User Manual M1
Contents
1. N L Power Supply 230 VAC Rx O Power Supply 24 VDC 2 Electrical connection 3 Function and operation descirption 3 Function and operation description Operation The operation is divided into two different levels Menu Level Here it is possible to navigate between the individual menu items Parameterization level The parameters stored in the menu item can be parameterized here Functions that can be adjusted or changed are always indicated with a flashing of the display Adjustments made at the parameterization level should be always confirmed by pressing the P key to save them However the display automatically saves all adjustments and then switches to operation mode if no further keys are pressed within 10 seconds Description Change to parameterization level with the relevant parameters Menu level For navigation at the menu level To confirm the changes made at the parameterization level Parameterization level y To change the value or setting Example Parameterization level 1 y ESPE P y El L Programming via configuration software PM TOOL MUSB6 You receive the software on CD incl an USB cable with a device adaptor The connection is done via a 6 pole micromatch connector plug on the back and the PC is connected via an USB connector plug System requirements PC with USB interface Software Windows XP Win
2. l sy is Off Display Hysterisis Sa Alarms Limit value undercut LOW By limit value undercut the alarm IE cat E eee ne S1 S2 is on below the threshold On i and switched off on reaching the z threshold z A v T E 3 v 1 a Off Display Hysterisis A Alarms optical setpoint display An activated set point can be optically indicated by flashing of the 7 segment display Functional principle of the alarms Alarms Deactivated display value Threshold Threshold limit value for switch over Width of the window between the thresholds Function ss Limit value exceedance limit value undercut 10 5 Factory settings EJ C3 C3 2c 1 EJ Ea paja Co mm Muy EJ EJ AA to Menu items Mao una iu ia Nat Aa pun 5 1 Default values Parameter 5 Factory settings OO onjon fon fon fon fon fon aan ponia On on jon en jan Oyo Jonjon fon fon fon fon jon Oy poo fo fon jon fon jon jon on T T D m g 2 2 2 2 2 2 2 2 282 x x 3309 09 en Jon fon Jon 9 3 09 09 an on fon fon a 3f0n on fon fon on on ESP pr pr or or for pa aa 08059 05 0505 0205 0500 10077000 000 0077 007 oyo jojojo o jo o 0 fon on oniorjon jon ooo Clan ion ono jojo o ojo ala fon oJ pag ka Eo O O Eno a a ca of ole E a Ea O 8 04 En On On ca cl cima 3foniea ar 0 En On tn oy am 23 ojm 121 T T TCI O olola J e EHEr I Il a I L I AE TET YT
3. AAA The preset value is add to the linearized value This way the characteristic line can be adjusted according to the selected value Zero point slowdown ZERO oeg 70 With zero point slowdown a value range around zero can be pre selected at which the display shows zero If for example a 10 is set the display would show a zero in the range from 10 to 10 and continue below it with 11 and above it with 11 4 3 1 MIN MAX value inquiry Assignment of key functions TAST HEr A ET 5 no P Here you can enter for the operating mode either a MIN MAX value inquiry or a threshold value correction on the arrow keys 4 Setting up the device Menu level Parameterization level 4 3 1 MIN MAX value inquiry Assignment of key functions TAST If the MIN MAX memory is activated with EHER the measured MIN MAX values will be saved during operation and can be called up via the arrow keys A Y The values are lost if the device is restarted If the threshold value correction Ll 1 is selected the limit values can be changed during operation without hindering the operating procedure If NO is parameterized the arrow keys W A have no function in operating mode 4 3 2 Flashing of display FLAS Here the flashing of the display can be added as an extra alarm function either to the first limit value select Li the second limit value select Li 2 or to both limit values select Li I2 With
4. NO works setting no flashing is assigned at all 4 3 3 Limit values Limits L 1 a an EA For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other Hysteresis for limit values HY a ding Bda yl For all limit values a hysteresis function exists that reacts according to the settings threshold exceedance threshold undercut Function if display falls below exceeds limit value FU Lalola 5 P The limit value undercut can be selected with LOUU LOW lower limit value and limit value exceedance can be selected with HIGH HIGH upper limit value If e g limit value 1 is on a switching threshold of 100 and occupied with function HiGH the alarm will be activated by reaching the threshold If the limit value is allocated to LOL an alarm will be activated by undercut of the threshold Limit value Limits L e a gngragta E For both limit values two different values can be parameterized With this the parameters for each limit value are called up one after the other 4 Setting up the device Menu level Parameterization level Hysteresis for limit values HY 2 CODA For all limit values a hysteresis function exists that reacts according to the settings threshold exceedance threshold undercut Ny A y Looe iv P To indicate if the value falls below the lower limi
5. YT Ey 10 Del oc me Oc oc Oc ac YES luna po Pm Pg Pf ag a ee el LL TOLL TOL TW cl LO ee Lo LO Uy OL Le CHUL CLL COC uy as Lale yy OL lolo Eo uy Capua Capua a Ag iaa pg ac pu lea fac pu tala ala 5 Factory settings A 4999 399939 O Tar a 7 a c J gt J c I LO LO LO o aL Lr E L L i L a oot o Loli La I J LO LO Lo x gt O L LO Li LW J y LOLA n Lo Lo J J 0 o Ij L L J LO R J p My LO LO LO T al o 1 LO Li O Lo ua Li Li E Li di 5o 1 l OC I i Pl 4 I a J J J LO LO Wo J J J J J J J J Li Li Li o La Li E J E LO LO La Lo O LO LO Lo Lo LO Loy L Lo LO LO pL ul JO O 1 LO Lau J J LU LO OLA TO Ln Do Co 4 4 5 2 Reset to default values To return the unit to a defined basic state a reset can be carried out to the default values The following procedure should be used e Switch off the power supply e Press button P e Switch on voltage supply and press P button until is shown in the display With reset the default values of the program table are loaded and used for subsequent operation This puts the unit back to the state in which it was supplied Caution All application related data are l
6. 2006 95 EG EN 61010 EN 60664 1 14 7 Safety advices 7 Safety advice Please read the following safety advice and the assembly chapter 1 before installation and keep it for future reference Proper use The M1 device is designed for the evaluation and display of sensor signals LN Danger Careless use or improper operation can result in N personal injury and or damage to the equipment s Control of the device The panel meters are checked before dispatch and sent out in perfect condition Should there be any visible damage we recommend close examination of the packaging Please inform the supplier immediately of any damage Installation The M1 device must be installed by a suitably qualified specialist e g with a qualification in industrial electronics Notes on installation There must be no magnetic or electric fields in the vicinity of the device e g due to transformers mobile phones or electrostatic discharge e The fuse rating of the supply voltage should not exceed a value of 6A N B fuse e Do not install inductive consumers relays solenoid valves etc near the device and suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes e Keep input output and supply lines separate from one another and do not lay them parallel with each other Position go and return lines next to one another Where possible use twisted pair So you receive bes
7. User Manual M1 Resistance values 1 kQ 10 kQ 100 kQ 1000 kQ Technical features e red display of 1999 9999 digits optional green orange or blue display e minimal installation depth 25 mm without plug in terminal e adjustment via factory default or directly on the sensor signal e min max value recording e 10 parameter driven setpoints e display flashing at threshold exceedance or undershooting e Tara function e impedance matching programming interlock via access code e protection class IP65 at the front e plug in screw terminal e pc based configuration software PM TOOL for devices without keypad for a simple adjustment of standard devices M1_16GB pdf Stand 28 10 2011 96x48 Identification STANDARD TYPES ORDER NUMBER Direct voltage resistance M1 1VR4B 0x06 570BD Housing size 96x48 mm M1 1VR4B 0x06 770BD Options breakdown of order code Basic type M Line Installation depth 38 mm incl plug in terminal Housing size 96x48x25 mm without plug terminal Display type Current voltage Resistance Display colours Blue Green Red Orange Number of digits 4 digit Digit height 14 mm Interface Without Ed lt 2 0 e el Melo El Dimension o physical Unit Version B B Setpoints o No setpoints Protection class 1 without keypad operation on the back IP65 plug in terminal Supply voltage 5 230 VAC 24 VDC galv insulated Measurin
8. dows Vista 4 Setting up the device 4 Setting up the device 4 1 Switching on Once the installation is complete you can start the device by applying the current loop Check beforehand once again that all the electrical connections are correct Starting sequence For 1 second during the switching on process the segment test 8 8 8 8 is displayed followed by an indication of the software type and after that also for 1 second the software version After the start up sequence the device switches to operation display mode 4 2 Standard parameterization To be able to parameterize the display press the P key in operating mode for 1 second The display then changes to the menu level with the first menu item TYPE Menu level Parameterization level Selection of the input signal TYPE As input versions resistance values of 1 10 100 or 1000 kQ signals as factory calibration without connected sensor signal and SENS with connected measuring signal as sensor calibration are available Confirm with P The display then switches back to the menu level again Setting the final value of the measuring range END JCA al BD yl dar ME v PT The final value is adjusted from the smallest to the highest place with W A and confirmed place selective with P A minus sign can only be parameterized on the highest place After the last place the display switches back to the menu level I
9. eterization RUN With the aid of the A Y keys you can choose between the deactivated key lock ULOC works setting and the activated key lock LOL Make the selection with P After this the display confirms the settings with and automatically switches to operating mode If LOC was selected the keyboard is locked To get back into the menu level you must press P for 3 seconds in operating mode You must now enter the CODE works setting 7 2 3 4 that appears using the A V keys plus P to unlock the keyboard FAIL appears if the input is wrong 4 Setting up the device 4 3 Extended parameterization By pressing the A 8 W buttons during standard parameterization for one second the display switches to the extended parameterization mode Operation is the same as in standard parameterization Menu level Parameterization level Rescaling of measuring input values ENDA EndA P gra te v a With this function the final value e g 1500 Q factory setting can be rescaled without connecting of a measuring signals At selected sensor calibration these parameters are not available Rescaling of measuring input values OFFA ri rm O g A gP geag aP With this function the initial value e g 500 Q factory setting can be rescaled without connecting of a measuring signals At selected sensor calibration these parameters are not available Setting of Tara Offset value TARA
10. f SEN has been selected you can then choose between N amp CA and CAL At NOCA the before adjusted value will be taken over at CAL the value alignment via the measuring section takes place and the analog input value is taken over Setting the initial value of the measuring range OFFS 5 _ A aOCA a avalan ca wP The initial value is adjusted from the smallest to the highest place with W A and confirmed place selective with P After the last place the display switches back to the menu level If SENS has been selected you can then choose between NOCA and CAL At NOCA the before adjusted value will be taken over at CAL the value alignment via the measuring section takes place and the analog input value is taken over 4 Setting up the device Menu level Parameterization level Setting the decimal place sign of physical unit END pa 4 noog Al fp M v LILI LILI v The decimal place and the physical unit are set with W A Confirm with P the display then switches back to the menu level again v The display time is set with A Y The display moves up in increments of 0 1 up to 1 second and in increments of 1 0 to 10 0 seconds Confirm the selection by pressing the P button The display then switches back to the menu level again Activation deactivation of the programming lock and completion of the standard param
11. g input 6 Resistance Analog output o Without Resistance value 8 1 kOhm 10 kOhm 6 1000 kOhm 1000 kOhm Please state physical unit by order e g mm Contents A A Assembly Electrical connection Function and operation description Setting up the device 4 1 Switching on 4 2 Standard parameterization 4 3 Extended parameterization 4 3 1 Min Max value inquiry TAST 4 3 2 Flashing of display FLAS 4 3 3 Threshold values F to Li c 4 3 4 Setpoints SPET Factory settings 5 1 Default values 5 2 Reset to default settings Technical data Safety advice Error elimination 0 ON nN Oa a FF W N 11 12 13 15 16 1 Assembly 1 Assembly Please read the Safety advice on page 15 before installation and keep this user manual for future reference Gap for physical eS unit EL pS 1 After removing the fixing elements insert the device 2 Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping screws by hand Then use a screwdriver to tighten them another half a turn CAUTION The torque should not exceed 0 1 Nm The dimension symbols can be exchanged before installation via a channel on the side 2 Electrical connection Type M1 1VR4B 0x06 570BD with a supply of 230 VAC Type M1 1VR4B 0x06 770BD with a supply of 24 VDC Input Supply OOO Rx
12. ge signal it is only connected on one side or the input is open Not all of the activated setpoints are parameterised Check if the relevant parameters are adjusted correctly The word HELP lights up in the e The unit has found an error in the configuration 7 segment display memory Perform a reset on the default values and re configure the unit according to your application 4 Program numbers for parameterising Programming lock is activated of the input are not accessible Enter correct code 5 ERRT lights up in the 7 segment e Please contact the manufacturer if errors of this display kind occur The device does not react as If you are not sure if the device has been expected parameterised before then follow the steps as written in chapter 5 2 and set it back to its delivery status 16 M1_16GB pdf Stand 28 10 2011
13. ost 12 6 Technical data 6 Technical data 96x48x25 mm BxHxT 96x48x38 mm BxHxT including plug in terminal Panel cut out 96x48 92 0 0 8 x 45 0 9 6 mm Insulation thickness up to 3 mm snap in screw element PC Polycarbonate black UL94V 0 EPDM 65 Shore black standard IP65 front IPOO back side Fixing Material Sealing material Protection class Weight approx 100 g Connection plug in terminal wire cross section up to 2 5 mm Display Digit height 14 mm Segment colour red Display range 1999 to 9999 Setpoints optical display flashing Overflow Underflow horizontal bars at the top horizontal bars at the bottom 0 1 to 10 0 seconds Measuring fault 0 1 1 kO 0 5 of measuring range 0 11 kO 0 5 of measuring range 0 110 kO 0 5 of measuring range 0 1100 kQ 0 5 of measuring range Temperature drift 100 ppm K 0 1 10 0 seconds Display time Measuring time Measuring principle U F conversion Resolution approx 18 Bit at 1 second measuring time Power pack 230 VAC 10 max 6 VA 24 VDC 10 max 1 VA Memory EEPROM Data life 2 100 years 13 6 Technical data Ambient conditions Working temperature Storing temperature Weathering resistance CE sign Safety standard 0 60 C 20 85 C relative humidity 0 80 on years average without dew EN 61326 Conformity to directive 2004 108 EG According to low voltage directive
14. t measuring results e Screen off and twist sensor lines Do not lay current carrying lines in the vicinity Connect the screening on one side on a suitable potential equaliser normally signal ground e The device is not suitable for installation in areas where there is a risk of explosion e Any electrical connection deviating from the connection diagram can endanger human life and or can destroy the equipment e The terminal area of the devices is part of the service Here electrostatic discharge needs to be avoided Attention High voltages can cause dangerous body currents e Galvanic insulated potentials within one complex need to be placed on a appropriate point normally earth or machines ground So a lower disturbance sensibility against impacted energy can be reached and dangerous potentials that can occur on long lines or due to faulty wiring can be avoided 15 8 Error elimination 8 Error elimination _ Error description Measures S 1 The unit permanently indicates e The input has a very high measurement check overflow the measuring circuit e With a selected input with a low voltage signal it is only connected on one side or the input is open Not all of the activated setpoints are parameterised Check if the relevant parameters are adjusted correctly The unit permanently shows e The input has a very low measurement check underflow the measuring circuit e With a selected input with a low volta
15. t value LOUU can be selected LOW lower limit value and if it goes above the upper limit value HIGH can be selected HIGH upper limit value LOW corresponds to the quiescent current principle and HIGH to the operating current principle Setting the code CODE 7 a y A a ege g a E With this setting it is possible to select an individual code works setting 1 2 3 Y for locking the keyboard To lock release the key proceed according to menu item RUN 4 3 4 Setpoints Number of additional setpoints SPCT mj A gd yO In addition to the start and end value 8 extra setpoints can be defined to linearize non linear sensor values Only the activated setpoint parameters are displayed Besgelg ele Under this parameter the setpoints are defined on a value basis At the sensor calibration one will be asked at the end like at Endwert Offset too if a calibration shall be triggered Analogue values for setpoints NP7 INP8 m1 mi m n A ongeonge y 5 P Setpoints are only displayed under works calibration 4 20 mA Here you can choose your analog values The entry of constantly rising values need to be done self contained 4 Setting up the device Functional principle of the setpoints Alarms Limit value exceedance HIGH By limit value exceedance the a al a oe at alarm S1 S2 is off below the on a i threshold and on on reaching the 1 threshold D as e rs
Download Pdf Manuals
Related Search
Related Contents
Silcoseal Select : Quick User Guide Datos técnicos Raypak B-195 User's Manual Guide d`utilisation du service de collecte en bac et sacs 2 - PageCarto - PageCarto Réseau Anact SD100R L Band Demodulator - downloads SERIE MODELOS LS-40/40TD/50TD Visualizza/apri - POLITesi Copyright © All rights reserved.