User Manual LON I/O Module DR-N 8S-10A

image

Contents

1. Default value Description Version 23 07 08 SNVT_switch value 0 100 State 0 1 1 ON state 1 and value gt 0 OFF state 0 or state 1 and value 0 Deactivated state 1 UCPTdefaultManOverrideSw i Control input with a higher priority than nviLAlampValue i After deactivation state 1 invalid value the switching channel adopts a status depending on the setting in UCPTafterReleaseManOverride i Alternatively this input can be logically linked with nviLAlampValue i The linking is selected using the parameter UCPTlogicFunction i Subject to modifications Page 9 of 20 Schneider LON I O Module DR N 8S 10A Electric Application 8818011_01B Output variables nvoLAlampValueFb i Type SNVT_switch Value range value 0 100 state 0 1 ON state 1 and value gt 0 Default value Description OFF state 0 or state 1 and value 0 UCPTdefaultLampValue i The current value status of the switching channel is sent to the network here either immediately upon being changed or after a delay defined in UCPTfeedbackDelay i Switch on and switch off delays are regarded as being complete This output can be cyclically sent over the period specified in SCPTmaxSendTime i Configuration variables UCPTonDelay i Switch on delay Type Value range Default value Description UNVT_time_sec 0 65 535 s increment 1 s 0
2. invalid_request Default value All bits 0 Description Is transmitted when an update to nviRequest is received nvo00FileDir Type SNVT_address Value range 16 384 64 767 Default value Undefined Description Is required for internal functionality Configuration variables UCPTdeviceButton Device buttons Type UNVT_enabled Range DISABLED ENABLED Default ENABLED Description To disable the device buttons Version 23 07 08 Subject to modifications Page 8 of 20 LON UO Module DR N 8S 10A Application 8818011_01B 5 3 Lamp Actuator LONMARK profile 3040 Output A Index 0 to H Index 7 Lamp Actuator 3040 nviLAlampValue i SNVT_switch nvoLAlampValueFb i SNVT_switch nviLAmanOverride i SNVT_switch UCPTonDelay i UCPToffDelay i UCPTautoOffTime i UCPTrestartAutoOffTimer i UCPTbreakAutoOffTimer i UCPTlogicFunction i UCPTlaMaxRevTime i UCPTfeedbackDelay i UCPTdefaultLampValue i UCPTdefaultManOverrideSw i UCPTafterReleaseManOverride i UCPTrcvFailureLampValue i UCPTpowerFailureLampValue i T Input variables nviLAlampValue i Type Value range Default value Description SNVT_switch value 0 100 State O 1 ON state 1 and value gt 0 OFF state 0 or state 1 and value 0 UCPTdefaultLampValue i Control input for switching the output channels Schneider nviLAmanOverride i Type Value range
3. Description An update to nviLAlampValue i must be received within the time period defined here otherwise the output is set to the value defined in UCPTrevFailureLampValue i ucPTfeedbackDelay i Feedback delay Type UNVT_time_msec Value range 0 65 535 ms increment 1 ms Default value 0 deactivated Description The transmission of the feedback value via nvoLAlampValueFb i is delayed by the value specified here The time is restarted on every value status change ucPTdefaultLampValue i Default lamp value Type SNVT_switch Value range value 0 100 state 0 1 ON state 1 and value gt 0 OFF State 0 or state 1 and value 0 Default value value 0 state 0 Description The value adopted by nviLAlampValue i after the power supply is restored or after a restart This normally reflects the output value UCPTdefaultManOverrideSw i Default override control Type SNVT_switch Value range value 0 100 State 0 1 1 ON State 1 and value gt 0 OFF State 0 or state 1 and value 0 Deactivated state 1 Default value value 0 State 1 The value automatically adopted by the input after the bus voltage is restored or after a reset Description Version 23 07 08 Subject to modifications Page 12 of 20 LON UO Module DR N 8S 10A Schneider Application 8818011_01B Configuration variables UCPTafterReleaseManOverr
4. The LON I O Module DR N 8S 10A has eight independent potential free relay outputs for switching of lighting components and other SS electrical consumer loads The device requires a 24 V DC power supply for operation The potential free outputs switch 230 V AC 10 A DG 24v The general device state is displayed by a service and operation LED The application software conforms to the LonMark guidelines 3 Installation The LON I O Module DR N 8S 10A in a DIN rail housing is intended for installation on DIN top hat rails according to the EN 50 022 standard The power supply cables are connected via screw type terminals The plug terminals can be screwed onto the cables before installation of the device and then plugged in later The consumer cables are connected via screw type terminals All devices mounted next to the UO module must be equipped with basic insulation at a minimum The green RUN LED does not illuminate until the application program has been correctly loaded into the device Pressing the service button sends the Neuron ID of the device The Service LED shows the programming status An application program is required to operate the device A separate tool is needed to load the application into the device Warning Safety clearances according to DIN VDE 0110 Part 1 must be maintained A clearance of at least 4 mm must exist between individual 230 V conductors and the bus cables Version 23 07 08 Subject to modifi
5. deactivated Switch on delay of the output after arrival of an ON telegram at nviLAlampValue i UCPToffDelay i Switch off delay Type Value range Default value Description UNVT_time_sec 0 65 535 s increment 1 s 0 deactivated Switch off delay of the output after arrival of an OFF telegram at nviLAlampValue i UCPTautoOffTime i Automatic switch off time Type Value range Default value Description UNVT_time_sec 0 65 535 s increment 1 s 0 deactivated The output is automatically switched off without receiving an OFF telegram after this time has expired The time begins as soon as an ON telegram is received at nviLAlampValue i uUCPTrestartAutoOffTimer i Automatic switch off time extendable Type Value range Default value Description Version 23 07 08 UNVT_boolean TRUE FALSE TRUE Defines whether the automatic switch off time UCPTautoOffTime i is restarted on receipt of every ON telegram TRUE or not reset FALSE Subject to modifications Page 10 of 20 Schneider LON I O Module DR N 8S 10A Electric Application 8818011_01B Configuration variables UCPTbreakAutoOffTimer i Automatic switch off interruptible Type UNVT_boolean Value range TRUE FALSE Default value FALSE Description Defines whether the automatic switch off time UCPTautoOffTime i is interrupted on receipt of an OFF telegram TRUE or not FALSE UCPTlog
6. 18011_01B 5 4 Scene controller LONMARK profile 3251 SceneCirl 1 Index 0 to 2 Index 1 nviSCScene i SNVT_scene nviSCSwitch i SNVT_switch nviSCSetting i SNVT_setting I nviSCSceneOffset i SNVT_scene Scene Controller 3251 nvoSCSwitch i SNVT_switch nvoSCSetting i SNVT_setting nvoSCOccupancy i SNVT_occupancy UCPTsceneKeeperSwitch i 20 UCPTsceneKeeperSetting i 20 UCPTsceneKeeperOccupancy i 20 UCPTsceneKeeperFadeTime i 20 UCPTsceneKeeperDimStep i 20 UCPTsceneKeeperDlyTime i 20 w J Input variables nviSCScene i Type Value range Default value Description SNVT_scene function SC_RECALL SC_LEARN Scene number 1 20 function SC_NUL Scene number 255 Recalling SC_RECALL and storing SC_LEARN scenes There are 20 storage locations available In SC_RECALL mode the settings are transferred to the output variables according to the selected scene_number InSC_LEARN mode the current values of nviSCSwitch i are stored in the storage location specified by scene_number Fading and delay times for nvoSCSwitch i are taken from the current values in UCPTsceneKeeperFadeTime i and UCPTsceneKeeperDelayTime il nviSCSwitch i Type Value range Default value Description Version 23 07 08 SNVT_switch value 0 100 State 1 0 1 value 0 State 1 Direct setting of a value in nvoSCSwitch i Thi
7. COccupancy i The room scene storage can be configured in 2 different ways The scene storage can be directly written via the configuration parameter UCPTsceneKeeperXxXxX i Jj The lighting control scenes can be adopted in the scene storage via nviSCSwitch i when bound under the scene number specified in nviSCScene i scene_number This is initiated by setting nviSCScene i function SC_LEARN in general with a long button push The variables nviSCSetting i allow switching the scene controller on and off thus disabling its functions After switching off the outputs are set to the values for scene 20 After being switched on again the last active scene is recalled The cross fade behaviour of a scene change at output nvoSCSwitch i can be set using the configuration variables UCPTsceneKeeperFadeTime i UCPTsceneKeeperDimStep i and UCPTsceneKeeperDelayTime i Invalid entries in the scene storage lead to the associated network output not being propagated sent The input nviSCSceneOffset i whose input value is added to the received scene number is available to allow scene panels to be linked to each other Display and control elements at the front of the device The RUN LED displays the operating status After a restart and in the configured online state the RUN LED illuminates If the node is placed offline then the LED switches off The Service LED shows the state of the LON node If it continuously illuminates then no va
8. Schneider LON I O Module DR N 8S 10A Electric Art no MTN881801 User Manual LON I O Module DR N 8S 10A Art no MTN881801 Directory IRC en EE 1 1 RT oli ea E 2 2 EE 3 3 Installato eee a E AEEA EEEE NE AETR AEREE E TEA 3 4 Technical EE 5 5 Applicaton E le ul TEE 6 5 1 System requirements A 7 5 2 Node object LONMARK profile D 8 5 3 Lamp Actuator LONMARK profile 22040 9 5 4 Scene controller LONMARK profile Map 14 5 5 GlobalControl LONMARK profile Sp 18 Version 23 07 08 Subject to modifications Page 1 of 20 Schneider LON I O Module DR N 8S 10A Electric Art no MTN881801 1 Description All connections are pluggable including the bus connection e Independent switching of eight load groups e Eight relay outputs NO 10 A Manual operation and status indication per output e Power down detection e Supply voltage DC 24 V Pluggable screw type terminals Device width approx 72 mm 4 pitch e DIN rail mounting according to EN 50 022 Software application for control of eight independent consumer loads according to the LonMark profile Lamp Actuator 3040 with timers prioritised control logic operation configurable reaction of the outputs to power up bus reset and two Scene Controller 3251 objects Version 23 07 08 Subject to modifications Page 2 of 20 Schneider LON I O Module DR N 8S 10A Electric Art no MTN881801 2 Function
9. by specifying 0 for the appropriate channel The delay UCPTmaxRandomDelay has no effect here Subject to modifications Page 18 of 20 LON UO Module DR N 8S 10A Schneider Application 8818011_01B Output variables nvoGCdeviceState Type SNVT_state Value angel bm bit8 0 1 reflects channel A D Default value All bits 0 Description This output reflects the status of the individual module channels Configuration parameters uCcPTsceneKeeperChannelSw8 Type UNVT_skc_8 Value range scene 1 2 255 priority 0 1 channel j SW NUL SW_HOLD GW OFF GW ON Default value scene i 1 priority 0 Channel GW OEF Description Storage for controlling the individual actuator channels with the following functions scene Received scene number priority Priority in relation to the input at the Lamp Actuator object 1 affects nviLAmanOverride 0 affects nviLAlampValue channel j SW_NUL Release nviLAmanOverride at priority 1 DW HOLD Retain existing channel state SW_OFF Channel OFF DW ON Channel ON UCPToccToScene Type UNVT_os_ scene Value range oc_occupied 1 2 255 oc_unoccupied 1 2 255 oc_standby 1 2 255 oc_bypass 1 2 255 oc_nul 1 2 255 Default value oc_occupied 1 oc_unoccupied 2 oc_standby 3 oc_bypass 4 OC DU 5 Description Version 23 07 08 Assignment of the occupancy state to a scene Subject to modifications Page 19 of 20 Schn
10. cations Page 3 of 20 Schneider LON I O Module DR N 8S 10A Electric Art no MTN881801 gt 4mm Cc Danger to life due to electric current Even when the manual switch is in the OFF position a BUS telegram can switch power to the connections at any time Always deactivate remove the upstream fuses before working on the device Output connections Danger to life due to electric current Vibration during transport can switch on the outputs Voltage may appear at the outputs when mains voltage is applied To switch off outputs After commissioning use bus telegrams to perform a switching cycle on off or set the manual switch to OFF reer Warning Switching actuators might be damaged Secure the switching contacts with an upstream 10 A circuit breaker Connect the device according to the connection example The consumer cables and the mains voltage L1 L2 or L3 are connected using screw terminals rated to a maximum of 10 A Notes Installation and mounting of electrical devices may only be done by a skilled electrician When planning and installing electrical equipment the applicable norms guidelines rules and regulations for the respective country are to be followed Beyond this the device specifications are also to be followed Detailed specialised knowledge of LON technology is a prerequisite for project work installation and commissioning The functioning of the device is software depende
11. ed If no telegram is received within the time defined in UCPTlaMaxRcvTime i then the associated channel is switched to the value defined in UCPTrcvFailureLampValue i Telegrams to prioritised inputs nviLAManOverride i directly switch the associated outputs without delays To release the output once more the state Se of the associated nviLAManOverride i variable must be set to 1 The output then switches to the value defined in UCPTafterReleaseManOverride i Alternatively the input nviLAManOverride i can be used as a logically linked input to nviLALampValue i The desired logical linking is defined in the parameter UCPTlogicFunction i Version 23 07 08 Subject to modifications Page 6 of 20 Schneider LON I O Module DR N 8S 10A Electric Application 8818011_01B The feedback value of the output is sent to nvoLALampValueFb i with the delay time specified in UCPTfeedbackDelay i it can also be cyclically sent in the time period specified in SCPTmaxSendTime i Working with scenes The room scene controller can store complex room scenes defining lighting values occupancy states and positional information for blinds Up to 20 different room scenes can be stored After switching on the scene controller via nviSCSetting i SET_ON the stored scheme can be called up based on the scene number by setting nviSCScene i function SC_RECALL and then output using nvoSCSwitch i nvoSCSetting i and nvoS
12. eider LON I O Module DR N 8S 10A Electric Application 8818011_01B Configuration parameters UcPTdirectInputMask Type SNVT_state Value range bm bit8 0 1 reflects channel A D Default value All bits 1 Description Parameter for hiding actuator channels from the central control via nviGCdirectInput bitx 0 means that the associated channel is not taken into account UcPTmaxRandomDelay Type Value range Default value Description Version 23 07 08 SNVT_time_sec 0 6 553 5 s increment 1 s 0 deactivated When an actuator is controlled via nviGCscene or nviGCoccupancy this maximum value is used to generate a random time that delays the activation of the scene values This helps to avoid current peaks in the central control system The delay time also affects switch on delays on restoration of power or after a reset but is limited to a maximum value of 64 s Reception of a new telegram at one of the two inputs starts the delay anew Subject to modifications Page 20 of 20
13. eperSetting i j Version 23 07 08 Subject to modifications Page 15 of 20 LON UO Module DR N 8S 10A Schneider Application 8818011_01B nvoSCOccupancy i Type Value range Default value Description SNVT_occupancy OC_OCCUPIED OC_UNOCCUPIED OC_BYPASS OC_STANDBY OC_NUL OC_NUL Output of the active scene value configured in UCPTsceneKeeperOccupancy i Jj Configuration parameters UCPTsceneKeeperSwitch i j Scene storage for nvoSCSwitch i Type Value range Default value Description UNVT_switch_cfg function SW_NUL SW_HOLD SW_VALUE value 0 100 function SW_HOLD value 0 Configuration of the scene values for nvoSCSwitch i SW_NUL nvoSCSwitch i value is adopted from value nvoSCSwitch i state is set to 1 SW_VALUE nvoSCSwitch i value is adopted from value nvoSCSwitch i state is setto 1 when value gt 0 and set to 0 when value 0 SW_HOLD no telegram is generated UCPTsceneKeeperSetting i j Scene storage for nvoSCSetting i Type Value range Default value Description UNVT_setting function SET_OFF GET ON SET_DOWN GET Up SET_STOP SET_STATE SET_NO_MESAGE SET_NUL setting 0 100 rotation 359 98 360 function GET NO MESSAGE setting 0 rotation 0 Configuration of the scene values for nvoSCSetting i Ifa value with function GET NO MESSAGE is stored here then the value is not propagated UCPT
14. h actuator channel The priority of the individual scenes with regard to the Lamp Actuator inputs nviLAlampValue and nviLAmanOverride can be adjusted For temporal correction of central switching commands the activation of the requested scenes can be parameterised with a configurable random period UCPTmaxRandomDelay The variable nviGCoccupancy refers to the internal scene storage in a similar manner to nviGCscene Assignment of the input values SNVT_occupancy to the scene numbers is done in the parameter UCPToccToScene The stored scenes for the actuator channels are switched according to the building state e g Occupied Standby etc All actuator channels can be controlled at lower priority or without delays using nviGCdirectInput SNVT_state Switching consumers Switch on off delays and automatic switch offs stairwell function can be parameterised in every lamp actuator object The reaction to different power supply events loss of power power switch on restart is configurable It is also possible to define group control membership The behaviour of the actuators after a restart is definable using the variables UCPTdefaultLampValue i The input nviLALampValue i switches the corresponding output at low priority The temporal behaviour of the output can be defined using the variables UCPTonDelay i switch on delay UCPToffDelay i switch off delay and UCPTautoOffTime i stairwell automation This input can be monitor
15. icFunction i Logic function Type UNVT_logic_fne Value range LF_OVERRIDE LF_AND LE Op LF_XOR LF_NAND LF_NOR LF_NXOR Default value LF_OVERRIDE Description This parameter can be used to define a logical linking of the inputs nviLAlampValue i and nviLAmanOverride i according to the truth table below The following assignments apply 1 On state 1and value gt 0 0 Off state Oor state 1 and value 0 1 invalid state 1 DLV Value defined in the UCPTdefaultLampValue i IDLV UCPTdefaultLampValue i inverted DMO Value defined in UCcPTdefaultManOverrideSw i IDMO UCcPTdefaultManOverrideSw i inverted nviLAlampValue i nviLAmanOverride i AND OR XOR NAND NOR NXOR 0 0 0 0 0 1 1 1 0 1 0 1 1 1 0 0 1 0 0 1 1 1 0 0 1 1 1 1 0 0 0 1 0 1 0 DMO 1 1 IDMO 0 1 1 DMO 1 1 IDMO 0 0 1 0 0 DLV 1 1 IDLV 0 1 1 DLV 1 1 IDLV 0 0 1 1 0 DLV 0 1 IDLV 1 The temporal behaviour of the outputs is not affected by the logical linking but is parameterised according to the result of the linking Under standard parameterisation LF_OVERRIDE nviLAmanOverride i is prioritised with regard to nviLAlampValue il Version 23 07 08 Subject to modifications Page 11 of 20 Schneider LON UO Module DR N 8S 10A Application 8818011_01B Configuration variables SCPTlaMaxRcvTime i Maximum reception pause Type SNVT_time_sec Value range 0 6 553 5 s increment 0 1 s Default value 0 deactivated
16. ide i Default manual override release Type Value range Default value Description UNVT_switch_cfg function SW_NUL SW_HOLD SW_VALUE value 0 100 function SW_NUL value 0 The value adopted by the output after nviLAmanOverride i is released SW_NUL Current value of the nviLAlampValue i input is adopted SW_HOLD Current value of the actuator channel is retained SW_VALUE The actuator channel adopts the value parameterised in value UCPTrcvFailureLampValue i Lamp value in case of reception failure Type Value range Default value Description SNVT_ switch value 0 100 State 0 1 1 ON state 1 and value gt 0 OFF State 0 or state 1 and value 0 Deactivated state 1 value 0 state 1 The value adopted by the output after the time specified in SCPTlaMaxRcvTime i has expired If state 1 the output is not changed UCPTpowerFailureLampValue i Lamp value in case of power failure Type Value range Default value Description Version 23 07 08 SNVT_ switch value 0 100 State 0 1 1 ON state 1 and value gt 0 OFF State 0 or state 1 and value 0 Deactivated state 1 value 0 state 1 Value adopted by the output when the power fails If state 1 the output is not changed Subject to modifications Page 13 of 20 Schneider LON I O Module DR N 8S 10A Electric Application 88
17. lid application is loaded into the node If it blinks then the device is not configured A blink task also exists When this is activated the RUN LED blinks for about 20 s The outputs can be directly switched using the manual buttons on the upper side of the device with a loaded application they show the status of the outputs 5 1 System requirements An LNS compatible LON management tool is required for the configuration of the application User defined configuration property types UCPTs are used as parameters in the DirectMemoryAccess To be able to use these parameters the Device Resource Files DRFs need to be installed before creating a device template The used LNS must be Version 2 0 or higher Version 23 07 08 Subject to modifications Page 7 of 20 LON I O Module DR N 8S 10A Application 8818011_01B Network interface LonMark objects 5 2 Node object LONMARK profile 0 Node Object 0 nviRequest nvoStatus SNVT_obj_request SNVT_obj_status nvo00FileDir SNVT_address UCPTdeviceButton Ke Input variables nviRequest Type SNVT_obj_request Value range Valid object ID in combination with RQ_NORMAL RQ_UPDATE_STATUS RQ_REPORT_MASK RQ_NORMAL Input used to initiate the node status messages Default value Description Output variables Schneider nvoStatus Type SNVT_obj_ status Value range The status bits supported by the object report_mask invalid_id
18. n terminals 2 pole for connection to 4 conductor pairs 68 x 72 x 90 mm H x W x D 4 pitch according to DIN 43 880 IP20 EN 60 529 IEC 144 according to EN 50 090 2 2 Subject to modifications Page 5 of 20 Schneider LON I O Module DR N 8S 10A Electric Application 8818011_01B 5 Application description The application 8818011_01A is used for controlling eight independent consumers connected to the relay outputs of the LON I O Module DR N 8S 10A It reflects the LonMark profiles Lamp Actuator 3040 8x and Scene Controller 3251 2x In addition to the functions specified in these profiles the application also allows timer functions for every switched output and controlling using different priorities The Global Control object allows a definable group of outputs to be switched on and off together The current status of the outputs is displayed above the corresponding switch positions on the upper side of the housing Function Central control and visualisation The Global Control allows actuator channels to be switched by a central binding The Global Control affects the actuator channels through internal bindings This allows implementation of group switching or lighting effects The Global Control object also shows the status of the outputs to be displayed via an output variable nvoGCdeviceState At the nviGCscene input freely definable scenes can be called up that define a separate switching value for eac
19. nt The installer has the responsibility of ensuring that the loaded application programs and the parameters defined within this agree with the external connections of the device This applies especially to situations where several application programs for different applications are available for the device Version 23 07 08 Subject to modifications Page 4 of 20 LON UO Module DR N 8S 10A Art no MTN881801 4 Technical data Power supply Operating voltage Current consumption Bus connection Transceiver type Outputs Number Type Rated voltage max Load current Operating elements Service button Manual control buttons 1 8 Display elements RUN LED Service LED Connections Power supply outputs Bus Housing Dimensions Type of protection ENC specification Noise immunity Version 23 07 08 Schneider 24 V DC 10 max 30 mA LON Free Topology Transceiver TP FT 10 Via pluggable bus connection terminals 8 Relays NO potential free 230 V AC 50 to 60 Hz 10A Sends the Neuron ID Pressing the service button during a hardware reset places the device in the unconfigured state Manual switching of the outputs ON Device is working normally OFF No application loaded no voltage OFF Device is working normally BLINKING Device is unconfigured ON Device has no application loaded Pluggable screw type terminals for cross sections of 1 5 2 5 mm Standard bus connectio
20. s allows manual entry of scene values Subject to modifications Page 14 of 20 LON I O Module DR N 8S 10A Schneider Application 8818011_01B Input variables nviSCSetting i Type Value range Default value Description SNVT_setting function GET OFF GET ON function GET ON Setting 0 rotation 0 Variable for switching the controller on SET_ON and off SET_OFF After switching on the last selected scene is active After switching off scene 20 is active Repeated reception of SET_ON has no effect nviSCSceneOffset i Type Value range Default value Description Output variables SNVT_scene function SC_RECALL Scene number 1 20 function SC_RECALL scene_number 255 The value stored at scene_number is added to the scene_number values of nviSCScene i For invalid values addition of both scene numbers gt 20 a value of 0 is assumed nvoSCSwitch i Type SNVT_switch Value range value 0 100 State 1 0 1 Default value value 0 State 1 Description Output of the active scene value configured in UCPTsceneKeeperSwitch i j nvoSCSetting i Type SNVT_setting Value range function SET_OFF GET ON SET_DOWN GET Up SET_STOP SET_STATE Default value Description SET_NUL setting 0 100 rotation 359 98 360 function SET NUL setting 0 rotation 0 Output of the active scene value configured in UCPTsceneKe
21. sceneKeeperOccupancy i j Scene storage for nvoSCOccupancy i Type Value range Default value Description SNVT_occupancy OC_OCCUPIED OC_UNOCCUPIED OC_BYPASS OC_STANDBY OC_NUL OC_NUL Configuration of the individual scene values If a value of OC_NUL is stored here then the value is not propagated UCPTsceneKeeperFadeTime i j3 Scene storage cross fade time for nvoSCSwitch i Type Value range Default value Description Version 23 07 08 UNVT_time_msec 100 65 535 ms 0 deactivated Cross fade time for scene change to nvoSCSwitch i Subject to modifications Page 16 of 20 Schneider LON I O Module DR N 8S 10A Electric Application 8818011_01B UCPTsceneKeeperDimStep i j Scene storage dimming step size for nvoSCSwitch i Type SNVT_lev_cont Value range 0O 100 Default value 3 5 Description Step size of the cross fade for a scene change to nvoSCSwitch i UCPTsceneKeeperDelayTime i j Scene storage delayed scene change for nvoSCSwitch i Type SNVT_time_sec Value range 0 6 553 4 s Default value 0 Description Delay time for activating the new scene at nvoSCSwitch i Version 23 07 08 Subject to modifications Page 17 of 20 LON UO Module DR N 8S 10A Schneider Application 8818011_01B 5 5 GlobalControl LONMARK profile 5 GlobalControl 5 nviGCscene SNVT_scene nvoGCdeviceState SNVT_state nviGCoccpancy SNVT_occupanc
22. y nviGCdirectInput SNVT_state UCPTsceneKeeperChannelSw8 UCPToccToScene UCPTdirectInputMask UCPTmaxRandomDelay T Input variables nviGCscene Type Value range Default value SNVT_scene function SC_RECALL Scene number 1 10 function SC_NUL Scene number 255 Description Input for central activation deactivation of functions ON OFF of the individual actuator channels UCPTmaxRandomDelay can be used to define a device specific random delay to avoid load peaks in the central control system nviGCoccupancy Type SNVT_occupancy Value range OC OCCUPIED OC_UNOCCUPIED OC_BYPASS OC_STANDBY OC_NUL Default value OC NUL Description Input to the central presence absence controller The states to be activated are defined in an assignment table UCPToccToScene that maps the values received here to the specified scene numbers On arrival of a telegram the scene entered for the corresponding occupancy state is called up UCPTmaxRandomDelay can be used to define a device specific random delay to avoid load peaks in the central control system nviGCdirectInput Type SNVT_state Value angel bm bit8 0 1 reflects channel A D Default value All bits 0 Description Input variable for direct control of the actuator channels using a priority according to Version 23 07 08 nviLAlampValue Channels that should not be controlled via this variable can be hidden using UCPTdirect InputMask

Download Pdf Manuals

image

Related Search

Related Contents

Philips 22PFL4008K 22" Full HD Black  JVC AA V15U User's Manual  DeLOCK 41836 slot expander    DaqBook User`s Manual - Artisan Technology Group  manutenzione del verde urbano capitolato speciale d`appalto  LCD-Bildschirm - Bedienungsanleitung  「ハイトシェルターS」取扱説明書  NCM45x0-2 Network Control Module Commissioning Guide  Générateur de fonctions/signaux arbitraires 20 MHz Agilent 33220A  