Home
        4200FA 80KVA Users Manual
         Contents
1.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            4200     XT 80kVA Installation and Operation Manual          BYPASS  INPUT   gt  TERMINALS    FOR DUAL  INPUT OPTION    CONTROL          V OUTPUT   2   TERMINALS       13    TOSHIBA    Leading Innovation  gt  gt  gt        41 1 Recommended Wire Size and Tightening Torque for UPS Input Output Terminals       Minimum Maximum Wire Size and Tightening Torque  of UPS Input and Output Terminals             Main Input   AWG AWG Tightening Torque  Bypass Input      EVES     in Ibs    208 120 VAC 500 MCM 375  Input    500  Neutral   480 VAC 1 0 AWG to 500 MCM N A 375       AWG AWG Tightening Torque   L1  L2  L3   OUTN   in Ibs      208 V 120 VAC 500 MCM 2 x  350     400 MCM  375  Input   500  Neutral     Battery Circuit AWG Tightening Torque   POS  NEG   in Ibs      288 VDC Nominal 400 MCM to 2 x  3 0     400 MCM     Input Output AWG Tightening Torque  Ground  GND   in Ibs      u x lt  1 2 AWG minimum  see note 1   see note 2     All wire sizes are per NEC       Use copper wiring with at least 75  C rated insulation  N
2.                                                                                                                                                                                                                                                                                                            6  SS                                                                                                                                                                                                                                            4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Dual Input UPS with no transformers  Shown with bottom cable entry  configuration                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         
3.                                                                                                                                                                                                                                                                                                 U                                                  E      DED    DK DL IK DT IN DD    V                                                                                                                                                                                                                                                                                                     EIO      o  fo  fo  fo  fo  fo  fo          M   2   2   o                              1010 0 10  2    o   NS 2                                   16 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Single Input UPS with no transformers  Shown with bottom cable entry  configuration                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  
4.                                                                                                                                                                                                                                 Ix   d B JL        9  ae 585          X J  o O O      x VY      olo             n           ED          m                                            cy      DODD DOD DU Co DOCE S              5 5   s      F                                                                                                                                                                                                                                                                                                                                                                                                   4200FA XT 80kVA Installation and Operation Manual 15    TOSHIBA    Leading Innovation  gt  gt  gt        Dual Input UPS with input transformer  Shown with bottom cable entry  configuration                                                                                                                                                                                                                                                                                                                    E               o Oo                                               i                                                                                                                       
5.                                                                                                                                                                              MAE ME M MS MESS MSS        MES M M  MAE ME M ME ME MES MES MES M ES MES M  MEE ME ME ME MES MES MESS MES M ES E       M  MM E ME MM E      MEME MES MEE MM                                                                     d            9  z Q JOO              OOO   5 s   x OOO V     2            I I        9                   1  ff    Qo 1   47       9pg      2           NEN NEN             18 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Single Input UPS with input transformer  Shown with top cable entry  configuration                                      d                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  
6.                                                                                                                                                                         4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Dual Input UPS with input transformer  Shown with top cable entry configuration                                                                                                                                                                                                                                                        c   3                              c   3               J                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                           IAN  2000 Pelee Genes      mE                                                                                                                                                                                                                JO                                                                                                                     
7.                                                                                                                                              c   3                                                                                                                                                                                                                                                                              i                                                                                                                  OJ        OJ                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       mmo                                                                                                                                                                22 4200FA      80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        4 4 3 Dual Input Configuration  Units are shipped from the factory wired for single input configuration  For those requiring a  dual input configuration see below  This change should o
8.                                   20 4200FA      80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Single Input UPS with no transformers  Shown with top cable entry configuration                                                                                                                                                                                                                                                                                                       o o                              OJ                                                                                                                                                                                                                                                                                     m xf m  m     2    gt                                                                                                                                                                                                                   G        e                                                                               B TO    s   9                                                                                                                   4200FA XT 80kVA Installation and Operation Manual    21    TOSHIBA    Leading Innovation  gt  gt  gt        Dual Input UPS with no transformers  Shown with top cable entry configuration                                       
9.                                 P 9 Symbol Deseripuon DB9 Female connector outline  1 This pin is not used  facing connector   2 Input RXD Receive Data  3 Output TXD Transmit Data  4 Output DTR Data Terminal Ready  5 SG Signal Ground  6 Input DSR Data Set Ready  7 Output RTS Request To Send  8 Input CTS Clear To Send  9 This pin is not used  4 2 3 UPS Shutdown  via RS 232C   When the UPS is operating from its internal batteries  a Shutdown order can be sent to the  UPS telling it to turn OFF after a user specified amount of time  This function can allow you  to stop discharging the UPS batteries after an orderly system shutdown has been completed   The UPS can be programmed to turn OFF up to 8 minutes after the Shutdown command is  given  This command can be cancelled before the specified time has elapsed by following  the directions listed on the RS232 screen   26 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        5 0 Specifications  5 1 Specifications   4200FA 80kVA without Internal Transformer       Model Number    T42F3F800FAXXN       Rated Output Capacity    80 kVA       External Dimensions   WxDxH     41 in  x 31 in  x 74 in    1041 mm x 787 mm x 1880 mm        Weight    2000 165  907 kg              Rated Voltage 208 120 Vac  Voltage Variation i  10  to  30     Rated Frequency 50 60 Hz       Number Phases   Wires    3 Phase   4 Wire       Power Factor      Greater than 0 99 when in inverter mode                        
10.                        54  8 1      Preventive                                 420  1                                      tenentes 54  8 2      Parts Replacement u 1 u hein hinted tein Winder eed 54  9 0 External Dimensions   Shipping Weights                                                          55  9 1      External DIMENSIONS           eine ahi an Mii        55  9 2    Shipping DIMENSIONS x    ccc eas ae oes      56  9 3    Shipping                tae del GA ave Greenlee a Wena deS 56  9 5  Cabinet Coleus u ET 56  APPENDIX      Installation Planning Guide                                                                57    ii 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        GENERAL SAFETY INSTRUCTIONS    DO NOT attempt to install  operate  maintain or dispose of this equipment until you have read and  understood all of the product safety information and directions that are contained in this manual     Safety Alert Symbol    The Safety Alert Symbol indicates that a potential personal injury hazard exists  The  symbol is comprised of an equilateral triangle enclosing an exclamation mark     Signal Words    Listed below are the signal words that are used throughout this manual followed by their descriptions and  associated symbols  When the words DANGER  WARNING and ATTENTION are used in this manual  they will be followed by important safety information that must be carefully adhered to     Warnings in this manual may ap
11.               Required Input Power 72 kW when in inverter mode  Walk in Function From 20  to 100  over 5 seconds  Inrush Current Less than 8 times rated current under synchronous operation  Current Limit 11596 maximum  Harmonic Currents   Less than 4  THD    Rated Voltage 208   120 Vac  Optional Voltage Variation  10  to    15     Bypass Input       Rated Frequency    50 60 Hz       Number Phases   Wires    3 Phase   4 Wire   GND       DC Nominal  Voltage    288 VDC  230 to 332 VDC        Float Charge  Regulation     324 VDC  42   with 2 25 V cell                                           Battery Ripple Voltage 296 R M S   Rated Back up Time   Refer to Battery System Manual  Rated Charge Current 20 0 Amps  Rated Voltage 208   120 VAC  Rated Current 223 Amps  Rated Power Factor 0 8 lagging  Number Phases   Wires 3 phase   4 Wire   GND  2      2   0 100  balanced load    3   0 100  unbalanced load   Voltage Adjustment Range   5V Manually from front key pad  Phase Displacement   2    0 100  balanced load    4    unbalanced load   Rated Frequency 50   60 Hz  Frequency Regulation   0 1  in free running mode  Output Frequency Synchronous    5 1 0 1 5 Hz    1 0 Hz  std   switch selectable by qualified    Operation Range       Frequency Slew Rate    technician   dip switch sets Slew Rate and Synch Range simultaneously         Voltage Transients   Recovery time  50 ms       3   100  load step change     5   loss or return of input voltage     3   transfer of bypass to inverter        
12.         25  4 22  RO 2B QC                                                     26  4 2 3    UPS Shutdown       RS 2320                  sse ener nennen nennen nnn intrent 26  5 0  SSC MMC ANOS MP EET C MTM 27  y ee Specifications     4200FA 80kVA without Internal                                        27  5 2      Specifications     4200FA 80kVA with Internal                                       28  5 3      Specifications     Efficiency and Thermal Loss at Different                                                                29  6 0     Operating Ihe UPS           Lu                                                                                   30  6 1      Operating the UPS    e t i po Frage ando PESE      30  6 1 1    AC Input Mode  normal operation                    1                  L n nana    30  6 1 2   Bypass          5  tei ei a      30  6 1 3    Battery Backup                 u                                            nnne tren nennt enne 31  6 1 4    External Maintenance Bypass  Customer Supplied                              sse 31  6 2      Battery Backup Time and Discharge                                         e 32  6 3      Battery Low Voltage                                   44  4  444424                                     32  6 4    Battery RHecharging           Leere need Le dece ide rte ede ee ee iiec ble Dee db den 33  6 5    Front Panel Layout  All Units            m einer iden testen tee testo ce            34  6 6      EPO  Emergency Powe
13.         cet ree ste         Pet tt eene dens 44  6 14 7  BUZZ STOP        ritu n uytunta e tbe bna                           ERE ass 45  GAAS RESET                                                                45  6 15  Menu Data SCIe6rs erar ear    e                                46  6 15 1  Settings for Calendar and Clock                        sse entente nnns nnne ns 46  6 15 2  AdJusting  Buzzer VOM EG uuu tette epe te OE EE t S ERE EE ET e EYE EE RE Den 46  6 15 3  Settings for Display  Duration u  irre ett scit tree ee eae er RE net PE RAE Per E ER dca d 47  6 15 4  Run SwitCh Select  estere             47  6 15 5  Serial  Com  Station Address m re t te seit aen s leer set PER ays i Ped dead 48  6 15 6  Output Voltage                            48  6 15 7  Equalize Charge Mode                              1    U    enne enne nnne ens 49  6 15 8  Reset to Default Settings                                                                     ens 49  6 16    Overload  OperatiOr    u diee diae n ee red uic iade an P esee un C        50  6 17    Backup History  amp  Fault                           nennen nemen nem inen nennen nnns 51  7 0  UPS Protection System                u naiiwanan adana danai cei iore eii inc 53  T ues System Protection                                                                                 53  7 2      System Protection Functions                          U    U    U    n    53  8 0 Preventive and Scheduled Maintenance   Part Replacemen t    
14.     37    TOSHIBA    Leading Innovation  gt  gt  gt        6 9 4    38    Line 4 System Messages    Line 4 messages reflect the UPS operating conditions  Warning messages will be displayed  when an abnormal operating condition occurs  The following table shows the allowable Line 4    messages     LINE 4 MESSAGES       Displayed Message    Meaning                  Displayed when input Phase rotation has been wired  in a counter clockwise rotation           NOT SYNCHRONIZE    Displayed when input and output frequencies are not  synchronized   abnormal          AUTOTRANSFER      Displayed when auto transfer to bypass is active  i e   current limit reached    abnormal          BATTERY LOW      Displayed when battery voltage is low  abnormal  or  the UPS batteries have failed self diagnostic test    abnormal          UPS OL  REDUCE LOAD      Displayed when UPS has tripped due to an overload  condition   abnormal        Displayed when the UPS has an internal failure                      DCOC     abnormal        Displayed when the UPS has an internal DC bus  DCOV  over voltage   abnormal   x x Displayed when the UPS has an internal DC bus  DCUB  unbalance referenced to Neutral   abnormal     UPS OL   Displayed when UPS has tripped due to an overload  condition   abnormal        Displayed when inverter output over voltage has  INOV  occurred   abnormal     INUV   Displayed when inverter output under voltage has    occurred   abnormal          BATTOH  OR MCCB B OPEN    Displayed when 
15.    14     5              1209       xEUOx  x 452 2     52 200  Zt SOGE   lt           2                   ox rusg  zo     gt  lt       gt  Sonra  be           22 enz       lt  lt  2  rz   a z  w  Ares a  az OFF 2S                      52620  vt              5 E  O                        MMM      MM        JME                                                                                       SMM   Wie  F    For international units  remove the screws that attach the shipping crate panels to each other    and to the pallet  Remove the crate and foam packing material     Unbolt the unit from the shipping pallet   Lift the UPS from the pallet using a forklift that has sufficient capacity  Approach the UPS only    Upon receipt of the UPS  a careful inspection for shipping damage should be made   from the front or rear                        NAM MEM                                                                  AS    7                                                                1              MUM                  3   4     Unpacking the UPS Equipment  2     TOSHIBA  Leading Innovation  gt  gt  gt   2 0 Unpacking Inspection Storage Disposal    2 1       Do not attempt to move the unit by the sides  Only move the    unit with a forklift or pallet jack  Moving the unit by pushing on  the sides may result in damage to the unit or injury to personnel     MMMM  SMM    4200FA XT 80kVA Installation and Operation Manual     N CAUTION    TOSHIBA    Leading Innovation  gt  gt  gt      
16.   2 2    2 3    2 4    UPS Equipment Inspection    UPS Equipment Inspection  Upon receipt of the UPS  a careful inspection for shipping damage should be made  Use  caution when removing unit from pallet  Refer to labels or documentation attached to packing  material    After Unpacking    1  Check the unit for loose  broken  bent or other damaged parts  If damage has occurred  during shipment  keep all packing materials for return to the shipping agent  The  equipment warranty will not apply to units that are damaged during shipment     2  Check to see that the rated capacity and the model number specified on the nameplate  conform to the order specifications     Storage of the UPS Equipment  If the UPS equipment is to be subject to long or short term storage  the following guidelines  should be used   Avoid   1  Storage in sites subject to extreme changes in temperature or high humidity   2  Storage in sites subject to exposure of high levels of dust or metal particles   3  Storage on inclined floor surfaces or in sites subject to excessive vibration     Before Storing   1  Allow the UPS to be operated for 24 hours to ensure that the batteries are fully charged   2  Stop the unit  see Shutdown Procedure in section 6 12    3  Place the MCCB switch of the UPS in the OFF position  see section 4 1 for location    Storing   1  Store within the temperature range of  4     104 F   20     40         2  For best results  store the UPS in the original shipping container and place on a 
17.   if battery voltage is low pin 7 will be connected to  System Common      2  Contacts are resistive loads rated at 30 VDC  0 1 A  125 VAC  3 A      3  Pin 3 is not used     4200FA XT 80kVA Installation and Operation Manual    25    TOSHIBA    Leading Innovation  gt  gt  gt        4 2 2    RS 232C  The RS 232C serial communication interface is available via a DB9 female connector located  under the Remote Eye Cover on the front of the UPS  see Section 4 for location   This  interface allows control of the UPS from a personal computer running special TOSHIBA  software  The computer and the UPS are connected through a serial RS 232C  communication port  The available data from the UPS  via the RS 232C communication link is  shown below        Input Voltage  Output Voltage  Output Current  Battery Voltage  Input Frequency  Output Frequency    Operating Conditions       Utility Power OK  Low Battery Voltage Detected  UPS Operating Status UPS in BYPASS Mode   Described as Yes or No  UPS in NORMAL Mode  Input and Output Frequency Synchronized  UPD FAULT Occurred           Described as Occurred or Not Occurred     DC Bus Over Current   DC Bus Over Voltage   DC Bus Under Voltage   Input Over Current   Overheat   Overload Being Timed   Overload  allowable time exceeded    Output Over Voltage  during Normal Mode   Output Under Voltage  during Normal Mode     Fault Details             The connector pin assignment and female connector outline are illustrated below                        
18.  Delta Input  208 120V Output    For Maximum cable sizes  see Note 7        General Mechanical Information                                     Dimensions   Approximate Thermal Load  UPS kVA  KW Rating Vin    Vout  W xDxH  d at Rated Output  Inches i kBTU s   Hr   80 kVA   64 kW 208 120 Vin    208 120 Vout 44 x 31 x 74 2100 29 8  80 kVA   64 kW 208 Vin    208 120 Vout 44 x 31 x 74 2300 34 4  80 kVA   64 kW 380 Vin    208 120 Vout 44 x 31 x 74 2300 34 4  80 kVA   64 kW 480 Vin    208 12 Vout 0 44 x 31 x 74 2300 34 4  80 kVA   64 kW 600 Vin    208 12 Vout 0 44 x 31 x 74 2300 34 4             Primary AC Input                                     Suggested ca   Suggested Maximum  Maximum Input Power Demand External Feeder uec cei gee a Feeder Length For Min  Wire   Breaker Size in Steel Conduit  Vin PF Amps     Nom   Max  Amps AWG or kcmil at 75   C Temp  Rating Feet  208 120 Wye   50 98   208  224  300 A  1 x500 kcmil   1  x 500 kcmil 480  208 Delta    gt 0 98   208  224  300 A  1 x300 kcmil 480  380 Delta    gt 0 98   114 123  175A  1  x 2 0 480  480 Delta   50 98 90  97  120A  1  x  2 AWG 480  600 Delta   50 98 72  78  100A  1  x  3 AWG 480                Optional Alternate AC Input     All 80        Models  208 120V 3 Phase   4 Wire                          Suggested um    Suggested Maximum  Maximum Input Power Demand External Feeder Suggested s deaur cetus Feeder Length For Min  Wire  Size Per Phase   Neutral         Breaker Size in Steel Conduit  Vin      Amps     Nom   Max  
19.  and to  any connected loads  see Section 6 6  EPO Function    All LEDs are off and the LCD display    will show the following message          OUTPUT SHUT DOWN    OUTPUT VOLTAGE  0V  CURRENT LOW LOW LOW              4200FA XT 80kVA Installation and Operation Manual    41    TOSHIBA    Leading Innovation  gt  gt  gt        6 13 Keypad Overview    The following illustrates the 12 key data entry pad with each key functionally labeled  see  Section 6 5     Front Panel Layout            MONI BATT F1          BATT  IN OUT TEST          BUZZ  STOP    RESET IN x    MENU   ENTER                                           MONI    Monitor  Press to display system monitoring screens  see Section 6 14 1            BATT    Battery  Press to display UPS battery conditions  see Section 6 14 4            F1    Function Key  Press to change settings of various menus  see Section 6 14 5            Input  Press to display UPS input conditions  see Section 6 14 2            OUT    Output  Press to display UPS output conditions  see section 6 14 3            BATT  TEST    Battery Test  Press to execute on line battery test  see section 6 14 6            BUZZ  STOP    Buzzer Off  Press to stop the audible alert buzzer  see section 6 14 7            MENU    Menu  Press to display the main menu  see section 6 14 5            ENTER    Enter  Press to accept a user selected command or action  see section 6 14 5            RESET    Reset Display  Press to reset the message display area of the UPS  see S
20.  is left blank              If an AC input power failure occurs and no abnormal operating conditions are present  the  UPS switches to the Battery Backup mode  The following system message is displayed when  the BATT key is pressed          BATTERY BACKUP    BATTERY VOLTAGE  324V  DISCHARGE CURR  76  Note  Line 4 is left blank              6 14 5 MENU  F1  ENTER  UP DOWN Keys    Press the MENU key during normal AC Input Mode of operation to access the menu of user  adjustable data screens  Press the Up Down arrow keys to scroll through the available data  screens  Pressing the F1 key changes to the adjustment screen for that menu item  Press the  Up Down arrow keys to move the display to the next     From the adjustment screen  if the MENU key is pressed any changes are discarded and the  display returns to the regular menu screen with the previous data values shown  If the  ENTER key is pressed from the adjustment screen  the changes are saved  After pressing  ENTER  the display screen will return to the regular menu screen with the new data values  shown  see Section 6 15 Menu Data Screens      6 14 6 BATT TEST Key  Pressing the BATT TEST key during normal AC Input mode of operation displays battery  back up information  The following system message is displayed          BATTERY TEST    BATTERY VOLTAGE  324V           gt  F1 ENTER TO BEGIN       Press the Fi  ENTER keys at the same time to begin the battery test  The following system  message is displayed          BATTERY T
21.  power source     2  Remove watches  rings  jewelry  or other metal objects    3  Use tools with insulated handles to prevent inadvertent shorts    4  Wear rubber gloves and boots    5  Do not place tools or metal parts on top of the batteries    6  Determine if the battery is inadvertently grounded  If inadvertently grounded  remove    source of ground                 LT LET o        LL     GIT Tho likelihood of such shock will be reduced if such grounds are  removed during installation and maintenance    7  Verify circuit polarities prior to making connections    Disconnect charging source and load prior to connecting or disconnecting terminals    9  VRLA batteries contain an explosive mixture of hydrogen gas  Do not smoke  or create a           or spark in the immediate area of the batteries  This includes static electricity from the body    10  Do not attempt to open the batteries in order to add water or sample the specific gravity of the  electrolyte  The batteries are valve regulated lead acid type and such servicing is not possible  without damaging the battery    11  Use proper lifting means when moving batteries and wear all appropriate safety clothing and  equipment    12       not dispose of lead acid batteries except through channels in accordance with local  state  and federal regulations                  6 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        INSTRUCTIONS IMPORTANTES CONCERNANT  LA SECURITE       
22.  tables     Line 1 System Messages  Line 1 messages are based on the operating mode  The following table shows all allowable  Line 1 messages  which occur while starting up and while in main monitor  MONI  screen  mode     LINE 1 MESSAGES                               Display Message Description    UPS START UP   Displayed when UPS is in the start up condition  or display board is resetting     BYPASS OPERATION   Displayed when the UPS is in Bypass  Operation     UPS ON LINE   Displayed when the inverter is running   Displayed during Utility abnormality  inverter is    BATTERY DISCHARGE   supplying power from batteries   Unit shuts  down after Vmin  is reached   Displayed during power failure if Vmin  is    OUTPUT SHUTDOWN   reached  or an EPO is received  or after  completion of Shutdown Sequence of the  Inverter and Bypass is not available     BATTERY BACKUP   Displayed during input power failure           Line 2 System Fault Messages  Line 2 fault messages are automatically displayed when a system fault is detected     LINE 2 MESSAGES                                        Display Message Meaning   DCUV DC Under voltage   DCOC DC Over current   DCUB DC Unbalanced   DCOV DC Over voltage   EERR Main EEPROM error  OH Overheat  internal   OL Output Overload   IVUV Inverter Under voltage   IVOV Inverter Over voltage          Line 3 System Messages  Line 3 messages show load current information  and user selected instructions     4200FA XT 80kVA Installation and Operation Manual
23. AGE         gt F1  DATA SET MODE   gt  A V  PRV NEXT SCREEN             Press the F1 key to display the following active adjustment screen        OUTPUT VOLT  ADJUST  REFERENCE ADJUST       gt A V  CHANGE DATA   gt ENTER  ACCEPT CHANGE             The fields marked    will show the numerical value of the allowable voltage adjustment  parameter values  Press the Up Down arrow keys to adjust the setting  5 volts  This results  in a  2   change      the output voltage     Attempts to adjust this setting while the inverter is not running will result in the following error  message        OUTPUT VOLT  ADJUST  ADJUST PROHIBITED   DATA CANNOT CHANGE      A V  PRV NEXT SCREEN             48 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 15 7 Equalize Charge Mode Select  Contact Toshiba Customer Support toll free at 1 800 231 1412 before using this option     DAMAGE to the battery system may occur if this option is used improperly   6 15 8 Reset to Default Settings    Press the MENU key to access the menu data screens  Press the Down arrow key to access  the original factory default settings adjustment screen        MENU DATA RESET  DATA INITIALIZATION   gt F1  TO ACCESS RESET   gt A V PRV NEXT SCREEN             Press the F1 key to display the following active adjustment screen        MENU DATA RESET  DATA INITIALIZATION   gt  MENU       DATA RESET   gt ENTER  ACCEPT CHANGE             When the ENTER key is pressed the followin
24. Amps AWG or kcmil at 75      Temp  Rating Feet  208 120 Wye   50 98   208  224  300 A  1 x500 kcmil   1  x 500 kcmil 480                   Battery Input  288VDC Nominal        Battery Capacity Required  for Full Load Output    Maximum Discharge  at Full Load Output    Suggested External  Feeder Breaker    Suggested Minimum Feeder    Wire Size    Suggested Maximum Feeder Length  For Min  Wire Size in Steel Conduit       kWB    Amps         Amps    AWG or kcmil at 75  C Temp  Rating    Feet       80 77          335        1  X 400 kemil    enon       2  x 2 0       70             AC Output  208 120V 3 Phase   4 Wire                                      Suggested 21 i   Suggested Maximum  Rated Output Power Demand External Feeder         testa Feeder Length For Min  Wire  Breaker Size in Steel Conduit  Vout PF Amps     Nom   Max  Amps AWG or kcmil at 75      Temp  Rating Feet  208 120 Wye 0 8 222 300 A  1  x 500 kcmil   1  x 500 kcmil 480  58 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    TOSHIBA INTERNATIONAL CORPORATION    INDUSTRIAL DIVISION   13131 West Little York Rd   Houston  TX 77041   Tel  713 466 0277 Fax 713 466 8773   US 877 867 8773 Canada 800 872 2192 Mexico 01 800 527 1204    www toshiba com ind    Printed in the U S A     
25. ED lamps  It should be used in conjunction with the LCD display   see Section 6 9  and the audible alarms  see Section 6 7  for total system monitoring                    LED ON OFF STATUS LED ON OFF STATUS  Normal UPS Operation Output Shutdown   UPS on line  no abnormal conditions   After Emergency Power Off received  EPO     AC IN   ON AC IN   OFF   INV   ON INV   OFF   BYP   OFF BYP   OFF   BATT   OFF BATT   OFF   FAULT   OFF FAULT   OFF             Bypass Operation  UPS Fault    Fatal Commu    nication Error     Display to Control Interface                             AC IN   ON AC IN  INV   OFF INV ALL ON OR  BYP   ON BYP FLICKERING  BATT   OFF BATT RAPIDLY  FAULT   ON FAULT  Battery Back up   Battery Voltage Low   AC IN   OFF  INV   ON  BYP   OFF  BATT   ON  Blinking   FAULT   OFF       36    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 9    6 9 1    6 9 2    6 9 3    LCD Functions    The LCD display is a 4 line by 20 character display  The LCD display conveys system  operational information  It should be used in conjunction with the LED display  see Section  6 8  and the audible alarms  see Section 6 7  for total system monitoring     Listed below are the types of user notification messages that are available for each line of the    LCD display screen and a description of each  This message displayed is determined by the  UPS operating mode and conditions  These messages are shown in the following line  message
26. EST    BATTERY VOLTAGE  324V     MINS    SECS   gt  PLEASE WAIT             44 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Upon completion of the battery test the previous operation is resumed and the main system  MONI screen will be displayed  The following system message is displayed if the battery test  detects a low DC battery voltage          UPS ON LINE    OUTPUT VOLTAGE  208V  CURRENT 38 55 48      LOW BATTERY               The following system message is displayed upon the successful completion of the battery  test          UPS ON LINE   Note  Press the MONI key to return    OUTPUT VOLTAGE  208V to the main monitoring menu   CURRENT 38 55 48   DATE  DAY  TIME             If the inverter is not operating when the BATT TEST key is pressed then the function will be  inhibited  disabled  and the following screen message will be displayed          BATTERY TEST    BATTERY VOLTAGE  324V       BATT  TEST INHIBITED          NOTE   After start up  the battery test function is inhibited for 20 min   Only one battery test can be  done approximately every 20 min       6 14 7 BUZZ STOP Key    Turns off the audible alarm     6 14 8 RESET Key    Resets the LCD display board software should a system lock up occur  The reset does not  reset memory variables     Use of the RESET function is very important when a fatal communication error has occurred     Press and hold the RESET key for five seconds or more to reset the display s
27. IN A TEMPERATURE AND HUMIDITY CONTROLLED INDOOR  AREA FREE OF CONDUCTIVE CONTAMINANTS      ANATTENTION    EN CAS D UTILISATION EN ATMOSPHERE CONTROLEE   CONSULTER LA NOTICE TECHNIQUE     BATTERY BACK UP TIME  WHICH WAS FACTORY SET AT A  PREDETERMINED LEVEL  DECREASES GRADUALLY BETWEEN  SERVICE PERIODS  THE BATTERIES SHOULD BE REPLACED  EVERY THREE YEARS AFTER THE LAST SERVICING  THE DATE  OF WHICH IS WRITTEN ON THE ID PLATE LOCATED ON THE  REAR SIDE OF THE UPS UNIT  OR IN THE BOX BELOW     DATE OF LAST BATTERY CHARGE           4 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        IMPORTANT SAFETY INSTRUCTIONS  SAVE THESE INSTRUCTIONS This manual contains important instructions    that should be followed during the  installation  operation  and maintenance of the UPS and its batteries  Turn off  lockout  and tagout all  power sources before proceeding to connect the power wiring to the equipment or when performing  maintenance  Hardwire type UPS units are not equipped with an over current protection device nor an  output disconnect for the AC output  Therefore  a circuit breaker should be provided by the user  between the UPS output and the load input  This device should be rated as follows     Device Type 80 kVA  Rated Output 208 120 VAC  Device Rating 240 V  300       The maximum ambient temperature in which the UPS unit should be operated is 40  C  104       The nominal battery voltage is 288VDC     Only a qualified TOSHIBA 
28. Inverter Overload Capacity    125  30 sec   150  5 sec       Bypass Overload Capacity    1000  10 ms  125  10 min        Crest Factor    2 5       Neutral Line Conductor    1 73 times line rating       Harmonic Voltage    1 5  max  linear load        Inrush Current protection    Automatic transfer to bypass  then retransfer to inverter          Environment    Efficiency  Typical     AC AC   See Section 5 3   DC AC  88        Heat loss to be removed    See Section 5 3       Audible Noise    75 dB  A  at 3 3 ft   1 m  from the units front display       Operating Temperature    0     104  F  0     40  C   optimal operating temperature  77  F  25  C        Operating Humidity    Less than 90  RH  non condensing           Altitude       Less than 6600 ft   2000 m           1   Specified at rated conditions under balanced linear loads     2  Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site  An initial  charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation   3   At 6600 ft   2000 m  above sea level  output capacity should be derated by 3   Consult factory for higher elevations      4     Continuous operation at  10  to  15  Vin requires EITHER derating the output capacity 15  OR decreasing the maximum Operating Temperature  to 90   F   32   C      5     Continuous operation at  15  to  30  Vin requires derating the output capacity 30      4200FA XT 80kVA I
29. N  SEC VB 324V  BT  PF OL   gt A V  EXIT F1  NEXT             Press the Up Down arrow keys to return to the Battery Discharge Count screen        BATT DISCHARGE COUNT    TIMES   gt  F1  FOR DETAILS   gt A V  TO SCROLL             Press the Up Down arrow keys to display the Fault Count screen        TOTAL FAULT COUNT     TIMES   gt  F1  FOR DETAILS   gt A V  TO SCROLL             4200FA XT 80kVA Installation and Operation Manual 51    TOSHIBA    Leading Innovation  gt  gt  gt        Press the F1 key to display the record relating to the first fault        FAULT HISTORY   1   Date Time  fault code   gt A V  EXIT   1  NEXT             Press the F1 key again to display the record relating to each subsequent fault        FAULT HISTORY       Date Time  fault code   gt A V  EXIT F1  NEXT             Press the Up Down arrow keys to return to the Fault Count screen        TOTAL FAULT COUNT     TIMES   gt  F1  FOR DETAILS   gt A V  TO SCROLL             52 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        7 0 UPS Protection System    7 1    Input Abnormal       yA    Power Flow      7 2    System Protection Features    The following one line schematic illustrates the electrical locations of the protection devices    on the 80 kVA UPS models        Low Battery PARS    System Protection Functions    Current Limit  Overload    Overcurrent    1  1  1    Over Voltage           Under Voltage        Output  Power         External Overheat  B
30. N Contact your TOSHIBA sales representative if using battery systems    The following illustration shows the battery discharge process at full load conditions      lt                           Voltage                _ Shutdown     voltage          100    20  0   Battery Capacity    6 3 Battery Low Voltage Tolerances    Excessive discharge will cause the UPS battery voltage to drop below tolerable levels  The  table below lists the normal operating voltage  the voltage levels at which the low voltage  alarm will sound  and the low voltage level at which an automatic shut down will occur                    Nominal Voltage 288 VDC  Alarm Voltage 252 VDC  Shutdown Voltage min  216 VDC          32 4200FA      80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 4 Battery Recharging  The illustration below shows the battery recharge process after a full discharge     Current  Voltage             Charging Battery  urr charge  Icharge   voltage          7Discharge  shut off point        Fully    charged  Period 1 Period 2 Period 3    The recharge process typically consists of three periods  During the first period  the charging  current is maintained at approximately 20 0 amperes  This current is the maximum value that  can be used to charge the batteries  for minimal recharge time  while assuring safety and  long battery life        Time       In the second period  constant voltage control starts and the current gradually decreases as  the ba
31. PS system is equipped with terminals for receiving an emergency power off   EPO  closed contact switch command from two locations   1  a remote location  see Section  4 2 Terminal Block Details  and  2  from a front panel mounted EPO switch  see Section 6 5  Front Panel Layout      This safety feature enables quick shutdown of the UPS AC output and battery circuits   Typically the emergency power off switch is installed in a central location that is easily  accessible to personnel concerned with the operation of the UPS unit and the equipment  connected to it  The EPO function is initiated by pressing the switch to the closed Shutdown  position  The effect of using the EPO switch is the same whether the UPS unit is in the AC  input mode  see Section 6 1 1   battery backup mode  see Section 6 1 3   or the circuit bypass  mode  see Section 6 1 2   See EMERGENCY OFF screen in Section 6 12 Shutdown  Procedure  The following figure shows the UPS condition after application of the EPO switch   Use the Start up Procedure  see Section 6 11  for restarting the unit                 Power Flow    Output  O Power    Charger   Chopper            External   Batteries   67 Audible Alarm Functions  While in the battery backup mode  during a fault  during a low battery condition  or if the  system is in an overload condition  an audible alarm will sound  The following table shows the  audible alarm pattern for each condition  Time intervals are shown in seconds  The audible  alarm can be stop
32. Representative who is knowledgeable in batteries and the required  precautions should only perform battery servicing  Keep unauthorized personnel away from batteries  To  arrange for battery replacement  contact TOSHIBA for service     Qualified Personnel ONLY    A Qualified Person is one that has the skills and knowledge relating to the construction  installation   operation  and maintenance of this electrical equipment and has received safety training on the hazards  involved  Refer to the latest edition of NFPA 70E for additional safety requirements      Qualified Personnel Shall    1  Have carefully read the entire operation manual    2  Be trained and authorized to safely energize  de energize  ground  lockout tagout circuits and  equipment  and clear faults in accordance with established safety practices    3  Be trained in the proper care and use of protective equipment such as safety shoes  rubber gloves    hard hats  safety glasses  face shields  flash clothing  etc   in accordance with established safety   practices      Be trained in rendering first aid    5  Be knowledgeable of batteries and the required precautions     For further information of workplace safety visit www osha gov   Refer to the Battery System Manual when scheduling battery maintenance or battery replacement     DANG ER Misuse of this equipment could result in injury and equipment damage   In no event will TOSHIBA Corporation be responsible or liable for    indirect  or consequential damage or in
33. TOSHIBA    Leading Innovation  gt  gt  gt        UNINTERRUPTIBLE POWER SYSTEM  UPS     4200FA XT    INSTALLATION AND  OPERATION MANUAL  Three Phase 80 kVA UPS       Document No   56418 005  Date  June 2011    TOSHIBA    Leading Innovation  gt  gt  gt        4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        4200FA XT  THREE PHASE 80 kVA  UNINTERRUPTIBLE POWER SYSTEM    USER   S MANUAL    c UL us    FOR MODELS    T42F3F800FAXXN  T42F3 800FAXXN  T42 3F800FAXXN    TOSHIBA INTERNATIONAL CORPORATION  INDUSTRIAL DIVISION  13131 West Little York Road  Houston  TX 77041 9990    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        IMPORTANT NOTICE    The Instructions contained in this manual are not intended to cover all of  the details or variations in equipment or to provide for every possible  contingency to be met in connection with installation  operation  or  maintenance  Should further information be required or should particular  problems arise which are not covered sufficiently the matter should be  referred to the local TOSHIBA sales office     The contents of this instruction manual shall not become a part of or  modify any prior or existing equipment  commitment  or relationship  The  sales contract contains the entire obligation of TOSHIBA  INTERNATIONAL CORPORATION  The wa
34. TOSHIBA power  electronics product  This manual includes a section on General Safety Instructions that describes the  warning labels and symbols that are used throughout the manual  Read the manual completely before  installing  operating  or performing maintenance on this equipment     This manual and the accompanying drawings should be considered a permanent part of the equipment  and should be readily available for reference and review  Dimensions shown in the manual are in metric  and or the English equivalent     TOSHIBA reserves the right  without prior notice  to update information  make product changes  or to  discontinue any product or service identified in this publication     TOSHIBA is a registered trademark of TOSHIBA INTERNATIONAL CORPORATION  All other product or  trade references appearing in this manual are registered trademarks of their respective owners     TOSHIBA shall not be liable for technical or editorial omissions or mistakes in this manual  Nor  shall it be liable for incidental or consequential damages resulting from the use of information  contained in this manual     This manual is copyrighted  No part of this manual may be photocopied or reproduced in any form without  the prior written consent of TOSHIBA INTERNATIONAL CORPORATION      Copyright 2010 TOSHIBA INTERNATIONAL CORPORATION     All rights reserved     Printed in the U S A     Contacting TOSHIBA Customer Support Center    The TOSHIBA Customer Support Center can be contacted to obtain he
35. Used  5     Inverter Supply 6   Inverter Supply  7     Remote Run  P2443  8   Remote Run  9   Remote Stop  P24A3  10   Remote Stop  11     Bypass 12 Common  13          14 EPO  TB3 Connections  3     Battery Shunt Trip Out 4     Battery Shunt Trip Out  5   Battery AUX In 6     Battery AUX In                Recommended Wire Size and Tightening Torque UPS Control and Battery Interface       Minimum Wire Size and Tightening Torque for UPS Control and Battery Interface Circuits  USE MINIMUM 75  C COPPER WIRING                TERMINAL  TERMINAL    AWG TIGHTENING TORQUE   UPS CONTROL CIRCUITS  1 18  14 16 8 in lbs      BATTERY CONTROL CIRCUITS  3 6  14 16 8 in lbs                 24     Indicates Class 1 wiring method is to be used     4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        4 2    4 2 1    Notes     Communication Interface    Remote Contact  The remote contact interface is a standard feature and is available as dry switch contacts  through a DB9 male connector located under the Remote Eye Cover on the front of the UPS   see Section 4 for location   The following schematic shows the contact state and pin  assignment for each signal and the associated DB9 connector pin out     moO 5 System Common  DB9 Male Connector Outline         E 6 Bypass Active  facing connector      O 7 Battery Voltage Low    i eroe 8 UPS On line            Battery Discharge       Fault Signal Detect    1  Switches are shown in their inactive states
36. abel  Wait  for at least the minimum time indicated on the label and ensure that the front panel  LED s have gone out before removing the front panel of the UPS once the UPS power  has been turned off    8  Do not attempt to disassemble  modify  or repair the UPS  Call TOSHIBA Service for  repair information    9  Turn the power on only after attaching ALL the covers and DO NOT remove any  covers of the UPS when the power is on    10  If the UPS should emit smoke or an unusual odor or sound  turn the power off  immediately    11  The heat sink and other components may become extremely hot to the touch  Allow  the unit to cool before coming into contact with these items    12  Warning signs should be placed on or near the load to let people know that the load is  being powered by the UPS     13  Additional warnings and notifications shall be posted at the equipment installation  location as deemed required by Qualified Personnel     CAUTION When the UPS is in the Inverter mode  turning the breaker to the OFF  position will cause the unit to go into the battery backup mode  The  UPS will continue to provide power to the load  The unit must be in Bypass mode and then   the breaker turned to the OFF position for the UPS to shut down power to the load     12 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt           CAUTION    reset     4 0 UPS Connections    4 1    UPS Power and Control Connections    Do not EPO  Emergency Power OFF  
37. ads     2  Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site  An initial  charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation   3   At 6600 ft   2000 m  above sea level  output capacity should be derated by 3   Consult factory for higher elevations    4     Continuous operation at  10  to  15  Vin requires EITHER derating the output capacity 15  OR decreasing the maximum Operating Temperature    to 90   F   32   C      5     Continuous operation at  15  to  30  Vin requires derating the output capacity 30      28    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        5 3 Specifications     Efficiency and Thermal Loss at Different Loads                                                  Percent of Rated Efficiency  Load  Transformerless W  Internal  Transformer  100  Load 88  86 4    Contact the factory for additional information on efficiency vs  load curves   Percent of Rated Load Thermal Loss  BTU Hr   Transformerless W  Internal  Transformer  100  Load 29 778 34 374  75  Load 23 184 26 662  50  Load 16 750 19 117  25  Load 11 984 13 225  No  Load 5 398 8 319            The thermal loss are listed for no load  25 50 75 100  loads under two sets of conditions      UPS without internal transformer     UPS with Internal transformer   NOTE  The thermal values listed are representative only  Individual 
38. atteries    The following tables show the built in UPS fault protection functions of the 80 kVA models     Built in UPS Fault Protection Functions       Inverter Overvoltage    Inverter Undervoltage                   Protection Item  IVOV   IVUV  UPS Overload  INVERTER INVERTER  LCD Message OVERVOLTAGE UNDERVOLTAGE SDUTPDLOVERLOAD  Cause Control Malfunction  Feedback Error Overload or short circuit at the load   Operation Mode    Inverter Overload  Transfer to bypass  Inverter stopped   after Fault Bypass Operation  Chopper and Inverter Stopped Bypass Overload  Inverter  Chopper   amp  Bypass stopped   Audible Alarm Yes  See Section 6 7 Audible Alarm Functions       Visible Alarm    Red Fault Lamp On    Inverter OL  No Fault Lamp     Bypass OL  Fault Lamp On       Relay Contact  Alarm    Fault Relay closed  Bypass Relay closed    Inverter OL  Bypass Relay closed  Bypass OL  Bypass Relay open and Fault relay closed       Auto Retransfer    No    Inverter OL  Yes  if bypass OK     Bypass OL  No          Protection Item    Low Battery Voltage    Low Battery Voltage    Inverter Output Current Limit        level 1   level 2   Line 4 will read  LCD Message BATTERY LOW DC UNDERVOLTAGE OUTPUT OVERLOAD       Cause    Battery Discharge    Battery Shutdown Level  reached    Load Inrush current       Operation Mode  after Fault    Battery Discharge    Shutdown  No Output    If Bypass OK  transfer to bypass  If not  current limit mode       Audible Alarm    Yes  See Section 6     7 Audibl
39. aximum size     15 25 30kVA   1 AWG               250 kcmil   80kVA  500 kcmil  Battery Terminals     600 kcmil  Nominal battery voltage based on the use of VRLA type batteries  2 0 volts   cell nominal    Maximum battery discharge current based on lowest permissible discharge voltage of 1 6 VPC     10  DC wires should be sized to allow not more than a 2 volt drop at maximum discharge current   11  Weights include internal batteries   12  Sizing calculations based on the following assumptions       Not more than 3 current carrying conductors installed in steel conduit in ambient temperature of  30 degrees C       Temperature rating of conductors and terminals  75 deg  C     Feeder distance calculations based on NEC Tables 8 and 9 data  allowing for 296 AC voltage drop       Reference  2008 NEC Handbook  Consult latest edition of applicable national and local codes for  possible variations     13  Ratings of wires and overcurrent devices are suggested minimums  Consult with a    registered Professional Engineer within your local area for proper size selections     TOSHIBA INTERNATIONAL CORPORATION    13131 West Little York Road  Houston  TX 77041  Telephone  800 231 1412  713 466 0277  Fax  713 896 5212  Corporate Web Site  www tic toshiba com  Group Web Site  www toshibaups com    4200FA XT 80kVA Installation and Operation Manual 57    TOSHIBA    Leading Innovation  gt  gt  gt        Installation Planning Guide for 80kVA UPS    Standard Systems  208 120V Wye  208 380 480 600V
40. creen will be displayed          BYPASS OPERATION    OUTPUT VOLTAGE 208V  CURRENT  100 100 100   gt PLEASE WAIT             Or if the UPS is waiting and the RUN STOP key switch is switched to the STOP position  while the UPS is waiting the following screen will be displayed          BYPASS OPERATION    OUTPUT VOLTAGE 208V  CURRENT  100 100 100   gt PLEASE WAIT             If the RUN STOP key switch remains in the STOP position when the wait period of the UPS  is complete the following screen will be displayed          BYPASS OPERATION    OUTPUT VOLATAGE    V  CURRENT 100 100 100   DATE  DAY  TIME             4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        If the RUN STOP key switch remains in the RUN position when the wait period of the UPS is  complete the following screen will be displayed          UPS ON LINE    OUTPUT VOLTAGE  208V  CURRENT 100 100 99   DATE  DAY  TIME             6 17 Backup History  amp  Fault History  Pressing the MONI and F1 keys simultaneously for a few seconds will cause the Battery  Discharge Count screen to be displayed        BATT DISCHARGE COUNT    TIMES   gt  F1  FOR DETAILS   gt A V  TO SCROLL             Press the F1 key to display the record relating to the first discharge event        BACKUP HISTORY   1    MIN  SEC VB 324V  BT  PF OL   gt A V  EXIT F1  NEXT             Press the F1 key again to display the record relating to each subsequent discharge event        BACKUP HISTORY        MI
41. e Alarm Functions       Visible Alarm    Battery Lamp Flickers    NO    NO       Relay Contact  Alarm    Low Battery Relay closed    Bypass Relay closed                                  Auto Retransfer No Yes  if bypass OK  Protection Item Memory error  EERR  Internal overheat  OH  DG eon ege DC circuit overcurrent  DCOC   LCD Message MAIN EEPROM ERROR OVERHEAT  INTERNAL DC OVERVOLTAGE DC OVERCURRENT  Cause Control board chip error Fan failure  high ambient Chopper malfunction Inverter   chopper fault  Operation Mode  E         after Fault Start is inhibited Bypass operation  chopper and inverter are stopped  Audible Alarm Yes  continuous buzzer       Visible Alarm    RED fault lamp On       Relay Contact  Alarm    Fault relay closed  bypass relay closed          Auto Retransfer       NO       4200FA XT 80kVA Installation and Operation Manual    53       TOSHIBA    Leading Innovation  gt  gt  gt        8 0 Preventive and Scheduled Maintenance   Part Replacement    8 1 Preventive Maintenance  TOSHIBA 4200FA Uninterruptible Power Systems have been designed to provide years of  trouble free operation requiring a minimum of preventive maintenance     The best preventive measure that the UPS user can take is to keep the area around the unit   particularly the air inlet vents  clean and free of moisture and dust accumulations  If the  atmosphere of the installation site is very dusty  use a vacuum cleaner to periodically remove  dust accumulations from the system  Schedule authoriz
42. e bypass circuit because of an overload  and the overload condition ends within a specified period of time  normal operation will  resume automatically  see Section 6 16 Overload Operation      If the power flow is transferred to the bypass circuit due to a fault condition  the power flow  must be transferred manually from the Bypass circuit back to the inverter circuit after the fault  is cleared  see Section 6 11 Start up Procedure          Static    Power Flow Bypass                       Isolating Output  TRUE mM    ee  Power    id    Charger   Chopper    External  Batteries    Power flow in circuit bypass mode for the 4200FA 80 kVA UPS    30 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 1 3 Battery Backup Mode  The following illustration shows power flow during the battery backup mode  In the event of  an AC power failure the batteries of the UPS instantly begin supplying DC power to the UPS  to the main inverter circuit  This circuit converts the DC power into AC power  The AC power  is available at the output of the unit  This back up process will continue until the UPS battery  voltage drops below a specific minimum level  At which time the batteries cease supplying  power to the load     This minimum level is the shutdown voltage minimum  V min   The rated battery voltage table  on page 36 shows  V min   The battery backup time and discharge process is explained in                        Section 6 2       Stat
43. e off  and that the RUN   STOP Switch is in the STOP  position     2  Switch on the power at the customer provided UPS input distribution panel   3  Setthe MCCB power switch of the UPS to On  see Section 4 for location   The AC IN    lamp will be on  The LCD display  see Section 6 5  Front Panel Layout   will show the  following message          UPS START UP   Note  Lines 2  amp  3 are blank            gt  PLEASE WAIT       With the key switch in the STOP position  both the AC IN and the BYP LEDs will be on and  the LCD display will show the following message          BYPASS OPERATION   Note  Actual numerical values may  OUTPUT VOLTAGE 208V differ from these examples    gt CURRENT 100 100 100    DATE  DAY  TIME             The battery charging circuit of the UPS is now activated  Move the RUN STOP key switch to  the RUN position  The inverter of the UPS will start and the UPS will be in the normal  operating mode     Both the AC IN and the INV LEDs will be on  The following system message is an example of  the main MONI  monitor  screen for standard operation  see Section 6 14 1  MONI  Function            UPS ON LINE    OUTPUT VOLTAGE 208V   gt CURRENT 100 100 100    DATE  DAY  TIME             If a fault occurs during start up  the red FAULT lamp will be on and the LCD display will  display a FAULT s  DETECTED at start up message such as the following        UPS FAULT  BYPASS ON  Note  UPS will not start when this   DESCRIPTION  message is displayed   PRESS DOWN TO DETAIL   
44. ection  6 14 8            Up     Arrow  Press to scroll forward through display data values  or to scroll forward  through menus  see section 6 14 5            D       Down Arrow  Press to reverse scroll through display data values  or to reverse scroll  through menus  see section 6 14 5            42    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 14 Key Functions  6 14 1 MONI    Upon completion of a successful UPS startup  the system will be in the AC Input mode of  operation  The LCD display will show the main MONI  monitor  function  If the MONI key is  pressed at this time the display output will not change  The MONI function monitors the entire  UPS system  The LCD display will switch off after a period of keypad inactivity and switch on  if any key is pressed  It will switch on if the battery discharge reaches a critical level or if an  abnormality develops in the system  see Section 6 15 3     Settings for LCD Display  Duration   All system line messages will be displayed from the MONI mode when system  problems are detected  If the AC input power is available and no abnormal operating  conditions are present the following system message is displayed          UPS ON LINE   Note  Actual numerical values may differ  from these examples  If output current  OUTPUT VOLTAGE  208V drops below 1596  display reads   CURRENT 100 100 100  OUTPUT CURRENT LOW   DATE  DAY  TIME             If an AC input power failure occur
45. ed factory service representatives to  perform internal parts inspections semi annually     C AUTION Only factory trained representatives should perform repairs or  maintenance on the UPS      Proper maintenance of the battery system of this unit by a qualified  CAUTION service technician is essential to the safety and reliability of your UPS    system  Refer to the battery service manual     8 2 Parts Replacement  The following list shows intervals for periodic maintenance and replacement of certain UPS  parts     1  Batteries  Valve Regulated Lead Acid  VRLA  batteries are maintenance free with  respect to electrolyte only  The charging voltage  temperature  performance and  connection resistance must be monitored periodically  Necessary corrective actions  must be made in order to assure safe reliable power is supplied by the UPS  The  aforementioned items affect the life of batteries  so replacement should be once  every 3 to 5 years as a minimum  All of the batteries must be replaced at the same  time     Recommended Quarterly Maintenance   A  Visual Checks  1  Leakage   2  Corrosion on positive terminal   Check battery temperature at the negative terminal   Measure and record the system float charging voltage   Measure and record the float charging voltage of each unit     gom    Recommended Semi Annual Maintenance  A  Repeat the quarterly checks   B  Perform impedance checks on the individual batteries   C  Testfor the purpose of trending the battery over time   D  Re 
46. ed load    phase phase    3   0 100  unbalanced load   Voltage Adjustment Range  5 V Manually from front key pad  Phase Displacement   2    0 100  balanced load    4   unbalanced load   Rated Frequency 50   60 Hz  Frequency Regulation   0 1  in free running mode  Output Frequency Synchronous    5 1 0 1 5 Hz    1 0 Hz  std                                 Operation Range    switch selectable by qualified technician       Frequency Slew Rate    1 Hz s to 3 Hz s       Voltage Transients   Recovery time  50 ms       3   100  load step change     5   loss or return of input voltage     3   transfer of bypass to inverter        Inverter Overload Capacity    125  for 30 sec   150  for 5 sec       Bypass Overload Capacity    125  for 10 min   1000  for 10 ms       Crest Factor    2 5       Neutral Line Conductor    1 73 times line rating       Harmonic Voltage Distortion    1 5  max  linear load        Inrush Current protection    Automatic transfer to bypass  then retransfer to inverter          Environment    Efficiency  Typical     AC AC     See Section 5 3  DC AC  83        Heat loss to be removed    See Section 5 3       Audible Noise    75 dB  A  at 3 3 ft   1 m  from the units front display       Operating Temperature    0     104 F  0     40   C   optimal operating temperature  77  F  25   C        Operating Humidity    Less than 9096 RH  non condensing           Altitude 7          Less than 6600 ft   2000 m           1   Specified at rated conditions under balanced linear lo
47. ent                                        Ent nae eb Leda n d    9  2 2  UPS Equipment Inspection        rr re ec etre ttes Fw a at va                    10  2 9    Storage of the UPS                             2 1  diet ttr taceo Fette tat d nae be t ecu 10  2 4    DISPOSAL Ems 10  3 0                                                                   11  3  sees Installation  d gor ojo p                                                                                11  3 2    Pre start PRECAUTIONS sass                                                                           12  3 93    Operating Precautioris                                        a de e ptt odia        12  40  UPS Connections                                         dnd 13  4 1      UPS Power and Control Connections                      sese nnns nnne nnne 13  4 1 1    Recommended Wire Size and Tightening Torque for UPS Input Output Terminals                   14  4 1 2    Power Connection Cable Routing                1 l nne nennen        15  4 1 3    Dual Input Configuration                              esent enne nennen nennen                   23  4 1 4    Control Circuit and External Battery Interface                                     24  4 1 5    Recommended Wire Size and Tightening Torque UPS Control and Battery Interface              24  4 2      Communication Interface                                         nnns                                 25  4 21  Remote                                   
48. eutral current calculated   1 73 of phase current   Note 1  Use a UL lug suitable for the wire size used     Note 2  Use tightening torque recommended by manufacturer of lug used     14 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        4 1 2 Power Connection Cable Routing    1  Use separate metal conduits for routing the input power  output power  battery  and  control circuits     2     separate ground cable should be run inside of the conduit with the input power  output  power  and control circuits       Always ground the unit to prevent electrical shock and to help reduce electrical noise   Follow wire size and tightening torque recommendations provided in this manual        CAUTION THE METAL OF A CONDUIT IS NOT AN ACCEPTABLE    GROUND    Single Input UPS with input transformer  Shown with bottom cable entry  configuration                                                                                                                                                                                                                                                                                                                                                                                             22  e                                                                                                                                                                                                                                
49. g factory defaults are reset   1  Reset the voltage reference setting to  0   2  Reset the buzzer volume to loud   3  Reset the serial station address to 31h   4  Reset the idle mode to 3 minutes     Press the MENU key to abandon the operation and return to the menu data screen     4200FA XT 80kVA Installation and Operation Manual 49    TOSHIBA    Leading Innovation  gt  gt  gt        6 16 Overload Operation    50    When the UPS is operating and an overload condition is detected the following screen is  displayed          UPS ON LINE   Note      indicates an actual  OUTPUT VOLTAGE     V numerical value    OUTPUT CURRENT           UPS OL  REDUCE LOAD               After a period of time  if the overload is still not reduced and the RUN STOP key switch is in  the RUN position  the UPS will transfer to bypass automatically  If the overload condition is  still present  the following screen will be displayed          BYPASS OPERATION    OUTPUT VOLTAGE 208                  114 116 114   DATE  DAY  TIME             If the RUN STOP key switch is in the STOP position  the UPS is in the bypass mode  and if  the overload condition is still present  the following screen will be displayed          BYPASS OPERATION    OUTPUT VOLTAGE 208                  114 116 114   DATE  DAY  TIME             After the load is reduced and if the RUN STOP key switch is in the RUN position  the UPS  will return to the Inverter mode of operation after a period of time  During the wait time the  following s
50. g is connected n clockwise rotation  CW   UPS  internal circuitry is designed to disable further UPS operation of the input phasing is  installed in counter clockwise rotation  CCW      3 2  Pre start Precautions    Before connecting the UPS to a power source  move the MCCB switch to the OFF position  and move the operation RUN STOP key switch  on the front panel  See Section 6 5 for  location   to the STOP position     3 3 Operating Precautions    1  The UPS should not be powered up until the entire User s Manual has been read     2  The input power source voltage must be within  10  to  15  of the rated input voltage  to initially start the UPS  The input frequency must be within the rated input frequency  range  Voltages and frequencies outside of the permissible range may activate the  internal protection device     3  The UPS should not be used with a load that has a rated input greater than the rated  UPS output     4       not use the UPS to provide power to motors that require high starting current or a  long starting time such as vacuum cleaners or machine tools  over sizing for locked  rotor current required      5  Do not insert metal objects or combustible materials in the ventilation slots of the UPS     6  Do not place  hang  or paste any objects on the top or on the exterior surfaces of the  UPS     7  The capacitors of the UPS maintain a residual charge for a while after turning off the  UPS  The required discharge time for each UPS is provided via a cabinet l
51. gt  ENTER FOR DETAILS             Refer to Section 6 9 2     Line 2 System Fault Messages for details     40 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 12 Shutdown Procedure    When turning off the UPS  the following shutdown procedure should be used     1  Move the RUN STOP key switch of the UPS to STOP  Operation of the inverter halts   Output power is now provided to the load via the bypass circuit  If a power failure occurs  in the commercial power source while in this state  the UPS will lose power and power to  the load will be interrupted  The battery charging circuit and chopper circuit will remain    active        Do not touch the UPS terminals even though the operation switch    D AN G       lhas been moved to the STOP position     power through the bypass circuit     The UPS may be supplying     The LCD display shows the following message when in the Bypass operating mode          BYPASS OPERATION  OUTPUT VOLTAGE 208V   gt CURRENT 100 100 100    DATE  DAY  TIME             Note  Actual numerical values may  differ from these examples     Move the MCCB power switch to Off  Power is removed from the UPS and to any  attached loads  All lamps are off and the LCD display shows the following message so long    as there is sufficient power to display it          OUTPUT SHUT DOWN    OUTPUT VOLTAGE  0V  CURRENT LOW LOW LOW              Emergency Power Off activation trips the MCCB and power is removed from the UPS
52. hat is free of vibration     2  Install the UPS in a well ventilated location with the required allowances for ventilation  and servicing as shown in figure 3 1     3  Install the UPS where the ambient  temperature is within the correct  operating range  see the UPS  Specifications in section 5   Verify that  the ventilation and air conditioning  System at the site is capable of  removing the heat generated by the  UPS unit  see Section  5 Specifications    Environment    Ambient temperature  range for operating the UPS is 32      104   F  0     40        77   F  25       is the  recommended operating temperature       i    7  a  iy    SUE  zi       IS  zi    Me  MZ         ME                                   0                  le  il            i i SSS jS   s da    for maximum battery life  CENE 2         ro  4  Do        install the UPS in a location that TR SS       2 M ME     Sti  is subject to high humidity  539 CENE  gt     5  Do not allow the UPS to be exposed to  direct sunlight     6  Donotinstall the UPS in areas that are  subject to contamination such as high  levels of airborne dust  metal particles   or flammable gasses     7  Avoid installation near sources of  electrical noise and always ensure that  the earth ground is intact to prevent     P   electrical shock and help prevent 2  electrical noise     8  Do not install the UPS in an area that REAR  may expose the UPS to water or that 0            may allow any foreign matter to get  inside    9  This UPS gene
53. he incoming  AC feed is turned off and locked out    The UPS and Battery Cabinet will have hazardous  voltages present even after the AC feed is turned off     If itis necessary to make measurements with the power   on  do not touch any electrical connection points  Remove  all jewelry from wrists and fingers  Make sure test equipment  is in good  safe operating condition     While servicing  stand on some type of insulation  and be  sure not to be grounded     Follow the safety instructions given in the equipment manual  carefully and observe all danger  warning and caution notices     40308       4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        A DANGER    RISK OF ELECTRIC SHOCK  Capacitors stay charged after power  has been shut off    Accidental contact with live parts can    cause personal injury and death    Turn off and lock out all power sources   Wait at least five  5  minutes for power  to dissipate then check voltage before  servicing  39561        For Battery Units Only         ANCAUTION   Risk of electric shock    DO NOT REMOVE COVER  NO USER SERVICEABLE PARTS  INSIDE  REFER SERVICING TO QUALIFIED SERVICE PERSONNEL   HAZARDOUS LIVE PARTS INSIDE THIS UPS ARE ENERGIZED  FROM THE BATTERY SUPPLY EVEN WHEN THE INPUT AC POWER  IS DISCONNECTED     CAPACITORS STORE HAZARDOUS ENERGY  DONOT REMOVE  COVER UNTIL 5 MINUTES AFTER DISCONNECTING ALL SOURCES  OF SUPPLY     TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK  INSTALL  
54. i ient d   CONSERVER CES INSTRUCTIONS  216                        concernant la s  curt         ATTENTION      un risque de choc   lectrique  de br  lure         ATTENTION    batteries est r  glement  e  Consultar les codes    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        1 0 Product Description    1 1    1 2    1 3    1 4    Theory of Operation    An Uninterruptible Power System  UPS  is a system that is installed between the commercial  power and the load equipment  The UPS provides steady AC output power during commercial  power fluctuations and interruptions     During normal operation the UPS receives commercial AC power and removes any high  voltage spikes and transients caused by switching or faults on the main utility  The result of this  process is maximum power conditioning and regulation of the power applied to the load     If the AC power supplied to the UPS drops below a specified voltage level  the batteries of  the UPS are automatically switched on and will supply power to the load  This insures that the  loads connected to the UPS continue to receive power with no interruption  This power is  provided for a period long enough to ensure that the load can be shut down in an orderly fashion   This prevents loss of data and possible damage to the hardware or software     When AC input power becomes available again  normal system operation resumes and the  UPS battery charge cycle resumes     Application and u
55. ic  Power Flow Bypass        Isolating Output             z                   id    Charger   Chopper    External  Batteries    Power flow in battery backup mode for the 4200FA 80 kVA UPS    6 1 4 External Maintenance Bypass  Customer Supplied     An external maintenance bypass may be installed in parallel with the UPS to allow servicing  of the UPS while maintaining power to the load  Contact an authorized service  representative for further information     C AUTI ON Ensure the UPS is set to BYPASS mode before switching the  external bypass from UPS to MAINTENANCE BYPASS     High transient currents may result if the external bypass is engaged  while the UPS is in normal mode     4200FA XT 80kVA Installation and Operation Manual 31    TOSHIBA    Leading Innovation  gt  gt  gt        6 2 Battery Backup Time and Discharge Process  The UPS system  when used in conjunction with a TOSHIBA designed Battery System  is  designed to provide several minutes of back up time for the 4200 FA UPS  Refer to the  Battery System Manual for back up times   These times are valid for full load operation  At  half load operation the batteries can provide approximately 2 times the specified value  The    exact times will depend on the UPS model used  condition of the batteries  amount and type  of load  temperature  and other variables     other than TOSHIBA designed battery systems to determine    compliance  Using other systems may void the warranty and or the  safety certifications     t CAUTIO
56. jury that may result from the misuse of this equipment      N CAUTION   _    CAUTION Do not open or mutilate the batteries  Released electrolyte is toxic and  harmful to the eyes and skin     Do not dispose of the batteries in a fire  The batteries may  explode        4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        CAUTION This unit contains sealed lead acid batteries  Lack of preventative  maintenance could result in batteries exploding and emitting gasses  and or flame  An authorized technician must perform annual preventative maintenance     CAUTION Failure to replace a battery before it becomes exhausted may cause  the case to crack  possibly releasing electrolyte from the battery    resulting in secondary faults such as odor  smoke  and fire     CAUTION Only personnel knowledgeable of batteries and the required  precautions should perform installation and servicing of batteries  Keep    unauthorized personnel away from the batteries     CAUTION Proper maintenance to the battery system of this unit must be done by  a qualified service technician  This is essential to the safety and    reliability of your UPS system  Refer to service manual     D A N G       A battery can present a risk of electrical shock and high short  circuit current  The following precautions should be observed  when working with batteries     TO BE PERFORMED BY QUALIFIED PERSONNEL ONLY     1  Verify that the UPS is off and is disconnected from the
57. lp in resolving any  Uninterruptible Power System problem that you may experience or to provide application information     The center is open from 8 a m  to 5 p m   CST   Monday through Friday  The Support Center   s toll free  number in USA is  877  867 8773     You may contact TOSHIBA by writing to     TOSHIBA INTERNATIONAL CORPORATION   INDUSTRIAL DIVISION   13131 West Little York Rd    Houston  TX 77041 9990   Attn  UPS Product Manager    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Table of Contents    GENERAL SAFETY INSTRUCTIONS                                                U                      T T    1  EQUIPMENT WARNING LABELS             I                2  IMPORTANT SAFETY INSTRUCTIONS                                                                          5  INSTRUCTIONS IMPORTANTES CONCERNANT                                                          7  10  Product Description                                                                                                         8  1 1  Theory of Operation               entere RR                                          8  1 2 x                   US                             8  1 3  5  POWO BACKUP                                                                  8  1 4  Power CONGITONING                            8  2 0 Unpacking Inspection Storage Disposal                                                             9  P       Unpacking the UPS  Equiptn
58. n the main unit     The UPS is in an overload condition     6 15 4 Run Switch Select    Press the MENU key to access the menu data screens  Press the Down arrow key to scroll to  the Run Switch Select screen        RUN SWITCH SELECT    lt LOCAL gt  REMOTE   gt  F1  DATA SET MODE   gt A V  PRV NEXT SCREEN             Press the F1 key to display the following active adjustment screen        RUN SWITCH SELECT    lt LOCAL gt  REMOTE   gt A V  CHANGE DATA   gt ENTER ACCEPT CHANGE             Press the Up Down arrow keys to toggle from RUN to SWITCH  Press the ENTER key to  save the selection or press the MENU key to exit to the main menu and discard the change   Remote S U option required   This function is available in the Bypass mode only     4200FA XT 80kVA Installation and Operation Manual 47    TOSHIBA    Leading Innovation  gt  gt  gt        6 15 5 Serial Com Station Address  Press the MENU key to access the menu data screens  Press the Down arrow key to access  the Run Switch select screen        SER COM STATION ADDR  STATION ADDRESS  31H   gt  F1  DATA SET MODE    gt  A V  PRV NEXT SCREEN             Press the F1 key to display the following active adjustment screen        SER COM STATION ADDR  STATION ADDRESS  31H   gt A V  CHANGE DATA    gt ENTER  ACCEPT CHANGE             6 15 6 Output Voltage Adjustment  While operating in the AC Input mode  press the MENU key for 4 seconds or more to display  the output voltage adjustment screen        OUTPUT VOLT  ADJUST  OUTPUT VOLT
59. ncorrect fuse replacement size    ON   OFF    may result in fire or inadequate  equipment protection     Replace only with same type    and rating of fuse     PN 40830          Risk of electrical shock    Battery circuit is not isolated from AC input   hazardous voltage may exist between  battery terminals and ground     Test circuit before touching  PN 40760       4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Hot surface     Contact may result in burn injury     Allow equipment to cool before  servicing  PN 40832    Heat sink not grounded     Risk of electrical shock     Disconnect UPS and electrically    test heat sink before touching  PN 40831       DANGER    HAZARDOUS VOLTAGES   Hazardous voltages are used in the operation   of this equipment and could cause severe personal  injury or loss of life    The following precautions should be observed to  reduce the risk ofinjury or death     Only qualified technicians familiar with this equipment and the  information supplied with it should be permitted to install and  operate this equipment     Installation of electrical equipment must be done in  accordance with National Electrical Code and any other state  or local codes  Proper grounding and conductor sizing must  be installed for safe operation     During operation  keep all covers in place and cabinet  doors shut     When performing visual inspections and maintenance  if  possible  be sure the UPS is turned off and t
60. nly be performed by factory trained  service personnel and not by the end user                                                                                   Bypass jumpers are factory installed on bypass bus bars     Single Input Configuration                                                                               Move wires from bypass bus bars to stand offs to configure for dual input     Dual Input Configuration    4200FA XT 80kVA Installation and Operation Manual       23    TOSHIBA    Leading Innovation  gt  gt  gt        4 1 4    Conirol Circuit and External Battery Interface Connections  The following illustrates the wiring connections of the Control Circuits and Battery Interface  Circuits     NOTE  Control circuit wiring should be routed in it   s own conduit  Do not route control circuit  wiring through conduit containing UPS power cables                                                                                                                                                                                                                                                                                                                                                                                                                                                           TB2 TB3  O          oF    O  1315717        OIOOOOOOOO OO  2146 8 1012141618 4  6  CUSTOMER CONNECTIONS  TB2 Connections  1     Low Battery 2     Battery Discharge  3     Fault 4     Not 
61. now activated  The AC IN lamp will be on  The LCD display  see  Section 6 5  Front Panel Layout   will display the following message          UPS START UP             gt  PLEASE WAIT       3  With the key switch in the STOP position  the AC IN and the BYP lamp will be on and  the LCD display will show the following message          BYPASS OPERATION     OUTPUT VOLTAGE 208V    gt CURRENT 100 100 100    DATE  DAY  TIME              4  Turn the Key Switch to RUN and the UPS performs the Automatic Battery Test  The  Automatic Battery Test is performed only when the software is enabled for this  function  The default setting is Disabled      Allow 24 hours for the batteries to fully charge    Should the Automatic Battery Test fail and the LOW BATTERY message is displayed use the  following procedure     1  Turn the key switch to STOP     2  Allow 24 hours for the batteries to charge and  upon completion  move the MCCB  switch  see Section 4 for location  to off     3  Repeat Initial Battery Charge procedure  a failure indicates battery replacement  required      4200FA XT 80kVA Installation and Operation Manual 39    TOSHIBA    Leading Innovation  gt  gt  gt        6 11 Start up Procedure  The UPS batteries must be charged before the UPS is used for the first time or if the unit has  not been used  ac power source removed  for more than 10 days  Refer to Section 6 10      If the batteries are charged perform the start up procedure as follows     1  Verify that all power switches ar
62. nstallation and Operation Manual       TOSHIBA    Leading Innovation  gt  gt  gt        5 2 Specifications     4200FA 80kVA with Internal Transformer       Model Number    T42 3F800FAXXN       Rated Output Capacity    80 kVA       External Dimensions   W x D x H     41 in  x 31 in  x 74 in    1041 mm x 787 mm x 1880 mm        Weight    2200 Ibs  1000 kg        Rated Voltage         B 208  N 380 Q 400 415  D 480        Voltage Variation        10  to  30          Rated Frequency    50 60 Hz       Number Phases   Wires    3 Phase   3 Wire       Power Factor      Greater than 0 99 when in inverter mode                        Mairi input Required Input Power 76 kW when in inverter mode  Walk in Function From 20  to 100  over 5 seconds  Inrush Current Less than 8 times rated current under synchronous operation  Current Limit 115  maximum  Harmonic Currents   Less than 4  THD    Rated Voltage 208   120 Vac  Optional Voltage Variation  10  to    1596    Bypass Input          Rated Frequency    50 60 Hz       Number Phases   Wires    3 Phase   4 Wire   GND       DC Nominal  Voltage Range     288 VDC  230 to 332 VDC        Float Charge  Regulation     324 VDC  42   with 2 25 V cell                Battery Ripple Voltage 296 R M S   Rated Back up Time 2 Refer to Battery System Manual 7  Rated Charge Current 20 0 Amps  Rated Voltage 208   120 VAC  Rated Current 223 Amps  Rated Power Factor 0 8 lagging  Number Phases   Wires 3 phase   4 Wire   GND  Voltage Regulation   2   0 100926 balanc
63. oftware  The  display board to main board interface will begin a new communication sequence  If a  communication response is not received by the display board from the main board within 15  seconds  a fatal time out occurs and the following system message displays          DISPLAY ERROR   Note  If the error message persists  MAIN COMM  ERROR contact the TOSHIBA Service  Center           PRESS  amp  HOLD RESET KEY       Upon a successful Reset the Startup Screen appears followed by the Main Monitor     4200FA XT 80kVA Installation and Operation Manual 45    TOSHIBA    Leading Innovation  gt  gt  gt        6 15 Menu Data Screens    6 15 1 Settings for Calendar and Clock  Press the MENU key to access the system configuration screens  Press the Down arrow key  until the time and date screen is shown           CALENDER   CLOCK  DATE  DAY  TIME   gt  F1  DATA SET MODE   gt A V PRV NEXT SCREEN          Press the F1 key to display the following active adjustment screen           CALENDER   CLOCK  DATE  DAY  TIME   gt  A V   UP DOWN   gt ENTER NEXT DATA          Press the Up Down arrow keys to adjust the character s  above the flashing cursor     Press the ENTER key to advance the cursor     6 15 2 Adjusting Buzzer Volume    Press the MENU key to access the menu data screens and press the Down arrow key to  access the Buzzer Volume adjustment screen           BUZZER VOLUME ADJUST   lt LOUD gt  MEDIUM SOFT   gt  F1  DATA SET MODE   gt A V PRV NEXT SCREEN          Press the F1 key to di
64. osed in a  triangle  The Explosion warning symbol is used to indicate locations and conditions where  molten exploding parts that may cause serious injury or death if the proper precautions are  not observed        4200FA XT 80kVA Install2 nd Operation Manual    1    TOSHIBA    Leading Innovation  gt  gt  gt        EQUIPMENT WARNING LABELS    DO NOT attempt to install  operate  maintain or dispose of this equipment until you have read and  understood all of the product warnings and user directions that are contained in this instruction manual     Shown below are examples of warning labels that may be found attached to the equipment  DO NOT  remove or cover any of the labels  If the labels are damaged or if additional labels are required  contact  your TOSHIBA representative for additional labels     The following are examples of the warning labels that may be found on the equipment  The labels are  there to provide useful information or to indicate an imminently hazardous situation that may result in  serious injury  severe property and equipment damage  or death if the instructions are not followed     A    DANGER    DC VOLTAGE   DC Voltage supplied by batteries is still  resent after equipment has been  urned off and taken off line    Accidental contact with live parts can   cause personal injury and death    Disconnect all DC Sources before   performing any service or testing   in this compartment 43784    DO NOT TURN OFF    CRITICAL FUSE SIZING WHILE UNIT IS RUNNING     I
65. pear in any of the following ways     1  Danger warning     The danger symbol is an exclamation mark enclosed in a triangle  which  precedes the word    DANGER     The Danger warning symbol is used to indicate situations   locations  and conditions that exist and will cause serious injury or death         DANGER    2  Caution warning     The caution symbol is an exclamation mark enclosed in a triangle  which  precedes the word  CAUTION   The Caution warning symbol is used to indicate situations  and conditions that can cause operator injury and or equipment damage      N CAUTION    3  Attention warning     The attention warning symbol is an exclamation mark enclosed in a  triangle which precedes the word  ATTENTION   The Attention warning symbol is used to  indicate situations and conditions that can cause operator injury and or equipment damage         ATTENTION    Other warning symbols may appear along with the Danger and Caution symbol and are used to specify  special hazards  These warnings describe particular areas where special care and or procedures are  required in order to prevent serious injury and possible death     1  Electrical warning     The electrical warning symbol is a lighting bolt enclosed in a triangle   The Electrical warning symbol is used to indicate high voltage locations and conditions that  may cause serious injury or death if the proper precautions are not observed     2  Explosion warning     The explosion warning symbol is an explosion image encl
66. ped by pressing the BUZZ STOP key  see Section 6 5 Front Panel Layout                  Condition Audible pattern  UPS in Battery Backup Mode 78 18   Battery Voltage 100 90   EC        UPS Low Battery 15   Battery Voltage  lt  90     4         Overload 5S  Fault 55                   4200FA XT 80kVA Installation and Operation Manual 35    TOSHIBA    Leading Innovation  gt  gt  gt        6 8 User Notification LEDs  The following is a list of the user notification LEDs and their function   AC IN On when the UPS has normal AC input power that is within tolerance  If there is an input    power failure this LED is off  If there is no power failure and the input voltage is in an over   voltage condition  the AC IN LED will flicker on and off rapidly  0 4 sec on and 0 4 sec off    If there is no power failure and the input voltage is in an under voltage condition the AC IN  LED will be off     On when the UPS inverter is operating     BYP   nce On when the UPS is in the static bypass mode    BATT On when the UPS is in the battery discharge mode  If the battery is low during a battery  discharge  the BATT lamp will flicker on and off slowly  1 2 second on and 1 2 second off    The BATT LED will go off if the battery voltage reaches the shutdown level during the  battery discharge mode    FAULT        On when the UPS is experiencing    fault    6 8 1 LED System Status    The following table shows the UPS system status that can be determined by decoding the on  and off condition of the L
67. performance may be  different due to variations in manufacture  transformer type  and transformer performance at  various loads      4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 0 Operating the UPS  6 1 Operating the UPS    6 1 1 AC Input Mode  normal operation   The following illustration shows circuit power flow when the UPS is operating normally in the  AC input mode  The converter of the UPS  including a boost chopper circuit  converts the AC  input power to DC power  The boost chopper circuit maintains a constant voltage and  provides current limiting for battery charging  It also supplies a DC voltage of the proper level  to the inverter section  The inverter section generates a high quality sine wave output voltage   The UPS batteries always maintain a charge during normal UPS operation             Power Flow    Static  Bypass                       Isolating Output  Power    id    Charger   Chopper    External  Batteries    Power flow in AC input mode for the 4200FA 80 kVA UPS    6 1 2 Bypass Mode  If the UPS detects an overload or develops an internal fault  power flow is automatically  switched from the main circuit of the UPS to the Bypass circuit  Power flow through the  Bypass is shown in the following illustration  This changeover occurs automatically in less  than 4 milliseconds  The switching period is not long enough to cause interruptions to occur  in most loads  If the power flow is transferred to th
68. r Off                              nnns 35  6 7    Audible  Alarm  Functions    een iiec        ee iiec        ede edd 35  6 8    User Notification           LI                                         esee ide etie te iet               cedes 36  6 8 1    EED System Status L UI ieri st tad ete ED PAR PE der eaa d Entre        36  6 92 ECD FUNCTIONS E 37  6 9 1    Line 1 System Messages                          U    U    n    37  6 9 2    Line 2 System Fault Messages                      U                                            37    4200FA XT 80kVA Installation and Operation Manual i    TOSHIBA    Leading Innovation  gt  gt  gt        6 9 3    Line 3 System                                                                               37  6 9 4    Line 4 System Messages                          U    U    entente si nnns innen ens 38  6 10    Initial  Battery Clhiarge                                       vice egere ylang a vay y a e En ege 39  6 11  Startup ProcedUure       ecce et die Viet    40  5 12    Shu  tdowrt Procedure    ite uo Galan vinee          dee len oul eval 41  6 13  Keypad OVenview ER 42  6 14    Key F  nctions       uoces Qe ele ens tinea ns de c teer nope Xn degrees 43  mM EE 43  mr Sistas alia idia a ia len al eae 43  6 14    OUT MM EE 43  6 14  4           Key cadere ne e egeo e pe vere dg ee                  u a Ma uapa Rege dd 44  6 14 5  MENU  F1  ENTER  UP DOWN Keys eranan tnei Eeunenn aenneren eanan aaaea ensis nennen 44  6 14 6           TEST    
69. rates and radiates radio   frequency energy during operation   There is no guarantee that the UPS will       d  MEMS  EG    v                   E            E  JE          ME  Jf  il                                                                7                                F                                Me                                       N     ma    fit          E  N  NN  NV  N  NK      N    not influence some sensitive devices E   TOP E s  that are operating close by  If such      22     550       g S  o       interference is experienced  the UPS  should be installed farther away from  the affected equipment and or powered  from a different source than the affected  equipment     10  The user should provide output over       current protection for hardwired UPS ee A  versions  See Safety Instructions on  00 min   page 9 for the correct device rating  Figure 3 1    4200FA XT 80kVA Installation and Operation Manual 11    TOSHIBA    Leading Innovation  gt  gt  gt        11  After ensuring that all power sources are turned off and isolated in accordance with  established lockout tagout procedures  connect power source wiring of the correct  voltage to the input terminals of the UPS  Connect the output terminals of the UPS to  an applicable load type application  refer to NEC Article 300     Wiring Methods and  Article 310     Conductors For General Wiring   Size the branch circuit conductors in  accordance with NEC table 310 16     NOTE  Ensure that the input phasin
70. rranty contained in the  contract between the parties is the sole warranty of TOSHIBA  and any  statements contained herein do not create new warranties or modify the  existing warranty     Any Electrical or mechanical modifications to this equipment  without prior written consent of the TOSHIBA will void all  warranties and may void UL CUL listing  Unauthorized  modifications may also result in equipment damage  personal  injury  or loss of life        UNINTERRUPTIBLE POWER SYSTEM    If additional information or technical assistance is required call TOSHIBA  Customer Support Center toll free at 1  877 867 8773  or write to  Toshiba  International Corporation  13131 West Little York Road  Houston  TX 77041   9990 Attn  UPS Product Manager     Please complete the following information for your records  Unless otherwise  specified on the warranty card  the warranty period for the UPS or UPS part  is 36 months from the shipment date  see bill of lading      Unless otherwise specified on the warranty card  the warranty period for a  UPS battery is 24 months from the shipment date  see bill of lading      Keep this manual with the UPS equipment   Job Number    Model Number    Serial Number    Application    Shipping Date    Date of Installation     Inspected By     4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        Purpose and Scope of Manual    This manual provides information on how to safely install  operate  and maintain your 
71. s and no abnormal operating conditions are present  the  UPS switches to standard Battery Backup mode  The following system message is displayed          BATTERY BACKUP    OUTPUT VOLTAGE  208V  CURRENT 2100 100 10096   DATE  DAY  TIME                         6 14 2 IN  Pressing the IN key during normal AC Input mode of operation displays input voltage  information  The following system message is displayed     UPS ON LINE    INPUT Vab  100   VOLTAGE Vbc  100           100   The bypass input voltage  frequency   Sync Mode  and converter current may be monitored  by pressing the DOWN UP keys   6 14 3 OUT    Pressing the OUT key during normal AC Input mode of operation displays output voltage   current  and frequency information  The following system message is displayed          UPS ON LINE   Note  If output current drops below     js zo 1596 display reads  CURR LOW   Ic  100              The Output Line Voltages  phase neutral  and phase to phase    Frequencies   Sync Mode  Inverter Output Power  and Power Factor may be monitored by  pressing the DOWN UP keys     4200FA XT 80kVA Installation and Operation Manual 43    TOSHIBA    Leading Innovation  gt  gt  gt        6 14 4 BATT Key  Pressing the BATT key during normal AC Input mode of operation displays battery capacity  information  The following system message is displayed        Note  Discharge current in Line 3 is 0     UPS ON LINE   unless unit is in the battery mode   BATTERY VOLTAGE  324V    CHARGE CURR  0  Note  Line 4
72. se    The TOSHIBA 4200FA Uninterruptible Power Systems  UPS  provide continuous computer grade  AC power in a compact and efficient high performance unit  The UPS assures safe  reliable  operation of critical office equipment  ranging from personal computers to mini computers to local  area networks  LAN   All units feature an audible alarm that sounds if the battery voltage drops  below standard during use  This is an additional aid to help in retaining the valuable office data  banks  and all units allow for computer interfacing     Power Backup    During an electrical power failure the batteries of the UPS unit supply DC power to the inverter  that supports the load equipment automatically  without interruption  For example  when used to  support a computer  a UPS backup assures additional time to complete your activity and store  data after a power failure occurs     Power Conditioning    While commercial power is present  the UPS supplies conditioned power to the load while  maintaining the batteries in a charged condition  The UPS protects the connected load against  the normal everyday problems associated with heavy use of raw commercial power  including  power sags  surges  signal interference  and spikes  This protection keeps power line problems  from reaching your load where it can cause equipment to operate erratically  or damage software  or hardware     4200FA XT 80kVA Installation and Operation Manual    TOP HEAVY EQUIPMENT       DANGER               az        
73. splay the following active adjustment screen           BUZZER VOLUME ADJUST   lt LOUD gt  MEDIUM SOFT   gt A V  CHANGE DATA   gt ENTER ACCEPT CHANGE          Press the Up Down arrow keys to move the curser to any of the three buzzer volume levels   Press the ENTER key to accept the change or press the MENU key to discard the changes  and return to the menu data screen     46    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 15 3 Settings for Display Duration    The LCD display is designed to switch off after a user set period of inactivity  To set the  duration of inactivity allowed  press the MENU key to access the menu data screens  Press  the Down arrow key to scroll to the Display Duration screen  The following system message  is displayed        DISPLAY DURATION SET    3 MIN   30 MIN   gt F1  DATA SET MODE   gt A V PRV NEXT SCREEN             Press the F1 key to adjust the LCD Idle mode setting        DISPLAY DURATION SET   lt 3 MIN gt  30 MIN    gt A V  CHANGE DATA   gt ENTER ACCEPT CHANGE             Press the Up Down arrow keys to toggle from 3 MIN to 30 MIN  Press the ENTER key to  save the selection or press the MENU key to exit to the main menu and discard the change     Under any of the following conditions the LCD will remain on continuously without regard to  the    Duration setting   1  The UPS has received an emergency off command   2  The UPS is in battery discharge mode   3  A fault has been detected i
74. the UPS and then reset the  breaker until the UPS has been fully discharged  The UPS could be  damaged if the unit is not fully powered down before the breaker is    The following illustration shows the wiring connections to the input and output termination  points and the Control Circuit Terminal Blocks for the 4200     80 kVA UPS     REMOTE EYE  BRACKET _   UNDER      COVER                                                                                                                                                                                                        2   sss HO  DISPLAY__   E  PANEL          E S E SES UE LED         ME ME ME MM M MEE MEE MM ME MI     Z                                                          1                                           INTAKE                                                                                                                   MCCB z I   AP  INPUT A h i  CIRCUIT       I SN       REAKER   3 i ALL         O   0  2               ope    alc ell lile feel lei    ig gp ur       BATTERY                       hg  TERMINALS   NEG                w        a P          V          mE    i m        TERMINALS     3                                                                                                                                                                                                                                                                                                                              
75. the optional battery over temp  sensor has annunciated  or if the external battery  disconnect is open   Verify TB3 5 6          UPS OK      Displayed when none of the above abnormal  conditions are present   normal          DISCHARGE CURR           Displayed when none of the above abnormal  conditions are present and the UPS is in battery  discharge mode   normal backup          TRANSFER INHIBITED      Displayed when key switch position is changed and  frequency is not synchronized   abnormal          EMERGENCY OFF      Displayed when an emergency  EPO  signal is  received          UPS OUTPUT DISABLED      Displayed when UPS has normally shutdown             FAULT S  DETECTED         Displayed when a fault or faults have occurred    abnormal        Note     1  Line 4 will be blank when the BATT key is pressed during battery backup mode    with normal battery voltage     2  The   symbol signifies numerical values or other information supplied by the    UPS     4200FA XT 80kVA Installation and Operation Manual       TOSHIBA    Leading Innovation  gt  gt  gt        6 10 Initial Battery Charge  The battery of the UPS must be charged before it is used for the first time or if the unit has  not been used  AC power source removed  for more than 10 days  Use the following  procedure to recharge the battery of the UPS     1  Switch on power at the UPS input distribution panel   2  Move the MCCB power switch to On  see Section 4 for location   Note  The battery    charging circuit is 
76. torque all battery connecting hardware  if applicable    2  Aluminum electrolytic capacitors  Replace once every 5 years   3  Fuses  Replace once every 7 years  see output fuse rating table below      4  Cooling fan  Replace once every 3 years     54 4200FA XT 80kVA Installation and Operation Manual    9 0 External Dimensions   Shipping Weights    Leading Innovation  gt  gt  gt   9 1    TOSHIBA       External Dimensions       31                                                  74                44                                                                                                                                                                                                            E       N                                                                                                                                                                                                                                                    55    4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        9 2    9 3    9 5    Shipping Dimensions       Shipping Dimensions     Shipping Dimensions                          All models Standard with crate   Inches  cm  Inches  cm    Width 56 2  143  56 9  145    Depth 42 8  109  45 0  114    Height 79 0  201  81 8  208    Height with packing material 82 0  208  82 0  208                                   Shipping Weights  Model Shipping Weight  Standard   Shipping Weight  with crate  Po
77. tteries charge to the fully charged state     In the third period  a trickle current continues to flow into the batteries to maintain the fully  charged status at the normal DC Voltage level     A full recharge requires approximately 24 hours  90  recharge in 10 X discharge time  after  a complete discharge     The following table shows the rated maximum and minimum battery voltages  and the charge  current for each of the sizes for 75 F  24   C  operation     Rated Battery Voltages                      V float 324 VDC  V min 216 VDC    charge 20 0 Amps       4200FA XT 80kVA Installation and Operation Manual 33    TOSHIBA    Leading Innovation  gt  gt  gt        6 5 Front Panel Layout  All Units                                                                                                                             4 line liquid crystal Emergency  display screen Power Off switch RUN STOP   see Section 6 9   see Section 6 6  key switch  Line 1    UPS  Line 2                                    STOP RUN  ea          BUZZ   MENU             C4 J  ACIN INV BYP            FAULT   lt                            user A   4 ON LINE 4200FA  UNINTERUPTIBLE POWER SYSTEM             Green light emitting Red light emitting 12 key Data entry keypad  diodes  LED  diode  LED   see Section 6 13    see Section 6 8   see Section 6 8     34 4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        6 6         Emergency Power Off  Function  The 4200FA U
78. unds  Kilograms  Pounds  Kilograms   T42B3F800F AXXN 2300  1043  2400  1089   T42D3F800F AXXN 2300  1043  2400  1089   T42F3F800FAXXN 2100  953  2200  998   T42N3F800F AXXN 2300  1043  2400  1089   T42F3D800FAXXN 2300  1043  2400  1089        Cabinet Color  All UPS cabinets are colored  White Gray  Trimite CO9079PA80123 Beige  Eggshell Texture  or Sherwin    Williams HHT2 70055079 Beige Texture      56    4200FA XT 80kVA Installation and Operation Manual          TOSHIBA    Leading Innovation  gt  gt  gt        APPENDIX A   Installation Planning Guide    Installation Planning Guide for 80kKVA UPS    Standard Systems  208 120V Wye  208 380 480 600V Delta Input  208 120V Output    Important Notes     1             8   9     Maximum Current required at Primary      Input based on full load output and maximum battery  charging current       Output load conductors are to be installed in separate conduit from input conductors     Control wires and power wires are to be installed in separate conduits     Recommended AC input and output overcurrent protection based on continuous full load current per    NEC       Wiring shall comply with all applicable national and local electrical codes     Grounding conductors to be sized per NEC Article 250 122  Neutral conductors to be sized per NEC    Article 310 15 and Table 310 16  75 deg  C Conductor     Primary AC Input  36  3 wire   ground    AC Output  36  4 wire   ground    DC Input  2 wire  Positive Negative    ground       Power cable m
79. wood or  metal pallet   3  The optimum storage temperature is 70   F  21   C   Higher ambient temperatures cause  UPS batteries to require recharging more frequently     After Storing     1  If stored in an ambient temperature less than 68   F  20   C   recharge the batteries every  9 months     2  If stored in an ambient temperature of 68     86   F  20     30        recharge the batteries  every 6 months     3  If stored in an ambient temperature of 86     104   F  30     40   C   recharge the batteries  every 3 months     Disposal  Please contact your state environmental agency for details on proper disposal of electrical  components and packaging in your particular area     ATT                It is illegal to dump lead acid batteries      landfills or dispose  of improperly  Please help our Earth by contacting the    environmental protection agencies in your area  the battery  manufacturer  or call TOSHIBA toll free at  800  231 1412 for more  information about recycling batteries     4200FA XT 80kVA Installation and Operation Manual    TOSHIBA    Leading Innovation  gt  gt  gt        3 0 Precautions    Because of the external dimensions of the 4200FA UPS and the way the outer panels are to  be removed  only a minimum amount of space around the unit is required for ventilation and  maintenance access  Figure 3 1 shows the minimum clearances required for proper UPS  installation     3 1 Installation Precautions  1  Install the UPS in a stable  level  and upright position t
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
H680 3G WiFi Router User Manual - E-Lins  Manual A2K2 - Seguridad Total  Miracle-Gro 903000-4100 Installation Guide  Índice LaCie Mobile Hard Drive Manual del usuario  BESPA Manual  Samsung כיריים חשמליות 4 מבערים, עם אזור גמיש וסליידר, 7.1kW CTR264KC01 מדריך למשתמש  Installation Manual Victoria Thermostatic Integrated Shower Valve  PDF User Manual - Smoke Machines  Racal 3351 User Manual  Bituthene 3000    Copyright © All rights reserved. 
   Failed to retrieve file