Home
        TCA SERIES WARNING
         Contents
1.                                            15                                  TO MULLION    Remove unit top panel and condenser section access  panel     Remove screws securing coil end plate to mullion     Remove clips connecting coils slabs and separate  AME colt               slabs 3 4   76 102          d BLOWER                            Clean coils with detergent or commercial coil cleaner           Rinse thoroughly with water and reassemble                          CONDENSER  COILS    CONDENSER  ACCESS PANEL       FIGURE 15                                ASSEMBLED ROOF MOUNTING FRAME  The accessories section describes the application of most of TCA090 150    the optional accessories which can be factory or field installed  to the TCA units     A LARMF and LARMFH Mounting Frames  TCA090 150    When installing either the TCA units on a combustible surface  for downflow discharge applications  the Lennox LARMF 10 15  14 inch or 24 inch  356 mm or 610mm  height roof mounting  frame is used  The roof mounting frames are recommended in  all other applications but not required  If the TCA units are not  mounted on a flat  roof  surface  they MUST be supported un   der all edges and under the middle of the unit to prevent sag   ging  The units MUST be mounted level within 1 16  per linear    foot or 5mm per meter in any direction     SUPPLY AIR        CROSS SUPPORT  The assembled LARMF mounting frame is shown in figure 16     Refer to the roof mounting frame installation instr
2.              Al                            1814                                                                                 R                               BBHBBBHBHBHHHBHHHBHHHHBH                               C                   aaaeeeaei                TEST                E                  549 KIO KI 550 K2      C  L   1               HB BHHH HH                   0 CMCI 0 CMC2 HP   53 K68   14  95 KI46 TI8 C 118 C       A                    8 HB E E E S E AEA E E                FIGURE 5    Page 1       3               2            5    oe E    se                   LR       hem      TABLE 3  TB14 24VAC TERMINAL DESIGNATIONS    rw    TABLE 4    Page 14    TABLE 6  P88 TERMINAL DESIGNATIONS    ma           Heat Stage 1 to A3                    PLUMBING  COMPRESSOR AND  REFRIGERANT CIRCUITS DETAIL  CONDENSER COIL             EVAPORATOR COIL                                        FREEZESTAT    S50 Sail  NH                                                    OPTIONAL LOW AMBIENT  SWITCHES  584    S11    BOTH FANS ARE ENERGIZED  DRIERS WITH A Y1 DEMAND     CONDENSER COIL         STAGE  CONDENSER  FAN 1    CONDENSER COIL CONDENSER  STAGE 1 FAN 2                      OPTIONAL HIGH  PRESSURE  SWITCH  S7                          COMPRESSOR  B1             B2   STG1 OPTIONAL       PRESSURE  SWITCH  S4        FIGURE 6    Page 15    B Cooling Components    All units use independent cooling circuits consisting of sep   arate compressors  condenser coils and evaporator coils   See fig
3.          24  III Start Up Operation                            24  IV Charging ses ive GR sae pee                   24  V Maintenance                                  26  VI ACCESSOMIES                xx          27  VII Wiring and Operating Sequence               33        2004 Lennox Industries Inc   itho U S A     SPECIFICATIONS    General Nominal Tonnage 7 5 Ton 8 5 Ton 10 Ton 12 5 Ton  Data Model No  TCA090S2B TCA102S2B TCA120S2B TCA150S2B  Efficiency Type Standard Standard Standard Standard  Cooling Gross Cooling Capacity   Btuh  kW  93 000  27 2  104 000  30 5  126 000  36 6  145 000  42 5   Performance 1Net Cooling Capacity   Btuh  kW  90 000  26 4  100 000  29 3  120 000  35 2  138 000  40 4   ARI Rated Airflow   cfm  L s  3000  1415  3400  1605  3800  1795  4250  2005   Total Unit Power  kW   1 EER  Btuh Watt   2 Integrated Part Load Value  Btuh Watt   Refrigerant Charge Circuit 1   7 lbs  0 oz   3 18 kg    7 lbs  8 oz   3 140 kg    10 Ibs  0 oz   4 53 kg    13 Ibs  0 oz   5 90 kg   Furnished       Circuit 2   6 Ibs  8 oz  22 kg    7 lbs  0 oz     kg    10 Ibs  0 oz  Eum kg    12 Ibs  0 oz  168                3 Sound Rating Number  dB   Condenser Net face area   sq  ft   m2  x3     total 29 3  2 72  total x  2 72  total 26 6      total         Tube diameter          mm  3 8  9 5  3 8  9 5  3 8  9 5  3 8  9 5   Number of rows 1 1 2 3  Fins per inch  m  20  787  20  787  20  787  20  787   Condenser Motor horsepower  W   2  1 3  249   2  1 3  249   2  1 3  249   2  1 
4.          LENNOX   UT INFORMATION    Corp  0411 L3  Revised 06 2005          Service Literature    TCA SERIES    7 5 to 12 5 ton  26 3 kW to 44 kW          090 150 SERIES    The        7 5  8 5 and 10 ton cooling package units are avail   able in standard efficiency  0905  1025  1205  and high effi   ciency  090H  102H  120H   The TCA 12 5 ton unit is avail   able in standard efficiency only  1505    The TCA 090 150  series uses one cabinet size with cooling capacities of  93 000 to 140 000 Btuh  27 2 to 41 kW      Optional electric heat is factory or field installed in TCA units   Electric heat operates in single or multiple stages depending  on the kW input size  7 5 KW to 45 kW heat sections are avail   able for the       090 and 102 and 15 kW to 60 kW heat sec   tions are available for the TCA120 and 150     All units utilize two scroll compressors and are designed to  accept any of several different energy management thermo   stat control systems with minimum field wiring  Factory or  field provided control options connect to the unit with jack  plugs  When  plugged in  the controls become an integral  part of the unit wiring     Information contained in this manual is intended for use by  qualified service technicians only  All specifications are sub   ject to change  Procedures outlined in this manual are pre   sented as a recommendation only and do not supersede or  replace local or state codes     If the unit must be lifted for service  rig unit by attaching four  cab
5.          seem             575V 20 Amp 600     208 230V 50 Amp 250V  EHA150 45  EHA150 60       Page 20    EHA 7 5  15  22 5  30  45  60KW  ELECTRIC HEAT SECTION PARTS ARRANGEMENT    HEATING ELEMENTS  HE1   HE7    SECONDARY ELECTRIC  HEAT LIMIT S20    ELECTRIC HEAT  VESTIBULE    CONTROL WIRE  HARNESS             PRIMARY ELECTRIC  HEAT LIMIT             FIGURE 11    ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT    TERMINAL STRIP   TB3                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          FUSE F3 FUSE F3 FIRST STAGE ELECTRIC SECOND STAGE ELECTRIC FUSE F3  F3 1 F3 2 HEAT CONTACTOR K15 HEAT CONTACTOR K16 F3 4       FIGURE 12    Page 21               9  7 5 TON STANDARD   HIGH EFFICIENCY   TCA090  8 5 TON STANDARD   HIGH EFFICIENCY   TCA102  REQUIRES UNIT FUSE BLOCK  TERMINAL BLOCK AND   HEATER CONTROL MODULE    Minimum Circuit Ampacity    3 Maximum Overcurrent Protection                            1                  Volts        Btuh Total Unit   E
6.      RPM                          RPM          RPM          RPM          RPM          RPM                          RPM          RPM BHP   kW   kW   kW     2250  455 0 30 555 0 45 640 0 601720 0 80 790 1 00 855 1 20 915   1060   0 22   0 34   0 45  0 60   0 75   0 90        4  04  5  16  7   27   8           975 1 60  1030 1 85 1080 2 05  1130 2 30 1175 2 55  1220 2 80            1 19   1 38   1 53   172   1 90   2 09    2500  475 0 40 575 0 55 660 0 70 735 0 90 805 1 10 870 1 30 985 1 75  1040 2 00 1090 2 25 1140 2 50 1185 2 75 1230 3 00   1180   0 30   0 41   0 52   0 67  0 82   0 97   1 31   1 49   1 68   1 87   2 05   2 24   2750  495 0 45 595 0 65 675 0 85 750 1 05 820 1 25 885 1 45 940 995 1 90 1050 2 20 1100 245 1145 2 65 1195 2 95 1240 3 25   1300   0 34   0 48   0 63     0 93   1 08   1 42   1 64   1 83   1 98   2 20   2 42   i     1 20  835 1 40 895 1 60 955 1010 2 10  1060 2 35  1110 2 65 1160 2 90  1205 3 20  1250 3 45      1 04   1 19  1 38   1 57   1 75   1 98   2 16   2 39   2 57    3250  550 0 65 640 0 90 715 1 10 790 1 35 855 160 915 1 80 970 2 05 1025 2 35  1075 2 60 1125 2 85 1170 3 15 1215 3 40 1260 3 70   1535   0 48   0 67   0 82   1   1 19   1 34   1 53   1 75   1 94   2 13   2 35   2 54   2 76     3500  580 0 80 665 1 05 740 1 25810 1 75 930 2 00 985 2 25 1040 2 55 1090 2 85 1135 3 10 1185 3 40 1230 3 70 1270 4 00   1650   0 78   0 93   2 31   2 54   2 76     3750  605 0 95 690 1 20 760 1 45 830   1770   0 90   1 08   12 145   1 68   1 87   2 09   2 31 
7.   2 50   2 72   2 95    1     7     4000  635 1 10 715 1 40 785 1 65 850 1 90 910 2 200965 2 45 1020 275 1070 3 05 1120 3 35  1165 3 65 1210 3 95 1255 4 30  1295 4 60   1890   0 82   1 04   1 23  1 42   1 64   1 83   2 05   2 28   2 50   2 72   2 95   3 21   3 43   4250  665 1 30 740 1 60810 1 85 870 2 15 930 2 45 985 2 75 1040 3 05 1090 3 35 1135 3 65 1185 4 00 1225 4 301270 4 65 1310 4 95   2005   0 97   1 19   1 38   1 60   1 83   2 05   2 28   2 50   2 72   2 98   3 21   3 47   3 69   4500  695 1 50 770 1 80 835 2 10 895 240 955 2 70 1005 3 00 1060 3 35 1105 3 65 1155 4 00 1200 4 30 1245 4 65  1285 5 00 1325 5 30   2125   1 12   1 34   1 57   1 79   2 01   2 24     2 72   2 98     0     5     0     5        1   1   1   1        0  3000  525 0 55 615 0 75 695 0 95 770   1415   041   0 56   07   0       05  78   20  90   35  01                          4750  725   2240   1 31   1 53   1 79   2 01  2 24   2 50   2 95   3 25         5000  760 205 825 2 35 885 2 65 945 3 00 1000 3 35 1050 3 65 1100 4 00 1145 4 35 1190 4 70 1235 5 05 1280 5 45   2360   1 53   1 75   1 98   2 24   2 50   2 72   2 98   3 25   3 51   3 77   4 07  5250  790 2 301855 2651910 2 95 970 3 35 1020 3 65  1070 4 00 1120 4 35 1165 4 70 1210 5 10 1255 5 45    2475   1 72   1 98   2 20   2 50   2 72   2 98   3 25   3 51   3 80   4 07     820 2 601880 2 95 940 3 30 995 3 70  1045 4 05  1095 4 40  1145 4 80  1190 5 15  1230 5 50 E                      Page 8    BLOWER DATA    DRIVE KIT SPECIFICATIONS  Motor Ou
8.   IDELAY ELECIRIC HEAT    FS JIFUSE ELECTRIC HEAT        F4             ELEMENT ELECT HEAT 2   HES      ELEMENT ELECTRIC HEAT 3      22 5  amp  30KW    HE HE2  7 5       NOT USED      7 5 15  AND 30KW UNITS     TB3 IS USED ON SOME UNITS            548 OR CBIO MAY BE USED    WIRING DIAGRAM            HEATING ELECTRIC      EHA 7 5 15 22 5 30 45 60 1 2 6          FOR USE WITH        UNITS    HEATIN ON  A4  BBA 472     534                 20 Lithe U S A        Page 36    Sequence of Operation         7 5  15  22 5  30  45  60 kW             G  J  M    NOTE  This sequence of operation is for all Electric  Heat kW ratings Y through J voltages  Each step of op   eration is numbered and can be followed in sequence  on the diagrams  Operation for G  J  and M voltages will  be the same     HEATING ELEMENTS     1  Terminal Strip TB3 is energized when the unit discon   nect closes  TB3 supplies line voltage to electric heat  elements HE1 through HE7  Each element is protected  by fuse F3     FIRST STAGE HEAT   2  Heating demand initiates at W1 in thermostat     3  24       is routed through from main control module  A45  After A45 proves        primary limit 515 and sec   ondary limit S20  the electric heat contactor K15 is en   ergized     4         contacts K15 1 close allowing the first bank of  elements to be energized     SECOND STAGE HEAT     5  With the first stage heat operating  an additional heat   ing demand initiates at W2 in the thermostat    6  Relay K9 is energized  N O  c
9.   See unit rating plate for correct  amount of charge     5  Refer to IV Charging for proper method to check refriger   ant charge    Three Phase Scroll Compressor Voltage Phasing   Three phase power supplied to the unit disconnect   switch must be phased sequentially to ensure the scroll   compressor and indoor blower rotate in the correct direc    tion  Compressor and blower are wired in phase at the   factory  Power wires are color coded as follows  line   1 red  line 2 yellow  line 3 blue    1  Observe suction and discharge pressures and blower  rotation on unit start up    2  Suction pressure must drop  discharge pressure must  rise  and blower rotation must match rotation marking     If pressure differential is not observed or blower rotation is  not correct     3  Disconnect all remote electrical power supplies     4  Reverse any two field installed wires connected to the  line side of K2 contactor  Do not reverse wires at blow   er contactor        5  Make sure the connections are tight     Discharge and suction pressures should operate at their  normal start up ranges     IV Charging   WARNING Do not exceed nameplate charge under any  condition    This unit is factory charged and should require no further  adjustment  If the system requires charge  reclaim the  charge  evacuate the system  and add required nameplate  charge    NOTE   System charging is not recommended below 60  F   15  C   In temperatures below 60  F  15  C    the charge  must be weighed into the sys
10.   Units may be equipped with  motors manufactured by various manufacturers  therefore  electrical FLA and LRA specifications will vary  See unit rating  plate for information specific to your unit     OPERATION   ADJUSTMENT  Blower Operation    Initiate blower demand at thermostat according to instruc   tions provided with thermostat  Unit will cycle on thermostat  demand  The following steps apply to applications using a  typical electro mechanical thermostat     1  Blower operation is manually set at the thermostat sub   base fan switch  With fan switch in ON position  blow   ers will operate continuously     2  With fan switch in AUTO position  the blowers will cycle  with demand  Blowers and entire unit will be off when  system switch is in OFF position     Blower Access    The blower assembly is secured to a sliding base which al   lows the entire assembly to be pulled out of the unit  See  figure 8     1  Turn off power from unit  Remove the clamp which se   cures the blower wiring to the blower motor base     2  Remove and retain screws on either side of sliding  base  Pull base toward outside of unit     3  Slide base back into original position when finished  servicing  Replace the clamp and blower wiring in the  previous location on the blower motor base     Determining Unit CFM    1  The following measurements must be made with a dry  indoor coil  Run blower without a cooling demand   Measure the indoor blower shaft RPM  Air filters must  be in place when measureme
11.  60 Hz   3 phase 208 230   460   575V 208 230   460   575V  Compressors Rated load amps   each  total    12 8  25 6  6 4  12 8  5 1  10 2  12 4  24 9  6 4  12 8  4 8  9 6    2  Locked rotor amps   each  total    91  182  46  92  37  74  88  176  44  88  34  68   Condenser Number of motors 2 2 2 2 2 2  Fan Motor Full load amps   each  total    2 4  4 8  1 3  2 6  1 0  2 0  2 4  4 8  1 3  2 6  1 0  2 0   Locked rotor amps   each  total    4 7  9 4  2 4  4 8  1 9  3 8  4 7  9 4  2 4  4 8  1 9  3 8   Evaporator Motor Output   hp 2 3 2 3 2 3 2 3 2 3 2 3  power kW  15   22 15   22 15   22 15   22 15   22 15   22              amps   75   106   34   48   27   39   75   106   34   48   27   39  Locked rotor amps   469   66   204   268   162   234   469   66   204   268   162   234    1 Maximum Overcurrent With Exhaust Fan   50 50 25 25 20 20 50 50 25 25 20 20  Protection  amps  Less Exhaust Fan   50 50 25 25 20 20 50 50 25 25 20 20  2 Minimum Circuit With Exhaust Fan   44 47 22 24 18 19 43 46 22 24 17 18  Ampacity Less Exhaust Fan   42 45 21 22 17 18 41 44 21 22 16 17  Optional Power  Number  Horsepower  W     1  1 3  249     1  1 3  249     1  1 3  249     1  1 3  249     1  1 3  249     1  1 3  249   Exhaust Fan Full load amps 24 1 3 1 0 2 4 1 3 1 0  Locked rotor amps 4 7 24 1 9 4 7 24 1 9  Service Outlet  2  115 volt GFCI  amp rating  15 15 15 15 15 15       NOTE   Extremes of operating range        plus and minus 10  of line voltage   1 HACR type breaker or fuse     2 Referto Nati
12.  8   The 208 230  Y  voltage transformers use two    208 230V TRANSFORMER   Primary voltage taps  BLUE    YELLOW as shown in figure 3   SECONDARY    while 460  G  and 575       J  voltage transform   208 VOLTS        ers use a single prima   RED ry voltage tap   PRIMARY    ORANGE BLACK       3 Terminal Strip TB1   All indoor thermostat connections will be to TB1 located on  the MCC board A45  For thermostats without  occupied   and  unoccupied  modes  a factory installed jumper across  terminals A1 and A2 found on the MCC board should be in  place     4 Terminal Strip TB14   Terminal strip TB14 located on the MCC board distributes  24V power from the indoor thermostat to the control box   Units not equipped with smoke detectors A17 or A64  will  have a factory installed jumper across terminals 24        and R    5 Condenser Fan Capacitors C1  amp  C2   Fan capacitors C1 and C2 are 370V   10 MFD capacitors  used to assist in the start up of condenser fans B4 and B5   Ratings are on side of capacitor or condenser fan motor  nameplate     6 Compressor Contactor K1  amp  K2    All compressor contactors are three pole double break  contactors with 24VAC coils  In     TCA090 150 units  K1  and K2  energized by MCC board A45  energize compres   sors B1 and B2 in response to thermostat demand  K2 also  serves as the line voltage terminal block for L1  L2 and L3     7 Blower Contactor K3  all units     Blower contactor K3  used in all units  is a three pole double   break contactor wi
13.  Ends  amp  Sides Open Diffuser   cfm L s in  w g  Pa in  w g  Pa in  w g  Pa in  w g  Pa  2400 1135 0 21 52 0 18 45 0 15 37 0 14 35  2600 1225 0 24 60 0 21 52 0 18 45 0 17 42  2800 1320 0 27 67 0 24 60 0 21 52 0 20 50  3000 1415 0 32 80 0 29 72 0 25 62 0 25 62  3200 1510 0 41 0 37 92 0 32 0 31  3400 1605 0 50 0 45 0 39 0 37  3600 1700 0 61 0 54 0 48 0 44  3800 1795 0 73 0 63 0 57 0 51    1700 0 36 90 0 28 70  1890 0 44 109 0 36 90   2170 0 60 149 0 49 122 0 42  2265 0 65 132 0 46    2360 0 69 144 0 50  2455 0 75 154 0 54    1980 0 22 55 47 0 16  2170 0 34 85 72 0 24  150 Models 2360 0 46 114 97 0 34  2550 0 58 122 0 43    2645 0 64 134 0 47  2735 0 70 147 0 51    Unit Air Volume  Size                                                 Page 10             ECONOMIZER   OPTIONAL                    FILTER DRIERS    CONDENSATE  DRAIN       TCA PARTS ARRANGEMENT    FILTERS EVAPORATOR   FOUR   18 X 24 X 2   CONDENSER    FANS          N N          59   q  m  N                                                       CONDENSER  L    BLOWER        ELECTRIC HEAT MOTOR  F4 FUSE BLOCK  Optional   COMPRESSORS  OPTIONAL           FIGURE 1    TCA CONTROL BOX    MCC Control Module Electric Heat Hat   A45  Section               Relay E  Time      Delay   e     DL12  Se      0                                      Blower       Transformer  5    Contactor Compressor Contactors CAPACITOR CAPACITOR  1        T1                                               Power Exhaust Relay   K65        s   K3   K1  a
14.  K2 1 closes energizing compressor B2   14  Optional N O  low ambient switch S84 closes energizing contacts K10 2  K10 2 close energiz   ing condenser fan B5        Page 34           7 5  15  22 5  30  45 60kW                                IKEY   COMPONENT _______________  22      FS                           HEAT C                                           ELEMENT ELECT HEAT          2   LEMENT ELECT  HEAT 2  HES ___             HEAT 8            HES  IELEMENT ELECTIRIC HEAT 6           CLEMENT ELECIRIC HEAT 7      2      lJACK ELECTRIC HEAT                            7  JACK ELECT HT SUD  BASE KIT   WAR PTOR              DACK CONTROL MODULE          J    9      RELAY HEAT   KTS  T  CONTACTO R ELECTRIC HT  _____   IKI6  1  CONTACTOR ELECTRIC HT 2        _ JPLUG ELECTRIC HEAT    22 5  amp  30KW                    NS           n  OS 2    HE4    m pg 1 HE6                    Q    cM  21520     44520 HE      2        HE4 HE5 HE6 HE7   5   1   3                 O      O  HE4      1   Xis        1            5    520        FAN        6    520                 deo MMC                             HE7    0 145      NOT USED      7 5 15  AND 30KW UNITS       TB3 IS USED ON SOME UNITS  AX TB2 548 OR CBIO MAY BE USED  WIRING DIAGRAM  2 04         HEATING ELECTRIC             7 5  15 22 5  30  45 60 1 2     FOR USE WITH TCA UNITS       N ON         ENT    Litho U S A        Page 35           7 5  15  22 5  30  45 60kW                              DESCRIPTION    KEY   COMPONENT          
15.  kW    2 hp  1 5 kW    3 hp  2 2 kW    3 hp  2 2 kW    5 hp  3 7 kW   Electric Heat Model No  EHA  see Electric Heat Data tables for additional information   kW Input  Range 7 5 15 22 5 30 45 15 22 5 30 45 60  Unit With 208 230V  Fuse Power  Block Exhaust 460V   3phase  Fans  575V  Without 208 230V 56K93 56K93 56K94 56K94 56K94 56K95 56K96  Power  Exhaust 460V 56K52 56K52 56K52 56K52 25K08 25K09 25  09            575   56  51 56  51 56K51 56K51 56K52 56K52 25K08          LTB2 ELECTRIC HEAT TERMINAL BLOCK   LTB2 175  30K75  175 amps  LTB2 335  30  76  335 amps   Required For Units Without Disconnect Circuit Breaker But With Single Point Power Source     LTB2 All hp 208 230V   30  75 30K75 30K75 30K75 30K75 30K75 30K75  Terminal  Block All hp 208 230V   30  75 30K75 30K75 30K75 30K75 30K75 30K75    All hp 208 230     30  75   30  75   30  75   30K75 30K75   30K75   30  75  All hp 208 230     30  75   30  75   30  75   30K75 30K75   30K75   30  75  All hp 208 230V                 m 30K76   30K76   30  76    NOTE        460V and 575V models use 30K75 terminal block   NOTE   Terminal Block is factory installed in units with factory installed electric heat without disconnect circuit breaker but with single point power source        All hp 208 230V   30  75 30K75 30K75 30K75 30K75 30K75 30K75             Page 5    ELECTRICAL DATA                                                                      7 5 TON STANDARD   HIGH EFFICIENCY  Model No  TCA090S       090    Line voltage data  
16.  kg  600 102 400  45 kW 208    115 300  220 129 000        150 45    255        152 160 175 175  2 240 153 600  440 37 8 129 000  180  460 41 3 141 000 76 79 80 80  575V 480 45 0 153 600  129 000  99J12 141 000 61 63 70 70  42 lbs   19 kg  153 600  60 kW 153 600  172 000  EHA150 60    188 000 161 169 175 175  208 230   204 800  22013 22 440 50 4 172 000  460V 22 460 55 1 188 000 84 80 90  99214 22 480   600 204 800  575V 22 550 50 4 172 000  99 15 22 575 55 1 188 000 64 67 70 70  49 Ibs   22 kg  22 600 60 0 204 800             1 Fuse block must be ordered extra  Factory installed heaters will have the fuse block factory installed  Fuse block must be installed in field installed heaters  Also requires  LTB2 Terminal Block  See Optional Electric Heat Accessories tables    2 Refer to National or Canadian Electrical Code manual to determine wire  fuse and disconnect size requirements  Use wires suitable for at least 167  F  75         3 HACR type breaker or fuse    4        be used with two stage control     Page 23                           AND INSTALLATION    Make sure the unit is installed in accordance with the  installation instructions and all applicable codes  See  accessories section for conditions requiring use of the  optional roof mounting frame  LARMF18 36 or  LARMFH18 24      lll Start Up   Operation    A Preliminary and Seasonal Checks    1  Make sure the unit is installed in accordance with the  installation instructions and applicable codes    2  Inspect all elect
17.  table 18  Setting A is recommended  See figure 20  At set   ting A  free cooling will be energized when outdoor air is  approximately 73  F  23  C  and 50  relative humidity  If in   door air is too warm or humid  lower the setpoint to B  At  setting B  free cooling will be energized at 70  F  21  C  and  50  relative humidity    When an optional A62 differential sensor is installed  turn  A6 enthalpy control free cooling setpoint potentiometer  completely clockwise to position              TABLE 18  ENTHALPY CONTROL SETPOINTS      8   rero               srarg     Damper Minimum Position  NOTE   A jumper is factory installed between TB1 A1  and A2 terminals to maintain occupied status  allowing  minimum fresh air   When using an electronic thermostat    or energy management system with an occupied unoc   cupied feature  remove jumper        Page 29    1  Set thermostat    occupied mode if the feature is avail   able  Make sure jumper is in place between A45 con   trol board TB1 terminals A1 and A2 if using a thermo   stat which does not have the feature     2  Rotate MIN POS SET potentiometer to approximate  desired fresh air percentage     Note   Damper minimum position can be set lower than  traditional minimum air requirements when an  AQ sensor  is specified  Dampers will open to DCV MAX setting  if CO2  is above setpoint  to meet traditional ventilation require   ments     3  Measure outdoor air temperature  Mark the point on  the bottom line of chart 1 and label the po
18.  to  move the motor outward and tighten the belt     3 Tighten two bolts on motor pulley side     IMPORTANT   Align top edges of blower motor base  and mounting frame base parallel before tightening  two bolts on the other side of base  Motor shaft and  blower shaft must be parallel     4 Tighten two bolts on other side of base     TO INCREASE CFM  LOOSEN ALLEN SCREW  amp   TURN PULLEY CLOCKWISE    TO DECREASE CFM  TURN PULLEY  COUNTERCLOCKWISE    BELT TENSION  ADJUSTING BOLT   TURN    SIDE VIEW    ALLEN  SCREW    PULLEY       BLOWER ASSEMBLY    CLOCKWISE TO TIGHTEN BELT    MOTOR BASE  ADJUSTMENT SCREWS    P   2 EACH SIDE    BLOWER MOTOR  MOUNTING FRAME    BLOWER  MOTOR BASE    REMOVE 2 SCREWS FROM BOTH  SIDES BEFORE SLIDING BLOWER  ASSEMBLY OUT OF UNIT    FIGURE 8    1  Loosen four bolts securing motor base to mounting  frame  See figure 8           1    To increase belt tension     Turn adjusting bolt to the right  or clockwise  to move  the motor outward and tighten the belt  This increases  the distance between the blower motor and the blower  housing     To loosen belt tension    Turn the adjusting bolt to the left  or counterclockwise  to loosen belt tension     3  Tighten two bolts on motor pulley side     IMPORTANT   Align top edges of blower motor base and  mounting frame base parallel before tightening two bolts on  the other side of base  Motor shaft and blower shaft must  be parallel     4  Tighten two bolts on other side of base     Check Belt Tension    Overtens
19.  x 15  381 x 381   1  15 x 15  381 x 381   Filters Type of filter Disposable  pleated MERV 7  standard  or MERV 11  optional     Number and size   in   mm   4  18 x 22x 2  4  18x 24x 2  4  18x 24x 2   457 x 610 x 51   457 x 610 x 51   457 x 610 x 51     Electrical characteristics 208 230V  460V or 575V   60 hertz   3 phase    NOTE   Net capacity includes evaporator blower motor heat deduction  Gross capacity does not include evaporator blower motor heat deduction    1 Certified in accordance with the ULE certification program  which is based on ARI Standard 340 360  95  F  35  C  outdoor air temperature and 80  F  27  C  db 67  F  19  C   wb entering evaporator air  minimum external duct static pressure    2 Integrated Part Load Value rated at 80  F  27  C  outdoor air temperature  80  F  27  C  db 67  F  19  C  wb indoor air temperature    3 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270      Maximum usable output of motors furnished by Lennox are shown  In Canada  nominal motor output is also maximum usable motor output  If motors of comparable output  are used  be sure to keep within the service factor limitations outlined on the motor nameplate           Page 3    Cabinet  Accessories    Ceiling  Diffusers    Controls    Cooling  Accessories    Economizer    Barometric  Relief    OPTIONAL FIELD INSTAL    Coil Guards   Hail Guards   Horizontal Discharge Conversion Kit  Step Down   Net Weight    Flush   Net Weight  Transitions  Sup
20. 2  372   Fans Motor rpm 1075 1075 1075 1075  Total Motor watts 700 700 700 1150  Diameter   in   mm    no  of blades  2  24  610    3  2  24  610    3  2  24  610    3  2  24  610    3  Total air volume   cfm  L s  8 000  3775  8 000  3775  8 000  3775  9 000  4245   Evaporator Net face area   sq  ft   m2  10 5  0 98  total 10 5  0 98  total 10 5  0 98  total 10 5  0 98  total  Coll Tube diameter   in   mm  3 8  9 5  3 8  9 5  3 8  9 5  3 8  9 5   Number of rows 3 3 4 4  Fins per inch  m  14  551  14  551  14  551  14  551   Drain Connection   no   amp  size    1  1 in  NPT coupling    1  1 in  NPT coupling    1  1 in  NPT coupling    1  1 in  NPT coupling  Expansion device type Balanced Port Thermostatic Expansion Valve  removable power head  Standard   Belt Drive   Nominal motor output 2 hp  1 5       2 hp  1 5 kW  3 hp  2 2 kW  5 hp  3 7 kW                   Maximum usable output  US Only  2 3 hp  1 7 kW  2 3 hp  1 7 kW  3 45 hp  2 6 kW  5 75 hp  4 3 kW     Drive Drive kit   kit  1   680   925 rpm   kit  1   680   925 rpm   kit  3   895   1120         kit  6   1100  1395  rpm    Wheel nominal diameter x width   in   mm   1  15    15  381 x 381   1  15 x 15  381 x 381   1  15 x 15  381 x 381    1  15 x 15  381 x  381     Filters Type of filter Disposable  pleated MERV 7  standard  or MERV 11  optional     Number and size                   4  18x 24 x2  4  18x 24 x 2  4  18x 24x 2  4  18x 24x 2   457 x 610 x 51   457 x 610 x 51   457 x 610 x 51   457 x 610 x 51     Electrica
21. 3   1 through F3   4     contactors are equipped with a 24VAC coil  The coils in 9 Fuse F4    the K15 and K16 contactors are energized by the  main panel A45  Contactor K15 energizes the first  stage heating elements  while K16 energizes the second  stage heating elements   4 High Temperature Limits 515  Primary     15 is a SPST N C  auto reset thermostat located on the  back panel of the electric heat section below the heating  elements  515 is the high temperature limit for the electric  heat section  When 515 opens  indicating a problem in    Page 19    Fuse F4 is used only with single point power along with  TB2  F4 gives over amperage protection to the compres   sor and other cooling components while F3 protects the  electrical heat component  The F 4 fuse block is located  inside    sheetmetal enclosure  figure 1                 8  TCA ELECTRIC HEAT SECTION FUSE RATING    Ce was      _         sw           _ _                   wem sa          100 7 5    Ce kea                   Emm                     Gem Dew                  pea             w            Dmm                Co pra                         een a                            ee e    20 Am            u a                          me rem  inno mm     ww wmew                        mew  sar                                     60 22 5 460        575V 20 Amp 600V a    208 230V 50 Amp 250V ELA    208 230V 50 Amp 250V ES         150 30   460   25        600   NELLE    poet                         C e     e          
22. 36 6  Maximum Overcurrent With Exhaust Fan   60   60   70   30   30   35   20   25   25   70   70   80   35   35  40  25  30   30  Protection  amps  Less Exhaust Fan   60   60   70   30   30   30   20   25   25   60   70   70   35   35   35   25   25   30    Minimum Circuit With Exhaust Fan   50   53   59   24   26   29   19   21   23   54   57   63   28   29   32   22   23   26  Ampacity Less Exhaust Fan   47   51   57   23   25   27   18   20   22   52   55   61   27   28   31   21   22   25  Optional Power  Number  Horsepower  W     1  1 3  249   1  1 3  249   1  1 3  249     1  1 3  249     1  1 3  249     1  1 3  249   Exhaust Fan Full load amps 24 13 10 24 13 10  Locked rotor amps 4 7 24 1 9 4 7 24 1 9  Service Outlet  2  115 volt GFCI  amp rating  15 15 15 15 15 15  NOTE   Extremes of operating range are plus and minus 10   of line voltage   1 HACR type breaker or fuse   2 Referto National or Canadian Electrical Code manual to determine wire  fuse and disconnect size requirements   12 5 TON STANDARD EFFICIENCY  Model No  TCA150S  Line voltage data   60 Hz   3 phase 208 230   460   575    Compressors Rated load amps   each  total  18 6  37 2  9  18  7 4  14 8   Q  Locked rotor amps   each  total  156  312  75  150  54  108   Condenser Full load amps   each  total  3 0  6 0  1 5  3 0  1 2  24   Fan Motors  2  Locked rotor amps   each  total  6 0  12 0  3 0  6 0  2 9  5 8   Evaporator Motor Output   hp 3 5 3 5 3 5                22 37 22 37 22 37  otor  Full load amps 10 
23. 6 16 7 4 8 7 6 3 9 6 1  Locked rotor amps 66 105 26 8 45 6 234 36 6  Maximum Overcurrent With Exhaust Fan 70 80 35 40 30 30  Protection  amps  Less Exhaust Fan 70 80 35 35 30 30    Minimum Circuit With Exhaust Fan 61 67 30 33 24 27  Ampacity Less Exhaust Fan 59 65 29 31 23 26  Optional Power  Number  Horsepower  W   1  1 3  249   1  1 3  249   1  1 8  249   Exhaust Fan Full load amps 24 13 1 0  Locked rotor amps 4 7 24 1 9  Service Outlet  2  115 volt GFCI  amp rating  15 15 15       NOTE   Extremes of operating range are plus and minus 10   of line voltage     1 HACR type breaker or fuse     2 Referto National or Canadian Electrical Code manual to determine wire  fuse and disconnect size requirements     Page 7    BLOWER DATA 090  102  120  150    BELT DRIVE BLOWER   BASE UNIT    BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY  NO HEAT SECTION  WITH DRY INDOOR COIL AND  AIR FILTERS IN PLACE  FOR ALL UNITS ADD    1   Wet indoor coil air resistance of selected unit    2   Any factory installed options air resistance  heat section  economizer  etc     3   Any field installed accessories air resistance  duct resistance  diffuser  etc    Then determine from blower table blower motor output and drive required        BOLD INDICATES FIELD FURNISHED DRIVE   Total Static Pressure   in  w g   Pa     20  50     40  100     60  150     80  200  1 00  250  1 20  300   1 40  350  4 60  400   1 80  450   2 00  495   2 20  545  2 40  595   2 60  645     RPM          RPM          RPM     
24. B2 Terminal Block  See Optional Electric Heat Accessories tables     2 Refer to National or Canadian Electrical Code manual to determine wire  fuse and disconnect size requirements  Use wires suitable for at least 167  F  75                     type breaker or fuse   4        be used with two stage control     Page 22               10  10 TON STANDARD   HIGH EFFICIENCY         120    12 5 TON STANDARD EFFICIENCY   TCA150  REQUIRES UNIT FUSE BLOCK  TERMINAL BLOCK AND   HEATER CONTROL MODULE                                                2 Minimum Circuit Ampacity   3 Maximum Overcurrent Protection  1 prae Heat       Volts kW Btuh Total Unit   Electric Heat Total Unit   Electric Heat   amp  Not Weight Steps Input Input Output  with Power Exhaust Fan   with Power Exhaust Fans   TCA120       150       120       150  15 kW 1 208 11 3 38 600  1 220 12 6 43 000        150 15     120H   70  1 230 13 8 47 100 e      1205   60       208 230V  39322 1 240 15 0 51 200  1 440 12 6 43 000  460   120     35  s 1 460 13 8 47 100 31 34 1205  30 40  1 480 15 0 51 200  n 1 550 12 6  1 575 13 8 25 27 25 30  31 Ibs   14 kg  1 600 15 0  22 5 kW 22 208  220  EHA360 22 5  250 84 92 90 100  208 230   240  9928 240  460V 460 42 45 45 45  575   550  99  30 575 34 36 35 40  38 Ibs   17 kg  600  30 kW 208   76 800  EHA150 30 220 86 000  t        25 i25  208 230V 230 93 900  59307 240 102 400  440 86 000  460V  4515 460 93 900 53 57 60 60  480 102 400        550 86 000  575 93 900 43 45 45 45  38 Ibs   17
25. Ibs  8 oz   3 86 kg  10 Ibs  0 oz   4 54        Fumish  d  HCFC 22           Circuit2   8 Ibs  8 oz   3 86 kg  8 Ibs  8 oz   3 86 kg  10 Ibs  0 oz   4 54 kg           3 Sound Rating Number  dB  88 88 88  Condenser Net face area   sq  ft   m2  29 3  2 72  total 29 3  2 72  total 29 3  2 72  total  Sell Tube diameter   in   mm  3 8  9 5  3 8  9 5  3 8  9 5   Number of rows 2 2 2  Fins per inch  m  20  787  20  787  20  787   Condenser Motor horsepower  W   2  1 3  249   2  1 3  249   2  1 3  249   Fans Motor rpm 1075 1075 1075  Total Motor watts 700 700 700  Diameter   in   mm    no  of blades  2  24  610    3  2  24  610    3  2  24  610    3  Total air volume   cfm  L s  8 000  3775  8 000  3775  8 000  3775   Evaporator Net face area   sq  ft   m2  10 5  0 98  total 10 5  0 98  total 10 5  0 98  total  Coll Tube diameter   in   mm  3 8  9 5  3 8  9 5  3 8  9 5   Number of rows 3 3 4  Fins per inch  m  14  551  14  551  14  551     Drain Connection   no   amp  size  1  1 in  NPT coupling  1  1 in  NPT coupling  1  1 in  NPT coupling    Expansion device type Balanced Port Thermostatic Expansion Valve  removable power head  Standard   Belt Drive   Nominal motor output 2 hp  1 5 kW  2 hp  1 5 kW  3 hp  2 2 kW   Indoor Maximum usable output  US Only  2 8 hp  1 7 kW  2 8 hp  1 7 kW  3 45 hp  2 6 kW     Blower and  Drive Motor   Drive kit kit  1   680   925 rpm kit  1   680   925 rpm kit  3   895   1120 rpm    Wheel nominal diameter x width   in   mm   1  15 x 15  381 x 381   1  15
26. ON CI  Supersedes Form No  New Form No    wem n            Litho U S A     POWER   1  Terminal strip TB1 found on the main control module A45energize thermostat components with 24VAC   OPERATION     2  The main control module A45 receives data from the electronic thermostat A2  Y1  Y2  W1  W2  G  OCP   A45 energizes the appropriate components for heat      cool demand        Page 38             SERIES ECONOMIZER    WIRING DIAGRAM 11 05    RIPTI  N  Ae CONTROL SOLID STATE ENTHALEY      ENTHALPY ACCESSORIES  IAA  SENSOR SOLID STATE ENTHALPY   ECONOMIZER    ineo    ENSOR ENTHALPY  INDOOR  OTOR DAMPER  ECONOMIZER FOR TCA TGA UNITS  ACK SENSOR  OUTDOOR ENTHALPY    ACK SENSOR RETURN AIR ENTHALP ECONOMIZER SECTION DI   LUG SENSOR  OUTDOOR ENTHALPY New Form No    LUG SENSOR RETURN AIR ENTHALPY   534  485W  2003    Litho U S A     Flos      DU pru i     lt     SEQUENCE OF OPERATION  POWER   1  Terminal strip TB1 found on main control module A45 energizes the economizer components with 24VAC     OPERATION     2  Enthalpy sensor A7 and A62  if differential enthalpy is used  communicates to the economizer control  module A6 when to power the damper motor B7     3                       control module      supplies B7 with 0   10 VDC to control the positioning of economizer   4  The damper actuator provides 2 to 10        position feedback        Page 39    
27. P CLASS IT VOLTAGE 5 zo tithe 0757                 33          090 150 SEQUENCE OF OPERATION    Power    1  Line voltage from unit disconnect energizes transformer T1  T1 provides 24VAC power to  terminal strip TB1  TB1 provides 24VAC to the unit cooling  heating and blower controls    Blower Operation    2  The main control module receives a demand from thermostat terminal G  A45 energizes  blower contactor      with 24VAC     3  N O       1 closes  energizing blower        Economizer Operation     4  The economizer control module receives a demand and energizes exhaust fan relay K65 with  24       at 50  outside air damper open  adjustable      5  N O  K65 1 and N O  K65 2 both close  energizing exhaust fan motor B10   1st Stage Cooling  compressor B1   First stage cooling demand Y1 and G is energized by the thermostat  G energizes blower     24       is routed through TB1 on main control module A45  A45 proves        freezestat S49   and optional N C  high pressure switch S4  Compressor contactor K1 is energized     N O  contacts K1 1 close energizing compressor B1   9  Optional N O  low ambient switch S11 closes to energize condenser fan relay K10   10  N O  contacts K10 1 close energizing condenser fan B4    2nd Stage Cooling  compressor B2 is energized   11  Second stage cooling demand energizes Y2     12  24VAC is routed through TB1on module A45  A45 proves N C  freezestat S50 and optional  N C  high pressure switch S7  Compressor contactor K2 is energized     13  N O 
28. TCA090S NORMAL OPERATING PRESSURES Doe  ee ee       Outdoor CIRCUIT 1 CIRCUIT 2 TABLE 16    Entenng   Dis   10 eT TCA120H NORMAL OPERATING PRESSURES    Air Temp   psig ig psig psig                CIRCUIT 1 CIRCUIT 2    180 e Entering   Dis  10   Suct  5   Dis  10   Suc   5  206 13                 psig psig psig psig                                              ccn 65  F  75  F      ar          78   22   9    Svr   244          22   8               12 10552   275   81   28   83    TCA090H NORMAL OPERATING PRESSURES 115     309 83 322 84              CIRCUIT 1 CIRCUIT 2  ol  Entering   Dis  10   Suct  5   Dis  10   Suc   5 TABLE 17  Air Temp   psig psig psig psig TCA150S NORMAL OPERATING PRESSURES  156 76 Outdoor CIRCUIT 1 CIRCUIT 2  181 18 Entering   015   10   Suct  5   Dis   10  209 80 Air Temp psig psig psig  29       65  F 70  274 83 S  m eee    21   72   27               13 95     74        1025 NORMAL OPERATING PRESSURES 105  F 76  Outdoor CIRCUIT 1 CIRCUIT 2 115  F 77          Coil                         Entering Dis   10 Suc   5  Air Temp psig psig Charge Verification   Approach Method  178 73  204 73 1  Using the same thermometer  compare liquid temper   237 74 ature to outdoor ambient temperature   272 76  313 77           Sh 78 Approach Temperature   Liquid temperature minus  ambient temperature   TABLE 14  EA MH NORMAL OPERATING PRESSURES 2  Approach temperature should be 7  F   1  3 8  C   0 5    Coil CIRCUITI        An approach temperature greater than this valu
29. air when an R1 mixed air sensor is installed     Page 31    F LAGED H  Gravity Exhaust Dampers    LAGED H 10 15 dampers  figure 23  available for        090 150 units are used in downflow and LAGEDH  are used in horizontal air discharge applications   LAGED H  gravity exhaust dampers are installed in the re   tum air plenum   The dampers must be used any time an  economizer or power exhaust fans are applied to TCA series  units    Gravity exhaust dampers allow exhaust air to be discharged  from the system when an economizer and or power exhaust is  operating  Gravity exhaust dampers also prevent outdoor air  infiltration during unit off cycle  See installation instructions for  more detail     LAGED AND LAPEF INSTALLATION    ECONOMIZER  FRESH AIR  HOOD                GRAVITY  EXHAUST    p  LAPEF         POWER EXHAUST  FAN ASSEMBLY                LAGED GRAVITY  EXHAUST DAMPERS       FIGURE 23    G LAPEF Power Exhaust Fans  all units     LAPEF10 15 available                90 150 units                          haust fans used in downflow applications only  TAPEF fans  requires optional down flow gravity exhaust dampers and LA   REMD economizers  Power exhaust fans provide exhaust air  pressure relief and also run when return air dampers are  closed and supply air blowers are operating  Figure 23  shows location of the LAPEF  See installation instructions  for more detail     H Control Systems  Three different types of control systems may be used with  the        series units  A
30. e indi   Entering   Dis   10 Dis   10   Suc   5 cates an undercharge  An approach temperature less  Air Temp psig psig psig nin  160 75 than this value indicates an overcharge   186 77  213 79 3  Do not use the approach method if system pressures  243 81 do not match pressures in tables 11 through 17  The  277 82 approach method is not valid for grossly over or under   313 84 charged systems              Page 25                               The unit should be inspected once a year by    qualified          vice technician     AWARNING    Electric shock hazard  Can cause injury  or death  Before attempting to perform  any service or maintenance  turn the  electrical power to unit OFF at discon   nect switch es   Unit may have multiple  power supplies     A CAUTION    Label all wires prior to disconnection when servicing  controls  Wiring errors can cause improper and dan   gerous operation  Verify proper operation after ser     vicing     AWARNING    Product contains fiberglass wool    Disturbing the insulation in this product during  installation  maintenance  or repair will expose you  to fiberglass wool  Breathing this may cause lung  cancer   Fiberglass wool is known to the State of Cal   ifornia to cause cancer     Fiberglass wool may also cause respiratory  skin   and eye irritation    To reduce exposure to this substance or for further  information  consult material safety data sheets  available from address shown on unit nameplate or  contact your supervisor     A Filt
31. ers    Units are equipped with four 18 X 24 X 2    filters  Filters  should be checked and replaced when necessary with fil   ters of like kind and size  Take note of air flow direction  marking on filter frame when reinstalling filters  See figure  14        B Lubrication    All motors are lubricated at the factory  No further lubrica   tion is required        REMOVE FILTERS                  PULL TO  REMOVE  FILTERS                      FIGURE 14    NOTE Filters must      U L C  certified or equivalent for use  in Canada     C Evaporator Coil    Inspect and clean coil at beginning of each cooling season   Clean using mild detergent or commercial coil cleanser   Flush coil and condensate drain with water taking care not to  get insulation  filters and return air ducts wet     D Condenser Coil    Clean condenser coil annually with detergent or commer   cial coil cleaner and inspect monthly during the cooling  season     Condenser coils are made of one  two  and three formed  slabs  Dirt and debris may become trapped between the  slabs  To clean between slabs  carefully separate coil slabs  and wash them thoroughly  See figure 15  Flush coils with  water following cleaning     Note   Remove all screws and gaskets prior to cleaning  procedure and replace upon completion    E Supply Blower Wheel   Annually inspect supply air blower wheel for accumulated  dirt or dust  Turn off power before attempting to remove ac   cess panel or to clean blower wheel     Page 26                  
32. ferential sensor  A62  may be used with the  A7 outdoor sensor to compare outdoor air temperature to  return air temperature  When the outdoor air temperature  is below the return air temperature  outdoor air is used for  free cooling     An optional mixed air sensor  R1  may be used to modulate  dampers to 55  F  13  C  discharge air     An optional IAQ sensor  A63  may be used to lower operat   ing costs by controlling outdoor air based on CO  level or  room occupancy  also called demand control ventilation or  DCV   Damper minimum position can be set lower than  traditional minimum air requirements  dampers open to  traditional ventilation requirements when CO  level reach   es DCV  IAQ  setpoint     Refer to instructions provided with sensors for installation     A6 Enthalpy Control LED   s    A steady green Free Cool LED indicates that outdoor air is  suitable for free cooling    When an optional IAQ sensor is installed  a steady green  DCV LED indicates that the IAQ reading is higher than set   point requiring more fresh air  See figure 20        A6 ENTHALPY CONTROLLER    DAMPER MINI   MUM POSITION    IAQ MAXIMUM  POSITION   set higher than  minimum position     IAQ READING IS  ABOVE SETPOINT    IAQ SETPOINT    OUTDOOR AIR  SUITABLE LED    FREE COOLING SETPOINT   A Completely counterclockwise  D Completely clockwise    FIGURE 20    Free Cooling Setpoint   Outdoor air is considered suitable when temperature and  humidity are less than the free cooling setpoints shown in 
33. figure 20     Note   DCV Max must be set higher than economizer mini   mum position setting for proper demand control ventilation     CHART 1  CALCULATE MINIMUM FRESH AIR PERCENTAGE  MIXED AND RETURN AIR TEMPERATURE      F  20  10 0 10 20 30 40     E  23  18  12  7  1 4    60 70 80 90 100   F  16 1 27 32 38         C   B       10       20       30    30       40    40       50    50       60        lt       05       ra  LL     z               ui        60    PERCENT FRESH AIR       70    70       80    80       90                      100    F  20  10 0 10 20 30 40    C  29  23   18  12  7  1 4       90                100  60 70 80 90 100   F  16 21 27 32 38   C    OUTDOOR AIR TEMPERATURE       Economizer Operation    The occupied time period is determined by the thermostat  or energy management system     Outdoor Air Not Suitable   During the unoccupied time period dampers are closed     During the occupied time period a cooling demand will  open dampers to minimum position and mechanical cool   ing functions normally     Page 30    During      occupied time period dampers will open to         MAX when IAQ reading is above setpoint  regardless of MANUAL OUTDOOR AIR DAMPER  thermostat demand or outdoor air suitability   SIDE VIEW    Outdoor Air Suitable           Loosen sheet metal screws  See table 19 for economizer operation with a standard two     to adjust damper position     stage thermostat  tighten screws when damp   er is in correct position     During the occupied pe
34. gure 18   Either air damper can be installed  in TCA units  Washable filter supplied with the outdoor air  dampers can be cleaned with water and a mild detergent   It should be sprayed with Filter Handicoater when dry prior  to reinstallation  Filter Handicoater is R P  Products coating  no  418 and is available as Lennox Part No  P 8 5069   D Supply and Return Diffusers  all units   Optional flush mount diffuser retum FD11 and extended  mount diffuser return RTD11 are available for use with all TCA  units  Refer to manufacturers instructions included with  transition for detailed installation procedures        LAOAD M  OUTDOOR AIR DAMPER    DAMPER  ASSEMBLY                               UNIT DIVISION  PANEL    SIDE VIEW    e    SHEET METAL  SCREWS    DAMPER  BLADES    FIGURE 18    E TAREMD Economizer   Field or Factory Installed     Unit may contain an optional factory installed three posi   tion economizer equipped with an A6 enthalpy control and  an A7 outdoor enthalpy sensor  The three position econo   mizer opens fully to use outdoor air for free cooling when  temperature is suitable and opens to minimum position  during the occupied time period     The      enthalpy control is located in the economizer ac   cess area  See figure 19  The A7 enthalpy sensor is located  on the division panel between horizontal supply and return  air sections     Page 28    ECONOMIZER CONTROLS    A6    AT ENTHALPY    ENTHALPY    SENSOR          FIGURE 19  Optional Sensors    An optional dif
35. iagram section for specific unit  operation     2 Freezestats S49 and S50    Each unit is equipped with a low temperature switch  freezes   tat  located on a return bend of each evaporator coil  S49   first circuit and S50  second circuit  are located on the  corresponding evaporator coils   Each freezestat is wired to the main control module A45   Each freezestat is a SPST N C  auto reset switch which  opens at 29  F   3  F   1 7       1 7  C  on a temperature drop  and closes at 58       4      14 4  C  2 2  C on atempera   ture rise  To prevent coil icing  freezestats open during  compressor operation to temporarily disable the re   spective compressor until the coil temperature rises   If the freezestats are tripping frequently due to coil icing   check the air flow   filters  economizer position and unit  charge before allowing unit back in operation  Make sure to  eliminate conditions which might promote evaporator ice  buildup   3 High Pressure Switches S4 and S7   optional   The high pressure switch is a manual reset SPST N C  switch  which opens on a pressure rise  Each switch is located in the  compressor discharge line and is wired in series with the com   pressor contactor coil   When discharge pressure rises to 450   10 psig  3103    69 kPa   indicating a problem in the system  the switch  opens and the respective compressor is de energized   the economizer can continue to operate    4 Low Ambient Switches S11  amp  S84   optional   The low ambient switch is an a
36. int    A     40  F   4 C shown      Measure return air temperature  Mark that point on the  top line of chart 1 and label the point  B   74 F  23      shown          1    5  Measure mixed air  outdoor and return air  tempera   ture  Mark that point on the top line of chart 1 and label  point  C   70  F  21  C shown      6  Draw a straight line between points A and B     7  Draw a vertical line through point C     8  Draw a horizontal line where the two lines meet  Read  the percent of fresh air intake on the side     9  If fresh air percentage is less than desired  adjust MIN  POS SET potentiometer higher  If fresh air percentage  is more than desired  adjust MIN POS SET potentiom   eter lower  Repeat steps 3 through 8 until calculation  reads desired fresh air percentage     DCV Set and Max Settings  Adjust settings when an optional IAQ sensor is installed     The DCV SET potentiometer is factory set at approxi   mately 5096 of the potentiometer range  Using a standard  1 2000ppm        sensor  dampers will start to open when  the IAQ sensor reads approximately 1000ppm  Adjust  the DCV SET potentiometer to the approximate setting  specified by the controls contractor  Refer to figure 20     The DCV MAX potentiometer is factory set at approxi   mately 50  of the potentiometer range or 6VDC  Damp   ers will open approximately half way when CO   rises  above setpoint  Adjust the DCV MAX potentiometer to  the approximate setting specified by the controls con   tractor  Refer to 
37. ioning belts shortens belt and bearing life  Check  belt tension as follows     1  Measure span length X  See figure 9     2  Apply perpendicular force to center of span  X  with  enough pressure to deflect belt 1 64  for every inch of  span length or 1 5mm per 100mm of span length     Example  Deflection distance of a 40  span would be  40 64  or 5 8     Example  Deflection distance of a 400mm span would  be 6mm    Measure belt deflection force  For a used belt  the  deflection force should be 5 Ibs   35kPa   A new belt  deflection force should be 7 Ibs   48kPa     A force below these values indicates an underten   sioned belt  A force above these values indicates an  overtensioned belt     MEASURE BELT TENSION    CD  1          DEFLECTION 1 64  PER INCH OF SPAN  OR 1 5mm PER 100mm OF SPAN    FIGURE 9       Page 18    D Optional Electric Heat Components   Tables 9 and 10 show all possible TCA to EHA matchups and  electrical ratings    All electric heat sections consist of electric heating ele   ments exposed directly to the airstream  See figure 10   EHA parts arrangement is shown in figures 11 and 12   Multiple stage elements are sequenced on and off in re   sponse to thermostat demand     HEAT SECTION PLACEMENT             CE                       Exc          ELECTRIC HEAT SECTION   behind hinged panel        FIGURE 10   1 Electric Heat Relay K9  Electric heat relay K9 is a N O  SPST pilot relay located on  the main control panel  figure 2   K9 electrically isolates  the 
38. l characteristics 208 230V  460V or 575V   60 hertz   3 phase    NOTE   Net capacity includes evaporator blower motor heat deduction  Gross capacity does not include evaporator blower motor heat deduction    1 Certified in accordance with the ULE certification program  which is based on ARI Standard 340 360  95  F  35  C  outdoor air temperature and 80  F  27  C  db 67  F  19  C   wb entering evaporator air  minimum external duct static pressure    2 Integrated Part Load Value rated at 80  F  27  C  outdoor air temperature  80  F  27  C  db 67  F  19  C  wb indoor air temperature    3 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270      Maximum usable output of motors furnished by Lennox are shown  In Canada  nominal motor output is also maximum usable motor output  If motors of comparable output  are used  be sure to keep within the service factor limitations outlined on the motor nameplate           Page 2    SPECIFICATIONS  General Nominal Tonnage 7 5 Ton 8 5 Ton 10 Ton  Data Model No  TCA090H2B TCA102H2B  Cooling Gross Cooling Capacity   Btuh  kW  93 000  27 2  106 000  31 0  126 000  36 9   Performance 1Net Cooling Capacity           kW  90 000  26 4  103 000  30 2  120 000  35 2   ARI Rated Airflow   cfm  L s  3000  1415  3400  1605  3800  1795   Total Unit Power  kW  8 0 9 2 10 9  1 EER  Btuh Watt  11 0 11 0 11 0  2 Integrated Part Load Value  Btuh Watt  11 4 11 4 11 4    Refrigerant Charge Circuit 1 8 Ibs  8 oz   3 86       8 
39. lectric Heat Total Unit   Electric Heat  odel No  with Power Exhaust Fan with Power Exhaust Fans   amp  Net Weight Steps Input Input Output          TCA090 TCA102 TCA090 TCA102  7 5 kW 1 208  I 1 220 090H   43  EHA102 7 5   27 Conse an 50 60  208 230V  99J01 1 240  1 440  460V 1 460  59702 22 25 30  1 480  575V 1 550  99J03 090H   17 102H   18  1 575 090S   18 1025   19 20 20  31 Ibs   14 kg  1 600  15        1 208  1 220        150 15            58 58  208 230  99704    2  1 440  460   1 460  Sosis 29 29 30 30  1 480  575V 1 550  99J06 1 575 23 23 25 25  31 Ibs   14 kg  1 600  22 5 kW 22 208  2  EHA360 22 5 2 220  22 230  208 230V 2  99J28 2 2  22 440  460   22 460  9926 40 40 40 40  22 480  575V 22 550  99J30 22 575 32 32 35 35  38 Ibs   17 kg  22 600  30 kW 22 208 76 800  22 220 86 000  EHA150 30  22 530 93 900 103 103 110 110  208 230   2  3907 2 240 102 400  22 440 86 000  460V 22 460 93 900       51 51 60 60  22 480 102 400  225 22 550 86 000  22 575 93 900 41 41 45 45  38 Ibs   17 kg  22 600 102 400  45 kW 22 208 115 300  22 220 129 000  EHA150 45    22 m 141 000 148 148 150 150  208 230   2  39910 2 240 153 600  22 440 37 8 129 000  460V 2         2 460 41 3 141 000 74 74  22 480 45 0 153 600  REN 22 550 37 8 129 000  22 575 41 3 141 000 59 59 60 60  42 Ibs   19 kg  22 600 45 0 153 600    1 Fuse block must be ordered extra  Factory installed heaters will have the fuse block factory installed  Fuse block must be installed in field installed heaters  Also requires    LT
40. les to the holes located in the unit base rail  two holes at  each comer   Refer to the installation instructions for the prop   er rigging technique     AWARNING    Improper installation  adjustment  alteration  service       maintenance can cause property damage  person   al injury or loss of life  Installation and service must  be performed by a qualified installer or service  agency        WARNING    Refrigerant can      harmful if it is inhaled  Refrigerant  must be used and recovered responsibly     Failure to follow this warning may result in person   al injury or death     Technical  Publications       Page 1       ELECTROSTATIC DISCHARGE  ESD   Precautions and Procedures    A CAUTION    Electrostatic discharge can affect electronic  components  Take precautions during unit instal   lation and service to protect the unit s electronic  controls  Precautions will help to avoid control    exposure to electrostatic discharge by putting  the unit  the control and the technician at the  same electrostatic potential  Neutralize electro   static charge by touching hand and all tools on an  unpainted unit surface before performing any  service procedure        Table of Contents    Specifications                                   2                  2 0  usuy usss chee       vee      4  Electrical Data                                  6  Blower Data                                    8  I Unit Components                              12     Placement and Installation             
41. ll thermostat wiring is connected to  terminal block TB1 located in the control box of the unit   Each thermostat has additional control options available   See thermostat installation instructions for more detail   1  Electro mechanical thermostat  13F06   The electro mechanical thermostat is a two stage heat    two stage cool thermostat with dual temperature levers   A non switching or manual system switch subbase  may be used   2  Electronic thermostat  see price book   Any two stage heat   two stage cool electronic ther   mostat may be used   3  Honeywell T7300 thermostat  60L59   The Honeywell T7300 thermostat is a programmable  in   ternal or optional remote temperature sensing thermo   stat  The T7300 provides occupied and unoccupied  changeover control     Il Smoke Detectors A17 and A64    Photoelectric smoke detectors are a factory installed op   tion  The smoke detectors can be installed in the supply air  section  A64   return air section  A17   or in both the supply  and return air section     J Blower Proving Switch 552   The blower proving switch monitors blower operation and  locks out the unit in case of blower failure  The switch is  N O  and closes at  14  W C   34 9 Pa  The switch is  mounted on the upper left hand corner of the blower deck     K Dirty Filter Switch S27    The dirty filter switch senses static pressure increase indi   cating a dirty filter condition  The switch is N O  and closes  at 1  W C   248 6 Pa  The switch is mounted on the top filte
42. nd  K2     IE ET cx     D olol     2                                                                                                                                                                                           S  oloo                                      S                                                                         FIGURE 2    Page 11    I UNIT COMPONENTS    AWARNING    Electric shock hazard  Can cause injury    or death  Before attempting to perform  any service or maintenance  turn the  electrical power to unit OFF at discon   nect switch es   Unit may have multiple  power supplies        The TCA unit components are shown in figure 1  All units  come standard with removable panels  All L1  L2  and L3  wiring is color coded  L1 is red  L2 is yellow  and L3 is blue     A Control Box Components    TCA control box components are shown in figure 2  The  control box is located in the upper left portion of the com   pressor compartment     1 Disconnect Switch S48  Optional all units    All units may be equipped with an optional disconnect switch  S48 or circuit breaker CB10  S48 and CB10 are toggle  switches  which can be used by the service technician to dis   connect power to the unit     2 Control Transformer T1  all units     All use a single line voltage to 24VAC transformer  mounted in the control box  Transformer supplies power  to control circuits in the unit  The transformer is rated at           and is protected by a 3 5 amp circuit breaker      
43. nts are taken     2  With all access panels in place  measure static pres   sure external to unit  from supply to return   Measure  static in duct below roof curb if roof curb is used     3  Refer to blower tables in BLOWER DATA  table of con   tents  in the front of this manual  Use static pressure and  RPM readings to determine unit air volume     4  The blower RPM can be adjusted at the motor pulley   Loosen Allen screw and turn adjustable pulley clock   wise to increase CFM  Turn counterclockwise to de   crease CFM  See figure 8  Do not exceed minimum and  maximum number of pulley turns as shown in table 7     TABLE 7  MINIMUM AND MAXIMUM PULLEY ADJUSTMENT    Minimum Maximum  Turns Open Turns Open      8 amp dm          9      No minimum number of turns open when B belt is used on  pulleys 6  O D  or larger        Blower Belt Adjustment    Maximum life and wear can be obtained from belts only if  proper pulley alignment and belt tension are main   tained  Tension new belts after a 24 48 hour period of  operation  This will allow belt to stretch and seat  grooves  Make sure blower and motor pulley are aligned as  shown in figure 7     PULLEY ALIGNMENT  ALIGNED    pud em        BLOWER      PULLEY BELT    MOTOR  PULLEY    NOT ALIGNED    FIGURE 7       Page 17    TO INCREASE BELT TENSION    1 Loosen four bolts securing motor base to mounting  frame     ALIGN TOP EDGES  PARALLEL BEFORE  TIGHTENING MOTOR    IN PLACE   gt  lt     2 Turn adjusting bolt to the right  or clockwise 
44. onal or Canadian Electrical Code manual to determine wire  fuse and disconnect size requirements     8 5 TON STANDARD   HIGH EFFICIENCY  Model No     TCA102S    TCA102H       Line voltage data   60 Hz   3 phase 208 230      460      575V    208 230V    460V    575V       Compressors   2     Rated load amps   each  total  14 7  29 4     91  182     7 1  14 2   50  100     5 8  11 6   37  74     14 7  29 4   91  182     7 1  14 2   46  92     5 1  10 2   37  74           Locked rotor amps   each  total   Full load amps   each  total  24  4 8   Locked rotor amps   each  total  47  94     Condenser  Fan Motors  2     13  2 6   24  4 8     1 0  2 0   1 9  3 8     2 4  4 8   4 7  9 4     1 8  2 6   2 4  4 8     1 0  2 0   1 9  3 8        Evaporator  Blower  Motor    Motor Output   hp 2 3  kW   15 22  Fullload amps   7 5 10 6  Locked rotor amps   46 9 66    2 3  1 5 22  34 4 8   204   268    2 3  1 5 22  2 7 3 9   162   234    2 3  1 5 22  7 5 10 6   46 9 66    2 3  1 5 22  34 4 8   204   268    2 3  1 5 22  2 7 3 9   162   234       With Exhaust Fan 60 60  Less Exhaust Fan 60 60    1 Maximum Overcurrent  Protection  amps     30 30  25 30    20 25  20 20    60 60  60 60    30 30  25 30    20 20  20 20       With Exhaust Fan 48 51  Less Exhaust Fan 46 49    2 Minimum Circuit  Ampacity       24 25  22 27       19 20  18 19       48 51  46 49       24 25  22 24       18 19  17 18          Optional Power  Exhaust Fan     Number  Horsepower  W     1  1 3  249     Full load amps  Locked r
45. ontactor  coil  K16   When S20 opens  contactors  K15  K16  are  de energized  When the contactors are de energized  first  stage and all subsequent stages of heat are de energized   The limit is factory set to open at 220  F   6   F  104  C    3 3 C  on a temperature rise and can be manually reset  when temperature falls below 160  F  71 0 C      6 Terminal Strip TB3    Electric heat line voltage connections are made to termi   nal strip TB3  or a fuse block on some models  located in  the upper left corner of the electric heat vestibule     7             Elements         HE2  HE6        HE7    Heating elements are composed of helix wound bare  nichrome wire exposed directly to the airstream  Three  elements are connected in a three phase arrange   ment  The elements in 208 230V units are connected  in a  Delta  arrangement  Elements in 460 and 575V  units are connected in    Wye    arrangement  Each stage  is energized independently by the corresponding contac   tors located on the electric heat vestibule panel  Once  energized  heat transfer is instantaneous  High temper   ature protection is provided by primary and redundant  high temperature limits and overcurrent protection is  provided by fuses     8 Fuse F3    Fuse F3 are housed in a fuse block which holds three  fuses  Each F3 fuse is connected in series with each leg of  electric heat  Figure 11 and table 8 show the fuses used  with each electric heat section  For simplicity  the ser   vice manual labels the fuses F
46. ontacts K9 1 close ener   gizing timer DL2    7  After a 30 second delay  DL2 closes energizing contac   tor K16     8  N O  contacts K16 1 close allowing the second bank of  elements to be energized     END OF SECOND STAGE HEAT     9  Heating demand is satisfied  Terminal W2 in the ther   mostat is de energized     10  Electric heat contactor K16 is de energized     11   The second set of electric heat elements are de ener   gized     END OF FIRST STAGE HEAT     12  Heating demand is satisfied  Terminal W1 in the ther   mostat is de energized     13  Electric heat contactor K15 is de energized   14  The first set of electric heat elements are de energized     Page 37    ELECTRONIC      ELECTROMECHANICAL THERMOSTAT                  dS  E   5     ins   25     COMMON  COMMON      N RI IS USED WITH OPTIONAL MODULATING  ECONOMIZER FIELD KIT    D RIPTI  N  COMPONENT  SENSOR ELECTRONIC  Y CONTROL MODULE      REMOVE JUMPER WHEN RI IS USED    65     SENSOR CO2 1    ICMC3 I CLOCK TIME        JACK UNIT  ECONOMIZER    THERMOSTAT HEAT ANTICIPATION SETTING 0 1 AMP    INDICATES MICRO PROCESSER  K65   RELAY EXHAUST FAN     lt    DESIGNATES OPTIONAL WIRING   P3      PLUG LESS ECONOMIZER CLASS II FIELD WIRING     76      PLUG SENSOR  ECONOMIZER          WIRING DIAGRAM  12703             ONTRO    BLOWER 4 ONTR ACCESSORIES                                SUPPLT AIR     ELECTROMECHANICAL OR ELECTRONIC   TBI      TERMINAL STRIP 24V CLASS II THERMOSTAT FOR TCA TGA UNITS    TEMPERATURE CONTROL SECTI
47. otor amps    24  4 7     1  1 3  249   13  24     1  1 3  249   10  19     1  1 3  249   24  4 7     1  1 8  249   1 3  2 4     1  1 3  249   1 0  1 9          Service Outlet  2  115 volt GFCI  amp rating     15       15       15       15       15          15       NOTE   Extremes of operating range are plus and minus 10   of line voltage   1 HACR type breaker or fuse   2 Referto National or Canadian Electrical Code manual to determine wire  fuse and disconnect size requirements     Page 6    10 TON STANDARD   HIGH EFFICIENCY    ELECTRICAL DATA                Model No  TCA120S TCA120H  Line voltage data   60 Hz   3 phase 208 230V 460   575V 208 230V 460V 575V  Compressors Rated load amps   each  total    15 4  30 8  7 4  14 8  5 9  11 8  17 3  34 6  9 0  18 0  7 1  14 2   Q  Locked rotor amps   each  total  124  248  59 6  119 2  49 4  98 8  123  246  62  124  50  100   Condenser Full load amps   each  total  24  4 8  1 3  2 6  1 0  2 0  2 4  4 8  1 3  2 6  1 0  2 0   Fan Motors  2  Locked rotor amps   each  total    4 7  9 4  24  4 8  1 9  3 8  4 9  9 4  24  4 8  1 9  3 8   Evaporator Motor Output   hp   2 3 5 2 3 5 2 3 5 2 3 5 2 3 5 2 3 5  mower kW   1 5  22   37   15  22   37   15  22   37   15  22   37   1 5   2 2   37   1 5   2 2   3 7  Full load amps   7 5  10 6  16 7   34   4 8   7 6   27   3 9   6 1   7 5  10 6 16 7   3 4   4 8   7 6   2 7   39   6 1  Locked rotor amps  46 9   66  105  20 4  26 8  456   16 2  23 4  36 6  46 9  66   105  20 4  26 8  45 6   16 2  23 4 1
48. plicable  the board will  energize Y1  Y2 and Y3 in successive order  In the same  manner a Y2  will be interpreted as a Y1 Y2  The MCC  control also incorporates a minimum run time of 4 minutes  for up to 2 independent cooling stages  This 4 minute run  time can be interrupted by pushing SW1 located on the  board  If pressed for 3 seconds or more  the control goes  into TEST mode disabling AUTO STAGING  The MCC  control board is used for all T series units  A dip switch   factory set  is provided to configure to unit type  TGA  gas  TCA cooling electric heat  THA heat pump  See fig   ure 4     Page 12               1              No power to Check field wiring  If problem per   board  sists refer to service manual     Press MCC pushbutton and    Processor error     hold for three seconds to reset    processor      Flashes  Flashes   Invalid unit DIP Make sure switches are set  Rapidly   switch selected    correctly  Refer to figure 4     Simultaneous  heat and cool  Rapidly demands     Flashes    Check thermostat and wiring         Press pushbutton and immediately release to override the  4 minute compressor minimum run time     UNIT TYPE DIP SWITCH  FACTORY SET     TGA UNITS    THA UNITS UNUSED   HEARTBEAT LED WILL FLASH  RAPIDLY IN ERROR        FIGURE 4    MCC CONTROL BOARD  A45           HHHHHHH                RW1 Y1 C G BL W2       OUT             YI                   Ye                   Y3                                        Y4                WI                W2   
49. ply and Return    Net Weight    Blower Proving Switch   Dirty Filter Switch   L Connection Network   Smoke Detector   Supply  Smoke Detector   Return   PVC Condensate Drain Trap  Copper Condensate Drain Trap  High Pressure Switch  Compressor Crankcase Heater  Low Ambient Kit   Economizer   Net Weight    Economizer Outdoor Air Hood   Net Weight  Number and Size of Filters    Economizer Enthalpy Control   Differential  Economizer Enthalpy Control   Outdoor    Down Flow Barometric Relief Dampers   Net Weight  Hood for Down Flow LAGED    Horizontal Barometric Relief Dampers   Net Weight    LED ACCESSORIES    TACGKGC10 15  TAHGKGC10 15  LTHSDKGC10 15    RTD11 135  205 Ibs   93 kg     FD11 135  174 1     79 kg     LASRT10 12  32 Ibs  15 kg     LTABPSK  LTADFSK  See Engineering Handbook  LTASASDK10 36  LTRASDK 10 30  LTACDKP03 36  LTACDKC03 36  TAHPK10 15  TACCHK10 15  TALAK10 15  TAREMD10 15   47 Ibs   21 kg     LAOAH10 15   11 Ibs   5 kg    2  16 x 25 x 1 in   406 x 635 x 25 mm     LTADEK03 36  LTASEKO03 36  LAGED10 15   8 lbs   4 kg   LAGEHO09 15                   15   8 Ibs   4 kg     RTD11 95  88 1  5   40 kg     FD11 95  75 Ibs   34 kg     LASRT08 10  30 Ibs  14 kg     RTD11 185  392 Ibs   178 kg     FD11 185  289 Ibs   131 kg     LASRT15  36 Ibs   16 kg        Outdoor  Air  Dampers    Damper Section  down flow    Automatic   Net Weight  Damper Section  down flow    Manual   Net Weight    Outdoor Air Hood  down flow  Net Weight  Number and Size of Filters    Power Exhaust Powe
50. r  channel corner     Page 32    Vil Wiring Diagrams and Sequence of Operation          090 150 UNIT DIAGRAM    From TBI R     lt                           0  e                               NOTE FOR USE WITH COPPER CONDUCTORS ONLY  REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT  AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE    USED ON  M  VOLTAGE UNITS AND UNITS WITH  HIGH EFFICIENCY MOTORS                         AI7 AND A64 ARE FIELD INSTALLED OPTIONS  DH400          REMOVE WIRE WHEN USING OPTIONAL  SMOKE DETECTOR         HRI  HR2 ARE OPTIONAL    WARNING    ELECTRIC SHOCK HAZARD  CAN CAUSE INJURY  OR DEATH  UNIT MUST BE GROUNDED IN  ACCORDANCE WITH NATIONAL AND LOCAL CODES     4132               ANY WIRE IN THIS APPLIANCE IS  REPLACED  IT MUST BE REPLACED WITH      52 WIRE OF LIKE SIZE RATING  INSULATION  THICKNESS AND TERMINATION   DISCONNECT ALL POWER BEFORE SERVICING           DESIGNATES OPTIONAL WIRING  CLASS II FIELD WIRING    WIRING DIAGRAM                ae T      G ECONOM         HAR   COMBINATION PACKAGEDZROOF IOP    H R COI    TCA  TGA 090  102  120  150 6             101  JACK SMOKE D                    AIR B          JACK SMOKE DETECTOR SUPPLY AIR                SWITCH FREEZESTAT  COMPRESSOR     n  JTS AGED JL OV WER  amp  COOL                   _____ISWITCH FREEZESTAT  COMPRESSOR 2   A 00         584         ISWIICH LOW PRESS LOW         COMP 2 N New Form No   HEA E      TIRANSFORMER CONTROL 4 554  476W  tes TJACK ECONOMTZER HARNESS   TET     TERMINAL  STRI
51. r Exhaust Fan   Net Weight    Electrical  Accessories    HACR Circuit Breaker  Disconnect Switch  GFI Service Outlets    TAOADM10 15   31 Ibs   14 kg   LAOAD10 15   26 Ibs   12 kg     LAOAH10 15   11 Ibs   5 kg    2  16 x 25 x 1 in   406 x 635 x 25 mm     LAPEF 10 15   28 Ibs   13 kg   TAHBK10 15    indicate size   TADK10 15 80  80A  TADK10 15 150  150A   LTAGFIK10 15    Filters MERV 11 High Efficiency AFK 11  18 x 24 x 2 specify four per unit     Indoor Air  Quality  CO2   Sensors    Standard  Roof Curbs    Cliplock 1000  Roof Curbs    CO   Sensor Duct Mounting Kit  Sensor   white case CO   display  Sensor   white case no display  Sensor   black case        display  Sensor   duct mount  black  no display  Aspiration Box for duct mounting  Handheld        Monitor   14 in   356 mm  height   Net Weight  24 in   610 mm  height   Net Weight  14 in   356 mm  height   Net Weight  18 in   457 mm  height   24 in   610 mm  height   Net Weight    Page 4    LTIAQSDMKO03 36  LTAIAQSWDKO03 36  LTAIAQSWNO3 36  LTAIAQSNDO03 36  LTAIAQSDMBNO03 36  LTIAQABD03 36  LTAIAQSHM03 36              0 15 14   126 Ibs   57 kg   LARMF10 15 24   174 Ibs   79 kg               0 158 14   126 Ibs   57 kg               0 158 18              0 158 24   174 Ibs   79 kg        OPTIONAL ELECTRIC HEAT ACCESSORIES       UNIT FUSE BLOCKS WITH ELECTRIC HEAT       Unit Model No        0905       090         1025       102         1205       120         1505  Blower Motor Size 2 hp  1 5 kW    2 hp  1 5 kW    2 hp  1 5
52. rical wiring  both field and factory installed  for loose connections  Tighten as required  Refer to unit  diagram located on inside of compressor access panel    3  Check to ensure that refrigerant lines are in good  condition and do not rub against the cabinet or other  refrigerant lines    4  Check voltage at the disconnect switch  Voltage must  be within the range listed on the nameplate  If not   consult the power company and have the voltage cor   rected before starting the unit    5  Recheck voltage and amp draw with unit running  If  voltage is not within range listed on unit nameplate   stop unit and consult power company  Refer to unit  nameplate for maximum rated load amps    6  Inspect and adjust blower belt  see section on Blower  Compartment   Blower Belt Adjustment      B Operation    1  Initiate first and second stage cooling demands ac   cording to instructions provided with thermostat     2  First stage thermostat demand will energize compres   sor 1  Second stage thermostat demand will energize  compressor 2  On units with an economizer  when out   door air is acceptable  a first stage demand will ener   gize the economizer  a second stage demand will en   ergize compressor 1     3  Units contain two refrigerant circuits or stages  See fig   ure 13     REFRIGERANT STAGES    CONDENSER  FAN 1    CONDENSER COIL  STAGE 2     BOTH FANS ARE  ENERGIZED  WITH A Y1 DEMAND     FIGURE 13       4  Each refrigerant circuit is separately charged with  HCFC 22 refrigerant
53. riod  dampers will open to DCV  MAX when        reading is above setpoint  regardless of DAMPER  thermostat demand or outdoor air suitability   DCV MAX BLADES  will NOT override damper full open position  When an R1  mixed air sensor for modulating dampers is installed  DCV  MAX may override damper free cooling position when oc   cupancy is high and outdoor air temperatures are low  If R1  senses discharge air temperature below 45 F  7 C   FIGURE 21  dampers will move to minimum position until discharge air   temperature rises to 48  F  9 C   DAMPER MOTOR       B Outdoor Air Dampers THUMBWHEEL    Optional manual and motorized outdoor air dampers pro   vide fresh outdoor air  The motorized damper assembly  opens to minimum position during the occupied time peri   od and remains closed during the unoccupied period   Manual damper assembly is set at installation and re   mains in that position  See figure 21     Set damper minimum position in the same manner as  economizer minimum position  Adjust motorized damper  position using the thumbwheel on the damper motor  See  figure 22  Manual damper fresh air intake percentage can  be determined in the same manner  FIGURE 22       TABLE 19  ECONOMIZER OPERATION  OUTDOOR AIR IS SUITABLE FOR FREE COOLING   FREE COOL LED               DAMPER POSITION  THERMOSTAT DEMAND MECHANICAL COOLING  UNOCCUPIED OCCUPIED  OFF NO    CLOSED CLOSED  G CLOSED MINIMUM NO  OPEN  OPEN  N    Y1        Dampers will modulate to maintain 55  F  13      supply 
54. tem    If weighing facilities are not available  or to check the  charge  use the following procedure        1  Attach gauge manifolds and operate unit in cooling  mode until system stabilizes  approximately five min   utes   Make sure outdoor air dampers are closed     2  Check each system separately with all stages operat   ing    3  Use a thermometer to accurately measure the outdoor  ambient temperature     4  Apply the outdoor temperature to tables 11 through 17  to determine normal operating pressures     5  Compare the normal operating pressures to the pres   sures obtained from the gauges  Minor variations in  these pressures may be expected due to differences  in installations  Significant differences could mean that  the system is not properly charged or that a problem  exists with some component in the system  Correct  any system problems before proceeding     Page 24    6  If discharge pressure is high  remove refrigerant from TABLE 15  the system  If discharge pressure is low  add refriger        1205 NORMAL OPERATING PRESSURES          ant to the system  e d CIRCUIT 1 CIRCUIT 2     in i Entering   Dls   10 Suct   5 Dis   10 Suc   5  Add or remove charge in increments  Air Temp    Allow the system to stabilize each time refrigerant 65     169 74 176 77  is added or removed  75     195 77 203 79  7  Use the following approach method along with the nor  85  F  mal operating pressures to confirm readings  95  F 81  105  F   283             11 115     319 84 340 84  
55. th a 24       coil used to energize the indoor  blower motor B3 in response to blower demand  K3 is ener   gized by the MCC board A45     8 Condenser Fan Relay K10  Condenser fan relay K10 is a DPDT relay with a 24VAC coil   K10 energizes condenser fans B4 and B5     9 Power Exhaust Relay K65  PED units     Power exhaust relay K65 is a          relay with    24         coil  K65 is used in all TCA units equipped with the op   tional power exhaust dampers  K65 is energized by the  economizer enthalpy control A6  after the economizer  dampers reach 5096 open  adjustable  When K65  closes  exhaust fan B10 is energized     10 MCC Control A45    The main control module A45  figure 5  controls all cool   ing operation and serves as a staging point for all internal  inputs to the appropriate components of the TCA unit  The  MCC control receives and sends out 24 volts to the com   ponents located in the TCA control box  economizer and  supply return compartments  The control communicates to  compressors contactors K1  K2   condenser fan relay K10 and  indoor blower contactor K3  Thermostat hook ups  TB1  and  accessory low voltage hook ups  TB14  are located on the  board  See tables 2 and 3 for terminal designations  Tables 4   5 and 6 show pin terminal designations     Features    The MCC A45 is equipped with a green LED for board sta   tus  See table 1 for LED flash codes  While in the cooling  mode the board will incorporate AUTO STAGING  If the  board receives a Y3 demand  if ap
56. tputs RPM Range    Drive 4    kW kW  2 3      680   925 895   1120  WEE   680   925 895   1120 1110   1395                                           Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required  Maximum usable output  of motors furnished by Lennox are shown  In Canada  nominal motor output is also maximum usable motor output  If motors of comparable output are used  be sure to keep  within the service factor limitations outlined on the motor nameplate           CEILING DIFFUSER AIR THROW DATA POWER EXHAUST FANS PERFORMANCE     Effective Throw Range Return Air System  Air Volume    Model No  RTD11 Step Down   FD11 Flush Static Pressure  in  w g          Air Volume Exhausted       0 05  0 10  0 15  0 20  0 25  0 30  0 35            6000   2830   44 54   13 17   40 50  12 15  6200   2925   45 55   14 17   42 51  13 16  6400   3020   46 55   14 17   43 52  13 16  6600   3115   47 56   14 17   45 56  14 17    150          Throw is the horizontal or vertical distance an air stream travels on leaving the  outlet or diffuser before the maximum velocity is reduced to 50 ft   15 m  per miute   Four sides open     Page 9    BLOWER DATA    ACCESSORY AIR RESISTANCE    Wet Indoor Coil MERV 11    Air Volume 090  102 1205  120   1505 Electric Heat Economizer Filter    in  w g                    AIR RESISTANCE   CEILING DIFFUSERS  RTD11 Step Down Diffuser FD11 Flush   2 Ends Open 1 Side  2 Ends Open   All
57. uctions for  details of proper assembly and mounting  The roof mounting FIGURE 16  frame MUST be squared to the roof and level before mount    ing  Plenum system MUST be installed before the unit is set on   the mounting frame  Typical roof curbing and flashing is shown   in figure 17  Refer to the roof mounting frame installation in    structions for proper plenum construction and attachment        Page 27    TYPICAL FLASHING DETAIL  UNIT BASE  BOTTOM            UNIT BASE  RAIL    FIBERGLASS  INSULATION   Furnished           COUNTER FLASHING  NAILER STRIP  Field Supplied      Furnished   CANT STRIP   Field Supplied     RIGID INSULATION   Field Supplied        MOUNTING FRAME   Extends around entire  perimeter of unit     ROOFING   MATERIAL  FIGURE 17  B Transitions  Optional supply return transitions LASRT08 10 is avail   able for use with the TCA 7 5 ton units and LASRT10 12  is available for the 7 5 and 10 ton units  utilizing optional  LARMF 10 15 roof mounting frames  TCA 12 5 ton units  will use LASRT15 with LARMF10 15 roof mounting  frame  Transition must be installed in the LARMF  mounting frame before mounting the unit to the frame   Refer to the manufacturer   s instructions included with the  transition for detailed installation procedures     C LAOAD M  Outdoor Air Dampers  LAOAD M 10 15 used      TCA090S 150 units consists of a  set of dampers which may be manually or motor  M  oper   ated to allow up to 25 percent outside air into the system at  all times  see fi
58. unit s 24V circuit from the electric heat 24V circuit 9 is  energized by main control A45 which in turn energizes  timer DL2    2 Time Delay DL2   DL2 is a factory installed solid state timer used in   22 5 to 60 kW electric heat units  DL2 is located on the  main control panel  figure 2   DL2 allows staging by  providing a timed interval between the first and sec   ond heating elements  When the timer is energized   the contacts are delayed for 30 seconds before clos   ing  When the timer is de energized  the contacts are  delayed 1 second before opening    3 Contactors K15  K16  Contactors K15 and K16 are three pole double break  contactors located on the electric heat vestibule  All    the system  contactor K15 is de energized  When K15 is  de energized  first stage and all subsequent stages of  heat are de energized  For EHA102 150 units  the high  temperature limit is factory set to open at 170  F   5  F   76  C   2 8      on a temperature rise and automatical   ly reset at 130  F   6 F  54 4   C   3 3  C  on a tempera   ture fall  For EHA100 units  the limit is factory set to  open     160  F   5  F  71 0  C   2 890       a tempera   ture rise and automatically reset at 120  F   6  F   49 0  C   3 3        on a temperature fall  The limit is not  adjustable     5 High Temperature Limit S20  Secondary     520 is a SPST        manual reset thermostat   Like the  primary temperature limit  S20 is wired in series with the  first stage contactor coil  K15  and second stage c
59. ure 6  Two draw through type condenser fans are  used in TCA090 150 units  All units are equipped with belt   drive blowers which draw air across the evaporator during  unit operation     Cooling may be supplemented by a factory  or field   installed economizer  The evaporators are slab type  and are stacked  Each evaporator uses a thermostatic ex   pansion valve as the refrigerant metering device  Each  evaporator is also equipped with enhanced fins and rifled tub   ing  In all units each compressor is protected by a freezestats   on each evaporator   Low ambient switches  S11  S84   and high pressure switches  S4  S7  are available as an op   tion for additional compressor protection     1 Compressors B1 and B2               090 150 units use two scroll compressors  Com   pressor capacity may vary from stage to stage  In all cases   the capacity of each compressor is added to reach the total  capacity of the unit  See  SPECIFICATIONS  and  ELEC   TRICAL DATA   table of contents  or compressor name   plate for compressor specifications        WARNING    Electrical shock hazard  Compressor must be  grounded  Do not operate without protective cover  over terminals  Disconnect power before removing       protective cover  Discharge                    before          vicing unit  Failure to follow these precautions could  cause electrical shock resulting in injury or death        Each compressor is energized by a corresponding com   pressor contactor   NOTE Refer to the wiring d
60. uto reset SPST N O  pres   sure switch which allows for mechanical cooling opera   tion atlow outdoor temperatures  In all models a switch  is located in each liquid line prior to the indoor coil sec   tion   In the TCA090 150  511 and S84 are wired in parallel with  outdoor fan relay K10  compressor one    When liquid pressure rises to 275   10 psig  1896   69  kPa   the switch closes and the condenser fans are en   ergized  When discharge pressure in both refrigerant cir   cuits drops to 150   10 psig  1034   69 kPa   the switches  open and the condenser fans are de energized  This inter   mittent fan operation results in higher evaporating temper   ature allowing the system to operate without icing the evap   orator coil and losing capacity     Page 16    C Blower Compartment   The blower compartment      all TCA090 1508 units is lo   cated between the evaporator coil and the condenser coil sec   tion  The blower assembly is accessed by disconnecting the  blower motor  See Blower Access in the Operation   Adjust   ment section  The blower pulls out as shown in figure 8     1 Blower Wheels    All TCA090 150 units have one 15 in  x 15 in   381 mm x 381  mm  blower wheel     2 Indoor Blower Motor B3   All units use three phase single speed blower motors  CFM  adjustments are made by adjusting the motor pulley  sheave    Motors are equipped with sealed ball bearings  All motor spec   ifications are listed in the SPECIFICATIONS  table of con   tents  in the front of this manual
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
取扱説明書 電気カーペット FHC-20C-M  Draper Envoy  71M653X - Software User`s Guide  Multi-Tech Systems Computer Drive MTD-EVe User's Manual  Novus LM arm 0-0-1 WH  STIGA PARK  Graco ISPP077AD User's Manual  LG WM3001H*A User's Manual  Manual de instalación, funcionamiento y  VIP Kit 16 channel software manual    Copyright © All rights reserved. 
   Failed to retrieve file