        TS1000 Series Vertical Tripod Turnstile User Manual
         Contents
1.  Electromagnet   g Timer   a ABDr    HH  gt  Passing Indicator      eu  L2R    L2COM ga    Direction Indicator       Direction Indicator    COW er e A     FUMA    Optocoupler Board    SanGunLun V1 4 130905    a e  Emergency Switch  GND  Emergency Switch       S  J    HE  db GND a  Su CP   24VIN      E LLO O O LLO O OIL OOOO OTL O  LLO OTL LLO O  LLO O O Ink    485 Reader       x  E  5    J  pe  y pueboiy    A  S  HL       10    
2.  fire or other emergencies    Direction Indicator Output  to connect a LED screen and indicate whether this passage is allowed to pass    Passing Indicator Output  to connect a LED screen and indicate if user verification is successful and whether it is able to pass     Counter Output  to connect a LED screen and display the number of people passed that is generated by the push of tripod arms  each  completed push means pass one time     Drop Arm Electromagnet Output  to control the tripod arms manually rise up and automatically drop down     4 2 Connection Diagram of the Access Control Panel or Standalone Access Control Device       Turnstile Control Board       O   O            or   MD   s   O           E   a Notes    2 1  The Counter is an optional accessory   2  The lock driving duration of the access control panel or standalone   O access control device needs to be set to 1s or Os  and the door sensor    D H H   5 needs to be set to    None            Q   A   Q        3   3   O           U   O   A    Figure 4 2  4 3 Parameter Configuration    Function description of the DIP switch       Figure 5 5       function Setting   Opening Duration    4 3 1 Setting the Turnstile Opening Duration    Opening duration refers to the period of time from opening to closing once the turnstile receives an open signal     In the DIP switch  number 1  2  and 3 are used for duration setting  It can be set to different values from 5s to 60s according to the    following chart   Duration   Bit
3.  than 80 mm  see figure 3 1      Setting a warning line for card swiping  see figure 3 2   A warning line is suggested to prompt users to swipe cards in a distance   which would greatly reduce the probability of equipment failure caused by improper operations        Figure 3 2    3 2 Cabling  There are inlets in the bottom plate for cabling  as shown in figure 3 3  Power supply and communication wire should go through the    inlet  Cable protection covers are suggested to use if it is surface mounted     Warning  The tripod turnstile must be connected to Ground  earth   there is wiring interface in the power switch     A      y 00 OO  amp           WIWQO CS                           320 00mm Es       Figure 3 3    3 3 Installation    1  Drilling holes  Drill holes based on the locations of the holes shown in figure 3 3     2  Fix the mounting plate to its original position  Placing the mounting plate properly and apply screw securing glue on the surface and the threads of the expansion bolts  install four    3    expansion bolts to secure the mounting plate  and use a horizontal ruler to test the levelness of the mounting plate  If the mounting  plate is not level  adjust it by the gaskets provided  Note that all the four expansion bolts must be installed properly  as shown in  figure 3 4     o    soo Nan A      NA_ GRAN 4      Screw securing glue shall    A aa iw be applied on the threads   i        i Sd 3    Figure 3 4  3  Put the turnstile on the mounting plate and tighten
4.  the screws  Apply screw securing glue before use and put gaskets on the screws  to adjust the direction of the turnstile  If the tripod turnstile is not level  you can place gaskets to adjust  as shown in figure 3 5     Installation levelness  A Installation levelness       Figure 3 5    4  Cable Diagram    4 1 Function Description of the Turnstile Control Board    If you are using TS1011 or TS1022  all the connections between access control and turnstile control board are done in factory  Just plug  in communication cable to access controller and do the setting     If you are using TS1000  you need to connect access control system to the turnstile control board  please check the content in this  chapter carefully   Warning  The third party access control system lock relay trigger time should be 1 second or less than 1 second           Ne of So ait es i gael see Nine a     ins E ait in   a y  a Q   T SO PO 59 5U 50 QO 85 g5          3 O 353 CJ  2 E 8  gt  SQ 2333 BF DR ef 30 39          T co 36 658 ZR cu 55    ns    un 5  O  A so E H aS E Pe ze   Wn   D O O o O oO 0  oo  O  G JI Q 2 Cc Oc 5 5   0 OD OD  O D v  Q    cCOo h ES 5 2550 02     a O  lt  D So 5 5 o a 059 Do   lt    D gt  UN   co o o a a O 3  gt  On  ae   D   Nn   a A 9 2s Do 2   5     E a  wm 3 Q5 5  O E 5 Q 5 o gos 52       ES E v s   OOo  ct  Figure 4 1    Interface description    Opening Signal Input  to receive relay signal and open the turnstile    Emergency Switch  to keep the turnstile open in case there are
5. In case of emergencies    This equipment is designed to drop down arms automatically if there is power failure thus make the passage being open to the public   And there is interface in the turnstile board to connect an emergency switch which would make the tripod turnstile keep open in case of  emergencies  Note after power restoration  wait for more than 6s and then lift the arms manually     5 2 Maintenance  Forming maintenance consciousness    The tripod turnstile needs to be maintained regularly and repaired once it is damaged  It is recommended that warning signs being  placed at conspicuous positions for prompting passers by to pass in a proper way and in good order  Reasonable maintenance  consciousness helps to guarantee long term usage of the tripod turnstile     Regular maintenance    Cleaning and protection liquid dedicated for stainless steel are recommended to wipe the outer shell of the equipment regularly  The  tripod turnstile used outdoors or in an environment with lots of dust must be maintained once a year at least  Note regular maintenance    should be performed after power off the equipment     The damping accumulator is used to adjust the tripod turnstile s elasticity and return speed  You can rotate it in clockwise direction to  enhance and in anticlockwise direction to weaken the elasticity and return speed of the tripod turnstile  See figure 5 2     Figure 5 3 shows the mechanical and electrical structure of this equipment     Drop arm Optical coupli
6. PTU Toco TS1000 Series Vertical Tripod Turnstile User Manual    Security and Time Management Solutions Version  1 0 Time  2014 3       TS1000  Tripod Turnstile  TS1011  Tripod Turnstile with Controller and RFID Reader  TS1022  Tripod Turnstile with Controller and Fingerprint Reader with RFID function     Please read this document carefully before installation and using the device     1  Technical Specifications    280    500  tn                                                          086                         120    Figure 1    2  Unpacking and Testing the Tripod       2 1 Unpacking    The vertical type tripod turnstile is top heavy and unsteady  do  not remove the foam at the bottom before installation  as shown  in figure 2 1        Do not remove the foam lining at  the bottom before installation     Figure 2 1    2 2 Arm Installation Method    Installation procedure    1  Open the glue and apply in the square openings of the arms as well as the four countersunk screws  as shown in figure 2 2   This is to    prevent screws from getting loose due to vibration after being used for a long time      2  Insert the arms to the connection points  and use the Hex key to fasten the four countersunk screws on each arm  as shown in figure    2 5   nn i  s _       nn A e e Tighten the four screws on each  B  lt  A EE arm in clockwise direction   Y HF a  gt  a E  3     ay je  This Opening shall be  S   applied with glue evenly    IN  Figure 2 2 Figure 2 3    2 3 Power on Test Before 
7. Setting   Duration   Bit Setting    10s 100 40s    15s 010 50s  20s 110 60s       Note  The turnstile opening duration is set to 5s by default     4 3 2 Direction Indicator    It is to indicate whether the passage allows people to pass  The green arrow means passing is allowed while the red  X  means passing is  prohibited  The indicator status can be set through number 4 and 5 in the DIP switch  The description of the bit settings are as follows     00   One way traffic  Green indicator indicates that passing is allowed while red indicator indicates that passing is prohibited   10   One way traffic  Green indicator indicates that passing is allowed while red indicator indicates that passing is prohibited   01   Passing is allowed in both directions    4 3 3 Memory Function    With the memory function  the turnstile could remember at most 20 swipes of one card at one time and allows up to 20 visitors to pass  so they don t have to swipe card each time  this function can be enabled or disabled through number 6 in the DIP switch  The description  of the bit settings are as follows     ON  up   indicates that the memory function is enabled     OFF  down   indicates that the memory function is disabled     5  Equipment Precautions and Maintet       5 1 Precaution  1  It is recommended to purchase optional accessories to use in outdoor environment    1  It shall install optional cooling fans for the equipment if the working temperature is often above 50   C    2  It is equivalent 
8. ng Damping  blanking disc accumulator        electromagnet    NOE             Figure 5 2    6  Troubleshooting       The indicator is not lighted when the equipment is  powered on     The arms of the tripod turnstile cannot be lifted  manually after the equipment is powered on     The tripod turnstile does not open after  authentication     The passing is not smooth after the turnstile is  opened  it encounters resistance when pushing  the arms  and the arms cannot return to the home  position after they rotate     The arms drop during the use                Turnstile opening  Trilobed wheel Lock rod electromagnet                                Turnstile opening  electromagnet                                              Lock rod                                                                                                                                                                         E     6   Sy NS                   Figure 5 3 hime    It may be caused by the power supply or circuit    Check whether the connection cable and power cable between are damaged   or the wiring is loose    It may be caused by the problem of relative components or drop arm  electromagnet       Check whether the stop base and turn plate withstands each other  as shown in    figure 6 1       Check whether the drop arm electromagnet is operating  Remove the upper    cover of the framework  use a hex key to remove the cover of the control   module  as shown in figure 6 2   and check the work s
9. tatus of the  electromagnet  as shown in figure 6 3    It may be caused by lack of permission or a circuit problem       Check whether the user has the permission to open the turnstile     Use a multimeter to check whether the NO and COM ports of the access control    system has a relay signal output     3  Short circuit the ports  K1  GND  and  K2  GND   if the turnstile is successfully    opened  it would be the controller problem  In this case  please refer to  Attachment 2 to check the cable connection of the controller     It is caused by the damper   Adjust the damper  as shown in figure 5 2     It may be caused by the problem of relative components or drop arm  electromagnet       Check whether there is any gap at the position shown in figure 6 1     Check whether the drop arm electromagnet is totally closed  If not  power off    the equipment and power on it again 2 minutes later     Control module cover    Screw for securing the  control module cover       Figure 6 1 Figure 6 2    NN    N            Normal status of the drop arm Normal status  closed  of the drop arm  electromagnet after being powered off electromagnet after being powered on    Figure 6 3    Attachment 1  Default Factory Settings      6   Passing Direction Indicator   Passing is allowed  Green Arrow        Note  The Lock Driving Duration is default 5 seconds  please set to 1 second     Attachment 2  Connection Diagram Overvi               ES Opening Electromagnet  P Opening Electromagnet  cS Drop arm
10. the Installation of Device    1  Please make sure that the power requirements are strictly met to avoid permanent damage to the unit  You could change the input    voltage 110V or 220V through the DIP switch  as shown in figure 2 4    Note  The tripod turnstile must be connected to ground  earth    2  Power on and wait 30s for the tripod turnstile to finish the self check program   3  Lift the arms manually  as shown in figure 2 5   4  Check whether the tripod turnstile and the LED indicators work properly     If there is any problem  please refer to section 4 2 or kindly contact the supplier        There is a voltage AS       J  E DIP switch in the  Z  side direction of    a 220   E this power supply  i  A  O  ma      110V       S HE  3  D gt      Figure 2 4 Figure 2 5  g g    3  Equipment Installation    3 1 Installation Conditions  The equipment must be installed on concrete ground  ensuring that expansion bolts can be secured firmly     You are suggested to install an assistant framework or fence to form a passageway  as shown in figure 3 1     Spuemdn 47       100      lt 80                                                                            J  M WLI   JUB SISSY                                     a    A E  A a NS a  e 4 4 4          Figure 3 1    Note     L     When installing the tripod turnstile against the wall  please reserve at least 100 mm space in order to open the cover for adjustment  and maintenance   The space at the end of the arm shall not be greater
11. to IP54 waterproof under proper installation  However  it cannot work in the region that may suffer typhoon      3  If the temperature is  30 C  a heating plate is suggested to install  It might need multiple times to power on while getting hot  automatically through the self check program      4  The service life of this equipment may be shortened if it works outdoors in coastal areas or a region prone to acid rain     2  If the power and signal cables are connected properly  this equipment can be immersed in water of 250 mm deep  but it must not be  powered on for operating when it is immersed in water     3  Itis highly recommended that a card swiping warning line to set for prompting passers by to swipe cards properly and a reasonable  passage width shall be set to prevent passers by from squeezing in illegally     4  It is recommended that a warning sign is placed at a conspicuous position  and prompt   Please swipe your card outside the  warning line and pass in order  Thank you        The maximum tolerance of the tripod turnstile s arms    Please note that the maximum stress tolerance at the center of the arm is 80kg and at the ends of the arm is 40kg  See figure 5 1  When  the impact force on the tripod turnstile reaches the designed limit  the arms break down first to ensure that the whole equipment is not  damaged and the passer by is not injured        e     y  sz 8   l o 2 Osx      X  mo  23 2g  a    an     D3 D3    COW KW     o on  A 5  o E o G  ME Figure 5 1    
    