1.   This button does not alter any other  settings     Using the Serial Connectors    e Make sure the PDU and your computer are connected to the same subnet on the same  network    e Connect a serial cable between one of the PDU s configured serial connectors and an  external device s serial port  The used Baudrates on both devices should be the same   e Start a Telnet session at the PDU s IP and with the correct port    e You will be asked for login credentials  the default values are     Login  admin  Password  1234    e You are now connected  please refer to the external device s documentation for more  information on the serial connection options        2011 Racktivity Inc  18 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Use Case    Requirements    e  A fully configured PDU with an active ethernet connection   e APC with Putty software  download it here  and an active ethernet connection  e Device with a console port  ie  a Cisco switch    e Afemale DB9 to console cable    How to    e Install Putty  e Connect the cable between the PDU s 1st RS232 port and the device s console port  e Make sure the PDU and PC are on the same subnet and are switched on  e Open Putty and enter the following   o Connection Type  Telnet  o Host name  the PDU s IP address  ie  192 168 14 250   o Port  the default port for RS232 connector 1 is 2001  can be changed at the Web Portal s  Serial page   e Press  Open   e You will be asked for login 
2.  Redwood City 94063  USA     www  racktivity com v 2013 11 18    The following settings are only available when the DHCP checkbox is unchecked     Ethernet  Warning  when changing these values connection to the Web Portal might be lost   e IP Address  The IP address used for TCP IP configuration  e Subnetmask  The subnet mask used for TCP IP configuration  e Std Gateway  The standard gateway used for TCP IP configuration    DNS server  The DNS server used for TCP IP configuration    DHCP  When checked the PDU will automatically be assigned an IP address  if a DHCP  server is present on the network     e Community read  Sets the community read string  default   public   When using SNMP  software on a pc to collect SNMP data  GET command  this string is used as verification   e Community write  Sets the community write string  default   private   When using SNMP  software on a pc to change SNMP data  SET command  this string is used as verification   e Write protection  When checked this setting will prevent changes being made through  SNMP  SET command   even when using the correct Community write string  It can be  used as an additional protection   e Trap receiver port  Sets the port for the SNMP Trap function  default   162    e Trap receiver IP  Sets the IP address where the SNMP Trap is sent  this is normally the IP  of a monitoring computer on the same network    e Min  before Off  Sets the OLED standby delay when no buttons are pressed  in minutes   e Brightness  2 10  
3.  Sets the OLED s brightness    e Login  Sets a new login and password  The default values are     Login  admin  Password  1234    Logging  e Sets the logging values for the Logging tab  o Short term  From 1   255 seconds  o Medium term  From 1   255 minutes  o Long term  From 2   255 medium term intervals  specified in the above setting     After editing the settings on the Settings tab  press the Save Data button  A pop up will appear  after the changes have been successfully saved     Time Settings  UTC   The following settings are only available when NTP is unchecked    e Time  HM   Sets the time  in hours minutes    e Date  DMY   Sets the date  in days months years    e Local NTP server  NTP server IP when Use Default NTP Server is not checked   e Use Default NTP server  When checked the PDU will connect to pool ntp org for the time  settings   e NTP  When checked the PDU will try to get time settings from an NTP server    O 2011 Racktivity Inc  14 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www racktivity com v 2013 11 18    Protection tab    Use this tab to set the thresholds and alarms that provide disaster prevention and other recovery  functions for each port     Port  Port name and status  Grey background  Port is powered OFF  Green background  Port is powered ON    Current  Real time current in milliampere   Maximum  Maximum current in milliamp  re since the last reset   Reset  Resets the Maximum value  Hover your mouse over this value to see a t
4.  UP and DOWN to select Current IP Address  The current IP address is shown in yellow at  the bottom of the OLED    Firmware Update    To obtain the necessary software to update your PDU s firmware  please contact Racktivity  Support     O O a    Make sure that your computer and the PDU are on the same network and fully functional  Unpack the update package   Open the software tool  Racktivity Ethernet Bootloader exe    Use the  File  button to select the  cry file that came with the update package   Fill in the appropriate IP address and login credentials of the designated PDU   Press  Update firmware  to start the update   The update has successfully completed when  Programming completed   Exit bootloader  is  shown  the update takes a few minutes     Latest version    The latest available firmware version for the PM0816 01 is v1 01        2011 Racktivity Inc  23 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Troubleshooting    After starting the update  FAILED  check Settings   is shown     Please make sure that    e The PDU is powered on and connected to LAN with a correct IP address   e You entered the correct login credentials under  Settings  in the software tool  e You are on the same LAN as the PDU    To verify the above settings are correct  go to the Web Portal and log in     The Status window continuously shows output similar to      ERROR Out of Sequence PDU Seq  5294 5299      e This is a mere warning and does n
5.  Use the UP and DOWN buttons to change the screen brightness   Press MENU to save and exit     Fa PUR    Reporting Screens    Overview  1 7     The Overview screen shows the total current in A  Amp  re   the real power usage in Watts  the  temperature in degrees Celsius and the humidity in RH  Relative Humidity   These values are  updated in real time     General  2 7     This screen shows the current  in Amp  re  for all 8 ports  A combined total is displayed on the  right  Tot Current   followed by the input voltage  in Volts  and frequency  in Hz   All values are  updated in real time  Ports shown in green are powered on  when shown in grey they are  powered off        2011 Racktivity Inc  8 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Port State  3 7     Here you can see the current  in Ampere  for all 8 ports  followed by the port name  The port  name is typically the name of the connected device and can be set via the Web Portal  Ports  shown in green are powered on  when shown in grey they are powered off     Changing the port state    Press OK   Use the UP and DOWN buttons to select the desired port   Press OK at the selected port  validate by pressing MENU  Press MENU again to exit port selection     PAN A    Power  4 7     This screen shows the Real Power  Apparent Power and Power Factor  PF  values for each of the  ports  Ports shown in green are powered on  when shown in grey they are powered off     When the c
6.  and   back on  Toggling a port s state manually ignores this setting      Voltage table    Value  Current voltage measured   Warning Min  When the measured voltage goes below this threshold an SNMP trap is  sent  with SNMP checked    Warning Max  When the measured voltage exceeds this threshold an SNMP trap is sent   with SNMP checked    SNMP  When checked  SNMP traps are sent when the measured voltage is below the  minimum or above the maximum threshold    After editing the settings on the Protection tab  press the Save Data button  A pop up will appear  after the changes have been successfully saved        2011 Racktivity Inc  15 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Serial tab    The settings for the PDU s 4 serial connectors can be changed on this tab     e Port  The number of the serial connector as seen on the front of the PDU   e Baudrate  Possible baudrates for serial communication  The baudrate of the serial  connector and a connected device must be the same   e TelnetPort  Sets the telnet port  The port must end in the same number as the  corresponding serial connector  serial connector 3 cannot have a port ending with 4  ie   30004   it must end with a 3  ie  14203    e Reset Telnet  Disconnects an active telnet session  This button does not alter any other  settings     After editing the settings on the Serial tab  press the Save Data button  A pop up will appear after  the changes have been successfull
7.  the shipment date of each Product unit to Buyer    Warranty Period    For purposes of this Agreement the term  defect  shall mean the Product  fails to operate or fails to conform to its applicable specifications  Any claim made pursuant to  this Agreement shall be asserted or made in writing only by Buyer  Buyer shall comply with  Racktivity s Standard Return Merchandise Authorization   RMA   procedure for all warranty  claims as set forth in Racktivity s operation manual  Buyer must return Products in original  packaging and in good condition  This limited warranty does not include labor  transportation  or  other expenses to repair or reinstall warranted Products on site or at Buyer s premises  The  warranty only applies to the original Buyer     Racktivity reserves the right to investigate any warranty claims to promptly resolve the problem  or to determine whether such claims are proper  In the event that after repeated efforts  Racktivity is unable to repair or replace a defective Product  then Buyer s exclusive remedy and  Racktivity s entire liability in contract  tort  or otherwise shall be the payment by Racktivity of  Buyer s actual damages after mitigation  but shall not exceed the purchase price actually paid by  Buyer for the defective Product     Racktivity shall have no responsibility or liability for any Product  or part thereof  that  a  has had  the Serial Number  Model Number  or other identification markings altered  removed or  rendered illegible   b  h
8. U until the Main menu appears  select Ethernet or Network using UP and DOWN  and press OK    2  Within the Ethernet or Network menu  select DHCP  off  and press OK until DHCP  on   appears    3  Press MENU to return to the Main menu and use UP and DOWN to select Current IP   Address  The current IP address is shown in yellow at the bottom of the OLED    4  Ona computer in the same network  use a browser to open the assigned IP address  for  example http   192 168 14 250   5  When browsing to the Web Portal  a popup appears requesting a username and password   The default values are     Login  admin  Password  1234    O 2011 Racktivity Inc  10 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Manual IP Address Assignment    Obtain the correct IP address  standard gateway  DNS Server IP and subnet mask from your  network administrator     1  Press the MENU button until the Main menu appears  select Ethernet or Network using the  UP and DOWN buttons and press OK    2  Within the Ethernet or Network menu  select DHCP  on  and press OK until DHCP  off   appears    3  Select SET IP ADDRESS and press OK to change the settings  when navigating the menus  the  value for that setting is shown in yellow at the bottom of the OLED     4  Use the UP and DOWN buttons to change the currently selected value and press OK to select  the next value  When holding the UP and DOWN buttons changing the values speeds up   When ready press MENU to retur
9. User manual    PMOS16 01    Contents       Contents aiae Teraa a ei be lars S   lee de eh veut evebu suet A EEA rA 2  IntrOdUCtION  A Arietta A A A ad 4  Applicable Models  id ida a dia iria 4  INVENTORY  2 A E I ADA ia ees ie ae eee 5  Inspectioniof the  Packet a area ennen En 5  OVA BAe a 6  PRON ai ceeae arsine eth ee ese a ita 6  O RO 6  Install in ti AA AAA A A AA EA et 7  Motinting the  PDU cas a iia Teds aaa 7  ConnectingthePDU sd A OA ae a ae 7  OLED  Dil e e 8  Activating the display it aida nodo aida E E A E E A AE 8  Using the displasia IAEA A EA E EEE A A as 8  Setting the DEBIO A A A de ada 8  Reporting Screens  tii in a A FN ees 8  OVERVIEW  M DA A org A A ee Es 8  General  2 7       cccccccssosccesscsssvscceccsvscceccsunssevesceussvncescceunancodscaccsssocedsdanaseoecccuanovececeedssseseccaussovececeeanate 8   POr State TA A A Ee ee AA ais Rh lass ABER 9  POWER  4 7  aan A otindeduaacl stated ener E E E A NEEE 9  Power Consumption  5 7          ccccsssccessssccecsscccesseseeccssecccaaeccesseseeecsseeccaaeeceesseeecesaeecessaeeceesseeeeeaeess 9  Ambient Mirta O ao beeen SAES 9  Current Of Ports  7 7        ccccccccsssscceesscceecsseeeccssueccesseececesseeccsaceccessesesecsseecesaaeccssaeeesecsteeeesauecessaeeeeenaes 9  TOPP COMTIBUNAT OM A A A wees dE 10  Dynamic IP Address ASSISNMENL    ccccccnnnnnononnonononnnnnnnnnnnnonnnnnnnnnnonnnnnnnnnnnnnannnnnnr seende kneben eee 10  Manual lP Address Assign MENE    dada 11  Using  the Web  Portal e ed e Lao 12  Opening 
10. as been damaged by or subject to improper installation or operation   misuse  accident  neglect and or has been used in any way other than in strict compliance with  Racktivity s operation and installation manual   c  has become defective or inoperative due to its  integration or assembly with any equipment or products not supplied by Racktivity   d  has been  repaired  modified or otherwise altered by anyone other than Racktivity and or has been subject  to the opening of any sealed boxes without Racktivity s prior written consent  If any warranty  claim by Buyer falls within any of the foregoing exceptions  Buyer shall pay Racktivity its then  current rates and charges for such services     THE ABOVE WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES  EXPRESS OR IMPLIED  INCLUDING  THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE  ALL OF WHICH ARE  EXPRESSLY DISCLAIMED  RACKTIVITY SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL   INCIDENTAL  SPECIAL  OR EXEMPLARY DAMAGES  EVEN OF IT HAS BEEN ADVISED OF THE  POSSIBILITY OF SUCH DAMAGES     For warranty issues  contact the Product Support Department  All repair and return shipments  must be approved by Racktivity and must be accompanied by a RMA  Return Merchandise  Authorization  number and dated proof of purchase        2011 Racktivity Inc  21 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Troubleshooting       Password Reset    Resetting the password can be done on the de
11. ble to the following  Racktivity 1U models     e PM0816 01    O 2011 Racktivity Inc  4 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Inventory       Inspection of the Package    Inspect the package  see inventory  and contents for shipping damage and make sure that all  parts were received  Immediately report any damage from shipping to the shipping agent  and  missing content  damaging or other problems to your reseller     Please verify the contents of the package     Standard Package  Item Quantity       PDU 1  Rack mounting brackets   Rack mounting bracket screws  PDU Power cable  3 meter   Installation manual    PPA N       2011 Racktivity Inc  5 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Overview       Front    1 TEMP   2 ANTENNA  3 RS232   4 CONSOLE  5 LAN   6 OUTPUT  7 OLED   8 UP   9 DOWN  10 MENU  11 OK   12 ALARM  13 POWER    Rear    1 FUSE  INLET  OUTLET   4 AIRFLOW   5 TEMP       2011 Racktivity Inc     2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com    N A  N A  4 x RS232 interface connector  Console connector  Ethernet connector   LED  Status LED is on   Ethernet connection established  Status LED is flashing   Ethernet activity on the network  Blue LED activity indicator for each of the 8 ports  OLED display  Move to the previous page or browse upwards in a selection list  Move to the next page or browse downwards in a sel
12. credentials  the default values are     Login  admin  Password  1234    e Many devices require that you press the Enter key a few times before anything can be seen     You are now connected to the device s console port through ethernet  Up to 4 devices can be  connected to the PDU s RS232 connectors     SNMP MIB Files       Download the MIB files appropriate to your firmware from the Support section    O 2011 Racktivity Inc  19 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Specifications       Devices Connectable   Supported Voltages   RS232 ports   Networking   SNMP Monitoring  alerting and management  Remote control software   Integrated Remote Control Web server  Max current per port   Max current per PDU   Enable Disable ports   Form factor   Color graphical OLED Display   LED Indicators   Rack Mountable   Power consumption   Steel Case   Control buttons on front   Automatic Fuse Hardware 15 Amp  re  Microcontrolled based Fuse on each port  Internal Temperature       2011 Racktivity Inc     2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com    8  110 220V  4  Ethernet  Yes   Yes   Yes   8A   15A   Yes   1U   Yes   Yes   Yes   4 watt  Yes   Yes   Yes   Yes   Yes    20 25  v 2013 11 18    PDU Family Warranty       Warranty and Limitation of Liability    Racktivity agrees to repair or replace Datacenter Management Units   Products   that fail due to  a defect within twenty four  24  months after
13. e full benefits of SNMP  monitoring  Software like   Reasoning s MIB Browser can help get results quickly  while Zenoss  monitoring software takes a more in depth approach     O 2011 Racktivity Inc  17 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Serial Configuration       The PDU has 4 serial RS232 connectors located at the front to connect upto 4 external devices   ie  switches  server s        These connectors are primarily for recovery purposes  so when you have been locked out of an  external device you can still connect to it through Telnet using the PDU s ethernet connection     Configuring the serial connectors    e Make sure that the PDU has been properly configured for use on the network  For more info  see TCP IP Configuration   e Use a browser to open the PDU s IP address  You will be asked for login credentials  the  default values are     Login  admin  Password  1234    e Go to the Serial tab   Here you can specify for each connector    e Port  The number of the serial connector as seen on the front of the PDU   e Baudrate  Possible baudrates for serial communication  The baudrate of the serial  connector and a connected device must be the same   e  TelnetPort  Sets the telnet port  The port must end in the same number as the  corresponding serial connector  serial connector 3 cannot have a port ending with 4  ie   30004   it must end with a 3  ie  14203    e Reset Telnet  Disconnects an active telnet session
14. ection list  Button to access menu function  Validation button  Red alarm LED indicator  Blue power LED indicator    15A circuit breaker  16A inlet  IEC C20  8x outlet plug  Note  maximum load of 8A on each of the ports  amp  15A in total  N A  N A    6 25    v 2013 11 18    Installation       Mounting the PDU    The PDU comes with brackets for mounting in a rack    e Choose the appropriate location for the brackets on the sides of the unit  depending on the  desired deepness     e Attach the rack mounting brackets to the unit using 2 retaining screws  provided for each of the  brackets    Attach the PDU to a vertical rail in your rack  Position the PDU  align the buttons with the   rack mounting slots and fix the PDU with the required screws  not inserted in the package     When mounting the device  ensure that nothing is leaning on or close to the PDU  Best is to   leave open space for airflow and to assure accurate internal temperature measurements    The PDU itself is a low power device with a power consumption of only 2 Watt     Connecting the PDU     gt     The PDU has a detachable power cord  Attach the included power cord to the device by  inserting the IEC C20 connector in to the IEC C20 inlet    Note  Optionally  a user supplied power cord can be attached to the PDU by connecting it to  the IEC inlet  Do not attempt to attach a user supplied power cord unless it is certified to be  compatible with the input power source that will be used by the PDU    Connect the in
15. imestamp   that indicates when the maximum value was measured    Warning Level  When this threshold  in milliamp  re  is exceeded an SNMP Trap is sent  if   the SNMP checkbox for this port is checked    Off Level  when this threshold  in milliamp  re  is exceeded the port is automatically   powered off and an SNMP trap is sent  if the SNMP checkbox for this port is checked    Temp Off  When this temperature threshold  in   C  is exceeded by the internal   temperature sensor the port is automatically powered off and an SNMP trap is sent  if   the SNMP checkbox for this port is checked    SNMP  When checked SNMP Traps are enabled for this port   Priority   o The PDU looks at the thresholds of each port before checking the SUM  So  if a port  exceeds its Off Level threshold that port is powered off  followed by a check of the   SUM  Off Level threshold    o When the Off threshold in the  SUM  row is exceeded  the device looks at the  individual port priority settings to determine which port to power down first   second     even when it wasn t that port that caused the threshold to be exceeded  A  lower number means a higher priority  1 is the highest priority  8 the lowest     o If 2 ports have the same priority level  the PDU will determine which port had the  highest current increase and will power off that port  If no current increase is found   the port that was powered on last is powered off    Delay On  sets the startup delay  in seconds  after the PDU has been powered off
16. n to the Ethernet or Network menu    5  Repeat the last 2 steps for the Subnet mask  Std Gateway and DNS Server settings    6  Onacomputer in the same network  use a browser to open the chosen IP address  for  example http   192 168 14 250   7  When browsing to the Web Portal  a popup appears requesting a username and password   The default values are     Login  admin  Password  1234    O 2011 Racktivity Inc  11 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Using the Web Portal       Opening the Web Portal    Use a browser to open the PDU IP address  You will be asked for login credentials  the default  values are     Login  admin  Password  1234    Status tab    e The Status Screen shows the ON OFF status of the 8 ports on the PDU  o Grey background  port is powered OFF  o Green background  port is powered ON  e The button underneath each port toggles the port status instantly  even when a delay  has been set on the Protection tab   The load is activated at the zero crossing of the  voltage to avoid interference on the voltage  Toggling a port state always triggers an  SNMP Trap  regardless of other settings   e For each port  the real time True RMS is displayed  in Amp  re   e The default port names  port1  port2      can be changed at the Settings tab     Power tab    This tab shows all the power measurements in real time     e Port  Port name and status  o Grey background  Port is powered OFF  o Green background  Port i
17. on     The PDU features both access to SNMP data and the ability to send SNMP Traps     Configuring SNMP    e Make sure that the PDU has been properly configured for use on the network   e Use a browser to open the PDU s IP address  You will be asked for login credentials  the  default values are     Login  admin  Password  1234    e Go to the Settings tab  e Under the SNMP section you will find the following     O    Community read  Sets the community read string  default   public   When using SNMP  software on a pc to collect SNMP data  GET command  this string is used as verification  Community write  Sets the community write string  default   private   When using SNMP  software on a pc to change SNMP data  SET command  this string is used as verification  Write protection  When checked this setting will prevent changes being made through  SNMP  SET command   even when using the correct Community write string  It can be  used as an additional protection   Trap receiver port  Sets the port for the SNMP Trap function  default   162    Trap receiver IP  Sets the IP address where the SNMP Trap is sent  this is normally the IP  of a monitoring computer on the same network    SNMP Usage    Monitoring software with SNMP functionality enables you to stay on top of any developments  concerning the PDU  All relevant data  measurements  settings  port states  thresholds      are  accessible through SNMP GET requests     Make sure to load the Racktivity MIB file  found here  to get th
18. ot compromise the update     The update fails and the PDU becomes unresponsive     e  f needed  restore power and or Ethernet to the PDU  e Repeat the steps above to start the update again    In case you need to know the IP address  and it cannot be retrieved using the regular methods  then     e Connect a console cable between the PDU and your pc    e Use the following settings to read the output  Baudrate 38400  8 databits  no parity  1  stopbit    e Reboot the PDU  the currently used IP address is shown in the console output    e Repeat the steps above to start the update again        2011 Racktivity Inc  24 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Support       Feel free to contact us if you need any support or have any other questions or remarks     Online www racktivity com support   E mail support racktivity com   Phone 003293242095  GMT 1       2011 Racktivity Inc  25 25    2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    
19. put plug to a compatible AC power outlet    Note  The AC power source should not share a circuit with a heavy electrical load    Connect your equipment s input plugs to the outlet plugs of the PDU    Only when the appropriate port status LED is lit does the PDU provide power to that port   All blue port status LEDs will light up at first time use     Note  When not first time use  it is possible that not all LEDs light up  The PDU will only activate  those ports that were active when power was shut down  Non lit ports are not active     O 2011 Racktivity Inc  7 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    OLED Display       Activating the display  The OLED standby delay can be set at the Settings page on the Web Portal  the default value is 1    minute    On the PDU  push any of the 4 buttons next to the OLED Display to activate the screen     Using the display  The OLED is controlled using the UP  DOWN  MENU and OK buttons next to the screen     Use the UP and DOWN buttons to navigate through the reporting screens or through a selection  list in the menus  Press OK to select the highlighted item and MENU to go back     When in a menu  the   gt   symbol indicates that clicking this item will open a submenu  The  e   symbol indicates that this menu item leads directly to a setting     Setting the brightness    Press the MENU button until the Main menu appears    Select Brightness using the UP and DOWN buttons and press OK  
20. s powered ON   e Current  The real time current is displayed  in Amp  re    e Maximum  The maximum current measured  in Amp  re   Hover your mouse over this  value to see a timestamp that indicates when the maximum value was measured  This  value can be reset at the Protection tab   e Real Power  The real power usage  in Watts    e Apparent Power  The apparent power  in Volt Amp  re    e Power Factor  The power factor  in      e Resettable kWh  The total amount of kilowatt hours since the last reset   e Resettable kVAh  Total apparent power  in kilo Volt Amp  re hours  since the last reset   e Reset  Resets the Resettable kWh and the Resettable kVAh  note  this reset will not clear  the maximum column  this can be done at the Protection tab    e kWh  The total kilowatt hours since the PDU has been in use  This value can NOT be  reset     The default port names  port1  port2      can be changed at the Settings tab        2011 Racktivity Inc  12 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Ambient tab    The Ambient tab shows the environmental parameters being measured     Sensor  e Airflow  The airflow measured by an optional external sensor  in meters per second   e  Intrusion1  Shows the state of an optional external intrusion detector  e  Intrusion2  Shows the state of an optional external intrusion detector    Relative Humidity  e Value  The current relative humidity  in  RH   e Min  The lowest value since the last rese
21. t  in  RH   e Max  The highest value since the last reset  in  RH   e Reset  resets the Min and Max columns to the current value  e Warning Min  Sets the minimum value at which an SNMP trap is sent  e Warning Max  Sets the maximum value at which an SNMP trap is sent  e SNMP  if checked SNMP traps will be sent when the Warning Min and or Warning Max  values are crossed     Temperature  e Temperature  Shows the state of both the internal temperature sensor  on the first row   and any connected optional temperature sensors  o Grey background  No sensor connected  o Green background  Connected and active sensor    Value  The current temperature  in   C   e Minimum  The lowest value since the last reset  in   C   e Maximum  The highest value since the last reset  in   C   e Reset  Resets the Minimum and Maximum columns to the current value  e Warning Level  Sets the maximum temperature that when crossed causes an SNMP trap  to be sent  e SNMP  If checked SNMP traps are sent when the Warning Level is exceeded    After editing the settings on the Ambient tab  press the Save Data button  A pop up will appear  after the changes have been successfully saved     Settings tab    General  e PDU Name  Name of the PDU  e Rack Position  Optional administrative parameter that indicates where the PDU is    installed   Port Name  e Sets the preferred port names  typically the internal identification used for the connected  devices     2011 Racktivity Inc  13 25    2100 Seaport Blvd   Suite 400 
22. the Web Portal              oooocccnccnnnnnnnnncnnnnninnnnnnnnnnnnnnn T 12  SNMP ContiBguratiON  0 A AA A A A A EG E RARE 17  Configure SNMP a ode 17  SNMPUS ABS O crio ii eis E EEE dd lid dali 17  Serial Co e e o ne  18  Configuring the serial CONNECTOFS        ccccccccnnccnncnnnnnnannnnnanonanononnnnnnonnnnnnnnnnnnnnnnnnnnnnnnnnnannnr nono nn nnnnnnnannos 18  Using the Serial CONNECTIONS moret A ee ahs a ES 18  O 19  SNMP  MIB Ele cid tdt 19  O 2011 Racktivity Inc  2 25    2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Specifica OO r a A AGE 20    PDU Family Warranty iener eeen aei aaeei aeaa eaaa e aasa aee se aa aa aae aae t eaea ai iaaa 21  Warranty and Limitation of Liability                     oooococcnccnnnninnnnnnnnnanonanononononnnnnnnnnonnnnnnononononnnnnnnnnnnnnns 21  To e e o a 22  Password  Reset nd rob be een reis  22  Factory RES Odia A A E DAR E AEREA E DAA AA AA a A 22  Determine  Your Fife aen ERE ER E A L A EAT Re OAA 22  Web Portal ari 3 rear di eee da 22  OLED Dis Play 2 ia Eb ee dd 22  Determine Your IPAddress  saa ra ad henne add is  23  Firmware Update A a nens 23  LES UN ii ts 23  TrOUublESHOGUN  EERE A A WARES wcities 24  SUPPOM ioe ate is ME ee ie eee es dn E Le 25     2011 Racktivity Inc  3 25    2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Introduction       Applicable Models    Unless specified otherwise  all information in this document is applica
23. urrent of a particular port has reached the preset Warning threshold  the values will  turn orange  When the Off threshold is exceeded the port will be powered off and the values will  turn red     Power Consumption  5 7     This screen shows the power consumption expressed in kilowatt hour and kilovolt A hour for  each of the 8 ports     Ambient  6 7     When external temperature probes are connected  up to 8  they will show up here  The internal  temperature    C   humidity   RH  and an optional external airflow sensor  meters second  are  also displayed on this screen     Current of Ports  7 7     This screen shows a real time graph of the used current for each port  in Amp  re   When the  Warning and or Off threshold have been set an orange  Warning  and or red  Off  line will  appear     The thresholds can be set using the Web Portal        2011 Racktivity Inc  9 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    TCP IP Configuration       There are two methods for setting up the IP address  Dynamic IP Address assignment and  Manual IP Address assignment  If you are uncertain which method to use  contact your network  administrator for assistance before continuing the installation process     Dynamic IP Address Assignment    Connect the PDU to a network  While the PDU is powered on  connect a standard Ethernet cable  to the RJ45 Ethernet port  the activity LED will light up to indicate Ethernet connectivity     1  Press MEN
24. vice itself     e Press and hold the UP and DOWN buttons simultaneously for 4 seconds   e The password will now be reset to the factory default settings     Login  admin  Password  1234    This reset only affects the login credentials  no other settings are changed     Factory Reset    If you would like to reset the PDU to the factory default settings this can be done on the device  itself    WARNING  This will completely erase all settings  and could power down all ports  Make sure no  vital equipment is connected to the PDU when performing a Factory Reset     e Press and hold the MENU and OK buttons simultaneously for 4 seconds   e The device is now completely erased of user specified settings  the default login values are     Login  admin  Password  1234    Determine Your Firmware    Web Portal    Open the Web Portal on the PDU  The firmware version is displayed in the top right corner after  you log in  next to  SW V    your firmware version      OLED Display    On the PDU open the Main menu  then select Version Numbers followed by Software Version     The firmware version is displayed at the bottom of the OLED in yellow     O 2011 Racktivity Inc  22 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    Determine Your IP Address    To determine the IP address currently used by the PDU  first choose your firmware version     Press MENU until the Main menu appears  select Network or Ethernet using UP and DOWN  and press OK    Use
25. y saved     Schedule tab    Here you can specify a schedule which defines for each port if and when it should be turned off  and or on and if this should be repeated on a daily basis     e Port  Port name and status  o Grey background  Port is powered OFF  o Green background  Port is powered ON   e Time Off  Time in hours minutes when the port is to be turned off  with Off Enable  checked    e Off Enable  When checked the port will be turned off at the time specified in Time Off   e Time On  Time in hours minutes when the port is to be turned on  with On Enable  checked    e On Enable  When checked the port will be turned on at the time specified in Time on   e Repeat Daily  When checked the specified schedule for that port will be repeated daily    The current time is displayed below the table   After editing the settings on the Schedule tab  press the Save Data button  A pop up will appear  after the changes have been successfully saved     Logging tab    The PDU s short  medium  long  and event logging are displayed on this tab  For each type the  number of items needed can be specified  Changing the logging intervals can be done at the  Settings tab     O 2011 Racktivity Inc  16 25  2100 Seaport Blvd   Suite 400  Redwood City 94063  USA     www  racktivity com v 2013 11 18    SNMP Configuration       SNMP  Simple Network Management Protocol  is mostly used in network management systems  to monitor network attached devices for conditions that warrant administrative attenti
    