Home

Service Manual - Appliance Factory Parts

image

Contents

1. For Concrete or similar type wall make holes into the wall and insert concrete nails instead of screws MOUNTING THE INDOOR UNIT The Indoor unit must be mounted before connecting the indoor outdoor wire drain hose and copper tubing To mount follow the procedures below 1 The tubing can be extended in 4 directions as shown below No cutting is necessary for left rear and right rear tubing connections If using left or right tub ing connections remove the plastic area with a hack saw so pipes can go through Left Rear 2 Make sure the drain hose and copper tubing are wrapped with the rubber insulation Using the tape wrap the indoor outdoor wire copper tubing and drain hose together CAUTION Make sure the Indoor units cord is not connect ed to AC power when performing these procedures Be sure to comply with local codes on running a wire from the indoor to the outdoor unit DO NOT LET THE INDOOR OUTDOOR WIRE COME IN DIRECT CONTACT WITH THE TUBING OR HOSE 3 Shape the tubing so it can easily go through the hole in the wall Push the indoor outdoor wire copper tub ing and drain hose through the hole in the wall angling downward Situate the indoor unit on the wall bracket by lifting the indoor unit slightly above the wall bracket and then down so it is securely locked in
2. Air and moisture remaining in the refrigerant system may create adverse conditions as indicated below pressure in the system rises operating current rises cooling efficiency drops moisture in the refrigerant circuit may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Therefore the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondesables and moisture from the system AIR PURGING WITH VACUUM PUMP TEST RUN Confirm each tube narrow and wide tubes between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed Remove the valve caps from the wide and narrow service valves on the outdoor unit Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage shipping position Charge Hose Leak Test 1 With the service valves on the outdoor unit remaining closed remove the threaded cover on the wide tube service port Save for reuse 2 Attach a manifold valve with pressure gauge and dry nitro gen gas cylinder to this service port with charge hoses Nitrogen Gas Cylinder Vertical Position CAUTION Be sure to use a manifold valve for air purging If it is not avail able use a stop valve for this purpose The Hi knob of the manifold valve must always be kept closed
3. AC250V SF64G 6A 200V 04 F3 Y 200V5A uH Vs DC30V HER503 2 4 12 R11 M 5 1K 4W cc2 1W 1KV DC 104 50V 3 M CE4 SD 4W 470uF 50V RX Ve DC15V 200V 2A F4 VC UF2003 3 3uH DC12V HER203 05 DC21V IC2 IC3 aca 7812 Y ECH CE7 j CC4 220uF 104 104 9 221K 35V 220uF sov 100 coy 1KV DC SD SOV 25v 25V SD SD 330uF 35V RX e e 4148 E R10 270 Vs DC30V R6 de R7 CC6 10 Ohm 104 50 R9 Ve DC15V VC il 110KF 0 396 CN2 Ref 2 5V DC12V vs DC30V KIA431AZ ka 5 IC4 E GND OT 0 5 Of 12 COMP GO TO INDOOR PCB MODEL DSA 123U 152U 183U 240U DATE 2003 1 Location Part Code Part Name Description BZ1 3105698200 BUZZER DP 2520BA CA1 CN5XD104M C ARRAY 6P F5 X 1042 CA2 CN4XD104M C ARRAV 5P F4 X 1042 CN3XD104M CCXE1H104M C ARRAY 4P F3 X 104Z 104 5OVDC CCXE1H104M 104M 5OVDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H104M CCXE1H103M 104M 50VDC 103M 50VDC CCXE1H103M 103 CCXE1H103M 103M 50VDC CCXE1H103M 103M 50VDC CCXE1H104M 104M 50VDC CEXE1E107C CEXE1E107C 100UF 25V 100UF 25V CEXE1C106A 10MF 16V SS CEXE1C475A 4 7MF 50V SS CEXE1E476C 47UF 25V SG 31088
4. JS3 open short F R21 R23 Indoot Fan Motor RPM select option with A D signal Buzzer Driving 10 KID 65004 DESCRIPTION Micom 34 Terminal put out Buzzer Driving Pulse its output is driving Buzzer through Buffer Ocillatorv Frequency of buzzer is selected by internal Micom This unit is setting at 4KHz Stepping Motor Driving 12 7 KID65004 DESCRIPTION There are one Stepping Motor for Flap up and down and it is used 4 face Drive Method It is driving as following Fig 12 1 Ring Count Method of 8 Status Normal Rotating Reversed Rotating Fig 12 1 REMOTE CONTROLLER ASSMBLY FUNCTIONAL TEST METHOD TEST START No Power supplv again Power Supply Y Is Display at the beginning ON Select ON OFF button eginning Check the Following Yes BATTERY SPRING Is Display at the GE beginning ON Select Mode button No ERROR No Select FAN DIR button Is display the begining ON Y Select TEMP Button A Y Whenever you selectted Temp Button it is changed by 1 18 32 No D ERROR Select ON OFF button Y 41 Is LCD display OFF gt ERROR Select TIMER ON Button Is it normal gt ERROR Sele
5. R2 RI IK 1 2W test R7 IK es wi E 482 mild high RQ IK JS1 heat cool o VS DC30V w 4A 103J o RA3 CAS FEDD BACK o GND F3 1037 o Ve DC15V o 12V 1WAY 16 DC12V o COMP 2 JDM 5 3 14 BZ AWAY 4 13 ODM 5 GO TO OUTDOOR PCB amp REMOCON 82 6 x 20 COMP 7 65004 8 9 F5 1047 CCH 104 R23 cool low R21 cool high R37 6A 103J DC5V CE2 100uF 25V jer 104 CIRCUIT DIAGRAM DSA 123U 183U 240U TAS 12 14 28003 e TAS 15 Indoor Unit PCB CONTROL PCB LED QUICK 1364 OM cc12 104 CN5 CN8 s mi 9 8 HE ol ilel SEINE 13 65004 wl Ei i 2 E P77 HSO VDD 2 16 1 u 22 P75 SO XTIN P21 4 P74 SI INT5 STOP P2 5 P73 SCK P17 6 IDM P72 PDO PWM P16 7 P71INT4 2 15 L 8 J P70 INT3 TC3XPPC P14 9 9 o P07 DVO P13 R14 2 R13 P06 INT2 TC1 P12 2 R12 SC IK EU P05 INT1 P11 o REMOCON 2 CN4 10K R38 P04 INTO P10 MW IK R25 13 KS 23408 B B Em 03 AIN7 P67 usa FLO gs ok R26 CC13 14 EMERGENCY SW 7 f s PO2 AIN6 P66 JS4 R27 1K CC14 15 Get R40 10K P01 N5 P65 JS5 R28 IK COLE a 1 2 4 Bil 10K 0015 16 Leen N4 P64 103 5 CCI6 U TEST N3 P63 R36 R35 1
6. To connect the drain hose follow the procedures below 1 Connect the drain hose extension to the drain hose coming from the indoor unit by loosing the clamp on the extension using a phillips screwdriver attaching the hoses together and then tightening the clamp 2 Run the drain hose slanted downward outside If the drain pipe is exposed indoors make sure it is thoroughly insulated so condensation does not ruin walls or furniture or come in contact with the AC connection or exten sion Also do not crease or form a trap in the tub ing Insert Putty Drain Hose CONNECTING THE CABLES One electric power cable must be connected to the outdoor unit The indoor unit is connected to outdoor unit through the connection cable To install the cables follow as below 1 Open the connection cover on the indoor unit 2 Open the SVC cover on the side of outdoor unit 3 Connect the connection cable to terminal blocks of the indoor and outdoor unit as shown below Must be connected with the same terminal number of indoor and outdoor unit Be sure not to slip the cables out of terminal 4 Connect the power cable and earth cable 5 Reinstall the connection cover and the SVC cover 6 Install the conduit kit The conduit kit is optional Connetion Cable Indoor Unit Terminal Block 1231415 Outdo
7. 3 Wrap the piping joints with the insulator plate and fas ten it with vinyl tape pipe vinyl A After wrapping the connection pipe with tape fasten it to the outside wall with saddles etc Teen MOUNTING OUTDOOR UNIT 1 After selection the appropriate site position the outdoor unit and make sure the space around the outdoor unit See overview instruction of installation 2 Mount the outdoor unit on appropriate base using anchor bolts 3 Install the CUSHION RUBBER provided to prevent vibration and noise 4 If the outdoor unit is expose to direct sunlight or strong wind install shield around the outdoor units The outdoor unit must be installed on stable and rigid base End Eng Model TAS 12 15 18 TAS 24 APPLYING PUTTV AND INSERTING THE WALL After running the wires and tubing outside putty should be inserted around the opening on the outside to protect against rain wind etc To apply putty see below 1 Apply the putty to any area Apply Putty 2 After applying putty on the outside hole that air Here insert the wall Cap at Insert Putty or rain can get into Indoor side and Outdoor side Tubing Drain Hose Indoor side Wall Outdoor side Indoor Unit AIR PURGING
8. RESISTOR ARRAY RESISTOR ARRAY 6P 5 X 103J RA8K3103J RESISTOR ARRAV 31 Location Part Code Part Name Description BD1 DKBJ408G DIODE BRIDGE KBJ408G 4A 800V CC1 CH1BBN103K C CERA BN 103K 1KV DC CC2 CCXE1H104M C CERA 104M 50VDC CC3 CCXE1H104M CCXE1H104M C CERA 104M 50VDC 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CH1BBN221K BN 221K 1KV DC CH1BBN221K BN 221K 1KV DC CEXE2G686C CEXE1H226A 68UF 400V SG 22MF 50V CEXE1E476C 47UF 25V SG CEXE1H105A 1UF 50V CEXE1H477C 470UF 50V RX CEXE1H227C 220UF 50V CEXE1V337C CEXE1V227C C ELEC 330UF 35V RX 220UF 35V CEXE1E227C C ELEC 220UF 25V CEXE1E107C C ELEC 100UF 25V CLV B3104M C LINE ACROSS 275V 104K PILKOR 3107000600 FUSE CLIP AFC 520 3108802500 3108803200 WAFER WAFER YW396 03AV YW396 06V DP6KE200A DIODE TVS PeKE200A DUF1007 DIODE UFR UF1007 1000V 1A DZN4148FTB DIODE 1N4148 AUTO 26MM DHER503 DIODE UFR HER503 200V 5A DUF2003 52F153K002 DIODE UFR LINE FILTER UF2003 200V 2A SQE2424 15MH 2A 52F2550R2 FILTER BEAD BFS2550 R2 52C3R3K000 CHOKE COIL 3 3UH 2A 52C3R3K000 CHOKE COIL 3 3UH 2A 5FVLB3152L FUSE GLASS TUBE 250V 50T 3 15A 3015700110
9. INSTALLING THE INSTALLATION PLATE install the wall bracket follow the procedures below One hole is required for the tubing and may be either on the left or right side 1 Determine the type of wall sheetrock concrete etc and make sure it is strong enough to hold indoor unit Select an approximate position for the unit taking the required distances away from walls AC outlet into consideration AN CAUTION Before making hole make sure there studs pipes electrical wiring or conduit directly behind the area to be cut 2 Determine if the hole is to be made at the left right hole location TAS 18 24 Indoor Unit Unil t mm inch 3 Using drill with hole cutting attachment or equivalent cut a hole 70mm 2 75 in diameter The hole should be made at a slight downward slant to the outdoor side Measure the thickness from the inside to outside edges and cut a PVC pipe at a slight angle 1 4 shorter than the thickness of the wall and insert pipe in wall Indoor Cut at slight angle 4 For sheetrock wooden or similar wall measure down from the ceiling using a level or tape measure and attach the wall bracket to the wall using 4 screws If you are not able to line up the holes with the beams use toggle bolts Make sure the wall bracket is even and flush against the wall
10. Pin 1 INPUT 2 GROUND 3 OUTPUT Pin 1 INPUT 2 GROUND 3 OUTPUT Equivalent Ciircuit 5 U9 KIA7042P RESET IC D INPUT DOG 2 GROUND OUTLINE 8 OUTPUT 9 DISASSEMBLY INSIRUC TIONS 1 INDOOR UNIT 5 12 PROCEDURES 1 Stop the Air conditioner and disconnect the power cord from the wall outlet 2 Removing the Insert Grille and Frame Grille Fig 1 2 1 Draw up the Insert Grille and remove it 2 Loosen one screw for fixing the Cover Ter Block 3 Loosen two screw at the Frame Grille 4 Remove the Frame Grille 3 Removing the Control Box Fig 3 1 Remove room and coil thermistors 2 Disconnect the fan motor lead wire from connection at the Control PCB 3 Disconnect the stepping motor lead wire from connection at the Control PCB 4 Remove the select switch from connection at the Control PCB 5 Loosen a screw for fixing ground wire 6 Remove the Control Box 4 Removing the Drain Pan Fig 4 1 Disconnect the Body drain hole left and right Body 2 Disconnect three hook and remove the Drain Pan 5 Removing the Indoor Evaporator Fig 5 6 1 Remove one screw for fixing indoo
11. 3 Remove the Propeller Fan 4 Removing the panel control Fig 4 1 Disconnect the wire at the control panel 2 Loosen the screw at the panel control 3 Remove the parts on the panel control 5 Removing the vaccum pump 6 Remove the partition panel Fig 5 1 Loosen four screws at the bracket motor 2 Disconnect the wire at the control panel 7 Removing the Over load Protector Fig 6 1 Remove the cocondenser 2 Loosen three volts at the compressor 3 Remove the compressor 51 10 EXPEODED VIEW AND PART LIST 1 INDOOR UNIT 9 5 12 PART CODE PART NAME SPEC Indoor Unit Part List TAS 12 REMARK 3110058500 BODY Ass HIPS T2 0 GY258A 3118008200 MOTOR IDU FDA3530DWA 3111503800 CUSHION MOTOR CR 3106400400 BEARING PLASTIC Ass y 3110046000 CFF 5 SAN G F 30 100 0xL615 3113000400 HOLDER MOTOR L HIPS T2 0 3113000500 HOLDER MOTOR R HIPS T2 0 3110054100 EVAPORATOR Ass y 3R 3C 1 5 3112500900 GUIDE EVAP PVC 3114503300 PLATE EVAP L PP T2 0 GY176A 3110059500 PAN DRAIN Ass y HIPS T2 0 GY258A 3108003910 MOTOR STEPPING MP24GA 3116501001 BLADE VERTICAL P P T1 5
12. BUZZER DP 2520BA CA1 CN5XD104M C ARRAY 6P F5 X 1047 CA2 CN4XD104M C ARRAV 5P F4 X 1047 CN3XD104M CCXE1H104M C ARRAY 4P F3 X 104Z 104M 50VDC CCXE1H104M 104M 5OVDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H104M CCXE1H103M 104M 50VDC 103M 50VDC CCXE1H103M 103 CCXE1H103M 103M 50VDC CCXE1H103M 103M 50VDC CCXE1H104M 104M 50VDC CEXE1E107C CEXE1E107C 100UF 25V 100UF 25V CEXE1C106A 10MF 16V SS CEXE1C475A 4 7MF 50V SS CEXE1E476C 47UF 25V SG 3108803200 YW396 06V 3108803100 3118702310 WAFER YW396 05V YMAW025 04R 3108804800 WAFER SMAW250 08 3118700800 WAFER SMAW250 06 DZN4148FTB DIODE 1N4148 AUTO 26MM 13GS87PH46 IC MICOM TMP87PH46N OTP 1L7805CV 1KD65004AP IC REGULATOR IC DRIVER L7805CV KID65004AP 1KD65004AP IC DRIVER KID65004AP 1KA7042P IC RESET KIA7042P 5L 3109400100 JUMPER 10MM 3109400100 JUMPER 10MM 5PRT800MG 1LTV817C RESONATOR IC PHOTO COUPLER RT8 00MG LTV 817C 3114308410 PCB CONTROL TAS18 24 163 25 123 1 6T FR1 RD 2K102J RESISTOR 1 2W 1K RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J RD 4K102J R CA
13. Fig 7 1 Remove the set screw fixed at the Motor shaft 2 Remove the Cross Flow Fan 7 Remove the Motor IDU and the Bearing Plastic 2 OUTDOOR UNIT TAS 12 15 18 PROCEDURES PHOTOS 1 Stop the operation of the air conditioner and dis connect the wire from in door unit to out door unit 2 Disassemble the case Fig 1 2 1 Remove the Top Panel 2 Remove the Side Cabinet 3 Remove the Front Cabinet 3 Removing the Propeller Fan Fig 3 1 Loosen the screw fixed at the motor bracket 2 Remove the Plain Washer G Remove the Propeller Fan 4 Remove the panel control Fig 4 1 Disconnect the wire at the control panel 2 Loosen the screw fixed at the panel control 3 Remove the parts on panel control 5 Remove the partition panel Fig 5 1 Loosen four screws at the bracket motor 2 Disconnect the wire at the control panel 6 Removing the Over load Protector Fig 6 1 Remove the cocondenser 2 Loosen three volts at compressor 3 Remove the compressor TAS 24 PROCEDURES PHOTOS 1 Stop the operation of the air conditioner and disconnect the wire from in door unit to out door unit 2 Disassemble the case Fig 1 2 1 Remove the Top Panel 2 Remove the Front Cabinet 3 Remove the Side Cabinet and Back Cabinet 3 Removing the Propeller Fan Fig 3 1 Loosen the screw fixed at the motor bracket 2 Remove the Plain Washer
14. Installation Plate Wrap with Power Power cable Ta Source Circuit Breaker Maximum Height 7M 21Ft Maximum Length 15M 49Ft Standard Lengih 25ft 7 6m more than 27 Adding Retrigerant 0 32 oz ft 30g m 4inch 6 0 22 S gt Adding additonal tubing will decrease efficiency S more than more than 4 inch 27 inch Drain Hose Tubing Not Supplied Ground Wire Not Supplied fof more than 24 inch INSTALLATION SELECTING A SITE INDOOR UNIT Do not install the unit in an area with direct sunlight near heat sources radiator etc or an area where leakage of flammable gas may be expected Select a position in the room high on the wall where the whole room can be uniformly cooled Select a location that can hold the weight of the unit and where the copper tubing drain hose and Indoor to Outdoor Wire have the shortest distance to the Outdoor unit Make sure the Indoor unit is installed at least 10cm 3 95in away from the top and left side wall and at least 30cm 11 8in from AC outlet and right side wall OUTDOOR UNIT Do not install the unit in an area near heat sources exhaust fans or an area where leakage of flammable gas may be expected Donotinstall the unit in a humid uneven location Select a location that is well ventilated Leave enough room around the unit for air intake exhaust and possible maintenance
15. Please read make sure all acces sories are included as shown below and read manual thoroughiv This Installation section is provided to assist the per son knowledgeable in air conditioner installation and should not be installed bv anvbodv who is not thoroughiv familiar with this type of installation Please contact a professional installer if necessary ACCESSORIES SUPPLIED WITH THE UNIT Part Name Remark Part Name Remark Installation Plate Batterv Remote Controller Nail Remote Holder Screw Deodorizing Filter Outdoor Cover Electrostatic Filter Foot Cushion OPTIONAL ACCESSORIES ACCESSORIES NOT SUPPLIED WITH THE UNIT D 2 4 0 9 m 7 5 Description Drain Hose Extension PVC 20mm x 2M Tape Finish PVC W80mm x 25M Insulator Plate PE T8 0 Putty Gray 80g Wall Cap HIPS Bracket Saddle SCT T0 8 24 Series Only Cable Tie DACT 190A 24 Series Only INSTRUCTION OF INSTALLATION Below is an overview for the connection of the Indoor unit to the Outdoor unit OVERVIEW This appliance must be installed according to national power supplv acquirement 10cm 3 95in from ceiling 30cm 11 8in from side wall 10cm 3 95in from side wall Wall Wall Cap 11
16. 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RN 4K1501F R METAL FILM 1 4 1 5K OHM F RD 4K331J R CARBON FILM 1 4 330 OHM J RN 4K1272F RD 4K331J R METAL FILM R CARBON FILM 1 4 12 7K OHM F 1 4 330 OHM J RN 4K1272F R METAL FILM 1 4 12 7K OHM F RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K562J R CARBON FILM 1 4 5 6K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K331J RD 4K103J R CARBON FILM R CARBON FILM 1 4 330 OHM J 1 4 10K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RA8K5103J RA8K4103J RESISTOR ARRAY RESISTOR ARRAY 6P 5 X 103J 5P 4 X 103J RA8K3103J RESISTOR ARRAV 4P 3 X 103J Location Part Code Part Name Description BZ1 3105698200 BUZZER DP 2520BA CA1 CN5XD104M C ARRAY 6P F5 X 104Z CA2 CN3XD104M C ARRAY 4P F3 X 104Z CC1 CCXE1H104M CCXE1H104M C CERA 104 5OVDC 104 50VDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H103M 103M 50VDC CCXE1H103M 103M 50VDC CCXE1H103M CCXE1H103M 103M 50VDC 103M 50VDC CCXE1H104M 104M 50VDC CCXE1H104M 104M 50VDC CCXE1H103M 1
17. 3 Pressurize the system to no more than 150 P S I G with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 150 P S I G Next test for leaks with liquid soap CAUTION To avoid nitrogen entering the refrigerant system in a liquid state the top of the nitrogen gas cylinder must be higher than its bottom when you pressurize the system Usually the cylinder is used in a vertical standing position 4 Do a leak test of all joints of the tubing both indoor and outdoor and both wide and narrow service valves Bubbles indicate a leak Be sure to wipe off the soap with a clean cloth 5 After the system is found to be free of leaks relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder When the system pressure is reduced to normal disconnect the hose from the cylinder 10 Evacuation 1 Attach the charge hose end described in the leak test area to a vacuum pump to evacuate the tubing and indoor unit Confirm the Lo knob of the manifold valve is open Then run the vacuum pump The operation time for evacuation varies with the tubing length and capacitv of the pump The following table shows the amount of time for evacuation Required time for evacuation when 30 gal h vacuum pump is used If tubing length is less than 33 ft 10 m If tubing length is longer than 33 ft 10 m 10 min or more 15 min or more 2 When the desired vacuum is reached
18. 3015700110 HEAT SINK HEAT SINK T35XW20XH40 T35XW20XH40 3105797200 HEAT SHINK 22 H 23 17 1TP247YGX IC SMPS TOP247Y GX 1L7815CV IC REGULATOR L7815CV 1L7812CV IC REGULATOR L7812CV 1K1A431 1LTV817C IC REGULATOR IC PHOTO COUPLER 32 KIA431 LTV 817C Location Part Code Part Name Description PCB 3114308510 PCB POWER TAS 170 89 1 6T FR1 R1 RS02Y683J R M OXIDE FILM 2W 68K OHM J RD 4K271J R CARBON FILM 1 4 270 OHM J RD 2K512J RD 4K153J R CARBON FILM R CARBON FILM 1 2 5 1K OHM J 1 4 15K OHM J RS02Y683J R M OXIDE FILM 2W 68K OHM J RD 4K105J R CARBON FILM 1 4 1M OHM J RD 4K105J R CARBON FILM 1 4 1M OHM J RD 4K689J R CARBON FILM 1 4 6 8 OHM J RD 4K479J RD 4K102J R CARBON FILM R CARBON FILM 1 4 4 7 OHM J 1 4 1K OHM J RD 4K100J R CARBON FILM 1 4 10 OHM J AT26 RN 4K1002F R METAL FILM 1 4 10 0K OHM F RN 4K1103 R METAL FILM 1 4W 110K OHM F 5SC010141B SW RELAY PCF 112 D 1M SEMU2834 D15G561K TRANS SMPS VARISTOR 2650 2834 15G561K 350V CH1BFB222K C CERA 2200PF 250V Y1 Power Supply 1 DESCRIPTION The DC power is SMPS power source DC Power Supply in circuit needs 30V 15V and 12V 12V is used for Compressor Driving Relay Buzzer Driving Swing and
19. BLADE VERTICAL M P P T1 5 3107600500 FLAP UP 3107600600 FLAP DOWN 3103200800 3104301700 DRAIN HOSE Ass LED PCB Ass y 3100077060 CONTROL BOX Ass P P Talk 20 3104308800 CONTROL PCB Ass y 3100400700 BODY TOP 3100077150 FRAME GRILLE Ass 3103401400 KNOB SWITCH 3101406820 COVER T BLOCK ABS 3100094400 FILTER ELECTRO Ass WHITE 3100094300 FILTER CARBON Ass BLACK 3102201500 FILTER FRAME DSB 240L LH 3100077200 INSERT GRILLE Ass 3104511800 3112501510 PLATE MOUNTING GUIDE SAFETY C SGCC 10 7 SUS304 01 5 Black 3112501520 GUIDE SAFETY 0 57 SUS304 01 5 Black 2 OUTDOOR UNIT 5 12 15 18 PART CODE Outdoor Unit Part List TAS 12 15 18 PART NAME SPEC REMARK 311000750P PAN Ass SECC T1 2 GY 171D COMPRESSOR QK164KBD 3117104320 RCA155U001 3117109500 RCA180U001 3RC7928RE0 3RC7928ME0 COMP OLP MRA 98996 12026 MRA 12013 696 MRA 12138 696 3110018920 CONDENSER Ass 97 0 2R 3C Fp 1 4 3112400700 GRILLE COND PE 310061000 BRKT SERVICE Ass y SECC T1 6 3115401900 3105400100 SERVICE VALVE C3771 3 8 TAS 12 C3771 1 2 TAS 15 18 3
20. GY176A 3117600101 FLAP HIPS T2 5 GY171A 3103210010 DRAIN HOSE 5 3104301700 LED PCB Assy 3110063610 CONTROL BOX Ass HIPS T2 0 BLACK 3114208600 CONTROL PCB Assy 3110400200 BODV TOP HIPS T2 0 3110063700 FRAME GRILLE Ass HIPS T2 5 3103401400 KNOB SWITCH 3111403400 COVER T BLOCK HIPS T2 0 3111901400 FILTER FRAME P P T2 0 BLACK 3101902510 FILTER CARBON Ass BLACK 3101902610 FILTER ELECTRO Ass WHITE 3110063800 INSERT GRILLE Ass HIPS T2 5 GY171A 3114503800 PLATE MOUNTING SGCG 3112501410 GUIDE SAFETY SUS 304 91 5 3112501420 GUIDE SAFETY B SUS 304 21 5 ST SVL PART CODE PART NAME SPEC Indoor Unit Part List TAS 15 REMARK 3100410000 BODY Ass y HIPS GY177A 3118008210 MOTOR IDU FDA3530DWB 3111503800 CUSHION MOTOR CR 3106400100 BEARING PLASTIC RUBBER 1 D 6 0 3101800200 CFF Ass y O D 0102xL861 3103000700 HOLDER BEARING ABS BLK 3103000600 HOLDER MOTOR L ABS BLK 3110606600 BRACKET MOTOR HIPS 3107400010 EVAPORATOR Ass 3108120020 PAN DRAIN 5 HIPS GY171A 3108004300 STEPPING MOTOR DC12V 400mm 3106500401 BLADE VERTICAL PP GY171A 3107600100 FLAP TOP ABS GY171A 31076
21. SPECIFICATIONS 2 INSTALLATION 3 REFRIGERANT CYCLE 4 WIRING DIAGRAM 5 CONTROL BLOCK DIAGRAM 6 TROUBLE SHOOTING 7 PCB DESCRIPTION 8 KEY COMPONENTS OF ELECTRONIC CIRCUIT 9 DISASSEMBLY INSTRUCTIONS 10 EXPLODED VIEW AND PART LIST Caution In this Manual some parts can changed for US improving their performance without notice in the parts list UL and c CUL listed LISTED
22. Swing Motor DC 30V is used for Indoor Fan Motor Power and DC 15V Vc is used for Motor Drive Refer to PCB Circuit Diagram Outdoor Unit Oscillator 2 DESCRIPTION Oscillatorv Frequency drive Micom it is made up 8MHz resonator oscillatory Fregency Ocillatory wave is as following Fig 2 1 Vss 10 Sensor 3 Room temperature and Evaporator temperature Sensor Input ROOM SENSOR MD SENSOR DESCRIPTION Temperature Number 24 25 of Micom is Terminal of A D convertor Input Voltage V No 1 3 Room temperature and Evaporator temperature is 1 127 1 127 sensing by change of Thermister Resistance Micom is put in 5V by ratio between R10 12 7 1 378 1 378 and R11 12 7KQ Relation between temperature and voltage is 1 650 1 650 following Table 3 1 CC5 6 is Noise filter Indoor Fan Motor Control 4 PG1 1 5KF 330 R4 FEDD BACK Vsp control pulse PIN31 of IC1 Table 3 1 ID MOTOR D DC30V VS PIN6 of L pc 5v vc DESCRIPTION Indoor Fan motor power is DC30V Vs Indoor Fan motor RPM is controled by Vsp 0 5V Vsp control pulse OUTPUT is Pin6 IC1 PIN31 is Indoor Fan motor RPM feed back input Remote Controller 5 DESCRIPTION Signal from Remote Controller put in only Control Data Signal at Micom Terminal of Numb
23. at left and right side Fig 7 8 Loosen a screw for fixing fan motor and blower 3 Renove the fan motor 47 PROCEDURES 7 Removing the blower After doing above procedures D Loosen a screw for fixing holder bearing 2 Remove the blower 5 18 24 PROCEDURES PHOTOS 1 Stop the operation of the Air conditioner and disconnect the power cord from the wall outlet 2 Removing the Insert Grille and Frame Grille Fig 1 2 1 Draw up the Insert Grille and remove it 2 Loosen the screws fixed at the Cover Ter Block 3 Loosen two screw at the Frame Grille 4 Remove the Frame Grille 3 Removing the Control Box Fig 3 1 Remove room and coil thermistors 2 Disconnect the fan motor lead wire from connection at the Control PCB 3 Disconnect the stepping motor lead wire from connection at the Control PCB 4 Remove the select switch from connection at the Control PCB 5 Loosen the screw fixed at the ground wire 6 Remove the Control Box 4 Removing the Drain Pan Fig 4 1 Disconnect the Body drain hole left and right Body 2 Disconnect three hooks and remove the Drain Pan 5 Removing the Indoor Evaporator Fig 5 6 1 Remove the hook fixed at the Plate mounting of the back of Body 2 Remove Indoor Evaporator 6 Removing the Cross Flow Fan
24. close the Lo knob of the manifold valve and stop the vacuum pump Finishing the job 1 With a hex wrench turn the narrow tube service valve stem counter clockwise to fullv open the valve 2 Turn the wide tube service valve stem counter clockwise to fullv open the valve CAUTION To avoid gas from leaking when removing the charge hose make sure the wide tube service valve is fully open and turned all the wav out 3 Loosen the charge hose connected to the wide tube ser vice port slightiv to release the pressure then remove the hose 4 Replace the threaded cover on the wide tube service port and fasten it securelv This process is verv important to prevent gas from leaking from the svstem 5 Replace the valve caps at both wide and narrow service valves and fasten them This completes air purging with a vacuum pump The air conditioner is now readv to test run ll Indoor Unit Outdoor Unit Pressure Gauge Charge Hose Vacuum Pump TEST RUN Check that all tubing and wiring have been completed correctly Check again that the wide and narrow tube service valves are fully opened Turn on the power and run the system Service Valve Construction Valve Position Closed The valve systems of both the wide and narrow tubes are turned all the way in The u
25. until a smooth match is made Make sure the copper extension has foam rubber insulation on it am coupler Flare Nut NOTE the inside unit When removing the flare nut stopper from the inside unit confirm Ping sounds because the mixed gas is charged in 3 Once a smooth match is made tighten the flare nut using a wrench Be very careful not to strip the threads or flare nut Repeat this process for the small and large tubing When tightening the flare nut use another wrench to securely hold the coupler from twisting and possibly damaging the tubing IN 4 Remove the flare nut stoppers from the outdoor unit s valves Connect the larger copper tubing to the larger valve on the outdoor unit Connect the smaller copper tubing to the smaller valve on the outdoor unit Perform a leak test on all copper tube connections To prevent heat loss and damage to walls from conden sation the copper tube connections coming from the wall must be insulated Do this by wrapping foam rub ber or equivalent around the connection approximate ly 8mm thick so no copper tubing is exposed NOTES As with all wiring and hookups on this unit make sure the AC plug on the indoor unit is unplugged Be very careful not to strip the threads or flare nut When insulating the connections use foam rubber or equivalent CONNECTING THE DRAIN HOSE
26. 00200 FLAP UNDER ABS GY171A 3103210010 DRAIN HOSE Ass INSULATOR 3100005270 CONTROL BOX Ass 3114308700 CONTROL PCB Ass y 3104300301 SWITCH PCB Ass y 3104300401 LED PCB Ass y 3102210020 FRAME GRILLE Ass ABS GY171A 3101403700 COVER T BLOCK ABS GY171A 310191000C FILTER PRE 5 P P BLACK 310192000C FILTER PRE L Ass y P P BLACK 3101930000 FILTER ELECTRO Ass WHITE 3101940000 FILTER CARBON Ass BLACK 3110017600 INSERT GRILLE Ass HIPS GY171A 3104500300 PLATE MOUNTING SGCC T0 8 3106300500 BAR DRAIN SUS 304 01 5 3100601400 BRACKET DRAIN SUS 304 T1 0 TAS 18 24 PART CODE PART NAME Unit Part List TAS 18 24 REMARK 3100076200 BODY Ass HIPS T2 5 311009F000 MOTOR IDU FDA3530DWG 3111503800 CUSHION MOTOR CR 3106400200 BEARING PLASTIC Ass y 0 D 37 0x1 D 6 0 3100076400 3103003800 CFF Ass y HOLDER MOTOR LB O D 0100xL864 DSB 240L LH 3110606700 BRACKET MOTOR HIPS T2 0 3103004000 HOLDER BEARING ABS T2 5 311009AC11 EVAP Ass y Fp 1 4 2R 5C 311009 01 Fp 1 4 2R 5C 3102501400 GUIDE EVAP 3100076810 PAN DRAIN Ass HIPS T2 0 GY258A 3108007600 MOTOR STEPPING GSP 24RW 062 3106502700
27. 03200 YW396 06V 3108803100 3118702310 WAFER YW396 05V YMAW025 04R 3108804800 WAFER SMAW250 08 3118700800 WAFER SMAW250 06 DZN4148FTB DIODE 1N4148 AUTO 26MM 13GS87PH46 IC MICOM TMP87PH46N OTP 1L7805CV 1KD65004AP IC REGULATOR IC DRIVER L7805CV KID65004AP 1KD65004AP IC DRIVER KID65004AP 1KA7042P IC RESET KIA7042P 5L 3109400100 JUMPER 10MM 3109400100 JUMPER 10MM 5PRT800MG 1LTV817C RESONATOR IC PHOTO COUPLER RT8 00MG LTV 817C 3114308210 PCB CONTROL TAS12 176 5 121 1 6T FR1 RD 2K102J RESISTOR 1 2W 1K RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 26 1 4 1K OHM J 1 4 1K OHM J Location Part Code Part Name Description R14 RD 4K102J R CARBON FILM 1 4 1K OHM J R15 RD 4K102J R CARBON FILM 1 4 1K OHM J R16 RD 4K102J R CARBON FILM 1 4 1K OHM J R17 RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RN 4K1001F R METAL FILM 1 4 1K OHM F RN 4K5761F R METAL FILM 1 4 5 76K OHM F RN 4K2432F R METAL FILM 1 4 24 3K OHM F RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4
28. 03M 50VDC CCXE1H103M 103M 50VDC CCXE1H103M CCXE1H103M 103M 50VDC 103M 50VDC CCXE1H104M 104M 50VDC CEXE1E107C 100UF 25V CEXE1E107C 100UF 25V CEXE1C106A 10MF 16V SS CEXE1C475A CEXE1E476C 4 7MF 50V SS 47UF 25V SG 3108803200 YW396 06V 3108803100 YW396 05V 3118702310 YMAW025 04R 3108804100 SMW250 07 3108802000 3108804200 WAFER SMW250 06 SMW250 02 3108802000 WAFER SMW250 06 DZN4148FTB DIODE 1N4148 AUTO 26MM 13GS87PH46 IC MICOM TMP87PH46N OTP 1L7805CV IC REGULATOR L7805CV 1KD65004AP 1KD65004AP IC DRIVER IC DRIVER KID65004AP KID65004AP 1KA7042P IC RESET KIA7042P 5L 3109400100 JUMPER 10MM 3109400100 JUMPER 10MM 5PRT800MG RESONATOR RT8 00MG 1LTV817C 3114308310 IC PHOTO COUPLER PCB CONTROL LTV 817C TAS15 110 130 1 6T FR1 Location Part Code Part Name Description R1 RD 2K102J RESISTOR 1 2W 1K RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J
29. 105400200 SERVICE VALVE C3771 1 4 3114464500 3114464510 3114464520 PIPE SUCTION 12 7xT0 7 12 7xT0 7 12 7xT0 7 3114464600 3114464610 3114464620 PIPE DISCHARGE 9 52xT0 7 9 52xT0 7 9 52xT0 7 311009F400 311009F410 311009F420 PIPE CAPILLARY 5 0 D 3 2x1 D 1 8xL1 000 0 D 3 2x1 D 1 8xL600 0 D 3 2x1 D 2 0xL1 000 3114500800 PLATE PARTITION SGCC T1 0 3110600200 BRACKET MOTOR SGCC 11 2 3118007160 MOTOR ODU 208 230V 60Hz Y DK 50 6A1 3101800100 FAN PROPELLER ABS G F OD420 3110025810 PANEL CONTROL Ass y SECC 8 3114308900 ODU PCB Ass v 3111101400 CASE PCB ODU P P Talk 2096 3109506320 3116903120 CAPACITOR DUAL 3 0 30HF 400VAC TAS 12 15 3 0 35HF 400VAC TAS 18 3101301100 CLAMP CAPACITOR SECC T1 0 311080021P CABINET FRONT SECC T0 8 3112400300 GRILLE DISCHARGE STEEL WIRE 3112500300 GUIDE SUPPORT SECC T1 2 311080030P CABINET SIDE SECC T0 8 311420050P PANEL TOP SECC T0 8 3111408300 COVER SERVICE SECC T0 8 3102101000 CUSHION RUBBER NR TAS 24 ASSY 1OBINOJ 91 Outdoor Unit Part List TAS 24 PART CODE PART NAME SPEC REMARK 31000
30. 41702 BASE PAN Ass y SECC T1 2 GY 171D 3117141200 COMPRESSOR QP325KBB OLP INTERNAL 3106800500 CONDENSER Ass FP 1 5 3102402100 GRILLE COND PE 3100041201 BRACKET SERVICE Ass y SECC T1 6 GY 171D 3105401300 SERVICE VALVE 5 3105401200 SERVICE VALVE 3 8 3114456700 PIPE SUCTION O D 215 88xT0 8 3114456800 PIPE DISCHARGE O D 212 7xT0 7 3100089310 PIPE CAPILLARY Ass y O D 23 2xl D 22 0xL500 3105300400 SUPPORT MOTOR SGCC M Z22 T1 6 3118008000 MOTOR ODU A2929GS010 3101802001 FAN PROPELLER ABS G F 20 3100031702 PLATE PARTITION Ass SGCC M Z22 T0 8 3100088680 PANEL CONTROL Ass SGCC T0 8 3114308900 ODU PCB Ass y 3111101400 CASE PCB ODU P P Talk 20 3116904800 CAPACITOR DUAL 5 0 40UF 400VAC 3101201100 CLAMP CAPACITOR SBHG1 T1 0 3100031400 CABINET FRONT 5 SECC T0 8 GY 171D 3102102000 GRILLE DISCHARGE STEEL WIRE 3100041100 GUIDE SUPPORT SECC T1 6 GY 171D 3100031520 CABINET SIDE SECC 0 8 GY 171D 3100041500 PANEL TOP SECC 0 8 GY 171D 3100089220 COVER SERVICE SECC 0 8 GY 171D 3111500400 CUSHION RUBBER 61 NR turbo air SERVICE MANUAL ROOM AIR CONDITIONER MODEL TAS 12 TAS 15 TAS 18 TAS 24 CONTENTS 1
31. 8 4 N2 P62 1 CE4 103 9 XIN N1 P61 4 7uF 50V 20 OUT NO P60 VASS VSS VAREF CN3 330 R31 103 I D SENSOR o o o 330 R33 DCISV O O O CC3 LTV817C 1D MOTOR 10uF 16V 23 O CN2 1N4148 D1 4A 1034 RA2 MA CH 1K R6 Vs DC30V 103 CC8 01119 GND GND 6 Ve DC15V 2 15 SIP e A 14 DN 4 13 d FT opel 6 11 7 8 IK RIS RAT 6A 1039 E 82 DC5V IC2 7805 CE2 4 CC1 100uF 104 25V CE1 100uF 25V MODEL DSA 152U TAS 15 2003 e TAS 12 15 18 24 Outdoor Unit F1 TS4BO6G SUNGHO FILTER F KBJ408G DIODES 10mH 2A e PAQ N 3 15A 01 VBR 190V7210V P6KE200A hd 01 561014 396 03 1 104 275V CE1 Col 68K 68uF 103k 2 400V IKV DC MEN 4 Low loss Y n UF4007 UI 10000 5 2550 DC12V RLI 1121 PC1 LTV817A 00
32. L SPECIFICATIONS ITEM Function Dehuminication Electrical Data Main Power AC 208 230V 60Hz 1 Ph Running Current i 6 4 7 5 Watts Refrigerant Quantitv 35 3 1000g 40 5 11509 42 3 12009 63 5 18009 Connection Flare Gas Side 3 8 9 52mm 1 2 12 7mm 1 2 12 7mm 5 8 15 9mm Liquid Side 1 4 6 35mm 1 4 6 35mm 1 4 6 35mm 3 8 9 52mm Compressor QK164KBD RCA155U001 RCA180U001 QP325KBB O L P MRA 98996 12026 MRA 12013 696 MRA 12138 696 Internal LRA 24 39 42 68 Indoor FDA353DWA FDA353DWB FDA353DWC Outdoor YDK 50 6B1 YDK 50 6B1 YDK 50 6B1 A2929GS010 Capacitor Dual 3 30uF 400VAC 3 30uF 400VAC 3 35HF 400VAC 5 40uF 400VAC Dimension Unit conversion 1 inch 25 4 mm Indoor WxHxD 815x285x195 1035x322x205 1080x298x200 1080 9298 2200 Weight net 20 3 9 2kg 26 7 12 1kg 32 4 14 7kg 32 4 14 7kg WxHxD 800x615x320 800x615x320 800x615x320 872x675x325 Weight net 110 3 50kg 110 3 50kg 110 3 50kg 141 1 64kg The Ranges of Temperature And Humidity Standard Rating Condition Indoor Temp Outdoor Temp Indoor Humidity Indoor Outdoor DB WB DB WB 65 90 F 70 109 F Less than 80 18 32 21 43 2 INSTALLATION BASIC ACCESSORIES This Installation section explains how and where to connect this new air conditioner
33. M 4 WIRING DIAGRAM e ndoor Unit TAS 12 18 24 9 TAS 15 CIRCUIT DIAGRAM CIRCUIT DIAGRAM ITERMINAL BLOCK TERMINAL BLOCK EMERGENCY BLU SWITCH RED RED ORG SWEEP YEL ee PNK BLU ROOM BLK SENSOR RED F ZA ORG BLK SWEEP o m ROOM MOTOR2 PNK LK SENSOR BLU SS 8 BLK e Outdoor Unit e TAS 12 15 18 9 TAS 24 CIRCUIT DIAGRAM CIRCUIT DIAGRAM GRN GRN YEL s FUSE L BLK BRN 250V 3 15A koz amp 6 N X p Seve WHT BLU BLU BLU BLU VEL VEL VEL WHT WHT WHT BLK BLK BLK RED RED RED TERMINAL TERMINAL BLOCK BLOCK 5 GONIROLBLOCK DIAGRAM SdWS 1 YSMOd OV 1 JoloN 4 joopino god Joolno 196 UO1 29JIQ UD4 paeds upj 89d JOOQNI 4 WdA Be 10J0W 1 nes 10104 95 dwaj 02 Joop
34. RBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J Location Part Code Part Name Description R14 RD 4K102J R CARBON FILM 1 4 1K OHM J R15 RD 4K102J R CARBON FILM 1 4 1K OHM J R16 RD 4K102J R CARBON FILM 1 4 1K OHM J R17 RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RN 4K1001F R METAL FILM 1 4 1K OHM F RN 4K5761F R METAL FILM 1 4 5 76K OHM F RN 4K2432F R METAL FILM 1 4 24 3K OHM F RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RN 4K1501F R METAL FILM 1 4 1 5K OHM F RD 4K331J R CARBON FILM 1 4 330 OHM J RN 4K1272F RD 4K331J R METAL FILM R CARBON FILM 1 4 12 7K OHM F 1 4 330 OHM J RN 4K1272F R METAL FILM 1 4 12 7K OHM F RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K562J R CARBON FILM 1 4 5 6K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K331J RD 4K103J R CARBON FILM R CARBON FILM 1 4 330 OHM J 1 4 10K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RA8K5103J RA8K4103J
35. RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RN 4K1001F R METAL FILM 1 4 1K OHM F RN 4K1022F R METAL FILM 1 4 10 2K OHM F RN 4K4122F R METAL FILM 1 4 41 2K0HM F RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RN 4K1501F R METAL FILM 1 4 1 5K OHM F RD 4K331J R CARBON FILM 1 4 330 OHM J RN 4K1272F R METAL FILM 1 4 12 7K OHM F RD 4K331J RN 4K1272F R CARBON FILM R METAL FILM 1 4 330 OHM J 1 4 12 7K OHM F RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K562J R CARBON FILM 1 4 5 6K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K103J R CARBON FILM 1 4 10K OHM J RD 4K103J RD 4K331J R CARBON FILM R CARBON FILM 1 4 10K OHM J 1 4 330 OHM J RD 4K103J R CARBON FILM 1 4 10K OHM J RD 4K103J R CARBON FILM 1 4 10K OHM J RD 4K103J R CARBON FILM 1 4 10K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RD 4K102J RD 4K102J R CARBON FILM R CARBON FILM 1 4 1K OHM J 1 4 1K OHM J RD 4K102J R CARBON FILM 1 4 1K OHM J RA8K5103J RESISTOR ARRAY 6P 5 X 103J RA8K3103J RESISTOR ARRAY 4P 3 X 103J Location Part Code Part Name Description BZ1 3105698200
36. ace the switch position to the Remote and then Check it once more 16 Note 1 D Neither indoor unit nor outdoor unit runs Check the following points first There are following case in normal operation a Is the timer mode set the timer ON b Is the timer mode set the timer OFF and the time had passed 2 Neither outdoor fan nor compressor runs while indoor fan runs Check following points first There are following cases in normal operation a Is the temperature set point suitable b Has the 3 minutes time guard for compressor operated Self Diagnostic Function 1 Error Code ON LED blinking 3 times at Emergency Mode When the compressor do not run i Check the voltage between IL and of terminal block Indoor Unit Outdoor Unit ii Check connecting wire of indoor unit and outdoor unit iii Check relay RL1 on power P C B outdoor PCB 2 Check fixing of indoor coil thermistor 3 Check the GAS LEAKAGE of the pipe 2 Error Code 2 ON LED blinking 1 Check the sensor and its circuit 2 It occurs when sensor is open or short 3 Error Code 3 TIMER LED blinking D Check the Indoor Fan Motor 2 Check the RPM feedback circuit 8 Indoor Fan Motor does not work for 5 seconds 17 Neither Indoor Unit nor Outdoor Unit Runs Confirm following statement When the unit operate normally Sometimes the outdoor unit and indoor unit cannot operate 1 Check the function select switch Is it
37. ct Timer Enter Button display ERROR Y Select CANCEL Button No Is all display OFF gt ERROR Y Select ON OFF Button Y Select OFF Timer Button 0 5 24 HOUR No gt ERROR Select SLEEP Button SLEEP MODE No Display ON Select SLEEP Button gt ERROR Is display at the beginning ON TEST OK 8 KECCOMPONENTSOF ELECTRONIC CIRCUIT 1 91 MICOM 77 HSO VDD P76 HSCK XTOUT P22 Steppping Motor Driving 21560 PTI HS P74 S INTSISTOPJP20 P70 P73 SCK P17 PTRPDOIPWM P74 INT4 Indoor Unit Motor Driving Buzzer Driving LED Driving Remocon Input Comp Relay Driving P04 Emergency Mode P0 Zero Crosing Detect Function P01 Function S W S W P00 TEST Reset Curcuit RESET n Temperature Oscillation NO P60 Sensor Input VASSJVSS VAREF 2 02 4 KID65004 DARLINGTON ARRAYS IN1 1 op 16 OUT 1 IN2 2 15 OUT 2 IN 3 3 H gt 14 OUT 3 GE IN 4 4 13 OUT 4 INS 5 12 OUT 5 OUT 6 IN7 7 E 9 COMMON FREE GND 8 WHEELING DIODES Equivalent Circuit Top View 3 U8 KIA7805P VOLTAGE REGULATOR 5VDC SCHEMATIC DIAGRAM 200 0 3
38. en and less than 90 Y of outdoor unit terminal Rating more than 9096 NG gt Change the control Check the wiring of outdoor unit PC B Check the compressor Open or Short a gt Change the Check the winding resistance compressor m Check the compressor capacitor 21 7 PCB DESC 1 PCB CIRCUIT DIAGRAM e 5 12 18 24 Indoor Unit 6 5 4 612 104 CN5 1 9 8 M 101 6 7 1 lt 65004 4 IC1 14 3 1 N 2 16 1 mr XTOU 3 75 50 XTIN 4 P74 SI 5 5 0 5 P73 SCK IDM e P72 PD0 PWM CN4 7 5 IK RIO P71 INT4 TC2 DREMOCON 5 P70 INT3 TC3XPPG o EMERGENCY 2 RI4 9 IK RI P07 DVC 10 o ES lt RA2 F4 1037 12 1 INTO R25 1K 2 13 AIN7 F C i 453 Fo HI AIN6 454 kal i AIN5 455 9 R36 5 6K LI ces in IK R35 18 9 ATI RESET AIN2 103 19 47 se d AND T 20 AINO OSC1 8MHZ 21 vass vss 104 AA Seah 127KF 2 mL 103 CC6 ca NN 330 R33 I D SENSOR 12 7 R34 104 aA 10uF 16V DC 12V DC30V PC1 EK 330 84 1 5KF ID MOTOR
39. er 33 which is gotten fid of Carrier 38KHz from Receive Module Signal Wave repeat third as following Fig 5 1 But in Secondary Wave Custom Code is Reversed Face 1 69ms Lose CUSTOM 2 25ms LEADER CODE CODE bit 1 Fig 5 1 Fig 5 2 BIT STRUCTURE Selecting Mode 6 SELECT S W INPUT OUTPUT MODE SELECT PUSH S W CA2 J F4104Z DESCRIPTION There are Mode according to SW position as POSITION MODE following Table 6 1 OPEN REMOCON According as port of fixed Micom is Low the unit is operating as following Table 6 1 GND EMERGENCY Table 6 1 Micom Power 7 DESCRIPTION MICOM Power is supplied 5V at Number 42 using VDD Number 19 20 Vsing Oscillator CC10 is noise filter 37 Reset 8 4 7uF 50V DESCRIPTION Voltage less than about 0 8V put in Micom Terminal of Number 18 and then Micom reset Reset IC detect Power ON and Voltage less than 4 25V and then send Reset Signal Vcc 5V DELAY TIME FOR POWER ON Function Selecting 9 SA 103J F4 103Z DESCRIPTION CA1 FS 1047 824 823 cool low R22 heat high R21 cool high R20 monitoring RAT 6A 103J When power source is put at fist Funtion selection input is recognized And when the unit is running the microcomputer ignore variation of funtion selection input
40. motor Run again Check the starting of indoor fan motor gt Change of fan motor Vsp 0 5V DC No Run again Normal Outdoor Fan and Compressor Do Not Confirm following statement When the unit operate normally Sometimes the outdoor unit and indoor unit cannot operate 4 Is the setting temperature proper 2 Is the unit during 3min Time delay of compressor 3 During frost prevention of Indoor unit i Check the wirin Check the voltge between L and Rating voltage 4 9 Y of indoor unit terminal under 90 Rating Check Check the voltge between L under 90 connecting wire Y of outdoor unit terminal Check the voltge between L and Rating voltage Check the Y of outdoor unit terminal under 90 connecting wire Check compressor outdoor fan motor individually Only Compressor Do not Run Check the following at cooling mode Rating voltage Check the control P C B the circuit for relay driving Check the voltge between L and Y of indoor unit terminal less than 9096 Rating voltage more than 90 Rating voltage Check the connecting wire between indoor and outdoor Check the voltge betwe
41. nit is shipped from the factory in this position and it is also used for Pump Down and Air Purging Valve Position Fully Open The valve stems of both the wide and narrow tubes are turned all the way out This is normal operating and Test Run position Valve Position Half Open With the narrow tube valve stem is turned to the halfwav down position This position is used for pressure measure ment and gas charging CAUTION When opening or closing the service valve stem be sure to use a hex wrench PUMP DOWN Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas This is performed when the unit is to be relocated or the refrigerant circuit is serviced Z N CAUTION Be sure to perform Pump Down procedure with the unit cooling mode Pump Down Procedure Connect a low pressure gauge manifold hose to the charge port on the wide tube service valve Open the wide tube service valve halfway and purge the air from the manifold hose using the refrigerant gas Close the narrow tube service valve all the way in Turn on the unit s operating switch and start the cooling operation When the low pressure gauge reading becomes 1 to 0 5 kg cm2 14 2 to 7 1 psi fully close the wide tube valve stem and then quickly turn off the unit At that time Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit Q N 3 REFRIG ERANTCYCLE DIAGRA
42. or Unit CAUTION The supply voltage must the same as the rated voltage of air conditioner Prepare the power source for exclusive use with the air conditioner circuit breaker must be installed between the power source and the unit This air conditioner must be installed according to the national electric rules INFORMATION The information for the cables of this air conditioner is as below ITEM SPECIFICATIONS 12K 15K BTU h 3G AWG 14 SJT or SPT 3 18K 24K BTU h 3G AWG 12 SJT or SPT 3 5G AWG 16 18 SJT 3G AWG 18 20 SJT 2G AWG 16 18 SJT CONDUIT SIZE 0 875 inch 22 2mm POWER CABLE CONNECTION CABLE 12K 24K BTU h TAPING UP THE WIRE TUBES HOSE After running the wire hose and tubing outside tape them up as shown below to insulate 1 Tape the two copper tubes drain hose and the electrical wiring if local codes permit together with the supplied tape Make sure the electrical wiring does not come in direct contact with the copper tub ing or drain hose Approximatelv 1 foot outside the hole let the drain hose out and separate from the copper tubing and wiring Drain hose 2 Begin wrapping from the point the tubing comes out of the outdoor unit and continue to the hole in the wall Leave no gaps or breaks and cover the entire length of the tubing As vou wrap overlap the previous turn bv half the width of the tape
43. place Installation Plate Insert Putty Drain Hose PREPARING THE COPPER TUBING NOT INCLUDED A copper tubing extension not included may need to be cut If this is the case it will also have to be deburred and flared as shown below 1 Cut the copper tube extension to the desired length with a tube cutter It is highly recommended that 1 foot is added to the requested length After cutting debur ring may be necessary see below diagram Perform this with a tube reamer BEFORE AFTER 2 Make a flare at the end of the copper tube with a flare tool Make sure the inside surface and edges are smooth and the sides are uniform length Flare nut Ee N E 22 N Se aa tool A CAUTION When using the tube reamer hold the tube downward and make sure no copper scraps fall into the tubing THE COPPER TUBES connect copper tubes follow the procedures below 1 Remove the flare nut stoppers from the inside unit Determine the location of the copper tubing and where the bends will be Gently bend the copper tub ing making sure to use big angles so no crimping will occur Try to do this on the first try as repeated bend ing may break or crimp the tubing R a 2 Remove the plastic stoppers from the tubing Connect the large and small copper tubing to the respective extension and rotate the flare nut with your finger
44. r Evaporator at the Body 2 Remove the hook for fixing Bracket Pipe at the back of Body 3 Remove Indoor Evaporator 6 Removing the Cross Flow Fan Fig 7 1 Remove set screw for fixing Motor shaft 2 Remove Cross Flow Fan 7 Remove Motor IDU and Bearing Plastic TAS 15 PROCEDURES PHOTOS 1 Stop the Air conditioner and disconnect the power cord from the wall outlet Removing the Insert Grille and Frame D Loosen three screws for fixing the the Insert Grille and Frame Pull out the frame cap before loosening three screws Fig 1 Loosen three screws at the Drain Pan Remove the Insert Grille and Frame Removing the Control Box After doing above procedures CD Disconnect indoor room and coil thermistors Fig 3 2 Disconnect the fan motor lead wire from connection at the main PCB Fig 3 Disconnect the swing motor connection wire 4 Loosen a screw for fixing ground wire 5 Loosen two screws for fixing the body Removing the Drain Pan After doing above procedures Loosen a screw for fixing body Fig 4 2 Unhook the right part of Drain Pan Removing the Indoor Coil After doing above procedures D Loosen four screws for fixing indoor coil at left and right side Fig 5 Loosen a screw for fixing the bracket tube at the back side Fig 6 3 Remove the indoor coil Fig 6 1 Removing the fan motor After doing above procedures Loosen two screws for fixing holder moter
45. timer mode 2 The function select switch locate the sleep mode and is the setting time over G Is the setting mode DEHUMIDIFIER mode The power is applied to the unit Rating voltage Check the Check the voltge between L and under 90 Breaker or Fuse Y of terminal block Rating voltage more than 90 Check the indoor unit display No l is the display all off Self Diagnostic function is ON Yes Press the ON OFF switch of Remote Control Check according to self Diagnostic function Is the indoor unit display all off Pull out the power plug Control P C B defect Ta and then insert the power plug after 5 second Control P C B is normal Recheck from the beginning Outdoor Unit Runs but Indoor Fan Do Not Run Check rotation of indoor fan DC Check the winding resistance of Indoor unit fan motor NO Check the Fan Motor Rotate indoor fan by hand peaning ane fan YES DC 30V Vs Check the power PC B Check input Voltage Vs of Fan DC 15V Vc outdoor PCB Motor connector at power P C B Fail wr The circuit for DC POWER Open or short Check of indoor PCB Check the connecting wire of indoor fan
46. ul 3110 1 09 3110 1 09 3LONIY Jolloals 9POW dup duip pup aloway 494 931 dWDI NO un 6 TROUBLE SHOOTING Is the unit display normal Outdoor unit does not run E Does the compressor run normally YES Indoor unit does NO not run YES l Normal Is the unit displav mormal Check the failure code according to check the the self diagnostic connecting YES point of magnetic contactor check the failure code according to the self diagonostic Trouble Is the power applied to the unit YES Is the power normal check the voltage between L amp N of terminal block press the power ON OFF button on remote controller Does the beeper beep two times Is the display all off NO NO Check power supply mains or interconnection wires Check the wiring of indoor Is the switch position on switch pannel at Remote Does control PCB status LED repeat one second on and off control PCB fault Micom or reset IC fault Check the connector on display PCB connected to control PCB Check the display PCB itself Check the remote signal receiver Check the connection between signal receiver and control PCB Pl

Download Pdf Manuals

image

Related Search

Related Contents

EFFECT 500 Mattress Overlay System User Manual  VT6912 MANUAL    Samsung 400MX-3 Manuel de l'utilisateur  ZipaBox Keyfob Z-Wave Gen5 User Manual  応用分子動力学計算プログラム RYUDO 取扱説明書  GSW-2404SF User Manual  SIGEM 2004 SIGEM 2004 – MODE D`EMPLOI MODE D`EMPLOI  LIGHT( C+W) USER MANUAL LED WASH    

Copyright © All rights reserved.
Failed to retrieve file