Home
AVPTC-183014 technic..
Contents
1. 75mis 82 60 100 OFF ON D 30sec 50 7 5 mins 82 30 50 ON Cooling Heat Pump Airflow Table Tap Stage Cool AVPTC183014 AVPTC313714 AVPTC42601 4 NOTE Airflow data shown applies to non communicating mode operation only For a fully communicating system please see the outdoor unit s installation instructions for cooling and heat pump airflow data See ComfortNet System Airflow Consideration section for details Electric Heat Airflow Table 183014 313714 426014 N 1190 N 1390 FF 1580 15 NOTE Airflow data shown applies to the emergency heat mode electric heat only in either non communicating mode operation or fully communicating mode operation 3 5 10 15 20 680 790 80 2 NOTE Airflow blink codes are approximations of actual airflow Heat Kit Selection MODELS HKR 03 HKR 05 05C HKR 06 HKR 08 08C HKR 10 10C HKR 15C HKR 20C HKR 21C ee ee ee xe EI ee I AVPTC18301 4A x x L x x P x P e P AVPTCADGO TAN Revision level that may or may not be designated C Circuit breaker option NOTE When 8kW and 10kW heat kits are used with an AVPTC1830 and AVPTC3137 matched with 2 ton outdoor unit see Note 1 below 1 Set Heater Kit dip switches 9 10 and 11 to 6kW setting 9 ON 10 OFF 11 ON to obtain 840 2 This heater kit can only be used for 1000 or
2. TECHNICAL MANUAL AVPTC Air Handlers Refer to Service Manual RS6200006 for installation operation amp troubleshooting information All safety information must be followed as provided in the Service Manual Refer to the appropriate Parts Catalog for part number information Models listed on page 3 This manual is to be used by qualified professionally trained HVAC technicians only Goodman RT6121001r6 does not assume any responsibility for property damage or personal injury due to improper Mav 2011 service procedures or services performed by an unqualified person y Copyright O 2010 2011 Goodman Manufacturing Company L P PRODUCT IDENTIFICATION The model number is used for positive identification of component parts used in manufacturing Please use this number when requesting service or parts information EXPANSION DEVICE F Flowrater T TXV Expansion Device MINOR REVISION MAJOR REVISION REFRIGERANT CHARGE 4 R 410A PRODUCT TYPE A Air Handler CABINET FINISH U Unpainted P Painted N Uncased APPLICATION EXPANSION C Ceiling Mount PSC Motor DEVICE ELECTRICAL D Downflow PSC Motor C 4 Wire 1 208 230V 1ph 60Hz E Multi Position Varible Speed Motor Communicating R Multi Position PSC Motor Ready S Energy Efficient Motor Multi Position PSC Motor T Coated Coils V Variable Speed ECM Motor NOMINAL CAPACITY RANGE Multi Position a
3. When this productis installed in the downflow installation in an unconditioned space remove the horizontal drain pan and install the following insulation kit 1830 DP136 42 20 See following chart for the correct DPIH kit 1830 DPIH36 42 3137 4260 DPIH48 61 AVPTC is a multi position variable speed air handler and is This kit is used to prevent sweating on the vertical drain pan eee WIL Is Be VOK E n ECM motor and is compatible with heat pumps and variable capacity cooling applications See note below 3137 4260 0 148 61 20 preventthe horizontal drain pan from sweating in high humidity applications it is recommended that a DPIH jd m din En n o deo NOTE Factory sealed to achieve a 2 or less leakage rate AON KE TE Re d at 1 0 water gauge external duct static pressure purchased separately Complies with the Factory sealed Air Handling Credit as listed inthe 2001 Florida Building Code Chapter 13 Section 610 2 A 2 1 PRODUCT DIMENSIONS AVPTC lt p 1 1 2 54 cm C 2 54 cm id gt 2 54 PLASTIC BREAKER LOGO SUCTION LINE LIQUID LINE gt 4 INLET TUBE 1 3 16 2 7 8 7 3 cm gt 3 0 INLET RIGHT SIDE VIEW FRONT VIEW HE EOS GE EC KCN EUN o Lew AVPTO420014 PRODUCT SPECIFICATIONS AVPT
4. higher applications 3 This heater kit can only be used for 1200 or higher applications BLOWER PERFORMANCE DATA Outdoor Data Line Indoor Control Control Voltages Vdc TERM TERM BIAS Dipswitches Dipswitch ON ze zz 05 For per s 9s ON OFF ON OFF ON I Fees N TERM1 TERM Termination dipswitches at outdoor unit See installation instructions with CT compatiable outdoor unit OFF ON 1 m BIAS 2 mi BIAS mj TERM Indoor Unit BIAS and TERMINATION Dipswitches WIRING DIAGRAMS NOTE WHEN INSTALLING HEATER KIT ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED MBS SPECIFIED FOR THE AIRHANDLER HEATER HIGH VOLTAGE AVPTC WARNING DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH KIT COMBINATION ON THIS UNIT S S amp R PLATE AFTER INSTALLING OPTION AL HEAT KIT MARK AN X IN THE _ PROVIDED ABOVE MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS IN STALLED NO MARK INDICATES NO HEAT KIT INSTALLED PL1 PL2 40 VA TRANSFORMER SEE NOTE 1 230 VAC 4 CIRCUIT HEATER CONNECTOR a CFM LED DIAGNOSTIC LED DEHUM UNUSED a 1CooL El DIP SWITCHES m m YOLOSNNOD YOLOW LUNIO 7 Ir r STATUS e LED excep Bi SEE NOTE 6 TWO STAGE INTEGR
5. ATED CONTROL MODULE ECM MOTOR HARNESS SNO LW LSONYSHL Avc DISCONNECT INDOOR AIR 4 CIRCULATOR BLWR f 208 230 VAC O 1 Eo f HEAT SEQUENCER R1 W2 2 Fo HEAT SEQUENCER R2 INDOOR AIR CIRCULATOR COLOR CODES PK PINK BR BROWN WH WHITE BL BLUE GY GRAY RD RED YL YELLOW OR ORANGE PU PURPLE GN GREEN BK BLACK LOW VOLTAGE 24V LOW VOLTAGE FIELD HI VOLTAGE 230V HI VOLTAGE FIELD JUNCTION TERMINAL INTERNAL TO INTEGRATED CONTROL EQUIPMENT GND FIELD GND FIELD SPLICE RESISTOR OVERCURRENT PROT DEVICE PLUG CONNECTION L F NOTES 1 PLACE RED WIRES ON TRANSFORMER TERMINAL 2 FOR 208 VAC OPERATION 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 3 IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 USE COPPER CONDUCTORS ONLY UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N E C AND LOCAL CODES TO RECALL THE LAST 6 FAULTS MOST RECENT TO LEAST RECENT DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY N THERMOSTAT INPUTS BIAS AND TERM DIP SWITCHES MUST BE IN ON POSITION RED STATUS LED PROVIDES NETWORK STATUS GREEN RX LED INDICATES NETWORK TRAFFIC USE LEARN BUTTON TO RESET NETWORK DISCARD CONNECTOR PL1 WHEN I
6. C 3 AVPTC183016 AVPTC313716 AVPTC426016 BlowerWheel Diameter Width Ps 59 1058 Lineset Connection Size J T Liquid Suction Electrical Data o BlowerMotor o FA 390 520 690 BLOWER PERFORMANCE DATA Speed Selection Dip Switches Cool Adjust Selection Selection Switches Switches Ta OFF ow oFF ow TO SET AIRFLOW 1 Select appropriate model from Cooling Heat Pump Airflow Table Based on desired Airflow for your application select corresponding tap A B C or D Set dip switches 1 amp 2 to the appropriate ON OFF positions 2 Select appropriate Airflow adjustment factor for application 0 10 10 Set dip switches 3 amp 4 to the appropriate ON OFF positions 3 If installed with Heater Kit Using Electric Heat Airflow Table set dip switches 9 10 and 11 to the appropriate ON OFF positions based on Heater kit installed If installed without Heater Kit Ensure dip switches 9 10 and 11 are set to a valid heater kit selection Example The only valid heater kits for AVPTC183014 applications are 3 5 6 8 and 10 KW Failure to do so will result in a Heater Kit error code TO SET COMFORT MODE Select desired Comfort Mode profile see profiles above Set switches 5 and 6 to the appropriate ON OFF positions Profile Selection Switches Sonun s 6 A 60sey1007 OFF B 30sec 50 60 100 OF
7. NSTALLING OPTIONAL HEAT KIT 0140A00039 D Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring 10
8. RNING The unit MUST have an uninterrupted unbroken electrical ground to minimize the possibility of per sonal injury if an electrical fault should occur The electrical ground circuit may consist of an appro priately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel Other methods of ground ing are permitted if performed in accordance with the National Electric Code NEC American Na tional Standards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 Failure to observe this warning can result in electrical shock that can cause personal injury or death A WARNING If this appliance is installed in an enclosed area such as a garage or utility room with any carbon monoxide CO producing appliance i e automo bile furnace water heaters etc ensure the area is properly ventilated AIR HANDLERS See Air Handler Specification Sheet for Proper Combinations ALL AIR HANDLERS USE DIRECT DRIVE MO TORS POWER SUPPLY IS 220 240 V 60 HZ 1 PHASE Installation Before installing this appliance insure that it is properly sized and adequate power is available This appliance can be installed in the vertical position with out modification The horizontal left and downflow positions require product modification and ins
9. mp Downflow Applications 1830 1 1 2 2 1 2 Tons 3137 2 1 2 3 Tons 4260 3 1 2 5 Tons All Airhandlers use DIRECT DRIVE MOTORS Power supply is AC 208 230v 60 hz 1 phase HIGH VOLTAGE A WARNING Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Installation and repair of this unit l A WARNING Pa ei dg A WARNING should be performed ONLY by in arising from improper service or service procedures If dividuals meeting at a minimum you install or perform service on this unit you assume the requirements of an entry level t chnician responsibility for any personal injury or property damage Hed by Air Conditioning Heating Refrigeration which may result Many jurisdictions require a license to Institute AHRI Attempting to instan Or repair this install or service heating and air conditioning equipment without such background may result product damage personal injury or death PRODUCT IDENTIFICATION The model number is used for positive identification of component parts used in manufacturing Please use this number when requesting service or parts information AVPTC183014 AVPTC313714 AVPTC426014 A WARNING The United States Environmental Protection Agency EPA has issued various regulations re garding the introduction and dis
10. posal of refrigerants introduced into this unit Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local EPA office Do not connect or use any device WARNING frat 1s nor design ceri d WARNING To prevent the of property A that is not design certified by 4 WARNING damage personal injury or death Goodman for use with this unit do not store combustible materials or use gasoline or Serlous property damage personal injury reduced unit other flammable liquids or vapors in the vicinity of this performance and or hazardous conditions may result appliance from the use of such non approved devices PRODUCT DESIGN WARNING When installing or servicing this equipment safety clothing including hand and eye protection is strongly advised If installing this equipment in an area that has special safety requirements hard hats etc observe these requirements To protect the unit when brazing close to the painted surfaces the use of a quenching cloth is strongly advised to prevent scorching or marring of the equipment fin ish A warnine HIGH VOLTAGE Disconnect ALL power before servicing or installling this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death WA
11. tructions for these field conversions can be found inthe AVPTC installation instruction manual This product is designed for zero inches 0 inches clear ance however adequate access for service or replacement must be considered without removing permanent structure This unit can be installed on a platform when deemed neces sary In an attic installation a secondary drain pan must be pro vided by the installer and placed under the entire unit with a separate drain line properly sloped and terminated in an area visible to the owner This secondary drain pan is required in the event that there is a leak or main drain blockage Closed cell insulation should be applied to the drain lines in uncondi tioned spaces where sweating may occur Appliances installed in garages warehouses or other areas where they may be subjected to mechanical damage must be suitably guarded against such damage by installing be hind protective barriers being elevated or located out of the normal path of vehicles When installed on a base the base must also be protected by similar means Heating and cooling equipment located in garages which may generate a glow spark or flame capable of igniting flam mable vapors must be installed with the ignition source at least 18 46cm above the floor level When more than one appliance is installed in a building it shall be permanently identified as to the area or space ser viced by the equipment PRODUCT DESIGN
Download Pdf Manuals
Related Search
Related Contents
Benutzerinformation Winkelfunktion Software Copyright © All rights reserved.
Failed to retrieve file