Home
        User Manual
         Contents
1.       15    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    2 4 Screens    Note  Screens count is device dependent  PQM 702 and PQM 703 have 9    screens  whereas PQM 710 and PQM 711 have 10 screens        Fig  5 presents the first screen displayed by the analyzer  The bar in the upper part is a per   manent element  shown independent of the selected screen        Fig  5  Screen 1 with a phasor diagram     The bar includes  from the left    o number of active measurement point  P1  P2  P3 or P4  In some modes measurement  point number is displayed alternately with additional graphic symbol     O  g The symbol of sinusoid is displayed when the memory of the measurement point is  completely filled with recorded data  or when the measurement point is not assigned to  any place  zero allocation   In such conditions  recording cannot be started  only viewing  the current values is possible     O The symbol of slope with an arrow indicates waiting for triggering the recording pro   cess by the first detected event  threshold triggering      O The hourglass symbol indicates waiting for recording to start in the scheduled re   cording mode  also between recording intervals     e available space on the memory card for an active measurement point   in MB or GB    e current date and time in the format day month year  hour minute second  Date and time are  displayed in green  when time of the analyzer is synchronized to GPS time and meets the  requirements for the accuracy specifi
2.      28    2 Operation of the analyzer    Transformer    Transformer       Voltage inputs Current inputs                      Fig  16  Wiring diagram     single phase          Voltage inputs Current inputs       Fig  17  Wiring diagram     split phase        Load    29    30    Transformer    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual         F    5   i O  43  rT  1 te oO 4  a a               Voltage inputs Current inputs  Fig  18  Wiring diagram     3 phase wye with a neutral conductor     Load       Voltage inputs Current inputs    Fig  19  Wiring diagram     3 phase wye without neutral conductor     2 Operation of the analyzer    Transformer       Voltage inputs Current inputs    Fig  20  Wiring diagram     3 phase delta     Transformer           E   A              I    Voltage inputs Current inputs    Fig  21  Wiring diagram     3 phase delta  current measurement using Aron method      31    Transformer    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Load       Voltage inputs Current inputs    Fig  22  Wiring diagram     3 phase wye without neutral conductor  current measurement    32    using Aron method      L1    L2    L3       Voltage inputs Current inputs    Fig  23  Wiring diagram     indirect system with transducers     wye configuration     2 Operation of the analyzer    Transformer  Load       Voltage inputs Current inputs    Fig  24  Wiring diagram     indirect system with transducers     delta configuration     Note  Frequency response of tra
3.      Measurement category of the whole system depends on the acces    sories used  Connecting analyzer with the accessories  e g  current   clamps  of a lower measurement category reduces the category of  the whole system     Note  e Do not unscrew the nuts from the cable glands  as they are perma   nently fixed  Unscrewing the nuts will void the guarantee   e Do not handle or move the device while holding it only by its ca   bles     POM 703 The icon with the analyzer name is placed next to sections of  the text that refer to specific features of the analyzer  particularly to avail   ability unavailability of a given function    All other parts of the text relate to both types of the analyzer        1 General Information    1 2 General characteristics    Power Quality Analyzers PQM 702  PQM 703  PQM 710 and PQM 711  Fig  1  are high tech  devices providing their users with a comprehensive features for measuring  analyzing and record   ing parameters of 50 60 Hz power networks and power quality in accordance with the European  Standard EN 50160  Analyzers are fully compliant with the requirements of IEC 61000 4 30 2008     Class A     The device is equipped with five voltage measurement inputs installed as cables terminated  with banana plugs marked as L1  L2  L3  N and PE  The range of voltages measured by four  measurement channels is up to  1500V  the device has two voltage sub ranges   This range may  be increased by using additional external voltage transformers        K
4.     ss mnel       OPERATING MANUAL    POWER QUALITY ANALYZERS  PQM 702  PQM 703  PQM 710  PQM 711    C       SONEL SA  ul  Wokulskiego 11  58 100 Swidnica  Poland    Version 1 2  06 07 2014       Sonnet  C  Ea       a      q  TResge osees 290          in A    CONTENTS    1 General IRTON I ATOM criccs acorn oe ceressets E E acts 6  1 1 FI e E kp aecienee a ssee sce acctavedeneee casaenusees st  6  1 2 General characteristics      ccccccccsseeececcceeensseeeeeeecesessueeseecessessaueeeeeesesssaaaeseeeeeseeas 7  1 3 Power supply of the ANALYZOL        cccscecccssescecsenseccseseecnauseessauseensuesesnauseessauesess 10  1 4 Tightness and outdoor operation          cccccccseeeeccensseeeeescaseeeesssueeeeessaaeseeessananes 10  i MOUNTING   n DIN TAN sessize aa EETA 11  1 6 Measured parameters        cccccsseeccccssneeeecscaueeccesaucseecssaueeeecssauneeessauensesssaaanses 12  1 7 Compliance with standards        1ssccccccccecesseeeseececesseseeeeeeceesessasceseeessssseeeseseees 14   2 Operation of the analyzet      ssssssssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 15  2 1 BUONO ioe aa a E roses aedooseeseaidieessaeoeesoetieeeee 15  2 2 Switching the analyzer ON OFF      ccsssssccccssseeececssansesecsaaueesessaaueesesssauensesssaens 15  2 3 AOO a E E E A E et eee errr erer 15  2 4 TE A ee ne EA E AEE ene E EA ENE E E EEA N AE 16  2 5  Sonel Analysis  software       1 cccccccccccesseeeseeccescssseeseeecessssssaeeeeeeesssaaaaeeseeeeeneas 21  2 6 PC connection and data tr
5.    Example  Basic uncertainty for RMS voltage measurement is 0 1  Unom within ambient temp   range of 0  C    45  C   at  20  C  measurement uncertainty is  0 18  Unom  multiplier 1 8   at  10  C  measurement uncertainty is  0 14  Unom  multiplier 1 4   at 0  C  measurement uncertainty is  0 1  Unom  multiplier 1 0   at  45  C  measurement uncertainty is 0 1  Unom  multiplier 1 0   at  55  C  measurement uncertainty is  0 2  Unom  multiplier 2 0     105    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Rated operating temperature range       M 1 8  2     20  C  55  C    Fig  56  Basic uncertainty multiplier M as a function of ambient temperature     6 4 3 Voltage  Voltage Range and conditions    Urms  AC DC  10  Unom    Urnms  lt  150  Unom 0 01  oa  0 1  ica ern  for Unom 2 64 V    Crest Factor 1  10 a   1  1 65 for 690 V voltage   1 Urms 2 10  Unom  6 4 4 Current  Range and conditions    Irms  AC DC  Input path without clamps    0  1 V  0  3 6 Vp p  0 01  lhom  0 1  Inom    Flexible clamps F 1 F 2 F 3    0 01  Inom Additional uncertainty   1     2  taking into account additional  error due to the position        Hard clamps C 4    0  1000 A 0 01  Inom Additional uncertainty    3600 Ap p  0 1  10 A     8    0 1 A   10 A   3   50 A   1 5   200 A   0 75   1000  1200 A   0 5     Hard clamps C 5    0  1000 A 0 01  Inom Additional uncertainty     3600 Ap p  0 5  100 A   lt   1 5    1 A   100  800 A   lt  2 5   800  1000 AAC   lt  4   800  1400 A DC   lt  4     Hard clamps
6.    Fig  8  Screen 4 with apparent and deformation power values     Screen 5  Fig  9  indicates THD factors in voltage and current  The factors shown on this  screen are related to the fundamental component     THOU1   3 013   THOI1  17 69    THOUZ   2 902   THDIZ  11 47    THOUS   2 895   THDIS  19 49    THOUnrc   18 32   THOIn  184 0         Fig  9  Screen 5 with THD factors     On screen 6  Fig  10  Power Factors  PF  are presented along with tang  i e  the ratio of reactive  power to active power      PF1  0 965 tanp1  0 191  PF2  0 978 tanp2  0 169  PF3  0 948 tanpd  0 259    PF   0 926 tanp   0 202       Fig  10  Screen 6 with power factors and tang     Screen 7 is the last of the measurement screens and it presents short and long term flicker fac   tors Py and Pr  Ps flicker severity is updated every 10 minutes  whereas Py flicker severity every  two hours     2 Operation of the analyzer    Pst1  4 337  Pst2  3 269  Pst3  2 710       Fig  11  Screen 7 with flicker     Screen 8 presents the following information     Start   25 02 2014 10 44 44  Stop       Time   OOd OOh 01m 13s    Events   7  GSM   Ready  HSUPA  GPS    YES  2D             Fig  12  Screen 8     e start time of the last recording  or the start time of the next scheduled recording interval in the  scheduled recording mode   e end time of the last recording  when recording is in progress dashes are displayed   or the  end time of the next scheduled recording interval in the scheduled recording mode   e durat
7.    Qi   3U  Tf sin py  where   U1  is the voltage positive sequence component  of the  var fundamental component  l1  his the current positive sequence component  of the  fundamental component   p1  is the angle between components U  and h   S    3U   where     Total reactive power  acc  to IEEE 1459    Effective apparent power j    2  3 U  U  U  tUs  U FU  18    L   Ip   I  i    Sen   Se    a    where   Se1  3 Ue1le1    Effective apparent distor     2  tion power 3 Ua1      Ugi      Uci     Vapi   User      Ucar       18      las  tax   l    m    Ip   a   Ii   Detot   Dga   Deg   Dac    Prot  PFrot   F  e    Total Budeanu distortion D  Btot  power    Total Power Factor  Total displacement pow  COSPtot  er factor DPFiot    Total tangent      Total active energy  con  Ep tot  sumed and supplied  Ep tot    Total Budeanu reactive  energy   consumed and supplied     1  COS Prot   DPFtot   3  cos Pa  COSPpz   cosc     _ Rtot  tan Prot   P  tot    where  Qot   Qstot  when Budeanu method was chosen   Qiot   Qitot  when IEEE 1459 method was chosen     calculated as for the split phase network    E QB tot    E calculated as for the split phase network  QB tot       Total reactive energy of E  Q1 tot   fundamental component E    consumed and supplied  PIR    Total apparent energy    RMS value of zero volt   age sequence    Voltage positive se   quence component    Voltage zero sequence  unbalance ratio  Voltage negative se   quence unbalance ratio    Current zero sequence  component   
8.    lt connection type gt     after the search  the analyzer is  not displayed on the list  Option GSM transmission available is enabled and the analyz   er is properly configured in the database  including IP number     Possible cause  TCP 4001 port is blocked   it is used for communication through a firewall in   stalled on the PC or in the server of internet service provider     42    2 Operation of the analyzer    Solution  check whether TCP 4001 port in program settings is not blocked  If it is not  please con   tact your local network administrator     Problem  When a SIM card is inserted into the analyzer  message   nvalid IP  is displayed    Possible cause  IP number assigned by the network is different than the one configured in the  analyzer    Solution  Check whether the analyzer database includes the correct IP number  as specified by  the provider  In the analyzer database enter settings and select Change GSM settings   Enter the correct IP address and confirm  Disconnect the analyzer and using the screen of  GSM connection status to check whether the analyzer properly connects to the Internet  If  this does not help  check whether the inserted SIM card is correct    Problem  The analyzer reports an error of  Invalid PIN code of SIM cara     Possible cause  PIN code used by the analyzer to unlock the SIM card is incorrect  This may be  caused by replacing SIM cards  or changing the PIN code of the card by an external de   vice    Solution  After connecting the ana
9.   100V Sys for 10MHz     Transients  p Q Measurement point 2           Fi Analyzer settings Log waveforms and transient charts    Phase voltage DC  E a E Log events    E Minimum    E Average    E Maximum    E Instantaneous    Fig  26  Settings for    Voltage    card in scenario 1     At Additional card select only the average value for the frequency  and uncheck other boxes    At Harmonics card and Voltage tab select fields for THD average values and for voltage  harmonic amplitudes   uncheck other boxes  List  THD calculated from  may be set according to  own requirements    At Interharmonics card and in Voltage and Mains signalling uncheck all the boxes     Step 9  Settings of the measurement point has been properly prepared  The next step is to send  the settings to the analyzer  The memory card will be formatted  To do this press Send button  In  the displayed window confirm the deletion of all data on the memory card of the analyzer and  sending the new settings     Step 10  The analyzer is ready to start recording acc  to specified settings  To begin recording at  the measurement point 1  select from the menu Analyzer gt Control  In the displayed window  select from Current measurement point the first position  this field contains a list of names given  to individual measurement points  and start recording by clicking Start  Recording is indicated on  the display of the analyzer by flashing P1 symbol in the upper left corner  Recording may be  continued for any length o
10.   PQM 703  PQM 710  PQM 711 Operating Manual    Voltage level in percent  10       0 1 1 10 100  Frequency in kHz    Fig  47  Allowable levels of mains signalling according to EN 50160 standard     In networks with substantial contents of harmonics  where additional filters are used for reduc   ing interferences  the consequences of their use may also include additional attenuation of the  frequency range used for the signalling  Both the presence of filters and a high level of harmonics  and interharmonics may significantly reduce the possibility of efficient use of the distribution net   work for communication with low frequency or PLCC methods     IEC 61000 4 30 standard provides the following measurement method of ripple control sig   nals   e if the frequency of a control signal is a multiple of 5 Hz  i e  it covers exactly the output line  of FFT frequency analysis   then only this single line is taken into account along with its  RMS   e if the frequency is not a multiple of 5 Hz  then RMS value is calculated from four adjacent  frequency lines of FFT     5 7 Unbalance    Unbalance is a concept associated with the three phase systems and may refer to   e supply voltage unbalance    e load current unbalance    e receiver unbalance     In three phase systems  the unbalance of voltage  current  occurs when values of three com   ponent voltages  currents  are different and or the angles between individual phases are not equal  to 120      The receiver unbalance occurs when
11.   for a direct connection  see chapter 2 12 3     Password  Key  in case of secured networks  for a direct connection  see chapter 2 12 3    External IP Address and External Port  The parameters required to work in a different  subnetwork than the tablet  computer   especially for connecting to the Internet     Configure the analyzer in the following manner     48    Connect the tablet  computer  with the analyzer via a USB cable    Perform the analyzer search  e g  by selecting Analyzer gt Current Settings  F4  and con   nect to the analyzer    Go to Wireless connections tab  Fig  34  and check whether Wi Fi communication ena   bled is active  If it is not  enable it       Wireless modules  2    SMS Alerts                                                      as  a  ainiti O    S   OR 1 Communication enabled    i acne      ie       Fig  34  Current Settings window    Select Options gt  Analyzer database  F3   In the analyzer database enter the option for ed   iting the analyzer settings  select the line with the serial number of the analyzer and click  Edit   In the displayed menu  click Change Wi Fi settings     Enter the following data  the access point name  SSID field  and in case of a secured net   work tick Modify box and enter the password  Key field   In case of a non secured network    Key  field remains empty  but  Modify  box must be ticked     2 Operation of the analyzer       d Certificate of Calibration    6 months    Analyzer type Y Serial number    1 PQM 711 B
12.   o all other measured parameters not listed here    Analyzer configuration  remote triggering and stopping of the recording process    When connected to a PC  the display shows message  PC Connection  and the type of  connection     OO 0 0    When connected to a PC  all analyzer buttons are locked except O  button  but when the  analyzer operates with key lock mode  e g  during recording   all the buttons are locked    To connect to the analyzer  enter its PIN code  The default code is 000  three zeroes   The  PIN code may be changed using  Sonel Analysis  software    When wrong PIN is entered three times in a row  data transmission is blocked for 10 minutes   Only after this time  it will be possible to re entry PIN    When within 30 seconds of connecting a PC to the device no data exchange occurs between  the analyzer and the computer  the analyzer exits data exchange mode and terminates the  connection     21    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Notes    e Holding down buttons     and op for 5 seconds results in an  emergency setting of PIN code  000     e If the keys are locked during the recording process  this lock has a high   er priority  first the user would have to unlock buttons to reset the emer   gency PIN   To unlock the keypad in emergency cases hold buttons    and   op pressed for 5 seconds        e If there is an active connection via one of the media  it is not possible to communicate with the  analyzer using another medium type  e g  a
13.   scribed in this manual  the resynchronization of intervals according to the method described  above is performed for averaging times  10 s  15 s  30 s  1 min  3 min  5 min  10 min  15 min  30  min  60 min  120 min     RTC GPS  next 10 min tick     i e  14 10 00        i 10 min aggregation  interval  x  timestamp       10 12 10 12 10 12  cycles cycles cycles    Fig  54  Determining the averaging intervals longer than 10 seconds  with the 10 minute  averaging    101    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Averaging with times less than 10 seconds is somewhat different  Although  they are all ex   pressed in time units  200 ms  1s  3 s  5 s   in reality they are measured in multiples of the mains  period  For example  selecting 3 second averaging period means averaging in the time equal to  150 180 mains cycles  fifteen 10 12 cycle measurements      RTC GPS    next 10 min tick   i e  14 10 00          3 sec interval   x   timestamp    ES ca 10 12  ES ca cycles        actually it is a 150 180 cycles time interval    Fig  55  Determining the averaging intervals shorter than 10 seconds  with the 3 second  averaging      The method of determining average values for such periods is shown in Fig  55  Also in this  case the resynchronization of 10 12 cycle intervals  but it is always done using clock time of 10  minutes  When the clock counts another integer multiple of the 10 min  period  another aggrega   tion interval is resynchronized and the next interval is st
14.   voltage and current RMS    o Ua 1 2  0 0    150 0  Unom 0 01  Unom  0 2  Unom    Detection thresholds Set by the user in percentage or absolute values  Event detection based on  the measurement of Urms 1 2   1 period RMS refreshed every  2 period    _hh mm ss ms      Waveform record max  1s of himm SSMS ra and max  960 ms pretrigger time   sampling  10 24 kHz  resolution  8 bit     RMS1 2 plot record max  30 s of recording and max  4 9 s pretrigger time  sampling  half cycle    Inms Current Range Resolution Basic uncertainty  ee max     Oooo   1 2  0 0    100 0  Inom 0 01  Inom  0 2  Inom    Detection thresholds Set by the user in percentage or absolute values  Event detection based on   aise na the measurement of IRusi1 2   1 period RMS refreshed every   period      Duration   gt    himm ss ms sd One period  Waveform record max  1 s of recording and max  960 ms pretrigger time   Wavtom record  ae  sof xarg an ra sampling  10 24 kHz  resolution  8 bit   sampling  half cycle       111    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    6 6 Event detection   other parameters    Parameter Range Detection method    Frequency 40    70 Hz  percentage   Detection based on 10 sec  measurement   min  max  or absolute value   acc  to IEC 61000 4 30   Voltage crest factor 1 0    10 0 Basing on 10 12 cycle value    min  max    Current crest factor 1 0    10 0 Basing on 10 12 cycle value    min  max    Voltage unbalance factor for nega  0 0     20 0  Basing on 10 12 cycle value   
15.  0s 60 5     _  Syn   100  1   752    100  1     1 52     cos 60     therefore  the measurement uncertainty is           v1 02   1 522    1 82     In the same conditions  but with phase shift o   10     _ cos 10 5     _    pn   100  1     SC     0 16   and the measurement uncertainty is           v1 07   0 16     1 01     These calculations do not take into account the additional errors intro   duced clamps and transformers        ae  5      90 9 60    80        a sen nnnnnnneecbannnnnnnnneeeeeenebennnnnccceeeees tdennnnnnnnnnnneee  p 50    OO a ea ae ae  60  p 40    50   30    40 EEP PERRE PEE ERER PI SERTE A PE EE GRLA ceases oun ge ERREA  FEAE EEE oe a eee oe eee p pI EN   20    30     10    20    p 0    ae  Ag       0  0 5 10 15 20 25 30    Fig  57  Additional uncertainty due to the phase error  depending on the phase angle     110    6 Technical data    6 4 11 Flicker    Range and conditions Resolution Basic uncertaint       Pst  10 min   0 2   10 0 01  5  within the values presented in ta   Pr  2 h  for Urms 2 80  Unom bles of IEC 61000 4 15 standard  6 4 12 Unbalance    Unbalance ratio for posi  0 0    20 0  ae 1   0 15   tive  negative and zero for  absolute uncertainty   sequence 80  Unom  lt  Urms  lt  150  Unom    6 4 13 Mains signalling    in accordance with IEC 61000 4 30 2008  Amplitude of ripple  control signal 0 01  Unom  UR1  UR2    6 4 14 Transients CUES PQM 711  Range and conditions    Voltage transients  6000 V   5    25 V              6 5 Event detection 
16.  2 1  Unom    n  0  50  for IRms 2 1  Inom       107    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    6 4 8 Harmonic Powers  Active and reactive 80  Unom  lt  Urms  lt  150  Unom depending on a  52 4 52 4 82  9  power of harmonics 5  Inom  lt  IRms  lt  Inom Unom and Inom L Oun T Oin   Opn 70    where     duh     basic measurement un   certainty for voltage harmonic  amplitude       n     basic measurement un   certainty for current harmonic  amplitude   dph     basic uncertainty of the  measurement of the phase  between voltage and current  harmonics     1  See chapter 6 4 10  Estimating measurement uncertainty values for power and energy        6 4 9 Power and energy    Conditions  Power and energy  for power and energy Resolution Basic uncertainty       80  Unom  lt  Urms  lt  120  Unom   Active power 1  Inom  lt  Inus  lt  5  Inom depending on T      1 0       h    Active Energy COS     1 Unom and Inom p  5  Inom  lt    RMS  lt  Inom    2 2 o  2  lhom  lt    RMS  lt  10  lhom    2 2 o  10  lnom  lt    RMS  lt  lnom    2 2 o  Reactive power 2  Inom  lt  IRms  lt  5  Inom depending on ee  Reactive energy sing   1 Unom and Inom   11 25   65     5  Inom  lt  IRMs  lt  Inom      2 2 o    10  Inom  lt    RMS  lt  Inom 2 2 o  sing   0 5 as A  10  lhom  lt    RMS  lt  Inom 2 2 o  sing   0 25    1 252   62       Apparent power 2  Inom  lt  Rms  lt  5  Inom depending on  Unom and Inom      h  5  Inom  lt    RMS  lt  10  Inom 2 2 o  sing   0 5 cme a  h    Apparent enerdy 5 
17.  2 11 2 Moagem CONNOTATION sassis dhe ses Sse seuten EEEE EEE EAEAN EEA eee 40  2 11 3 CHECKING GSM CONNGCHON 22  cszcicce casos se ssusvees initia rie eiri rorik EE srik P CEEE TEETER 42  2 11 4 Possible problems with GSM settings and troubleshooting               11ssssseeeeeeeeeees 42  2 12 Wi Fi communication mode Panno  E E E E PIE N fsacenetase 43  2 12 1 General Information wecccescncconssenccescacndeccctsncecasnvanctensundssesensdeccaaeededsscaneeessdnnsecceeeeee 43  2 12 2 Factory CONGA UON seereis a a E Ea 46  2 12 3 Enabling   disabling   configuring the Wi Fi access point in the tablet                    46  2 12 4 Configuring Wi Fi connection via USB CONNECTION          cccccc teen eee e teen ee neeeneeees 48  2 12 5 Editing the Wi Fi settings in the analyzer database in the absence of USB  CONMMCCHON resesi er r E NEEE thaw seeded does ee E TENS 50  2 12 6 Checking Wi Fi connection       cccccccsseeceeecccnnaeeeseeecennsansuseeeesnsaaeaseesessnaaneaseseesnaaaaes 51  2 12 7 Possible problems with Wi Fi settings and troubleshooting           1  cccccseeeeeeeneeeees 51  2 12 8 Transferring data from the tablet to a desktop compute            1  ccsseeecsseeenenenennens 53  2 13  Notification of analyzer changed location          11cccccsseeeceeeeeceaeeeesensnessaenessaes 54  adl KOVO eee tia paint Sen E E E E E E EA 55    219     ICCD VINO OO on E TT E Ta 55    3 Design and Measurement MeCthOAS         c11ecccccccennsseceneennnsssseeenennesseees 56  3 1 Voltage TOU
18.  4002 port in program settings is not blocked  If it is not  please con   tact your local network administrator     Problem  During direct connection tablet    analyzer  the transmission speed drops below 200  kB s   Possible causes    1  The distance between the tablet and the device is too large    2  The tablet operates as a Wi Fi access point while connected to an external Wi Fi router   e g  to obtain access the Internet    3  Too much interference in the channel used for the transmission    Solution    1  Shorten the distance between the tablet and device to a less than 10 m    2  Ifthe analyzer is connected to the access point in the tablet  then disconnect the tablet  from the external Wi Fi router  disable the access point in the tablet  and then turn it on  again  Fig  33   This will force the Access Point in the tablet to operate in a channel free  form interferences    If the transmission of the analyzer is carried out via external Wi Fi router  make sure that  the access point in the tablet is turned off  Fig  33     3  When the Wi Fi access point is the tablet  then it must be turned off and on again in the  settings window  Fig  33   This will force the Access Point to operate in other channel free  form interferences  However  if an external Wi Fi router is the access point  then force its  operation in another channel     Problem   The connection with the analyzer is lost   Possible cause   1  In the window for wireless connections  Fig  34   the Wi Fi was di
19.  72    Voltage negative se   quence component    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    calculated as for the split phase network    Estot    gt  SeT        where    i is subsequent number of the 10 12 period measure   ment window   Se i  represents the effective apparent power Se  calcu   lated in i th measuring window    T i  represents duration of i th measuring window  in  hours     Uo   mag  Uo     where Uar  Us1  Uc  are vectors of fundamental compo   nents of phase voltages Us  Us  Uc  Operator mag   indicates vector module    1 2  U    3  Ua   Ua  a Urs     U    mag U      where Uar  Us1  Uc  are vectors of fundamental compo   nents of phase voltages Us  Us  Uc  Operator mag   indicates vector module  oe 1 v3     a  lema Been    a2   1   240        1 2  U  z  Un  a Up   aU         U    mag  U2     where Ua  Us1  Uci are vectors of fundamental compo   nents of phase voltages Us  Us  Uc  Operator mag   indicates vector module    a   1e 120      _       1  3  la   Ip   Ic     lo   mag  Ip   where Jaz   s1  Ici are vectors of fundamental compo   nents for phase currents  a  IB  Ic  Operator mag   indicates vector module       4 Calculation formulas    1 2     la   ale   a Ie     Current positive se   quence component    I    mag J    where lar  Is    Ic   are vectors of fundamental current  components  a  ls  Ic  Operator mag   indicates vector module    1 2  I    ata Ip1   al       Current negative se  I    mag  Jp   l2 A  quence component where lar   s1 
20.  C 6    0 01  Inom Additional uncertainty  0 01  0 1 A     3    1 mA   0 1  1 A   2 5   1  12 A   1        106    6 Technical data    Hard clamps C 7    0 01  Inom Additional uncertainty  0  100 A     0 5    0 02 A    45  65 Hz   0  100 A     1 0    0 04 A    40  1000 Hz     Crest Factor 1  10  1  3 6 for Inom  0 01  5   for ne 2 1  Inom    6 4 5 Frequency  Range and conditions    40  70 Hz 0 01 Hz  0 01 Hz  10   Unom  lt  Urus  lt  200  Unom  6 4 6 Harmonics    a amonies    _ Range and conditions    ing  harmonics sub groups acc  to IEC 61000 4 7    Urms E 0  200  Uron 0 01  Unom  0 05  Unom if m v  lt 1  Unom   5  of m v if m v 2 1  Unom   acc  to IEC 61000 4 7 Class l     IRms amplitude Depending clamps 0 01  Inom  0 15  Inom if M V  lt 3  Inom  used  see specifica  m v  if m v  23  Inom  tions for Irms   acc  to IEC 61000 4 7 Class l      n   2  50  for Urms 2 1  Unom   n   2  50  for IRms 2 1  Inom  for IRms 2 1  Inom    Phase angle  voltage   180      180   i  nx n  Phase angle  current     180      180               6 4 7 Interharmonics    Range and conditions Basic uncertainty  ey   0  50  grouping  interharmonics subgroups acc  to IEC 61000 4 7  subharmonic addi   i rr takes into account 5 Hz bin     Urs amplitude 0  200  Unom 0  01  Unom  0 05  Unom if m v  lt 1  Unom   5  of m v if m v 2 1  Unom   acc  to IEC 61000 4 7 Class l     IRms amplitude Depending clamps 0 01  Inom  0 15  Inom if moe Inom  mons for IRs   acc  to IEC 61000  4 7 Class l     n   0   50  a Urms
21.  Ici are vectors of fundamental compo   nents for phase voltages Ia  Is  Ic  Operator mag   indicates vector module    I   Current zero sequence io        100   unbalance ratio L  ea I   Current negative se i      100   L    quence unbalance ratio  4 4 3 phase wye without N conductor and delta networks       3 phase wye without N conductor and delta networks   parameters  voltage and current  DC voltage and DC current  THD and K factors  symmetrical components and unbalance factors   flicker are calculated as for 1 phase circuits  instead of the phase voltages  phase to phase voltages are used     Parameter  Designa   tion  eoe voltage  CA  l      Method of calculation    Uca       U4g   Upc     h         13     Current l2   Aron measuring circuits     Se   3U 1   where     Uap    Upc    Uca      Ue    o go      Ip   I   I            _    Qtot   N   yS     P     Total apparent power    Total reactive power   Budeanu and IEEE Qtot  1459        M M  1  Prot   T Uiaclia     Dacha  i 1 i 1  where   Total active power W Uiac is a subsequent sample of voltage Ua c  Uigcis a subsequent sample of voltage Us c  la is a subsequent sample of current la  lig is a subsequent sample of current  s  M   2048 for 50 Hz and 60 Hz    73    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Total Budeanu distortion  a       So    oa  where   Sei   3Verle1  Effective apparent distor   tion power ease Uasi    Usci    Ucn    as   Ucar     Iga      Iga      Ter   pgs      BEING ENEY CON Umea EPs
22.  Inom   IRms   Inom    Power factor  PF  0   1 0 01  0 03  50  Unom  lt  Urms  lt  150  Unom  10  lhom  lt    RMS  lt  Inom  Displacement power 0   1 0 01  0 03  factor  cos   DPF  50  Unom  lt  Urms  lt  150  Unom  10  lhom  lt    RMS  lt  Inom     1  See chapter 6 4 10  Estimating measurement uncertainty values for power and energy        108    6 Technical data    6 4 10 Estimating measurement uncertainty values for power and energy    The total measurement uncertainty for power  active and reactive energy and harmonics is  based on the following relation  for energy we ignore the additional uncertainty due to time meas   urement  as it is much smaller than other uncertainties        p o   CA     2   Ooh    where    ro  measurement uncertainty for active or reactive power   dun     total measurement uncertainty of voltage harmonic amplitude  analyzer  transduc   ers      n     total measurement uncertainty of current harmonic amplitude  analyzer  transducers    Oph     additional uncertainty of the measurement of the phase between voltage and current  harmonics     Oph uncertainty may be calculated when the phase angle is known for the considered frequen   cy band  Tab  8 shows the phase error between voltage and current harmonics for analyzers   without clamps and transducers      Tab  8  Phase error of PQM 702 703 710 711 analyzers  depending on the frequency     Phase difference error      id Phase difference error S    O  40  70 Hz   70  200 Hz   200  500 Hz   500 Hz  
23.  The device is supplied with a bracket for mounting the analyzer on a standard DIN rail  The  bracket must be fixed to the back of the analyzer with the provided screws  The set includes also  positioning catches  in addition to fasteners for mounting the analyzer on a pole   which should be  installed to increase the stability of the mounting assembly  These catches have special hooks  that are supported on the DIN rail                                                                                      Fig  4  The rear wall of the analyzer with fixtures for mounting on DIN rail     11    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    1 6 Measured parameters    The analyzer is designed to measure and record the following parameters     e RMS al Fe and jects voltages   up to 760 V  peak voltages up to  1500 V      transient voltages  overvoltages  in the range up to  6 kV    e RMS currents  up to 3000 A  peak currents   up to  10 kA  using flexible clamps  F 1  F 2  F   3   up to 1000 A  peak values   up to  8600 A  using clamps  C 4 or C 5   up to 10 A  peak  values   up to  36 A  using C 6 clamps  or up to 100 A  peak values   up to  360 A  using C 7  clamps    crest factors for current and voltage    mains frequency within the range of 40  70 Hz    active  reactive and apparent power and energy  distortion power    harmonics of voltages and currents  up to 50th     Total Harmonic Distortion THD    and THD  for current and voltage    K Factor  factor loss in transfo
24.  USB connection is active  the user cannot use  OR 1 radio or GSM connection  In this case  the device displays a message that another  connection is already active     2 6 1 USB communication    USB is an interface that is continuously active and there is no way to disable it  To connect  the analyzer  connect USB cable to your PC  USB slot in the device is located on the left side and  is secured with a sealing cap   Before connecting the device  install  Sonel Analysis  software with  the drivers on the computer   Transmission speed is 921 6 kbit s  In addition  a built in mass storage reader enables  downloading recorded data with speed significantly higher than the standard speed  In this mode   the analyzer provides its memory card as a mass storage space  allowing you to read data ata  speed of a few MB s  During data read out  the normal communication with the device is not  available e g  data preview in LIVE mode  After reading data from the memory card   Sonel  Analysis  automatically switches the analyzer from reader mode to standard communication  mode     Note  In the reader mode  the entire memory card appears as a drive in the op   erating system   this solution provides an unrestricted access to its con     tents  To prevent damaging the file system on the card and losing the  stored data  the user must not interfere with the file system on the card   e g  by creating and storing own files  or deleting files stored by the ana   lyzer   For this purpose do not
25.  by the capacitor  Active  power of the capacitor is zero    However  it turns out the energy oscillation seems only an effect  and that it appears in partic   ular cases of circuits with sinusoidal current and voltage waveforms  and is not the cause of reac   tive power  Research in this area has shown that reactive power occurs also in circuits without  any energy oscillation  This statement may surprise many engineers  In latest publications on  power theory  the only physical phenomenon mentioned which always accompanies appearance  of reactive power is phase shift between current and voltage    The above mentioned formula for calculating the reactive power is valid only for single phase  sinusoidal circuits  How then we should calculate the reactive power in non sinusoidal systems   For electrical engineers this question opens the  Pandora   s box   It turns out that the reactive pow   er definition in real systems  and not only those idealized  has been subject to controversy and  now  2013  we do not have one  generally accepted definition of reactive power in systems with  non sinusoidal voltage and current waveforms  not to mention even unbalanced three phase sys   tems  The IEEE  Institute of Electrical and Electronics Engineers  1459 2000 standard  from  2000  does not give a formula for total reactive power for non sinusoidal three phase systems      as three basic types of power the standard mentions are active power  apparent power and     at   tention     non a
26.  clamps  114       L1 N   2 phase  split phase  Split phase with a neutral conductor  terminals  L1  L2  N   i inals  L1  L2  L3  N           6 Technical data    6 10 Supported current clamps    Types of supported current clamps    Flexible clamps  Rogowski coil   perimeter  120 cm  measuring range 3000 Arms  Flexible clamps  Rogowski coil   perimeter  80 cm  measuring range 3000 Arms  Flexible clamps  Rogowski coil   perimeter  45 cm  measuring range 3000 Arms    6 11 Communication       Communication    Max  transmission speed 921 6 kbit s  mass storage reader mode with few MB s  USB throughput   Compatible with USB 2 0  Built in 433 MHz radio module    POM 702 ETE  Connection via OR 1 wireless module   Wireless Max  transmission speed  57 6 kbit s  Range up to 5 m    Internal Wi Fi IEEE 802 11b g n module     POM 710     POM T11   Max  effective transmission speed 300 kB s  on distance up to 10 m   IEEE 802 11b g    IEEE 802 11 n single stream   WPA WPA2 PSK encryption supported   Internal GSM modem  UMTS standard    Max  transmission speed  5 76 7 2 Mbit s  upload   download        6 12 Environmental conditions and other technical data    Environmental conditions    Operating temperature range   20  C    55  C    Storage temperature range  30  C    60  C    Humidit 10   90  with possible condensation    Ingress protection  according to EN IP 65  60529     Aefarance canciones Ambient temperature  0  C    40  C  Humidity  40   60     Dimensions 200 x 180 x 77 mm  without ca
27.  component  Then  the signal is routed to    1 Current sensing for energy metering  William Koon  Analog Devices  Inc   57    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    the Phase Locked Loop circuit as a reference signal  PLL circuit generates a frequency which is a  multiple of the reference frequency required to clock the ADC    The need for the phase locked loop results directly from the requirements of IEC 61000 4 7  standard  which describes the methodology and acceptable errors when measuring harmonics   This standard requires that the measuring window  which is the basis for a single measurement  and evaluation of the harmonics  is equal to the duration of 10 mains cycles for 50 Hz systems  and 12 cycles for 60 Hz systems  In both cases  it corresponds to approx  200 ms  Since the fre   quency of the mains may be subject to periodic changes and fluctuations  the duration of the win   dow may not be exactly 200 ms  and for example for frequency 51 Hz it will be approx  196 ms    The standard also prescribes that before applying the Fourier formula  in order to extract the  spectral components  data should not be subject to windowing  No frequency synchronization and  a situation where FFT is performed on the samples not covering integer number of cycles  may  lead to spectral leakage  This would cause blurring of the harmonic line over a few adjacent inter   harmonic bands  which may lead to loss of information about the actual level and power of the  tested
28.  current  live  parameters of the measured network and to configure and  control the analyzer  It is not recommended to read a large amount of data stored on the memory  card via a radio link  due to the slower data transmission     PQM 710 Co The analyzer is supplied with a dedicated tablet  which is pre configured  to work with the meter  After the tablet is turned on  it activates  Sonel Analysis  software  which  automatically finds assigned to the analyzer  The tablet acts as an Access Point  which is used to  connect the analyzer through wireless transmission  Wi Fi   More information about the Wi Fi set   up and possible transmission modes is presented in the manual of  Sonel Analysis  software and  in sec  2 6 4     GSM network transmission requires an active user s SIM card to be inserted into the slot of  the analyzer  The card should have the service of data transmission activated and a static IP  number  A PC connected to the analyzer  must have the Internet access     Mounting space for fasteners for bands   for mounting the analyzer on a pole    or positioning catches   for mounting the analyzer on a DIN rail        Mounting space for  DIN rail bracket    Fig  2  The rear wall of the analyzer     COS CD Compared to PQM 702 and PQM 710 models  PQM 703 and PQM 711  analyzers additionally enables the user to measure transient voltages in the range of  6 kV with    9    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    sampling rate from 100 kHz to 10 MHz  Meas
29.  ee ee eee eee ee E eee ee een eee ee 106  6 4 4 CIE as cb serena ase anew a acne testes meee tsa eats nee teenecen a a ea 106  6 4 5 FROG eo can hte sapere EEEE EE ENTE E want EAEN EEE A een os 107  6 4 6 PIONS pee ates ace essa see noes ee anes O EETA 107  6 4 7 Hahei gral gi g 9  O manne mee e Pe ae eT E E ene fee eee ee Ce ee 107  6 4 8 Harmonie TOW GIG sec ti ui it ev iw again shee 108  6 4 9 Fow anrd CHETOY aarre A E sewing ated Sao 108  6 4 10 Estimating measurement uncertainty values for power and energy                     109  GAIL FIE e E a rel eee orn rsT rere 111  6 4 12 E 821E E   eee AN AEN E AOE A A ES T AA E E E TE V A A E E ee eee 111  6 4 13 MANS SONANO eee EEE anne E NE i 111  6 4 14 Transients POM 703  cup EP INE E E ELAT A AEE A AE ET AS 111  6 5 Event detection   voltage and current RMS        cccecccccssseseeceeeeeeeessaneeeeeseaaes 111  6 6 Event detection   other parameters           cccccseeeccsneseccaneeecsaeeeesanenessaenessaanes 112  6 6 1 Event detection hysteresis ccxtauspctavatanniataanpebssatnsateisansaaueeacsinasanthpeacaestaneatebonwias 113  6 7 PecordNg serieei n E A 113  6 8 Power supply and NCALEL         cssccccssseecnscececsaneccnsuuecensuseecsauseensunesenssssssanees 114  6 9 Supported NCTWOFKS         ccccccccccseeeeeeceeeecsaeeeseeccesesasueeesecessssssaeeeecesssssaaanseeees 114  6 10 Supported current clamps        11sscccccccccccsseeseccceseesseeseeceessssaseeeeeeessesseneseseees 115  CAL COMM ANON aar re ENE EE E 115  6 12 Enviro
30.  flexible clamps  to be used with the analyzer  is approx  45uV A   Such low voltages require the use of precise and low noise amplifiers which of course increase  the costs    As the output voltage is proportional to the current derivative  it is necessary to use an inte   grating circuit  generally  the flexible probes comprise a Rogowski coil and an analogue integrator  circuit  characteristic battery powered module   On the integrator output the voltage signal is  available and proportional to the measured current and suitably scaled  for example 1mV A     Another problem concerning Rogowski coil  is its sensitivity to external magnetic fields  A per   fect coil should be sensitive only to the fields closed within its area and should totally suppress ex   ternal magnetic fields  But this is a very difficult task  The only way to obtain such properties is  very precise manufacturing of the coil  with perfectly homogeneous windings and impedance as  low as possible  It is the high precision which results in a relatively high price of such clamps    The user may connect the analyzer to the following flexible clamps offered by Sonel S A     e F 1  with coil perimeter equal to 120 cm   e F 2  perimeter of 80 cm   e F 3  perimeter of 45 cm     All these clamps  probes  have identical electrical parameters  Peak current that may be  measured by connecting the analyzer is 10 kA  this restriction results from the properties of input  channels  and not the probe itself      5 2 Fli
31.  impedance values of individual receiver branches are  not equal    These phenomena are particularly dangerous for three phase motors  in which even a slight  voltage unbalance can cause current unbalance that is many times larger  In such situation  the  motor torque is reduced  heat losses in windings increase  and mechanical wear is faster  The  unbalance also has an unfavorable effect on power supply transformers    The most frequent reason of unbalance is uneven load on individual phases  A good example  is connecting to three phase systems of large one phase loads  such as railway traction motors     94    5 Power quality   a guide    The analyzer is capable of measuring the voltage and current unbalance with a symmetrical  components method  This method is based on the assumption that each set of three unbalanced  vectors can be resolved to three groups of vectors  positive sequence  negative sequence and ze   ro sequence        Ur    AU yg   AU    3U        Fig  48  Example of determining positive sequence component     Presented example shows the method for calculating voltage positive sequence component   By definition     1  U    3  Uia   aU  g   a U        where  U  is a vector of positive sequence   where Uj  Uys  Uc are vectors of fundamental components of phase voltages Us  Up  Uc    1 V3    fpr     Aia  a e am  1 3  2     1el24r                j  a e 7 z     Fig  48 shows graphical method of determining this component  As we can see from the defi   nition  the
32.  ing with 1000 coils the current will be only 1 A  if the circuit is closed   In clamps with voltage out   put  a shunt resistor is located in the clamps     75        PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual  This type of current transformer has several distinguishing   features  It may be used to measure very high currents and its   power consumption is low  Magnetizing current causes a phase   shift  tenth of a degree   which may introduce an error in power   measurement  especially at low power factor   The disadvantage   of this type of clamps is the core saturation when very high cur    rents are measured  above the nominal range   Core saturation   Fig  43  CT clamps with as a result of magnetizing hysteresis leads to significant meas   voltage output urement errors  which may be eliminated only by the core de     magnetization  The core becomes saturated also when the   measured current has a considerable DC component  Undeniable disadvantage of hard clamps is  their significant weight   Despite these drawbacks  CT clamps are currently the most widely used non invasive method for  measuring alternating currents  AC     Together with the analyzer  you can use the following types of CT clamps for measuring alter   nating currents   e C 4  with a nominal range of 1000 A AC   e C 6  with a nominal range of 10 A AC   e C 7  with a nominal range of 100 A AC     5 1 2 Clamps for measuring alternating and direct currents  AC DC     In some situations it is necessar
33.  line  It is allowed to apply Hann weighting window  which reduces the adverse effects of  spectral leakage  but this is limited only to situations when PLL loses synchronization    IEC 61000 4 7 specifies also the required accuracy of the synchronization block  This is ex   pressed as follows  the time between the rising edge of the first sampling pulse and  M 1  th  pulse  where M is the number of samples within the measuring window  should be equal to the  duration of specified number of periods in the measuring window  10 or 12  with a maximum al   lowable error of   0 03   To explain it in a simpler way  consider the following example  Assuming  network frequency of 50 Hz  the measuring window lasts exactly 200 ms  If the first sampling  pulse occurs exactly at time t 0  then the first sampling pulse of the next measurement window  should occur at t 200   0 06 ms  This  60 us is the permissible deviation of the sampling edge   The standard also defines the recommended minimum frequency range at which the above stated  accuracy of the synchronization should be maintained and defines it as   5  of nominal frequen   cy  i e  47 5   52 5 Hz for 50 Hz and 57   63 Hz for 60 Hz     Another issue is the input voltage range for which PLL will work properly  For this issue   61000 4 7 standard does not provide any specific guidance or requirements  However  61000 4   30 standard defines the input voltage range in which the metrological parameters cannot be com   promised and for c
34.  meaning that it is converted to direct voltage  DC   and then  with a high frequency and efficiency is converted to required output voltage  Such a solution   however  has an undesirable side effect  Smoothing capacitors are recharged by short current  pulses at moments when the mains voltage is close to peak value  From power balance rule it is  known that if the current is taken only at short intervals  its crest value must be much higher than  in case it is taken in a continuous manner  High ratio of current crest value to RMS value  a so   called Crest Factor  and reduction of power factor  PF  will result in a situation in which in order to  obtain a given active power in a receiver  in watts   the power supplier must supply power greater  than the receiver active power  this is a so called apparent power expressed in volt amperes  VA    Low power factor causes higher load on the transmission cables and higher costs of electricity  transfer  Harmonic current components accompanying such parameters cause additional prob   lems  As a result  the electricity suppliers have started to impose financial penalties upon the cus   tomers who have not provided sufficiently high power factor    Among entities that may be potentially interested in power quality analyzers are power utility  companies on one hand   they may use them to control their customers   and on the other hand  the energy consumers who may use the analyzers to detect and possibly improve the low power  factor a
35.  measured voltages     Fig  40 presents that the power supply   circuit of the analyzer is independent Power  of the measuring circuit  The power pececceesccerececscrees    adapter has a nominal input voltage   Transient detection module      range 90   760V AC and has separate  terminals     The analyzer has two voltage sub    ranges in the main circuit    e low voltage range  with peak volt   age  450V  is enabled at nominal  voltages of mains with the range  of 64V   127V and at the configu   rations with voltage transducers   the range is also always selected  for channel Un  pe    e high voltage range  with peak  voltage  1500V  is enabled at  nominal voltages of mains from  220V and more  without voltage  transducers         l Fig  40  Voltage inputs  with transient module  and  Using two voltage ranges enables the AC adapter    user to maintain the declared meas   urement accuracy  according to class A of IEC 61000 4 30 standard for all nominal voltages     3 2 Current inputs    The analyzer has four independent current inputs with identical parameters  Each input may  be used for connecting CT current clamps with voltage output in standard 1 V  or flexible   Rogowski  clamps F 1  F 2 and F 3    A typical situation is the use of flexible clamps with built in electronic integrator  However the  described analyzer allows user to directly connect Rogowski coil to the current channel and the  signal integration is performed digitally     3 3 Digital integrator    The analy
36.  power supply from mains  similarly as during normal op   eration with the battery power supply  After discharging  the analyzer will switch off totally and  sending SMS messages will be impossible     Note  Anti theft feature requires the following arrangements for proper opera   tion     e active GSM modem with properly configured SIM card    e at least one emergency telephone established to send SMS s    While activating the anti theft function  both of the above features must be  checked        54    2 Operation of the analyzer    2 14 Key lock    Using the PC program  the user may select an option of locking the keypad after starting the  process of recording  This solution is designed to protect the analyzer against unauthorized stop   ping of the recording process  To unlock the buttons  the user must enter a code consisting of 3  digits    e pressing any button will display message  Enter Code   and three dashes          e using buttons on the keyboard  the user can enter the correct unlock code  button    may   be used to enter the correct unlock code  whereas button changes numbers in sequence 0  1     2   9  O at the first position  button Cc on the second and button Gy on the third    e athree second inactivity on the keyboard will start the verification of the entered code    e correctly entered password is indicated by word OK and the lock is cancelled  whereas  entering wrong password results in displaying message  Invalid Code  and returning to the  previous s
37.  reactive energy to the active energy in a settle   ment period  Going back for a while to the power triangle in sinusoidal systems  we can see that  the tangent of the phase shift angle between the voltage and the current is equal to the ratio of re   active power Q to active power P  Consequently  the requirement to maintain the tang below 0 4  means nothing else but only that maximum level of measured reactive energy may not exceed 0 4  of the measured active energy  Each consumption of reactive energy above this level is subject to  additional fees    Does the knowledge of tang calculated in this manner gives both interested parties an actual  view of energy transmission effectiveness  Have we not mentioned before that the reactive pow   er is only one of the non active power components which influence the power factor reduction   Indeed  it seems that instead of tang we should use the power factor PF which takes into account  also other issues    Unfortunately  the present regulations leave no choice  therefore the correct reactive power  measurement seems a key matter  Now  a question should be asked whether the reactive energy  meters ensure correct readings in the light of the controversies described above  And what we  actually measure using this popular reactive power meters    The answers to these questions may be searched in the standard concerning such devices   IEC 62053 23  Unfortunately  to our disappointment  we will not find there any reference to meas   ure
38.  right side  icons are displayed representing individual measurements  event and  recorded waveforms in the timeline  This graph with a large amount of data may be freely  enlarged to get more details    Click Measurements button to display table with the values of all measured parameters   according to selected averaging time  In this scenario  the selected averaging time is equal to 1  second  therefore every second the analyzer recorded voltage THD and harmonics  frequency is  always measured every 10 seconds   Each line contains the data recorded in the consecutive  second and each column shows individual parameters    After pressing Events you may view all the recorded events  In this scenario  the following voltage  events were recorded  swell  dip  interruption and transients  Each row in the table corresponds to  one detected event  When for a given event graphs are available  e g  waveforms and RMS    graphs   as in this scenario  the last column contains the icon of saved graphs  After clicking it  the  user may display graphs related to a given event     Step 13  Display the time plot for voltage and THD  To generate the graph  go to Measurements   click Measurements button   select column headings for time  always select time column first    voltage  L1  THD L1  columns will be highlighted  and then click Plots and choose Time plot  A  window will be displayed with a graph containing two timeplots  L1 voltage and THD  The graph  may be freely enlarged  using the t
39.  switch  contacts exceeds boundary voltage of the dielectric and spark over occurs  which may be repeat   ed  until the gap is too big for breakdown    Transients may also be propagated in different ways between network segments  e g  light   ning stroke in a MV network can partially penetrate through the transformer to a LV sub network   Attenuation properties of the transformer usually significantly reduce the amplitude of the surge   as well as change its timing parameters     5 10 CBEMA and ANSI curves    CBEMA curve was first proposed in the 70 s of the last century by the organization that gave  the curve its name   Computer and Business Equipment Manufacturers Association  now Infor   mation Technology Industry   which associated manufacturers of computer and office equipment   The curve was developed as a guide in the construction of power supply adapters and at the be   ginning it was a graph showing the tolerance of equipment to the size and duration of the disturb   ances in the power grid  Later  the curve was used to design equipment sensitive to voltage fluc   tuations as the reference range in which the equipment must operate properly  Finally the curve  began to be widely used in the analyses of power supply quality in terms of disturbances such as  swells  dips  interruptions     99    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Voltage  YoU rom       500     ANSI  ITIC     400        300        200        140     110   100     80                 r
40.  the  socket in the meter    The arrow located on one of the jaws indicates the current  flow direction  It is assumed that the current is flowing in the  positive direction if it is flowing from the source to the receiver   Such clamp orientation is required for a correct power meas   urement        Fig  58  C 4 clamp     Note  Currents above 1200 A must not be measured  The measurement time for currents above  1000 A shall be limited as follows     I lt  1000 A 1000 A  lt  I lt  1200 A    Operation mode continuous   15 minute measurement   then 30 minute break    0 For frequency f  lt  1 kHz  Limitation of maximum current for continuous operation for frequen     cies above 1 kHz according to the relationship Icon   1000 A f  KHz     Warning  Do not use the device on non insulated conductors with a potential of more than 600 V  in relation to the earth and a measurement category greater than III        e Reference conditions    e Temperature  20    26  C   e Humidity 20   75  RH   e Conductor position conductor centered in jaws  e Sinusoidal current frequency 48   65 Hz   e Harmonics content  lt 1    e Current DC component none   e Continuous magnetic field earth field   lt 40 A m    e Alternating magnetic field none   e Conductors in direct vicinity no flowing current    118    7 Equipment    e Technical parameters    7 2 2    The C 5 clamp is used to measure the alternating and  direct current without interrupting the circuit with the flowing  current  The measuring range 
41.  the following groups    e lightning surges   caused by atmospheric discharges    e oscillating transients caused most often by switching capacitor banks    e other switching transients  including ferroresonance      97    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual       P Transient  Transient L1 PE  Sf  Close    Save Print Copy to dipboard Export to csv  oar Wie  vere BB oe BB unre  g                           AB       2013 12 05 10 51 52 266    Value 1  U L1 PE  Difference 1 2  Value 2  U L1 PE  6 339 kV  Difference 2 3  Value 3  U L1 PE  Difference 1 3    2013 12 05  10 51 52 253   176 3 V    106us    2013 12 05  10 51 52 253    8 370 kV    2013 12 05  10 51 52 253   2 032 kV    nA       FOF          1 855 kV    ps                   Fig  51  Example of lightning surge     Surges caused by atmospheric discharges may have destructive effects due to the very high  energy triggered during the discharge  Most of surges of this type observed in networks  result  from voltage induced by close but not direct lightning stroke  In the area of lightning stroke  a very  strong electromagnetic field is generated and long overhead underground lines induce high volt   age that penetrate into the distribution network  These surges have pulse nature with rise time on  the order of microseconds  An example of the lightning impulse recorded by PQM 703 analyzer   with amplitude of approx  6 6 kV is shown in Fig  51     Tests of ICT devices carried out before introducing them into mar
42.  thresholds for all interharmon   ics in the range of 0   50    K Factor  max  1 0  50 0 Basing on 10 12 cycle value  Mains signaling  max  Basing on 10 12 cycle value    POM 703   POM 711 50   5000 V or dV dt Independent transient detection module   Voltage transients Amplitude or slew rate method    112       6 Technical data    6 6 1 Event detection hysteresis    Event detection hysteresis Calculation method    Hysteresis 0  10  For each of the parameters calculated as a per   centage of maximum threshold value  for excep   tions see 3 12        6 7 Recording    Recorder  Averaging time        Averaging min   max for Urms  Averaging min   max for IRms  Waveforms snapshot    Recording activation mode    Measurement Points    Recording time  Memor  Memory Model  a    200 ms  1s  3s  5s  10s  158s  305s  1 min  3 min  5 min  10 min  15 min   30 min  60 min  120 min    Special Mode    period  recording only    Urmsc1 2  and IRus 1 2         period  period  200 ms  1s 3s 5s         period  period  200 ms  1s 3s 5s     Option to record three periods of OS Ome for active channels  after each  averaging period   manual   starting at the first detected event   scheduled  four defined time intervals    memory card  the option to allocate the whole space to a given point  Depending on the configuration  see 2 7 3    Built in memory card 8 GB  as standard   option of extending up to 32 GB  Linear   Key lock to prevent unauthorized access  data read out lock with PIN         Averaging 
43.  to it    it is necessary to check whether the modem is turned on  To do this  select Analyzer   gt  Actual settings from the program menu and go to Wireless connections card  Check  whether GSM transmission available option is active   enable it if it is not    disconnect the USB connection and use buttons to select screen  lt 8 9 gt   If the modem is  switched on  but no SIM card is inserted  line GSM will show message  No SIM cara    insert SIM card into the slot on the side of the device The slot is of  push push  type  push  gently to remove the card   it will be pushed out by the device   The analyzer will detect  inserted card and will attempt to connect to the network    if PIN code of the SIM card has not been configured  the analyzer displays message   n   valid PIN code of SIM cara   This message will also be displayed on screen  lt 8 9 gt   It    2 Operation of the analyzer    means that the SIM card rejected PIN  which was used by the analyzer to attempt the  communication  This is normal when you insert a new card into the analyzer   To configure missing parameters required to perform GSM transmission  the user must  reconnect PC to the analyzer via USB and choose Options Analyzer database from  the program  In the analyzer database enter the option for editing the analyzer settings   click the line with the serial number of appropriate analyzer and click Edit   Click Change  GSM settings button   In the displayed widow enter the following data  IP number   in I
44.  transient is not important   both transients of small and large amplitude  will be detected  provided that the minimum rise requirement is met     3 11 Current limiting function    In situations where the measured current has very low values or measuring clamps were re   moved from the analyzer  resetting function may be useful for parameters related with the current  channel  This is particularly important for parameters such as THD  which in case of noise indicate  high and sometimes confusing values  When current clamps are disconnected during event detec   tion  then the analyzer almost instantly detect exceeding the threshold  which may mislead the  user  To avoid such situations  limiting function is introduced for current parameters  when RMS  value of the measured current is below the threshold specified by the user  To enable this function  check box  Current limit   located in the main settings of the measurement point  under the list of  clamp types  When the option is enabled  the user may specify the limit threshold as the percent   age of the nominal range of selected clamps   0 00 to 0 50  of Inom     Checking whether the current value is below the specified threshold  is carried out every  10 12 period window  approx  every 200 ms   If the RMS value of the measured current in the  channel is lower than the specified threshold  then the following parameters are zeroed    e RMS current   current direct component  DC    current crest factor   current harmonics i
45.  use programs other than Sonel Analysis        2 6 2 Radio communication via OR 1 PQM 702 PQM 703    After connecting OR 1 radio module to a PC  the user may communicate with the analyzer  using 433 MHz band  The range in this mode is limited to about 5 m  and the maximum rate data  of data transmission is 57 6 kbit s    Note  Before connecting to the analyzer through a wireless connection  OR 1 or  GSM   the user must add the analyzer to the database of analyzers  Op     tions  gt  Analyzer database in  Sonel Analysis    When searching for  analyzers  the list of displayed analyzers includes only those entered in  the database  For more information   see the manual for  Sonel Analysis         22    2 Operation of the analyzer    The radio interface that communicates with OR 1 receiver may be turned off in the analyzer   To switch it back on  use one of two remaining transmission modes  USB  or GSM     2 6 3 Communication via GSM network    The built in GSM modem ensures the access to the analyzer from any chosen global location  with available GSM network  The modem supports UMTS HSPA data transfer with maximum data  transfer rate of 5 76 7 2 Mbit s  upload download respectively   To operate this feature   insert a  valid SIM card to the side slot of the analyzer    The SIM card must have the following services activated   e General Packet Radio Service  GPRS    e static IP address   e SMS option to send alarm messages     In order to configure the SIM card and modem in the 
46.  vector of positive sequence component equals one third of the sum of the components   U44  aU yp  a Uc  Operator a and a    are unit vectors with angles of 120   and 240    The procedure  is as follow  turn voltage vector U g by 120   counter clockwise  multiply by a  and add to vector  U    Then  turn the vector Uc by 240   and add to the previous sum of vectors  The result is vector  3U   Vector Ut is the desired symmetrical positive sequence component  Note that in case of per   fect symmetry  equal voltages and angles  the positive sequence component is equal to the value  of the phase to neutral voltages    The positive sequence component is a measure of similarity of the tested set of three phase  vectors to the symmetrical set of positive sequence vectors    Similarly  the negative sequence component is a measure of similarity to the symmetrical set  of negative sequence vectors    The zero sequence component exists in the systems in which the sum of three voltages  or  currents  is not equal to zero    A measure of the system unbalance which is widely used in the power generation is the nega   tive Sequence and zero sequence unbalance  formulas are for voltage      U  Up   7   100   1    95    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    22 100   uU     0  2 U   where  uo     unbalance factor for zero sequence     uz     negative sequence unbalance    Uo     zero symmetric component    U      positive sequence symmetrical component   Us     negative sequenc
47.  with voltage waveform shift by 90     which gives a result close to the reactive power of the fundamental component    The higher the harmonics content  the higher difference in readings  and of course  as a con   sequence  other fees for measured energy    As it has been indicated before  the reactive power measurement in unbalanced three wire    83    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    systems with traditional meters is subject to an additional error caused by creation of a virtual zero  inside the meter which has little to do with actual zero of the receiver    On top of that  the manufacturers usually do not give any information about the applied meas   uring method    We may only wait for the next version of the standard  which will define  hopefully  the meas   uring and testing methods much more precisely  also for non sinusoidal conditions     5 3 5 Apparent power  Apparent power S is expressed as the product of RMS voltage and current     S   UI    As such  the apparent power does not have a physical interpretation  it is used during design   ing of transmission equipment  In terms of value  it is equal to maximum active power which can  be supplied to a load at given RMS voltage and current  Thus  the apparent power defines the  maximum capacity of the source to supply usable energy to the receiver     The measure of effective use of supplied power by the receiver is the power factor  which is the  ratio of apparent power to active power   In si
48. 0 4 15    1 12  Pir  5 X Eor   i 1    Long term flicker 3    where Psri is subsequent i th indicator of short term  flicker    Ep     gt  PDT  BOY for PO  0    oe   0 for P i   lt  0    oe X P_ i T i     IP i   for P i   lt 0  0 for P i   gt 20    Active energy  consumed   and supplied  P_ i    f  where   i is subsequent number of the 10 12 period measure   ment window  P i  represents active power P calculated in i th measur   ing window  T i  represents duration of i th measuring window  in  hours     Fore     Qg   TW    AO for QB  gt  0  0 for Qp i   lt  0    Eos    X  OTO    QG    for Qg i   lt 0  0 for QD   0    Qos       Budeanu reactive energy   consumed and supplied    Qp_ i    f    where    i is subsequent number of the 10 12 period measure   ment window   Qa i  represents Budeanu active power Qs calculated in  i th measuring window   T i  represents duration of i th measuring window  in  hours        4 Calculation formulas    For     Qu OTO    Q   i  for Q   gt 0  QC    0 for Q  lt  0    Eq    X Q OTO  Reactive energy of fun     i 1  damental component 0 _ i    ag   for Qa    lt 0   consumed and supplied    0 for Qi 20    where    i is subsequent number of the 10 12 period measure   ment window    Q  i  represents reactive power of fundamental compo     nent Q  calculated in   th measuring window   T i  represents duration of i th measuring window  in  hours     Fee   S T  i     where    i is subsequent number of the 10 12 period measure   ment window    S i  repres
49. 1 kHz   1  2 kHz   2  3 kHz    Phase error introduced by transducers and clamps may be usually found in their technical  documentation  In this case  we need to estimate the resultant phase error between the voltage  and the current for a given frequency caused by all elements of the measuring circuit  current and  voltage transducers  clamps  and the analyzer    The uncertainty of the harmonics active power measurements may be calculated according to  the following formula        Syn   100  1     222       cosp   0    coso    On the other hand  the uncertainty of the harmonics reactive power measurement may be cal   culated according to the following formula     dyn   100  1   Hete       sing   0    sing  In both formulas      means the actual phase shift angle between the current and voltage com   ponents  and Ag means the total phase error for a given frequency  The conclusion which can be  drawn from these relationships is that power measurement uncertainty for the same phase error    very clearly depends on the displacement power factor between current and voltage  It is shown in  Fig  57     109    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Example  Calculation of measurement uncertainty of active power fundamental  component   Conditions  Q  60    Urms   Ghorm 5 lRms  5  lor     Basic uncertainty is    1 02   Sbn       For the frequency range of 40  70 Hz  phase error of the analyzer is less  than 0 5    After substituting equation   _   cos pt A g   _ _   
50. 11 Operating Manual    e information about GPS position   2D   and or about receiving the correct GPS time  clock  icon      Screen 9  Fig  13  allows user to quickly view the main configuration parameters of the measure   ment point    e mains system    e clamps type    e nominal values of  voltage  current and frequency     System type  3 phase wye  Clamps   F x    Frequency   50 Hz  Unom   230 V       Fig  13  Screen 9 with information on the measurement point settings     PQM 710    POM 711 Screen 10 displays the current status of the wireless Wi Fi connection  Using   this screen  you can read    e radio signal level     indicated by icon F  where the number of green fields represents the  signal level from 0     none  to 4     high    e connection status  Ready  Getting IP address  Searching for network    e MAC address of the analyzer Wi Fi interface    e  P address of the analyzer in the Wi Fi network  If the address is automatically assigned  then  message   DHCP   is displayed    e SSID of the Wi Fi network  to which the analyzer is connected     Wi Fi   Ready    00 23 47 9B 2D 08  IP   192 168 100 141  DHCP     SSID    AP_BSO041       Fig  14  Screen 10 with information on the current status of Wi Fi connection  PQM 710 and  PQM 711 only      20    2 Operation of the analyzer    2 5  Sonel Analysis  software     Sonel Analysis  is an application required to work power analyzers of PQM series  It enables    the user to     configure the analyzer    read data from th
51. BR0O001   o IP assigned automatically by the access point  192 168 173 X  where X is in the  range of 2   254   gateway 192 168 173 1   o WPA encryption is active  the key is the same as SSID    Sonel Analysis software  tablet version  is installed on the tablet and starts automatically after  turning it on           b     9  A a wl    amp        Active media   y Connection settings Wl Serial Port    E crr over Gsm    WiFi        Active media  Serial port settings    A wri       Fig  32  Choosing active connection types    2 12 3 Enabling   disabling   configuring the Wi Fi access point in the tablet     e During direct connection  tablet    analyzer  the tablet acts as a Wi Fi access point   e The access point is configured at the production stage and starts automatically when Sonel    Analysis software is activated   e The user may change the configuration of the access point  and even turn it off     To change the access point settings  select from Program configuration menu option Media  Settings  and then from the list on the left side  select Wi Fi  Window shown in Fig  33 will be dis     played     46    2 Operation of the analyzer    Ga oR Ex      amp  be  wy 8 A iy  a w   a 4    Mode    connection settings ors  e E s0 OO O  eke ee BS0001    Active media Software based wireless access point    SSID  PEE eee Siem AP BSOO01  ame AP BSOO001       Fig  33  Wi Fi access point configuration    The window provides the following options   e    enabling disabling the access po
52. CIWOIK aroraa ra a ate R A ane 69  4 3 3 phase wye network with N CONCUCEHOLS         c cssscsccceeseeeeecseaneeeecseaneesessaaaanees 71  4 4 3 phase wye without N conductor and delta N tWOsKkS            cccccseeseeseeneeeeees 73   5 Power quality   a guide wsisit isa a ee 75  5 1 BaSIC IMO AUON i225 5 eitinta rat Wesabe a eS 75   5 1 1 Current Transformer  CT  clamps for measuring alternating currents  AC            75  D2 Clamps for measuring alternating and direct currents  AC DC              cccccssseeeeees 76  5 1 3 PICXIDIC CLANS e a dane auartenal ncn nce E EAA S AI 76  5 2 FUCK ea ioe tate con DOA ta des Ane eat taee tats toate aoa as MnP pega ne ana Gatos at aes aaaena 77  5 3 Fo  wer measurement  osne EEEE E E E 78  5 3 1 ACUVE DOW CF re SAE A A EAA TEE ATE AA EEATT 78  5 3 2 FICACIIVE DOWEL ai 8 oii alates le a a timed leah coasted ea a ae a s wages 79  care pro Reactive power and three wire SYStCINS          cccccccseeeeeeceeeeseeceeeeeeseaaeeeeeeesssaaaeseeees 82  5 3 4 Reactive power and reactive energy Meters          ccccseeceeceneeeeeeeaeeeeeneaeeeeessaeneenes 83  5 39 95 APPA CHT POW CN Gases ts Te E T A ER ENE E E EE 84  5 3 6 Distortion power Dg and effective apparent power Sen     ccssseccccecccccnseeceneeensesesenes 85  5 3 7 FOWE ACIOn EE E E E N a 86  5 4 PATIO CS r renare A O A 86  5 4 1 Harmonies active DOW CI  arra e e a E EE E E N E E atuateecce 87  5 4 2 Harmonies Teave DOW EM yie sa D E sod tea a Oseln ea ube ad 88  5 4 3 Harmonics in three phas
53. M 711 are class A products  In a domestic environment these products may  cause radio interference in which case the user may be required to take adequate measures        6 14 Standards       116    7 Equipment    7    7 1  The    Equipment  Standard equipment    standard set of equipment supplied by the manufacturer includes    Permanently fixed cables  2 2 m  with banana plugs  7 pcs    K01 crocodile clip  black  3 pcs    WAKROBL20K01    K02 crocodile clip  blue   WAKROBU20K02    crocodile clip  yellow KO2     WAKROYE20K02    red crocodile clip  2 pcs    WAKRORE20K02    phase splitter AC 16   WAADAAC16    mains plug with banana inputs  L1 and N  for connecting the analyzer to a socket in order to  charge the battery and or carry out data transmission from a PC   WAADAAZ1   software for data reading and analyzing  Sonel Analysis     USB cable   WAPRZUSB     USB wireless module OR 1      WAADAUSBORI1     POM 702  PQM 703  a case for the analyzer and standard accessories     WAW ALXL2    band for mounting the device on a pole  2 pcs    WAPOZOPAKPL    bracket for mounting the analyzer on DIN  ISO  rail with stabilizing connectors      WAPOZUCHS    connectors for bands used for mounting the device on a pole  2 pcs   WAPOZUCH4    voltage adapter with thread M4 M6  5 pcs  used to connect voltage wires to rail connectors in  switchboards   WAADAM4M6    magnetic adapter  4 pcs   used to connect voltage wires to overvoltage switches type S and  circuit breakers and RCDs in switchboar
54. Pv4 field  it should be  provided by the service provider  APN  username and password  if required and provided  by the service provider   Confirm new data by pressing OK   Then a pop up will be displayed  asking you to enter PIN code of the SIM card  Enter the  code supplied with the SIM card and confirm it by clicking OK   If you have entered the correct data  the analyzer will use it to properly log into the GSM  network  The connection status may be checked in screen  lt 8 9 gt  of the analyzer  USB  session must be disconnected   Correct connection is indicated by GSM status   Ready    lt connection type gt     lt connection type gt  depends on the location and type of data trans   mission services in the area   the correct order of the messages displayed on screen  lt 8 9 gt  when connecting to GSM  network is as follows    o Turning on     Connecting to the network     Connecting to the Internet     Ready   lt connection type gt     O O 0          88 28    E Certificate of Calibration    PQM 702 2013 01 09    D 192 125 41 236 4001    PQM 702  py 2013 02 11 oe  PQM 702 o  2013 02 11    PQM 702 2013 02 05  n    12 months v    Registered devices    Analyzer type ipti Date of calibration Auto PIN  SIM Active  IP Address       PQM 702 2013 02 01                      PQM 702       Analyzer type  Serial number        Edit analyzer description  GSM settings    IPv4   AZ0012    Date of calibration  Port     09 01 2013 ba APN     Expiration reminder     Expira User name     Desc
55. QM 702  PQM 703  PQM 710  PQM 711 Operating Manual    e Limitation of maximum current for continuous operation for frequencies above 1 kHz ac   cording to the relationship  lcont   1000 A f  kHz     e Switching on  To switch on the clamp  put the switch in the 1 mV A position  Green LED indicates the  correct operation  If after switching the LED is not lit or goes off  replace the battery     e DC zero indication correction  Make sure the jaws are closed and there is no conductor inside them  Then  connect  the clamp to the analyzer and launch the    Sonel Analysis    software in the instantaneous  values viewing mode  check if the measurement point is correctly configured for meas   urement with the C 5 clamp   Press the knob and turn until the DC current indication is  zero     e Reference conditions    e Temperature   18    28  C   e Humidity  20   75  RH   e Battery voltage  9V 0 1V   e Conductor position  conductor centered in jaws   e Current  direct  DC  or sinusoidal  AC  f  lt  65 Hz  e Continuous magnetic field  earth field   lt 40 A m    e Alternating magnetic field  none   e Conductors in direct vicinity  no flowing current    e Technical specification  e Accuracy     800   rane  tae       Basic uncertainty        lt 15  1A    1 as   of measured value    e Phase error  45   65 Hz      Current  10   200 A   200   1000 A       e ratio  1mV 1A   e frequency range  DC   5 kHz   e output impedance  100 Q   e DC zero adjustment range   10A   e noise  DC up to 1 kHz   l
56. S esis A E E E eeaeanaridataee ee 56  3 2 CUEN IOPU sees ass sched TEE E dente ncnsdansanecd  ndenbaddndenacsaasnded  56  3 3 BIHAR WATE GCAO sae a a clea a ae plas als end tal a ie ewes ae a 56  3 4 SIGHAl Sal PUING ass  fia cicada tata aaah a E gee d eased tae ees  57  3 5 PE LSS VACHIOMIZAUOM crete an  aieccstoa rescence a doses teccshsasal ease a R 57  3 6 Frequency MEASUSCINENN        ccsccccccseseecnacececseneeccseeecnaceeessauseensnesssansnessanesess 58  of The method for measuring harmonics        11ccccccseeceecsssnessecssaneeeecssaneesesssanenees 58  3 8 The method for measuring INTEFNALMONICS         1 ccccecesneeeeeeeaneeeeeeeaeenesseaneeees 59  3 9 Measurement of ripple control SIQNAIS           1 cccccseeeccenseeeeaneeeseaneeessaeseessneneees 60  3 10 Measurement Of transients         cccccccccccceecceeenseeesseceeessuessesesseessnessnsenesseneseess 60   3 10 1 Tiesha MENO peerecen ter err re renre ey yerre renee ttre ee reer eroeere eryeeterrntre ret ery reper er scrrertenrrerere 62  3 10 2 DIOW Ale  aV an meo o let teed EE EEN E AA EET 62  3 11 Current limiting function          sceeeccccccccesseseeeceescasneeeseceessessueueesecessssaaaeeeeeeseaas 62  Ole HEVENUOCICCHON erien ENG 63  3 13 Methods of parameters averaging         1 ccccsescccsneeecsaeeeessnesessaueeessaeeessanenessaes 65   4 Calculation formulas sisiocecvsccecsxxnacctsvssctecadee vedas tacseen sevavedeoussctesnesesedieuss 66  4 1 ONE DAASSNGIWONK susien ern E E E E ATE ance  66  4 2 SDII DNASC N
57. S0003          WiFi settings    Addresses     Automatic  DHCP    manual IP Address  192    i68    173_ 250  01 01 1970  NetMask  255    255    255   p Gateway  1920  fei i730     Description  MAC Address oo   jos _  port    BB External 1p address External Port 4002    Om oe       Fig  35  Example configuration of Wi Fi connection for direct or local network  communication    e Select the method for assigning IP address  In case of manual mode     enter appropriate  values into fields  IP Address  Net Mask and Gateway  In automatic mode  select DHCP    e With USB connection  MAC Address field will be filled in automatically  as read from the  analyzer     e Port field is not editable  it is always 4002    e Incase of operating in other subnetworks  the Internet   fill in External IP Address and Ex   ternal Port fields  For a direct connection  tablet  lt  analyzer   and for working in a local  network  tablet    Wi Fi router   analyzer  these fields must be left inactive    e If the analyzer has a static IP address  the search time may be shortened  To do this  enter  IP address of the device in External IP Address field and enter  4002  in External Port  field    e Confirm the settings by pressing OK  This will send new data entered in fields  SSID  Key   IP configuration  to the analyzer    e lf the correct data have been entered  the analyzer will try to connect to Wi Fi access point   After disconnecting  the connection status may be followed on screen  lt 10 10 gt      Th
58. The analyzer that is chosen for the connection must be entered into the Analyzer database   when the configuration was performed as described in sec  2 12 4 this will be ensured     e Disconnect any connection to the analyzer  USB  GSM     e Perform a search for the analyzer  selecting any available method  e g   by clicking Live  mode   The search list should show the analyzer with note  Connection via Wi Fi   Select the  analyzer and click OK    e After a while  the screen should display the desired window  e g  Live Mode  and the status  bar should display  Connectea  message  Also the analyzer screen will display  Connected  to PC  Wi Fi   message  The connection attempt was successful     2 12 7 Possible problems with Wi Fi settings and troubleshooting    Problem  The search progress bar quickly reaches 100  and no analyzer is found    Possible cause  It may indicate that Wi Fi search is disabled in program settings or in the  analyzer database    Solution  From program menu select Options gt Program     configuration gt Media  settings gt  Active media  Wi Fi box should be ticked     Problem  The search progress bar quickly  in a few sec   reaches 100  and no analyzer is found   Possible causes   1  The analyzer is turned off or its Wi Fi connection is inactive not configured   2  MAC address of the analyzer does not match the address entered into the database of  analyzers     51    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    3  IP addresses of the analyzer 
59. ae plied   Eoin  Ea1  Reactive energy  consumed and  Eas   Eae  supplied    Es Apparent energy  Uni  Uhs0 Voltage harmonic amplitudes  Int  Ih50 Current harmonic amplitudes    Angles between voltage and current  Qun   Quiso 5  harmonics  Phi  Phso harmonics active power    U  Upc  lbc  F  Q    QB  S  PF          _   lt         oh     CE eee eeehe    Symmetrical components and unbal   TID   Current total interharmonic distortion  Uino  Uinso Voltage interharmonics amplitudes  PQM 703  POM 711 Voltage transients      Explanations  L1  L2  L3  L12  L23  L31  indicate subsequent phases  TOT is the total value for the system    1  In 3 wire networks  the total reactive power is calculated as inactive power N   4S2     P     lino   linso Current interharmonics amplitudes  N is a measurement for voltage channel N PE or current channel In  depending on the parame    see discussion on reactive power in section 5 3     UR1  UR2 Mains signalling in voltage  ter type    2  Voltage transients are measured in channels  L1 PE  PE L2  L8 PE and N PE     PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    1 7 Compliance with standards    The analyzer is designed to meet the requirements of the following standards    Standards valid for measuring network parameters    e IEC 61000 4 30 2008     Electromagnetic compatibility  EMC    Testing and measurement  techniques   Power quality measurement methods    e IEC 61000 4 7 2007     Electromagnetic compatibility  EMC      Testing and Measuremen
60. alue  T   period for which  the power is calculated     In sinusoidal systems  the active power may be calculated as   P   UlIcosp  where  U is RMS voltage    is RMS current and   o is the phase shift angle between voltage and  Current     The active power is calculated by the analyzer directly from the integral formula  using sam   pled voltage and current waveforms     78    5 Power quality   a guide    M  1  P     gt  U l   i 1    where M is a number of samples in 10 12 period measuring window  2048  and U  and l  are suc   cessive voltage and current samples     5 3 2 Reactive power    The most known formula for reactive power is also correct only for one phase circuits with si   nusoidal voltage and current waveforms     Q   Ulsing    Interpretation of this power in such systems is as follows  it is the amplitude of AC component  of the instantaneous power on source terminals  Existence of a non zero value of this power indi   cates a bidirectional and oscillating energy flow between the source and the receiver    Imagine a system with a single phase sinusoidal voltage source  where the load is a RC cir   cuit  As under such conditions  these components behave linearly  the source current waveform  will be sinusoidal  but due to the properties of the capacitor it will be shifted in relation to the volt   age source  In such a circuit  reactive power Q is non zero and may be interpreted as an ampli   tude of the energy oscillation  which is alternately stored and returned
61. analyzer  press ON OFF button  Directional but   tons LEFT and RIGHT are used primarily to change the information screens  The screens change  circularly  i e  after pressing RIGHT button  when the last screen is displayed  the device goes to  screen 1  After pressing LEFT button  screens are displayed in reverse order  START STOP but   ton is used to start and stop the recording as defined in the configuration of current set point     2 2 Switching the analyzer ON OFF    e The analyzer may be switched on by pressing button cop Then a welcome screen is  displayed  showing the name of the meter  the internal software version  firmware   hardware  version and serial number  Then  the analyzer performs a self test and in case of detecting  errors  the display shows an error message  accompanied by a long beep  When an error  occurs during memory card launching  the following message is displayed  Memory card  error   If the file system on the card is damaged  e g  when the user manually formatted the  card as mass storage memory accessible only for the user  the analyzer will suggest    formatting the memory  message  Format memory card    and button G will trigger the  process of formatting  3 short beeps   After the formatting is completed  the analyzer will  repeat initialization of the card    e When during the card initialization  the analyzer detects FIRMWARE PQF file in the root  directory  which includes a newer version of the firmware  internal software   the upgrade  p
62. analyzer  the user must obtain the fol   lowing data from the data transmission service provider   e PIN code for SIM card  e PUK code for SIM Card   for emergency cases  when SIM card is locked after repeat   ed attempts of enter wrong PIN   e  P number assigned to SIM card  it must be a static number    e APN  Access Point Name    e user name and password  optional  usually not required      After inserting the SIM card for the first time into the analyzer  the device will attempt to use  the PIN entered last time or the default code  Usually  such an attempt fails  and the analyzer dis   plays the message about incorrect PIN code  To enter the correct data  establish a connection  with the analyzer via USB  or OR 1  and configure a GSM connection  The procedure described  in chapter 2 11 2  If the analyzer is configured correctly it will attempt to connect to the GSM net   work and then to the Internet  The analyzer will now be visible on the Internet with assigned IP  number  The device will wait for incoming connections using port 4001  Such connection may be  established by  Sonel Analysis    If the GSM modem will not be used  it may be turned off using the program    More information about the analyzer configuration for GSM communication is presented in  chapter 2 11     2 6 4 Radio communication via Wi Fi LL CUD    PQM 710 711 analyzers are equipped with Wi Fi module working in IEEE 802 11 b g standard  and n single stream  access points with a single antenna   This a
63. ancial settlements between the electricity supplier and consumer is  electric energy calculated as the product of power and time    In electrical engineering  several different power types are distinguished    e Active Power   marked with P and measured in Watts    e Reactive Power   marked with Q  unit  var    e Apparent Power  S  unit  VA    These three types of power are the most known  but there are also other types    At school we are taught that these powers form the so called    power triangle    with properties  expressed in the equation     P    Q    S     This equation  however  is valid only for systems with sinusoidal voltage and current wave   forms    Before moving to a more detailed discussion concerning power measurement  individual types  of power should be defined     5 3 1 Active power    Active power P is a magnitude with precise physical meaning and it expresses the ability of a  system to perform a particular work  It is the power most desired by the energy consumers and it  is for this supplied power that the consumer pays the supplier in a given settlement period  the  problem of fees for additional reactive power is discussed separately     see below   It is the active  power  and consequently  the active energy  which is measured by electric energy meters in each  household    The basic formula for calculating the active power is as follows     t T    P     u t i t dt    t    where  u t      instantaneous voltage value  i t    instantaneous current v
64. ansmission       ccccccccssseeeseecceseceseeeseceesessueeeseseessees 21   2 6 1 USB COMMU CAMO sssrds iperen a E AEE E decals 22  2 6 2 Radio communication via OR 1 POM 702  POM 703  PEENE EEIN A EE A A S 22  2 6 3 COMMUNICATION via GSM network      eecccccccssseececcccccsseeeeeecesseasneeeseeesssanceseesssseeseees 23  2 6 4 Radio communication via Wi Fi cui cui EN AVINI TNEI N 23  2 7 TAKING measurements        1ccccscceccceesecnsuecccsauecenscusecsauseessaussenscasessauseessansesnaes 24  2 7 1 Measurement Points         cccccccscccccscccenscueenseneecscueensenuenscueenscueenscusensausenscasensnasensees 24  2 7 2 Start   stop OF FECONM ING  tuterctstessarsiisinadiredtenhindadenettcdiencnbendencntectind EEEE ETES 25  2 13 Approximate recording times        cccccecccseccccscececsceeecaceeecscueecscaeessaeesscasensusenseanenses 25  2 8 Measuring CIPCUIES        1cccccscececnsneeecsanececsuuseenauseecsauseessaseessaueesnsseessaeeessauesess 27  2 9 EXAMS OF USE a E E E E sed  33  210 Time SynenNonizaloN ossen E SEE E E 38  2 10 1 Requirements of IEC 61000 4 30        ccccccsssseseccscsescccscnsescssauseeecsacseseenaeeessennseenss 38  2 10 2 OF TECA    a E E A E 38  2 10 3 Data a009 CONCE aiena E E 38  2 10 4 Time TOSVICHIONIZAUON ssis iinei nE SE AE E r EEEE 39  2 11 GSM COMMUNICATION MOUS  amp  ascscccnccccctssveceseteccccatseveneecseecssvesernesnodaadevetnesoncoasee 39  2 11 1 General information about GSM CONNECTION            1    cceeeeeeeeeeeeeeeeeeeeenaananeeeneeeeeees 39 
65. approximation can be  allowed only after a clear reservation that the indicated value is not a result of actual measure   ment  but only an approximated value     82    5 Power quality   a guide    5 3 4 Reactive power and reactive energy meters    Reactive energy meters are devices unknown to the household users who for settlements with  energy suppliers use the meters of active energy expressed in Wh or kWh  Household users are  in a comfortable situation     they pay only for usable energy and do not have to think what the  power factor is in their installations    In contrast to the first group  the industrial consumers are obliged in their contracts and some   times under pain of financial penalties to keep the power factor at an appropriate level    The EN 50160 standard gives some guidelines for the power quality requirements  and de   fines the quality parameters which should be met by energy supplier  Among these parameters  are  among others  mains frequency  RMS voltage  total harmonic distortion  THD  and allowed  levels of individual voltage harmonics  Besides EN 50160 requirements there is often an addition   al condition  the supplier does not need to comply with those requirements if an energy consumer  does not ensure the tang factor below some threshold  agreed value which can be changed in the  contract between the energy supplier and consumer  i e  0 4  and or exceeds the agreed level of  consumed active energy    The tang is defined as a ratio of measured
66. armonic  460 Hz  10  Unom   The apparent change in the voltage envelope with frequency of 10Hz  that may cause flicker  Unom   230 V RMS  50 Hz      5 5 1 Total Interharmonic Distortion  A measure of the total presence of interharmonics is the TID  which is defined as     Fn A  TID    E 100   1    Fn A  TID    E x 100   RMS    where  7 D    Total Interharmonic Distortion related to fundamental component   TID    Total Interharmonic Distortion related to RMS value   Ain     RMS of ih th interharmonic  interharmonic sub group    A      RMS of the fundamental component   Arms     RMS of the waveform   n   incase of analyzers described in this manual it is equal to 50     TID is the ratio of the RMS value of all interharmonics to the fundamental component  for TIDF  or  RMS value  for TIDp     Acceptable level of interharmonic interferences in voltage is a matter discussed among pro   fessionals involved power quality matters  Some sources state that the overall rate of voltage  interharmonics distortion should not exceed 0 2      5 6 Mains signalling    Ripple control signals are signals entered into the electricity network in order to control and  check of remote control devices connected to the same network  In addition to the transmission of  electricity  a distribution network is in this case used as a transmission medium for communication  between devices  EN 50160 standard distinguishes three types of signals    e Ripple control signals from 110 to 3000 Hz     92    5 Powe
67. armonics     88    5 Power quality   a guide    The sign of the individual power components indicates the character of load for this compo   nent  When the sign is positive      then the character is inductive  and when it is negative      it is  Capacitive    Passive source current may be reduced to zero when the following condition is met for each  harmonic       B    Byn  0  where   B      receiver susceptance for the h th harmonic   Bp     parallel compensator susceptance for the h th harmonic     As the compensator complexity grows proportionally to the number of harmonics subjected to  compensation  usually only the fundamental component is compensated and maximum a few  higher harmonics with the largest values  However  the compensation of the fundamental compo   nent may considerably improve the power factor and may be sufficient     5 4 3 Harmonics in three phase systems    In three phase systems  harmonics of given orders have a particular feature which is shown in  the table below        2  3   4  5   6   7  8   9    Taney PEE rey oo       Sequence      positive        negative   0 zero      Sequence  line refers to the symmetrical components method which allows to decompose  any of the three vectors into three sets of vectors  positive  negative and zero sequence  more in  section related to unbalance     For example  Lets assume that a three phase motor is supplied from a balanced  4 wire  mains  RMS phase to neutral voltage values are equal  and angles between t
68. arted  the aggregation interval  x  is termi   nated normally  until the specified number of 10 12 cycle windows are gathered  e g  for 3 second  averaging  always 15 intervals are gathered   The re synchronization results in generating Over   lap 2  see Fig  55   where data from two aggregation intervals are simultaneously processed    x    interval ends   x 1  interval starts   The size of the overlap depends on fluctuations in the mains  frequency    The time stamp corresponds to the end of the aggregation interval     Averaging of measurement results leads to the loss of extreme values  Smoothing of results    In cases when the information about limit values of the measured parameter is important  the user  may use the option of measuring the minimum  maximum values in the averaging period  If a giv   en parameter is measured in the 10 12 cycle time  the minimum and maximum value is respec   tively the smallest and the largest 10 12 cycle value measured in a given averaging interval  On  the other hand  the instantaneous value is the last 10 12 cycle value in this averaging interval    In case of RMS current and voltage  the method of searching for minimum and maximum val   ues is more flexible and it is controlled by Min Max calculation period parameter  The user may  choose from the following options  half period  200 ms  1 s  3s and 5s  If the half period option is  selected  the minimum and maximum values will be searched for with the highest sensitivity     up  to Ur
69. attern while de   signing their products  in order to ensure their reliable operation and maintaining proper output  voltage  Note  however  that the curve represents typical cases and cannot be a guarantee of cor   rect operation for each device  as tolerance for interferences is very different    ITIC curve is the successor of the CBEMA curve developed by ITI in 1994  and later modified  to its present form in 2000  This curve has the form of two broken lines and is also known as ANSI  curve  as it was adapted by ANSI  American National Standards Institute   Both curves are pre   sented in Fig  53     Sonel Analysis  software provides the ability to modify the characteristic points of the curves  allowing user to adjust them to individual requirements     100    5 Power quality   a guide    5 11 Averaging the measurement results    Mains monitoring over a longer period means that a significant amount of data needs to be  collected  To ensure that such data analysis is possible at all  it is necessary to introduce the  mechanisms for reducing data size to the values acceptable by both  people and machines    Let us take the example of EN 50160 compliant power quality measurements The basic mains  test period is one week  If all 200 millisecond RMS values were to be remembered  we would get  3 024 million measurements  Processing this amount of data may be time consuming and difficult    Therefore  the averaging concept has been introduced which involves recording one value p
70. bles   Weight approx  1 6 kg  Display color LCD TFT  320x240 pixels  diagonal 3 5     built in memory card 8 GB  as standard   option of extending up to    Data Memory 32 GB       6 13 Safety and electromagnetic compatibility    Safety and EMC  Compliance with IEC 61010 1    Ill 1000 V IV 600 V  pollution class 2   Measurement category acc  to IEC 61010 1    Insulation  Electromagnetic compatibility  IEC 61000 4 3   sinusoidal modulation 80  AM  1 kHz   80   1000 MHz  10 V m   1 4   2 0 GHz  3 V m   2 0   2 7 GHz  1 V m    Immunity to electrostatic discharge IEC 61000 4 2  Air discharge  8 kV  Contact discharge  4 kV    115    Immunity to radio frequency interferences       PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    IEC 61000 4 6    Immunity to conducted disturbances  in  sinusoidal modulation 80  AM  1 kHz    duced by radio frequency fields 0 15   80 MHz  10 V    IEC 61000 4 4  Immunity to series of fast transients bursts Amplitude 2 kV  5 kHz    panne 1o Surges Amplitude 2 kV  L L   4 kV  L PE   IEC 61000 6 3  PQM 702  PQM 710  class B   30   230 MHz  30 dB uV m  at 10 m  Emission of radiated RF disturbances 230   1000 MHz  37 dB uV m  at 10 m  PQM 703  PQM 711  class A   30   230 MHz  40 dB uV m  at 10 m  230   1000 MHz  47 dB uV m  at 10 m  IEC 61000 6 3  Levels for a quasi peak detector   Emission of conducted disturbances 0 15 kHz   0 5 MHz  66 dBuV   56 dBuV  0 5 MHz   5 MHz  56 dBuV  5 MHz   30 MHz  60 dBuV    EN 55022 Compliance statement   PQM 703 and PQ
71. c components up to the 50th order  the harmonics of the 50th or 40th order are used to cal   culate THD  the user can select either 40  or 50  order as the limit     Please note that when the waveforms are very distorted  the two definitions presented above  will give significantly different results  THDR cannot exceed 100   while THD  has no such limit  and may be 200  or more  Such a case may be observed when measuring very distorted current   The voltage harmonic distortion usually does not exceed a few percent  both THD  and THDp      90    5 Power quality   a guide    e g  EN 50160 standard defines the limit of 8   THDr      5 4 5 K Factor    K Factor  also called the transformer loss factor is a measure used in determining the re   quirements for power transformers  Higher harmonics in current cause increased heat losses in  windings and metal parts of the transformer  The main reasons is the presence of eddy currents  generated by current components of higher frequencies and by the skin effect    The transformer temperature increase is directly proportional to current components squared   the value called K Factor takes this into account  and the factor is calculated according to the fol   lowing formula     50  KFactor    gt  Lhe    h 1    50 22  h 1 Ihh    I    where  ly  relative value of the h th order harmonic component  in relation to the fundamental  component    l    amplitude of the h th order of current harmonic component   l     amplitude of current fundamen
72. category acc  to IEC 61010 1     double  according to IEC 61010 1  III 1000 V    IP 65   15 5 mm   30 mm   F 1  120 cm   F 2  80 cm   F 3  45 cm   F 1  360 mm   F 2  235 mm   F 3  120 mm   F 1  about 410 g  F 2  about 310 g  F 3  about 220 g  2m    20  C    80  C   IEC 61000 6 3 2008  IEC 61000 6 2 2008    1575 42 GHz   RHCP   26 dB  3 V     lt 1 2 1   14 0 x 34 2 x 38 2 mm   40  C    85  C   IP 67   10m   15   25 mA    magnetic  any surface    Fig  65  External GPS antenna     125    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    8 Other Information    8 1 Cleaning and maintenance    Note    Use only the maintenance methods specified by the manufacturer in this  manual        The casing of the analyzer may be cleaned with a soft  damp cloth using all purpose deter   gents  Do not use any solvents or cleaning agents which might scratch the casing  powders   pastes  etc      Cables should be cleaned with water and detergents  and then dried    The analyzer electronic system does not require maintenance     8 2 Storage    In the case of storage of the device  the following recommendations must be observed    e Disconnect all the test leads from the meter    e Clean the meter and all its accessories thoroughly    e In order to prevent a total discharge of the accumulators in the case of a prolonged storage   charge them from time to time     8 3 Dismantling and utilization    Worn out electric and electronic equipment should be gathered selectively  i e  it must not be  
73. ceiver    A GPS receiver and antenna is installed inside the analyzer  in order to receive GPS signal  outdoors without any additional accessories  The antenna is installed in the lower left corner of the  casing under the top cover  in a place where GPS logo on the sticker is applied   To enable the  time synchronization of the analyzer inside buildings  the analyzer must be connected to an exter   nal antenna  optional accessory   with a cable of 10 m and installed outside of the building  The  analyzer detects the external antenna and switches into the receiver mode instead of using addi   tional internal antenna    GPS synchronization time depends on weather conditions  clouds  precipitation  and on the  location of the receiving antenna  The antenna should be provided with high  visibility  of the sky  in order to obtain the best results  To read the time with the required accuracy  the GPS receiver  must first determine its own current geographical location  it must  see  at least 4 satellites   posi   tion and altitude   After determining the position and synchronizing time to UTC  the receiver en   ters the tracking mode  To ensure time synchronization in this mode  the visibility of only one GPS  satellite is required  However  to determine the analyzer position  when it is moved   still four sat   ellites must be available  seen   3 satellites if GPS does not update the altitude data   This is im   portant for example in anti theft mode  when the device needs contin
74. cker    In terms of power quality     flicker    means a periodical changes of light intensity as a result of  fluctuations of voltage supplied to light bulbs    The flicker measurement function appeared in the power quality analyzers when it turned out  that this phenomenon causes discomfort  irritation  sometimes headache  etc  The luminous in   tensity fluctuations must have a specified frequency  they cannot be too slow  as the human pupil  is able to adapt to changes in illumination  they cannot be too fast because the filament inertia  eliminates these fluctuations almost totally    Studies have shown that the maximum discomfort occurs for frequencies around 9 changes  per second  The most sensitive light sources are the traditional light bulbs with a tungsten fila   ment  Halogen bulbs  which filaments have much higher temperature  have also much higher iner   tia  which reduces the perceived brightness changes  Fluorescent lamps have the best flicker  re   sistance   as due to their specific properties they stabilize the current flowing through the lamp  during the voltage changes  and thus reduce the fluctuations    Flicker is measured in perceptibility units  and there are two types of flicker  short term Px   which is determined once every 10 minutes and long term Pi  which is calculated on the basis of  12 consecutive Py values  i e  every 2 hours  Long time of measurement results directly from the  slow changing nature of this phenomenon   to collect sample data 
75. ctive power designated as N  Reactive power has been limited only to the funda   mental component and marked as Q4    This standard is the last document of this type issued by recognized organization which was  to put the power definition issues in order  It was even more necessary as for many years special   ists in scientific circles reported that the power definitions used so far may give erroneous results   Controversies concerned mainly the definition of reactive power and apparent power  and distor   tion power     see below  in single  and three phase circuits with non sinusoidal voltages and cur   rents    In 1987  professor L S  Czarnecki proved the widely used definition of reactive power defined  by Budeanu was wrong  This definition is still taught in some technical schools and it was pre   sented by prof  Budeanu in 1927  The formula is as follows     Qg    gt  UnIn sin Pn  n 0    where U  and h are voltage and current harmonics of order n  and   n are angles between these  components   79    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    When this parameter has been introduced  the known power triangle equation was not valid  for circuits with non sinusoidal waveforms   therefore Budeanu introduced a new parameter called    the distortion power   Das  s2      P2   Q5        Distortion power strain was meant to represent powers occurring in the system due to distort   ed voltage and current waveforms    For years  reactive power was associated with the en
76. d formulas could no longer be tolerated    A very significant event was publishing by IEEE  in 2000  1459 standard  Definitions for the  Measurement of Electric Power Quantities Under Sinusoidal  Non sinusoidal  Balanced  or Unbal   anced Conditions   For the first time  Budeanu   s definition of reactive power has been listed as  not recommended for new reactive power and energy meters  Many parameters have been also  divided into the part related to the current and voltage fundamental component  first harmonics   and the part related to remaining higher harmonics  In most cases  it is recognized that the usable  part of energy is transmitted by the 50 60Hz components  with much smaller  and often harmful   participation of higher harmonics    The standard also introduced a new parameter     non active power N which represents all    non active components of power   N   yS      P     Reactive power is the power of one of the components of the inactive power N  In single   phase systems with sinusoidal voltage and current waveforms  N equals Q  hence the non active  power does not have any other components  In three phase systems  this is true only for symmet   rical sinusoidal systems with a balanced purely resistive load     Other non active power components are related to specific physical phenomena  According to  prof  Czarnecki   s theory  which is one of the best in explaining the physical phenomena in three   phase systems  the power equation in such systems is as foll
77. dditional transformers and clamps    e Abbreviations    e m v    reference measured value    Unom     Nominal voltage    lhom     nominal current  clamps     RMS     root mean square value    n     harmonic order    Sph     additional uncertainty caused by the error of phase measurement between the volt    age and current harmonics     6 1 Inputs    Voltage input terminals  Number of inputs 5  L1  L2  L3  N  PE   4 measuring channels  not galvanically isolated  Maximum input voltage 760 Vams    Peak input voltage  no ADC 1500 V  high voltage range   clamping 450 V  low voltage range    1500 V  high voltage range        Range of measured DC voltages  450 V  low voltage range     Number of inputs  Nominal input voltage  CT clamps   Peak input voltage  CT clamps   Analog pass band   3dB     Inout Impedance CT clamps circuit  100 kQ    Flexible clamps circuit  12 4 kQ    Flexible clamps F 1 F 2 F 3  1  3000 A  410000 A peak  50 Hz   Measurement range  without Hard clamps C 4  C 5  1  1000 A   3600 A peak   transformers  Hard clamps C 6  0 01  10 A   36 A peak    Hard clamps C 7  0  100 A   360 A peak   Transducers    6 2 Sampling and RTC    Sampling and RTC  A D converter 16 bit    Samoplina rate 10 24 kHz for 50 Hz and 60 Hz  eae Simultaneous sampling in all channels    Samples per period 204 8 for 50 Hz  170 67 for 60 Hz       PLL synchronization 40  70 Hz  Reference channel for PLL     3 5 ppm max  approx   9 sec  month   in the temperature range of  20  C    55  C    Real tim
78. der harmonics are of minimal value  If we consider this property  it turns out  that the group of harmonics with the most undesirable properties is the 3rd  9th  15th  zero se   quence   and the 5th  11th  and 17th  negative sequence     The current harmonics which are multiples of 3 cause additional problems in some systems   In 4 wire systems  they have a very undesirable property of summing up in the neutral conductor   It turns out that  contrary to other order harmonics  in which the sum of instantaneous current val   ues is zeroed  the waveforms of these harmonics are in phase with each other which causes add   ing of the phase currents in the neutral conductor  This may lead to overheating of this conductor   particularly in the distribution systems where the conductor has a smaller cross section than the  phase conductors  as it was widely practiced until recently   Therefore  in systems with non linear  loads and large current distortions  it is now recommended that the cross section of neutral con   ductor is larger than that of the phased conductors    In the delta systems  the harmonics of these orders are not present in the line currents  provided  these are balanced systems   but they circulate in the load branches  also causing unnecessary  power losses    The nature of individual harmonics as shown in the table is fully accurate only in three phase  balanced systems  Only in such systems  the fundamental component has the exclusively positive  sequence charact
79. do not match the address entered into the database of ana   lyzers  Internet connection     4  Fields External IP Address and External Port are active in the database of analyzers  in  case of direct connection tablet  lt  analyzer or for work in the same network   5  The analyzer has active Wi Fi connection with another client or temporary network prob   lems    Solution    1  When the analyzer is available check the Wi Fi status on screen  lt 10 10 gt   If the status is   Disabled   then select  Analyzer  gt  Actual settings from the program menu  go to Wire   less connection card and check whether Wi Fi communication enabled is enabled  if  not  enable it   Check Wi Fi settings    2  Check whether the correct MAC address is entered to the database of analyzers  MAC  address is displayed on screen  lt 10 10 gt    3  Check whether the analyzer database contains correct External IP Address and External  Port  configured in the Wi Fi router    4  Deselect External IP Address field in the analyzer database    5  Try to re establish the connection     Problem  Despite correct status    Ready     after the search  the analyzer is not displayed on the  list  Option Wi Fi transmission available is enabled and the analyzer is properly configured in  the database  including IP number     Possible cause  TCP 4002 port is blocked   it is used for communication through a firewall in   stalled on the PC  tablet  or in the server of internet service provider    Solution  check whether TCP
80. ds   WAADAUMAGKPL    built in Li lon rechargeable battery    operating manual    guarantee card    calibration certificate     cun cuip PQM 710 and PQM 711 analyzers standard equipment also includes     dedicated tablet with preinstalled Sonel Analysis software   tablet sleeve   backpack     WAFUTLS8     7 2 Optional accessories    Additionally  the following items that are not included in the scope of standard equipment can    be purchased from the manufacturer or the distributors     CT clamps C 4 1000 A AC   WACEGC4OKR    Hall effect clamps C 5 1000 A AC DC     WACEGC5OKR    CT clamps C 6 for low currents in 10A AC transformers   WACEGC6OKR    CT clamps C 7 100A AC      WACEGC7OKR    flexible clamps  Rogowski coil  F 1 for current up to 3kA AC  length  120cm       WACEGF10KR    flexible clamps  Rogowski coil  F 2 for current up to 3kA AC  length  80cm       WACEGF2OKR    flexible clamps  Rogowski coil  F 3 for current up to 3kA AC  length 45cm       WACEGF3OKR   Li lon rechargeable battery  replaceable by SONEL after sale services    WAAKU11    hard case for current clamps      WAW ALL2    external GPS antenna 10 m      WAPOZANT10GPS     117    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    7 2 1 C 4 current clamp    The C 4 clamp is used to measure the alternating current in  medium and high power electrical installations  The output sig   nal is voltage proportional to the measured current  The output  signal is supplied by a 1 5 meter lead with a pin adapted for
81. e SYSLOMS          cccssscscensonsscensonsesensensesscnsnsessonsanestonsonseons 89  5 4 4 TOlal AHarmonie DISON i  tween ea eine ee a eE e E EE aa e A EE EREET 90  5 4 5 KEAC O e N coat  A E N O A A N 91  BD PECTIN AI TOWNS ea tats ct eter tetas tacit tle lea tom leh aica data teastinald alow TA 91  5 5 1 Total interharmone DISIOMION csere E E a E 92  5 6 Mains Signallin gerei a A E 92  5 7 UND AIANCE acan oie aa oi a E ee ee 94  5 8 Voltage dips  swells ANC interruptions           sscccccsseeeceseeecseeeesaneneesanseessneneees 96    5 9 Transients ANC OVESLVOlLAGES       ccccccssesceccsaneeeecssaeeecessauseecessauenseessauessessaaaanees 97  5 10  CBEMA and ANSI CUIVES 1       1ccccccecccccsnecccceeeceeseecesaeeeeessescesaueeeesaeeeessneeeesaes 99  5 11 Averaging the measurement results           cccceeeeeceeneeeeeeeeneeeeeeeaneseeeteaaeenenees 101  FECHA OI izarsec estate T doe dese EER EE 104  6 1 OS cs deacon tate atest eine soeeee eet dla naires tame eticind oan enart ies otissmeoese ante emir uae 104  6 2 Sampling and HTC vase soca satetae2etsenadesaetscandecenananndtnstucbetetabaaatseiiuesacascaesatveeee 104  6 3 Transient module Kuy POM  PEA EE E I A E 105  6 4 Measured parameters   accuracy  resolution and FANGES       1  cccssssersneseees 105  6 4 1 Reference CONOINONS ci cdacbecescccasestdanrnlosaitaecnldasdelaacanedacg tev EENE EA ES Ea ENEA 105  6 4 2 The measurement uncertainty due to ambient temperature              1  ccccceeeeeeees 105  6 4 3 VO eet ae eee eee
82. e clock       104    6 Technical data    6 3 Transient module PQM 703  cup    DC voltage range  6000 V  Analog pass band   3dB 2 5 MHz  A D converter 4 channel  12 bit  simultaneous sampling in all channels    10 MHz  5 MHz  1 MHz  500 kHz  100 kHz  user selectable    Waveform recording time io to 20000 samples  from 200 us to 200 ms  depending on set     from 10  to 90  of the recording time  Detection method   amplitude  50 V   5000 V     slew rate  dV dt  from 100 V 500 us to 100 V 5 us     Inactivity time after detection       6 4 Measured parameters   accuracy  resolution and ranges    6 4 1 Reference conditions    Tab  7  Reference conditions     Continuous  external magnetic  lt  40 A m  d c    field  lt  3A   m  a c   for 50 60 Hz frequenc    DC voltage and DC current  50 Hz  0 2  or 60 Hz  0 2        6 4 2 The measurement uncertainty due to ambient temperature    Basic uncertainty given in technical specifications is guaranteed for the ambient temperature  range of 0  C    45  C  Outside this range  use an additional multiplier  M   which increases the  specified basic uncertainty to the actual measurement uncertainty  Fig  56 shows a graph of  M multiplier  depending on the ambient temperature within nominal operating temperatures  The  multiplier has a value of 1 0 in the temperature range of 0  C    45  C  Above  45  C and up to   55  C  the multiplier rises in linear manner up to 2 0  Below 0  C  down to  20  C   the multiplier  rises in linear manner up to 1 8  
83. e correct order of the messages displayed on the screen is as follows   o  Searching the network       o  Connecting to the network       o  Obtaining IP address      for DHCP   o  Ready     49    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual         Certificate of Calibration    6 months    Analyzer type YW Serial number    1 PQM 711 BS0003          WiFi settings    Addresses     Automatic  DHCP      Manual IP Address  Description  MAC Address oo   os port  External IP Address External Port    01 01 1970    Fig  36  Example Wi Fi configuration for communicatin via Internet       2 12 5 Editing the Wi Fi settings in the analyzer database in the absence of USB  connection    The following procedure applies to cases when the analyzer was previously configured  and  there is a need to add it to the database or to edit Wi Fi parameters that identify the device     To properly configure the connection  the following elements will be required   e Physical Address of the analyzer  MAC Address   this parameter must be read from screen   lt 10 10 gt  of the analyzer   e External IP Address and External Port  The parameters required to work in a different  subnetwork than the tablet  computer   especially for connecting to the Internet     Configure the analyzer in the following manner    e Select the appropriate analyzer from the database and click Edit or use Add button to add it  to the database    e Use Change Wi Fi Settings button and fill MAC Address field    e Incase of op
84. e device    real time preview of the mains    delete data in the analyzer    present data in the tabular form    present data in the form of graphs    analyzing data for compliance with EN 50160 standard  reports   system commands and other  user defined reference conditions    independent operation of multiple devices    upgrade the software and the device firmware to newer versions     Detailed manual for  Sonel Analysis  is available in a separate document  also downloadable    from the manufacturer s website www sonel p       2 6 PC connection and data transmission    The analyzer provides three ways of communication with a PC  They are as follows     wired communication via USB     radio communication in 433 MHz band using OR 1 receiver   built in wireless connectivity via GSM modem   radio communication via wireless Wi Fi transmission     a PC and the    analyzer must be connected to the same LAN or have the ability to communicate through the  WAN  correct configuration of the router      Connection to a computer  PC mode   ensures     Transmission of data stored in the recorder memory    o itis possible to read the data of all measurement points regardless of the recording state   Viewing mains parameters on PC    o instantaneous values of  current  voltage  power and energy  total values for the entire  system    harmonics  interharmonics  harmonic power values  THD  TID    unbalance    phasor diagrams for voltages    current and voltage waveforms drawn in real time  
85. e input voltage range  90   760 V AC  127   760 V DC   which is provided with independent cables terminated with ba   nana plugs    An important feature of the device is its ability to operate in harsh weather conditions   the an   alyzer may be installed directly on electric poles  The ingress protection class of the analyzer is  IP 65  and operating temperature ranges from  20  C to  55  C    Uninterrupted operation of the device  in case of power failure  is ensured by an internal re   chargeable lithium ion battery    The user interface includes a color 3 5  LCD display with a resolution of 320x240 pixels and a  keypad with four buttons    The full potential of the device may be released by using dedicated PC software  Sonel Anal   ysis     The analyzer may communicate with a PC in the following ways   e via USB connection with a transmission speed up to 921 6 kbit s  available data reading from   a memory card with a speed of a few MB s           via radio interface     using OR 1 receiver with a transmission rate of 57 6  kbit s  range limited to approx  5 m      1 General Information        POM 710 POM  via Wi Fi radio interface with effective transmission rate up to 300 kB s   max  sustained speed in a 10 m distance    e via GSM connection using the Internet     POM 702   POM 703 In order to use the first mode of wireless communication  OR 1 receiver  must be connected to a PC using its USB port  Communication in this mode is slower  therefore  we recommend it to view
86. e symmetrical component     The most convenient method to calculate the symmetrical components and unbalance is us   ing the complex number calculus  The vectors parameters are amplitude of the voltage  current   fundamental component and its absolute phase shift angle  Both of these values are obtained  from FFT     5 8 Voltage dips  swells and interruptions    Voltage dips  swells and interruptions are network disturbances when the effective voltage   RMS  is significantly different from the nominal value  Each of the three states may be detected  by the analyzer when the event detection is activated and when the user defines the threshold  values    Voltage dip is a state during which the RMS voltage is lower than the user defined voltage dip  threshold  The basis for the dip measurement is Urmsi1 2   which is the one period RMS value re   freshed every half period    Definition of dip  acc  to IEC 61000 4 30 standard     The voltage dip starts at the moment when Urmsi1 2  voltage decreases below the dip threshold  value  and ends at the moment when Uamsi1 2  voltage is equal to or greater than the dip threshold  value plus the voltage hysteresis    The dip threshold may be specified at 90  of Unom  During the voltage dip  the analyzer re   members the minimum recorded voltage  this is called the residual voltage Ures and is one of the  parameters characterizing the dip  and the average voltage value     maximum swell  value    RMS     swell threshold  hysteresis      hyst
87. e value measured during the event     Depending on the parameter type  you can set one  two or three thresholds which will be  checked by the analyzer  The table below lists all parameters for which the events can be detect   ed  including specification of threshold types    Some of the parameters may have values that are positive or negative        For example  ac   tive power  reactive power and power factor  Since the event detection threshold may only be a  positive value and to ensure proper detection for these parameters  the analyzer compares abso   lute values of these parameters with the set threshold     Example  Threshold for detecting active power events was set at 10 kW  If the load  has a generator nature  the active power with correct connection of    clamps will be a negative value  If the measured absolute value exceeds  the threshold  i e  10 kW  e g   11 kW  an event will be recorded for ex   ceeded maximum active power        Two types of parameters  RMS voltage and RMS current may generate events  for which the  user may also record waveforms    The analyzer records the waveforms of active channels  voltage and current  at the event  start and end  The user may set recording time for waveforms  from 100 ms to 1s  and the  pretrigger time  from 40 ms to 960 ms   Waveforms are saved in 8 bit format with sampling fre   quency of 10 24 kHz    Information about the event is recorded when the event ends  In some cases  it may happen  that event is active when t
88. ecording  event detection  and event thresholds  A few selected configurations are  given in Tab  4  The last column gives the approximate recording times when 2 GB of memory  card space is allocated to a measurement point  The typical configurations shown below are  based on the measurement of the N PE voltage and   n current     25    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Tab  4  Approximate recording times for a few typical configurations     Approximate   Configuration System type Waveforms cordi  type  Averaging  current Events Event wave    after averag   time with   recorded pa  time aeiee n torms ing period   2 GB allocat     rameter  ameters ed space    according to EN  according to the   voltages and 3 phase wye 270 days  currents  profile  3 phase wye 23 days    according to the  3 phase wye 22 5 day     voltages and  currents  profile  all possible pa  3 phase wye  rameters  all possible pa  3 phase wye 25 days  rameters    according to the   Power and har   monics  profile    according to the   Power and har   monics  profile    rameters    j Ser 1 phase  1000 events    1000 events 14 5 days    day    day     1s  1s  1s  1s  10s  10s  10s       26    2 Operation of the analyzer    2 8 Measuring circuits    The analyzer may be connected directly to the following types of networks   1 phase  Fig  16    2 phase  split phase  with split winding of the transformer  Fig  17    3 phase 4 wire wye with a neutral conductor  Fig  18     3 phase 3 wire wye 
89. ed in IEC 61000 4 30 and valid for analyzers of class A   If time does not meet these requirements  it is displayed in orange    e indicator of mains power supply or battery status    e indicator of GSM network signal strength  if a SIM card is inserted and connection GSM net   work is active      Screen number is displayed in the lower right corner of the display     Screen 1 is displayed by default after turning the analyzer on and after changing a measurement  point  It presents a phasor diagram of the measured mains and an indicator of correct connection  to the mains  When the connection is correct  a green OK message is displayed  but when a po   tential error is detected  red X symbol with ERROR message is displayed  When ERROR is dis   played the analyzer still operates as normal and measurements are possible    The criteria used by the analyzer for detecting a connection error are as follows    e deviation of RMS voltage exceeding  15  of nominal value     16    2 Operation of the analyzer    e deviation of the phase angle of the voltage fundamental component exceeding  30   of the  theoretical value with resistive load and symmetrical mains  see note below    e deviation of the phase angle of the current fundamental component exceeding  55   of the  theoretical value with resistive load and symmetrical mains  see note below    e network frequency deviation exceeding  10  of the nominal frequency     Note  To detect a phase error  the fundamental component of the mea
90. en should look as sown in Fig  25   Set the following items   e mains system  element   S as in Fig  25  as a single phase   nominal voltage HH at 230 400 V   nominal frequency   S at 50 Hz   averaging period   A at 1 s   triggering     at Immediate   event detection hysteresis 4 at 1 5    clamp type ES set to None   voltage transducers ES and N PE voltage  in section Additional measurements EA    set as unchecked     In the upper part of the window select the second tab Additional  where sliders may be used  to set the required time of recording waveforms and RMSy1  2 graphs for events and recording times  for transient graphs  These times should be set according to individual preferences     Then select Standard card from the tree with settings and ensure that  Enable logging    according to Standard  box is not checked   Adjust settings at Voltage card and Basic tab  as shown in Fig  26     35    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual                       Settings           Ba 9 TE  iLocal Ee  Phase voltage    opea All Log events    Sf g Measurement point 1  A E Minimum     CY Standard   lt  E Swells  Dips  i Maximum     Current Interruptions  ll Instantaneous  i  Power and energy     H Harmonics Log waveforms and RMS 1 2    m Interharmonics IB Log waveforms after each averaging period    Min Max calculation period     Half period ba Log events  transients   Sampling frequenc MHz   P send pling frequency  v    Threshold fs S         Analyzer Slew rate   dv dt
91. ent are subjected to FFT  as a result of which we receive  the harmonics amplitudes with phase shifts    It turns out that the knowledge of voltage and current harmonics and of phase shift between  these harmonics allows calculating the active power of each harmonic individually     Pa    Up Ih COS Pp     87    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    where   Pn     active power of the h th order harmonic   Un     RMS voltage of the h th order harmonic   In   RMS current of the h th order harmonic   Pn     phase shift angle between the voltage and current harmonics of the h th order     When Ph power has positive sign      then the dominating source of energy of this harmonics  is on the energy supplier s side  When it is negative  the receiver is the dominating source  It must  be noted that on the basis of harmonics active powers measured in this way one cannot deter   mine that only one party is the sole source of the harmonics  as the measured value is a resultant  of the supplier and the consumer     Example  When the supplier generates active power of harmonic Php   1 kW  and    the consumer  generates  the power of this harmonics equal to Pho    100 W  then the resultant power measured at the terminals between the  supplier and the consumer is Pr   Pap     Pho   0 9 kW        In a situation presented above  we are dealing with two separate sources of energy flow  Un   fortunately  basing on such measurement  we cannot directly indicate the actual distribu
92. ent sampl   of voltage Ua n  M   2048 for 50 Hz and 60 Hz  number of all voltage periods Ua n  counted during 10 sec period  clock time  divided by the  total duration of full periods    L    Current   True RMS     DC Current    where    is a subsequent sample of current la  M   2048 for 50 Hz and 60 Hz    M  1  apc   ra     t 1  where    is a subsequent sample of current la  M   2048 for 50 lat and 60 Hz     59 va    where Ujis a subsequent sample of voltage Us n  liis a subsequent sample of current la  M   2048 for 50 Hz and 60 Hz    Budeanu reactive power    Qg     UnIn Sin Phn    h 1  where Uh is the h th harmonic of voltage Ua n  In is the h th harmonic of current I   gn is the h th angle between harmonic Uh and Ih  Q     Uh sin p1   where U1 is fundamental component of voltage Ua n   damental component l   is fundamental component of current la  g   is angle between fundamental components U  and h    Apparent power    er Sy   4S       Uh    Apparent distortion pow  N ates  PP ar P where U  is fundamental component of voltage Ua n  l   is fundamental component of current la    Budeanu distortion power a      7 B  S  Power Factor i If PF  lt  0  then the load is of a generator type  If PF  gt  0  then the load is of a receiver type    Reactive power of fun        4 Calculation formulas    Displacement power fac  cose  tor DPF    Harmonic components of Unx  voltage and current Ihx    Total Harmonic Distortion  for voltage  referred to  the fundamental compo  Te  nent  Tota
93. ents apparent power S calculated in   th  measuring window   T i  represents duration of i th measuring window  in  hours     Apparent energy       4 2 Split phase network    Split phase network     parameters not mentioned are calculated as for single phase     Parameter  Designa  Method of calculation  tion    Total Budeanu reactive   power var Qetot   Qpa   Opp  Total reactive power of    fundamental component iil Qitor   Q14   Ore    Total apparent power VA Stot   Sa   Sp    Total apparent distortion  Total Budeanu distortion  Piot  Total Power Factor PFtot PF ot   RA  tot    Total displacement pow  COS  tot  er factor DPFiot    Total tangent     tan tot    1  COS Prot   DPFeot   z  cos Pa   COSp     _ Qtot  tan Prot   P  tot    where  Qiot   Qsto  when Budeanu method was chosen   Qiot   Qitot  when IEEE 1459 method was chosen        69    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    m  Ep tot     Prot   i T  i     i 1   Prot  for Prox   gt  0  0 for Pro   lt  0  m    Ep tot     Peot  OTO    i 1  IPror OI for Proc  lt  0  0 for Pro    0    Prot   i    f    Total active energy  con   sumed and supplied  Piot   i    f    where    i is subsequent number of the 10 12 period measure   ment window    Pror i  represents total active power Pio calculated in   th  measuring window   T i  represents duration of i th measuring window  in  hours     Eop tot     QBtot  OT     Os  for Qztor   gt  0  oo Qstot  i   lt  0    Eop tot   2 QBtot  OT     DAO for Qrtot  i   lt  0  0 
94. er  In actual systems  with some degree of supply voltage unbalance and the  load unbalance  there are non zero positive and negative sequence components  The measure of  such unbalance is so called unbalance factors  And this is due to this unbalance of the fundamen   tal component and additionally the differences in amplitudes and phases of the higher harmonics   that also these harmonics will have the positive  negative and zero sequence components  The  larger the unbalance  the higher the content of remaining components    IEC 61000 4 30 standard recommends that the harmonic subgroup method is used in power qual   ity analyzers for calculating harmonic components     5 4 4 Total Harmonic Distortion    Total Harmonic Distortion  THD  is the most widely used measure of waveform distortion  Two  versions of this factor are applied in practical use   e THD   THD F or simply THD      total harmonic distortion referred to the fundamental compo   nent   e THDr  THD R      total harmonic distortion referred to the RMS value   In both cases  THD is expressed in percent  Definitions are presented below     n AZ  THD            x 100   Ay  n AZ  THD         x 100   Arms    where  An     RMS of the h th order harmonic   A      RMS of the fundamental component   Arms     RMS of the waveform     Limitation of the number of harmonics used to calculate THD is conventional and results  mainly from measuring limitations of the device  As the analyzer is capable of measuring the har   moni
95. er  a specified time interval for the analysis purposes  For the EN 50160 standard  such time interval  is 10 minutes  In such case  the analyzer calculates an average 10 minute value basing on about  3000 of 200 millisecond values  approximately  as in reality the conventional 200 millisecond val   ue is 10 12 period value synchronized with the mains frequency   Each average voltage value is  recorded every 10 minutes which gives  only  1008 measurement results    Fig  54 presents the method according to which the analyzer determines the average values  at averaging intervals equal to or greater than 10 seconds with the 10 minute averaging time   This method meets the requirements for a Class A of IEC 61000 4 30 standard     Average values are synchronized with a real time clock as follows  When the clock counts an   other integer multiple of the averaging period  two processes occur    e current 10 12 cycle interval  k th measurement in Fig  54  is assigned as the last in the   aggregation interval  x     e simultaneously the first 10 12 cycle interval is started for the next averaging period  x  1     Such a resynchronization method generates Overlap 1  see Fig  54   The data from this area  are processed twice  as each of the 10 12 cycle interval is analyzed independently  The aim of  this kind of resynchronization is to ensure that the two analyzers of Class A  connected to the  same system  and synchronized with UTC  will give the same results  In the analyzers here de 
96. erating Manual    In three phase systems  only the positive sequence component is taken into account   Qi   3U  singi    Correct measurement of this power requires the same phase rotation sequence  i e  phase L2  delayed by 120   in relation to L1  phase L3 delayed by 240   in relation to L1    The concept of positive sequence component will be discussed in more detail in the section de   voted to unbalance     The value of reactive power of the fundamental component is the main value which allows es   timating the size of capacitor to improve the displacement power factor  DPF   that is the dis   placement of the voltage fundamental components in relation to the current fundamental compo   nent  i e  compensator of the reactive power of the fundamental component      5 3 3 Reactive power and three wire systems    Correct reactive power measurement is impossible in unbalanced receivers connected in 3   wire systems  delta and wye systems without N conductor   This statement may be surprising    The receiver can be treated as a    black box    with only 3 terminals available  We cannot de   termine its internal structure  In order to calculate the reactive power  we need to know the phase  shift angle between the voltage and the current at each leg of such receiver  Unfortunately  we do  not know this angle  In the delta type receiver we know the voltages on individual impedances  but  we do not know the current  in such systems  the phase to phase voltages and line currents a
97. erating in other subnetworks  the Internet   fill in External IP Address and Ex   ternal Port fields  For a direct connection  tablet  lt  analyzer   and for working in a local  network  tablet  lt  Wi Fi router   analyzer  these fields must be left inactive    e Note  If the analyzer has a static IP address  the search time may be shortened  To do this   enter IP address of the device in External IP Address field and enter  4002  in External  Port field    e Confirm the settings by pressing OK     50    2 Operation of the analyzer    d Certificate of Calibration    i 6 months    Analyzer type Y Serial number escription Date of calibration          B 1 PQM 711 BS0001 08 04 2014       Connect selected       WiFi settings  offline   Close SSID  Key  Addresses     Automatic  DHCP   J Manual IP Address    08 04 2014  Net Mask Gateway    Description  MAC Address joo   o   Port  External IP Address External Port    C       Fig  37  Example configuration for setting Wi Fi connection with remote analyzer  offline  mode     2 12 6 Checking Wi Fi connection    If status screen  lt 10 10 gt  shows the Wi Fi status as  Ready   it means that a connection may  be performed from a remote PC  tablet   The user may perform a test connection to verify the  connectivity with  Sonel Analysis     e Inthe program settings  check whether the search of the analyzers via Wi Fi is enabled  se   lect Options  gt Program configuration  gt Media settings gt Active media  Wi Fi box should  be ticked    e 
98. eresis     hysteresis      interruption threshold    minimum dip  and interruption value       Fig  49  Voltage swells  dips and interruptions    96    5 Power quality   a guide    Interruption is a state during which Urmsi1 2  voltage is lower than the specified interruption  threshold  The interruption threshold is usually set much below the voltage dip level  at approx   1  10  Unom    The voltage interruption starts at the moment when Urwsci 2  voltage decreases below the in   terruption threshold value  and ends at the moment when Urpmsiii2  voltage is equal to or greater  than the interruption threshold value plus the voltage hysteresis    During the interruption  the analyzer remembers the minimum recorded voltage and the aver   age voltage value     Voltage swell is a state of in  RMS4 9 RMS4 2 RMS4 5  creased voltage  The swell Oe A  threshold is usually set at a level  close to 110  of Unom  Phase A  Swell starts at the moment  when Urmsi1 2  voltage increases  above the swell threshold value  ee n ai  and ends at the moment when RMS4 2 RMS4 72 RMS4 2  Urmsa 2 voltage is equal or be  RMS4 2 RMS4  2 RMS4  2  low the swell threshold value mi  tet a T ei  nus the voltage hysteresis  Dur   ing the swell  the analyzer re   members the maximum record  Phase B  ed voltage and the average volt   age value    The hysteresis for all three RMS4 2 RMS   RMS   states is the same and it is a us   er defined percent of nominal Fig  50  Determining values of Urmsc 2   voltage  Even
99. ergy oscillations between its source and  the load  The formula indicates that according to Budeanu   s definition  the reactive power is the  sum of individual harmonics  Due to sing factor  such components may be positive or negative  depending on the angle between the voltage and current harmonics  Thus  it is possible that the  total reactive power Qs is zero at non zero harmonics  Observation that at non zero components   total reactive power may be zero  according to this definition  is a key to a deeper analysis which  finally allowed proving that in some situations Qs may give quite surprising results  The research  has questioned the general belief that there is a relation between energy oscillations and Budeanu  reactive power Qs  Examples of circuits may be presented  where despite the oscillating character  of instantaneous power waveform  reactive power according to Budeanu is zero  Over the years   the scientists have not been able to connect any physical phenomenon to the reactive power ac   cording to this definition    Such doubts about the correctness of this definition of course also cast shadow on the related  distortion power Dg  The scientists have started to look for answers to the question whether the  distortion power Ds really is the measure of distorted waveforms in non sinusoidal circuits  The  distortion is a situation in which the voltage waveform cannot be    put    on the current waveform  with two operations  change of amplitude and shift in t
100. etting  and a sampling frequency of 10 MHz  Transient graph recording should  be activated     33    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    After the measurement  generate timeplots of measured parameters and a sample  measurement report  Data should be saved for further analysis     How to perform the measurements     Step 1  Connect the analyzer to the tested network  as shown in Fig  16  Connect inputs L1  N   and PE  for transient measurements   Clamps do not need to be connected  as the current  measurement is not required  Power supply of analyzer  red wires  may be also connected to the  tested network to avoid battery discharge during recording     Step 2  Turn on the analyzer by pressing button  Screen 1 9 should be displayed as shown  In Fig  5     Step 3  run  Sonel Analysis  program  Connect the analyzer to a PC via USB cable  If this is the  first connection  wait to install the drivers of the analyzer     Step 4  click  Settings  on the toolbar of Sonel Analysis or select Analyzer gt Settings from the  menu  Then in the displayed window click  Receive   This will result in reading the current  configuration of the measurement points saved in the analyzer     Step 5  optional   If the analyzer has not been previously connected to the program  status at the  bottom bar of Sonel Analysis indicates  Disconnected  in red  when the analyzer is not  connected to the program   then clicking  Receive  will result in displaying window for connecting  with 
101. example  the analyzer may be configured to detect power factor drop  below a defined value  THD exceeding another threshold  and the 9th voltage harmonic exceed   ing a user defined percentage value  Each event is recorded along with the time of occurrence   For events that relate to exceeding the pre defined limits for voltage dip  swell  interruption  and  exceeding minimum and maximum current values  the recorded information may also include a  waveform for voltage and current  It is possible to record from 5 mains cycles of up to 1 second   with adjustable pre triggering time  Together with the waveform  half cycle RMS values  RMS   2   may be also recorded with time adjustable from 1 s to 30 s     A very wide range of configurations  including a multitude of measured parameters make the  analyzer an extremely useful and powerful tool for measuring and analyzing all kinds of power  supply systems and interferences occurring in them  Some of the unique features of this device  make it distinguishable from other similar analyzers available in the market    Tab  2 presents a summary of parameters measured by analyzer  depending on the mains  type     1 General Information    Tab  2  Measured parameters for different network configurations     3 phase delta  without N   L2 _N  TOT  L1   L2  L3  N  TOT L12 L23 L31 TOT   e  Je  e  eje  fe  eje     e  fJef  e  eje  J elele     e  Jejejeje     Network type   channel    Parameter    as    7    E Active energy  consumed and sup   e
102. eys on the keyboard    Serial number       LCD display    Input ratings    AC adapter  inputs       External GPS antenna  connector        Current clamps inputs  L1  L2  L3  N          j  N  Voltage measurement inputs SNG  L1  L2  L3  N  PE    Fig  1  Power Quality Analyzer  General view     Measurements are carried out using four current inputs installed on short cables terminated  with clamp terminals  The terminals may be connected to the following clamp types  flexible claps   marked as F 1  F 2  F 3  with nominal rating up to 3000 A  differing from others only by coil di   ameter   and hard clamps marked as C 4  range up to 1000 A AC   C 5  up to 1000 A AC DC   C   6  up to 10 A AC  and C 7  up to 100 A AC   The values of nominal measured currents may be    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    changed by using additional transducers     for example  using a transducer of 100 1 ratio  the user  may select C 6 clamps to measure currents up to 1000 A     Tab  1  Main differences between analyzers     __  PQM 702   PQM 703   PQM 710   PQM 711  10 MHz transient detection  module  433 MHz radio interface   with OR 1 receiver     Wi Fi interface    Dedicated tablet in standard  equipment    The device has a built in 8 GB memory card  To guarantee fast data read out  the analyzer is  equipped with a built in mass storage reader  which ensures the data readout with a few MB s   Data read out may be also be carried out by one of the three available communication 
103. f time  connection of the program with the analyzer is not required   During the measurement  disconnect L1 lead from the tested network to simulate a voltage dip     Step 11  Stop recording and upload data for the analysis  Display Control window  if not open  yet  by selecting Analyzer gt Control  Click red button Stop  Click Analysis icon on the toolbar  or  select Analyzer  gt  Analysis from the menu   to open the window for loading previously recorded  data for analysis    The window shows four bars of memory used for each of the measurement points  Check the box  next to the bar of measurement point No  1  The size of recorded data is shown in the right side of    36    2 Operation of the analyzer    bar  After selecting it  Load data button is activated   press it  A window will appear showing data  loading progress  After loading all data  a window is displayed for saving downloaded data into the  disk  It is recommended to save the data to a desired location on the disk  in order to retrieve it for  further analysis  Indicate the location on the disk  name the file and click Save    In the displayed window click on the horizontal bar indicating time of recording placed under text  Measurement point 1  User   after clicking it turns orange  and then click Data analysis     Step 12  Data analysis  In the main window of data analysis four main buttons are available   General  default view after loading data   Measurements  Events  Configuration  In General  view  on the
104. for Qstot      0    Qstot        f    Total Budeanu reactive  energy   consumed and supplied     Eqsutot   EQB tot Qertot   i    f  where   i is subsequent number of the 10 12 period measure   ment window   Qestot i  represents reactive power Qstot calculated in   th  measuring window     T i  represents duration of i th measuring window  in  hours     Eoi tot    gt    Qitot  OTC     Quron     for Qitot  i   gt  0  oor Qitot i   lt  0    E91 tot z  gt  Qitot  DT Ci     IQrtor_     for Qitot i   lt  0  0 for Qitot i    0    Qitot         f    Total reactive energy of  fundamental component   consumed and supplied     EQirot    Eat tot Qitot  C      f    where    i is subsequent number of the 10 12 period measure   ment window    Qitor I  represents reactive power Qrtot calculated in ith  measuring window    T i  represents duration of i th measuring window  in  hours     m  Estot    gt  Stt OTT  i 1    where    i is subsequent number of the 10 12 period measure   ment window   Stot i  represents the total apparent power Sto calculated  in   th measuring window   T i  represents duration of i th measuring window  in  hours     Total apparent energy       70    4 Calculation formulas    4 3 3 phase wye network with N conductor    3 phase wye network with N conductor   parameters not mentioned are calculated as for single phase      a  Designa   tion  Total active power  Total Budeanu reactive Q  power ee    Method of calculation    Piot   Pa   Pg   Pe    Qetot   Opa   Opp   Qec 
105. g relations    e Iy      I    ina single phase system    e Iy     I      I 2  ina 2 phase system    e Iy   ly     l     l3  ina 3 phase 4 wire wye system     These relations stated above are true provided that zero current is present in PE conductor  In  typical situations  this current is indeed negligible  but note that in emergency situations  e g  short  circuit   until the switch breaker is tripped  current in PE conductor may reach significant values   therefore the calculated value of current In will differ from the actual     27    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Note  In order to correctly calculate total apparent power S  and total Power  Factor  PF  in a 4 wire 3 phase system  it is necessary to measure the    current in the neutral conductor  Then it is necessary to activate option N   conductor current and connect 4 clamps  as shown in Fig  18  Another  option is to turn on analytical calculation of current In  More information on  total apparent power Se   see sec  5 3 5        For systems with available PE and N conductors  earthing and neutral  it is also possible to  measure N PE voltage  To do this  connect PE conductor to PE voltage input of the analyzer  In  addition  select option N PE voltage in measurement point settings     Pay attention to the direction of current clamps  flexible and CT   The clamps should be in   stalled with the indicating the load direction  It may be verified by conducting an active power  measurement   in 
106. g temperature   humidity    height    electromagnetic compatibility     measuring category acc  to IEC 61010 1     maximum measured conductor diameter     100 mV AC 1 A AC   40 Hz   10 kHz   double  according to IEC 61010 1  II  600 V    IP 40  with open jaws  IP 30  135 x 50 x 30 mm   about 240 g   21 mm   69 mm   20 mm   1 5m      10  C    55  C    lt 85  RH    lt  2000 m   IEC 61000 6 3 2008   IEC 61000 6 2 2008    7 Equipment    7 2 4 C 7 current clamp    C 7 Clamps are used to measure alternating currents in net   works of low and medium power within the range up to 100 A   The output signal is a voltage proportional to the measured current  at the sensitivity of 5 mV A  It is introduced via a cable  length  1 5  m  ended with a plug suitable for a socket in the meter     The arrow marked on one of the clamps indicates the direction of  current flow  It is assumed that the current flows in the positive di   rection if it flows from the source to the receiver  This orientation of  clamps is required for the correct power measurement        Attention     Do not use non insulated clamps for conductors with a Fig  61  C 7 clamp     potential exceeding 300 V with respect to the ground  and in systems with the measurement category higher than Ill        e Reference conditions  e temperature   e relative humidity      18    28  C   lt 85   non condensing     e Technical data     test range  e frequency range     maximum allowable continuous current  e accuracy  sine wave     Ba
107. group of 0 order  i e  subharmonic  consists of eight lines  with frequencies from 5Hz to 40Hz  Each following interharmonic subgroup consists of seven lines  located between harmonic subgroups  e g  subgroup of 1st order includes spectral lines of fre   quencies from 60 Hz to 90 Hz  In case of subharmonic subgroup  the range of spectral lines was  extended by 5 Hz line  otherwise the energy in this lowest frequency band would not be included  and would be lost  All subsequent spectral lines are included either in the harmonic subgroup or  interharmonic subgroup     Similarly as in case of the harmonics  interharmonics are calculated at least to 50th order  for  mains frequency of 50 Hz it gives a range of slightly above 2 5 kHz  and for 60 Hz  a range of  slightly above 3 kHz     3 9 Measurement of ripple control signals     The analyzer allows user to monitor two user defined frequencies in the range up to 3000 Hz   After exceeding the threshold limit defined by the user  the analyzer records the signal level for a  specified period of time  up to 120 seconds   As a standard  the analyzer measures the average  values of signals for the time interval selected in settings  the main averaging period   When re   cording acc  to EN 50160 is selected  then additionally all 3 second average values are recorded  for both frequencies   they are compared with limits specified in the standard  when the report is  prepared      3 10 Measurement of transients    COS The option for measu
108. hanged location    The analyzer  which operates a GSM modem and is within a range of GPS  may notify the  user about its movements  To use this feature the user must activate  Anti theft function  from the  PC program and fill the appropriate list of emergency phone numbers for sending SMS messages  with appropriate information  In this mode  the analyzer saves the position where it was acquired  for the first time after turning on the recording and then sends an SMS message to the defined  phone number s   if the analyzer changes its location by more than 100 m  SMS message con   tains the actual coordinates of the analyzer  Also  Sonel Analysis  enables user to connect user to  the analyzer via GSM to check the analyzer current location on the status screen  even when the  analyzer is turned off   see below   When the analyzer remains for a long time at a distance great   er than 100 m from its start position  then it sends SMS messages every 10 minutes detailing the  current position of the analyzer  max  10 SMS messages     In adverse conditions for GPS reception  weak signal  signal reflections  the analyzer may  send erroneous message on the location  The user is also notified of the loss return of GPS signal  by additional SMS messages    After activating the anti theft function  the analyzer behaves differently during switch off mode   GSM modem and a GPS receiver are continuously active  This is also the cause of faster dis   charging of the battery in the absence of
109. he individual funda   ihe components are 120   each         sign in the line specifying the sequence for the 1st harmonics means the normal direction  of the motor shaft rotation  The voltage harmonics  for which the sign is also     cause the torque  corresponding with the direction of the fundamental component  The harmonics of the 2nd  5th   8th and 11th order are the opposite sequence harmonics  meaning that they generate the torque  which counteracts normal motor direction of rotation  which can cause heating  unnecessary en   ergy losses  and reduced efficiency  The last group are the zero sequence components  such as  the 3rd  6th and 9th  which do not generate torque but flowing through the motor winding cause  additional heating    Basing on the data from the table  it is easy to note that the series         0 is repeated for all  successive harmonic orders  The formula which links the sequence with order is very simple  and  for  k  being any integer    Sequence Harmonic order    positive     3k  1    zero  0  3k       The even order harmonics do not appear when a given waveform is symmetrical in relation to    2 L S  Czarnecki    Power values in electrical circuits with non sinusoidal voltage and current  waveforms   Publishing House of Warsaw Technical University  Warsaw 2005  p 109  89    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    its average value  and this is the case in majority of power supply systems  In a typical situation   the measured even or
110. he recording is stopped  e g  during a voltage dip   Information about  such event is also recorded  but with the following changes    e there is no end time of the event    e extreme value is calculated only for the period until the recording is stopped    e the average value is not reported    e only the beginning waveform is available for RMS voltage or current related events     64    3 Design and measurement methods    To eliminate repeated event detection  when the value of the parameter oscillates around the  threshold value  the analyzer has a function of user defined event detection hysteresis  It is de   fined as a percentage value in the following manner    e for RMS voltage events  it is the percent of the nominal voltage range  e g  2  of 230 V    which is 4 6 V     e for RMS current events  it is the percent of the nominal current range  e g  for C 4 clamps and   in absence of current transducers  2  hysteresis is 0 02x1000 A   20 A    e for events related to DC voltage and Un pe voltage  the hysteresis is calculated as a percent   age of the threshold value  but not less than 50 mV  referred to input     e for remaining parameters  the hysteresis is specified as a percent of maximum threshold  e g   when maximum threshold for current crest factor has been set to 4 0 the hysteresis is   0 02x4 0   0 08      3 13 Methods of parameter   s averaging    Method of parameter averaging       Symmetrical components U      Unbalance factor U    calculated from average va
111. he recording process  At the same time the status bar displays  the number of measurement point alternately with the hourglass symbol  If all the scheduled  times are over  the recording process will be inactive  unavailable  and the status bar will  display the number of measurement point  alternately with the sinusoid symbol  meaning that  only Live preview of current mains values is possible      The measurement point number  which is displayed in the upper left corner of the screen   flashes once per second  while the device is in the recording mode     Stopping the recording process   e recording ends automatically as scheduled  if the end time is set   in other cases the user    stops the recording  using button or the software     e recording ends automatically when all memory assigned to a measurement point on the  memory card is filled  In this situation  the display will show the number of the measurement  point alternately with the sinusoid symbol    e the display will remain blank after the recording process is completed  if the user activated the   sleep mode   Press any button to turn the screen on and to display the last screen  if the key  lock is off  or the screen requesting the code for unlocking the keypad  if the key lock is on      2 7 3 Approximate recording times    The maximum recording time depends on many factors such as the size of the allocated  space on a memory card  averaging time  the type of system  number of recorded parameters   waveforms r
112. he tree of cards for this point  double clicking Measurement point 1  automatically expands the tree   The following items should be displayed after expanding   Standard  Voltage  Current  Power and energy  Harmonics  Interharmonics     34    2 Operation of the analyzer    J Settings     k   fe     oe  w    Local n    Add 7  p Measurement point name Events detection hysteresis  u isin X m    A    v  gt  Measurement point 1 Mains nominal values Mains system yv Clamps type  A Voltage Un      r t 3 phase 4 wire Wye v  GY Standard   eee 3  r  max  1 00  kA      gt  Voltage Frequency fn  Current limit         oy  Triggering and averaging 0 05 v    0 5A   Ave od  nn E Voltage transducers    Harmonics   10s v  m   c  10000  Triggering  Interharmonics one    m og B  A 7  b Measurement point 2 p     Additional measurements Of  too  Oo i l  i ja cats Sate pines anes E current transducers    Measured    ie  asur    SA  P   send C   receive   Calculated  e  1 0000    Analyzer M N PE voltage   1 00  lz Analyzer settings  b 9 Measurement point 1    2013 02 15    0100 00 2013 02 15  b Q Measurement point 2  b Q Measurement point 3 2013 02 15 01 00 00      b Measurement point 4  Q necarenentcon F 2013 02 15 01 00 00 2013 02 15    Koy 2013 02 15 01 00 00 _ BBs    Estimated memory usage 0 0   0 0 1844MB  Total time span       Fig  25  Main settings of the measurement point     To change the main settings of the measurement point  single click Measurement point 1 at     Local    panel  The scre
113. hole process of recording     2 11 GSM communication mode    2 11 1 General information about GSM connection    Built in GSM modem ensures wireless communication with the analyzer from almost any loca   tion with Internet access  Similarly as in case of USB and OR 1 connection  this mode provides  the user with a full control of the analyzer   the user may view current data  start and stop record   ing  read the data for analysis  etc  To use this mode  the analyzer must be equipped with a SIM  card of the following service parameters    e General Packet Radio Service  GPRS    e static public IP address     39    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    SMS option to send alarm messages     Note  Ordinary SIM card removed from a cell phone cannot be used with the  analyzer  GPRS in the analyzer requires a non standard static IP address  service  reserved only for a given SIM card  This static IP address en     sures that the analyzer has one permanent address in the Internet  This   type of service is commonly used for transmission  machine to machine     M2M  used e g  in industry transmissions for monitoring and exchanging  measurement data between devices        The communication is performed in the following manner     the modem connects to a GSM network  and then log on to the Internet    the modem initiates TCP IP server service with IP address assigned by the service pro   vider  Usually  the port number used by the analyzer is 4001  The analyzer is prese
114. hree markers mark specific points on the graph and read the  parameters of indicated points  The graph may be saved  in selected graphic format  by clicking  Save icon on the top toolbar     Step 14  Displaying graphs with harmonics  Two types of graphs may be displayed for harmonics   The first one is a graph of recorded harmonics during the recording period  To display the graph   first select the time column and then the columns of selected harmonics  e g  third and fifth order   and click Plots gt  Time plot    The second type of the graph is a bar graph of harmonics  It shows all the harmonics in selected  1 second interval  one row   To generate it  first select the desired cell from the time column and  then select the column of any harmonic  click Plots and choose Harmonics  In the same manner   the user may also select the time interval by dragging time column cells  Then a graph is shown  with average values of harmonics in the specified time period     Step 15  Generating measurement report  In order to generate a report containing values of  required parameters  select the columns of these parameters  always select the time column first    and then click Reports and select User report  Click Preview in the displayed window to see  saved data  Save button saves data in a format specified by the user  pdf  html  txt  csv      Step 16  Checking events  If the analyzer  during recording process  detects any event  it will be  displayed in a table in Events view  The r
115. hus initially there is a sudden voltage drop almost to zero  followed  by fast recovery and an overshoot when voltage much higher than the nominal is reached  usually    98    5 Power quality   a guide    it does not exceed the double value of peak voltage in standard conditions   and then the disturb   ance is suppressed in oscillatory way  The oscillating nature of the disturbance is caused by the  interaction of the capacitor capacitance with network inductance and resulting resonance  The os   cillation frequency is usually around a few hundred Hz  The resistance in the circuit results in  gradual suppression of these oscillations  The whole transient usually lasts no longer than a few    few dozen milliseconds  An example of such a transient is shown in Fig  52     T T   T T       Voltage       0 10 20 30 40 50 60 70  Time  ms        Fig  52  An example of a transient after switching capacitor banks     Apart from the causes listed above  transients in networks are generated by switching on and  off capacitive loads  inductive loads  by tripping protection devices  fuses  and by short circuits   Switching on loads  circuits  connected to the transformer windings  often leads to ferroreso   nance  which is an oscillating transient caused by resonance between the capacitances in the cir   cuit and by the non linear inductance of transformer ferromagnetic core  Disconnection of induc   tive loads is often accompanied by the sparking on contacts  The voltage generated at the
116. identifying the possible cause of a problem   and not a long term analysis    Recording with a short averaging time may be sufficient to evaluate the performance of the  mains and disturbances in it  However  equally detailed information can probably also be obtained  with longer times  in minutes  but with activated recording of minimum and maximum values and  event detection  An important advantage in this situation that the volume of recorded data is much  smaller which means faster data retrieval and analysis    On the other hand  the power quality tests are usually made according to the EN 50160  In  this case  the analysis is carried out over a longer period of time  e g  7 days   and therefore the  chosen averaging time is also long   10 minutes     Please note that there is no single best setting for both  the averaging time and other parame   ters or event thresholds  Each mains system is different and so are the goals of the mains tests   Therefore  the optimal configuration of the analyzer may require several approaches and will also  depend on the experience of the operator     103    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    6 Technical data    e Specifications are subject to change without prior notice  Recent revisions of technical docu   mentation are available at www sonel pl    e Basic uncertainty is the uncertainty of a measurement instrument at reference conditions speci   fied Tab  7    e Provided uncertainties apply to the analyzer without a
117. ime  In other words  if the following condi   tion is met    u t    Ai t     T     then  voltage is not distorted in relation to the current  In case of sinusoidal voltage and load which  is any combination of RLC elements  this condition is always met  for sinusoidal waveforms  these  elements maintain linearity   However  when the voltage is distorted  the RLC load does not en   sure absence of current distortion in relation to voltage any more  and the load is no longer linear      it is necessary to meet some additional conditions  module and phase of load impedance  changing with frequency     And then  is really Dg a measure of such distortion  Unfortunately  also in this case the Bu   deanu   s power theory fails  It has been proven that the distortion power may be equal to zero ina  situation when voltage is distorted in relation to current waveform  and vice versa  the distortion  power may be non zero at total absence of distortion    Practical aspect of this power theory which relates to improvement of power factor in systems  with reactive power was to be the feature to take the most advantage of correct definitions of reac   tive power  The compensation attempts based on the Budeanu reactive power and related distor   tion power failed  These parameters did not allow even a correct calculation of correction capaci   tance which gives the maximum power factor  Sometimes  such attempts resulted even in addi   tional deterioration of power factor    How come  then  
118. imply takes current in  alternating or discontinuous way  All the energy is supplied solely by the generator    In the next step  we may modify the circuit by introducing some impedance between the generator  and the receiver  Such impedance represents the resistance of cabling  transformer winding  etc    Measurements of voltage and current harmonics will give slightly different results  What will  change  Small voltage harmonics will appear  and in addition current frequency spectrum will  slightly change    When analysing the voltage waveform on the receiver  one could notice that original sinusoi   dal waveform was slightly distorted  If the receiver took current mainly at voltage peaks  it would  have visibly flattened tops  Large current taken at such moments results in larger voltage drops on  the system impedance  A part of the ideal sinusoidal voltage is now dropped on this impedance  A  change in the current spectrum is a result of slightly different waveform of voltage supplied to the  receiver    The example described above and  flat tops  of the sinusoid are very frequent in typical sys   tems to which switched mode power supplies are connected     5 4 1 Harmonics active power    Decomposing receiver voltage and current to harmonic components enables using more de   tailed analysis of energy flow between the supplier and the consumer    We assume that the power quality analyzer is connect between the voltage source and the  receiver  Both  supply voltage and curr
119. in 1922 by F  Buchholz   a German physicist     S305     It is based on the effective values of voltage and current  and the power is called the effective  apparent power  for this reason  index  e  is used in marking three phase systems   Those effec   tive voltage and current values are such theoretical values which represent voltage and current in  an energetically equivalent three phase balanced system  Consequently  the key issue is to de   termine Ue and Ie    IEEE Standard 1459 specifies the following formula  In three wire systems     84    5 Power quality   a guide    lL     h   1      L            In four wire systems     We th Pe Fh  aea ae    O F U aa a ae  ee 18    where la  lb  lo are RMS currents for individual phases  line or phase   In is the RMS current in  neutral conductor  Ua  Up  Uo are RMS phase to neutral voltages  and Uab  Ubo  Uca are RMS  phase to phase voltages    Se calculated in this manner includes both the power losses in the neutral conductor  in four   wire networks  and the effect of unbalance     le    5 3 6 Distortion power Ds and effective apparent power Sen    During the discussion on reactive power  it was mentioned that the distortion power according  to Budeanu cannot be used for large distortions of voltage and current and for the unbalance of  three phase systems  a paradox of distortion power which is not a measure of actual distortion    However  this power is often used by energy quality specialists and manufacturers of systems f
120. int  Start and Stop buttons      Note    Disabling the access point will prevent a direct connection analyzer  gt   tablet via Wi Fi        e changing the software actions at the startup  Sonel Analysis may operate in one of two  modes  Default setting is  Paired  This automatically connects the program with the factory  paired analyzer after the program is started  Paired device field shows the serial number of  the paired analyzer  To make this possible  the access point must be set as Enabled  Se   lecting Normal mode starts normal operation of the program  In this case  the automatic  connection to the paired analyzer during startup will be disabled     Next two fields  SSID and Key enable user change the parameters of the access points in the  tablet   e SSID field is used to name the wireless access point   e Key field is used to secure the connection with a password     In order to properly configure a Wi Fi access point   Disable the current access point  Stop button    Enter the access point name  SSID field     Enter the password  Key field    Press Start button     47    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Note  In order to enable the connection between the analyzer and the access    point in the tablet  the analyzer needs the same name SSID and Key en   tered  see chapter 2 12 4        2 12 4 Configuring Wi Fi connection via USB connection  To properly configure the connection  the following elements will be required     Access Point Name  SSID 
121. ion  THD   THD F   Current total harmonic distortion  THD   THD F    a ae   a ee ee   ae a   ee a  TID R    ella a  TID F   oen d a   e   e   ae a   a ae    Voltage interharmonics amplitudes Vino    Uinso    Angles between voltage and current harmonics   D1    50   Ripple control signals UR1  UR2     Only when using C 5 clamps   2  During recording for the purposes related to compliance with EN 50160 standard  3 second average values  are also recorded        6 8 Power supply and heater    Power supply    90   760 V AC  127   760 V DC   CAT IV 600 V   max  30 VA   Li lon 4 4 Ah  Operating time on batter  Battery charging time  fully discharged battery   Current consumption from battery in analyzer off  mode  mains power failure  does not apply to  lt 1mA  anti theft mode     Heater temperature threshold  activation   5      Heater power supply from AC adapter    6 9 Supported networks    Types of supported networks  directly and indirectly   1 phase with a neutral conductor  terminals  L1  N       3 phase wye with N  3 phase wye with a neutral conductor  terminals  L1  L2  L3  N  3 phase delta Three phase delta  terminals  L1  L2  L3  N shorted with L3    Three phase delta  terminals  L1  L2  L8  N shorted with L3  with two cur   3 phase Aron delta  rent clamps  3 phase wye without N  EN wye without neutral conductor  terminals  L1  L2  L3  N shorted  3 phase wye without Aron N  3 phase wye without neutral conductor  terminals  L1  L2  L3  N shorted  with L3  with two current
122. ion of the current or completed recording  optionally   duration of the interval in the  scheduled recording mode   e the number of events recorded by the analyzer from the start of recording   e GSM network status  This line displays messages that relate to the current status of the built   in GSM modem   o  Turning on      the modem is being activated   o  Connecting to the network   the modem logs on to GSM network  o  Connecting to the Internet     the modem initiates exchanging data packets and connects  with the Internet   o  Ready  UMTS   the modem has properly registered itself in GSM network and waits for  a client connection  UMTS  Universal Mobile Telecommunications System Network  is  the name of a standard for data exchange  which depends on the availability of services  In a given area     The analyzer may display different messages here  e g  indicate errors   No SIM Cara  when  the SIM card is not inserted    nvalid PIN  when PIN submitted by the analyzer was rejected  by the SIM card  etc  More related information may be found in the chapter on GSM connec   tions   chapter 2 11    e the last line of screen 8 9 shows the status of the GPS receiver  when sufficient signal is re   ceived from GPS satellites  from internal or external antenna   the device displays word   YES   When no signal is received  the device displays  No signal  message  See more about  GPS receiver in chapter 2 10    e current level of GPS signal     19    PQM 702  PQM 703  PQM 710  PQM 7
123. is 1400 A for DC and 1000 A  AC  The output signal is voltage proportional to the meas   ured current  The clamp has one 1000 A measuring range   with the 1 mV A sensitivity  DC zero adjustment knob  and       e accuracy   0 as   of measured value   e input signal for max  current 1VAC   e ratio 1 mV AC 1 A AC   e frequency range 30 Hz   10 kHz   e insulation type double  according to IEC 61010 1   e measuring category acc  to IEC 61010 1 Il  600 V    e protection rating acc  to IEC 60529 IP 40  with open jaws  IP30   e dimensions 216 x 111 x 45mm   e weight about 640 g   e jaws opening 53 mm   e open jaws height 139 mm   e maximum measured conductor diameter O52 mm   e clamp lead length 1 5m   e operating temperature    10  C    55  C   e relative humidity  lt 85    e height  lt  2000 m   e electromagnetic compatibility IEC 61000 6 3 2008    C 5 current clamp    LED power supply indicator     The output signal is supplied by a 1 5 meter lead with a pin    adapted for the socket in the meter     The arrow located on one of the jaws indicates the current  flow direction  It is assumed that the current is flowing in the  positive direction if it is flowing from the source to the re   ceiver  Such clamp orientation is required for a correct    power measurement     Overload   e Direct current  DC    e Alternating current  AC      IEC 61000 6 2 2008       Fig  59  C 5 clamp     up to 3000 A  continuous mode    up to 1000 A in continuous mode up to  the 1 kHz frequency    119    P
124. isadvantages of an abrupt time change  there is an option to carry it  out even when recording process is active  A threshold is defined in seconds  Time resynchroni   zation threshold parameter   to set the minimum difference between internal and UTC time at  which the abrupt  one step  time change will be performed     Note  Abrupt change of time during the recording process may lead to irreversi     ble loss of recorded data  therefore it is advised to use the slow resyn   chronization mode        To avoid the problems with time measurement during recording  please remember the follow   ing issues    e The analyzer must have properly set its time zone and the time displayed on its screen must  be precisely compatible with local time  if there is no GPS signal before starting the record   ing     e Turn slow resynchronization of time  by setting Time resynchronization threshold parame   ter to zero value and set resynchronization factor at a low value  e g  below 25      e  f possible  before starting the process of recording  receive the GPS signal to synchronize the  analyzer time to UTC  This will ensure the least possible timing errors during the recording  and a fast tuning time in case of a temporary loss of GPS signal    e In order to ensure the compliance of the whole measurement with requirements of IEC 61000   4 30 in terms of time marking for devices of Class A  the internal analyzer clock must be syn   chronized to UTC  and GPS signal must be available for the w
125. kets  include immunity tests  for simulated lightning surges  AC power connections are tested with  2 kV pulses applied be   tween power lines and grounding lines  and  1 kV pulses applied directly between power supply  lines  Standardized pulse has voltage rise time of 1 2 us and voltage fall time of 50 us  For the  measuring devices that may be connected directly to distribution networks at the distribution  boards or at LV transformers  authorities defined a measurement category  overvoltage category    which informs about the device protection level against surges  For example  to be included into  measurement category IV 600 V  the category of PQM 702 and PQM 703 analyzers   the devices  must be immune to impulses of 1 2 us 50 us with 8 kV amplitude  applied directly between test  terminals at source impedance of 2 Q  Peak current during surge may be therefore equal to 4 kA    The main protection measures against such surges include the circuits limiting the maximum  voltage such as gas discharge tubes  GDTs  and varistors  Their construction must ensure receiv   ing impact energy and limiting voltage penetrating the device circuits to a safe level     Transients caused by switching compensation capacitance  as opposed to lightning strokes   have their source within the distribution network  The compensation is used to improve the power  factor and efficiency of energy transfer to the load  At the moment of switching on  a capacitor is a  short circuit for the network  t
126. l Harmonic Distortion  for voltage  referred to THDUR  RMS  Total Harmonic Distortion  for current  referred to  the fundamental compo  TADIR  nent    cos       DPF   cos  y    91    where qgu1 is an absolute angle of the fundamental com   ponent of voltage Ua n  gi is an absolute angle of the fundamental component  of current  a    tang   P    where  Q   Qs when Budeanu method was chosen   Q   Q  when IEEE 1459 method was chosen   method of harmonic subgroups according to IEC 61000   4 7  x  harmonic order    1  50    50 2  h 2 Uj     THDUp           x 100   1    where Uh is the h th harmonic of voltage Ua n  U  is fundamental component of voltage Us n    DE  UZ  THDUp   Sree 100     where Ur  is the h th harmonic of voltage Us  n  reada  THDIr          x 100   1    where Ihis the h th harmonic of current la  l   is fundamental component of current la    method of interharmonic subgroups  acc  to IEC 61000 4 7  x  interharmonic order    0  50   sub harmonic also includes the 5 Hz bin       50 772  in 0 Vin  U1    where Un is the ih th interharmonic of voltage Us   U  is fundamental component of voltage Us n    Interharmonic compo  U   nents of voltage and cur     se  ihx  rent  Total Interharmonic Dis   tortion for voltage  re   ferred to the fundamental MOE   component  Total Interharmonic Dis   tortion for voltage  re  TIDUR  ferred to RMS  Total Interharmonic Dis   tortion for current  re   ferred to the fundamental TDIr  component  Total Interharmonic Dis   tortion for c
127. lass A the range is  10    150  Uan  The analyzer meets the requirements  listed above relating to the operation of PLL  for the rated voltage Unom  gt   100 V  i e  up to approx   10 V     3 6 Frequency measurement    The signal for measuring 10 second frequency values of the network  is taken from L1 voltage  channel  This is the same signal that is used to synchronize the PLL  L1 signal is sent to a 2nd or   der band pass filter  for which the passband was set at range of 40   70 Hz  This filter is designed  for reducing the level of harmonics  Then  a square signal is formed from the filtered waveform   The signal cycles number and their duration are counted during the 10 second measuring cycle   10 second time intervals are determined by the real time clock  every full multiple of 10 second  time   The frequency is calculated as the ratio of the number of cycles counted and their duration     3 7 The method for measuring harmonics    Harmonics measurement is carried out according to IEC 61000 4 7   It defines the method for calculating individual harmonics    The whole process consists of several steps   e synchronous sampling  10 12 periods    e FFT  Fast Fourier Transform      e grouping     FFT analysis for the test window of 10 12 period  approx  200 ms   As a result of FFT  we re   ceive a set of spectral lines from 0 Hz  DC  to the 50 th harmonics  approx  2 5 KHz for 50 Hz or    58    3 Design and measurement methods    3 kHz for 60 Hz   The distance between succe
128. le  the screen should display the desired window  e g  Live Mode  and the sta   tus bar should display  Connected  message  Also the analyzer screen will display  Con   nected to PC  GSM   message  The connection attempt was successful     2 11 4 Possible problems with GSM settings and troubleshooting    Problem  The search progress bar quickly reaches 100  and no analyzer is found    Possible cause  It may indicate that GSM search is disabled in program settings or in the analyz   er database    Solution  from program menu select Options  gt Program settings gt  Media settings gt  Active  media  Check TCP IP over GSM box     Problem  The search progress bar in a few sec  reaches 100  and no analyzer is found   Possible causes   1  The analyzer is turned off or its GSM is inactive   not configured   2  IP address of the analyzer does not match the address entered into the database of  analyzers   3  The analyzer has active GSM connection with another client or temporary network  problems   Solution   1  When the analyzer is available check the status of GSM modem on screen  lt 8 9 gt   If the  status is  Disabled   then select  Select Analyzer gt  Actual settings from the program  menu  go to Wireless connection card and check whether GSM transmission available  is enabled  if not  enable it   Check settings of the modem   2  Check whether the correct IP address is entered to the database of analyzers   3  Try again in a few minutes     Problem  Despite correct status   Ready
129. links  USB   OR 1 radio receiver  and GSM modem    The device is provided with a built in GSM modem  UMTS standard  and an antenna  This so   lution provides it with almost unrestricted access to the analyzer from any chosen global location  with available GSM network  On the left side of its housing the analyzer has a SIM card  which is  required for data transmission via GSM networks    Another advantage of the device is a built in GPS receiver with antenna  making the analyzer  fully compliant with the requirements of IEC 61000 4 30 Class A  without the need of installing  additional accessories  The GPS receiver ensures the synchronization with UTC  Universal Time  Clock   and provides measurement accuracy of tens of nanoseconds  GPS receivers may receive  satellite signals in the open air  therefore synchronization with a built in antenna is possible only  outside of buildings  When the analyzer is used indoors  in order to ensure the availability of the  GPS signal  the device should be connected to an external GPS antenna  cable length  10m  lo   cated outside the building  External antenna is an additional accessory    Recorded parameters are divided into groups that may be independently turned on off for re   cording purposes and this solution facilitates the rational management of the space on the  memory card  Parameters that are not recorded  leave more memory space for further measure   ments    The analyzer has an internal power supply adapter operating in a wid
130. llows the analyzer to communi   cate with the tablet  or computer  remotely  A direct connection  tablet    analyzer is possible  as  well as operation in a local network or via the Internet     You can work in an open network or in a network secured with WPA WPA2 PSK     With a direct connection  a Wi Fi access point  router  is the tablet  For this kind of operation   the analyzer and tablet are configured at the factory    The tablet may work with multiple analyzers  This requires adding them to the analyzer data   base    When connected to an access point  the analyzer starts TCP IP server connections with static  IP address or with an address assigned by DHCP server of the access point  TCP port used in the  local network and for direct connections is 4002    Due to the possibility of using dynamic address  during the operation in local network and with  direct connection  Sonel Analysis software scans the entire subnetwork to find the analyzer with  MAC address corresponding to the one assigned to the analyzer with a given serial number     23    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Connecting to the analyzer via the Internet requires a Wi Fi router properly configured by the  network administrator    The analyzer  which has no access point within its range  remains in scanning mode of  2 4 GHz Wi Fi band     Note    Connecting to the analyzer via the Internet requires a Wi Fi router proper   ly configured by the network administrator        For more i
131. lot of transient only in channels where events meet the criteria  set by the user  After detecting a transient  the analyzer is insensitive to subsequent transients for  3 seconds  A special case is when the transient is detected only in one channel and in the time  between its detection and ending of the recording process  subsequent transients occur in other  channels  In this particular situation  the analyzer will record waveforms of all channels where  transient events were detected  Since transients detected slightly later than the transient in the  first channel  will not have exactly the same pretrigger time  recording of these channels will end  up at the same time as the recording in the first channel triggered by the first event    Sonel Anal   ysis  software marks these events as  Transient     Waveforms for the channel that triggered the  first event  they will always appear with the other channels that triggered later event  Similarly  the  opening of the graph of a later waveform  secondary transient  will also display other channels   where the disturbance occurred within the same time period  In this way  you can easily analyze  the time dependence between channels     In the event table for transients the following parameters are specified   e Extreme column includes maximum measured transient amplitude  peak to peak    e Duration column presents an approximate duration of the disturbance     Measuring lines are referenced to PE input  see also Fig  40   Tra
132. lues of symmetrical components   Power Factor PF calculated from the averaged power values   arithmetic average   THD U    calculated as the ratio of the RMS value of the higher order harmonics to  the RMS value of the fundamental component  for THD F   or the ratio of  the RMS value of higher order harmonics to the total RMS voltage  for  THD R    TID U    calculated as the ratio of the RMS value of interharmonics to the RMS val   ue of the fundamental component  for TID F   or the ratio of the RMS value  of interharmonics to the total RMS voltage  for TID R    Interharmonic amplitudes U      Active and reactive power of   arithmetic average   harmonics   Note     Active  Reactive  Apparent and   arithmetic average  Distortion Power  calculated from the averaged power values  Harmonic amplitudes U     The angles between voltage and   arithmetic average  current harmonics  RMS average value is calculated according to the formula        The arithmetic average  AVG  is calculated according to the formula   N  1  AVG   wD x    where   e xX  is subsequent parameter value to be averaged   e Nis the number of values to be averaged     65    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    4 Calculation formulas    4 1 One phase network    One phase network    Parameter  Designa  Method of calculation  tion    Voltage   True RMS     DC Voltage Uanc    Cc    tet Tf l ojele     where Uj is a subsequent sample of voltage Ua n  M   2048 for 50 at and 60 Hz    where Uj is a subsequ
133. lyzer via USB cable  enter the analyzer database and select  Change GSM settings  and then Change PIN code of the SIM card  Enter any of the  four digits in Previous PIN  this field is ignored in this case   and then enter the same cor   rect SIM code in the two fields below  Save the settings  Disconnect the analyzer and  screen  lt 8 9 gt  will be displayed by the analyzer to check the status of GSM  whether the  connection available or not      Problem  Analyzer reports a GSM error by displaying  PUK Required     Possible cause  The card inserted into the analyzer is blocked due to several attempts of enter   ing incorrect PIN code  Unlock the SIM card by entering PUK code    Solution  After connecting the analyzer via USB cable  enter the analyzer database and select  option Change GSM settings  Select Change GSM PIN  This should open a window al   lowing you to enter PUK code and new PIN code  Enter the codes and confirm  Discon   nect the analyzer and on screen  lt 8 9 gt  check the status of GSM  whether the connection  is made properly     The card may be also unlocked by inserting it into any mobile phone and entering PUK  code and a new PIN code    Note  several attempts to enter incorrect PUK code will result in irreversible block   ing of the SIM card     Problem  The analyzer reports GSM errors   Network Error      SMS Error      No network  or other    Possible Cause  One of GSM network errors occurred  It may be caused by entering wrong  phone number for SMS no
134. me resynchronization    As the availability of the GPS signal cannot be guaranteed on a permanent basis  it is neces   sary to ensure proper management of internal time when the GPS signal becomes available and  when it differs from the internal time of the analyzer    When no recording is on   the situation is simple   after receiving the satellite time  the analyz   er clock automatically synchronizes with it without any additional conditions    When the recording process is on  a sudden change of the internal time may lead to a loss of  measurement data when time is reset  or it may create a time gap in gathered data  when UTC  time is ahead of the analyzer time  To prevent this  a slow synchronizing mechanism was intro   duced to synchronize the internal analyzer time with UTC time  The implementation of this con   cept is based on the deceleration or acceleration of the internal analyzer clock in such a manner  that after a time the two clocks   internal and GPS   are equalled and achieve synchronization   The advantage of this solution is the fact that there is no data loss or discontinuity    The user has the option to set two configuration parameters that affect the resynchronization   during the recording process  One of them  resynchronization factor  defines the speed of the  synchronization  The lower is the factor value  the longer is resynchronization  but the length of  the measurement intervals will be close to the averaging time   Despite the aforementioned d
135. ments in non sinusoidal conditions     the calculation formulas relate to sinusoidal conditions   we can read in the standard that due to    practical    reasons  non sinusoidal waveforms have been  excluded   The standard does not give any measurement criteria which would allow checking the  meter properties at distorted voltage and current waveforms  As a surprise comes also the fact  that the older standard  IEC 61268  already withdrawn  defined the test which involved checking  the measurement accuracy at 10  of the third current harmonic    The present situation leaves the choice of measuring method to the meters designers  which  unfortunately leads to significant differences in reactive energy indications in the presence of high  harmonic distortion level    Older  electromechanical meters have characteristics similar to that of a low pass filter     the  higher harmonics are attenuated in such meters and the reactive power measurement in the  presence of harmonics is very close to the value of reactive power of the fundamental component    Electronic meters which are more and more popular may carry out measurements using vari   ous methods  For example  they may measure active and apparent power  and then calculate the  reactive power from the power triangle  Square root from the sum of both such powers squared    In reality  taking into account IEEE 1459 2000 standard  they measure the non active power  not  the reactive power  Another manufacturer may use the method
136. most types of passive receivers active power is positive  When clamps are in   correctly connected  it is possible to change their polarity using  Sonel Analysis  software     CE POM 711 When measuring overvoltages  transients  is also required  remember that  the analyzer measures them in relation to PE input  Therefore  in such cases always ensure that  PE input of the analyzer is connected to a local earthing  This remark applies to all types of sys   tems  including 3 wire systems  Unconnected PE conductor will result in a failure to detect transi   ents  In 3 phase 3 wire systems  to be able to detect transients in L3 voltage channel  a L3 in   put must be connected to the tested mains  in these systems  when transients measurement is  not needed  L3 input can be left disconnected      The following figures show schematically how to connect the analyzer to the tested network  depending on its type     Icons used in the drawings with respect for optional connections have the following meanings      Urre  if Un pe voltage measurement is required  make connection as shown by the icon in dia   gram  connect PE input to the protective conductor     Cin  i In current measurement is required  make connection as shown by the icon in diagram   connect clamps in channel In       Trans   jf transients measurement is required  make connection as shown by the icon in dia   gram  connect PE input to the local earthing or protective conductor  and L3 input de   pending on mains system 
137. nd analyze power quality parameters  In order to provide safe operation  and correct measurement results  the following recommendations must be ob   served     e Before you proceed to operate the analyzer  acquaint yourself thoroughly with the present   manual and observe the safety regulations and specifications provided by the producer    e Any application that differs from those specified in the present manual may result in damage  to the device and constitute a source of danger for the user    e Analyzers must be operated only by appropriately qualified personnel with relevant certificates  authorizing the personnel to perform works on electric systems  Operating the analyzer by  unauthorized personnel may result in damage to the device and constitute a source of danger  for the user    e The device must not be used for networks and devices in areas with special conditions  e g   fire risk and explosive risk areas    e tis unacceptable to operate the device when     itis damaged and completely or partially out of order     its cords and cables have damaged insulation    e Do not power the analyzer from sources other than those listed in this manual    e  f possible  connect the analyzer to the de energized circuits    e Opening the device socket plugs results in the loss of its tightness  leading to a possible dam   age in adverse weather conditions  It may also expose the user to the risk of electric shock    e Repairs may be performed only by an authorized service point
138. nd solve other problems related to widely understood power quality issues    The power source quality parameters  as well as the properties of receivers  are described  with many various parameters and indices  This paper can shed some light on this area    As already mentioned  the lack of standardization of measurement methods has caused sig   nificant differences in values of individual mains parameters calculated with various devices  Ef   forts of many engineers resulted in IEC 61000 4 30 standard concerning power quality  For the  first time  this standard  and related standards  provided very precise methods  mathematical rela   tions and required measurement accuracy for power quality analyzers  Compliance with the  standard  in particular  the class A  should be a guarantee of repeatable and almost identical  measurement results of the same magnitudes measured with devices from different manufactur   ers     5 1 1 Current Transformer  CT  clamps for measuring alternating currents  AC     CT clamps  CT   Current Transformer  are simply large current transformer processing high  current of the primary winding into the lower current in the secondary winding  The jaws of typical  current clamp are made of a ferromagnetic material  e g  iron  wound around the secondary wind   ing  The primary winding is a conductor around which the clamp jaws are closed   usually it is one  single coil  If the 1000 ampere current flows through the tested conductor  in the secondary wind  
139. nformation about configuring Wi Fi connection and the ways of connecting with the  meter  refer to section 2 12    2 7 Taking measurements    2 7 1 Measurement Points    The analyzer allows the user to store four completely independent measurement configura   tion  which are called  measurement points   Number of active measurement point is shown in the  upper left corner of the screen     Press buttons     and Cc at the same time and hold them pressed for 1 second to dis   play the screen for selecting the measurement point Fig  15     Choose measurement point     P1 P2 P3 P4       Fig  15  Selection of the measurement point     To select one of the four points  press the corresponding button indicated by a triangle on the  screen     e to select measurement point 1  select D  e to select measurement point 2  select  e to select measurement point 3  select  e to select measurement point 4  select    After selecting the measurement point the analyzer displays the phasor diagram  screen 1 9    and checks the validity of mains connections  If an error is detected  the device emits a long beep     If the user chooses to not to select the measurement point and does not press any key  after a  few seconds  the analyzer returns to the previous screen     In some cases  changing the measurement point is not possible  At least two of such cases  are as follows     24    2 Operation of the analyzer    e the analyzer is recording  in such case the device displays message  Recording in 
140. nmental conditions and other technical data            1 cccccssseccseeeereneees 115  6 13 Safety and electromagnetic compatibility          cccccccseeeececeeeeeceseneseceesaneeees 115  0I      21610  218  cee nee ee eee eee a 116  7  EQUPMEN See eee ne eee eee eee eee 117  7 1 Standard equipment        cccccccccesseeceeecceecesuesseeceesesssueeseecesssssaaeeseeeeessssaaeeeseees 117  7 2 Optional accessories       ccccccccccssseeseeecceecseeeseeceesessaueeeceesssssseeeecesssssaaeeeseees 117  7 2 1 GA CUON CaN Aer ee eE E en eae ne nee 118  7 2 2 O  Cunen CAND aoas aE EE o E EAEE E AE EE REEERE 119  7 2 3 C 6 current clamp us seeccccccccsneeeeccceesssueeeecesessseeuseceessssueeseeessssasaeeeeeessssaaeeeeessssaanes 121  7 2 4 Cr Cunen CaN riser ae AE O N 123  7 2 5 F 1 F 2 Fo curent lampe serere sre peee EEE EE EEEE EENES 124  7 2 6 External active GPS antenna eccszcdedtesemadincctadspdeerncupreavseetectecicedictieesdxaeteeleais 125   8 Other Information te iota ss secs vase eases epee ninina aaa 126  8 1 Cleaning ANA maintenance         sseeeccccsseeeeecseaeeeeessaeeeeesaaseeeesssaaeseessaaeneeesees 126  8 2 RO 18 EI E ETAR EE E EE E E E E E T 126  8 3 Dismantling and utilization       ccsceccccssneeeeceeeseeeecesaueeeecssaneceeessaaeeeessaaesessasanes 126  8 4 ManutactuUrOT  sesepi SEE EE EE E 126    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    1 General Information    1 1 Safety    PQM 702  PQM 703  PQM 710 and PQM 711 devices are designed to measure    AN record a
141. nsformers is usually very narrow  so the net   work disturbances at high frequencies  e g  lightning surges  are largely    suppressed and distorted on the secondary side of the transformer  This  should be taken into account when making transient measurements in  configuration with transformers        2 9 Example of use    The procedure presented below shows how to make a sample measurement with the  analyzer     step by step      from connecting the device to generating the measurement report  It  provides guidelines how to quickly start to operate the analyzer and Sonel Analysis software  It is  assumed that Sonel Analysis software is already installed  The example assumes the use of  PQM 703 analyzer  If using an analyzer without transient measurement capability  skip settings  that refers to transient measurement     Scenario  single phase measurement acc  to user settings     Measurement scenario is as follows  the user wants to measure voltage parameters of 1   phase network 230 V 50 Hz  The measurement is to be made with averaging equal to 1 second   The following parameters are to be recorded    e average values of voltage  THD and harmonics    e frequency    e voltage event detection should be turned on and set at level of  105  Unom for swell  95   Unom for dip  10 Unom for interruption  When an event is detected  the waveform and  RMS  graph must be recorded    e transients should be activated at the lowest possible voltage threshold of 50 V  the most  sensitive s
142. nsient module monitors the  voltage between the inputs   e L1 PE   e L2 PE   e L3 PE   e N PE     Note  For proper measurement of transients  it is necessary to connect PE input    of the analyzer to the local earthing system  It is also required for 3 wire  delta and wye systems without neutral conductor        61    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    3 10 1 Threshold method    Threshold method is chosen by selecting Threshold  in voltage settings of the measurement  point  and setting the threshold voltage in the range from 50 V to 5000 V  In this method  the ana   lyzer detects a transient after it exceeds the pre set amplitude in volts  Transients  whose ampli   tude does not exceed the set threshold will not be detected by the analyzer  In this mode  the  waveform rise time is not taken into account  Both slow and fast transients will be detected  when  the amplitude criterion is met    NOTE  Threshold value entered is a transient amplitude  not the absolute voltage referred to  the PE earth voltage level     3 10 2 Slew rate  dV dt  method    Slew rate method  dV dt  is activated by selecting Slew rate and indicating an appropriate  sampling rate  which indirectly selects the voltage slew rate from several available values  see  Tab  5   In dV dt method the device analyses the voltage waveforms in a specific time window and  detects transient  if the slew rate in the window exceeds the value set by the user in settings  The  absolute amplitude of the
143. nt in  the Internet with this IP and port    PC from which the user tries to connect with the analyzer via GSM modem must have ac   cess to the Internet     Sonel Analysis  software while searching for analyzers  tries to connect to those analyz   ers that have IP number configured in the data base  additionally the user must enable   TCP IP over GSM  in program settings   Only port 4001 of a remote host is checked by  default    If an analyzer is found under typed address and its serial number match the serial number  of an analyzer is the database  then the device will be shown in the list of found devices   After connecting the communication will be performed via the Internet  After completing  the connection  the software closes the connection with the analyzer  which enters a   stand by  mode waiting for a client connection     2 11 2 Modem Configuration    In order to configure the SIM card and modem in the analyzer  the user must obtain the fol   lowing data from the data transmission service provider     40    PIN code for SIM card   PUK code for SIM Card   for emergency cases  when SIM card is locked after repeated  attempts of enter wrong PIN    IP number assigned to SIM card  it must be a static number     APN  Access Point Name     user name and password  optional  usually not required      Configure the analyzer for GSM connectivity in the following manner     connect to the analyzer via a USB cable  If the analyzer is not present in the database it  should added
144. nterharmonics amplitudes   current THD and TID   all power values in a given channel   power factor and cos      the angles between voltage and current harmonics   harmonics active and reactive power  tang and K factor     Total values of the system are zeroed only if all current channels are below the reset thresh   old  Then  the following values are also reset   e current unbalance factors and current symmetrical components     For events  some parameters are managed in a way that takes zeroing into account  The pa   rameter value is taken into account  when detecting start and end of the event and calculating ex   treme and average values  only when the current value is above the threshold  Parameters man   aged in this way include    e current crest factor   e current THD and TID     62    3 Design and measurement methods    e power factor and cos      e tang and K factor   e current unbalance     Zeroing is highlighted in live mode and in analysis  In order to distinguish between the actual  measured value from zeroed value of reset parameter  the following rules apply    e in live mode  the zeroed values are marked with   symbol  asterisk  next to a value  e g   0 000       e inthe data analysis  the heading of a parameter that can be zeroed is marked by adding  symbol  e g   I   L1  A    single cells are not selected but only the header to indicate that  the limiting function was applied     e the display of the analyzer shows the zeroed values in grey          3 12 E
145. nusoidal systems     pa ee    Sa   COSQ       In non sinusoidal systems such simplification is not acceptable and the power factor is calcu   lated based on the actual ratio of active power and apparent power     PF       S    In single phase systems  the apparent power is calculated as shown in the formula above and  there are no surprises here  However  it turns out that in three phase systems calculation of this  power is equally difficult as calculation of reactive power  Of course  this is related to actual sys   tems with non sinusoidal waveforms which additionally can be unbalanced    The tests have shown that the formulas used so far can give erroneous results if the system is  unbalanced  Since the apparent power is a conventional parameter and does not have a physical  interpretation  determination which of proposed apparent power definitions is correct could be dif   ficult  Yet  the attempts have been made  based on the observation that the apparent power is  closely related to the transmission losses and the power factor  Knowing the transmission losses  and the power factor  one can indirectly specify a correct definition of apparent power    The definitions used so far include arithmetic apparent power and vector apparent power   The test have shown however that neither the arithmetic definition nor the vector definition give  correct value of the power factor  The only definition which did not fail in such a situation  was the  definition proposed as early as 
146. oe Ps    haad       aiat h aiad    4    raras    100us Ims ms 10ms 20ms 100ms 058 1s 10s Time    Fig  53  Voltage tolerance curves  ANSI  ITIC  and CBEMA     0        The vertical axis of the graph presents voltage in percent of the nominal value  whereas the  horizontal axis presents time  in logarithmic scale   The middle part of the graph  between curves   represents the area of the correct operation of the device  The area above represents high voltage  conditions that may damage the device or trigger over voltage protection  while the area under the  curves represents a situation of low voltage in mains  which may disconnect the power supply or  temporary power shortage resulting in incorrect operation of the equipment    As shown in the graph  there is a relationship between the voltage value and the duration of  the disturbance  For example  voltage swell of 200  Unom and with duration of 1 ms  in typical  cases  does not result in failure or malfunctioning  point between curves   but an interference of  such amplitude  which lasts for half period of the mains may be have very adverse effects  the  point above two curves   Generally it is accepted that in a typical situation  events occurring in the  power grid when it comes to the value of the mains voltage  should fit in the middle area of the  graph  between curves  and then they should not lead to malfunction or damage to the connected  equipment  Equipment manufacturers  especially power adapters  often use this p
147. ogowski   a German physicist  It is an air core  coil wound around a conductor with current  Special de   sign of the coil allows leading out its both ends on the  same side  thus facilitating clamp placement around the  conductor  the return end is placed inside the coil at its  entire length   The current flowing through the measured  conductor causes centric magnetic field lines which due  to the self induction phenomenon induce the electromo   tive force at the end of the coil  This voltage  however  is  proportional to the rate of current change in the conduc   tor  and not to the current itself    Rogowski coil has some undeniable advantages  compared with current transformers  As it does not have    HO   X    Re e  A  To  ee      PATA  YY    3    V           Fig  44  Rogowski coil    5 Power quality   a guide    a core  the core saturation effect is eliminated  thus being a perfect instrument to measure high  currents  Such coil has also an excellent linearity and a wide pass band  much wider than a cur   rent transformer  and its weight is much smaller    However  until recently the wider expansion of flexible clamps in the current measurement ar   ea was difficult  There are some factors that hinder the practical implementation of the measure   ment system with a Rogowski coil  One of them is a very low voltage level which is induced on the  clamps  it depends on geometrical dimensions of the coil   For example  the output voltage for 50  Hz frequency of the F series
148. onnection via Internet    When connected to an access point  the analyzer starts TCP IP server connections with static  IP address or with an address assigned by DHCP server of the access point  The port used in the  local network and for direct connections is 4002    Due to the possibility of using dynamic address  during the operation in local network and with  direct connection  Sonel Analysis software scans the entire subnetwork to find the analyzer with  MAC address corresponding to the one assigned to the analyzer with a given serial number    Connecting to the analyzer via the Internet requires a Wi Fi router properly configured by the  network administrator    The analyzer  which has no access point within its range  remains in scanning mode of  2 4GHz Wi Fi band     Remote connection of Sonel Analysis software via Wi Fi is possible  when this mode is active  in software settings  Software Configuration  gt  Active Media  Fig  32      45    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    2 12 2 Factory configuration  The factory Wi Fi configuration of the tablet and the analyzer is as follows   e The tablet is configured as an access point   o Network SSID  AP_analyzer_serial_number  e g  AP_BR0O001   o IP number of the access point  192 168 173 1   o Subnet mask  255 255 255 0  o Automatic assigning of IP addresses  DHCP   enabled  o WPA encryption is active  the key is the same as SSID  e Analyzer settings   o Network SSID  AP_analyzer_serial_number  e g  AP_
149. or  reactive power compensation    It must be clearly said that this parameter has given relatively good results only in conditions  of slight distortion of voltage and current waveforms    IEEE 1459 2000 standard lists this definition of power  however just like in case of Budeanu  reactive power  it has a non removable defect and it is recommended to discard it entirely  Instead  of Ds  another value was proposed to reflect total distortion power in a system in a better way     it  is called non fundamental apparent power Sen  Sen power allows a quick estimation whether a  load works in conditions of small or large harmonic distortion  it is also a basis for estimating the  static values and active filters or compensators    According to the definition  for 3 phase systems      Sen    Se   Si    Se1   3le1 Vex    where     Effective current and RMS voltage of the fundamental component  le1 and Ue  respectively   are calculated similarly to    and Ue but instead of RMS phase to neutral or phase to phase volt   ages  the effective voltages of fundamental components are substituted    In single phase systems to calculate the distortion apparent power  a simpler formula may be    used   Sy   yS a  U 1       where U  and    are effective values of the fundamental components of phase to neutral voltage  and current     85    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    5 3 7 Power Factor    True Power Factor or Power Factor  TPF or PF  is the value which takes into acco
150. ow describing the specific event displays time of the  event  start and end   extreme value  e g  minimum voltage during the dip   waveform and RMSj 2  graph when the event was voltage  or current related  In this scenario  event graphs were  activated in settings  therefore when the analyzer detects any event  the last column of the table   with Waveform header  should include a graph icon  Click it to display the graphs     37    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    2 10 Time Synchronization    2 10 1 Requirements of IEC 61000 4 30    The analyzer has a built in GPS receiver  whose main purpose is to synchronize the analyzer  clock with an atomic clock signal distributed via GPS satellites  Time synchronization of the ana   lyzer with UTC is required by IEC 61000 4 30 standard for Class A for marking the measurement  data  Maximum error cannot exceed 20 ms for 50 Hz and 16 7 ms for 60 Hz  Such action is nec   essary to ensure that different analyzers connected to the same signal provide identical read outs   Synchronization with UTC is also needed when the network of analyzers is dispersed  When the  source of the time signal becomes unavailable  an internal real time clock has to ensure the accu   racy of time measurement with accuracy better than  1 second to 24 hours  but even in these  conditions  to ensure the compliance with class A  the accuracy of measurement must be the  same as previously specified  i e   max  1 period of mains      2 10 2 GPS re
151. ows     S2    P    D    Q   D     D  is the scattered power  which occurs in the system  as a result of changing conductance of  the receiver with frequency  Thus  the presence of reactive elements may result in the scattered  power    In this equation  reactive power Q appears when there is a phase shift between the voltage and  current harmonics    D  means the unbalanced power which is a measure of unbalance of a three phase receiver   This component explains the situation in which an unbalanced three phase load of a purely resis   tive character results in the power factor less than one  Such receiver has no reactive power Q   and still the results from the power triangle S  P  Q are totally different  the Budeanu   s power theo   ry with its distortion power could not explain this situation either     in a purely resistive receiver  the  distortion power Dg equals zero     An attempt to combine IEEE 1459 2000 standard with the Czarnecki   s power theory leads to  the conclusion that non active power includes at least three separate physical phenomena  which  influence the reduced effectiveness of energy transmission from the source to the receiver  i e   reduction of the power factor     P P  PF           Se JP2 D   Q   D     In IEEE 1459 2000 standard  reactive power known as Q has been limited to the fundamental  component and it applies both to single phase and three phase systems   In single phase systems     Q    Uh sing   81    PQM 702  PQM 703  PQM 710  PQM 711 Op
152. p computer    Data analyzed on the tablet may be freely transferred to a desktop computer  This may be  performed in at least two ways     1   2     Copy the data from the tablet to a micro SD card or USB memory  then transfer them to  any computer   Use the Wi Fi connection  To do this   make sure that the tablet has its Wi Fi access point enabled  Fig  33   connect the computer to the access point of the tablet  Fig  38   open File Explorer  Fig  39  and enter IP address of the tablet   192 168 173 1  the tablet should display an assigned folder  from which you can copy files to the com   puter       Obecnie po    czono z  tt  AP_BS0003  is E Brak dostepu do Internetu    WBK  Dostep do Internetu    Po    czenie sieci bezprzewodowej A    NetworkProfile Potaczono all     Nazwa  NetworkProfile   WBK Sita sygnatu  Znakomita  Typ zabezpieczen  WPA2 PSK  Typ radia  802 11n  SSID  AP_BS0003          Otworz Centrum sieci i udostepniania             Fig  38  Available wireless connection view in Windows     53    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Sa NAE      9 f Przeszukaj  192 168 1731      Plik Edycja Widok Narz  dzia Pomoc          Organizuj    Centrum sieci i udost  pniania 2   aaa  jj e  a        Ulubione J iae      Ostatnie miejsca Udzia    l   Pobrane  E Pulpit       Biblioteki    Dokumenty     Muzyka  1  Nowa biblioteka      Obrazy    a Wideo    1 element  A    A    Fig  39  Tablet   s shared folders view in Windows        2 13 Notification of analyzer c
153. placed with waste of another kind    Worn out electronic equipment should be sent to a collection point in accordance with the law  of waste electrical and electronic equipment    Before the equipment is sent to a collection point  do not dismantle any elements    Observe local regulations concerning disposal of packages  waste batteries and accumula   tors     8 4 Manufacturer    The manufacturer of the device and provider of guarantee and post guarantee services     SONEL SA  ul  Wokulskiego 11  58 100 Swidnica    Poland  Front desk   48 74 85 83 860  Fax   48 74 85 83 809    e mail  export sonel pl  internet  www sonel pl    Note    Service repairs must be performed only by the manufacturer        126    Notes    127    
154. progress    e the communication with a PC is in progress  via USB  OR 1  Wi Fi or GSM   In this case   LEFT and RIGHT keys are inactive     The user may assign any chosen percentage of memory to each point  e g  100  for the first  point and 0  for others or 25  for each point   If any measurement point has the whole memory  assigned  selecting any other measurement point results in displaying the number of selected  point alternately with the symbol of the sine wave  indicating that the parameters may be viewed  only in  LIVE  mode     2 7 2 Start   stop of recording  When the selected measurement point still has the assigned disk space left  the user may    start recording by pressing button     or initiate it from the software using connected PC    Starting the recording mode depends on how its configuration during the configuration of the   measurement point  There are three modes available    e Immediate start   when recording begins immediately after pressing the button    e start after detecting the first event   in such case the analyzer waits for the record triggering  event  i e  when the first of the parameters configured for the measurement point exceeds  the threshold triggering the event  While waiting for the event  the analyzer uses the status  bar to display the number of the measurement point alternately with the symbol of slope with  an arrow    e start according to scheduled recording time  Screen 8 may be used to see the next  scheduled start and end of t
155. r quality   a guide    e Power Line Carrier Communication  PLCC  frequency range from 3 to 148 5 kHz   e Marking signals  short transients imposed at a specific point on the voltage waveform     Since the introduction of such signals to the power supply may have negative consequences  for some devices  similarly to the effect of harmonics or interharmonics  EN 50160 standard de   fined limits for the 3 second mean values of such signals  as shown in Fig  47  During the meas   urement  99  of average 3 second control signals values must be below the specified limit     Low frequency signals  up to 3 kHz  are used for switching on off the loads  filters and protec   tion devices  One application is to control the street lighting or  in some countries  remote control   ling of HVAC devices  Often  this kind of signals are used for customers using two types of energy  tariff  e g  when using a cheaper night tariff  the energy supplier automatically disables selected  loads   This type of communication is usually unidirectional  Due to the low attenuation features of  the distribution network at this frequency range  attenuation increases with increasing frequency    communication using this method allows users to achieve the greatest range of transmission   even hundreds of kilometres   During the transmission control signal is transmitted in several  packages and repeated at specified intervals  The period during which the signal is active may be  quite long  e g  for 2 seconds 
156. re  measured  Each line current is a sum of two phase currents  In the wye without N type receivers   we know the currents flowing through impedance  but we do not know the voltages  each phase   to phase voltage is a sum of two phase to neutral voltages    We need to take account of the fact that at given voltage values at terminals and currents  flowing into such    black box     there is an infinite number of variants of receiver internal structure  which will give us identical measurement results of voltage and current values visible outside the  black box    Then  how is it possible that there are reactive power meters intended for measurements in  three wire systems and the mains analyzers which allow the reactive power measurement under  such circumstances    In both cases  the manufacturers use the trick which involves an artificial creation of a refer   ence point  virtual neutral terminal N   Such point may be created very easily by connecting to the  terminals of our black box a wye connected system of three resistors of the same value  The po   tential of the central point in the resistor system is used to calculate the  phase voltages   Obvi   ously quotation marks are justified here  as such virtual zero will provide quite correct results only  when the unbalance of the receiver is minimal  In any other case  an indication of reactive power  from such device should be treated very cautiously    In no case should a measuring instrument mislead the user  and such 
157. reases with decreasing frequency    e flicker  also in this case subharmonics have particularly adverse effects  For example  subharmonic with 8 8Hz frequency causes the modulation of mains voltage within the  range  where human eye is most sensitive to this phenomenon  see also sec  5 2    low frequency oscillations in mechanical systems   interferences in the operation of control and protection systems   telecommunications and acoustic interferences   saturation of magnetic cores by subharmonic components  e g  transformers  motors   etc      The interaction of higher harmonics and interharmonics may also lead to unexpected phe   nomena such as beating in at low frequencies  For example  ninth harmonic  450 Hz  with inter   harmonic of 460 Hz frequency generates the effect of beating in at the frequency of 10 Hz  de   spite the fact that in this frequency spectrum a component of this frequency is not present  Human  eye is very sensitive in this frequency range  and the interaction may lead to a significant flicker    91    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    effect  230 V 50 Hz voltage waveform for this case is presented in Fig  45  significantly higher lev   el of the interharmonic was assumed in this case to illustrate the effect better      400   300 sul   i             I  ott ft VY MO rl fy  oo  4 HV TL et dy TA TY LE    SUAUAURERRGHEURUAER  i COO  e AAA  ea     400    O    Fig  45  The effect of 9th harmonic interaction  450 Hz  10  Unom  and interh
158. ring transients is available only for PQM 703 and  PQM 711     Analog to digital converters  typically used in power quality analyzers  have relatively low  sampling frequency and are insufficient to provide required accuracy of transient recording due to  the short term nature of these disturbances and their wide frequency spectrum  For this reason   PQM 703 and PQM 711 analyzers are using a separate 4 channel A D converter with a maximum  sampling frequency of 10 MHz  This corresponds to the time between individual samples of 100  ns  In this mode it is possible to record the fastest transients  and the recording time reaches  2ms     60    3 Design and measurement methods    Tab  5  Summary of transient measurement modes in PQM 703 and PQM 711       eer   Recording time range  Sampling frequency   Rise time with dV dt method  2000   20000 samples     10 MHz 100 V 5 us 0 2   2 ms  5 MHz 100 V 10 us 0 4   4 ms    100 kHz 100 V 500 us 20   200 ms    To configure the transients measurement  a few options are provided for the user   e main sampling frequency of A D converter in the range from 100 kHz to 10 MHz   e detection method  based on the set minimum transient amplitude  from 50 V to 5000 V  or  a minimum slew rate  dV dt method    e switching recording on off of the transient waveforms   e recording time for timeplot in the range from 2 000 to 20 000 samples   e _pretrigger time is within the range of 10  to 90  of the recording time        The analyzer records the timep
159. ription     V  AutoPIN    Fig  27  Entering GSM settings in the analyzer database    If you remove the SIM card from the slot  the analyzer will display error message  No SIM  card   This message is repeated during next activations of the analyzer  Removing the SIM card    41    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    while the analyzer is in operating mode  it is not recommended  as it prevents correct analyzer  logging off from the GSM network     Note    After any change in GSM settings  its automatic restart is initiated        2 11 3 Checking GSM connection    If status screen  lt 8 9 gt  shows the status of GSM modem as  Ready   lt connection type gt    it  means that a connection from a remote PC may be performed via Internet  The user may perform  a test connection to verify the connectivity with  Sonel Analysis       e Inthe program settings  check whether the search of the analyzers via GSM network is  enabled  select Options  gt  Configuration gt  Media settings gt  Active media  Check  TCP IP over GSM box    e The analyzer that is chosen for the connection must be entered into the Analyzer data   base  when the modem was configured as described in sec  2 11 2 this will be ensured     e Disconnect any connection to the analyzer  USB or OR 1     e Perform a search for the analyzer  selecting any available method  e g   by clicking Live  mode   The search list should show the analyzer with note   GSM    Select the analyzer  and click OK    e After awhi
160. rmers caused by higher harmonics     active and reactive powers of harmonics    the angles between voltage and current harmonics    power factor  cos   DPF   tang    unbalance factors and symmetrical components for three phase mains    flicker severity Ps and Pi    interharmonics of voltages and currents  up to 50th     Total Interharmonic Distortion TID  and TIDpg for current and voltage    mains signaling voltage in the frequency band of 5   3000 Hz     Some of the parameters are aggregated  averaged  according to the time selected by the us   er and may be stored on a memory card  In addition to average value  it is also possible to record  minimum and maximum values during the averaging period  and to record the instantaneous val   ue occurring at the end of aggregation period     The module for event detection is also expanded  According to EN 50160  typical events in   clude voltage dip  reduction of RMS voltage to less than 90  of nominal voltage   swell  exceed   ing 110  of the nominal value  and interruption  reduction of the supplied voltage below 5   of  the nominal voltage  The user does not have to enter the settings defined in EN 50160  as the  software provides an automatic configuration of the device to obtain power quality measurement  mode compliant with EN 50160 The user may also perform manual configuration   the software is  fully flexible in this area  Voltage is only one of many parameters for which the limits of event de   tection may be defined  For 
161. rocess will be suggested by the analyzer by displaying message  Update firmware          Button cy triggers this process  3 short beeps  and its progress may be observed on the    display  The update may be skipped by pressing the briefly button cop When he update is  successfully completed  message  Update successful      will be displayed or in other case   Update Failed      Then the analyzer will automatically switch off    e After switching on  the analyzer is activated at the last measurement point and displays 1 9  screen with a phasor diagram     e To switch the analyzer OFF  keep button Gop pressed for 2 seconds  when no buiton or  recording lock are active    e Pressing the active button results in a short beep of a higher pitch  for inactive button the beep  is longer and at a lower pitch     e Pressing button   a  or Cc for at least 1 5 s forces the display to refresh   2 3 Auto off    When the analyzer operates for at least 30 minutes powered by the battery  no power supply  from mains  and it is not in the recording mode and PC connection is inactive  the device automat   ically turns off to prevent discharging the battery    The analyzer turns off automatically also when the battery is fully discharged  Such emergen   cy shut down is performed regardless of the mode of the device  In case of active recording  it will  be interrupted  When the power supply returns  the recording process is resumed  Emergency  shut down is signalled by message  Battery discharged
162. s required for a correct power measurement     Warning  Do not use the device on non insulated conductors with a poten     tial of more than 1000 V in relation to the earth and a measure   ment category greater than Ill        e Reference conditions    e Temperature   18    22  C   e Conductor position  centered in relation to the clamp loop  e Continuous magnetic field  earth field   lt 40 A m    e Alternating magnetic field  none   e External electric field  none    e Technical specification    e Rated measuring range  1 A   3000 A   10000A peak for 50 Hz   e input output ratio  38 83 mV 1000 A  50 Hz   46 6 mV 1000 A  60 Hz   e Basic uncertainty   1  in the 1 A   3000 A range  e Linearity   0 2   e Additional error caused by conductor position  2  max   e Additional error caused by external magnetic field    0 5  max   e Additional error caused by temperature   0 07   e Output impedance  30 2 400 mm    124    7 Equipment    7 2 6    e Remaining data     e insulation type     protection rating acc  to IEC 60529   coil diameter    closing unit diameter  maximum    coil circumference     internal coil diameter  closed clamp    e weight     e clamp lead length   e operating temperature   e electromagnetic compatibility     External active GPS antenna    e frequency    e polarization    e LNA gain    e VSWR    e dimensions  without cable     e operating temperature    e protection rating acc  to IEC 60529   e cable length    e current consumption    e mounting        measuring 
163. sabled   2  Wi Fi access point was disabled  The distance between the analyzer and the tablet is too  large in case of a direct connection   4  The distance between the analyzer and the Wi Fi access point or between computer  tab   let  and the Wi Fi access point  5  Too much interference in the channel used for the transmission     52    2 Operation of the analyzer    Solution     1   2     3     Connect the analyzer via USB cable or GSM network and enable Wi Fi transmission in  the analyzer  Fig  34    Turn on a Wi Fi access point and wait until the analyzer connects to it  On screen  lt 10 10 gt   Wi Fi status is  Ready     Approach with the tablet to the analyzer and try to connect again  Preferably  the analyzer  should be within sight  then screen  lt 10 10 gt  shows Wi Fi status and signal level  Only   Ready  status guarantees the connection  Preferably  the indicated signal level should  have at least two bars    If possible  place the analyzer computer  tablet  and or Wi Fi access point in a place  where the level of Wi Fi signal is indicated by at least two bars     both in the analyzer and  the computer    When the Wi Fi access point is the tablet  then it must be turned off and on again in the  settings window  Fig  33   This will force the Access Point to operate in other channel free  form interferences  However  if an external Wi Fi router is the access point  then force its  operation in another channel     2 12 8 Transferring data from the tablet to a deskto
164. ses of harmonic components in the frequency domain    In a perfect situation  voltage is generated in a generator which at output gives a pure sinus   oidal 50 60 Hz waveform  absence of any higher harmonics   If the receiver is a linear system   then also current in such situation is a pure sinusoidal waveform  In real systems  voltage and cur   rent waveforms can be distorted  hence in addition to the fundamental component there must be  harmonics of higher orders    Why is the presence of higher harmonics in the network undesirable    One of the reasons is the skin effect which involves pushing out the electrons from the centre of  conductor towards the surface as the current frequency is increasing  As a result  the higher the  frequency  the smaller the effective conductor cross section which is available for the electrons   which means that the conductor resistance is increasing  Consequently  the higher the current  harmonics  the higher effective cabling resistance for this harmonics  and this inevitably leads to  more power losses and heating of conductors    A classic example connected with this effect is related to neutral conductor in three phase  systems  In a system with little distortion  little unbalance and a balanced  or slightly unbalanced   receiver  the current in neutral conductor has the tendency of zeroing  it is much smaller that RMS  phase currents   Such observation has tempted many designers to obtains savings by installing  the cabling in such sys
165. sic    0   100 A AC  40 Hz  3 kHz  100 A AC  50 60 Hz     45   65 Hz  0 5   0 1 mV  40 Hz   1kHz    1 0   0 2mV       e ratio  5mV AC 1 A AC   e output impedance 119   e type of insulation  double  according to IEC 61010 1  e measurement category according to IEC 61010 1  III 300 V   e dimensions  100 x 60 x 26 mm   e   weight  approx  160 g   e maximum diameter of tested cable  O24 mm   e length of clamp cables  1 5m   e operating temperature  0  C    50  C   e    _ relative humidity   lt 85   non condensing   e electromagnetic compatibility  IEC 61326    123    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    7 2 5 F 1  F 2  F 3 current clamps    F 1  F 2 and F 3 flexible clamps  Rogowski coil  are used to measure the alternating current  of frequencies up to 10 kHz in the 1 A   3000 A range    The only difference between the F 1  F 2 and F 3 flexible clamps is the coil size  The electrical  parameters are identical    The output signal if voltage proportional to the derivative of the measured current  with the  sensitivity equal to 38 83 mV 1000 A for 50 Hz and 46 6 mV 1000 A for 60 Hz        Fig  62  F 1 clamp Fig  64  F 3 clamp    Fig  63  F 2 clamp    The output signal is supplied by a 2 meter lead with a pin adapted for the socket in the meter    The arrow located on the closing unit indicates the current flow direction  It is assumed that  the current is flowing in the positive direction if it is flowing from the source to the receiver  Such  clamp orientation i
166. signal is on and for 2 seconds it is off   this sequence is repeated  several times  There are cases when this type of transmission results in flicker  An example of this  type of transmission is shown in Fig  46     T2 2 s    signal level    time       Fig  46  An example of low frequency signal transmission     Higher transmission frequencies  and hence  higher bit rates  are typical for PLCC communi   cation  This type of communication uses modulation of amplitude or carrier frequency  or other  modulation method   Modern methods use complex algorithms to process signals in order to  achieve the highest resistance to interference and highest bit rate  transmission speed   PLCC  transmission continuously gains popularity and its application range increases  The communica   tion between network points may be bidirectional  The concept of so called smart grid is based on  PLCC  which is one of the main methods of communication between energy meters and central  points  The main application areas include  telemetry  optimization of power consumption  remote  control of loads  Attenuation of the distribution network limits the maximum transmission range   Maximum range may reach a few km  while there is a strong correlation between the type of mod   ulation  bit rate and achieved distances    At the same time  standardization works are in progress to use of higher frequencies  above  148 5 kHz to tens of MHz  for the purpose of short distance data transmission     93    PQM 702
167. ssive lines directly results from the duration of the  measurement window and is approximately 5 Hz    The analyzer collects 2048 samples per measurement window  for 50 Hz and 60 Hz   thus it  fulfills the requirement for FFT stating that the number of samples subject to transformation equals  a power of 2    lt is essential to maintain a constant synchronization of the sampling frequency with the  mains  FFT may be performed only on the data containing an integer multiple of the network peri   od  This condition must be met in order to minimize the so called spectral leakage  which leads to  falsifying information about the actual levels of spectral lines  The analyzer meets these require   ments  as the sampling frequency is stabilized by the phase locked loop  PLL      Because the sampling frequency may fluctuate over time  the standard provides for grouping  the main spectral lines of harmonics with the spectral lines located in their direct vicinity  The rea   son is that the energy of components may partially pass into adjacent interharmonics compo   nents    Two methods of grouping are provided   e harmonic group  includes the main line and five or six adjacent interharmonic components    e harmonic subgroup  includes the main line and one of each adjacent lines      harmonic harmonic harmonic  subgroup subgroup subgroup  order 1 order 2 order 3  FFT  output  50 100 150 frequency  Hz   1 2 3 harmonic order    Fig  41  Determining harmonics subgroups  50 Hz system     E
168. sured se     quence must be at least equal to 5  of the nominal voltage  or 1  of the  nominal current  If this condition is not fulfilled  the correctness of angles  is not verified        This feature allows user to perform quick visual assessment of mains parameters and their  compliance with the analyzer settings     Screen 2 is shown in Fig  6  It shows the measured values of RMS voltages and currents within  the tested system and the mains frequency     U1   224 5 V l  22 27 A  U2   227 6 V I2  28 39 A  U3   228 0 V IS  23 37 A  Unpe   0 028 Y In  10 95 A  f   50 00 Hz       Fig  6  Screen 2 with the values of effective voltages and currents     Screen 3  Fig  7  shows the active and passive power values  Power values of successive phases  are marked with numbers from 1 to 3  Total power values are displayed in the last line  marked as  P and Q      P1  4 825 kW O1  929 3 var  P2  6 301 kW 02  1 087 kvar  P3  4 981 kW O3  1 289 kvar    P   16 11 kW Q   3 307 kvar       Fig  7  Screen 3 with active and reactive power     Screen 4  Fig  8  shows values of apparent distortion power  marked as SN  and values of appar   ent power  S   When the user selected power measurement according to Budeanu method in   stead of apparent power distortion  the device displays distortion power  D      17    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    SN1  984 6 var   S1  7 617 kVA  SN2  778 3 var    2  10 04 kVA  SN3  1 100 kvar S3  8 081 kVA    SN   4 831 kvar S   26 28 kVA    
169. t  Techniques   General Guide on Harmonics and Interharmonics Measurements and  Instrumentation for Power Supply Systems and Equipment Connected to them    e IEC 61000 4 15 2011     Electromagnetic compatibility  EMC      Testing and Measurement  Techniques   Flickermeter   Functional and Design Specifications    e EN 50160 2010     Voltage characteristics of electricity supplied by public distribution  networks     Safety standards   e IEC 61010 1     Safety requirements for electrical equipment for measurement control and  laboratory use  Part 1  General requirements    Standards for electromagnetic compatibility   e IEC 61326      Electrical equipment for measurement  control and laboratory use   Requirements for electromagnetic compatibility  EMC      The device meets all the requirements of Class A as defined in IEC 61000 4 30  The sum   mary of the requirements is presented in the table below     Tab  3  Summary of selected parameters in terms of their compliance with the standards    IEC 61000 4 30 Class A    e Basic measurement time for parameters  voltage  current  harmonics  unbal   ance  is a 10 cycle interval for 50 Hz power supply system and 12 cycle in   terval for 60 Hz system    e Interval of 3 s  150 cycles for the nominal frequency of 50 Hz and 180 cycles  for 60 Hz     e Interval of 10 minutes    e Interval of 2 h  basing on 12 intervals of 10 min     e Synchronization of aggregation intervals   IEC 61000 4 30 Class A    e Clock synchronization to GPS time 
170. t 1mVp p  or 1 Ap p     DC up to 5 kHz   lt 1 5mVp p  or 1 5 Ap p   1 Hz up to 5 kHz   lt 0 5mVp p  or 0 5 Ap p     e Additional errors     e caused by current frequency  65  440 Hz   2   440  1000 Hz   5   1  5 kHz   4 dB  e caused by battery voltage   lt 1 A V  e caused by temperature   lt  300 ppm   C or 0 3  10  C  e caused by relative humidity in the10   85  range    lt 0 5     120    7 Equipment    e caused by position of  20 mm conductor     DC up to 440 Hz   lt 0 5   DC up to 1 kHz   lt 1   DC up to 2 kHz   lt 3   DC up to 5 kHz   lt 10     e caused by a parallel conductor with the 50   60 Hz AC  at 23 mm from the clamp     e common mode rejection ratio    e Other data  e insulation type     e measuring category acc  to IEC 61010 1     e protection rating acc  to IEC 60529     power supply    operating time with alkaline battery   dimensions    weight     clamp lead length    operating temperature   humidity    height    electromagnetic compatibility     7 2 3 C 6 current clamp    The C 6 is used to measure the alternating   current with frequencies up to 10 kHz in the  10 mA   10 A range   The output signal is voltage proportional to the  measured current with the 100 mV A sensitivity   The output signal is supplied by a 1 5 meter lead  with a pin adapted for the socket in the meter     The arrow located on one of the jaws indicates the  current flow direction  It is assumed that the cur   rent is flowing in the positive direction if it is flow   ing from the source 
171. tal component   h     harmonic order     In case of this parameter  the higher harmonics are much more important than the lower      each harmonic component is multiplied by its order squared    K Factor is useful when defining the requirements for transformers which must work in condi   tions of significant current distortion  It t is assumed that the transformer  which works in condi   tions  where K  x  will generate x times more heat than at purely sinusoidal current  K 1      5 5  Interharmonics    Interharmonics are components of the frequency spectrum for voltage or current with a fre   quency that is not a multiple of the fundamental frequency network  50 or 60 Hz   The cause of  interharmonics may be e g  asynchronous processes and transient states related to connection  processes  frequency converters that generate the output frequency different from the frequency  of the power supplying mains and introduce into the system spectral interharmonics  arc furnaces   induction motors and drives with variable load  Ripple control signals  i e  signals with defined fre   quencies generated in control systems and introduced into mains should also be considered as  interharmonics components  Interharmonics at frequencies lower than the mains fundamental fre   quency are called subharmonic components    The effects of interharmonics may include    e increased losses in mechanical motors  temperature rise  subharmonics are particularly   harmful elements  as the power loss inc
172. tate  e g  blank screen when it was blank before      After unlocking  the keyboard automatically locks again  if the user has not pressed any button  for 30 seconds     Note    Holding down buttons ST  and   op for 5 seconds results in an  emergency unlocking of the keypad and removes the lock        2 15 Sleep mode    The PC program provides an option to activate the  Sleep mode   In this mode  after 10 sec   onds of the recording  the analyzer switches off the display  From this point  every 10 seconds the  screen displays  in its upper left corner  the number of measurement point to indicate active re   cording  After completing recording  e g  when the memory is full  the screen remains blank until  the user presses a button     55    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    3 Design and measurement methods  3 1 Voltage inputs    The voltage input block is shown in Fig  40  Two measurement blocks are shown  on the right  side of terminals main voltage circuits are presented   they are used for majority of voltage meas   urements  Sampling frequency of this circuit is 10 24 kHz  Three phase inputs L1  L2  L3 and pro   tective conductor PE have common reference line  which is the N  neutral  conductor     COE Go On the left side  connection of transient module with input terminals  PQM 703  and PQM 711 only   As it is shown  all four channels are referenced to PE input  This circuit has  wide bandwidth  sampling frequency  up to 10 MHz  and a greater range of
173. tems with neutral conductor of a smaller cross section than in phase con   ductors  And everything went well until the appearance of odd harmonic orders which are multi   oles of 3  third  ninth  etc    Suddenly  the neutral conductor began overheating and the measure   ment showed very high RMS current  Explanation of this phenomenon is quite simple  In this ex   ample  the designer did not take into consideration two circumstances  in systems with distorted  waveforms  the higher harmonics might not zero in the neutral conductor  and quite to the contra   ry  they may sum up  and secondly  the skin effect and high harmonic currents additionally con   tributed to the neutral conductor heating     86    5 Power quality   a guide    Let s try to answer two basic questions   What is the cause of harmonic components in voltage   What is the cause of harmonic components in current     Seemingly  these two questions are almost identical  but separation of current and voltage is  extremely important to understand the essence of this issue    The answer to the first question is as follows  harmonics in voltage are a result on a non zero  impedance of the distribution system  between the generator  assuming that it generates a pure  sinusoid  and the receiver    Harmonics in current  on the other hand  are a result of non linear impedance of the receiver   Of course  it must be noted that a linear receiver to which distorted voltage is supplied will also  have identically distorted c
174. ters   the whole  procedure is performed by computing  there is no issue of component ageing  drifts etc  However   similarly to the analog version  the saturation problem may also occur and without adequate pre   vention it may cause the failure of digital integration  Please note that input amplifiers and analog   to digital converters have some limited and undesirable offset  which must be removed before the  integration process  The analyzer software includes a digital filter whose task is to completely re   move the DC component  The filtered signal is subject to digital integration  The resulting phase  characteristics are excellent and the phase shift for the most critical frequencies  50 Hz and  60 Hz  is minimal    Ensuring the smallest phase shift between current and voltage signals is extremely important  to achieve small power measurement errors  It can be shown that approximate power measure   ment error may be expressed in relation        Power measurement error   phase error  in radians  x tan    x 100     where tan    is the tangent of the angle between the current and its voltage fundamental compo   nents  The above formula indicates that measurement errors increase with decreasing displace   ment power factor  e g  with the phase error of 0 1   and cosp 0 5 the error is 0 8   Anyway  to  ensure accurate power measurements  the phase coincidence of voltage and current circuits must  be the highest     3 4 Signal sampling    The signal is sampled simultaneousl
175. that the Budeanu   s power theory has become so popular  There may be  several reasons for this  Firstly  engineers got accustomed to old definitions and the curricula in  schools have not been changed for years  This factor is often underestimated  though as a form of  justification it can be said that this theory had not been refuted for 60 years  Secondly  in the  1920s there were no measuring instruments which could give insight in individual voltage and cur   rent harmonic components and it was difficult to verify new theories  Thirdly  distorted voltage and  current waveforms  i e  with high harmonics contents  are a result of revolution in electrical power  engineering which did not start before the second part of the last century  Thyristors  controlled  rectifiers  converters  etc  began to be widely used  All these caused very large current distortion    80    5 Power quality   a guide    in the mains  and consequently increased harmonic distortion  Only then the deficiencies of Bude   anu s theory became evident  Finally  the scientific circles related to power engineering were  aware of the fact that industrial plants had invested a fortune in the measuring infrastructure  en   ergy meters   Any change in this regard could have huge financial implications    However  slow changes in the approach of electrical engineers began to be visible  With time   as non linear loads were more and more frequent and the waveforms more and more distorted   the limitations of use
176. the analyzer  This window should display one analyzer found  if not  click  Search again     Select the found analyzer by double clicking it  If the analyzer has not been added yet to the  database of the analyzers in the program  a window will be displayed prompting user to enter PIN  code of the analyzer  Default factory code is  000   three zeroes   Proper connection is confirmed  by displaying window  Connection established   the analyzer screen will display  Connected to PC   USB       Step 6  Then a message will be displayed asking user to confirm the read out of settings  Click   OK  and then in the confirming window also  OK   Doing this will upload the settings of all four  measurement points   they may be viewed and changed in Settings window     Step 7  Checking allocation of the memory  In the top part of Settings window  the program  displays panel  Local   The first item in this panel is Analyzer settings  In the main part of the  window  one of the three tabs is displayed  Analyzer type  Memory allocation  GPS  synchronization   Display Memory allocation tab and ensure that there is enough space   memory allocation  on the memory card  default is 25   for measurement point No  1  When the  space is very little or set at 0   adjust it using sliders     Step 8  Modify the settings of measurement point No  1   carry out this operation as presented in  the scenario above  In Local panel click  Measurement point 1  to modify the settings for this  point and expand t
177. the measurement must be  long  Ps equal to 1 is considered to be a value on the border of annoyance     certainly sensitivity  to flicker is different for different persons  this threshold has been assumed basing on tests carried  out on a representative group of people    What causes flicker  Most frequently  the reason is the voltage drop as a result of connecting  and disconnecting large loads and some level of flicker is present in the majority of mains sys   tems  In addition to the previously described adverse impact on human health  flicker does not  need to be  and usually it isn t  a symptom of malfunctioning of our installation  However  if a ra     7     PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    ther abrupt and unexplainable flicker increase is observed in the mains  increased Ps and Pi pa   rameters  it should not be ignored under any circumstances  It may turn out that the flicker is  caused by poor connections in the installation     increased voltage drops on connections in the  distribution panel  for example  will result in higher voltage fluctuations on the receivers  such as  light bulbs  The voltage drops on connections also cause their heating  and finally sparking and  possibly a fire  Periodical mains tests and described symptoms may turn our attention and help  find the source of hazard     5 3 Power measurement    Power is one of the most important parameters determining the properties of electrical cir   cuits  The basic unit used in fin
178. tifications or temporary loss of network coverage    Solution  In case of SMS error  check the correctness of the entered phone number  In other  cases  do not take additional steps  The analyzer will try to repeat the operation after  some time  e g  5 minutes      2 12 Wi Fi communication mode  POM 710 gug    2 12 1 General Information    PQM 710 711 analyzers are equipped with Wi Fi module working in IEEE 802 11 b g standard  and n single stream  access points with a single antenna   This allows the analyzer to communi   cate with the tablet  computer  remotely  A direct connection  tablet  lt  analyzer is possible  Fig   28  Fig  29   as well as operation in a local network  Fig  30  or via the Internet  Fig  31      You can work in an open network or in a network secured with WPA WPA2 PSK     43    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    With a direct connection  a Wi Fi access point  router  is the tablet  For this kind of operation   the analyzer and tablet are configured at the factory     The tablet may work with multiple analyzers  This requires adding them to the analyzer data   base  see chapter 2 12 4 and chapter 2 12 5             Fig  29  Direct connection  tablet    multiple analyzers     In configurations with external router an operation in open or WPA WPA2 PSK secured net   work is possible  When working in open networks the Key field in Analyzer database must be  empty  see also Fig  35      44    2 Operation of the analyzer       Fig  31  C
179. times shorter than 10 sec  are in fact equal to a multiple of the mains cycle   200 ms     10 12 cycles  1 s     50 60 cycles  3 s     150 180 cycles  5 s     250 300 cycles     2  Urmsci 2  and Irusc1 2  are RMS values for one cycle  refreshed every half cycle     3  Averaging periods min  max  200 ms  1s  3s  5s are in fact equal to a multiple of the mains cycle  200 ms      10 12 cycles  1 s     50 60 cycles  3 s     150 180 cycles  5 s     250 300 cycles    oe   Instanta   Mean Minimum Maximum  neous  value value value    Recorded parameters    RMS phase phase to phase voltage  depending on  the type of system  Urms   RMS phase to phase voltage  only 3 phase wye sys   tem with N and 2 phase system  Urms    Unbalance factors for negative and positive se   quence  symmetrical components  negative  positive   zero  voltage  Uo  U1  U2  Uo  U2    Unbalance factors for negative and positive se   quence  symmetrical components  negative  positive   zero  current  lo  h  l2  io  i2    Flicker severity Pst and Pit  Active power  consumed and supplied  P   P    Reactive power  consumed and supplied  Qn  Q1     Qs  QB    Apparent power S   Distortion power D   Apparent distortion power Sn  Power Factor PF   Displacement power factor cos    DPF   Tang factor       113    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Active energy  consumed and supplied  Ep   Ep  i a  Reactive energy  consumed and supplied  Ear  E           Apparent energy Es   Voltage total harmonic distort
180. tion    In real systems  determination of the dominant source is often sufficient  By grouping the har   monic components with plus signs  we receive a set of power values which are responsible for the  energy flow from the source to the receiver  which is the useful energy    On the other hand  the set of harmonics active power values with negative sings makes up  this part of energy which does not play any useful role and is  returned  back to the distribution  system    By adding all active harmonics power values we receive the receiver active power  Hence  we  can notice that there are at least two alternative active power measurement methods    The first method involves calculation of average active power instantaneous value  which is  calculated on the basis of successive voltage and current     M  1  P     gt  U  I   i 1    where Uj is a successive voltage sample     is a successive current sample and M is the number of  samples in the measuring window     The second method involves adding individual harmonics active power values which are ob   tained by the FFT decomposition     P  U  Ip COS   h  h    5 4 2 Harmonics reactive power    The harmonics reactive power values may be calculated in a similar manner as the active  power values     Qn   Unln sin Ph    Knowledge of reactive power harmonics is valuable information used in the development of  reactive parallel compensators of reactive power  Such compensators consist of LC branches  tuned to a specific frequency h
181. tive sequence  max     Current unbalance factor for nega  0 0     20 0  Basing on 10 12 cycle value  tive sequence  max   Short term flicker Pst  max  Basing on 10 minute value    Long term flicker Px  max   Active power P  min  max  Basing on 10 12 cycle value  figuration  for consumed and supplied power   Reactive power Q  min  max  Basing on 10 12 cycle value  figuration  for consumed and supplied power   tion power Sn  min  max  figuration    Power Factor PF  min  max  Basing on 10 12 cycle value    Displacement power factor cosg  0   1 Basing on 10 12 cycle value  DPF  min  max     Active energy Ep  max  Checked every 10 12 cycles  for consumed  Raia figuration and supplied energy   figuration and supplied energy   figuration  THD F  max   Total harmonic distortion of current 0   200  Basing on 10 12 cycle value  THOLE ra Dee dee    Voltage harmonic amplitudes  max  0    100  or absolute Basing on 10 12 cycle value   values Independent thresholds for all harmonics in  the range of 2   50    Current harmonic amplitudes  max  0   200  or absolute Basing on 10 12 cycle value   values Independent thresholds for all harmonics in   the range of 2   50   voltage TID F  max    current TID F  max    Voltage interharmonics amplitudes 0    100  or absolute Basing on 10 12 cycle value     max  values Independent thresholds for all interharmon   ics in the range of 0   50   Current interharmonics amplitudes 0    100  or absolute Basing on 10 12 cycle value     max  values Independent
182. tly  on electric poles  Two bands with buckles and two plastic fasteners are used for mounting the an   alyzer  The fasteners are screwed to the back wall of the housing  and bands should be passed  through the resulting gaps                                   Fig  3  Fasteners for bands  for mounting the analyzer on a pole     1 General Information    The ingress protection class of the analyzer is IP 65  and operating temperature ranges from   20  C to  55  C     Note  In order to ensure the declared ingress protection class IP 65  the  following rules must be observed     e Tightly insert the stoppers in the slots of USB and SIM card    e Unused clamp terminals must be sealed with silicone stoppers    e Tighten the plug of the socket used for external GPS antenna  or tightly  screw the external GPS antenna into the socket         At ambient temperatures below 0  C or when the internal temperature drops below this point   the internal heater of the device is switched on   its task is to keep the internal temperature above  zero  when ambient temperatures range from  20  C to 0  C    The heater is powered from the AC DC power adapter  and its power is limited to approx  10 W    Due to the characteristics of the built in lithium ion rechargeable battery  the process of charg   ing is blocked when the battery temperature is outside the range of 0  C   60  C  in such case   Sonel Analysis software indicates charging status as  charging suspended       1 5 Mounting on DIN rail   
183. to the receiver  Such clamp    orientation is required for a correct power measurement     Warning    maximum measured conductor diameter      lt 10 mA A    caused by the 400 A m  50 Hz  external magnetic field on the centered conductor     lt 1 3A   gt 65 dB A V  50   400 Hz     double  according to IEC 61010 1  II  600 V     IP 30   9 V battery  6LR61  6LF22  NEDA 1604   about 120 h   237 x 97 x44 mm   about 520 g    O39 mm   1 5m     10  C    55  C   lt 85  RH    lt  2000 m   IEC 61000 6 3 2008  IEC 61000 6 2 2008       Fig  60  C 6 clamp     Do not use the device on non insulated conductors with a potential of    more than 600 V in relation to the earth and a measurement category  greater than Ill        121    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Reference conditions   e Temperature    e Relative humidity    e Conductor position    e Sinusoidal current frequency   e Harmonics content    e Current DC component    e Continuous magnetic field    e Alternating magnetic field    e Conductors in direct vicinity     Technical specification  e Accuracy     20    26  C   20   75    conductor centered in jaws  48   65 Hz    lt 1    none   earth field   lt 40 A m    none   no flowing current     a    0 01   0 1A  lt 3   1 mA not specified    0 1   1A  1  12A       10 as   of measured value    ratio   frequency range   insulation type     protection rating acc  to IEC 60529   dimensions    weight    jaws opening    open jaws height     clamp lead length    operatin
184. tot calculated as for the split phase network  and supplied  Ep tot    Estot   5 SeT   i 1  where   i is subsequent number of the 10 12 period measure   Total apparent energy Estot Men AN  OW  Se i  represents the total apparent power Se calculated in  i th measuring window  T i  represents duration of i th measuring window  in  hours        74    5 Power quality   a guide  5 Power quality   a guide    5 1 Basic information    The measurement methodology is mostly imposed by the power quality standards  mainly IEC  61000 4 30  This standard  introducing precise measurement algorithms  ordered analyzers mar   ket  allowing customers to easily compare the devices and their results between the analyzers  from different manufacturers  Previously  these devices used different algorithms  and often the  results from measurements on the same object were completely different when tested with differ   ent devices    The factors behind growing interest in these issues have included wide use of electronic pow    er controllers  DC DC converters and switched mode power supplies  energy saving fluorescent  lamps  etc   that is widely understood electrical power conversion  All of these devices had a ten   dency to significantly deform the supply current waveform   The design of switched mode power supplies  widely used in household and industrial applica   tions  is often based on the principle that the mains alternating voltage is first rectified and  smoothed with the use of capacitors 
185. ts detection hys   teresis parameter     The analyzer remembers the event start and end time  with a half a period accuracy     The minimum voltage dip  interruption and swell duration is a half of the period    Urms1 2  Values are determined in 1 period during crossing through zero of the fundamental volt   age component   they are refreshed every half period  independently for each voltage channel  It  means that these values will be obtained at different times for different channels  Fig  50 shows  the method for determining RMS  values at two voltage phases  Information on crossing zero of  the fundamental component is obtained by FFT                 5 9 Transients and overvoltages    Transients are unwanted  rapid and short term disturbances in the mains  They are accompa   nied by a sudden change in voltage and current  The duration of a disturbance is typically from a  few nanoseconds to a few milliseconds  Often  terms used to describe them include  overvoltages   voltage peaks  surges  impulse waves  oscillations  But these terms narrow their meaning  Transi   ent is a disturbance in signal over the time  and as such  its meaning includes all of the above  terms  It may be classified in terms of duration and rise  amplitude  frequency spectrum  transmit   ted energy  source  etc  The most dangerous for electrical devices are transients that cause a sig   nificant voltage increase in the supply line  surges   Due to the source  the transients are often di   vided into
186. unt also the  presence of higher harmonics  For sinusoidal circuits  it is equal to Displacement Power Factor   DPF  i e  popular coso    DPF is therefore a measure of the phase shift between the fundamental voltage and current  components  Power Factor is the ratio between active and apparent powers     P  U lhcosgyin  S  UI  COSPuin    pr   S    In case of a purely resistive load  in a one phase system   the apparent power is equal to ac   tive power  in terms of value   and reactive power equals zero  so such load fully uses the energy  potential of the source and the power factor is 1  Appearance of reactive component inevitably  leads to reduction of energy transmission effectiveness     the active power is then less than ap   parent power  and the reactive power is increasing    In three phase systems  the power factor reduction is also influenced by receiver unbalance   see discussion on reactive power   In such systems  correct power factor value is obtained using  the effective apparent power Se  that is the value defined  among others  in IEEE 1459 2000  standard     5 4 Harmonics    Dividing periodic signal into harmonic components is a very popular mathematical operation  based on Fourier   s theorem which says that any periodic signal can be represented as a sum of  sinusoidal components with frequencies equal to multiples of fundamental frequency of such sig   nal  Time domain signal can be subjected to Fast Fourier Transform  FFT  to receive amplitudes  and pha
187. uous position information     2 10 3 Data flagging concept    The analyzer saves measurement records along with the flag indicating the lack of time syn   chronization  If for the whole averaging period the analyzer was synchronized to UTC  then the    flag is not turned on and during data analysis the icon indicating the lack of synchronization    is  not displayed  The absence of this icon indicates full compliance of gathered data with Class A in  terms of time marking  Synchronization with UTC is also indicated on the screen of the analyzer  by green date and time on the top bar    When the analyzer was initially synchronized to UTC  GPS status on the analyzer screen dis   played as YES  and later the signal was lost  No signal status   this does not mean that the ana   lyzer immediately lost the synchronization of its clock  In fact  for some time  even a few minutes  or more  internal timing accuracy is sufficient to meet the requirements of IEC 61000 4 30 in part  relating to the accuracy of determining time data  This is because the internal clock of the analyz   er is very slow in de synchronizing from UTC time  due to no GPS signal   and the error does not  exceed a few milliseconds for an extended period of time  Thus  despite the  No signal  status   data will continue to be saved without the flag signalling the lack of synchronization to UTC  Only  when the error exceeds the limit value the flag will be turned on     38    2 Operation of the analyzer    2 10 4 Ti
188. uring circuits for transients are independent from the  rest of voltage circuits and connected to voltage inputs L1  L2  L3  N  PE  The analyzers have four  measurement channels  L1 PE  PE L2  L8 PE and N PE  Recording time waveforms is done with  user defined pretrigger time and detection threshold  while the number of recorded samples is up  to 20000 per channel  2 ms for 10 MHz sampling      1 3 Power supply of the analyzer    The analyzer has a built in power adapter with nominal voltage range of 90   760 V AC or   127   760 V DC  The power adapter has independent lines  red  marked with letter P  power   To  prevent the power adapter from being damaged by undervoltage  it automatically switches off  when powered with input voltages below approx  80 V AC  110 V DC    To maintain power supply to the device during power outages  the internal rechargeable battery is  used  It is charged when the voltage is present at terminals of the AC adapter  The battery is able  to maintain power supply up to 2 h hours at temperatures of  20    55  C  After the battery is dis   charged the meter stops its current operations  e g  recording  and switches off in the emergency  mode  When the power supply from mains returns  the analyzer resumes interrupted recording     Note    The battery may be replaced only by the manufacturer s service de   partment        1 4 Tightness and outdoor operation    The analyzer is designed to work in difficult weather conditions   it can be installed direc
189. urrent  re  TIDIR  ferred to RMS    Voltage crest factor    TIDUp   x 100     50 y2  ih 0    ih  TIDUR              x 100     ARMS  where Un is the ih th interharmonic of voltage Us    50  2  th 0  th  TIDI         gt        x 100   1  where la is  h th interharmonic of current la    l   is fundamental component of current la    50  2  th 0  ih  TIDIz                x 100   ARMS  where l   is ih th interharmonic of current la    max  U     CFU          Uarms  where the operator max U   expresses the highest abso   lute value of voltage U  a n samples    i   2048 for 50 Hz and 60 Hz       V  A  Total Harmonic Distortion pple Fe  for current  referred to THDIe THDIp                x 100   RMS Tarms  where his the h th harmonic of current la  V  A    67    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    Current crest factor CFI where the operator max J   expresses the highest abso   lute value of current  4 samples  i   2048 for 50 Hz and 60 Hz  50 22  co KFactor   Ziz lh   K Factor   Ii   where hais the h th harmonic of current la  l   is fundamental component of current la    P    UnIn COS Mn  where Unis the h th harmonic of voltage Ua n  lais the h th harmonic of current la  ph is the angle between harmonics Uhn and lha  Qn   Unln sin Ph  where Uh is the h th harmonic of voltage Ua n  lais the h th harmonic of current la  ph is the angle between harmonics Up and lha    Harmonic active power  Harmonic reactive power    Short term flicker calculated according to IEC 6100
190. urrent waveform    The literature often uses the statement that  receiver generates harmonics   It should be re   membered that in such case  the receiver is not a physical source of energy  as suggested by the  word  generates    The only source of energy is the distribution system  If the receiver is a passive  device  the energy sent from the receiver to the distribution system comes from the same distribu   tion system  We are dealing here with a disadvantageous and useless bidirectional energy flow   As mentioned earlier in the section on power factor  such phenomenon leads to unnecessary en   ergy losses  and the current  generated  in the receiver causes an additional load on the distribu   tion system    Consider the following example  A typical non linear receiver  such as widely used switched   mode power supplies  i e  for computers  receives power from a perfect generator of sinusoidal  voltage  For now  let s assume that the impedance of connections between the generator and the  receiver is zero  The voltage measured on the receiver terminals will have sinusoidal waveform   absence of higher harmonics      this is imply the generator voltage  The receiver current wave   form will already include harmonic components     a non linear receiver often takes current only in  specified moments of the total sinusoid period  for example  maximum current can take place at  the voltage sinusoid peaks     However  the receiver does not generate these current harmonics  it s
191. us  1 2   AS this time is increasing  additional smoothing is being introduced  for example  with  5 seconds  first a 5 second average value is calculated which is then used to search for the mini   mum and maximum values  This gives a lower sensitivity to instantaneous changes of the meas   ured value     102    5 Power quality   a guide    Note  similarly to the averaging times shorter than 10 seconds  the 200 ms  1s  3s and 5s times  are actually the multiples of the mains period   10 12  50 60  150 180 and 250 300 mains cycles   respectively     Selecting the right averaging time is not easy  To a large extent it depends on the type of dis   turbance in the system and the user s expectations for the final data analysis  A frequent situation  is that we know only that there is a problem in the mains  and the measurements with the analyzer  will only help us identify the cause  In this situation it is better to use shorter averaging times  e g   10 seconds   and activate the recording of minimum and maximum values  for the voltages and  currents it is advisable in such situation to set the shortest possible time for determining the max   imum and minimum value  i e  half period   Short time averaging will give more precise diagrams  of changes of parameters over time  and minimums and maximums will be detected and record   ed  Recording with short averaging times is performed mostly during a limited time  primarily due  to rapid growth of data  the aim of such recording is 
192. using the built in GPS receiver with inter   nal or external antenna    e Built in real time clock  which is set from  Sonel Analysis     e RTC accuracy after GPS signal loss   better than  0 3 s day    Compliant with IEC 61000 4 30 Class A of the measurement method and un   Tieie ene  certainty  p Compliant with IEC 61000 4 30 Class A of the measurement method and un   ower supply voltage certainty  Voltage fluctuations  flicker  The measurement method and uncertainty meets the requirements of IEC  9 61000 4 15 standard   Dips  interruptions and surg    Compliant with IEC 61000 4 30 Class A of the measurement method and un   es of supply voltage certainty  S Compliant with IEC 61000 4 30 Class A of the measurement method and un   upply voltage unbalance certainty  Voltage and current harmon    Compliant with IEC 61000 4 30 Class A of the measurement method and un   ics certainty  IEC 61000 4 7 Class 1   Voltage and current inter  Compliant with IEC 61000 4 30 Class A of the measurement method and un   harmonics certainty  IEC 61000 4 7 Class 1     Mains signalling voltage on Compliant with IEC 61000 4 30 Class A of the measurement method and un   the supply voltage certainty    Aggregation of measure   ments at different intervals    Real time clock  RTC  un   certainty       14    2 Operation of the analyzer    2 Operation of the analyzer  2 1 Buttons    The keyboard of the analyzer consists of four buttons  ON OFF cop LEFT q   RIGHT      START STOP  smr J To switch on the 
193. vent detection    The analyzer offers wide range of event detection options for measured networks   Event  is a  situation where the parameter value exceeds the threshold defined by the user     Tab  6  Types of event thresholds for each parameter     Parameter Interruption   Dip   Swell   Minimum   Maximum _     RMS voltage  DC voltage  Frequency   Voltage crest factor  Voltage negative sequence unbal   ance  Flicker Pst  Flicker Pit   RMS current  DC current   Current crest factor    Current negative sequence unbal   ance    Active power  Reactive power  Apparent power  Distortion power   Power Factor   Displacement power factor  Tangento factor    E gt   E Active energy  consumed and sup   cus plied     Eset Reactive energy  consumed and  ae supplied     Apparent energy    THDF U voltage THDr    Se    THD    current THDe    Current harmonic amplitudes  Iho  Ih50  n   2   50   TIDF U voltage TIDr       PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    init  a    TIDF   current TIDF    Current interharmonics amplitudes  liho   lih50  n   0 50     UR   UR2 Mains signalling  POM 703  POM 711 Voltage transients      ine  pK TK Factor      fini            applies to Un pe voltage    with C 5 clamps only    Detected events are recorded on a memory card as an entry containing   parameter type    channel  in which the event occurred    start and end time of the event    the threshold value set by the user    parameter extreme value measured during the event    parameter averag
194. without neutral conductor  Fig  19  Fig  22     3 phase delta  Fig  20  Fig  21      Indirect measurements in medium voltage networks can be performed   e in wye network  Fig  23    e in delta network  Fig  24      In three wire systems  current may be measured by the Aron method  which uses only two  clamps that measure linear currents l   and lis  lL2 current is then calculated using the following  formula     l2   Ih     Ths    This method can be used in delta systems  Fig  21  and wye systems without a neutral con   ductor  Fig  22      Note  As the voltage measuring channels in the analyzer are referenced to N  input  then in systems where the neutral is not present  it is necessary to    connect N input to L3 network terminal  In such systems  it is not required  to connect L3 input of the analyzer to the tested network  It is shown in  Fig  19  Fig  20  Fig  21 and Fig  22  three wire systems of wye and delta    type         In systems with neutral conductor  the user may additionally activate current measurement in  this conductor  after installing additional clamps in In channel  This measurement is performed af   ter activating in settings the option of N conductor current with option Measured    An alternative to In current measurement with clamps is the calculation of current in neutral con   ductor applying the analytical method  The analyzer provides such option after selecting N   conductor current and Calculated  Neutral current is calculated from the followin
195. xample  In order to calculate the 3rd harmonic component in 50 Hz system  use    150 Hz main spectral line and adjacent lines 145 Hz and 155 Hz  The re   sulting amplitude is calculated using RMS method        3 8 The method for measuring interharmonics    Interharmonics measurement is carried out according to IEC 61000 4 7 and IEC 61000 4 30   They provide a method of calculating the individual components of interharmonics in power  quality analyzers   The whole process  similarly as in case of harmonics  consists of several steps   e synchronous sampling  10 12 periods    e FFT  Fast Fourier Transform    e grouping     FFT analysis for the test window of 10 12 period  approx  200 ms   As a result  we obtain a  set of spectral lines from 0 Hz  DC   The distance between successive lines results from the dura   tion of the measurement window and is approximately 5 Hz     59    PQM 702  PQM 703  PQM 710  PQM 711 Operating Manual    interharmonic interharmonic    interharmonic    subgroup subgroup subgroup  order 0 order 1 order 2  FFT  output  0 50 100 150 frequency  Hz   0 1 2 3 harmonic order    Fig  42  Determining interharmonics subgroups  50 Hz system     Each interharmonic subgroup is the sum of RMS for seven  for 50 Hz mains  or nine  for  60 Hz mains  spectral lines obtained by Fourier transform  The exception is zero subgroup  i e   sub harmonic subgroup that contains one line more   5Hz  It is presented in Fig  42 with an exam   ple of 50 Hz network  Interharmonic sub
196. y in all eight channels with a frequency synchronized with  the frequency of power supply voltage in the reference channel  This frequency is 10 24 kHz for  50 Hz and 60 Hz    Thus  the single period contains 204 8 samples for 50 Hz and 170 67 for 60 Hz  16 bit analog to   digital converter was used to ensure 64 times oversampling    3 decibel analog attenuation has been specified for frequency approx  20 kHz  and the ampli   tude error for the maximum usable frequency 3 kHz  i e  the frequency of the 50th harmonic for  60 Hz network  is approximately 0 1 dB  The phase shift for the same frequency is less than 15     Attenuation in the stop band is above 75 dB    It should be noted that for the correct measurement of phase shift between the voltage har   monics in relation to current harmonics and power of these harmonics  the important factor is not  absolute phase shift in relation to the basic frequency  but the phase coincidence of voltage and  current circuits  Maximum phase difference error is f   3 kHz  max  15    This error decreases with  the decreasing frequency  When estimating measurement errors in power harmonics  also take in   to account additional error introduced by the clamps and transformers     3 5 PLL synchronization    The synchronization of sampling frequency is implemented by hardware  After passing  through the input circuits  the voltage signal is sent to a band pass filter which is to reduce the  harmonics level and pass only the voltage fundamental
197. y to measure the current DC component  For this purpose the  user must apply clamps with a principle of operation different than a traditional current transform   er  Such clamps operate basing on  Hall effect  and include a built in Hall sensor  called also    hal   lotron      In brief  the effect is based on the occurrence of an electrical voltage on the walls of the  conductor  through which an electric current flows and which is in magnetic field of direction trans   verse to the induction vector of this field    Current clamps based on this phenomenon may measure both DC and AC current compo   nents  The conductor with current located inside the clamps generates a magnetic field which  concentrates in its iron core  In the core slot  where the two parts of clamps meet  a semiconduc   tor Hall sensor is located  and its output voltage is amplified by battery powered electronic circuit    Clamps of this type usually have a current zero adjustment knob  To adjust the current zero   close the jaws  no conductor inside  and turn the knob until DC indication is zero    Sonel S A  offers this type of clamps  C 5 with a nominal range of 1000 A AC   1400 A DC   Clamps of this type have a voltage output and for nominal current of 1000 A the provide voltage of  1 V  1 mV A      5 1 3 Flexible clamps    Flexible clamps  Flexible Current Probes  operate on  a different physical principle than the current transformer   Their most important part is Rogowski coil  named after  Walter R
198. zer uses a solution of digital integration of signal provided directly from the  Rogowski coil  This approach allowed us to eliminate problems related to analog integrators and  the need to ensure declared accuracy for long periods and in difficult measurement environment   Analog integrators must also include protection systems to prevent output saturation when con   stant voltage is present at the input    The ideal integrator has infinite gain for DC signals which descends at a rate of 20  56    3 Design and measurement methods    dB frequency decade  The phase shift is constant over the entire frequency range and is equal to  90      Theoretically infinite gain for DC signal  when present at integrator input  causes the input  saturation close to the supply voltage and prevents its further work  In practical systems  a solu   tion is introduced to limit the gain for DC signals to some fixed value  Additionally  periodic reset of  the output is performed  There are also techniques for active cancellation of DC voltage  based on  its measuring and feeding it back to the input  but with the opposite sign  effectively cancelling it   In such case professionals use term  leaky integrator     Analog  leaky integrator    is simply an inte   grator with shunted capacitor  by resistor with high resistance   Such a system operates in the  same manner as a low pass filter with a very low cut off frequency    Digital implementation of the integrator ensures excellent long term parame
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Lubrication Equipment Buyer`s Guide  Béziers 2  novedad - Cristian Lay  Los perpetradores del Holocausto en perspectiva  Allumisol - EDILCHIMICA  Aloha QuickService User`s Guide  Eignungsprüfbericht für Gaskomponenten  User Manual of Airwheel Electric Unicycle  Whirlpool W5CE3625AB Use and Care Manual  取扱説明書    Copyright © All rights reserved. 
   Failed to retrieve file