone other than those being tested all sounder output and relay output circuits will activate as configured for a zone in alarm The sounders will continue to ring until silenced from the panel 4 9 4 Auto High Test User Option The Auto High Test if configured during commissioning automatically polls and tests all devices on the loop at a specified time of day This test takes about 70 80 seconds to complete To run the test manually 1 Fromthe Test Menu using the numeric keypad press the button to select the Auto High Test 2 When the LCD displays the start Auto High Test message press the button to start the test 3 Each sensor is tested individually The device under test is displayed on line 2 of the LCD in the format shown below then re displays the Test Menu 4 After each device test the pass or fail message is displayed as in the examples below 5 Ifa fault occurs while the Auto High Test is active the LCD displays a fault message example given below 6 Pressthe button to display additional zonal and device text information Press the Q button to return to the Test menu Clear the fault and repeat the test 4 9 5 O
30. e overall system and display the panel status The panel has five function pushbuttons twelve numeric cursor keys and thirty two zonal LED indicators two FIRE indicators and fourteen system status LED indicators An access level 2 keyswitch is provided to enable the operation of panel controls and access to user menus without entering a passcode via the numeric keypad ST 0000000000000009 000 062080384085 7 amp o 10 Wl WW We WS 16 O 6 O600000000006066 FIRE MUTE BUZZER DISABLEMENT e FAULT O EXTEND TEST POWER SUPPLY FAULT O _____PEVAY DELAYS ACTIVE EARTH FauLtT END DELAY EVACUATE FIRE OUTPUT FAULT DISABLED SYSTEM FAULT O SILENCE FIRE OUTPUT ACTIVE e SOUNDER FAULT DISABLED e RESOUND PLANT ALARM e PRE ALARM O POWER FIRE CONTROL O P FAULT DISABLED e RESET 2 1 Controls The pushbuttons are listed below together with references to the relevant sections of the manual Function Pushbuttons MUTE BUZZER e MUTE BUZZER Section 4 2 n EXTEND DELAY B e EXTEND DELAY Section 4 3 i e END DELAY EVACUATE Section 4 4 moon O e SILENCE RESOUND Section 4 5 RESET e RESET Section 4 6 1 Also configurable as Transmission Device TD Enable Disable Numeric Cursor Keys Section 4 7 e Num
31. eric Cursor keys Keyswitch Turn the keyswitch to enable level 2 access The keyswitch provides an alternative to entering the level 2 access code via the numeric keys See Section 4 1 3 and Section 4 1 4 3 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 2 2 Indicators ZONEFIRE 000000000 eee The panel status indicators comprise three groups 123 4 5 6 7 8 9 10 11 12 13 14 15 16 a Zone Status LED indicators b Panel System LED indicators c Visible Audible indicators Zone Status LED Indicators e ZONE FIRE these LEDs indicate affected zone s e ZONE FAULT DISABLE TEST these LEDs indicate EE 0000000000000000 agiecied zane 123 4 5 6 7 8 9 10 11 12 13 14 15 16 Panel System LED Indicators e FIRE these LEDs indicate a fire condition FIRE z e Other System Status LEDs FAULT indicates a fault has been detected by the panel DISABLEMENT indicates the presence of a manually configured disablement TEST indicates a test is in progress DELAY ACTIVE indicates delays are active san FAULT FIRE OUTPUT ACTIVE indicates fire outputs have TEST POWER SUPPLY FAULT been operated PERS ACTIVE aa FAULT 4 PRE ALARM indicates a pre alarm FIRE OUTPUT ACTIVE SOUNDER FAULT DISABLED condition exists PLANT ALARM
32. es Panel Operating Manual 4 10 2 Outputs User Option The Outputs option allows the user to disable or enable all sounders the extinguishant system if fitted and relay and control outputs To Disable Enable these outputs proceed as follows n TR E 1 Usingthe numeric keypad press the 0 pushbutton to display the Disable Enable Outputs menu 2 Press the appropriate numbered button on the numeric keypad to display one of the following a Press the 0 button to disable enable all sounders Sa S somen b Press the button to disable enable all transmission device outputs s e anon c Press the button to disable enable all Extinguishant System outputs Sali car d Press the button to disable enable all Fault relay outputs RT come e Press the button to disable enable other relays and control outputs 3 Press the Q button to confirm the selected operation The LCD automatically returns to the Disable Enable menu O O When outputs are disabled the general DISABLEMENT O LED and if applicable the FIRE CONTROL O P FAULT SYSTEM FAULT O mb DISABLED FIRE OUTPUT FAULT DISABLED and or e O e FIRE DISABLEMENT TEST DELAYS ACTIVE FIRE OUTPUT FAULT DISABLED FIRE OUTPUT ACTIVE PLANT ALARM POWER FAULT POWER SUPPLY FAULT EARTH FAULT TE SOUNDERS FAULT DISABLED LEDs illuminate If the E
33. f in accordance with the battery manufacturer s recommendations and local regulations A2 3 Cleaning The panel may be cleaned periodically by wiping with a soft damp lint free cloth Do not use any solvents A2 1 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Appendix 3 1D60 Single Loop Panel Differences The ID60 Panel differs from the ID50 Panel in that it supports Very Intelligent Early Warning VIEW and SMART 4 multi criteria sensors This appendix describes differences to the user operations required by the ID60 Panel VIEW Sensor GAN Each VIEW sensor has to be calibrated on first N operation with the panel If a VIEW sensor is removed and cleaned or replaced with a new one wait at least 30 secs after removal before replacing it Q Calibration is carried out automatically for each sensor approximately 60 secs after the sensor is installed on a Following replacement panel which is already operating normally VIEW sensors remain During this initial period which is required to allow the inoperable for 60 seconds VIEW sensor to stabilise the sensor must not be while calibrating exposed to smoke or any other abnormal conditions otherwise the panel may report a sensor fault SMART 4 Sensor No user procedures are required with this sensor However a new advisory message is logged whenever a SMART 4 device approaches the end of the useful life of the CO se
34. hese to stop testing as required Press the B button again to exit and return to the Test Outputs menu 25 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual Test Loop Booster Outputs A number of tests are available to satisfactorily test the To perform a Loop Booster operation of the Loop Booster Modules LBMs during output test an access level 3 alarm conditions The tests are designed so that the power passcode is required delivered to the loop by the panel can be switched off from either end or each LBM in turn can be prevented from being turned on The tests are designed when combined with a walk test to check that a The panel operates all loop powered devices correctly with the LBM s with one source of loop power isolated b Allloop powered outputs operate correctly with any individual LBM disabled or with the loop only powered from one end 1 Pressthe 0 button on the numeric keypad to select the Loop Booster test procedure With the panel currently at access level 2 the following warning is displayed prompting for entry of access level 3 passcode 2 Having entered the access level 3 passcode press the button to start the test 3 Before the test starts a 0 percentage indication of the Select Both Sides to test loop equipment under test is displayed on the top line As the test powered sounders only LBMs progresses the percentage value increases to 100
35. is as shown below The DELAY ACTIVE LED will extinguish when the Day Mode operation has been ended either when day mode is turned off or when the timer has timed out No delays are active 0000 Note lf Day Mode is NOT cancelled manually Day Mode delays are automatically deactivated at the end of the set time period 997 264 000 11 Issue 11 32 October 2010 ID50 Series Panel Operating Manual 4 10 4 Delays User Option The Disable Enable Delays option allows the user to cancel or initiate the Delays function of the panel which is configured during commissioning refer to 997 263 ID50 Series Panel Installation Commissioning and Configuration Manual Sections 5 5 5 4 Primary Extend Delay Timers and 5 7 8 CBE Zones To Disable Enable Delays 1 Using the numeric keypad press the button to select the Disable Enable Delays option 2 At the prompt press the button to confirm the Delays operation lf delays are disabled the LCD prompts to enable delays and vice versa When the delays are disabled the DELAY ACTIVE LED is extinguished When the delays are enabled the LED is illuminated FIRE DISABLEMENT TEST DELAYS ACTIVE FIRE OUTPUT FAULT DISABLED FIRE OUTPUT ACTIVE PLANT ALARM POWER If a Day Mode time period is configured the CBE Rule delays will activate when Day Mode is started either a Using the Disable En
36. ltiple alarms the LCD displays the first alarm event 5 When evacuation of the premises is achieved or at the direction of an authorised person the Alarm Sounders may be silenced by pressing the SILENCE RESOUND pushbutton Note The SOUNDERS SILENCED LED illuminates if this option was configured during panel commissioning The default function for this LED is PRE ALARM 6 To re start the sounders press the SILENCE RESOUND pushbutton You must wait at least 10 seconds after having originally silenced the sounders before resounding them If the SOUNDERS SILENCED LED option was configured during commissioning to illuminate this will now extinguish 7 When the cause of the alarm has been removed and call points and input devices have been locally reset the system may be returned to Status NORMAL by pressing the RESET pushbutton Unless the Site name menu was edited during commissioning refer to Section 4 1 1 Liquid crystal Display ID50 Series Panel Operating Manual EN54 2 7 11 c Total time for configured delays MUST NOT exceed 600 seconds MUTE pte wa gt i 1b Er FIRE DISABLEMENT TEST 0000 2 END DELAY EVACUATE onn 00 00 01 RESET 3 1 1 Fire in Delayed Mode The Delayed Mode introduces a delay between an alarm being detected and the sounders and output modules activating Depending upon the pa
37. meric keypad press the Oo button to select the View Mode menu adi Met 4 Press the buttons to display further menu options e avein Tir ID60 panels only cd c oQ an _ oQ ON Cc O prann S lt x be e Pt 1 pes cd 37 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 12 1 Log User Option The Log User Option allows the user to view all logged events one at a time To display the Log from the VIEW Mode menu 1 On the numeric keypad press the pushbutton to select the Log option Oo oe 2 The LCD automatically displays the last recorded event Viewing commences from this point press the buttons to scroll through the Log entries Example Log entries are given below Note Press the Q button to view additional zone text information To return to the previous display press any numeric cursor key Alternatively if no key is pressed within ten 10 seconds the LCD returns to the View Log display automatically 3 Pressthe B pushbutton to return to the View Mode menu 4 12 2 Devices User Option The Devices User Option allows the user to observe all loop devices in turn Device data is displayed on the bottom line of the display and the format depends on the configured protocol CLIP or OPAL of the selected device To view Devices from the View Mode menu 1 Onthe numeric keypad press the button to selec
38. ndard function of the SEA allows the panel keyboard to be functionally control keys is suppressed while this test is active Normal function resumes upon test completion 1 Using the numeric keypad press Q to display the TEST menu 2 Press the QQ pushbuttons to display the next screen options To test the keyboard press the Q button on the numeric keypad 3 The following screen is displayed Press each panel pushbutton in turn When a pushbutton is pressed the corresponding display entry is replaced by an equivalent number of asterisk characters The five pushbuttons MUTE BUZZER SA are represented by A to E where A is the top button EXTEND DELAY B Once all pushbuttons have been pressed the display will return to the test menu The keyboard test will END DELAY C A A A EVACUATE automatically abort after one minute if no key is pressed SILENCE RESOUND D E RESET 27 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 10 DISABLE ENABLE User Option This option allows the user to disable or enable depending on their current state the following parts of the system a Zone Device or Full Zone b Outputs c Day Mode d Delays To display the DISABLE ENABLE menu 1 At the Status NORMAL message press the 6 button The LCD prompis for a Level 2 3 access code 2 Either turn the keyswitch or u
39. nel configuration this may be a single delay or a 2 stage delay an initial brief delay which may be extended by pressing EXTEND DELAY to allow an investigation The delay is initiated if the panel enters an alarm condition during Delayed Mode Note For any configured delays pressing EXTEND DELAY cancels the initial response time and initiates the fire investigation period Activation of an MCP will also cancel any configured delay period The maximum time for the primary initial response time is 300 secs the TOTAL time for both periods is 600 secs The delay period can only be configured at Level 3 by the Commissioning Engineer The delayed mode status is indicated on the LCD as below ta When the panel enters a fire condition the delay countdown is started and the internal buzzer sounds The buzzer can be silenced by pressing the MUTE BUZZER pushbutton The LCD displays the alarm information on the top line this alternates for 1 sec every 5 secs with the time remaining before the shortest day mode delay expires 1b If the 2 stage delay is configured pressing the EXTEND DELAY pushbutton during the primary delay initiates the fire investigation period Note If configured to do so the DISABLEMENT LED is illuminated not default from the initiation of the primary delay and extinguishes at the end of the primary delay period or fire investigation period 2 If the delay time elapses a full alarm condition is entered the c
40. nsor element approximately 6 months before the sensor needs a complete replacement A new print option is available with the ID60 that allows printing of the maintenance log It is still possible to print the maintenance log even if it contains no entries The print out will confirm that the maintenance log is empty Service Due Indication If configured the advisory message Status SYSTEM SERVICE DUE will replace the Status Normal screen when the service due date has been reached Contact the authorised servicing company T O c D i D m a LI m La c D O 2 lt This service due message can only be reset or disabled by the authorised servicing company A3 1 997 264 000 11 Issue 11 October 2010 NOTIFIER by Honeywell Charles Avenue T 44 0 1444 230 300 Burgess Hill F 44 0 1444 230 888 W Sussex E sales notifierfiresystems co uk RH15 9UF www notifierfiresystems co uk Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein Design features may be changed or amended without prior notice v UKAS Quany MANAGEMENT 007 Quality Systems Certificate No 154 Assessed to ISO9001
41. onfigured fire outputs are activated To cancel the delay operate the END DELAY EVACUATE pushbutton the full alarm condition is entered and the internal buzzer sounds it can be silenced by pressing the MUTE BUZZER pushbutton Note A Fire alarm in a different zone to the first alarm will also cancel the delay 3 When the cause of the alarm has been cleared press the RESET pushbutton to return to the Status NORMAL message ade 7 997 264 000 11 Issue 11 October 2010 e e e wd jan n LI E es amp lt x Oo par oQ ad lt 0000 112 3 4 MA 2e WI ID50 Series Panel Operating Manual FIRE DISABLEMENT TEST O O O O FAUL POWER SUPPLY FAULT EARTH FAULT SYSTEM FAULT SOUNDER FAULT DISABLED PRE ALARM FIRE CONTROL O P FAULT DISABLED 997 264 000 11 Issue 11 October 2010 0000000 3 2 Pre alarm When one or more input devices signal to the panel a reading higher than normal but not yet at the FIRE level this is a PRE ALARM condition Automatic panel actions a Intermittent operation of the internal buzzer one second ON one second OFF b Operation of the appropriate ZONE FAULT DISABLE TEST LED and yellow PRE ALARM LED c Displays information on the LCD regarding the pre alarm condition d Operation of any assigned outputs in response to
42. ons Only one alarm condition can be displayed at a time on the LCD If fire alarms faults and or warning conditions Plant Alarm are present on the panel at the same time they are displayed in the following priority order a Fire Alarms b Pre alarms c Faulis d Warnings The alarm condition is registered in a log The user must then enter a Level 2 access code or turn the keyswitch to the right to enable the panel s pushbuttons When the Level 2 access code is active the buttons can be used to scroll through the alarms and the Q button will display the first alarm Fire Automatic panel actions If the system detects a fire alarm the panel always does the following automatically a Operates the internal high pitched buzzer b Illuminates the red FIRE LEDs and the numbered red ZONE FIRE LED c Displays information on the LCD regarding the fire condition The information includes device address and device location see example below LOGGED ZONE DEVICE TIME OF LOGGED ALARM NUMBER TYPE ALARM CONDITION ZONE TEXT DEVICE DEVICE ADDRESS TEXT 5 Note If a delay is configured DELAYED is displayed on the top line of the LCD When a delay is active the DELAY ACTIVE LED illuminates and the remaining time before the first day mode delay expires is displayed every 5 secs The LED only extinguishes when the delay period has expired d Operates the sounders and output modules according
43. ored Relay Type Output ESE Extinguishant System Output VdS ESM Extinguishant System ESO Monitored Extinguishing System Output EST Extinguishant Monitor System Trigger ION lonisation Smoke Detector IRL Immediate Release Input LBM Loop Booster Module MCP Manual Call Pointt MLT Advanced Multi Sensor MNS Monitor module no short circuit MON Fire Alarm Monitor Input MRL Manual Release Input M CZ Conventional Interface input OPAL OPT Optical Photo electric Smoke Detector OPX Optiplex Multi sensor RLE Unmonitored Relay Type orO C Outputs VdS RLY Unmonitored Relay Type or O C Outputs SDR Monitored Sounder Type Output SDH Monitored Sounder Type Output high load SM2 SMT2 SMART 2 Multi criteria Sensor SM3 SMT3 SMART 3 Multi criteria Sensor SM4 SMT4 SMART 4 Multi criteria Sensor STRB Strobe OPAL TMP Temperature Detector TxD Monitored Transmission Routing Output ZMX Conventional Detector Input CLIP Note Devices marked are supported by the ID60 Panel only The Device marked 7 is also available as DKM not used in this application provided to be compatible with VdS requirements 1 3 Cleaning The panel case may be cleaned periodically by wiping with a soft damp lint free cloth Do not use solvents 997 264 000 11 Issue 11 2 October 2010 ID50 Series Panel Operating Manual 2 Panel Controls and Indicators The panel s controls and indicators are used to operate th
44. playing each upper case character in turn To test the LCD enter access Level 2 and follow the procedure below 1 Using the numeric keypad press Q to display the TEST menu 2 Totestthe LCD press the 0 button on the numeric keypad 3 Each character is then displayed in turn on the LCD When all characters have been displayed press the button to cancel and return to the Test Menu Ag 21 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual 4 9 3 Zones User Option The Test Zones option selected from the Test Menu allows the user to perform a walk test on one zone at a time During the walk test the TEST and relevant ZONE FAULT DISABLE TEST LEDs are illuminated indicating that the system and zone is in TEST mode To perform a walk test at the TEST menu 1 Pressthe 0 button on the numeric keypad to select the walk test procedure en Set Pre 2 The LCD displays the Test Zones menu Select either the Ring Sounders or No Sounders walk test kai a Using the numeric keypad press Q to display the 0000 112 3 4 0000 Q FIRE 5 DISABLEMENT Q TEST O DELAYS ACTIVE 3 o OPAL Protocol Devices in Walk Test When a zone with OPAL protocol enabled is put into Walk Test the OPAL device LEDs flash green with a longer ON duration to indicate that the device is ready for testing When a device is
45. rating Manual 4 9 TEST User Option The following tests are available at Access Level 2 from the Test User Option menu g a b c d e f LEDS LCD Zones Auto High Test Outputs Buzzer Keyboard To start the TEST User Option 1 At the Status NORMAL message press the 6 button The LCD prompis for a Level 2 3 access code To cancel press Note Entering an incorrect access code causes the LCD 2 to display the ERROR INCORRECT PASSCODE message then an automatic return to the access code prompt Either turn the keyswitch or using the numeric keypad enter the correct Level 2 access code and confirm using the 6 button The User Option menu is displayed with the user number U0 to U9 in the top left hand corner 20 ID50 Series Panel Operating Manual 4 9 1 LEDs User Option This option selected from the Test menu illuminates each LED in turn To test the panel LEDs enter access Level 2 and follow the procedure below 1 Using the numeric keypad press Q to display the TEST menu 2 To test LEDs press the Q button on the numeric keypad 3 Each of the panel LEDs illuminates in turn while the LCD flashes the message shown below When all LEDs have been tested press the button to cancel and return to the Test menu 7 AL A 4 9 2 LCD User Option The LCD Option selected from the Test menu tests the LCD by dis
46. sing the numeric keypad enter the correct Level 2 access code and confirm using the Q button to display the menu The LCD displays the user number UO to U9 in the top left hand corner Note An incorrect access code causes the LCD to display the ERROR INCORRECT PASSCODE message After one minute the LCD returns to the Status NORMAL message 3 Using the numeric keypad press the 0 button to display the DISABLE ENABLE menu 4 10 1 Zone User Option This option allows the user to disable enable a full zone or part of a zone selected devices To perform this operation 1 Using the numeric keypad press the Q button to select the Disable Enable Zone option o onn 2 The LCD displays the Zone option and prompts for a zone number Enter the zone number one or two digits entered via the numeric keypad Press the to N confirm the zone number 997 264 000 11 Issue 11 28 October 2010 ID50 Series Panel Operating Manual 3 The LCD then displays the current state of the zone Vou Fully enabled Fully disabled or Part disabled and prompts for selection of Full Zone or Devices in zone Note Press the buttons to step to the previous next zone and confirm using the button 4 Todisable a A Full Zone Press the Q button on the numeric keypad to select the Full Zone option and the 0 button to confirm FO 0000 3 FIRE gt DISABLEMENT O O O
47. t Zonal and device text if any A B C D E F FIRE OUTPUT ACTIVE O PLANT ALARM aje POWER H G When the cause of the alarm has been cleared the message will automatically be removed from the LCD and the LED extinguished The panel returns to quiescent mode FIRE OUTPUT ACTIVE O PLANT ALARM _ e POWER 3 5 Fault Output Fault Disabled Optional Oo _ n LI es amp lt x Oo pen oQ _ lt x If the panel has been configured to indicate the status of the Fault Output relay circuit a message is displayed if a Fault Output relay circuit fault condition is detected or if it has been disabled FIRE OUTPUT FAULT DISABLED FIRE OUTPUT ACTIVE FAULT OUTPUT FAULT DISABLED Note An output device configured to a Fault CBE rule remains active if disabled from a source other than the panel Fault Output relay disable function 000 11 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual SYSTEM NORMAL 2 DISABLE ENABLE 3 CLOCK 4 VIEW MODE 5 COMMISSIONING 6 PRINT The Commissioning Menu is ONLY available with a Level 3 passcode 997 264 000 11 Issue 11 October 2010 4 4 1 Operator Actions at Panel Introduction Operator actions at the panel require the correct pushbutton and access code entry The LCD and the user pushbut
48. t the Devices display The LCD displays the last viewed sensor address ada 2 Press the buttons to scroll through device address entries until the desired sensor is displayed If the loop has mixed protocol devices the display will show the approriate device information 997 264 000 11 Issue 11 38 October 2010 ID50 Series Panel Operating Manual CLIP protocol Device Address Device Type pe ab AE Pulse Width Time Periods OPAL protocol Sensors amp Non Multi modules Device Address Device Type Sub address values Isolator state value OPAL protocol Multi Modules Module Address Channel A Multi module Types MON MON M720 or MON MON RLY M721 Values for Sub addresses 0 1 2 amp 3 see below Isolator state value sub address 127 Notes Multi modules consist of a number of channels channel A or core channel corresponds to the rotary address switch setting channels B and C if it exists are reserved memory allocations and use the next consecutive addresses The first three values are sub address 0 System sub address 1 Channel A and sub address 2 Channel B The fourth value is sub address 3 Channel C and corresponds to the output RLY of an M721 module Press the 0 0 buttons to display details of each sub address For the example above module type M721 with its core address M04 the sub addresses for this module are as follows Module Address
49. t selection Pressing the SILENCE RESOUND pushbutton again SOUNDER FAULT DISABLED O to operate the sounders the SOUNDERS SILENCED SOUNDERS SILENCED LED extinguishes c i gt an _ oQ a O pan S lt ho sf 1 dhe Q Note If the pushbuttons are enabled to operate at Level 2 enter the Level 2 passcode in the manner described in the RESET pushbutton procedure Section 4 6 997 264 000 11 Issue 11 16 October 2010 ID50 Series Panel Operating Manual 4 6 RESET Pushbutton The RESET pushbutton is used to clear all non quiescent conditions and return the panel to a normal quiescent condition Provided that the control keys have been enabled for Level 1 operation the following occurs a All FIRE and FAULT lamps are switched off b All sounders cease to operate c The system status returns to NORMAL provided that no operator actions are being carried out Ifthe pushbuttons are enabled to operate at Level 2 follow the procedure below RESET following gine VBnSp 2 Either turn the keyswitch or enter an appropriate Level ete o 2 access code and confirm using the button If Alarm s and or Fault s conditions are still present when i is operated An condition will be reported as if it were a completely new event with appropriate annunciation s 1 Press the RESET pushbutton The LCD displays the cd c iy an
50. tested the green LED will show red momentarily with an end to the green prolonged flash to indicate that testing is now finished for that device Approximately 1 sec ON 1 sec OFF 997 264 000 11 Issue 11 October 2010 Ring Sounders menu as below In this mode the sounders will ring for a few seconds when a device is tested then reset automatically i Usethe QO buttons to selectthe zone to be tested Press the 0 button to confirm the zone number ii The LCD prompts for confirmation Press the Q button to start the walk test for this zone Repeat steps i and ii for any further zones to be tested Test the devices see Checking the Devices overleaf Press the button to exit the Ring Sounders menu and return to the Zones menu To walk test devices on a specific zone without activating the sounders press 0 on the numeric keypad to select the No Sounders option The walk test procedure is otherwise the same as given above for Ring Sounders To end the walk test For aspecified zone at the Test Zones menu press the button on the numeric keypad to select the View Stop Test menu N N ID50 Series Panel Operating Manual 0 or as i Use the buttons to select the zone then press the button to confirm the zone number Marano ii Press the button to stop the walk test for the selected zone If no other walk tests are active the following is displayed
51. the Q button to select the Disablements display m ai 2 The LCD automatically displays either a The zone disablements or AT NNA b The NO disablements message if no current Disablements are present on the system 3 If more than one disablement is present press the Q Q buttons to scroll through the Disablement entries see examples below a Condition b Disablement currently displayed Active disablements Zone number Device address Device type a gt ee eee Zonal and device text if any 4 Press the B button to return to the View Mode menu 4 12 6 Alarm Count User Option The Alarm Count User Option allows the user to view the number of times the panel has entered alarm condition since manufacture To view the Alarm Count from the VIEW Mode menu A B C D F G GO TOO OQ O 1 Using the numeric keypad press the Q button to select the Alarm Count display Mo omes oveen Ta ID60 panels only 2 The LCD displays the Alarm Count Press the button to return to the View Mode menu 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Operating Manual With sounder circuits configured as transmission device TxD the Voltages User option is used to set the transmission circuit reference impedance With the TxD circuit selected use the numeric keypad and press the pushbutton This sets the impedance reference value for the TxD circuit
52. the area under its supervision Associated Documents This manual does not describe the installation or configuration procedures of the panel For information on these topics refer to the ID50 Series Panel Installation Commissioning and Configuration Manual Ref 997 263 000 X The ID50 ID60 Series Panel The panel as supplied by NOTIFIER is a 1 loop 16 zone Analogue Addressable Panel The single loop has the capacity for up to 99 analogue sensors plus up to 99 modules and in some installations panels may also be connected to repeaters using the RS485 Communications Link All the control and operation functions described in this manual can be carried out using the pushbuttons on the front of the panel A keyswitch is provided which when set to the right has the same effect as entering an access 2 passcode Set it to the centre to cancel out of all menus and return to the Status NORMAL display This indicates access level 2 is de selected 1 997 264 000 11 Issue 11 October 2010 O prann oO O os pen ID50 Series Panel Operating Manual 1 2 1 Device Type Abbreviations Throughout this manual the panel may refer to devices by an abbreviated name The following table lists the device type abbreviation and its description Abbreviation Type Description AUX Plant Warning Input AVR Advanced VIEW Reference AVS Advanced VIEW Sensor CTE Monitored Relay Type Output VdS CTL Monit
53. tons located on the panel allow the following actions to be carried out a Mute the panel buzzer Extend Delays Panel reset aou End Delays Evacuate terminate delays to outputs if delay is active and activate sounders Silence and resound the alarms p Menu navigation and alphanumeric key entry Operator controlled tests Fe Disable and enable of zones outputs or delays Set the clock and date j View log devices faults input events disablements voltages and versions Note Maintenance alarm count is also available but this is an ID60 feature available at access level 3 only All actions are access controlled either through turning the panel keyswitch to the right or by entering a Level 2 access code see Section 4 1 3 Access Codes 4 1 1 Liquid Crystal Display The Liquid Crystal Display LCD provides 80 characters of alphanumeric information on a 2 line display The LCD is backlit to assist viewing under dim ambient light conditions System Normal Display When in a quiescent state the LCD shows the Status NORMAL message on line 1 and the day date and time on line 2 The message will be different if the Site Name menu was edited during commissioning The user options are accessed via a menu structure which in tum is accessed from the Status NORMAL message see opposite If the Status NORMAL message is not present press the Q button repeatedly until it is displayed
54. u Button Operating the O button enables the Level 2 menu and prompts for the entry of an appropriate access code as described in Section 4 1 3 Access Codes Pressing the menu button toggles between the panel status and user menus 997 264 000 11 Issue 11 18 October 2010 ID50 Series Panel Operating Manual 4 8 Level 2 Option Menus The following Level 2 Option Menus are available after a correct Level 2 access code has been input or the keyswitch has been operated The menu map at left shows an overview of the Level 2 menus The Commissioning menu is shown inverted to nn indicate that a Level 3 access is required ni ame dizan su Fiesso ei a a 1 ua Disabled kon Me Fre Alarm Count 7 Voltages T cd S an _ ON G O pan S lt da sf pes i N U 5 COMMISSIONING lalala na ml Notes 1 Level 3 Configuration Menus are Eo ie described in 997 263 000 X ID50 Series a piped Panel Installation Commissioning amp ME Configuration Manual Section 5 3 Maintenance ID60 Configuration orn 2 With a fire alarm active the panel status display will override the user menu 5 secs after the last key press 19 997 264 000 11 Issue 11 October 2010 E wo an _ oQ v O pran S lt Dm sent i Q 997 264 000 11 Issue 11 October 2010 ID50 Series Panel Ope
55. utputs User Option The Test Outputs option accessed from the Test Menu tests the panel s internal sounder and relay circuits and the Signalling Line Circuit SLC loop outputs To perform this test Test Internal Outputs 1 From the Test Menu press the button on the numeric keypad to select the Outputs option 24 ID50 Series Panel Operating Manual ya N 2 Pressthe Q button on the numeric keypad to display the Internal Test menu di 3 Usethe buttons to select the internal output required for testing and press the Q button to start a the test The LCD then displays the following 4 Check that the output operates To stop the test press the button again Press the Y button again to exit and return to the Test Outputs menu Test SLC Outputs 1 Fromthe Outputs menu press the 0 button on the numeric keypad to display the SLC Output Test menu 2 Use the buttons to select the first output required for testing and press the button to start the test Use the QQ buttons to select other outputs for testing as required For modules the LCD then displays the following 3 For OPAL sensors configured with a Remote Output set to CBE mode the LCD displays the following 4 Check that the output operates To stop the test of the currently displayed device press the Q button again 5 If other outputs were also put into test mode use the buttons to select t
56. xtinguishant System is disabled only the DISABLEMENT LED will illuminate 31 997 264 000 11 Issue 11 October 2010 PRE ALARM FIRE CONTROL O P FAULT DISABLED O0COO0O8CO ID50 Series Panel Operating Manual The FIRE CONTROL O P FAULT DISABLED FIRE OUTPUT FAULT DISABLED and the SOUNDERS DISABLED LEDs extinguish when the corresponding outputs have been enabled The DISABLEMENT LED will only extinguish when ALL disablements have been enabled 4 10 3 Day Mode User Option If Day Mode is enabled during panel commissioning this option allows the user to activate deactivate Day Mode delays during the set Day Mode time period This has no effect on any sensor sensitivity changes that may have been configured during commissioning Any sensor sensitivity changes will automatically occur at the set Day Mode period start and end times To Disable Enable Day Mode proceed as follows di 1 FromtheDisable Enable menu press the o button to display the following D koom semen 2 Press the button to confirm the requested operation The LCD automatically returns to the Disable Enable menu If Delays have been configured the DELAY ACTIVE LED illuminates when Day Mode is started FIRE DISABLEMENT TEST DELAYS ACTIVE FIRE OUTPUT FAULT DISABLED FIRE OUTPUT ACTIVE PLANT ALARM POWER O 3 To end Day Mode repeat steps 1 and 2 the display

Download Pdf Manuals

image

Related Search

Related Contents

TANDBERG Content Server None User's Manual  Kenwood KVT-627DVD Car Video System User Manual  ZR-03-38  battery start-up  Targus AMU7502EU mice  

Copyright © All rights reserved.
Failed to retrieve file