M714_User - ProMinent Fluid Controls, Inc.
Contents
1. Turn OFF setpoint 3275 00 uS 4 B3 Blowdown DiagnosticS Control Type Rising Setpoint 4 B3 Blowdown DiagnosticS 7 Day Event Cycle 0 events Day 4 4 B3 Blowdown Diagnostics minutes ON today 234 6 minutes 4 B3 Blowdown DiagnosticS Time Owed 0 0 minutes Inhibitor Pump DiagnosticS Captured Sample 0FF Resample 26 4 m 26 2 5 System Diagnostics 1 of 2 Power ON display OR key UP DOWN to System amp ENTER Key ENTER at Diagnostics Firmware version is followed by the two modules that form the base controller M7 is a 7 analog 7 digital input module M14 is a 14 analog 12 digital input module PR10 is a 10 relay output PR5 a 5 relay output PR10 controllers include an AC Current Transformer AC Current is the total controller current including All pumps valve amp solenoid current OK is an intact Relay 1 to 5 load fuse OPEN is a failed fuse Pumps amp Solenoids controlled by relays 1 5 are OFF OK is an intact Relay 6 to 10 load fuse OPEN is a failed fuse Pumps amp Solenoids controlled by relays 6 10 are OFF M714 _User_Master doc Updated Aug 25 2015 System 2003 10 03 S N M0389001 Alarms 16 38 11 4 D G 2 Sys lt H System Diagnostics lt Enable I 0 Configure System DiagnosticS Firmware Version A814 M7 PR10 4 System DiagnosticS AC Current 4 06
2. Current value of controlling sensor displayed Controller checks Turn ON Setpoint at the end of every Measure period M714 _User_Master doc Updated Aug 25 2015 Boiler 3 Cond AF 3628 uS B3 Blowdown 4 ON 1 2 min lt H B3 Blowdown 4 Diagnostics Pi Configure Alarms Y B3 Blowdown 4 DiagnosticS Prime Output YES t B3 Blowdown 4 DiagnosticS Current State Special Control ON B3 Blowdown 4 DiagnosticS Control by F 3420 23 uS t 4 B3 Blowdown 4 DiagnosticS Turn ON setpoint 3300 uS 4 Continued on Page 2 25 2 4 Control Diagnostics 4 of 4 CAPTURED SAMPLE EXAMPLE page 2 Controller checks Turn OFF Setpoint at the end of every Measure period Rising Setpoint blows down above Turn ON and samples only below Turn OFF It would be unusual to have timed feed events on a boiler blowdown valve In this example there are 0 events set and its day 4 Wednesday today Today s ON time for the blowdown valve from midnight Captured Sample Time Owed would usually be zero If Prime Output is active Time Owed will count down from 5 minutes Displays the Captured Sample ON OFF state and which timer is counting down SAMPLE MEASURE BLOWDOWN RESAMPLE are the four captured sample states Varying Cycles and Fail to Sample status Displays follow the state display M714 _User_Master doc Updated Aug 25 2015 B3 Blowdown DiagnosticS
3. then amp Notes DOWN to inputs or outputs Key ENTER amp DOWN to select DOWN to Description DOWN to Digits after decimal LCD amp Browser display DOWN to Displayed Units WARNING Do not modify network parameters without site IT permission DOWN to Metric Units DOWN to Digital Input Type ENTER DOWN to Contact Set DOWN to Description DOWN to New Password for current userid DOWN to Keypad Password Requires upgrade code Linked to controller serial 57 M714_User_ Master doc Updated Aug 25 2015 4 5 Revision Log 1 of 1 Issued Contents 2004 01 01 Original issued 2004 03 16 Section 1 7 Removes userid selection for keypad log in Applies only to controllers with Keypad Passwords ON 2004 04 05 Cover page revised Repagination Safety grounding information added to page 3 2004 04 21 Section 4 3 Specification 1 Specification revised to match controller nameplate 2 M5 amp M10 enclosure sizing and weights added 3 Installation cabling insulation rating specified Section 3 1 Read This First 1 Emphasis added for controller specific HELP section 2007 10 02 Section 4 3 Specification Environmental Added CSA statements Page 51 2015 8 24 Safety Added caution statement on pg 4 58
4. 12 04 30 45 Executes Exits 4 4 then 1 Edit an Event Day Start ON min 12 06 15 119 Executes Exits j L gt then lt 12 Changing Biocide Timing 2 of 2 ADD AN EVENT OR EVENTS Key ENTER at selected chemical pump Key DOWN to Timed Events amp ENTER Key RIGHT to select the field you wish to modify Key UP DOWN to modify the field ENTER to update Key UP DOWN to select ONCE WEEKLY ALTERNATE WEEKS 7 Day Cycles select one of ONCE DAILY ALTERNATE DAYS 1 Day Cycles select one of ONCE HOURLY ALTERNATE HOURS In this example we added weekly events Increasing the total events from 8 to 12 Keying UP DOWN Add an Event Displays the Delete all Events option Key ENTER to remove all events M714 _User_Master doc Updated Aug 25 2015 Biodispersant 5 Timed Events Add an Event YES Events 8 I n Add an Event Day Start ON min 6 14 30 15 Executes Exits then lt Select one Event frequency Once Executes Exits 4 then lt Biodispersant 5 Timed Events Add an Event YES Events 12 Biodispersant 5 Timed Events Delete all Events YES lt 4 13 1 6 Adjusting Feeds 1 of 2 ADJUST BASE FEED Key UP or DOWN to the pump control amp key ENTER Key DOWN to Configure amp ENTER Key DOWN to Special Control amp ENTER Key enter to View or change existing control Percentag
5. H x6 5 D 320mm W x 380mm H x 165mm D 11 8lb 5 4kg nominal Rated for outdoor use Limited to 5 Amps plugbox 2 amp 4 plug boxes provided with 36 of flexible non metallic conduit Pollution Degree 2 Altitude 2000m Installation Category Il Humidity 5 to 95 Notes Switch selectable 5x20mm 120VAC fusing Relays 1 5 amp 6 10 6 3A ea Control 1 5A Controller transformer isolated from AC line Electrical grounds at bottom of aluminum backplate Conductor insulation rated 600VAC minimum MAX AWG 14 150 150mm Conductor insulation rated 600VAC minimum Field wiring terminals on M7 amp M14 Notes Nominal dimensions excluding entry fittings and flexible conduit Including mounting Enclosure door hinged left Allow 18 left for door opening Allow 24 below for cable conduit access Plug boxes not included 1 At hardwired and 240VAC sites 2 With controllers shipped outside of North America 54 ___ Temperalure 06 to 406 nan M714_User_ Master doc Updated Aug 25 2015 55 4 4 Keypad Navigator 1 of 2 Activity Top Level then then UP DOWN DOWN amp Notes to amp ENTER 4 20mA Output Output Configure ENTER amp ENTER to toggle MANUAL AUTO C1 C8 MANUAL AUTO 4 20mA Output Output Configure DOWN to Control by Control Modify C1 C8 4 20mA Output Output Diagnostic DOWN to Output Card C1 C8 Location C1 C8 See Section 3 2 4 of 4 Alarm Relay OPEN CLO
6. Control Input Connections Loop Powered Pump or Valve 4 20mA Input Controller DC Supply 15 to 22 VDC Supply Dual 4 20mA Output Loop Powered Dual output driver Sensor shown Sinlge Driver has 1 amp 1 Terminals Controller DC Suppli 4 20mA Output t 15 to 22 VDC Supply Powered Loop 4 20mA Current Loop Dual Input Current Loop Inputs may be any combination or powered and loop powered E g Loop 1 Loop 2 gt 3 5 MA gt 3 5 mA M714_User_Master doc Updated Aug 25 2015 33 3 2 Connect Sensors 4 of 4 M7 Module Sensor Locations Sensor G Sensor E Sensor F Sensor B Sensor A Sensor D Sensor C QDOSDOVE SA M14 Module Sensor Locations Sensor E Sensor F Sensor G Sensor H Sensor M Sensor N Sensor K Sensor L m lt a O Oo a o c c O N N Sensor D Sensor C Sensor J es cai QD CDDSODVE QDOSODVE M714 _User_Master doc Updated Aug 25 2015 34 A 3 3 Connect Pumps Valves Solenoids M714 _User_Master doc Updated Aug 25 2015 35 Typical Wiring for Pumps Solenoids and Valves Black 1 White 1 Green Pump Red 2 Red 2 Green Solenoid 7 Red 4 Black 4 White 4 Green Motorized Valve Black 6 White 6 Green Pump Red Red Green Solenoid Red 8 Black 9 White 9 Green Motorized Valve M714 _User_Master doc Updated Aug 25 2015 Purnps are usually plugged in Solenoids are bo
7. R or S contact 4 then lt sets closed to operate the pump Steam Treatment 5 R S ANDS requiring both R amp S contact set to be Configure closed to operate the pump Interlocked by In this example R amp S may close when RIS Boiler s1 amp 2 are ON line M714_User_ Master doc Updated Audg 25 2015 41 3 8 Verify Blocking Relays BLOCKING PREVENTS TWO CONTROLS FROM TURNING ON AT THE SAME TIME This example shows an Inhibitor Pump 1 blocked when the Oxidant Pump 3 is ON to prevent Inhibitor Oxidant reaction Key ENTER Key DOWN to Configure and key ENTER then key DOWN to Blocking Relays This example shows that Relay 1 is OFF whenever relay 3 is ON Key ENTER to modify the blocking relay Selecting none removes the block This example shows an Inhibitor Pump turned OFF when Relay 2 is ON Relay 2 is a tower bleed solenoid This block stops Inhibitor from being pumped down the tower drain Key ENTER then key DOWN to Configure and key ENTER Key DOWN to Blocking Relays A 2 3 block would prevent the Inhibitor from feeding during bleed AND Oxidant feed Key ENTER to modify the blocking relays M714 _User_Master doc Updated Aug 25 2015 Inhibitor Pump 1 OFF Blocked 3 Oxidizing Biocide 3 ON 14 2 min lt H Inihibitor Pump 1 Diagnostics Configure v Alarms then Inhibitor Pump 1 Configure Blocking Relays 3 lt 4 Inhibitor Pump 1 OF
8. Updated Aug 25 2015 Tower Make up 40 12650 gal Inhibitor Pump 1 OFF Setpoints n Tower conduct ty 4B 1862 uS Bleed Solenoid 2 ON 113 2 min Tower pH C 7 62 pH Acid Pump 13 0N 8 6 min Boiler 1 cond AE 3521 uS Bl B down Valve qw4 OFF Setpoints 4 Biocide 1 47 ON owes 13 4 Biocide 2 lt 8 OFF No Control 4 Condensate Cond AF 20 3 uS 4 20mA Output C1 C1 8 46 mA 20 3 uS 37 3 4 Verify Controls 2 of 2 VERIFY MODIFY SETPOINTS The Tower pH sensor at input C Controls the acid pump powered by relay 3 Key ENTER at Acid Pump to verify modify setpoints Key DOWN to Configure and key ENTER Key DOWN to Turn ON Setpoint Its currently 8 25pH Key ENTER to Modify Key DOWN to verify modify Turn OFF Setpoint Key ENTER at 4 20mA display Key DOWN to Configure amp key ENTER 4mA level ous Key ENTER to modify or DOWN to verify modify 20mA Level 20mA level 100uS Key ENTER to modify M714 _User_Master doc Updated Aug 25 2015 Tower pH AC 7 62 pH Acid Pump 3 ON 8 6 min lt H Acid Pump 3 Diagnostics Configure v Alarms then lt Acid Pump 3 CONT 1 SUC viene eases Turn ON setpoint 8 25 pH ef 4 20mA Output C1 Cl Diagnostics Configure b then 4 20mA Output C1 Cl CONFIZU Cs se s4 Ma 4mA Level 0 00 uS 4 or lt m 4 20mA Output C1 Cl CONT TEU Ci e os amp oe es 20mA Level 100 00 uS e 38 3 5 Setting S
9. active alarms OR Scroll down to view all active alarms Name of alarming Sensor Alarm type pH Sensor value above High alarm for a user set time Name of alarming Water Meter Alarm type Low alarm checked at midnight High meter alarm trip immediately Name of Output control alarming Alarm type Feed limit timer turns OFF Pump Day Timer may be set to limit on time day M714 _User_Master doc Updated Aug 25 2015 System 2003 10 03 4 S N M0389001 Alarms 16 38 11 CK 3 lt H Alarms Clear Alarms Alarms lt lt H Alarms ALar MS raei ww ceed cas No Active Alarms Alarms ALANS s 3 7 sa pH Sensor Alarmed High YS Alarms Water Meter O Alarmed Low J i or toexit Alarms Acid Pump Limited ON timer 4 Wilf 1 2 Checking amp Clearing Alarms 2 of 3 CLEAR ALARMS Power UP first display Key ENTER to view detail on Sensors C K amp Relay 3 amp to clear alarms Key ENTER to Clear Alarms Clear Alarms Resets only all active alarms If you wish to end biocide events Prebleeds or lockouts OR restart special controls Clear the target relay alarm See page 3 of 3 Information only display EXIT key escapes Internet HELP reference for more detail Refer to Technical Support M714 _User_Master doc Updated Aug 25 2015 System 2003 10 03 S N M0389001 Alarms CK 3 lt H Alarms Clear Alarms Alarms qH Alarms Clear Ala
10. and System Alarms Sensors and the relays they control are grouped Key ENTER on sensor for sensor O menu amp ENTER on the relay 1 relay menu Sensor E menu Diagnostics Alarms Calibrate Configure Relay 2 menu Diagnostics Configure Alarms Timed Events Setup The display line with the ENTER arrow Displays Relay 9 menu on ENTER Sampling timing is adjusted by keying ENTER DOWN to Configure amp ENTER Sensor display current value Relays sown ON OFF state and run time if ON Water meters show volume from midnight Flowswitch T is ON and has been on for 560 2 minutes from midnight Biocide B pump is controlled by Relay 8 and is now OFF M714 _User_Master doc Updated Aug 25 2015 What s Happening Now System 2003 10 03 S N M0389001 Alarms 16 38 11 DG 2 Sys 4 Tower Make up 40 12800 Gal Inhibitor Feed 1 OFF L NG Tower Conduct y E 1246 uS Tower 1 Bleed v2 ON 18 6min 4 Blr 2 Conduct y AF 5240 uS B2 B down Valve 9 ON 0 4min Wl Corrosion Rate D 1 45 mpy Tower Bleed meter Q 34000 Gal 4 Flowswitch 1 AT ON 560 2min Biocide B 48 OFF 4 4 5 1 2 Checking amp Clearing Alarms 1 of 3 CHECK ALARMS Power UP first display Key DOWN to Alarms amp ENTER to view detail on Sensors C K amp Relay 3 amp to clear alarms Key DOWN to view active alarms amp ENTER Display on no
11. and Re sample delay are adjusted using the same key sequence M714 _User_Master doc Updated Aug 25 2015 B1 Blowdown 2 Captured Sample Re sample delay 45 minutes 4 B1 Blowdown 2 Captured Sample Fail to Sample B1 Fail to Sample 4 Typical Modify Blowdown time B1 Blowdown 2 Captured Sample Blowdown Time 60 seconds f HH Editing Value Blowdown Time 90 0 seconds gt Executes Exits j L2 then lt B1 Blowdown 2 Captured Sample Blowdown Time 90 seconds t 20 2 3 Sensor Diagnostics Key UP or DOWN to the desired sensor amp key ENTER This example is a cooling tower conductivity sensor Connected to input E Key ENTER at Diagnostics Each I O type has it s own set of Diagnostics Sensors have driver cards Water Meters and contact sets connect directly to top center terminal blocks Operational sensors are not Alarmed This example is a sensor operating outside of the HIGH or LOW alarms Current displayed value of the sensor and sensor units An increasing Gain indicates a fouled sensor Gain Multiplier changes with sensor calibration M714 _User_Master doc Updated Aug 25 2015 1 of 2 Tower Conduct vty E 986 uS Bleed Valve OFF Setpoints lt H Tower Conduct vty Diagnostics Alarms Calibrate Tower Conduct vty Diagnostics Input Card Type Conductivity Tower Conduct vty Diagnos
12. t 4 System DiagnosticS Relay 1 5 Fuse 0K System Diagnostics Relay 6 10 Fuse OPEN t 4 Continued on Page 2 27 2 5 System Diagnostics 2 of 2 Current state of alarm contacts The controller may be configured to OPEN or CLOSE alarm contacts on alarm Displays the current state of the dry contacts at the AL1 amp AL2 terminal block on the PR5 or PR10 module Increasing watchdog resets indicate external electrical spikes or internal controller faults Date and time of most recent full control reset A Default Admin Password has not been changed from the factory default Internal calibration check Factor required to correct internal 2 5V reference 1 0 05 Current loop and turbine water meter power supply Thermally fused Will read lt 10V if there is wiring a loop or meter fault Internal 12V Relay Supply Ethernet Option amp Feed Verify Option displays follow the 15V display M714 _User_Master doc Updated Aug 25 2015 System DiagnosticS Alarms CLOSED System DiagnosticS Watchdog Resets 6 t 4 System DiagnosticS Reset to Factory 2003 11 08 10 30 00 System Diagnostics Admin Password Default t System DiagnosticS Internal 2 5V 0 9996 System DiagnosticS 15V External Supply 20 276 4 28 3 1 Read this first ONE CONTROLLER MANY APPLICATIONS Controller
13. up meter Diagnostics Alarms Calibrate v then gt oO Make up meter 0 Calibrate Volume per Contact 100 gal v 4 then lt Editing Value Volume per Contact 200 gal A gt Executes Exits j 4 then dH Editing Value T Ta CO 2s 682 0a 321 5 gal gt Executes Exits 4 gt then dH Make up meter 0 Calibrate Reset to Factory NO lt 4 4 or or lt 11 Changing Biocide Timing 1or2 MODIFY EXISTING EVENT REVIEW EVENTS Key ENTER at selected chemical pump This one s powered by Relay No 5 Key DOWN to Timed Events amp ENTER This Biodispersant has 8 existing events See Page 2 for Add an Event If there are 0 events then the Edit an Event option does not exist ENTER to select the Event you wish to edit Key UP DOWN to Select one of 28 events OR Review existing timed events Day 1 to 28 for 4 week feed cycles Day 1 to 7 on weekly feed cycles Key RIGHT to select the field you wish to modify Key UP DOWN to modify the field ENTER to update M714 _User_Master doc Updated Aug 25 2015 Biocide A 44 ON 36 5 min Biodispersant 5 OFF Setpoints lt H Biodispersant 5 Configure 4 Alarms Timed Events gt then lt Biodispersant 5 Timed Events Add an Event YES Events 8 if Biodispersant 5 Timed Events Edit an Event YES lt 4 lt 1 Select one Day Start ON min
14. 0 cycles l lt l Inhibitor Pump 1 Key UP DOWN and RIGHT to modify PIXed CYCTES lakea then ENTER 4 230 cycles gt Executes Exits Increasing the concentration from 3 5 to 4 23 increases the calculated ppm 4 gt then lt Feed Verification Primer Feed Verification must be set to YES in the Inhibitor pump control Configure menu option The Inhibitor pump relay must be controlled by the make up water meter A fail to feed alarm is set on the feed verification meter input if the meter does not measure volume after the pump has been ON for 30 seconds Meter Cycles ppm calculation requires a water meter on the tower bleed Cycles of concentration is calculated using ratio of the Make up to Bleed meter volumes Bleed Cycles ppm calculation requires the conductivity of the tower make up Cycles of concentration is calculated using ratio of the Tower to Make up conductivities M714_User_Master doc Updated Aug 25 2015 47 Time amp Date are battery backed Adjusting Timer amp Date may not be required on start up Key ENTER at System Key DOWN to Time amp Date and key ENTER Displays current Date and Time Key ENTER to modify Key UP DOWN and RIGHT to modify the Date and Time Key ENTER Displays modified Date amp Time EXIT returns to System M714 _User_Master doc Updated Aug 25 2015 3 12 Time amp Date System 2003 10 27 S N M0389001 Alarms 16 38 11 none qH System Enable I 0
15. 00 us f When the Make up Conductivity is T a ea less than High Range amp greater than Med Range Bleed is controlled at High Cycles Tower Bleed 2 Variable Cycles Key ENTER to modify the High Cycles High Cycles 2 500 cycles l 4 or e When the Tower Conductivity exceeds Maximum Conductivity the Towe r Bleed 2 Bleed is controlled at Max Conductivity Variable Cycles i Max Conduct 3000 uS Key ENTER to modify the Maximum Conductivity or 4 or Variable Cycles Primer Variable Cycles must be set to YES in the Bleed control Configure menu option The bleed relay must be controlled by a conductivity ratio Example Control Equation is E F where E Tower Conductivity amp F Makeup Conductivity The Control Equation may be modified in the Bleed control Configure menu option Variable Cycles modifies bleed setpoints as make up conductivity changes Setpoint adjustment is blocked when Variable Cycles is controlling Bleed Setpoint units are set to cycles when Variable Cycles are selected You will need to modify the Range and Cycle Setpoints for your site makeup water chemistry and water treatment program M714 _User_Master doc Updated Aug 25 2015 45 3 11 Modifying Feed Verification 1 of 2 Controller Option Feed Verification calculates Inhibitor ppm and Inhibitor tank level with fail to feed alarms Requires a feed verification meter on the inhibitor chemical pump feed Key ENTER Key DO
16. 2 Inhibitor 8 OFF No Control qH Tower 2 Inhibitor 8 Diagnostics Configure dq Alarms then Tower 1 Inhibitor 6 Conflgure Special Control Bleed amp Feed t 4 then lt Tower 1 Inhibitor 6 Special Control Bleed amp Feed 4 Executes Exits lt H then 4 then lt Tower 1 Inhibitor 6 Bleed amp Feed of Time 54 av lt Editing Value of i i 49 t gt Executes Exits Jj L2 then lt 15 1 7 Userid Passwords IGNORE IF PASSWORDS NOT ON IN YOUR CONTROLLER YES appears if passwords are ON Your present USERID also displays If YES Key ENTER amp key in your password Key an incorrect password to log off Auto logoff occurs 30 minutes after the last keystroke If you keyed a correct password you ll see this display If your password is incorrect you ll still be the public user If you require the ADMIN password you ll see this display when you are already logged in under another userid If you are any user but public amp you key DOWN Login Required you can adjust your password Keep your password simple If you are using the keypad M714 _User_Master doc Updated Aug 25 2015 System Passwords Login Required YES public t lt H Editing Value Key Password G lt Executes Exits j 4 then lt System Time amp Date 4
17. 4 Configure Time amp Date H then lt System Time amp Date Adjusts Date Time 2003 10 27 16 38 lt H System Adjusts Date Time 03 11 27 17 38 Wed4 gt Executes Exits j 4 then lt System Time amp Date Adjusts Date Time 2003 11 27 17 38 4 48 Protects Power Relays Fuse 1 5 amp Fuse 6 10 Controller Modem Control Fuse Part M FUSES Cable Xover Mod LCD4 Mod M3000 Mod M7 Mod M14 Mod PR5 Mod PR10 Modem SFCBL4 SFCBL2 H SEN6 M714 _User_Master doc Updated Aug 25 2015 4 1 Spare Parts Fusing Manufacturer Vendor Littlelfuse Type 217 250VAC Digikey Part F953 ND Digikey Part F950 ND Rating Type 6 3 Amps 120VAC 3 Amps 250VAC 5mm x 20mm Fast Acting www digikey com 1 800 344 4539 Cooper Bussmann PC TRON PCC Series 250VAC Digikey Part 283 2758 ND Digikey Part 283 2120 ND 1 5 Amp 120VAC Y2 Amp 250VAC www digikey com 1 800 344 4539 Controller Parts Description 120VAC Fuse Kit 20 x 6 3A Relay Fuses 4 x 1 Amp control fuses Crossover cable Controller RJ45 to Notebook NIC Replacement 4x20 LCD Display Micro controller module Seven analog Six digital input module Fourteen analog Twelve digital input module Five power relay power module Ten power relay power module Modem serial cable amp power cube 120VAC Four Plug box flex conduit amp fittings pre wired 120VAC T
18. ENTER then UP or DOWN to override If you key DOWN you ll have the Reset to Factory option Key ENTER then UP or DOWN to Reset M714 _User_Master doc Updated Aug 25 2015 Tower Conduct vty E 986 uS Bleed Valve 42 OFF Setpoints lt H Tower Conduct vty E Diagnostics Alarms Calibrate v then lt Tower Conduct vty E Calibrate ines te Enter Current Value 986 uS v 4 then qu Editing Value Enter Current Valu 996 uS gt Executes Exits 4 then e Tower Conduct vty E Calibrate Sensor fault Override warning lt 4 4 then Tower Conduct vty E Calibrate zx c 92 Reset to Factory NO v 4 then lt 4 10 1 4 Calibrating Sensors 2 of 2 CONTACT HEAD amp TURBINE METERS Key ENTER at selected water meter Key DOWN to Calibrate amp ENTER Key ENTER to change value OR DOWN amp ENTER to Reset to Factory option Use the UP amp DOWN keys to adjust the value RIGHT moves the cursor across the screen EXIT abandons calibrating If the calibration succeeds you ll return to the sensor value display Turbine and Paddlewheel meters use pulses unit volume as calibration value If you key DOWN you ll have the Reset to Factory option Key ENTER then UP or DOWN to Reset Setting Volume per Contact OR K Factor to 100 M714 _User_Master doc Updated Aug 25 2015 Make up meter 0 23400 gal Inhibitor Pump 41 OFF Setpoints n Make
19. F Blocked 2 Oxidizing Biocide 3 ON 14 2 min lt H Inihibitor Pump 1 Diagnostics Configure lt Alarms then lt Inhibitor Pump 1 Configure Blocking Relays 2 3 lt 4 42 3 9 Selecting Special Controls This example shows an Inhibitor Pump with Bleed then Feed Special Control Key ENTER Key DOWN to Configure and key ENTER then key DOWN to Special Control Displays current special control Key UP DOWN to view available Special Controls Meter controlled relays do not have Special Controls No Control amp sensor controlled relays can select from Bleed amp Feed Bleed then Feed Captured Sample Time Prebleed Lockout Time Modulation Holding Time and Time Modulation Key ENTER to view modify current Special Control Key ENTER to modify the Bleed Relay Or DOWN to view the of Time In this Bleed Then Feed example For every 5 minutes of Tower Bleed time the Inhibitor runs for 46 or 136 seconds AFTER the bleed turns OFF Key ENTER to modify the of Time This example increase the of time from 46 to 52 Special Controls are detailed in the on line M714 Tech technical service manual M714 _User_Master doc Updated Aug 25 2015 Inhibitor Pump OFF No Control Biocide A ON 8 6 min HH Inhibitor Pump Diagnostics Configure Alarms 4 then lt Inhibitor Pump Configure Special Control Bleed then Feed HH and lt Inhibitor Pump Bleed then Fee
20. LAN Setup Passwords v System Passwords Login Required YES public y System Passwords New Password YES v 4n System New Password XK t gt Executes Exits j 4 then 1 16 2 1 Setting Biocide Prebleed Lockout 1 of 2 Key UP or DOWN to the biocide pump control amp key ENTER Key DOWN to Configure amp ENTER Key DOWN to Special Control amp ENTER If not set to Prebleed Lockout key UP DOWN Key ENTER to adjust Prebleed Lockout parameters Bleed Relay prebleeds before each biocide feed and is locked out after each feed event Key ENTER to modify Lockout Time turns OFF the bleed relay during biocide kill time Key ENTER to modify Prebleed Time turns ON the bleed relay reducing the tower conductivity before a biocide feed event Key ENTER to modify M714 _User_Master doc Updated Aug 25 2015 Biocide A 43 OFF No Control Biocide B 44 OFF No Control lt H Biocide A 3 Diagnostics Configure v Alarms then lt Biocide A 3 Configure s src Special Control Prebleed Lockout 4 then lt then lt Biocide A 3 Prebleed Lockout Bleed Relay Tower 1 Bleed 4 Biocide A 3 PreblLeed Lockout Lockout Time 120 0 Minutes f Biocide A 3 Prebleed Lockout Prebleed time 30 0 minutes t 4 Continued on Page 2 17 2 1 Setting Biocide Prebleed Lockout 2 of 2 You can Pre
21. SE System Configure DOWN to Alarm opens contacts Biocide Cycle Output 1 10 Setup DOWN to Event Cycle Set 1 7 28 days Contact Set to Meter Modify Input O Z Configure DOWN to Digital Input Type ENTER DOWN to Contact Head OR Turbine Meter Control Type Output 1 10 Configure DOWN to Control Type Action on Setpoints Rising Falling amp Between Setpoints OR Active only during Timed Events Default Configuration LOAD System Configure DOWN to Load Configuration Restores Default Controller Default Configuration SAVE System Configure DOWN to Save Configuration Makes current configuration the default Disable Input Input A Z Configure DOWN to Disable Input Disable Output Output 1 10 Setup DOWN to Disable Output C1 C8 M714_User_ Master doc Updated Aug 25 2015 56 Activity Enable I O Input Name Modify Input Resolution Modify Input Units LAN IP Netmask Gateway MAC Ports Modify Metric ON OFF Meter to Contact Set Modify Output Name Modify Password Modify Passwords ON OFF Upgrade Reset Passwords M714 _User_Master doc Updated Aug 25 2015 Top Level UP DOWN to System Input A Z Input A Z Input A Z System System Input O Z Output 1 10 System System System 4 4 Keypad Navigator 2 of 2 then DOWN amp ENTER Enable I O Configure Configure Configure LAN Setup Configure Configure Setup Passwords Configure Upgrade
22. WN to Feed Verify and key ENTER The Verify Meter measures the volume pumped by the inhibitor pump Key ENTER to modify Verify Meter sensor location Inventory Location logs tank level lowering level as inhibitor is pumped Key ENTER to modify Inventory location ppm location logs the calculated ppm based on volume pumped and the method used to calculate cycles Key ENTER to modify ppm location One of three methods is used to calculate cycles Fixed Cycles Bleed Cycles Meter Cycles Key ENTER to modify the cycles method M714 _User_Master doc Updated Aug 25 2015 Tower Make up 40 18425 gal Inhibitor Pump 1 ON 10 6 min lt H Inhibitor Pump 1 Setup A Variable Cycles Feed Verify v then lt Inhibitor Pump 1 Feed Verify Verify Meter Meter Input Q 4 or qu Inhibitor Pump 1 Feed VerlTfy Inventory Location Sensor Input G 4 or lt Inhibitor Pump 1 Feed Verify ppm location Sensor Input H 4 4 or iq Inhibitor Pump 1 Feed Verify ppm method select Fixed Cycles lt Continued on Page 2 46 3 11 Modifying Feed Verification 2 of 2 Fixed Cycles applies a user set cycles select one to calculate ppm ppm method select Fixed Cycles Key ENTER to view modify cycles Executes Exits lt Inhibitor Pump 1 l ppm method select ppm is calculated using 3 5 cycles of concentration Fixed Cycles Key ENTER to modify 3 50
23. bleed until this sensor measures the conductivity that you set Key ENTER to modify This is the Prebleed conductivity target Prebleed ends at this conductivity OR at the end of Prebleed Time Key ENTER to modify Set high to control on Prebleed Time only All Prebleed Lockout parameters are modified by ENTER when the parameter is displayed Key UP DOWN amp RIGHT to modify then key ENTER Bleed solenoid or valve now turns ON For 45 minutes before each feed event on Biocide A powered by Relay No 3 M714 _User_Master doc Updated Aug 25 2015 Biocide A 3 PreblLeed Lockout Prebleed Sensor Tower Conduct ty Biocide A 3 PrebTteed Lockout Prebleed Value 750 0 uS lt 4 Typical Modify Bleed time Biocide A 3 PrebTteed Lockout Prebleed time 30 0 minutes f HH Editing Value Prebleed Time 45 0 minutes gt Executes Exits j L2 then lt Biocide A 3 Prebteed Lockout Prebleed time 45 0 minutes lt t 18 2 2 Adjusting Boiler Blowdown Timing 1 of 2 Key UP or DOWN to the boiler blowdown control amp key ENTER This example is using Relay No 2 It s been ON for 1 2 minutes either Blowing down OR Sampling Key DOWN to Configure amp ENTER Key DOWN to Special Control amp ENTER Key ENTER twice to view or adjust timing Sampling opens the blowdown valve so the conductivity sensor gets a new sample Key ENTER to mo
24. controller AC power to the ground screw labeled and located on the bottom right of the aluminum backplate External 120VAC plug boxes are provided with controllers installed in North America External plug boxes are grounded to the ground screw labeled A located on the bottom center of the aluminum backplate A USER WARNING CAUTION Water Treatment Controllers operate steam and water valves and may pump hazardous corrosive and toxic chemicals Opening the controller enclosure exposes user to the risk of electrical shock at power line voltages Understand fully the implications of the control setpoints interlocks and alarms that you select Harm to personnel and damage to equipment may result from mis application Unplug or turn OFF the AC power to the controller if you have any concerns regarding safety or incorrect controller operation and notify supervisory staff YOUR CONTROLLER Controllers are supplied in many different configurations The HELP section in the back of this manual contains the information for terminating the sensors supplied with your specific controller The HELP section in the back of this manual depicts the installation plumbing header showing the sensor set supplied with your specific controller M714 User Master doc Updated Aug 25 2015 4 Power UP first display current date Key ENTER for System menu Key DOWN amp enter to clear all alarms And to view detail on Sensor D Relay 2
25. d Bleed Relay Tower Bleed Inhibitor Pump Bleed then Feed Of Time 46 then lt Editing Value Of Time 52 Executes Q 1 v3 Apn t gt Exits 4 then lt 43 3 10 Modifying Variable Cycles 1 of 2 Variable Cycles may be used where varying make up conductivity cause water treatment fault Requires a make up conductivity sensor Key ENTER Key DOWN to Variable Cycles and key ENTER Key ENTER to modify Low Range When the Make up Conductivity is less than Low Range Bleed is controlled at Low Cycles Key ENTER to modify the Low Cycles Key ENTER to modify Medium Range When the Make up Conductivity is less than Medium Range amp greater than Low Range Bleed is controlled at Medium Cycles Key ENTER to modify the Medium Cycles M714 _User_Master doc Updated Aug 25 2015 Conductivity AE 1384 uS Tower Bleed 2 ON 8 6 min lt H Tower Bleed 2 Timed Events Setup Variable Cycles then lt Tower Bleed 2 Variable Cycles Low Range 350 uS 4 or lt Tower Bleed 2 Variable Cycles Low Cycles 6 100 cycles yv amp or lt Tower Bleed 2 Variable Cycles Med Range 650 uS v 4 or lt Tower Bleed 2 Variable Cycles Med Cycles 4 250 cycles Y or lt Continued on Page 2 44 3 10 Modifying Variable Cycles 2 of 2 Tower Bleed 2 Variable Cycles Key ENTER to modify High Range High Range 10
26. dify Measure cools the sample at the conductivity sensor At the end of Measure conductivity is compared to the ON OFF setpoints Key ENTER to modify If the conductivity is above the TURN ON setpoint the valve opens for the Blowdown Time Key ENTER to modify M714 _User_Master doc Updated Aug 25 2015 Boiler 1 Cond AE 2546 uS B1 Blowdown a2 ON 1 2 minutes lt H B1 Blowdown 2 Diagnostics Configure Alarms then B1 Blowdown 2 CONTTISUPC Yi v n si e 4 Special Control Captured Sample 4 then lt then dH B1 Blowdown 2 Captured Sample Sampling Time 30 seconds t B1 Blowdown 2 Captured Sample Measure Time 60 seconds aie B1 Blowdown 2 Captured Sample Blowdown Time 60 seconds t 4 Continued on Page 2 19 2 2 Adjusting Boiler Blowdown Timing 2 of 2 If the measured conductivity is below the TURN OFF setpoint the next Sample occurs after the Re Sample delay If the measured conductivity is above the TURN OFF setpoint Blowdown Time s are followed by Measure Times as the boiler conductivity falls Key ENTER to modify If your installation does not include a Fail to Sample sensor none will be displayed Key UP DOWN to Blowdown Time amp ENTER Key ENTER to adjust timing Key UP DOWN amp RIGHT to modify then key ENTER We ve increased the Blowdown Time from 60 to 90 seconds Sampling Time Measure Time
27. e Boilers Interlocking Blocking M714 _User_Master doc Updated Aug 25 2015 4 3 Specifications 2 of 4 Rating Detail User set deadband and controlling sensor s or contact set User defined rising falling or between Setpoints or active only during timed events 28 Events per relay 1 minute resolution Lockout Prebleed on both time and conductivity User defined control by sensor or relay control equation Auto Manual switching Timed Modulation and Timed Cycling Special Controls User set measure volume amp pump ON time Sequential control measures Makeup volume then bleeds for user set volume Bleed amp Feed and Bleed then Feed Includes of Bleed Time User set Time Prime Holding Time Sample Measure Blowdown Resample user set timing Fail to Sample sensor support included 1 to 4 contact set inputs AND amp OR support 1 to 4 relays may block any other relay Notes Any relay can be user configured for any Control Control by up to 4 analog sensors using x amp math Each relay can be set to 1 7 or 28 day cycle Timed events may exist concurrently with other controls Software ZERO amp SPAN adjust Interlocked current loops go to 4mA ON time modified by Setpoint to actual delta Rate to Volume conversion routes analog input to Water Meter s Bleed amp Feed based on 5 minute period Time amp Prime on 5 minute period Holdin
28. e Time turns ON for user set every 5 minutes Key ENTER to view adjust current Percentage Time is set to 28 Pump runs for 84 seconds every 5 minutes Key ENTER to modify Key UP DOWN amp RIGHT to modify then key ENTER 31 is 93 sec every 5 minutes M714 _User_Master doc Updated Aug 25 2015 Tower 1 Inhibitor 6 ON 6 2 min Tower 2 Inhibitor 8 OFF No Control lt H Tower 1 Inhibitor 6 Diagnostics Configure H Alarms then lt Tower 1 Inhibitor 6 Configure Special Control Percentage Time f then lt Tower 1 Inhibitor 6 Special Control Percentage Time 4 Executes Exits Tower 1 Inhibitor 6 Percentage Time ON Time 28 lt lt H Editing Value ON Time 31 A gt Executes Exits 4 d then lt 14 1 6 Adjusting Feeds 2 of 2 ADJUST BLEED FEEDS Key UP or DOWN to the pump control amp key ENTER Key DOWN to Configure amp ENTER Key DOWN to Special Control amp ENTER Key enter to View or change existing control Key DOWN if you wish to switch from BLEED amp FEED to BLEED THEN FEED Key DOWN to of Time amp ENTER Percentage Time is set to 54 Pump runs for 162 seconds every 5 minutes Key ENTER to modify Key UP DOWN amp RIGHT to modify then key ENTER 49 is 147 sec every 5 minutes M714 _User_Master doc Updated Aug 25 2015 Tower 1 Inhibitor 46 ON 6 2 min Tower
29. ensor Alarms VERIFY MODIFY ALARMS Key UP DOWN to the target sensor and key ENTER Key DOWN to Alarms and key ENTER Key ENTER to modify High Alarm or DOWN for Low Alarm Key ENTER to modify Low Alarm or DOWN for Alarm Relay A Tower pH alarm will trip the controller alarm relay Key ENTER amp UP DOWN to select NO to not set the alarm relay on a pH alarm A high or low alarm will register 5 minutes after it occurs to block alarms on transients Key ENTER to modify A delay of 0 0 minutes will alarm immediately M714 _User_Master doc Updated Aug 25 2015 Tower pH 7 62 pH Acid Pump ON 8 6 min HH Tower pH Diagnostics Alarms Calibrate then Tower pH ALOT Siac aden acne High Alarm 10 00 pH 4 or qu Tower pH Alarms Low Alarm 5 50 pH 4 or e Tower pH Alarms Set Alarm Relay YES amp or qi Tower pH DA TS k4 245244 oes Delay on Alarm 5 0 minutes 39 HC v3 C A lt 3 6 Setting Output Alarms VERIFY MODIFY FEED LIMIT ALARMS Key UP DOWN to the target control and key ENTER Key DOWN to Alarms and key ENTER An acid pump limit timer prevents overfeed on pH sensor fault Key ENTER to modify Minutes Actuation or DOWN for Minutes Day Key ENTER to modify Minutes Day or DOWN for action on alarm Acid pumps are usually set to Turn OFF on Alarm Bleed controls are usually set to NOT Turn OFF on alarm A feed limit alarm wil
30. g time averages sensor values for control Any sensor may be used Support for high pressure sites Relay OFF when contact set opens Support for common Oxidant Inhibitor feed If Blocking relay ON this relay OFF 52 Controls Alarms Feed Limit Timers Variable Cycles Feed Verification Option Data Logging Log Content Log Size Logging Rate Log File Format XML System Controller Configuration Watchdog Field Upgrades M714 _User_Master doc Updated Aug 25 2015 4 3 Specifications 3 of 4 Rating Detail Minutes Actuation Minutes Day User defined trip alarm relay and or dial out Three user defined ranges of make up conductivity and target cycles User defined maximum tower conductivity ppm calculation based on volume fed and cycles of concentration Alarm on fail to feed User selected cycles method Fixed Ratio of Tower Makeup conductivity Ratio of Makeup Bleed Volume Rating Detail Analog Inputs Min Max amp Average Digital Water Meters Volume Digital Contact Set ON Time 600 entries for each of 26 analog and digital inputs and each of 10 relay outputs 21 600 Entries Total User set independently for each I O from 5 to 1440 minutes entry User defined start amp end date for XML download Rating Detail User selected Save and Restore to FLASH memory 1 sec Hardware relay lockout Enable ETHERNET Feed Verification Add Sensors and Dr
31. ivers Notes User defined OFF on Feed Limit Auto reset on Bleed amp Feed and Bleed then Feed Requires control by the ratio of analog sensors 1 deadband on cycles and maximum conductivity Requires feed volume meter or 4 20mA input on feed rate Fail to to feed is no volume fed after 30 seconds Notes Year to date included for Meters 600 entries 25 Days at 60 minutes Logging Rate Default 60 minutes dtd defines date stamping for each of 21 600 log entries Notes Makes current configuration factory default Active on power up and firmware blocked Upgrades locked to Serial and date limited 53 Electrical AC Input Fusing Surge Spike Suppression AC Terminals Sensor Digital Input Terminals DC Loop Turbine Meter Power Mechanical Enclosure Rating Dimensions Weight 120VAC Plug Boxes Environmental M714 _User_Master doc Updated Aug 25 2015 4 3 Specifications 4 of 4 Rating Detail 120 or 240 VAC 50 60Hz M10 Version 12 6 Amps 120VAC 6 Amps 240VAC M5 Version 6 3 Amps 120VAC 3 Amps 240VAC Relays 2 5 and 7 10 NO contacts snubbed 0 1uF 150R Varistor on control AC input AC Input AWG 12 240mm AC Outputs AWG 14 150mm AWG 22 0 25 0 50mm 15 22 VDC unregulated Thermally fused 200mA Rating Non metallic NEMA4X IP65 M10 Version 14 W x 17 H x 6 75 D 355mm W x 430mm H x 170mm D 17lb 7 7kg nominal M5 Version 12 5 W x 15
32. l trip the controller alarm relay Key ENTER amp UP DOWN to select NO to not set the alarm relay on feed limiting Key down to view Reset amp Most Recent Alarm M714 _User_Master doc Updated Aug 25 2015 Tower pH AC 7 62 pH Acid Pump 3 ON 8 6 min lt H Acid Pump 3 Diagnostics 4 Configure Alarms v then lt Acid Pump 3 ALORS soot edt ee eee Minutes Actuation 45 0 minutes 4 4 or qu Acid Pump 3 Alar WS 264 O48 SERRE 5 Minutes Day 600 0 minutes 4 or qu Acid Pump 3 Alar HS 26 y4 a Turn OFF on Alarm YES t 4 or e Acid Pump 3 Alaf MS 24 3 644 48 gas Set Alarm Relay YES lt 4 40 3 7 Verify Interlocks INTERLOCKS PREVENT CONTROLS Conductivity E FROM TURNING ON 1245 uS Tower Bleed v2 Key UP DOWN to the target control ON 8 6 min and key ENTER lt Tower Bleed 2 Diagnostics 4 Key DOWN to Configure and key ENTER Configure v then key DOWN to Interlocked by Alarms l 4 then lt Tower Bleed 2 In this example when the Flowswitch connected to Configure input T closes the Tower Bleed can operate Interlocked by T Key ENTER to modify the interlock Steam Demand AP In the 2 d example Steam Treatment is being fed 32500 1b based on Steam demand Steam Treatment 415 ON 10 4 min Key ENTER then key DOWN to Configure and key ENTER l Steam Treatment 5 Diagnostics Configure lt H Key DOWN to Interlocked by Alarms v An R S ORS requiring either
33. mple sensors and contact sets connected to R S amp T M14 Type Controllers Water meters are typically connected to inputs O P amp Q and U V amp W Flowswitches fail to sample sensors and contact sets connected to R S amp T and X Y amp Z Digital Inputs Inputs O to Z may be user configured for water meters and volume measurements OR contact closure and state interlocking functions Typical Water Meter amp Flowswitch Connections Water Meters Turbine Meters Flowswitches and Contact Sets may be connected any digital input O to T OQDOSODLS QOD Black Red Red Red Contact Head Flowswitches Water Meters amp Interlocks M714_User_ Master doc Updated Aug 25 2015 30 3 2 Connect Sensors 2 of 4 Typical Sensor Driver Connections ORP amp pH Red to S Black to S White to T Bare Shield to Green to T Clear center wire to Conductivity Temperature Sensor Sensor Entry amp Solution Ground Conductivity ey Temperature 2nd sensor connects to 2 2 Terminals Sensor 1 Sensor cabling is not polarized Sensor 1 Sensor cabling is 2nd sensor not polarized connects to S2 Terminals 2nd sensor connects to Corrosion 2 Terminals Rate Boiler Condensate M714 _User_Master doc Updated Aug 25 2015 31 3 2 Connect Sensors 3of4 M714 _User_Master doc Updated Aug 25 2015 32 Remote Proportional Typical 4 20mA Output amp Monitor
34. multiF LEX M10 and M5 User Manual ProMinent M714_User_ Master doc Updated Aug 25 2015 CONTENTS Safety STANDARD OPERATIONS What s Happening Now Checking amp Clearing Alarms Checking amp Changing Setpoints Calibrating Sensors Changing Biocide Timing Adjusting Feeds 1 1 1 1 1 1 1 1 Userid Passwords NOOR WD 2 ADDITIONAL OPERATIONS 2 1 Setting Biocide Prebleed Lockout 2 2 Adjusting Boiler Blowdown Timing 2 3 Sensor Diagnostics 2 4 Control Diagnostics 2 5 System Diagnostics 3 START UP PROCEDURE 3 1 Read this first 3 2 Connect Sensors 3 3 Connect Pumps Valves Solenoids 3 4 Verify controls 3 5 Setting Sensor Alarms 3 6 Setting Output Alarms 3 7 Verify Interlocks 3 8 Verify Blocking Relays 3 9 Selecting Special Controls 3 10 Modifying Variable Cycles 3 11 Modifying Feed Verification 3 12 Modifying Time amp Date 4 ADDITIONAL INFORMATION 4 1 Spare Parts 4 2 Technical Support 4 3 Specifications 4 4 Keypad Navigator 4 5 Revision Log M714 _User_Master doc Updated Aug 25 2015 Saftey A Electrical Shock Hazard CAUTION The operator of this instrument is advised that if the equipment is used in a manner not specified in this manual the protection provided by the equipment may be impaired Opening the controller enclosure with the controller plugged in exposes the user to AC line voltages on the lower of the two controller circuit boards Ground the
35. nse Water Meters 400 Hz max 0 5mA 5VDC measurement current M7 5 1SPST 4 SPDT M14 10 2 SPST 8 SPDT Dry contact set Unfused PR10 Only Rating Detail 5 Key Tactile feedback UP DOWN ENTER EXIT RIGHT 4 Line x 20 Character Backlit HTML Telnet micro Web Server Full command control reconfigure via browser Network parameters and ports User set 56K V 90 Remote Telnet access Dedicated controller serial port Controllers configured M7 PR5 M7 PR10 M14 PR5 amp M14 PR10 Notes 3 Dual amp 1 Single Driver 7 Dual Drivers Auto configure on Driver installation and removal Single amp Dual Drivers Each 4 20mA output uses an Analog Input Auto configure on Driver installation and removal User configurable as water meters or contact sets Contact head meters software debounced Turbine Paddle wheel rating Seametrics max pulse rate Relays rated 10A 120VAC Fused in sets of 5 relays Detection and Alarm on fusing User selected NO or NC Measures total AC load current Notes Scan rate 100mS nominal User adjustable contrast Password UserID protected Browser can show LCD is real time Auto configures views linking sensors and controls HELP links for on line users Dial out on alarm to pager or PC Forced dial out diagnostics 51 Controls ON OFF Biocide Feed Timed Events Proportional 4 20mA Proportional ON OFF Volumetric Timed Captured Sampl
36. rms Clear All Alarms YES lt H Alarms Alarms Cleared Key to Exit iNet HELP 0700 A 16 38 11 1 2 Checking amp Clearing Alarms 3 of 3 RESET RELAY USING CLEAR ALARMS Key UP or DOWN to the output relay amp key ENTER Any relay can be reset This example is a Biocide pump with 16 6 minutes of ON time remaining Key DOWN to Alarms amp ENTER Key DOWN to Reset Alarm amp Time amp ENTER Relay 4 will turn OFF Biocide feeds and prebleeds will end If this relay is timing a biocide lockout it will end Special controls like Bleed amp Feed Time or Boiler Captured Sample controls will restart After you key ENTER you see the value of the relay feed limit timer Key EXIT twice amp you ll see that Relay 4 is now OFF Relays don t need to be ON to be reset You may wish to restart special control Or end the lockout of a bleed relay M714 _User_Master doc Updated Aug 25 2015 Biocide A 4 ON owes 16 6 Biocide B v5 OFF No Control n Biocide A Diagnostics Configure Alarms v then lt Biocide A 4 Alar MS ociera denea Reset Alarm amp Time YES lt 4 then Biocide A 4 AlarmS s2 Ta s2 4 Minutes Actuation 120 0 minutes t and amp to exit gt gt Biocide A 4 OFF No Control v Biocide B 5 OFF No Control 4 1 3 Checking amp Changing Setpoints Key UP or DOWN to the output relay amp key ENTER Relays follow the controlling sen
37. s are shipped configured with a wide range of sensors for one or more cooling towers multiple boilers hot amp chilled closed loops condensate monitoring waste water control and monitoring YOUR CONTROLLER SENSOR SET The installation instructions for your specific controller are in the HELP section YELLOW pages HELP is the last tab in the manual binder YOUR APPLICATION CHANGES The controller can be completely reconfigured using the keypad or optional browser Feed methods and interlocking can be changed pH control can be switched to ORP A tower controller can be switched to waste water or boiler condensate controls You need to automate sensor cleaning measure more water meters Feed based on steam production Bleed on the ratio of make up amp bleed volume YOU NEED TO ADD ANOTHER PH ORP BOILER CONDUCTIVITY Upgrade kits can expand the controller to 14 analog sensors 10 watermeter digital inputs and 10 Relay controls The controller recognizes new sensor drivers and auto configures The digital inputs can be switched between water meter inputs to contact closure inputs THE REST OF SECTION 3 Not all of the following sections apply to your controller or application You may need some of these functions as your application evolves M714 _User_Master doc Updated Aug 25 2015 29 3 2 Connect Sensors 1 of 4 M7 Type Controllers Water meters are typically connected to inputs O P amp Q Flowswitches fail to sa
38. sor Key DOWN to Configure amp ENTER Key DOWN to Turn ON amp ENTER Select Measure Volume for water meter controls Current setpoint is 1000uS Use the UP amp DOWN keys to adjust the setpoint RIGHT moves the cursor across the screen EXIT abandons adjusting the setpoint You can adjust ON or OFF setpoints or both Key ENTER to adjust or UP DOWN to view current settings Turn OFF gt Turn ON not allowed with a Rising Setpoint control M714 _User_Master doc Updated Aug 25 2015 Tower Conduct vty 4E 986 uS Bleed Valve 42 OFF Setpoints lt H Bleed Valve 2 Diagnostics Configure v Alarms then lt Bleed Valve 2 CONT TEU Oses 6 4 duy ake Turn ON 1000 us t 4 then Editing Value Turn ON saaana 1150 uS 4 gt Executes Exits 4 then lt Bleed Valve 2 Configure sse s Turn OFF 980 uS 4 4 then qu Editing Value PUEN ORF ec Reels 1130 uS A Executes Exits 4 4 then lt Calibrating Sensors 1 of 2 SENSORS Key ENTER at selected sensor Key DOWN to Calibrate amp ENTER Key ENTER to change sensor value OR DOWN amp ENTER to Reset to Factory option Use the UP amp DOWN keys to adjust the value RIGHT moves the cursor across the screen EXIT abandons calibrating If the calibration succeeds you ll return to the sensor value display If the sensor is outside of calibration limits You ll view the override option Key
39. t Cycles may repeat every 1 7 or 28 days This example has 8 events which repeat every 4 weeks 28 days Today is Day 9 Monday of week No 2 Today s Inhibitor pump ON time from midnight Inhibitor pump ON Time Owed Increases while the cooling tower is making up and decreases to zero when the make up float closes Varying Cycles and Feed Verification status Displays follow the Special Control display M714 _User_Master doc Updated Aug 25 2015 Inhibitor Pump 1 DiagnosticS Then turn ON for 20 sec Inhibitor Pump 1 DiagnosticS Last fed at 38300 gal t Inhibitor Pump 1 DiagnosticS 28 Day Event Cycle 8 events Day 9 Inhibitor Pump 1 Diagnostics minutes ON today 110 6 minutes t Inhibitor Pump 1 DiagnosticS Time Owed 0 3 minutes Inhibitor Pump 1 DiagnosticS Special Control none 4 24 2 4 Control Diagnostics 3 of 4 CAPTURED SAMPLE EXAMPLE page 1 Key UP DOWN to the blowdown control amp ENTER Blowdown valve is ON and has been ON for 1 2 minutes Key ENTER at Diagnostics Each control type has it s own set of Diagnostics Priming overrides boiler timing turning ON the blowdown valve for 5 minutes Select Alarms then Reset Alarm amp Time to end Prime Output Current State displays that the Captured Sample Special Control has turned ON the Blowdown Controlling sensor in this example is sensor F
40. th hardwired and plugged in Motorized Valves must be hardwired Black 1 Red 2 White 1 Red 2 White 4 Red 4 Black 4 Aluminum Backlate Green Fractinnal HH pumps require motor start relays Black 6 Red 6 White 6 Valve connections vary with Red Z manufacturer White 3 Worcester WHITE to flying Red 9 lead RED to NC amp leas BLACK ta NO 2 D Y Z Y S 2 ay 2 S VOOY VOSS SJP 828002 OO ee 36 3 4 Verify Controls 1 of 2 VERIFY SENSORS MATCH CONTROLS Controlling sensors are followed by the controlled pumps valve amp solenoids Make meter connected to input O Controls the inhibitor pump powered by Relay 1 Key ENTER to verify modify pump setpoints Conductivity Sensor connected to B Controls the bleed solenoid powered by Relay 2 Key ENTER to verify modify bleed setpoints pH Sensor connected to C Controls the acid pump powered by Relay 3 Key ENTER to verify modify acid feed setpoints Page 2 shows key sequence Boiler Conductivity Sensor connected to E Controls the blowdown valve powered by Relay 4 Key ENTER to verify modify blowdown setpoints Biocides follow sensor no used for control As you key UP DOWN Sensors may be used to control 4 20mA outputs In controllers with IO Driver cards Condensate Monitoring Sensor connected to F Controls the C1 4 20mA control Key ENTER to verify modify 4 20mA span M714 _User_Master doc
41. tics Current State Alarmed Tower Conduct vty Diagnostics Displayed Value 968 4 uS Tower Conduct vty Diagnostics Gain Multiplier 5 7160 4 Continued on Page 2 21 A2 m 2 3 Sensor Diagnostics 2 of 2 Selecting Reset to Factory during sensor calibration sets the Gain Multiplier to the Default Gain Conductivity adjusts Gain Multiplier to calibrate pH ORP and temperature modifies Offset Adjust to calibrate Selecting Reset to Factory during sensor calibration sets the Offset Adjust to the Default Offset Measured Level is the raw sensor level Before Gain Multiplier and Offset Adjust are applied Each driver card range and configuration jumper setting has a unique ID used by the controller to auto configure Watermeters and contact sets do not require IDs Some driver cards have internal drive levels Corrosion Rate cards use Drive Level to correct for DC isolation offsets Key EXIT to return to sensor menu M714 _User_Master doc Updated Aug 25 2015 Tower Conduct vty E DiagnosticS Default Gain 5 6000 Tower Conduct vty E DiagnosticS Offset Adjust 35 0000 Tower Conduct vty E DiagnosticS Default Offset 35 0000 Tower Conduct vty E DiagnosticS Measured Level 184 5 mV Tower Conduct vty E DiagnosticS Input card ID 76 7 mV Tower Conduct vt
42. wo Plug box flex conduit amp fittings pre wired Sensor entry gland six cable seal Replacement Sensors and Upgrade Kits Refer to 4 2 Technical Support 49 Technical Support ProMinent Fluid Controls Inc formerly Aquatrac Inc 136 Industry Drive Pittsburgh PA 15275 412 787 2484 8 00AM 5 00PM EST Other Keypad Functions Navigation to keypad functions is detailed in Section 4 4 Keypad Navigator Upgrade Kits Controls can be added to installed controllers Upgrade kits include sensor entry fitting driver card and installation instructions On Line Help Internet HELP is linked in real time by browser users with internet accessible controllers Keypad connect to www aquatrac com help with iNet HELP from LCD display Browser Users Manual Download M714_browse from www aquatrac com Controller Technical Manual Download M714_tech from www aquatrac com M714 _User_Master doc Updated Aug 25 2015 50 Analog Digital I O Analog Inputs 4 20 ma Outputs Digital Inputs Relay Outputs Alarm Relay Load Current Communications User Interface Keypad LCD 10 BaseT TCP IP Ethernet LAN Optional Modem Optional M714 _User_Master doc Updated Aug 25 2015 4 3 Specifications 1 of 4 Rating Detail M7 7 Analog Sensors M14 14 Analog Sensors 0 to 8 DC isolated loop powered Nominal 0 1 resolution Auto polarity correction field wiring M7 6 M14 12 Dry Contacts 250mS respo
43. y E DiagnosticS Drive level 0 0 mV 4 22 2 4 Control Diagnostics 1 of 4 INHIBITOR FEED EXAMPLE page 1 Key UP DOWN to Inhibitor Pump amp ENTER The pump is ON and owes 6 1 minutes of ON time Key ENTER at Diagnostics Each control type has it s own set of Diagnostics Key ENTER to turn ON the Pump for 5 minutes WARNING Immediately turns ON pump Unless blocked interlocked or on biocide lockout Select Alarms then Reset Alarm amp Time to end Prime Output Current State displays Interlocked Blocked Timed Out status messages Controlling sensor in this example is water meter O Current value of control displayed Volume controls measure a user set volume before turning ON the pump In this example 100 gallons M714 _User_Master doc Updated Aug 25 2015 Make up Meter AO 38400 gal Inhibitor Pump 1 ON owes 6 1 lt H Inhibitor Pump 1 Diagnostics lt Configure Alarms Y Inhibitor Pump 1 Diagnostics Prime Output YES v Inhibitor Pump 1 DiagnosticS Current State ON owes 5 6 t Inhibitor Pump 1 D iaglostiCS Control by 0 38400 gal t Inhibitor Pump 1 DiagnosticS Measure volume 100 00 gal 4 Continued on Page 2 23 2 4 Control Diagnostics 2 of 4 INHIBITOR FEED EXAMPLE page 2 In this example after each 100 gallons the Inhibitor pump turns ON for 20 seconds Water meter volume when last feed occurred Even