Home
        1747-SDN DeviceNet Scanner Module Installation Instructions
         Contents
1.                                                                                1747 SDN DeviceNet Scanner M odule 37   Numeric   Description Take this action   Code   85 Data size was incorrect for this device at e Slave device is transmitting incorrect  runtime  length data    e Verify device is not configured for  variable poll connection size   e Try replacing the device    86 Device is producing zero length data  idle state    Check device configuration and slave node status   while module is in Run M ode    87 The primary owner has not allocated the slave    Put the primary owner on line    88 The connection choices  polled  strobed  etc     Reconfigure the shared input only connection   s  between the primary connection and the shared   choice s  to be the same as  or a subset of  the  input only connection do not match  primary connection s choice s     89 Slave device initialization using Auto Device e Putthe slave device into configurable  Replacement parameters failed  mode    e Check the slave s EDS file  if the slave is  configured offline    e Check to see if the slave device has been  replaced with an incompatible device    90 User has disabled communication port  Check M odule Command Register for DISABLE bit  set    91 Bus off condition detected on comm port  Check DeviceNet connections and physical media   Module is detecting communication errors  integrity  Check system for failed slave devices or  other possible sources of network interference    92 No netw
2.                          The COP instruction below copies six words of data from an M1 data file in a  module positioned in slot four to an integer file  N1 0   This technique is used to  monitor the contents of an MO or M1 data file indirectly  in a processor data file  An  update of these six words is made for each SLC program scan              Publication 1747 INO58C EN P   M ay 2002       COP  COPY FILE   Source  M1 4 3  Dest  N10 0  Length 6    1747 SDN DeviceNet Scanner M odule 19                      Reduce Scan Time  To reduce processor scan time  use discretion when you use  instructions addressing the MO or M1 files  For example  XIC  instruction M1 2 1 1 is used in rungs 1 and 2 below  adding    approximately 2 ms to the scan time if you are using a 5 02   Series B processor   M1 2 1 B3  1       1 10  B3 M1 2 1 B3  2   J      o   2 1 14  XIC instructions in rungs 1 and 2 are addressed to the M1 data file  Each of       these instructions adds approximately 1ms to the scan time  5 02  Series B  processor     In the equivalent rungs below  XIC instruction M1 2 1 1 is used only in rung 1   reducing the scan time by approximately 1 ms           M1 2 1 B3  1 di ce      1 10  B3 B3 B3  2 jf 1 E      12 10 14                These rungs provide equivalent operation to those of the previous diagram by  substituting XIC instruction B3 10 for XIC instruction M1 2 1 1 in rung 2   Scan time is reduced by approximately 1ms  5 02 Series B processor      The first two ladder diagr
3.   where the transaction is routed     Publication 1747 IN058C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 31    e MAC ID  node address    the DeviceNet network address of the slave  device where the transaction is sent  This value can range from 0 to 63   The port and MAC ID attributes coupled together identify the target slave  device  The slave device must be listed in the scanner module   s scan list and  be online for the Explicit Message transaction to be completed successfully    e service   for each Explicit Message Request and Response  the service  attribute contains the service request and response codes that match the  corresponding request for the TXID     The following figure describes the format and mapping of transaction blocks for  request and response messages in the scanner module                                                  Format of 32 word MO Transfer File Format of 32 word M1 Transfer File  for Explicit Message Request for Explicit Message Response  1 0 15 0  Transaction TXID   cmd status   word 224 Transaction TXID   cmd status   word 224  Header     port size word 225 Header     port size word 225   3 words  service MAC ID   word 226  3 words  service   MACID   word 226  Class  Instance  Attribute  optional   Transaction   Transaction    Service Response Data  l  Service Data  word 255 word 255                      How the Processor and Scanner Module Manage Messages    File transfer operations between the processor and the scanner alway
4.  M1 files are read write files     MO and M1 files can be addressed in your ladder program and they can also be  acted upon by the module  independent of the processor scan     IMPORTANT During the processor scan  MO and M1 data can be changed  by the processor according to ladder diagram instructions    addressing the MO and M1 files  During the same scan  the  module can change MO and M1 data  independent of the rung  logic applied during the scan        Address the M 0 M 1 Files    The addressing format for MO and M1 files is as follows   Mf S w b    Where M   module   f   file  0 or 1    S  slot  1 30    w  word  0 maximum supplied by the module   b   bit  0 15     When You Cannot Use M0 M 1 Data File Addresses    You can use MO and M1 data file addresses in all instructions except the OSR  instruction and the instruction parameters below                    Instruction Parameter  characterized by file indicator     BSL File  bit array    BSR   SQ0 File  sequencer file    SQC   SQL   LFL LIFO  stack    LFU   FFL FIFO  stack    FFU          Publication 1747 INO58C EN P   May 2002    1747 SDN DeviceNet Scanner M odule 17    Monitor Bit Instructions with M 0 or M1 Addresses    When you monitor a ladder program in the Run or Test mode  the following bit  instructions  addressed to an MO or M1 file  are indicated as false regardless of their  actual true false logical state        Mf S w Mf S w M   S w Mf S w Mf S w  yk 3 E      L   U   b b b b b   XIC XIO OTE OTL OTU    To sho
5.  Shock      0 60  C  32  140  F     mn       Storage Temperature    EC 60068 2 1  Test Ab  Un packaged Non operating Cold    EC 60068 2 2  Test Bc  Un packaged Non operating Dry Heat    EC 60068 2 14  Test Na  Un packaged Non operating Thermal Shock        40 to 85  C    40 to 185  F           Relative Humidity       EC 60068 2 30  Test Db  Un packaged Non operating  Damp Heat    5  95  non condensing                            Vibration EC60068 2 6  Test Fc  Operating    2g   10 500Hz  Shock EC60068 2 27 1987  Test Ea  Unpackaged shock  ES 002   Operating   30g  Non operating   50g  Emissions CISPR 11   Group 1  Class A  with appropriate enclosure   ESD Immunity EC 61000 4 2   4KkV contact discharges  Radiated RF Immunity EC 61000 4 3   10V m with 1kHz sine wave 80  AM from 30M Hz to 1000M hz  EFT B Immunity EC 61000 4 4    2KV at 5kHz on communications ports  Surge Transient Immunity EC 61000 4 5      2KV line earth CM    on signal ports                   Conducted RF Immunity EC 61000 4 6   10Vrms with 1kHz sine wave 80 AM from 150kHz  0 30M Hz  Enclosure Type Rating None  open style   Wiring    Type 1771 CD    Category  2  10 pin Linear Plug    Torque 5 7 pound inches      Catalog Number       1787 PLUG10R       Specifications continued on back page    Publication 1747 INO58C EN P   M ay 2002       Specifications   Continued       Certifications UL UL Listed Industrial Control Equipment   when product is marked  CSA CSA Certified Process Control Equipment  CSA CSA Certifi
6.  device on the network  The bits are  assigned in consecutive order to consecutive device addresses starting with node 0  at M1 S 220 0  If the bit is set  the corresponding node has failed to verify     Publication 1747 INO58C EN P   May 2002    24  1747 SDN DeviceNet Scanner Module    Explicit Message Program Control    Words 224 through 255 are used for Explicit Message Program Control  Use this  feature to configure device parameters on your DeviceNet network via the MO and  M1 files in the SLC processor that is controlling these devices  This feature is  described in detail on page 27     Download Output Data to the Module    The SIC 500 processor writes output data to the module using two methods   e output image table  e MO file transfer    Output Image Table    The output image table is a 32 word table for the module slot that is updated from  the processor with each program scan  The first word  word 0  of this table is  reserved for the module command register  The remaining 31 words can be used to  transfer data from the SLC output table to the DeviceNet nodes     Module Command Register    The module command register is located at word 0 in the output image area for the  slot  To execute a command  set the appropriate bits in the module command word  using SLC ladder instructions     Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 25       The following table describes the functionality of the command register bits           Command 
7.  essage is now available to be  Response available in M1 read interpreted by the ladder program   file   0  Empty  SLC M1 File    The SLC M1 file is a 256 word file that can be used to transfer a large quantity of  information to the module with a single SLC instruction        IM PORTANT Transferring data using this file takes more time than using the  input image table        The first 150 words are used for data transfer from the module  The remaining 106  words are reserved for    e device active table   e node status   e scan counter   e device idle table   e device failure table   e auto verify table   e explicit message program control  For a details on the mapping of input and output image tables  refer to page 13     Device Active Table    Words 206 through 209 in the M1 file are used for the Device Active Table  The  scanner assigns one bit in consecutive order to consecutive device addresses  starting at node 0 at M1 S 206 0  If a bit is set  it indicates that the node is in the  scanner   s scan list and has successfully communicated with the scanner module   The bit is reset if the scanner tries to communicate to the node but the node has  gone offline     Publication 1747 IN058C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 23    Node Address Status Indicator    Word 210 is used for node address and scanner diagnostic information displayed in  numeric codes  The high byte is the node address and the low byte is the status for  that node  These codes and 
8.  is a multicast transfer of data  64 bits in length  sent by the  scanner module that solicits a response from each strobed slave device  There is  one bit for each of the possible 64 node addresses  The devices respond with their  data  which can be as much as 8 bytes     Change of State    Change of state enables the scanner module to perform a scan     e whenever a network data change occurs  or  e at a user configurable heartbeat rate    Because data is only sent on an as needed basis  this feature increases system  performance by reducing network traffic     Publication 1747 INO58C EN P   May 2002    6  1747 SDN DeviceNet Scanner Module    Cyclic 1 0  Cyclic I O allows you to instruct the scanner module to perform a scan at a specific  send rate     Because data is only sent at a periodic rate  this feature increases system  performance by reducing network traffic     Pass Through    The SLC 500       pass through    feature allows communication with the DeviceNet  network from another network  This feature can be used to adjust and fine tune the  nodes on your network    The pass through feature is not intended to replace a 1770 KFD  PCD  PCID  or  PCIDS connection to the network     System Requirements for Pass Through    To use the pass through feature you must meet the following hardware  software  and firmware requirements                 Component Requirement Requirement   SLC 500 processor SLC 5 03 or higher SLC 5 03 or higher  1747 SDN firmware 4 015   5 001 6 00
9.  the  responses to the requests using the TXID field     Processor Scanner Module DeviceNet Network                   MO file transfer          Request Request Scanner  Transaction Se Transaction   Request  Block Blocks Queue                   Le ne DeviceNet i  are   Process Request  Explicit Message Meee  Land Responses _  Requests and   Device      y nl ea          Done or  Error detached          Response Response   Scanner  Transaction Transaction   Response  Block  lt   Blocks Queue                   M1 file transfer                                  Explicit Message Program Control Limitations    e The processor is always the DeviceNet client and the slave is always the  DeviceNet server    e A maximum of ten Explicit Message Request Transaction Blocks with the  execute command can be queued to the scanner module at any time  For  example  ten MO file transfers containing one transactions each  can be  queued at any time  The scanner module receives and deletes any additional  client server requests with the execute command over the maximum of ten     As transactions are removed from the queue and response transaction blocks are  returned to the processor  additional transaction blocks can be issued in their place   as long as the total does not exceed ten   e The scanner module supports one transaction block per upload and  download   e Request Transaction Blocks can only be queued for slave devices of the  scanner module and must appear in the scanner module   s scan 
10. 0 223 Auto Verify Failure Table   4 words   224 255 Explicit Message Program Control  32   224 255 Explicit M essage Program Control  words   32 words   256 394 Pass Through  139 words  256 394 Pass Through  139 words                 Use RSLogix 500 Softw are to Configure M0 M1 Files    To enable pass through capability of the scanner module  you must configure the  MO and M1 files associated with the 1747 SDN module to 395 words  If you do not    want to use pass through  configure the files to the default length of 256 words     ATTENTION       The pass through feature is not intended to replace a  1770 KFD  PCD  PCID  or PCIDS connection to the network     e Pass through is intended only for fine tuning and  adjustment of your network devices  Do not attempt to  configure your entire network using a pass through    driver or a time out may occur     e The pass through method is not suitable for real time  monitoring of your network devices        Publication 1747 INO58C EN P   May 2002    14  1747 SDN DeviceNet Scanner Module       Use the following procedure to configure the 1747 SDN   s MO and M1 files using  RSLogix 500 software     1  Run RSLogix 500 and go offline to the SLC 500 processor        Project  H  Help    Controller    i Controller Properties  Processor Status          i Jul 10 Configuration  BE Channel Configuration       2  Under the Controller folder in the Project window  double click on  IO Configuration     The I O Configuration window will open   170 
11. 1 or higher   RSLinx software 2 10 or higher 2 31 or higher   M 0 and M1 files Configured for 361 words Configured for 395 words       Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner Module 7    External Module Features  Use this illustration to identify the external features of the scanner module              DeviceNet  STATUS    M odule Status Indicator MODULE NET Network Status Indicator  indicates module status      indicates status of DeviceNet                   channel communication link  Node address and status  displays numeric codes    and indicates scanner ADDRESS ERROR    node address or error                    lt  Access door          Wiring color codes                                                                                                                                                             O O  O O  10 pin linear plug t       o O  inserted into DeviceN et O  O  port  O O                                                    Front of module    Publication 1747 INO58C EN P   M ay 2002    8  1747 SDN DeviceNet Scanner Module    Hardware and Softw are Requirements    Before you install your module you need the following items   e personal computer with Microsoft Windows    95 or later operating system  e RSNetWorx for DeviceNet software  version 2 22 or later  e RSLogix 500 software  e SLC 1746 chassis with SLC 5 02  5 03  5 04 or 5 05 processor    For network communication  you have two options     e use the pass through feature 
12. 47 6 5 5  Performing the ControlFlash Update oe Firmware Upgrade Kit User 1756 6 5 6  RSLogix 500    software Getting Results with RSLogix 500 9399 RL50GR  RSLinx    software Getting Results with RSLinx 9399 WAB32GR  Connecting the DeviceNet network DeviceNet Cable Planning and Installation   ny    7 2       Manual          Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner Module 5    Module Features    Slave Mode  Slave mode allows processor to processor communication and enables the scanner  to perform as a slave device to another master on the network     When the scanner module is in slave mode  it exchanges data with only one master   You control what information is exchanged through scan list configuration and  associated mapping functions of RSNetWorx for DeviceNet software     This feature has the following variations                       When the scanner module is in  the scanner    Null mode Contains an empty or disabled scan list  default   Serves as a master to one or more slaves but is not   M aster mode simultaneously serving as a slave to another  master   Slave mode Serves as a Slave to another master   Dual mode Serves as both a master to one or more slaves and  as a slave to another master simultaneously   Poll    A poll message is a point to point transfer of data  0 255 bytes  sent by the scanner  module that solicits a response from a single device  The device responds with its  input data  0 255 bytes      Strobe    A strobe message
13. AB Installation Instructions    ur    1747 SDN  DeviceNet Scanner Module    Cat  No  1747 SDN B                                                                                  Contents  Use this document as a guide to install the 1747 SDN B scanner module   For this information See page  portant User Information 1  Prevent Electrostatic Discharge 3  Where to Find M ore Information 4  odule Features 5  External M odule Features 7  Hardware and Software Requirements 8  stall the Scanner M odule Into the Chassis 9  Connect the Scanner M odule to the DeviceNet    Network 10  Apply Chassis Power 12  Understand the Data Organization of the Scanner M odule 12  Program the Scanner M odule Using the M 0 and M 1 Files 16  Upload Input Data from the Scanner M odule 20  Download Output Data from the Scanner M odule 24  Explicit M essage Program Control 27  Troubleshoot the M odule and Network 35  For this reference information See page  Specifications 39             Publication 1747 INO58C EN P   M ay 2002    2 1747 SDN DeviceNet Scanner Module       Important User Information    Because of the variety of uses for the products described in this publication  those  responsible for the application and use of these products must satisfy themselves that all  necessary steps have been taken to assure that each application and use meets all  performance and safety requirements  including any applicable laws  regulations  codes  and standards     In no event will Allen Bradley be responsible o
14. Configuration      x        m Current Cards Available   1 A Slot Rack Filter   All 10 Ra   2 fizo Rack Not Installed  gt   RG  Config  1 746 1 8 Any 8pt Discrete Input Module   3  I0 RackNotinstaled 7  1746116 Any 16pt Discrete Input Module   1746 132 Any 32pt Discrete Input Module  Eoas 1746 08 Any 8pt Discrete Output Module   1 746 016 Any 16pt Discrete Output Module   1 746 0 32 Any 32pt Discrete Output Module   AMCI 153x AMCI Series 1500 Resolver Module   AMCI 1561 AMCI Series 1561 Resolver Module   1746 BAS 5 01 BASIC Module   500   5 01   1 746 BAS 5 02 BASIC Module   M0 M1 capable   1 747 DCM 1 4 Node Adapter Module  1 4 Rack    1 747 DCM 1 2 Node Adapter Module  1 2 Rack    1 747 DCM 3 4 Node Adapter Module  3 4 Rack    1 747 DCM FULLNode Adapter Module  Full Rack    1747 DSN 7 Distributed 1 0 Scanner   1 0 Block   1747 DSN 30 Distributed 1 0 Scanner 30 1 0 Block   1 746 FI0 41 Fast Analog 2 Ch In 2 Ch Current Out   1 746 F104Y Fast Analog 2 Ch In 2 Ch Volt  Out   1746 HS Single Axis Motion Control   1 746 HSCE High Speed Counter Module    Lycra   Help   Hide All Cards   1 746 HSRY Motion Control Module x     3  Click on the Read I O Config  button to upload the I O configuration from  the processor              i  Pott  Dao  0 1747 L5424 5 04 CPU   24K Mem  05400  1       2 1747 SDN DeviceNet Scanner Module  3             4  Double click on the 1747 SDN module     Publication 1747 INO58C EN P   May 2002    1747 SDN DeviceNet Scanner M odule 15    The Advanced I O Con
15. DeviceNet channel is disabled for communication  No communication may  occur over this channel  Outputs on the network are not under program control   If scanner was in Run mode  devices will go to their fault state    5   Reserved    6 1  halt scanner Halt Scanner  All scanner operations stop when this command is issued  No communications  occur over either DeviceNet port  No M  file or discrete I O mapping occurs   Outputs on the network are not under program control  If scanner was in Run  mode  devices will go to their fault state    7 1  reboot Reboot  This command causes the scanner to reset as though power had been cycled   When this command is issued  all scanner communication stops for the duration of  the scanners initialization sequence  Outputs on the network are no longer under  program control  If scanner was in Run mode  devices will go to their fault state    8 15   Reserved        1 All reserve bits must be set to zero or improper operation may result        Publication 1747 INO58C EN P   May 2002    26  1747 SDN DeviceNet Scanner Module    Restore Factory Default Settings Flush Memory    To restore the scanner module   s factory default settings  follow these procedures     1  While the SLC processor in Program mode  clear the module command word  0 and set bit 2 of word 0 for the scanner module to    ON    or 1  starting with    bit 0 going from right to left  this is the third bit      IMPORTANT If other bits in the module command word are set  then the  s
16. Transaction completed successfully  2 Transaction in progress  not ready   3 Error   slave not in scan list  4 Error   slave offline  5 Error   DeviceNet port disabled  offline  6 Error   transaction TXID unknown  7 Error   slave not responding to explicit request  8 Error   Invalid command code  9 Error   Scanner out of buffers  10 Error   Other Client server transaction in progress  11 Error   could not connect to slave device  12 Error   response data too large for block  13 Error   invalid port  14 Error   invalid size specified  15 Error   connection busy   16 255 Reserved          e TXID  transaction ID    when you create and download a request to the  scanner  the processor s ladder logic program assigns a TXID to the  transaction  This is a one byte integer in the range of 1 to 255  The scanner  uses this value to track the transaction to completion  and retums the value  with the response that matches the request downloaded by the processor   The ladder logic program monitors rollover and usage of TXID values     Transaction  Header   3 words     15    0          TXID    cmd status       port    size       service       MAC ID       Transaction Body   29 words              word 224  word 225  word 226    word 255    One word   two bytes   16 bits    e size   the size of the transaction body in bytes  The transaction body can be  as many as 29 words  58 bytes  in length  If the size exceeds 29 words  an  error code will be returned     e port  the DeviceNet port  zero
17. Word 0 5 0 Operating Mode Description  Bit   Operating Mode  0 1  Run mode  0   Idle Run    mode    The scanner module maps output data from its scanner output table  M 0  and  discrete outputs to each device on the network  Inputs are received and mapped  into the scanner input table  M 1  and discrete inputs  Outputs on the network are  under SLC program control     Idle   The scanner does not map output data to the devices  but keeps network  connections to devices open so device failures can be detected  Input data is  returned from devices  and mapped into the scanner input table  M 1  and the  discrete inputs  Outputs on the network are not under program control and will be  in their configured    idle state     The scanner is put into this mode to perform online  configuration of the scanner database tables                                   1 1  fault network Fault Network rec  The scanner stops communicating with devices on the network  No outputs or  inputs are mapped  Outputs on the network are not under program control   If scanner was in Run mode  devices will go to their fault state    2 1  restore to factory Restore to Factory Defaults Flush Memory   defaults flush memory The scanner may receive a scan list or configuration that causes inappropriate   scanner behavior  It may be necessary to restore to the scanner module s factory  defaults to recover from this state  This procedure is described below    3 Reserved    4 1  disable netw ork Disable Netw ork  The 
18. affic from other modules detected on the   Check the network configuration   Scanlist may be   network  empty     76 No direct network traffic for module detected    None  The module hears other network  communication    77 Data size expected by the device does not match  Reconfigure your module for the correct transmit   scan list entry  and receive data sizes    78 Slave device in scan list table does not exist    Add the device to the network  or delete the scan  list entry for that device    79 odule has failed to transmit a message  Make sure that your module is connected to a valid  network    Check for disconnected cables    80 odule is in Idle mode  Put controller in Run mode  Enable Run bit in  module command register    81 odule is in FAULT mode  Check M odule Command Register for fault bit set    82 Error detected in sequence of fragmented 1 0   Check scan list table entry for slave device to make   essages from device  sure that input and output data lengths are correct   Check slave device configuration   83 Slave device is returning error responses when   Check accuracy of scan list table entry  Check  odule attempts to communicate with it  slave device configuration  Slave device may be in  another master   s scan list  Reboot slave device   84 odule is initializing the DeviceNet network    None  This code clears itself once module                      attempts to initialize all slave devices on the  network        Publication 1747 INO58C EN P   M ay 2002      
19. ailure is detected  you can put the communication into the Idle  mode  so that all output devices go to a safe state     The SLC program can monitor the bits in the module status register and set the  appropriate bits of the module command register to automatically control the  operating mode of the module should a device failure occur     Status Word I s 0       Operating Mode Description                                     Bit   Operating Mode  0 1  Run mode  0  Idle mode   Run   echoed from the module The scanner module maps output data from its scanner output table  M 0  and  command register  discrete outputs to each device on the network  Inputs are received and mapped  into the scanner input table  M 1  and discrete inputs  Outputs on the network are  under SLC program control   Idle  The scanner does not map output data to the devices  but keeps network  connections to devices open so device failures can be detected  Input data is  returned from devices  and mapped into the scanner input table  M 1  and the  discrete inputs  Outputs on the network are not under program control and will be  in their configured    Idle state     The scanner must be put into this mode to perform  offline configuration of the scanner database tables   I 1  fault netw ork  echoed Fault Netw ork  from the module command The scanner has stopped communicating with devices on the network  No outputs  register  or inputs are mapped  Outputs on the network are not under program control   If scan
20. amage  or  economic loss     Identifies information about practices or circumstances that can  ATTENTION lead to personal injury or death  property damage  or    economic loss                    Identifies information that is critical for successful application  IMPORTANT  and understanding of the product        Publication 1747 IN058C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 3          ATTENTION Environment and Enclosure    This equipment is intended for use in a Pollution Degree 2  industrial environment  in overvoltage Category II applications  as  defined in IEC publication 60664 1   at altitudes up to 2000 meters  without derating     This equipment is considered Group 1  Class A industrial  equipment according to IEC CISPR Publication 11  Without  appropriate precautions  there may be potential difficulties  ensuring electromagnetic compatibility in other environments due  to conducted as well as radiated disturbance     This equipment is supplied as  open type  equipment  It must be  mounted within an enclosure that is suitably designed for those  specific environmental conditions that will be present and  appropriately designed to prevent personal injury resulting from  accessibility to live parts  The interior of the enclosure must be  accessible only by the use of a tool  Subsequent sections of this  publication may contain additional information regarding specific  enclosure type ratings that are required to comply with certain  product safety certifi
21. ams in the last section illustrate a technique you use to  capture and use MO or M1 data as it exists at a specific time  In the first diagram  bit  M1 2 1 1 could change state between rungs 1 and 2  This could interfere with the  logic applied in rung 2  The second diagram avoids the problem  If rung 1 is true   bit B3 10 captures this information and places it in rung 2     The following diagram illustrates another economizing technique  The COP  instruction addresses an M1 file  adding approximately 4 29 ms to the scan time if  you are using a 5 02  Series B processor  You can save scan time by making this  rung true only periodically  For example  you can use a clock bit S 4 8  clock bits  are discussed in the programming manual      Publication 1747 INO58C EN P   May 2002    20  1747 SDN DeviceNet Scanner Module    A rung such as this might be used when you want to monitor the contents of the  M1 file  but monitoring need not be continuous           S 4 Bll COP    OSR  COPY FILE  S 4 8 causes the M1 4 3 file 8 0 Source  M1 4 3  to update the N10 0 file rah ae  every 2 56 seconds              In this example  a COP instruction can be used to monitor the contents of an M1  file  When the instruction goes true  the six words of data in file  M1 4 3 is captured  as it exists at that time and placed in file  N10 0  All subsequent logic should  address the data in  N10 0  The data will be consistent and it shortens scan time by  eliminating reads to the module each time an MO 
22. ata Attribute data was not saved prior to this request   19H Store operation failure Attribute data was not successfully saved   1FH Vendor specific error Second byte may offer details   refer to vendor  documentation   20H Invalid parameter Parameter associated with request is invalid   DOH Reserved and service specific Used only when none of the standard error codes   CFFH   errors supplemented by the second byte accurately describes   the problem        Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule    35       Troubleshoot the Module and Network    The bicolor  green red  module status indicator  MODULE  located on the front of  your module displays module status  It indicates whether the module has power    and is functioning properly     Module Status Troubleshooting             If the MODULE Then  Take this action    indicator is    Off There is no power applied to the module    Verify power connections and apply power   Green The module is operating normally  No action required        Flashing Green    The module is not configured     Configure the module        Flashing Red    There is an invalid configuration     Check configuration setup        Red       The module has an unrecoverable fault        Replace the module        The DeviceNet channel has a bicolor  green red  network status indicator  NET    The following table provides troubleshooting information about the DeviceNet    channel communication link     DeviceNet Channel Com
23. canner module will generate an error     2  Set bit 0 of word 0 for the scanner module to    OFF    or 0     3  On the SLC processor  cycle the keyswitch from Program mode to Run mode  then back to Program mode        IM PORTANT The ladder logic may set bit 0 of word 0 for the scanner  module  If this happens  then you must disable or delete this    rung from the ladder program        4  When the code F9 is displayed on the Address  Error LED display the default  settings have been restored     5  Set bit 2 of word 0 for the scanner module to    OFF    or 0     6  Cycle power to the 1746 chassis to restore normal operation to the scanner  module     The scanner module will now have its factory default settings     node 63     125 K baud     no scanlist    Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 27    SLC MO File    The SIC MO file is a 256 word file that can be used to transfer a large quantity of  information to the module with a single SLC instruction  Transferring data using this  file can take several scans and more time than using the output image table    The first 150 words are used for sending data to DeviceNet nodes  The next 74  words are reserved for future use  the next 32 words are used for explicit message  program control and the final 139 words are used for pass through     For a detailed description of the mapping of input and output image tables  refer to  page 13     Using Explicit Message Program Control    Use the Ex
24. cations     See NEMA Standards publication 250 and IEC publication 60529   as applicable  for explanations of the degrees of protection  provided by different types of enclosure  Also  see the appropriate  sections in this publication  as well as the Allen Bradley  publication 1770 4 1   Industrial Automation Wiring and  Grounding Guidelines    for additional installation requirements  pertaining to this equipment          Prevent Electrostatic Discharge    This equipment is sensitive to electrostatic discharge which can  cause internal damage and affect normal operation  Follow these  guidelines when you handle this equipment    e touch a grounded object to discharge potential static   e wear an approved grounding wrist strap   e do not touch connectors or pins on component boards   e do not touch circuit components inside the equipment   e if available  use a static safe workstation   e when not in use  store the equipment in appropriate  static safe packaging             Publication 1747 INO58C EN P   May 2002    4 1747 SDN DeviceNet Scanner Module       Where to Find More Information    The following table describes related documentation  To order a copy or to view or  download an online version  visit The Automation Bookstore at     www theautomationbookstore com    For information about     See this document     Publication number        Configuring the scanner module and    SLC 500    DeviceNet Scanner M odule                eatin hardware in an example User M anual 17
25. e can accommodate one request or response for each  transaction block  You must format each transaction block as shown in the  following figure              15 0  TXID cmd status word 224  Transaction  Header port size word 225   3 words  service MAC ID word 226             Transaction Body   29 words              word 255  One word   two bytes   16 bits    The transaction block is divided into two parts   e transaction header   contains information that identifies the transaction to  the scanner and processor  e transaction body   in a request  this contains the DeviceNet Class   Instance  Attribute and Service Data portion of the transaction  In a response   this contains only the response message   Each of the data attributes in the transaction header are one byte in length     e command  status   for each download  you assign a command code to  instruct the scanner how to administer the request                       Command Code   Description  0 Ignore transaction block  block empty   1 Execute this transaction block  2 Get status of transaction TXID  3 Reset all client server transactions  4 Delete transaction from response queue  5 255 Reserved          Publication 1747 INO58C EN P   May 2002    30  1747 SDN DeviceNet Scanner Module       For each upload  the status code provides the processor with status on the device  and its response                                                                 Status Code   Description  0 Ignore transaction block  block empty   1 
26. ed Process Control Equipment for Class     Division 2 Group A B C D Hazardous Locations  ce  European Union 89 336 EEC EM C Directive  compliant  with     EN 50081 2  Industrial Emissions   EN 50082 2  Industrial Immunity   European Union 73 23 EEC LVD Directive  compliant   with    EN 61131 2  Programmable Controllers   C Tick3 Australian Radiocommunications Act  compliant with   AS NZS 2064  Industrial Emissions   ODVA ODVA conformance tested to ODVA DeviceNet  specifications             User M anual 1747  6 5 5         To remain compliant with UL CSA certification  the DeviceNet power supply must meet NEC Class 2  requirements     2Use this conductor category information for planning conductor routing as described in publication 1770 4 1    Industrial Automation Wiring and Grounding Guidelines    3See the Product Certification link at www ab com for Declarations of Conformity  Certificates  and other  certification details           DeviceNet is a trademark of the Open DeviceNet Vendors Association     SLC  SLC 500  SLC 5 02  SLC 5 03  SLC 5 04  SLC 5 05  RSLinx  RSLogix 500 and RSNetW orx are trademarks of Rockwell  Automation  Inc     Windows is a trademark of Microsoft Corporation     www rockwellautomation com    Corporate Headquarters  Rockwell Automation  777 East Wisconsin Avenue  Suite 1400  Milwaukee  WI  53202 5302 USA  Tel   1  414 212 5200  Fax   1  414 212 5201    Headquarters for Allen Bradley Products  Rockwell Software Products and Global Manufacturing Solu
27. equest issued  there is a response                                                        DeviceNet                        5       drop line   FE 200  am     w 7 1203 GKS 1305 AC  Slave s Explicit Communication Drive    Request Adapter    1  Format an MO file transfer in the processor to send an Explicit Message  Request to the scanner module  download      2  The scanner module transmits the Explicit Message Request to the slave    device over the DeviceNet network     3  The slave device transmits the Explicit Message Response back to the  scanner and is queued into a file transfer buffer     4  The processor uses an M1 file transfer to retrieve the Explicit Message  Response from the scanner   s buffer  upload      5  Format an MO file transfer with a Delete Response Command and the current  transaction ID read in step 4  The transaction IDs are deleted and can be    reused     The scanner module requires a precisely formatted MO and M1 file transfer size of  32 words including words 224 255  The scanner module uses the file memory    content as a client server request     Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 29    How to Format the Explicit Message Transaction Block    Up to ten 32 word transaction blocks may be queued within the scanner module  for Explicit Message Program Control  The transaction blocks accommodate both  the download of Explicit Message Requests and the upload of Explicit Message  Responses     The scanner modul
28. figuration window will open        ATE  F 1727 500 Oayeihiei 5 carr Mods   t      Hassan Iras Aone    SE          Mipamumn Output sors    Sema                _               Seanad brp teach je  Scanned Output Words   a  bem See Routes SALE ln  MO Length   335  Wi Length  Frs  BE Fie Length lt Eda G Daia         5  Set the MO Length and the M1 Length to one of the following   a  256 for 1747 SDN firmware prior to 4 015 for no pass through support  b  361 for 1747 SDN firmware 4 015 5 001 for pass through support  c  395 for 1747 SDN firmware 6 001 or higher for improved pass through  support    6  Click on the OK button     7  Download the changes to the processor     IM PORTANT The SLC 500 must be placed in Run mode at least one time after  downloading the M0 Miconfiguration to enable 1747 SDN    pass through transactions     For more information on how to     e configure your module for DeviceNet operation  e map data from DeviceNet nodes to M1  MO  input and output image files     refer to the Getting Results with RSLogix 500  publication number    9939 RL50GR  and the 1747 SDN Scanner User Manual  publication number  1747 6 5 5      Publication 1747 INO58C EN P   May 2002    16  1747 SDN DeviceNet Scanner Module    Program the Module Using the SLC M0 and M1Files    The M0 and M1 files are data files that reside in the module  There is no image for  these files in the processor memory  The MO file is a module output file and the M1  file is a module input file  Both MO and
29. list     Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 33       e If a slave device is not communicating at the time the scanner module  processes its Request Transaction Block  the scanner module will return an    error status for that transaction     e Check documentation of destination device for specifics concerning services  supported and Class Instance Attribute information  At a minimum  the  scanner module supports the following DeviceNet services in Request  Transaction Blocks                 Service Name  Service Code  Example    Get_Attribute_Single OE hex Upload a single parameter value from a  device   Set_Attribute_Single 10 hex Download a single parameter value to a  device   Get_Attribute_All 01 hex Upload all parameter values from a device   Set_Attribute_All 02 hex Download all parameter values to a device             e All transaction blocks are processed  therefore  an unused transaction block  must be left blank     e Client Server commands and requests with transaction IDs that are in use are    ignored by the scanner module     e Ifa slave device retums a DeviceNet error in response to the request  downloaded from the processor  the scanner recognizes the error as a  successful transaction  status code  1      Publication 1747 INO58C EN P   May 2002    34  1747 SDN DeviceNet Scanner Module       A failure to respond to the request within the number of retries or timeout period  specified for the Explicit Message Connecti
30. munications Troubleshooting                         Ifthe NET  Then Which indicates Take this action   indicator   is    Off The device has no power or the The channel is disabled   Power up the module  provide network power to  channel is disabled for communication   for DeviceNet the channel  and be sure the channel is enabled  due to bus off condition  loss of communication  in both the module configuration table and the  network power  or has been module command word   intentionally disabled    Green Normal operation  All slave devices in the   None    scan list table are  communicating  normally with the  module    Flashing he two digit numeric display for the   The channel is enabled   Configure the scan list table for the channel to   Green channel indicates an error code that   but no communication   add devices   provides more information about the   is occurring   condition of the channel    Flashing he two digit numeric display for the   At least one of the Examine the failed device and the scan list table   Red channel displays an error code that slave devices in the for accuracy   provides more information about the   modules scan list table  condition of the channel  has failed to   communicate with the  module    Red he communications channel has The module may be Reset module  If failures continue  replace  ailed  The two digit numeric display   defective  module        orthe channel displays an error code  hat provides more information about  he condition of 
31. ner was in Run mode  devices will go to their fault state   2 Reserved  3 Reserved  4 1  disable network  echoed   Disable Netw ork  from the module command The DeviceNet channel is disabled for communication  No communication may  register  occur over this channel  Outputs on the network are not under program control   If scanner was in Run mode  devices will go to their fault state   5 Reserved  6 1  device failure  at least Device Failure  one device failed  One or more of the devices in the scanners scan list has failed to communicate  with the scanner   7 Reserved  8 1  autoverify failure  at Autoverify Failure  least one device has failed One or more of the devices in the scanner s scan list is returning an incorrect  auto verify  number of bytes of data in response to a connection establishment  according to  the information stored in the scanner s scan list   9 Reserved  10   1  communication failure Communications Failure          There is no communication on the port        Publication 1747 INO58C EN P   May 2002    22 1747 SDN DeviceNet Scanner Module    Status Word l s 0 Operating Mode Description       Bit   Operating Mode       11   Reserved       12   1  duplicate node address   Duplicate Node Address Failure  failure There is another node with the same address as the scanner on the network        13   Reserved       14   Reserved                15   1  Explicit Message Explicit Message Program Control  Program Control A response to a previously sent Explicit M
32. ombinations of equipment in your system are  subject to investigation by the local Authority Having  Jurisdiction at the time of installation           Informations sur l   utilisation de cet   quipement  en environnements dangereux      Les produits marqu  s  CLI  DIV 2  GP A  B  C  D  ne  conviennent qu    une utilisation en environnements  de Classe   Division 2 Groupes A  B  C  D dangereux  et non dangereux  Chaque produit est livr   avec des  marquages sur sa plaque d identification qui  indiquent le code de temp  rature pour les  environnements dangereux  Lorsque plusieurs  produits sont combin  s dans un syst  me  le code de  temp  rature le plus d  favorable  code de  temp  rature le plus faible  peut   tre utilis   pour  d  terminer le code de temp  rature global du  syst  me  Les combinaisons d   quipements dans le  syst  me sont sujettes    inspection par les autorit  s  locales qualifi  es au moment de l installation              EXPLOSION HAZARD    e Do not disconnect  equipment unless  power has been  removed or the area is  known to be  nonhazardous     e Do not disconnect  connections to this  equipment unless  power has been  removed or the area is  known to be  nonhazardous  Secure   y external   connections that mate   to this equipment by  using screws  sliding  latches  threaded  connectors  or other  means provided with  this product     e Substitution of  components may impair  suitability for Class     Division 2    e If this product contains  batterie
33. on is recognized by the scanner module  as an error  The error code is returned in the status attribute of the transaction  header     Explicit Messaging Error Codes   Error codes have two bytes of data  The first byte is a General Error Code and the  second is an optional Additional Code Field that may contain additional information  about the error  If this field is unused  the value OFFH is shown  The following table  describes explicit messaging error codes                                                                                            Numeric Name  Description    Code    02H Resource unavailable A needed resource was not available   08H Service unsupported Service is not defined or implemented for this  class instance   09H Invalid attribute value Data is invalid for the specified attribute   OBH Already in requested state Object is in the requested state   redundant request   OCH Object state conflict Not allowed with object in present state   OEH Attribute cannot be set Read only attribute   OFH Privilege violation A permission  privilege check failed   10H Device state conflict Not allowed with device in present state   11H Reply too big Reply larger than buffer allocated when connection  was established   13H Too little data Request included insufficient data   14H Attribute not supported Attribute number is incorrect   15H Too much data Request included extra data   16H Object does not exist Class instance numbers are incorrect   18H No stored attribute d
34. or M1 address is encountered in  the program     Upload Input Data from the Module to the SLC Processor    The SLC 500 processor reads input data from the module using two methods   e input image table  e M1 file transfer    Input Image Table    The input image table is a 32 word table for the module slot that is updated by the  processor with each program scan  The first word  word 0  is reserved for the  module status register  The remaining 31 words can be used to transfer DeviceNet  input data to the SLC input image table  The addressing format is     I S w b  Where S   slot    w  word  0 31   b   bit  0 15     Module Status Register    The module status register is located at word 0 in the input image area for the slot   Bits 0 5 echo back to the processor  the current state of bits 0 5 of the module  command register  The echoes verify that the commands were executed  The  module sets the remaining bits when it detects a problem  The bits latch in the ON  state until the problem clears  Bits 6 and 8 indicate that you should read the device  failure table for more specific information about which devices failed     Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 21       You can use bit 6 to keep the communication port in the Idle mode until the bit  clears  When the bit clears  this indicates that all devices in the scanner   s scan list  are up and available  When the devices are available  you can put the port in Run  mode  If a device f
35. ork power detected on communication   Provide network power  M ake sure that module  port  drop cable is providing netw ork power to module   comm port    95 Application FLASH update in progress  None  Do not disconnect the module while  application FLASH is in progress  You will lose any  existing data in the modules memory    97 odule operation halted by user command  Check M odule Command Register for HALT bit set    98 Unrecoverable firmware failure  Service or replace your module    99 Unrecoverable hardware failure  Service or replace your module    E2 RAM Test Failure Service or replace your module    E4 Lost power during FLASH upgrade Service or replace your module    E5 No boot or main code Service or replace your module    E9 odule memory has been flushed for factory   Cycle module power to recover              default settings           Publication 1747 INO58C EN P   May 2002    38  1747 SDN DeviceNet Scanner Module       The follow ing information applies when  operating this equipment in hazardous  locations     Products marked  CL I  DIV 2  GP A  B  C  D    are  suitable for use in Class   Division 2 Groups A B C   D  Hazardous Locations and nonhazardous locations  only  Each product is supplied with markings on the  rating nameplate indicating the hazardous location  temperature code  W hen combining products within  a system  the most adverse temperature code  lowest     T    number  may be used to help determine the  overall temperature code of the system   C
36. plicit Message Program Control feature to configure device parameters  on your DeviceNet network via the MO and M1 files     Use the Explicit Message Program Control feature to   e transmit configuration data from your scanner module to its slave devices on  your DeviceNet network  e receive status and diagnostics from these devices on your DeviceNet  network    e make runtime adjustments to device parameters according to changing  conditions detected by your processor    Publication 1747 INO58C EN P   May 2002    28  1747 SDN DeviceNet Scanner Module       How the Explicit Message Program Control Feature Works          MO file transfer  including words 224 255    sent from processor to scanner module               M1 file transfer  including words 224 255    sent from scanner module to processor                                                                                                                 LA  M1 file transfer  is completed  TXIDs A ps  are deleted and can a Masters Explicit aa   be reused      Request   4  ON PO RE Le A    DeviceNet trunk line Loreena      Explicit Message   A message used to transmit  commands  data  requests for data or responses   The message is sent from a client on the DeviceNet  network to a server on that network     Request   An explicit message sent by a client  to a server requesting the server to perform  a function     Response   An explicit message sent by a server to  a client in response to the client   s request  For every  r
37. r liable for indirect or consequential  damage resulting from the use or application of these products     Any illustrations  charts  sample programs  and layout examples shown in this  publication are intended solely for purposes of example  Since there are many variables  and requirements associated with any particular installation  Allen Bradley does not  assume responsibility or liability  to include intellectual property liability  for actual use  based upon the examples shown in this publication     Allen Bradley publication SGI 1 1  Safety Guidelines for the Application  Installation and  Maintenance of Solid State Control  available from your local Allen Bradley office    describes some important differences between solid state equipment and  electromechanical devices that should be taken into consideration when applying  products such as those described in this publication     Reproduction of the contents of this copyrighted publication  in whole or part  without  written permission of Rockwell Automation  is prohibited     Throughout this publication  notes may be used to make you aware of safety  considerations  The following annotations and their accompanying statements help you  to identify a potential hazard  avoid a potential hazard  and recognize the consequences  of a potential hazard        Identifies information about practices or circumstances that can  cause an explosion in a hazardous environment  which may    lead to personal injury or death  property d
38. rolFLASH Firmware Upgrade Kit User Manual  publication 1756 6 5 6     Make Sure That Your Processor and Adapter are Compatible    You can use the 1747 SDN Scanner Module in an I O chassis any slot except for the  left most which is reserved for the SLC 500 processor        IM PORTANT You cannot use the scanner module in a remote I O chassis  with a 1747 ASB adapter module  The adapter module does    not support M file transfer        Install the M odule Into the Chassis    To install your module into the chassis   1  Turn off the chassis power supply   If you insert or remove the scanner module with power    WARNING   applied to this module or any device on the network  an  electrical arc can occur  This could cause an explosion in    hazardous location installations  Be sure that power is  removed or the area is nonhazardous before proceeding           Publication 1747 INO58C EN P   May 2002    10 1747 SDN DeviceNet Scanner Module    2  Select a slot for the module in the chassis  You may use any slot except the  leftmost slot  which is reserved for the SLC 500 processor     FA         al         SIN  _ ESS       HE  Na   ae  BEL  TE    3  Insert the module into the slot you have selected     4  Apply firm  even pressure to seat the module in the I O chassis backplane  connectors     Connect the Module to the DeviceNet Netw ork    To connect your module to the DeviceNet network     1  Turn off the network power supply     If you connect the scanner module with power applied 
39. s  they must  only be changed in an  area known to be  nonhazardous        o                       Publication 1747 IN058C EN  P   M ay 2002       AVERTISSEMEN RISQUE D   EXPLOSION    e Couper le courant ou  s assurer que     environnement est  class   non dangereux  avant de d  brancher       quipement   e Couper le courant ou  s assurer que     environnement est  class   non dangereux  avant de d  brancher les  connecteurs  Fixer tous  es connecteur   externes reli  s    cet    quipement    l aide de  vis  loquets coulissants   connecteurs filet  s ou  autres moyen  avec ce produi        s   i  e La substitution de   composants peut rendre   cet equipeme  inadapte a une  utilisation en  environnement de  Classe    Division 2     e S assurer que  l environnement est  class   non dangereux  avant de changer les  piles                 v       fournis                      1747 SDN DeviceNet Scanner M odule 39       Specifications       M odule Location    SLC 5 02 or later chassis       Module Defaults    Node Address   63  Baud Rate   125 Kbits s       Power Consumption    Backplane Current      DeviceNet     5Vdc  500 mA  24Vdc  90mA Class 2       Isolation Voltage    Optical Isolation between backplane and DeviceNet channel  tested to  withstand 500Vac for 60 seconds  1 Megohm resistor from DeviceNet channel to chassis       Operating Temperature    EC 60068 2 1  Test Ad  Operating Cold    EC 60068 2 2  Test Bd  Operating Dry Heat    EC 60068 2 14  Test Nb  Operating Thermal
40. s originate in  the processor  The scanner module can only wait for the processor to download a  transaction block to the module or request an upload of a transaction block from  the module     Once an Explicit Message Request transaction block is downloaded to the scanner  module  a ladder logic program in the processor polls the scanner module for the  transaction block containing the Explicit Message Response for that request  This is  done by the processor with an M1 file transfer on the scanner module     Depending on the network load  the scanner could take a few seconds to complete  the request  When a response is loaded  bit 15 of the module status register is set to  1  The program may have to poll the scanner module a number of times before the  scanner returns a Response Transaction Block     The scanner module recognizes I O data and control as higher priorities over  explicit messaging on DeviceNet     Publication 1747 INO58C EN P   May 2002    32  1747 SDN DeviceNet Scanner Module    Message lengths and slave device types impact transaction message completion  times  If the processor has queued multiple Explicit Message Transactions to the  scanner module for multiple slave devices  the transactions with the slaves may not  complete in the order in which the requests were received  The slave responses are  queued to the 32 word M1 file transfer in the order in which they are received    As response transaction blocks are uploaded  the processor s program matches
41. t  88   2  Firmware major revision  01 through 7F hexadecimal   3  Firmware minor revision  01 through FF hexadecimal     4  Baud rate  indicates 00 for the default of 125  01 for 250 or  02 for 500 Kbits s     5  Node address  00 to 63 with 63 as the default     Use the RSNetWorx for DeviceNet software to change the baud rate and node  address     Refer to the Numeric Code Display Summary table on page 36 for a complete listing  of numeric displays     Understand the Data Organization of the Module    The module has four data areas to transfer data  status and command information  between the module and the processor    e SLC input image table   e SLC output image table   e SLC M1 file   e SLC MO file    Publication 1747 INO58C EN P   M ay 2002    Input and Output Image Tables    1747 SDN DeviceNet Scanner M odule 13    The following table describes the mapping of the 1747 SDN input and output image  tables and the M1 and MO files                                            Words SLC Input Image Words SLC Output Image  0 Status 0 Command  1 31 DeviceNet Input Data  31 words  1 31 DeviceNet Output Data  31  words   Words SLC M1 File Words SLC MO File  0 149 DeviceNet Input Data  150 words  0  149 DeviceNet Output Data   150 words   150 205 Reserved  56 words  150 223 Reserved  206 209   Device Active Table  4 words   74 words   210 Node Address Status Indicator   1 word   211 Scan Counter  1 word   212 215 Device Idle Table  4 words   216 219 Device Failure Table  4 words   22
42. the channel                    Publication 1747 INO58C EN P   May 2002    36  1747 SDN DeviceNet Scanner Module       Numeric Codes and Descriptions    Your module uses numeric displays to indicate diagnostic information about the  status of your module  The display flashes at 1 second intervals  The following table  summarizes the meanings of the numeric codes     Numeric Code Display Summary                                                                            Numeric   Description Take this action   Code   0 63 Normal operation  The numeric display indicates   None    the 1747 SDN  node address on the DeviceNet  network    70 odule failed Duplicate Node Address check    Change the module channel address to another  available one  The node address you selected Is  already in use on that channel    71 Illegal data in scan list table  node number Reconfigure the scan list table and remove any   alternately flashes   illegal data    72 Slave device stopped communicating  node Inspect the field devices and verify connections    number alternately flashes     73 Device s identity information does not match Verify that the correct device is at this node   electronic key in scan list table entry  number  M ake sure that the device at the scrolling  node address matches the desired electronic key   vendor  product code  product type  etc      74 Data overrun on port detected  Modify your configuration and check for invalid  data  Check network communication traffic    75 No tr
43. their descriptions are listed on page 36     Scan Counter    Word 211 is used for the module scan counter  The module increments this counter  whenever a scan of the DeviceNet devices is completed  The counter rolls over  when it reaches a maximum value of 65535  It is located at M1 S 211     Device Idle Table    Words 212 through 215 in the M1 file are used for the device idle table  This table  indicates that there are devices on the network in Idle mode  The module tracks  devices in Idle mode by assigning one of the 64 bits in the table to each device on  the network  The bits are assigned in consecutive order to consecutive device  addresses starting at mode 0 at M1 S 212 0     Device Failure Table    Words 216 through 219 in the M1 file are used for the device failure table  This table  indicates communication failures of devices on the network  The module tracks  device failures by assigning one of the 64 bits in the table to each device on the  network  The bits are assigned in consecutive order to consecutive device  addresses starting at mode 0 at M1 S 216 0     Auto Verify Failure Table    Words 220 through 223 in the M1 file are used for the auto verify failure table   The auto verify failure table is used to verify that data size received from the device  matches the setting in the scanners scanlist entry for that node  This check occurs  at connection establishment time  The module tracks auto verify failures by  assigning one of the 64 bits in the table to each
44. tions   Americas  Rockwell Automation  1201 South Second Street  Milwaukee  WI 53204 2496 USA  Tel   1  414 382 2000  Fax   1  414 382 4444   Europe  Rockwell Automation SA NV  Vorstlaan Boulevard du Souverain 36 BP 3A B  1170 Brussels  Belgium  Tel   32  2 663 0600  Fax   32  2 663 0640  Asia Pacific  Rockwell Automation  27 F Citicorp Centre  18 Whitfield Road  Causeway Bay  Hong Kong  Tel   852  2887 4788  Fax   852  2508 1846    Headquarters for Dodge and Reliance Electric Products   Americas  Rockwell Automation  6040 Ponders Court  Greenville  SC 29615 4617 USA  Tel   1  864 297 4800  Fax   1  864 281 2433  Europe  Rockwell Automation  Br  hlstraRe 22  D 74834 Elztal Dallau  Germany  Tel   49  6261 9410  Fax   49  6261 17741   Asia Pacific  Rockwell Automation  55 Newton Road   11 01 02 Revenue House  Singapore 307987  Tel   65  351 6723  Fax   65  355 1733    Publication 1747 IN058C EN P   M ay 2002 PN 957678 59    Supersedes Publication 1747 INO58B EN P   August 2001 Copyright    2002 Rockwell Automation  Inc  All rights reserved  Printed in the U S A     
45. to communicate with the DeviceNet network  from another network  This method is intended for fine tuning and  adjustment of network devices     e use a 1770 KFD RS 232 DeviceNet adapter or 1784 PCD   PCID or  PCIDS  DeviceNet PC Card  This method is necessary for a complete network  configuration and real time monitoring of your network devices     Before you install your module you must know how to     e program and operate an Allen Bradley SLC 500 programmable controller  e install and configure the devices on your DeviceNet network    Electronic Data Sheet Requirement    This release of the scanner module requires the latest EDS file for RSNetWorx for  DeviceNet software  If the software displays the device as an    unknown device      the EDS file must be downloaded     You can get the latest EDS file online at   http   www ab com networks eds  Once you are at this location     1  Select DeviceNet   2  Enter the catalog number  1747 SDN  3  Enter major revision number   4  Enter minor revision number    5  Select Search    For more information  contact Rockwell Automation Technical Support at  440 646 5800     Publication 1747 INO58C EN P   M ay 2002    1747 SDN DeviceNet Scanner Module 9    Perform the ControlFLASH Update    If you have the previous release of firmware and you want to upgrade it to this  release  you must perform the ControlFLASH update  To get the kit  contact  Rockwell Automation Technical Support at 440 646 5800  To install the kit  refer to  the Cont
46. to this    WARNING   module or any device on the network  an electrical arc can  occur  This could cause an explosion in hazardous location  installations  Be sure that power is removed or the area is  nonhazardous before proceeding           Publication 1747 IN058C EN P   M ay 2002    1747 SDN DeviceNet Scanner M odule 11    2  Connect the DeviceNet drop line to the ten pin linear plug by matching the  wire insulation colors to the colors shown on the label     424V Red AF   woe  N   KY  Can_H White   Ten pin Red          Drain Shield           linear plug  Can_LBlue       gt o 4    24V Return Black et  En                                             3  Locate the DeviceNet port connector on the front of the module     4  Insert the ten pin linear plug into the DeviceNet port connector   AER IO    T SN        Ten pin  linear plug    i                      DeviceN et port  connector       DeviceNet drop line  You have installed and wired your module  To operate the module    you must apply power and then configure and program the SLC processor to  communicate with it  We describe how to do this in the next three sections     Publication 1747 IN058C EN P   M ay 2002    12 1747 SDN DeviceNet Scanner Module    Apply Chassis Power    When you apply chassis power the module numeric indicators cycle through the  following displays        DeviceNet                                        Module  STATUS numeric  MODULE NET indicators  ADDRESS ERROR             1  Seven segment lamp tes
47. w the state of the MO or M1 addressed bit  transfer the state to an internal  processor bit  This is illustrated below  where an internal processor bit is used to  indicate the true false state of a rung                 B3 B3 EQU M0 3 0      E EQUAL     0 1 Source    N7 12 1  Source B N7 3             This rung does not show its true rung state because the EQU instruction is  always shown as true and the MO instruction is always shown as false                               B3 B3 rm EQU                   B3    1 E       EQUAL     0 1 Source A N7 12 2  MO 3 0  Source B N7 3 C   1    OTE instruction B3 2 has been added to the rung  This instruction shows the true or  false state of the rung     Transfer Data Between Processor Files and M0 or M1 Files    The processor does not contain an image of the MO or M1 file so you must edit and  monitor MO and M1 file data via instructions in your ladder program  For example   you can copy a block of data from a processor data file to an MO or M1 data file or  vice versa using the COP  copy  instruction in your ladder program     Publication 1747 INO58C EN P   M ay 2002    18  1747 SDN DeviceNet Scanner Module    The COP instructions below copy data from a processor bit file and integer file to             an MO file   S 1 COP  ae  COPY FILE  15 Source  B3 0  7 Dest M0 1 0  First scan bit  It makes this rung Length 16  true only for the first scan after  entering Run mode   COP  COPY FILE  Source  N7 0  Dest  M0 1 16  Length 27            
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Utilizzo dell`origine dati TWAIN  Phaser 3300MFP Brochure  ねじゲージ - レッキス工業  PPDE.13.Piano manutenzione opera  CANAL JET  Circular Reglamentaria Externa DODM    取扱説明書  The OTISS User Manual - Public Schools of North Carolina  Katun 38750    Copyright © All rights reserved. 
   Failed to retrieve file