        Model 8702 DP-CALC Micromanometer Operation and Service
         Contents
1.    Ventilation Testing Balancing    Model 8702  DP CaLc     Micromanometer    Operation and Service Manual    1980260  Revision F  July 2006       Model 8702  DP CaLc     Micromanometer    Operation and Service Manual    1980260  Revision F    July 2006  U S  INTERNATIONAL  Sales and Sales and  Customer Service  Customer Service    800  874 2811  001 651  490 2811   651  490 2811   651  490 3824  001 651  490 3824  SHIP MAIL TO  E mail address   TSI Incorporated answers tsi com  500 Cardigan Road Website     Shoreview  MN 55126 3996 USA www tsi com    TSI       Copyright    TSI Incorporated   August 2000 2006   All rights reserved     Address  TSI Incorporated   500 Cardigan Road   Shoreview  MN 55126    USA    Fax No    651  490 3824    LIMITATION OF WARRANTY AND LIABILITY  Seller warrants  the goods sold hereunder  under normal use and service as described in  the operator s manual  shall be free from defects in workmanship and  material for twenty four  24  months  or the length of time specified in  the operator s manual  from the date of shipment to the customer  This  warranty period is inclusive of any statutory warranty  This limited  warranty is subject to the following exclusions    a  Hot wire or hot film sensors used with research anemometers  and  certain other components when indicated in specifications  are  warranted for 90 days from the date of shipment    b  Parts repaired or replaced as a result of repair services are  warranted to be free from defects in w
2.  can store  individual readings and compute the average of  these readings     Keypad Functions   When pressing the keys on the front panel  the  DP CALC will beep to confirm the function  If you  press a key and the DP CALC does not beep  then  the DP CALC does not allow that function during  the selected mode  The beep function can be  disabled by changing of the internal DIP switch     refer to Appendix B      ON OFF Key  Use the ON OFF key to turn the DP CALC on and  off  When the instrument is first turned on it goes  through a preprogrammed power up sequence that  includes an internal self check  First  all  displayable items will appear for a three seconds  If  a problem is detected  the display will light    SErr     for one second and then    CAL    to indicate that it  should be returned for servicing and calibration   Operation 5    After completing the internal self check  the  approximate percentage of battery life remaining  will be displayed  This feature is accurate for  alkaline batteries only  When the battery voltage  becomes very low     LO    appears on the display     Pressure Key   Press the PRESSURE key to display differential  pressure measurements  the DP CALc will  automatically start in pressure mode   The pressure  will be displayed in inches H20  mm Hg  or Pa  depending on the setting of DIP switches  3 and  4     refer to Appendix B      To measure pressure  tubing must be connected to  the pressure ports on the top back of the unit   Connect th
3.  goods returned under  warranty to Seller s factory shall be at Buyer s risk of loss  and will be  returned  if at all  at Seller s risk of loss     Buyer and all users are deemed to have accepted this LIMITATION OF  WARRANTY AND LIABILITY  which contains the complete and  exclusive limited warranty of Seller  This LIMITATION OF  WARRANTY AND LIABILITY may not be amended  modified or its  terms waived  except by writing signed by an Officer of Seller     Service Policy   Knowing that inoperative or defective instruments are as detrimental to  TSI as they are to our customers  our service policy is designed to give  prompt attention to any problems  If any malfunction is discovered   please contact your nearest sales office or representative  or call TSI s  Customer Service department at  800  874 2811  USA  and  001 651   490 2811   International              150  9001 2000      For current information  www tsi com    CONTENTS    Chapters  1  Unpacking and Parts Identification      1  2  Setting UP     ooooooocccnnnnniccnnnociccnnnaniccnnnnno 3  Supplying Power to the DP CALC             3  Installing the Batteries                         3  Using the Optional AC Adapter            3  Selecting the Display Units                      4  Connecting the Optional Portable  Printen vesie heera ae aee eaae A Ta 4  3  OperatioON     iii 5  OVEE Wii doi 5  Keypad Functions   oooocccccconociccconancnnncnnanos 5  ON OFF  Keys  iii 5  Pressure  Key        4eH iin 6  Zeroing Pressure    
4.  measuring mode  You can  later return to any mode and add additional  values to the already stored values     Average Key   Press the AVERAGE key to display the  average of the stored values of the current  operating mode  The message    AVERAGE     will appear along with a number  between 1  and 255  indicating how many stored values  are in the memory buffer  The average value is  then displayed for one second  To keep  displaying the average value  press and hold  the AVERAGE key  You can store additional  values after the AVERAGE key has been  pressed  The next time the AVERAGE key is  pressed  the additional values are averaged  with those already accumulated     Operation 9    Clear Key   Press the CLEAR key to erase the stored value  in the buffer of the currently active function   Pushing the CLEAR key in one function will  not affect the value stored in the other buffer   For example  pushing CLEAR while  measuring velocity will not affect the values  stored for pressure     Arrow Keys   The arrow keys are used for field calibration only   For details on field calibration contact TSI for a  copy of Application Note TI 112     Printer Port   While pressing the SAMPLE  AVERAGE or  CLEAR key the data is automatically transmitted to  the printer port  If you have the Portable Printer  connected  the readings will be printed     Press the PRINT key to print the value shown on  the display  To print out the averages of the stored  pressures and velocities  press and hold 
5. 7  Velocity Key        useeesnenennennnnneennnen 7  Time Constant Key    7  Using the Clear  Sample  and Average  Function  teten ren 8  Sample KEY ora ETEA 8  Average Koy ecese en 9  Clear oia AE 10  Arrow Keys onne dan 10    Printer PO ae aerala aaaea sia 10    Appendices  A  Specifications                                       B  DIP Switch Settings                                U S   800  874 281 1  651  490 2811  Fax   651  490 3824    International  001 651  490 2811  Fax   001 651  490 3824    Chapter 1    Unpacking and Parts  Identification    Carefully unpack the instrument and accessories  from the shipping container  Check the individual  parts against the list of components in Table 1  If  any are missing or damaged  notify TSI or your  local distributor immediately     Table 1  List of Components    AC Adapter  Optional     115 V  NEMA 5 2613033  230 V  European  CEE 7 16 2613078  230 V  Great Britian 800169   240 V  Australian 2613105    Operation and Service Manual   1980260       Parts Identification          Figure 1 1  DP CALc    1  Keypad   2  Display   3  Pressure Measurement Ports  4  RS 232 Printer Port   5  Battery Access Cover    2 Chapter 1    Chapter 2    Setting Up    Supplying Power to the DP CALc  The DP CALC can be powered in one of two ways   four size AA batteries or the optional AC Adapter     Installing the Batteries   Insert four AA batteries as indicated by the  diagram located on the inside of the battery  compartment  TSI ships the unit 
6. To display pressure in Pa or mm Hg  DIP  switch  3 must be in the ON position     18 Appendix B                   TSI                 TSI Incorporated  500 Cardigan Road  Shoreview  MN 55126 U S A   Tel   1 651 490 2811 Toll Free  1 800 874 2811    E mail  answers tsi com  For current information  www tsi com    P N 1980260 Rev F Copyright O 2006 by TSI Incorporated  Printed in U S A     
7. city    TIME CONSTANT  Values  1 5  10  15  or 20 seconds    15    POWER REQUIREMENTS     Batteries  Four AA size Alkaline or NiCd  rechargeable   AC adapter  7 VDC nominal  300 mA   Approx  battery life  40 hours  Alkaline   15 hours   NiCd    PHYSICAL    External dimensions  4 0 in x 6 6 in x 1 5 in     102 mm x 168 mm x 38 mm   Weight  with batteries   0 76 Ib   0 35 kg     Display  4 digit LCD  0 6 in  15 mm   digit height   PRINTER INTERFACE    Type  Serial   BAUD rate  1200    2 Accuracy is a function of converting pressure to  velocity  Conversion accuracy improves when actual  pressure values increase    1 Pressure velocity measurements are not  recommended below 1 000 ft min  5 0 m s  and are  best suited to velocities over 2 000 ft min  10 0 m s      16 Appendix A    Appendix B    DIP Switch Settings    To access the DIP switches  remove the batteries  from the battery compartment  On the inside of the  battery compartment  there is a window with eight  DIP switches  The table on the following page  shows the functions for each switch     Caution  Make certain that power is turned off  before changing DIP switch settings           Figure B   1  DIP Switch Location    17    1 Velocity ft min  amp  m s  ft min    3 Pressure in  H O Pa and mm  Hg      4  Pressure   Pa  mmHg      A a comma  Calibration   Calibration  Disabled Enabled      8  Reserved   Reserved Reserved    The ON position is away from the batteries and the  OFF position is toward the batteries        e 
8. dated every  second  however  the reading displayed is the  average reading over the last time constant period   For example  if the current time constant is set to  10 seconds  the display will show readings  averaged over the previous 10 seconds  updated  every second  This is also called a 10 second     moving average        Using the Clear  Sample  and Average  Functions   The DP CALC has the ability to compute the  average of a number of individual stored readings   Every time the SAMPLE key is pressed  the  currently displayed reading is added to a storage  buffer  When the AVERAGE key is pressed  the  readings in the storage buffer are divided by the  number of stored readings to get the average  The  CLEAR key is used to clear out the storage buffer  in order to start taking a new average  When the  DP CALC is turned off  all values stored in the  buffers are cleared     Sample Key   Press the SAMPLE key to store the currently  displayed measurement  The display will show     SAMPLE    for one time constant and a  number indicating the number of stored data    8 Chapter 3    points that are in memory for about one  second  and then the recorded value will be  displayed     The individual stored values can not be  recalled  Only the average of the stored values  can be recalled  There are two different store  buffers  one for pressure and one for velocity   You can switch between measuring modes and  store data without affecting data stored in the  buffer for the other
9. e other ends of the tubing to the  measurement device or pressure source  with the  more positive pressure connected to the port  marked         and the more negative pressure  connected to the port marked          When the  pressure source is connected the same way the  pressure ports are marked  the meter will display a  positive number     6 Chapter 3    Zeroing Pressure   If the zero reading of pressure has drifted  the  pressure function can be easily re zeroed  To  reset the zero  first make sure that both  pressure ports are exposed to ambient pressure     Press and hold the PRESSURE key down for  at least three seconds  The DP CALC will beep  and the display will show    0 in  H O    or  whatever units have been selected   When the  pressure key is released the pressure will be re   zeroed     Velocity Key   Press the VELOCITY key to display velocity  The  velocity will be displayed in ft min or m s  depending on the setting of DIP switch  1  refer to  Appendix B      Time Constant Key   Momentarily press and release the TIME  CONSTANT key to view the current time   constant  To change the time constant  press and  hold the key  The available time constant choices   1  5  10  15 and 20 seconds  will sequence on the  display  When the desired value is displayed  immediately release the key  The DP CALC will  always reset the time constant to 1 second when  turned off     Operation 7    The time constant is actually an averaging period   The DP CALC display is always up
10. ead Replace the  batteries batteries or plug  in the AC    adapter   Dirty battery Clean the battery  The DP CALC_   Return to factory    has detected an   for service   internal fault       13    Possible Corrective  Symptom Causes Action    Display Low battery Replace or  reads  LO    charge recharge  batteries   Replace with the  correct AC  adapter   Low AC line Correct the AC  voltage line voltage or  use batteries   contacts contacts     You are trying   Read or record    to enter more the average  clear   than 255 the storage   readings register and  proceed    The pressure or   Use an alternate   velocity is too   measurement   high method     WARNING     The pressure sensor is protected from  damage for up to 7 psi  48 kPa or   360 mm Hg   At higher pressures it can  burst        14 Chapter 5    Appendix A    Specifications    Specifications are subject to change without notice   Specifications in parentheses    indicate metric  equivalents     PRESSURE    Range   5 to  15 in  H20   1245 to 3735  Pa   9 3 to 28 0 mm Hg    Accuracy  1  of reading   0 005 in  H O    1 Pa   0 01 mm Hg    Resolution  0 001 in  H20  1 Pa  0 01 mm  Hg    VELOCITY    Range  250 to 15 500 ft min   1 27 to 78 74 m s    Accuracy     1 5  of reading at 2 000 ft min     1 5  of reading at 10 00 m s     INSTRUMENT TEMPERATURE RANGE   Operating range  32 to 158  F  0 to 70  C    Storage range   40 to 185  F  40 to 85  C      AVERAGING CAPABILITY   Range  Up to 255 values each of  pressure and velo
11. orkmanship and material   under normal use  for 90 days from the date of shipment    c  Seller does not provide any warranty on finished goods  manufactured by others or on any fuses  batteries or other  consumable materials  Only the original manufacturer s warranty  applies    d  Unless specifically authorized in a separate writing by Seller   Seller makes no warranty with respect to  and shall have no  liability in connection with  goods which are incorporated into  other products or equipment  or which are modified by any person  other than Seller        The foregoing is IN LIEU OF all other warranties and is subject to the  LIMITATIONS stated herein  NO OTHER EXPRESS OR IMPLIED  WARRANTY OF FITNESS FOR PARTICULAR PURPOSE OR  MERCHANTABILITY IS MADE     TO THE EXTENT PERMITTED BY LAW  THE EXCLUSIVE  REMEDY OF THE USER OR BUYER  AND THE LIMIT OF  SELLER S LIABILITY FOR ANY AND ALL LOSSES  INJURIES  OR  DAMAGES CONCERNING THE GOODS  INCLUDING CLAIMS  BASED ON CONTRACT  NEGLIGENCE  TORT  STRICT LIABILITY    OR OTHERWISE  SHALL BE THE RETURN OF GOODS TO  SELLER AND THE REFUND OF THE PURCHASE PRICE  OR  AT  THE OPTION OF SELLER  THE REPAIR OR REPLACEMENT OF  THE GOODS  IN NO EVENT SHALL SELLER BE LIABLE FOR ANY  SPECIAL  CONSEQUENTIAL OR INCIDENTAL DAMAGES   SELLER SHALL NOT BE RESPONSIBLE FOR INSTALLATION   DISMANTLING OR REINSTALLATION COSTS OR CHARGES  No  Action  regardless of form  may be brought against Seller more than 12  months after a cause of action has accrued  The
12. the PRINT  key until the display counts down to zero  Release  the PRINT key while    0    is displayed to print     10 Chapter 3    Chapter 4    Maintenance    The DP CALC requires very little maintenance to  keep it performing well     Recalibration   To maintain a high degree of accuracy in your  measurements  we recommend that you return your  DP CALC to TSI for annual recalibration  For a  reasonable fee  we will quickly recalibrate the unit  and return it to you in    as new    working condition  along with a Certificate of Calibration and NIST  traceability  This    annual checkup    helps ensure  that the DP CALC is always in good working  condition  it is especially important in applications  where strict calibration records must be maintained     Cases   If the instrument case or storage case needs  cleaning  wipe it off with a soft cloth and isopropyl  alcohol or a mild detergent  Never immerse the  DP CALC     Storage   When storing the DP CALC for more than a month   removing the batteries is recommended  This  prevents damage due to battery leakage     11    12    Chapter 4    Chapter 5    Troubleshooting    Table 3 lists the symptoms  possible causes  and  recommended solutions for common problems  encountered with the DP CALC  If your symptom  is not listed  or if none of the solutions solves your  problem  please contact TSI     Table 3  Troubleshooting the DP CALC   Symptom  canes  Acton  Symptom Causes Action  No display   Unit not Switch on the    Low or d
13. with alkaline  batteries  The DP CALC is designed to operate  with either alkaline or NiCd rechargeable  batteries  Carbon zinc batteries are not  recommended because of the danger of battery  acid leakage  Typical battery life at 20   C is  40 hours for alkaline batteries  or 15 for NiCd  batteries     Using the Optional AC Adapter   The optional AC adapter allows you to power  the DP CALC from a wall outlet  When using  the AC adapter  the batteries  if installed  will  be bypassed  The AC adapter is not a battery  charger     Setting Up 3    Selecting the Display Units   The DP CALLC is capable of displaying the  measured values in several different measurement  units  as shown in Table 2     Table 2  Choices of Measurement Units    Velocity    in  H O ft min    mm Hg m s  Pa       If you wish to change the display units on your  DP CALC  see Appendix B  DIP Switch Settings        Connecting the Optional Portable Printer  To connect the printer to the DP CALC  locate the  Printer Interface cable  supplied with the optional  printer  and connect the 9 pin end labeled     PRINTER    to the printer and the other end to the  data port of the DP CALC  Always turn the DP   CALC on BEFORE the printer  If the printer prints    random characters  reset it by turning it off and    then on again  If necessary  refer to the Portable  Printer Manual     4 Chapter 2    Chapter 3    Operation    Overview   The model 8702 DP CALC measures differential  pressure and calculates velocity  It
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
FLIP-XC Series I/M English  Kathrein VCA 20  User Manual  Studio Auto Clam Junior Mode d`emploi    Almanach bio du jardinier - édition 2011  Teacher`s Guide  HYDRIM® M2  Page 1 l: GSR 1 4,4 VES-2 3... 7 8...12 13...17 18...22 23...27 28...32  Catalogo Tifcom generato il    Copyright © All rights reserved. 