Home

CC-Link IE Controller Network Module User`s Manual (Hardware)

image

Contents

1. ceceeecceceeeseeeceeeeeeeeeeseeeeeeesaeeeseeatees 1 3 MOUNTING AND INSTALLATION in 4 3 1 Handling Precautions 2245 inner lent 4 3 2 Installation Environment suiiissasenansenenteeh itenstantt 4 4 PART NAMES 5 WIRING 5 1 Connecting Optical Fiber Cables 8 5 2 Wiring Pr cautions 22 ee rece Se etre are eme deren 9 6 EXTERNAL DIMENSIONS inner 10 BT GT GP SA nt eae E ane nu 10 6 2 QJ71GP21S SX A 6 Manuals The following table lists the manual on this product You can order it as necessary Relevant Manual Manual name Manual No Model code i SH 080668ENG CC Link IE Controller Network Reference Manual 13JV16 Compliance with the EMC and Low Voltage Directives 1 For programmable controller system To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller EMC and Low Voltage Directives compliant into other machinery or equipment refer to Chapter 9 EMC AND LOW VOLTAGE DIRECTIVES of the QCPU User s Manual Hardware Design Maintenance and Inspection The CE mark indicating compliance with the EMC and Low Voltage Directives is printed on the rating plate of the programmable controller 2 For the product No additional measures are necessary for the compliance of this product with the EMC and Low Voltage Directives A 7 1 OVERVIEW This manual explains how to install and connect the
2. M3 R1 25 3 2 No external power supply 0 3 to 1 25mm function 0 42 to O 58N m ims Level PS1 By noise simulator of 500Vp p noise voltage 1 Us noise width and 25 to 60Hz noise frequency Internal current consumption 5V DC Table 2 1 Performance specifications Continued Specification QJ71GP21 SX QJ71GP21S SX 0 85A 0 90A External dimensions 98 H x 27 4 W x 90 D mm 98 H x 55 2 W x 90 D mm Weight 0 18kg 0 28kg 1 2 3 4 A Universal model QCPU can be set to a station No within the range of No 1 to No 120 For a module other than Universal model QCPUs station No 1 to No 64 can be set A station with a Basic model QCPU or safety CPU operates as a normal station It cannot be set to a control station All I O signals of the CC Link IE controller network module are used by the system Use prohibited Two I O slots are occupied In the Start I O No field of Network parameters set a value obtained by adding 10H to the I O No of the module installed slot Note that 0 point can be set instead of 16 points for the first half in 1 0 assignment of Network parameters Example When the module is installed to slot 0 set 10H to Start I O No When 0 point is set to slot 0 in I O assignment set OH to Start I O No 3 MOUNTING AND INSTALLATION 3 1 Handling Precautions This section describes precautions for handling the CC Link I
3. save this manual to make it accessible when required and always forward it to the end user A 1 DESIGN PRECAUTIONS DANGER For each station s operating status in the case of a communication error in the network refer to CC Link IE Controller Network Reference Manual A malfunction due to a communication error may result in an accident To control a running programmable controller data modification by connecting GX Developer to a CPU module or connecting a personal computer to an intelligent function module create an interlock circuit on the sequence program so that the entire system will function safely all the time Also before performing any other controls e g program modification operating status change status control to the programmable controller read the manual carefully and ensure the safety Especially in the case of controlling a remotely located programmable controller from an external device a programmable controller side problem could not be resolved immediately due to data communication failure To prevent this establish corrective procedures for communication failure between the external device and the programmable controller CPU as well as creating an interlock circuit on the program Laser diodes are used in the optical transceivers of the CC Link IE controller network The class of these laser diodes is Class 1 A CAUTION Do not install the control lines and or communication cables to
4. 2IS SX EXT PW A 98 3 86 au7iGP215 8X ns co j r 90 3 54 r 0 43 55 2 2 17 Unit mm inch Figure 6 2 External dimensions Ethernet is a trademark of Xerox Co Ltd in the United States Other company names and product names used in this document are trademarks or registered trademarks of respective owners Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties A For safe use This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system Country Region Sales office Tel Country Region Sales office Tel U S A Mitsub
5. 71GP21S SX When Universal model QCPU is used for control station 120 Control station 1 Normal station 119 i When any other than Universal model QCPU is used for control station 64 Control station 1 Normal station 63 a Connection cable Optical fiber cable Multi mode fiber 3 gt CC Link IE Controller Network Reference Manual Overall cable distance 66000m When 120 stations are connected Station to station distance Max 550m Core Clad 50 125 m Max number of networks 239 Max number of groups 32 Transmission path Duplex loop Optical fiber 1000BASE SX MMF optical fiber cable specifications Standard IEC60793 2 10 Types A1a 1 50 125 m multimode Transmission loss max 3 5 dB km or less 850nm Transmission L band min 500 MHz km or more 850nm Connector specifications Duplex LC connector Standard IEC61754 20 Type LC connector Connection 0 3 dB or less loss Polished A sas surface PC Physical Contact polishing Number of occupied 1 0 points 7 48 I O assignment Empty first 32 Intelli 32 points 3 half 16 points Latter half 32 points for intelli a4 Voltage Current Terminal screw size Applicable solderless terminal External Applicable power wire size sic raion Allowable momentary power failure time Noise immunity 20 4V to 31 2V DC 0 28A
6. E controller network module itself 1 Since the module case is made of resin do not drop the module or apply a strong impact to it 2 Do not remove the printed circuit board of the module from the case Doing so will cause failure 3 Be careful to prevent foreign matter such as dust or wire chips from entering the module Failure to do so may cause a fire failure or malfunction 4 A protective film is attached to the module top to prevent foreign matter such as wire chips from entering the module during wiring Do not remove the film during wiring Be sure to remove it for heat dissipation before system operation 5 Before handling the module touch a grounded metal object to discharge the static electricity from the human body Not doing so may cause a failure or malfunction of the module 6 Tighten the module fixing screws or terminal screws within the following torque range Table 3 1 Screw tightening torque Tightening torque range Module fixing screw M3 screw 0 36 to 0 48N m Terminal screw on external power supply terminal block M3 screw 1 The module can be easily fixed onto the base unit using the hook at the top 0 42 to 0 58Nem of the module However it is recommended to secure the module with the module fixing screw if the module is subject to significant vibration or shock 3 2 Installation Environment For details refer to the user s manual for the CPU module used 4 PART NAM
7. ES This section explains the names of each part of the CC Link IE controller network module QJ71GP21 SX QJ71GP21S SX TET ex Pw lt 2 4 3 Figure 4 1 CC Link IE controller network module appearance Table 4 1 Names of parts Description Indicates the operating status of the CC Link IE controller network module 7377 1 in this section Used to connect an optical fiber cable to the CC Link IE controller network module The cable is connected to OUT connector of another station I 3 in this section Used to connect an optical fiber cable to the CC Link IE controller network module The cable is connected to IN connector of another station 23 3 in this section External power Connects a cable for supplying external power to the CC Link supply terminal block IE controller network module Indicator LED IN connector OUT connector 1 Indicator LEDs QJ71GP21 SX QJ71GP21S SX QJ71GP21 SX RUN PRM Oz MODE D LINK so RD ERR x100 10 1 QJ71GP21S SX rN move sO ERR PRM Oza D LINK ext pw RD x100 10 1 LED status ON green Figure 4 2 Indicator LEDs Table 4 2 LED indication Description Operating normally OFF Hardware fault or watc
8. MITSUBISHI CC Link IE Controller Network Module User s Manual Hardware QJ71GP21 SX QJ71GP21S SX Thank you for purchasing the Mitsubishi programmable controller MELSEC Q series Prior to use please read this and relevant manuals thorougly to fully understand the product MODEL QJ71GP21 SX U HW MODEL ee US CODE 13JY13 Controller IB NA 0800364 D 0804 MEE 2007 MITSUBISHI ELECTRIC CORPORATION SAFETY PRECAUTIONS Be sure to read these instructions before use Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The instructions given in this manual are concerned with this product For the safety instructions of the programmable controller system please read the CPU module user s manual In this manual the safety instructions are ranked as DANGER and CAUTION Indicates that incorrect handling may cause i a DANGER hazardous conditions resulting in death or severe 1 I injury l Indicates that incorrect handling may cause I I I I A CAUTION hazardous conditions resulting in minor or moderate injury or property damage Note that the A CAUTION level may lead to a serious consequence according to the circumstances Always follow the instructions of both levels because they are important to personal safety Please
9. QJ71GP21 SX or QJ71GP21S SX CC Link IE controller network module hereinafter referred to as CC Link IE controller network module Packing list Table 1 1 Packing list Quantity QJ71GP21 SX QJ71GP21 SX CC Link IE controller network module QJ71GP21S SX CC Link IE controller network module with external power supply function QJ71GP21S SX 2 PERFORAMNCE SPECIFICATIONS The following describes the performance specifications of the CC Link IE controller network module For general specifications of the CC Link IE controller network module refer to the following manual 7 QCPU User s Manual Hardware Design Maintenance and Inspection Table 2 1 Performance specifications Specification QJ71GP21 SX QJ71GP21S SX 32K points 32768 points 4KB Basic model QCPU or safety CPU 16K points 16384 points 2KB Max link points 128K points 131072 points 256KB f f i LW Basic model QCPU or safety CPU 16K points 16384 points per network 32KB LX 8K points 8192 points 1KB LY 8K points 8192 points 1KB LB 16K points 16384 points 2KB Max link points 16K points 16384 points 32KB per station LX 8K points 8192 points 1KB LY 8K points 8192 points 1KB LB Transient transmission Up to 1920 bytes capacity Communication speed 1Gbps Table 2 1 Performance specifications Continued Specification Number of stations per networl QJ71GP21 SX QJ
10. able Disconnection Turn the power OFF 4 Press the connector hook to disconnect the cable Completed CC Link IE controller network module lt Cable side connector i Connector hook Module side connector Figure 5 3 Disconnecting the optical fiber cable 8 5 2 Wiring Precautions a b c d e Use the optical fiber cable described in the following manual lt gt CC Link IE Controller Network Reference Manual There are restrictions on the bending radius of the optical fiber cable For details check the specifications of the cable to be used When handling an optical fiber cable do not touch the optical fiber core of the cable side or module side connector and protect it from dirt or dust If oil from your hand dirt or dust is attached to the core it can increase transmission loss arising a problem in data link When connecting or disconnecting an optical fiber cable hold the connector part of the cable Make a full connection between the cable side and module side connectors until a click can be heard 6 EXTERNAL DIMENSIONS 6 1 QJ71GP21 SX QJ71GP21 SX z RUN pau T MODE D LINK ER 100101 amp oO g oo n 4 fe OUT i curiaeet st 90 3 54 4 5 0 18 27 4 1 08 t k gt Unit mm inch Figure 6 1 External dimensions 10 6 2 QJ71GP21S SX QUTIGP
11. ation No of the CC Link IE controller network module is indicated Example When indicating station No 15 1 1 4 X100 10 10 5 15 Figure 4 3 Example of station No setting indication 3 IN and OUT connectors IN Forward loop receiving IN Reverse loop sending OUT Reverse loop receiving OUT Forward loop sending OVO IOLO Figure 4 4 IN and OUT connectors 5 WIRING 5 1 Connecting Optical Fiber Cables 1 Connection method Connect an optical fiber below cable between OUT and IN as shown Note that there is no need to connect the cables in the order of station numbers CC Link IE controller network module Normal station Station No 2 Control station Normal Station Figure 5 1 Connection method 2 Connecting the optical fiber cable Connection Turn the power OFF 4 Connect the cable side connector to the module side connector paying attention to the orientation Push it until a click is heard Lightly pull it to check that it is securely connected Completed CC Link IE controller network module Module side connector K AIl N Cable side connector Connector hook Figure 5 2 Connecting the optical fiber cable 3 Disconnecting the optical fiber c
12. el 39 039 60531 F Spain Mitsubishi Electric Europe B V Spanish Ar annayao Gangtok 10230 Thailand Branch Carretera de Rubi 76 80 E 08190 Sant Cugat del Valles Bang Chan Industrial Estate No 111 Indonesia P T Autoteknindo Sumber Makmur Muara Karang Selatan Block A Utara No 1 Kav No 11 Kawasan Industri Barcelona Spain Per rgudangan Jakarta Utara 14440 Tel 34 93 565 3131 P O Box 5045 Jakarta 11050 Indonesia France Mitsubishi Electric Europe B V French Tel 62 21 6630833 Branch i 5 India Messung Systems Pvt Ltd 25 Boulevard des Bouvets F 92741 Electronic Sadan NO III Unit No15 Nanterre Cedex France M I D C Bhosari Pune 411026 India i TEL 33 1 5568 5568 Tel 91 20 2712 3130 South Africa Circuit Breaker Industries Ltd Australia Mitsubishi Electric Australia Pty Ltd Private Bag 2016 ZA 1600 Isando 348 Victoria Road Rydalmere South Africa N S W 2116 Australia Tel 27 11 928 2000 Tel 61 2 9684 7777 2 MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN When exported from Japan this manual does not require application to the Mi of Economy Trade and Industry for service transaction permission Specifications subject to change without notice Printed in Japan on recycled paper
13. gether with the main circuit or power cables and also do not bring them close to each other Keep a distance of 100mm 3 94 inch or more between them Failure to do so may cause a malfunction due to noise A 2 INSTALLATION PRECAUTIONS A CAUTION Use the programmable controller in the environment conditions given in the general specifications of the User s Manual for the CPU module used Failure to do so may cause an electric shock fire malfunction or damage to or deterioration of the product While pressing the installation lever located at the bottom of the module insert the module fixing projection into the fixing hole in the base unit to mount the module Incorrect module mounting may cause a malfunction failure or drop of the module In an environment of frequent vibrations secure the module with the screw The screw must be tightened within the specified torque range If the screw is too loose it may cause a drop short circuit or malfunction Excessive tightening may damage the screw and or the module resulting in a drop short circuit or malfunction Be sure to shut off all phases of the external power supply used by the system before mounting or removing the module Failure to do so may damage the module Do not directly touch any conductive part or electronic component of the module Doing so may cause a malfunction or failure of the module WIRING PRECAUTIONS DANGER Be sure to s
14. hdog timer error ON green Online mode Flashing green Test mode OFF Offline mode ON green Operating as a Control station OFF Operating as a Normal station ON green Data link in operation Cyclic transmission operated Flashing green Data link in operation Cyclic transmission stopped OFF Data link not in operation Disconnected from network Received data are erroneous Receive frame error A frame error above a certain level has occurred between stations The Control station or a station number is duplicated Cable disconnection or incorrect cable connection between OUT and IN Network parameters are corrupted or some settings Reserved station specification Total number of stations Network No etc are inconsistent between the Control and Normal stations OFF Normal status N green Sending data OFF Not sending data ON green Receiving data OFF Not receiving data 1x 100 1 2 4 8 x 10 1 2 4 8x1 ON green Numeric display The station No is set 777 2 in this section OFF No station No is set EXT PW 1 OFF ON green External power supplied Own station power status SB0042 is ON OFF External power not supplied Own station power status SB0042 is OFF When the CPU module is reset the LEDs other than the EXT PW LED turn 2 Station No setting St
15. hut off all phases of the external power supply before installation or wiring Failure to do so may result in an electric shock or damage to the product A 3 WIRING PRECAUTIONS A CAUTION Always ground the FG terminal to the protective ground conductor Failure to do so may cause a malfunction Verify the rated voltage and pin out and connect the external power supply cable properly Connecting a power supply with a different voltage rating or faulty wiring may cause a fire or failure Terminal screws must be tightened with the specified torque If a screw is loose it may cause a short circuit fire or malfunction Be careful to prevent foreign matter such as dust or wire chips from entering the module Failure to do so may cause a fire failure or malfunction Be sure to place the communication cables or power cables in a duct or clamp them If not dangling cables may swing or inadvertently be pulled resulting in damage to the module or cables or malfunctions due to poor cable connection When disconnecting a communication cable or a power cable from the module do not pull the cable part For a cable with connectors hold the connector by hand and disconnect it from the module For a cable connected to a terminal block loosen the terminal block screws and disconnect the cable from the module Pulling a cable that is still connected to the module may cause a malfunction or damage the module and or the cab
16. ishi Electric Automation Inc Hong Kong Mitsubishi Electric Automation 500 Corporate Woods Parkway Vernon Hong Kong Ltd Hills IL 60061 U S A 10th Floor Manulife Tower 169 Electric Tel 1 847 478 2100 Road North Point Hong Kong Brazil MELCO TEC Rep Com e Assessoria Tel 852 2887 8870 Tecnica Ltda China Mitsubishi Electric Automation Rua Correia Dias 184 Shanghai Ltd Edificio Paraiso Trade Center 8 andar 4 F Zhi Fu Plazz No 80 Xin Chang Road Paraiso Sao Paulo SP Brazil Shanghai 200003 China Tel 55 11 5908 8331 Tel 86 21 6120 0808 Germany Mitsubishi Electric Europe B V German Taiwan Setsuyo Enterprise Co Ltd Branch 6F No 105 Wu Kung 3rd Rd Wu Ku Gothaer Strasse 8 D 40880 Ratingen Hsiang Taipei Hsine Taiwan GERMANY Tel 886 2 2299 2499 Tel 49 2102 486 0 Korea Mitsubishi Electric Automation Korea Co Ltd UK Mitsubishi Electric Europe B V UK 1480 6 Gayang dong Gangseo ku Branch Seoul 157 200 Korea Travellers Lane Hatfield Hertfordshire A Tel 82 2 3660 9552 AL10 8XB U K Singapore Mitsubishi Electric Asia Pte Ltd Tel 44 1707 276100 307 Alexandra Road 05 01 02 Mitsubishi itsubishi ii i Electric Building Singapore 159943 Italy Mreubishi Electric Europe B V Italian Tel 65 6470 2460 Centro Dir Colleoni Pal Perseo Ingr 2 Thailand Mitsubishi Electric Automation Thailand 20041 i Co Ltd Via Paracelso 12 1 20041 Agrate Brianza Milano Italy Moo 4 Serithai Rd T Kannayao T
17. le A protective film is attached to the module top to prevent foreign matter such as wire chips from entering the module during wiring Do not remove the film during wiring Be sure to remove it for heat dissipation before system operation A 4 Revisions The manual number is given on the bottom right of the cover Print Date Manual Number Jan 2007 IB NA 0800364 A Revision First edition Apr 2007 IB NA 0800364 B Model added QJ71GP21S SX Partially revised SAFETY PRECAUTIONS Chapter 1 and 2 Section 3 1 Chapter 4 Section 5 1 Chapter 6 Added Section 6 2 Jan 2008 IB NA 0800364 C The entire manual was reviewed since the existing MELSECNET G network module has been integrated into the CC Link IE controller network module Partially revised Section 5 1 Apr 2008 IB NA 0800364 D Partially revised Compliance with The EMC and Low Voltage Directives Chapter 2 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2007 MITSUBISHI ELECTRIC CORPORATION A 5 CONTENTS T OVERVIEW iors este che dae merlin Otel ay Se cetera 1 2 PERFORAMNCE SPECIFICATIONS

Download Pdf Manuals