Installation Manual - Pritchard Mechanical
Contents
1. Products to avoid Spray cans containing chloro fluorocarbons Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine type bleaches detergents and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products Excessive dust and dirt Areas likely to have contaminants Dry cleaning laundry areas and establishments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual Perform maintenance per schedule below Figure 2 Service and maintenance schedules Owner maintenance see following pages for instructions Service technician see Boiler Manual for instructions Check boiler area Check air openings Check pressure gauge Check boiler interior piping Check venting system Monthly Check air vents Check condensate drain system Check relief valve Follow the procedures listed in the Boiler Manual Test low water cutoff i
2. www weil mclain com
3. DO NOT install combustion air intake where there is a risk of combustion air contamination Carbon monoxide detector e Por Direct Exhaust units a carbon monoxide detector is required in the boiler room The carbon monoxide detector must be wired on the same electrical circuit as the boiler e Por Direct Vent units a carbon monoxide detector that is wired on the same electrical circuit as the boiler is strongly recommended Boiler water Do not use petroleum based cleaning or sealing compoundsin boiler system Gaskets and seals in the system may be damaged This can result in substantial property damage e Leaks in boiler or piping must be repaired at once to prevent make up water Use this boiler ONLY in a closed loop system Continual fresh make up water will reduce boiler life Mineral build up in heat exchangers reduces heat transfer overheats the materials and causes failure Addition of oxygen carried in by make up water can cause internal corrosion e Do not add cold water to hot boiler Thermal shock can cause heat exchanger to crack Freeze protection fluids NEVER use automotive or standard glycol antifreeze Use only freeze protection fluids made for hydronic systems Follow all guidelines given a the antifreeze manufacturer Toronta clean and flush any replacement boiler system that has used glycol before installing the new boiler GV90 GAS FIRED WATER BOILER User s Information Manual Pre
4. If they have been there for an ex tended period call a qualified service technician to inspect the boiler and vent system for possible damage from acid corrosion If products cannot be removed immediately call a qualified service technician to install an outside combustion air source for the boiler if not already installed Combustible flammable materials Do not store combustible materials gasoline or any other flammable vapors or liquids near the boiler Remove immediately if found Air contaminants Products containing chlorine or fluorine if allowed to contaminate the boiler intake air will cause acidic condensate in the vent and boiler This will cause significant damage to the vent and or boiler if allowed to continue Read the list of potential materials listed on page 4 of this manual If any of these products are in the room from which the boiler takes its combustion air they must be removed immediately or the boiler combustion air must be supplied from outside See WARNING above Check air openings 1 Verify that combustion and ventilation air openings to the boiler room and or building are open and unobstructed Verify that boiler vent discharge and air intake are clean and free of obstructions Remove any debris on the air intake or flue exhaust openings Check boiler pressure temperature gauge L Make sure the pressure reading on the boiler pressure temperature gauge does not exceed 24 psig Higher pressur
5. tank sized too small Flooded expansion tank Inoperative limit control Leaks in boiler or piping Oxygen corrosion due to leaks in boiler and piping Locate thermostat on inner wall away from heat sources or cool drafts Adjust thermostat per manufacturer s instructions Set limit according to system needs Maximum setting is 200 F Increase limit setting to decrease cycling Check all valves to and from boiler Return to proper setting Confirm circulator size Call qualified service technician to check expansion tank operation and size Call qualified service technician to check expansion tank operation Call qualified service technician to replace limit control Have qualified service technician repair leaks at once to avoid constant use of makeup water Makeup water can cause mineral deposits which in turn can cause boiler section failure Do not use petroleum base stop leak compounds Have qualified service technician repair at once Keep pH of water between 7 0 to 8 5 13 GV90 GAS FIRED WATER BOILER User s Information Manual Common problems and solutions continea Mineral deposits in sections due to constant use of makeup water Popping or percolating noise heard in boiler Incorrect pH of boiler water Insufficient water flow through boiler Contaminated combustion air supply See page 4 in this manual Metal flakes found in vent outlet or vent starter tee fl
6. the circulator is controlled by the IBC depending on the temperature of the water entering the boiler sections Pump must remain on boiler do not remove Bypass circulator The IBC operates the bypass circulator to mix hot water from the boiler outlet with colder return water from the system as needed to prevent condensation of flue gases in the cast iron heat exchanger When the water returning to the boiler is below 140 F the IBC regulates the bypass circulator and system circulator flow rates to raise the return water temperature up to 140 F before it enters the cast iron sections By balancing these flow rates the IBC can protect against condensation even if return water is as low as 60 F Pump must remain on boiler do not remove Air pressure switch The air pressure switch signals the IBC telling the control whether air is moving through the blower Water temperature sensor The water temperature sensor monitors the temperature of the water entering the boiler sections The sensor sends this information to the IBC The IBC determines how much to adjust the circulator flow rates to provide at least 140 F water to the cast iron heat exchanger LEGEND a Supply to system 1 NPT b Return from system 1 NPT C Combustion air inlet fitting 3 PVC connection d Flue outlet 3 PVC connection e Gas valve negative pressure regulated gas control f Pressure temperature gauge g Flueway inspectio
7. there is a risk of flue gas flow into the building The boiler must not be operated and must be inspected and serviced only by a qualified service technician Failure to comply with this directive could result in the possibility of severe personal injury death or substantial property damage Check boiler relief valve 1 Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage 2 Ifthe relief valve often weeps the expansion tank may not be working properly Immediately contact your qualified service technician to inspect the boiler and system Test low water cutoff if installed PERIODIC N Maintenance If the system is equipped with a low water cutoff test the low water cutoff periodically during the heating season following the low water cutoff manufacturer s instructions Clean vent termination amp air intake screens 1 Remove all lint and debris from both the boiler air intake screen and the flue discharge screen 2 The boiler control module will sense blockage of the air intake or flue and lockout if the blockage is excessive It will signal the failure by flashing the appropriate indicator lights on the control board 3 If removing the debris does not allow the boiler to operate correctly afterwards contact your qualifed service technician to inspect the boiler and vent air systems 8 Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Informa
8. M WEIL McLAIN User s Information Manual Gas Fired Water Boilers ENERGY STAR If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liguids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS e Do not try to light any appliance e Do not touch any electrical switch do not use any telephone in your building e Immediately call your gas supplier from a neighbor s telephone Follow the gas supplier s instructions e f you cannot reach your gas supplier call the fire department Installation amp service must be performed by a qualified installer service technician or the gas supplier Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual Please read this page first How to use this manual To Learn precautions Prevent air contamination Maintain boiler Locate boiler components Start or Shutdown boiler Troubleshoot common problems Warnings and definitions Laundry room or pool make sure boiler air is piped to boiler per manual Read list of air contaminants you must avoid Have boiler air piped in if you can t avoid Set up a plan for maintaining the boiler using the schedule included in this manual Schedule an annual start up by a qual
9. alve to seat Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain If the valve weeps lift the seat again to attempt to clean the valve seat If the valve continues to weep afterwards contact your qualified service technician to inspect the valve and system 5 If water does not flow from the valve when you lift the lever completely the valve or discharge line may be blocked Immediately shutdown the boiler following the lighting instructions on the inside jacket top Call your qualified service technician to inspect the boiler and system Follow boiler shutdown procedure 1 Follow TO TURN OFF GAS TO APPLIANCE on the Operating instruction on the inside of the jacket top panel You will also find these instructions on page 12 of this manual 2 Do not drain system unless exposure to freezing temperatures will occur 3 Do not drain the system if it is filled with an antifreeze solution 4 Donotshut down boilers used for domestic water heating They must operate year round GV90 GAS FIRED WATER BOILER User s Information Manual How it works 10 Integrated boiler control The integrated boiler control IBC responds to signals from the room thermostat air pressure switch inlet water sensor and boiler limit circuit to operate the circulators gas valve igniter and blower When a room thermostat calls for heat the IBC starts the system circula
10. damage Part number 550 142 055 0411 AWARNING Failure to adhere to the guidelines on this page can result in severe personal injury death or substantial property damage Boiler service and maintenance e To avoid electric shock disconnect electrical supply before performing maintenance To avoid severe burns allow boiler to cool before performing maintenance e You must maintain the boiler as outlined in the manual and have the boiler started up and serviced at least annually by a qualified service technician to ensure boiler system reliability Boiler operation Do not block flow of combustion or ventilation air to boiler This boiler is equipped with a control which will automatically shut down the boiler should air or vent be blocked If vent or air blockage is easily accessible and removable remove it The boiler should attempt to restart within an hour If blockage is not obvious or cannot be removed have the boiler and system checked by a qualified service technician e Should overheating occur or gas supply fail to shut off DO NOT turn off or disconnect electrical supply to circulator Instead shut off the gas supply at a location external to the appliance Do not use this boiler if any part has been under water Imme diately call a gualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water Combustion air e
11. e may indicate a problem with the expansion tank 2 Contact a qualified service technician if problem persists Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual User maintenance procedures continues MONTHLY Maintenance Part number 550 142 055 0411 Figure 3 Automatic air vent Check boiler interior piping 1 Remove boiler jacket top 2 Visually inspect for leaks around internal piping circulators relief valve and other fittings Immediately call a qualified service technician to repair any leaks AWARNING Have leaks fixed at once by a qualifed service technician Continual fresh makeup water will reduce boiler life Minerals can build up in sections reducing heat transfer overheating cast iron and causing section failure AWARNING Do not use petroleum based cleaning or sealing compounds in boiler system Severe damage to boiler and system components can occur resulting in possible severe personal injury death or substantial property damage Check venting system 1 Visuallyinspect the flue gas vent piping for any signs of blockage leakage or deterioration of the piping Notify your qualified service technician at once if you find any problem AWARNING Failure to inspect the vent system as noted above and have them repaired by a qualifed service technician can result in vent system failure causing severe per sonal injury or death Check automatic air vent
12. f used Periodically Clean vent termination air intake screens Q T T O ahead 09 gt lt Oil blower motor Every 6 months Operate relief valve End of season Shut down procedure Part number 550 142 055 0411 5 GV90 GAS FIRED WATER BOILER User s Information Manual User maintenance procedures Boiler must be serviced and maintained DAILY Maintenance AWARNING The boiler should be inspected and started annually at the beginning of the heat ing season only by a qualified service technician In addition the maintenance and care of the boiler designated on page 5 and explained on the following pages must be performed to assure maximum boiler efficiency and reliability Failure to service and maintain the boiler and system could result in equipment failure causing possible severe personal injury death or substantial property damage ACAUTION The following information provides detailed instructions for completing the maintenance items listed in the maintenance schedule page 5 In addition to this maintenance the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician Check boiler area AWARNING Io prevent potential of severe personal injury death or substantial property damage eliminate all materials discussed below from the boiler vicinity If con taminants are found Remove products immediately from the area
13. ified service technician before every heating season How the boiler works and illustration Follow the Lighting instruction sheet details to start or shutdown your boiler Use the common problems solutions table to resolve typical heating system boiler problems Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual STOP Read before proceeding User Have this boiler serviced inspected by a qualified service tech nician at least annually Failure to comply with the above could result in severe personal injury death or substantial property dam age When calling or writing about the boiler Please have the boiler model number from the boiler rat ing label and the CP number from the boiler jacket Hazard definitions The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product Indicates presence of hazards that will cause severe personal injury death or substantial property dam age Indicates presence of hazards that can cause severe personal injury death or substantial property dam age Indicates presence of hazards that will or can cause minor personal injury or property damage Indicates special instructions on in stallation operation or maintenance that are important but not related to personal injury or property
14. n port cover h Sensor hose trap i Manual air vent j Relief valve k Thermal fuse a one time fuse device that shuts boiler off if flue temperature exceeds its setpoint m Condensate trap line shipped loose with boiler field installed n Condensate drain connection 14 PVC female This boiler uses a negative pressure regulated gas valve set for an outlet pressure approximately 0 20 water column DO NOT set the outlet pressure higher than factory setting Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual GV90 Water Boiler Part number 550 142 055 0411 1 GV90 GAS FIRED WATER BOILER User s Information Manual Operating instructions AWARNING Before attempting to start the boiler check the boiler pressure temperature gauge If boiler and system are full of water and properly pressurized the gauge should read at least 12 psig on most systems Operating the boiler without proper water content will damage boiler and controls and could result in severe personal injury death or substantial property damage Figure 5 Operating instructions NNN FOR YOUR SAFETY READ BEFORE OPERATING NN A This appliance does not have a pilot It is C Use only your hand to rotate the handle on the gas cock Never equipped with an ignition device which use tools If the valve handle will not move by hand don t try automatically lights the burner Do not tr
15. nformation above If you don t smell gas go to the next step 8 Rotate gas cock handle counterclockwise v to open gas line handle lined up with gas line as in the drawing at right 9 Turn on all electric power to the appliance 10 Set thermostat to desired setting 11 If the appliance will not operate follow the instructions TO TURN OFF GAS TO APPLIANCE below and call your service technician or gas supplier 12 Replace jacket top panel Set the thermostat to lowest setting Turn off all electric power to the appliance if service is to be performed MA TO TURN OFF GAS TO THE APPLIANCE IIN 85020 1B Rotate gas cock counterclockwise to open When open rotate clockwise to close See below Rotate gas cock handle clockwise until handle is perpendicular to gas line see drawing above right to close valve 1 2 3 Remove jacket top panel 4 5 Replace jacket top panel 12 Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual Common problems and solutions Thermostat installed where drafts or heat affect reading Rapid cycling boiler turns on and off frequently Frequent release of water through relief valve Need to frequently add makeup water Black water condition Part number 550 142 055 0411 Heat anticipator in thermostat adjusted incorrectly Incorrect limit setting Insufficient water flow through boiler Expansion
16. s if used use automatic air vents with diaghragm type expansion tanks only l See Figure 2 2 Remove the cap from any automatic air vent in the system and check operation by depress ing valve B slightly with the tip of a screwdriver 3 Ifthe air vent valve appears to be working freely and not leaking replace cap A twisting all the way on 4 Loosen cap A one turn to allow vent to operate 5 Have vent replaced if it does not operate correctly GV90 GAS FIRED WATER BOILER User s Information Manual User maintenance procedures continued Check condensate system MONTH LY 1 NOTICE To improve clarity this illustration of the condensate trap is Maintenance shown with no air inlet pipe attached If your boiler has an air pipe connected here DO NOT tamper with it The trap is also shown as item m on page 11 2 Inspect the condensate P trap item 1 in the illustration at right The trap is translucent You should be able to see water in the trap as shown 3 If the trap does not contain water turn off the boiler ON OFF switch and call your boiler service technician imme diately 4 Item2intheillustration is the tubing or pipe from the boiler condensate outlet to the condensate drain or condensate pump Inspect this tubing or piping making sure it is in good condition and not obstructed AWARNING If the condensate trap is dry or the condensate line is damaged or obstructed
17. tion Manual User maintenance procedures continue EVERY 6 MONTHS Maintenance END OF SEASON Maintenance Part number 550 142 055 0411 Oil blower motor Figure 4 Blower motor 1 Remove the jacket top panel to access the blower motor 2 Use only Anderol 465 DO NOT use household universal oils AWARNING Use only Anderol 465 to lubricate the bl ower motor Do not use common uni versal household oils 3 See Figure 4 4 Place afew drops of oil in each of the two oiler cups on the side of the blower motor Oil cup JN 85037 Operate boiler relief valve 1 Before proceeding verify that the relief valve outlet has been piped to a safe place of dis charge avoiding any possibility of scalding from hot water AWARNING To avoid water damage or scalding due to valve operation a metal discharge line must be connected to relief valve outlet and run to a safe place of disposal This discharge line must be installed by a gualifed heating installer or service techni cian in accordance with the instructions in the GV90 Boiler Manual The discharge line must be terminated so as to eliminate possibility of severe burns should the valve discharge 2 Read the boiler pressure temperature gauge to make sure the system is pressurized 3 Lift the relief valve top lever slightly allowing water to relieve through the valve and dis charge piping 4 If water flows freely release the lever and allow the v
18. tor and blower The IBC runs the blower to purge the boiler flue passages then turns on the igniter and lets it warm up After igniter warm up the IBC opens the gas valve turns the igniter off and checks for flame The flame must come on within 4 seconds or the IBC will shut down and try the full cycle again When the room thermostat is satisfied the IBC turns off the boiler components and waits for the next heat call The IBC indicator lights show normal sequence when the lights are on steady When a problem occurs the IBC flashes combinations of lights which indicate the most likely reason for the problem Transformer The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit Blower The blower pulls in air and mixes it with gas from the gas valve The blower forces this mixture into the burner for combustion inside the boiler chamber Recuperator The recuperator is a stainless steel heat exchanger that increases boiler efficiency by ex tracting additional heat from the flue gases Return water passes through the recuperator before entering the boiler Water temperature limit switch The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting The circulators will continue to run as long as there is a call for heat System circulator The system circulator circulates water through the external system piping The flow rate of
19. ueway corrosion Condensation of combustion gases in boiler sections Some radiators or baseboard units do not heat or are noisy Air in system Low system pressure High limit set too low 14 Call gualified service technician to de lime boiler if necessary In some cases deposits will be too heavy to remove with de liming procedures Have gualified service technician repair leaks to eliminate need for constant makeup water Call gualified service technician to check pH level and correct pH should be maintained between 7 0 to 8 5 Check all valves to and from boiler Return to proper setting Confirm circulator size Remove any contaminating products See page 4 in this manual Provide outside air for combustion Have gualified service technician pipe up kit Have qualified service technician check operation of mixing system Repair replace if necessary Bleed air from system through air vents in radiators or baseboard units Fill to correct pressure Check for leaks in boiler or piping Have qualified service technician repair at once Adjust high limit to higher setting Part number 550 142 055 0411 GV90 GAS FIRED WATER BOILER User s Information Manual lt O m O vI Part number 550 142 055 0411 1 GV90 GAS FIRED WATER BOILER User s Information Manual Weil McLain U E L N L AIN 500 Blaine Street Michigan City IN 46360 2388 http
20. vent combustion air contamination Air contamination Common household and hobby products often contain fluorine or chlorine compounds When these chemicals pass through the boiler they can form strong acids in the vent system or boiler The acid can eat through the vent or boiler wall causing serious damage and presenting a possible threat of flue gas spillage into the building Please read the information below If the contaminating chemicals will be present have your installer pipe the boiler air from outside per the Boiler manual AWARNING If the boiler is installed in any area likely to cause contamination or if products which would contaminate the air cannot be removed you must pipe combustion air to the boiler air in take Contaminated combustion air will damage the boiler and vent system re sulting in possible severe personal injury death or substantial property damage Do not operate a GV90 boiler in a laundry room or pool facility for example without using ducted outside air These areas will always contain con taminants Figure 1 Combustion air contamination AWARNING Ensure that the combustion air will not contain any of the contaminants in Figure 1 Combustion air supply openings or intake terminations must NOT be near a swimming pool for example Avoid areas subject to exhaust fumes from laundry facilities These areas will always contain contaminants Corrosive contaminants and sources
21. y to to repair it call a qualified service technician Force or attempted light the burner by hand repair may result in a fire or explosion B Before OPERATING smell all around the D Do not use this appliance if any part has been under water appliance area for gas Be sure to smell next to Immediately call a qualified service technician to inspect the the floor because some gas is heavier than air appliance and to replace any part of the control system and any and will settle on the floor See below gas control which has been under water WHAT TO DO IF YOU SMELL GAS e Do not try to light any appliance Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions Do not touch any electric switch do not use any phone in your building If you cannot reach your gas supplier call the fire department OPERATING INSTRUCTIONS IIN STOP Read the safety information above on this label Set the thermostat to lowest setting Turn off all electrical power to the appliance Remove jacket top panel a oS i This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 6 Rotate gas cock handle clockwise to close gas line handle perpendicular to gas line see drawing at right 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety i