CL2X8-D1S2 CC-Link/LT Remote I/O Module User`s Manual

image

Contents

1. 2 Cable removal Insert the tool into the corresponding square shaped hall until it stops Pull the wire out of the hall completely Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system eee Country Region Sales office Tel Country Region Sales office Tel U S A Mitsubishi Electric Automation Inc Hong Kong Ryoden Automation Ltd 500 Corporate Woods Parkway Vernon 10th Floor Manulife Tower 169 Electric Hills IL 60061 Road North Point HongKong Tel 1 847 478 2100 Tel 852 2887 8870 Brazil MELCO TEC Rep Com e Assess
2. 69 2 72 4 5x5 1 elongated mounting hole M4 screw 4 60 5 2 38 0 4 0 02 45 10 016 1 0 18 5 0 39 AAS 88888880 5 5 Paha S 0 16 o A o z e S en 1 tl g a La l Center of DIN rail kia 4 5 installation hole M4 screw 40 1 57 Unit mm inch 7 Cable Installation Procedure 1 Cable Installation Insert the tool into the square shaped hole which corresponds to the terminal you wish to use While the tool is inside the hole insert the wire into the circular shaped hole as shown below Remove the tool from the square shaped hole taking care not to remove the wire After the wire has been clamped gently pull the wire to confirm that it is secure Square shaped hole 1 Take care that the wire strip length Circular shaped hole is between 8mm to 11mm If the wire strip length is too long his will expose the bare wire which increases the risk of electric shock Tool 2 or short circuit If the wire strip length is too short his will result in the wire not being securely attached Wire strip length 2 When mounting removing the cable 8mm to 11mm 1 make sure to use the dedicated tool i e a tool dedicated to spring clamp erminal block and insert the tool vertically into the hole If a general slotted screwdriver is used instead of the dedicated tool or the tool is not vertically inserted he spring clamp terminal part or erminal block resin part might be broken
3. On Indicates that a communication data error has occurred or the setting switch is outside the allowable range Flicker at regular intervals Indicates that the setting switch has been changed while current is being conducted The module continues to operate even while the LED is flickering The changed settings will be reflected when the power has been restored Flicker at irregular intervals Indicates that the terminal resistor is left unconnected or that the module or connection cable are affected by noise Off Normal communication Displays the ON OFF status of the input turned on in the ON status and turned off in the OFF status Response time Set the response time OFF ON ON OFF time of the remote I O setting switch module SW8 OFF is set as default factory set Noise may be taken in as input if high speed response type is set Be sure to set response time in consideration of the environment ON 0 5ms High speed response type OFF 1 5ms Standard type Station number Select 1 20 or 40 to set the ten s place of the station number setting switches Select 1 2 4 or 8 to set the one s place of the station number SW1 to 7 All switches are set to OFF at shipment from the factory Always set the station number within the range of 1 to 64 A setting error occurs and L ERR LED flickers if the value outside the range 1 to 64 is set Example Set the switches as below when setting the station number to
4. 0 12kg I O part connection method 2 piece 20 point spring clamp terminal block Module installation method DIN rail installation mounted by screws of type M4 x 0 7 mm x 16 mm or larger Can be installed in six directions Applicable wire size 0 3 to 1 5mm AWG22 to 16 3 Part Names This section explains the names of the components for the remote I O module 1 y AiP s p OUUUEEEU rw O00 G See MN 1 r E E STATON NO in CERLE EENEN 1c2ae oc24e coma come comelcome comelcome comelcom 5 6 Pin numbers and s ignal Terminal numbers and signal names 1 3 5 779 n 73 5 17 19 4324 lpceaafpceaal xo x1 x2 xs xa x5 xe x7 oo0g0 2 4 e 8 io i2 is 7 20 lbc24 oc248 comB coms coms come come coma coms come LINK PW Description Confirmation details On Power supply on Off The power supply is turned off or the voltage drop is too large On Normal communication Off Communication cutoff time expiration error
5. 32 Station Ten s place One s place number 40 20 10 8 4 2 1 32 OFF ON ON OFF OFF ON OFF Connector for Connector for CC Link LT communication line and module power supply CC Link LT interface Terminal block Terminal block for connecting input signals and external power supply o for I O interface the input part Hook for Hook for installing the module on a DIN rail DIN rail Operating LED name status indicator LEDs PW O0to7 4 Handling Precautions 1 Tighten the terminal screws for the module to the specified torque shown below Insufficient tightening torque could result in shorts failures or malfunction 0 824 to 1 11N m 0 425 to 0 575 N m Module mounting screw M4 screw Terminal block mounting screw M3 screw Clamping torque range 2 When using a DIN rail attach the DIN rail after taking the following items into consideration a Applicable DIN rail types conform to JIS C 2812 TH35 7 5Fe TH35 7 5Al b Interval between the DIN rail s installation screws Tighten the screws using a pitch of 200mm 7 87in or less when attaching a DIN rail 3 To attach the remote I O module to the DIN rail press the centerline area of the DIN rail hook beneath the module until a click is heard 4 Maintain some distance between the module and other components and parts 10 mm from the top and 50mm 1 97in from the bottom of th
6. MITSUBISHI CL2X8 D1S2 CC Link LT Remote I O Module Thank you very much for purchasing this product Please read this manual thoroughly before starting to use the product and handle the product properly User s Manual MODEL CL2X8 D1S2 U CC Link LT MODEL IB NA 0800256 B 0506 MEE 2003 MITSUBISHI ELECTRIC CORPORATION SAFETY PRECAUTIONS Read these precautions before using Please read this manual carefully and pay special attention to safety in order to handle this product properly Also pay careful attention to safety and handle the module properly These precautions apply only to Mitsubishi equipment Refer to the user s manual of the CPU module to use for a description of the PLC system safety precautions These SAFETY PRECAUTIONS classify the safety precautions into two categories DANGER and CAUTION 1 i a i 1 Procedures which may lead to a dangerous condition and cause i 7 DANGER death or serious injury if not carried out properly H 1 1 ji Procedures which may lead to a dangerous condition and cause 1 1 H A CAUTION superficial to medium injury or physical damage only if not carried out properly Depending on circumstances procedures indicated by NCAUTION may also be linked to serious results In any case it is important to follow the directions for usage Store this manual in a safe place so that you can take it out and read it whenever necessary Always forward i
7. No 11 Kawasan Industri France Mitsubishi Electric Europe B V French Pergudangan Jakarta Utara 14440 Branch Tel 62 21 663 0833 India Messung Systems Put Ltd 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 Circuit Breaker Industries LTD Australia Tripswitch Drive Elandsfontein Gauteng South Africa Tel 27 11 928 2000 Electronic Sadan NO 111 Unit No15 M 1 D C BHOSARI PUNE 41 1026 India Tel 91 20 712 2807 Mitsubishi Electric Australia Pty Ltd 348 Victoria Road PostalBag No 2 Rydalmere N S W 2116 Australia Tel 61 2 9684 7777 MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE 1 8 12 OFFICE TOWER Z 14F HARUMI CHUO KU 104 6212 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN South Africa Specifications subject to change without notice Printed in Japan on recycled paper
8. ad voltage 24V DC Rated input current Approx 4mA Max simultaneous Ol points N input 100 ON voltage ON curre nt 19V or higher 3mA or higher OFF voltage OFF current 11V or lower 1 7mA or lower Input resistance 5 6kQ Response time setting 0 5ms High speed response type 1 5ms Standard type OFF gt TYR 0 05 ms ON MAX 0 1 ms 1 5ms ON gt TYP 0 2 ms OFF MAX 0 5 ms 1 5 ms Common wiring met od 8 points 1 common terminal block 2 wire type Input method Positive common negative common shared type Number of stations occupied In 4 point mode Occupies 2 stations In 8 or 16 point mode Occupies 1 station Voltage 24V DC 15 to 20 ripple ratio within 5 Module Current consumption 40mA or lower When 24V DC and all point is on power supply Current on startup 70mA or lower 24V DC Noise durability DC type noise voltage 500Vp p noise width 1s noise carrier frequency 25 to 60Hz noise simulator condition First transient noise burst IEC 61000 4 4 1kV Withstand voltage 500V AC for 1 minute between primary external DC terminal and secondary internal circuit Insulation resistance 10MQ or more between primary external DC terminal and secondary internal circuit when measured with a 500V DC insulation resistance tester Protection class IP2X Weight
9. e module in order to improve ventilation and to make replacement of the module easy if a remote I O module is installed on a board 5 Install the remote I O module on a level surface If the surface is uneven unnecessary force is applied to the printed circuit board causing malfunctions 5 Wiring Connector for CC Link LT interface CL2x8 D1S2 Insulation 1 24V Dt i Baa DA DB ocloc 24G 1 Terminal Block 1 for O interface Positive common 1 DC24A DC24B DC24A DC24B External power External power supply ofthe Terminal block supply of the input part for I O interface input part DC24V Negative common DC24V fate L i D240 2 DC24B DC24B Bfoo ro All COM B and DC24B terminals are connected within the module common The power to the module is supplied via the power adapter 6 External Dimensions
10. isassemble or modify the module Doing so may cause failure malfunction injury or fire Do not drop or apply any strong impact to the module Doing so may damage the module Completely turn off the externally supplied power used in the system before mounting or removing the module Not doing so could result in damage to the product Before touching the module always touch grounded metal etc to discharge static electricity from the human body etc Not doing so can cause the module to fail or malfunction DISPOSAL PRECAUTIONS When disposing of this product treat it as industrial waste 1 Overvi ew This user s manual explains specifications and names of individual parts of the CL2X8 D1S2 type CC Link LT remote I O module hereinafter abbreviated as remote 1 O module 2 Specifications 2 1 General Specifications The General specifications for the remote I O module are shown in the following table Item Specifications Operating ambient s temperature 0 to 55 C Storage ambient F temperature 25 to 75 C Operating ambient humidity 5 to 95 RH non condensing Storage ambient humidity 5 to 95 RH non condensing Vibration resistance Frequency Acceleration Amplitude Sweep count Under 0 075mm Conforming intermittent 10 t 57Hz 0 003in 10 times each 5 ap ce vibration 57to150Hz 9 8m s in X Y Z 61131 2 Under 49 to 57Hz 0 035mm directions f
11. or continuous 0 001in 80 min vibration 57to150Hz 4 9m s Shock resistance Conforming to JIS B 3502 IEC 61131 2 147 m s 3 times in each of 3 directions X Y Z Operating ambience No corrosive gases Operating altitude 2000m 6562ft max Installation location Inside control panel 3 Overvoltage category 1 Il max Pollution level 2 2 max 1 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises Category II applies to equipment for which electrical power is supplied from fixed facilities The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V 2 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used Pollution level 2 is when only non conductive pollution occurs A temporary conductivity caused by condensing must be expected occasionally 3 It can also be used in an environment other than on the control panel if the conditions such as usage ambient temperature and humidity are satisfied 2 2 Performance specifications The performance table Number of inputs specifications for the remote I O module are shown in the following CL2x8 D1S2 8 points Isolation method Photocoupler isolation Rated lo
12. oria China Ryoden Automation Shanghai Ltd Tecnica Ltda 3F Block5 Building Automation Rua Correia Dias 184 Instrumentation Plaza 103 Cao Bao Rd Edificio Paraiso Trade Center 8 andar Shanghai 200233 China Paraiso Sao Paulo SP Brazil Tel 86 21 6120 0808 Tel 55 11 5908 8331 Taiwan Setsuyo Enterprise Co Ltd Germany Mitsubishi Electric Europe B V German 6F No 105 Wu Kung 3rd RD Wu Ku Branch Hsiang Taipei Hsine Taiwan Gothaer Strasse 8 D 40880 Ratingen Tel 886 2 2299 2499 GERMANY Korea HAN NEUNG TECHNO CO LTD Tel 49 2102 486 0 1F Dong Seo Game Channel Bldg UK Mitsubishi Electric Europe B V UK 660 11 Deungchon dong Kangsec ku Branch Seoul Korea Travellers Lane Hatfield Herts AL10 Tel 82 2 3660 9552 8XB UK Singapore Mitsubishi Electric Asia Pte Ltd Tel 44 1707 276100 307 Alexandra Road 05 01 02 Italy Mitsubishi Electric Europe B V Italian Mitsubishi Electric Building Branch Singapore 159943 Centro Dir Colleoni Pal Perseo Ingr 2 7 Tel aa PA aR Via Paracelso 12 20041 Agrate B Thailand F A Tech Co Ltd A Milano Italy 898 28 29 30 S V City Building Office Tel 39 039 6053344 Tower 2 Floor 17 18 Rama 3 Road Spain Mitsubishi Electric Europe B V Spanish Bangkpongpang Yannawa Branch Bangkok 10120 Carretera de Rubi 76 80 Tel 66 2 682 6522 08190 Sant Cugat del Valles Indonesia P T Autoteknindo SUMBER MAKMUR Barcelona Spain Jl Muara Karang Selatan Block a Utara Tel 34 93 565 3131 No 1 Kav
13. s may be damaged which may cause the module to drop from its installation position or short circuit WIRING PRECAUTIONS Completely turn off the externally supplied power used in the system when installing or placing wiring Not completely turning off all power could result in electric shock or damage to the product Terminal screws which are not to be used must be tightened always Otherwise there will be a danger of short circuit against the bare solderless terminals Perform correct wiring for the module according to the product s rated voltage and terminal arrangement Connecting to a power supply different from rating or miss wiring may cause fire and or product failure Fix terminal screws securely within the regulated torque Loose terminal screws may cause fire and or malfunction If the terminal screws are too tight it may cause short circuit or erroneous operation due to damage of the screws Make sure foreign objects do not get inside the module such as dirt and wire chips It may cause fire product failure or malfunction STARTING AND MAINTENANCE PRECAUTIONS Do not touch terminals when the power is on Doing so could cause an electric shock Switch off all phases of the externally supplied power used in the system when cleaning the module or retightening the terminal or module mounting screws Not doing so could result in electric shock STARTING AND MAINTENANCE PRECAUTIONS Do not d
14. t to the end user DESIGN PRECAUTIONS Configure an interlock circuit in a sequence program so that the system operates on the safety side using the communication status information in the event the data link falls into a communication problem Otherwise erroneous output and malfunction may result in accidents Input could be switched on or off when a problem occurs in the remote I O modules So build an external monitoring circuit that will monitor any input signals that could cause a serious accident Do not have control cables and communication cables bundled with or placed near by the main circuit and or power cables Wire those cables at least 100mm 3 94 inch away from the main circuit and or power cables It may cause malfunction due to noise interference INSTALLATION PRECAUTIONS Use the module in an environment that meets the general specifications contained in this manual Using this module in an environment outside the range of the general specifications could result in electric shock fire erroneous operation and damage to or deterioration of the product Do not directly touch the module s conductive parts Doing so could cause malfunction or trouble in the module Tighten the module securely using DIN rail or installation screws within the specified torque range If the screws are too lose the module may drop from its installation position short circuit or malfunction If the screws are too tight the screw