PAN200 Series Positive and Negative Duct Accreditation

image

Contents

1. Leakage class P Pressure inwg Leakage Testing Standards Highlights 29 26 Round Duct Allowable Air Leakage Leakage Rate cfm 100 ft2 0 2 4 6 8 10 12 14 Static Pressure in wg Leakage Class 12 Leakage Class 6 Leakage Class 3 Figure 13 Allowable Air Duct Leakage from Round Ducts per SMACNA Standard Rectangular Duct Allowable Leakage Leakage Rate cfm 100 ft2 0 2 4 6 8 10 12 14 Static Pressure in wg Leakage Class 24 Leakage Class 12 Leakage Class 6 Figure 14 Allowable Air Duct Leakage from Rectangular Ducts per SMACNA Standard The SMACNA standard does not generally require correcting leakage flow rates to standard conditions unless 1 Air temperature lt 40 F or gt 100 F 2 Elevation lt 1500 ft above sea level 3 Duct static pressure lt 20 inwg or gt 20 inwg Appendix B Should one of these conditions not be satisfied then correcting the leakage to standard conditions may be done using one of these formulas I 3 ACFM SCFM 460 T 530 where T actual dry bulb air temperature F moisture is negligible pressure between 20 and 20 inwg ACFM SCFM 0 075 d where d air density from psychrometric chart ACFMe lb dry air minute humid volume ft lb dry air e The SMACNA standard does not specify the information to be reported but instead def
2. 11 Measuring Duct Static Pressure 11 Measuring Duct Leakage Flow 12 Turning on the PAN200 Duct Leakage Tester 12 Using Leakage Test Application in the Model 9565 P 13 Troubleshooting Guide cae e u n eat tue esa diues 16 APPENDIX A SPECIFICATIONS 17 APPENDIX B LEAKAGE TESTING STANDARDS HIGHLIGHTS 21 Standards S DDOrI6SC zn u suyus dress ee tese re ceti ova utl oe ea ous 21 EU Standards sostiene cu tesiate vus aya Qu sie una teu ese PLURES 22 US Standards u u uuu uuu uuu uns Md qu dint cab Nus E OR hi 25 APPENDIX C TYPICAL SETUP 29 APPENDIX D PROCEDURE FOR USING SMOKE PELLETS IN LEAKAGE TESTERS etes eur pera rx cient ees 31 This page intentionally left blank Chapter 1 Unpacking and Parts Identification Carefully unpack the PANDA system and instrument cases from the shipping container Check the individual parts against the list of components below If anything is missing or damaged notify TSI immediately The PANDA system consists of the following Part Number Reference Picture Low flow nozzle 6002598 Primary duct adapter 6002638 spigot plus rubber bung to fit to test duct Cam lock primary spigot 6002607 to connect flexi duct to PANDA 4 in 100 mm 6002683 adj
3. E mail tsifrance tsi com Website www tsiinc fr Germany Tel 49 241 523030 E mail tsigmbh tsi com Website www tsiinc de India Tel 91 80 41132470 E mail tsi india tsi com China Tel 86 10 8251 6588 E mail tsibeijing tsi com q b Singapore Tel 65 6595 6388 E mail tsi singapore tsi com Contact your local TSI Distributor or visit our website www tsi com for more detailed specifications P N 6005007 Rev A Copyright 2012 by TSI Incorporated Printed in U S A
4. when the power cord is plugged in Position the Fan Control switch to the RUN position to energize the fan Increase the fan to the desired speed by turning the Fan Speed Controller clockwise To decrease the fan speed turn the Fan Speed controller counter clockwise Chapter 3 CAUTION Press the MENU key to access the menu system on the Model 9565 P Use the A Y keys to highlight the Applications item Press the ENTER key to access the Applications menu Select Leakage Test and press key Select either the EN Standard or SMACNA leakage test Performing a Duct Leakage Test Using Leakage Test Application in the Model 9565 P The Model 5825 and Model 9565 P meters must be zeroed before entering the Leakage Test Application MENU Zero Press Display Setup Settings Flow Setup Actual Std Setup Data Logging Zero CO Applications Calibration Discover Printer APPLICATIONS Draft Rate Heatflow Turbulence Outside Air Leakage Test LEAKAGE TEST EN Standard SMACNA 13 Instrument Operation if EN Standard Test Protocol is Selected 1 Enter key parameters LEAKAGE TEST a Surface Area of ductwork Surface Area section to be tested Static Pressure b Static Pressure of test as dos Tightness Class measured by Model 5825 Test Length micromanometer Run Test c Flow Device as Nozzle or Flow Grid d Leakage class as A B C or D Note that tests with negative pressures must be
5. 0 Class m s m s 1000 1000 1000 Class D ductwork is only for special apparatus e ENI2237 circular ductwork Air Air leakage Static Pressure Limit ps Tightness limit fmax Pa Class m s m 1000 1000 1000 1000 Class D ductwork is only for special apparatus 22 Appendix B Eurovent 2 2 Air Tightness For Installed Duct Testing Air Tightness Air leakage limit fmax Class m s m 1000 1000 1000 DW 143 A Practical Guide to Ductwork Leakage Testing Static Pressure Duct Limit Maximum Air leakage Pressure Air Velocity limits Class Pa Pa m s l s m Class A pressure Class B High pressure 2000 7 0 003 p Class C Leakage Rate l s m2 0 500 1000 1500 2000 2500 Static Pressure Pa Class Class A Class B Figure 12 Allowable Air Leakage Rates from DW 143 Leakage Testing Standards Highlights 23 24 The measured leakage flow rates shall be corrected if the temperature and or barometric pressure are different from standard conditions 20 C and 101 325 Pa as follows 293 D de Sees Saga 7 arias where q corrected flow leakage rate Qmeasured Measured flow leakage rate t measured temperature C p measured barometric pressure Pa The test report shall give the following general information of the test performed o Date and place o Test personnel and witness o Test equipment including pressuring mean
6. ENERGY AND COMFORT Ventilation Testing Positive and Negative Duct Accreditation PANDA System Model PAN200 Series Operation and Service Manual q b SCIENCE INNOVATION Copyright TSI Incorporated 2012 All rights reserved Address TSI Incorporated 500 Cardigan Road Shoreview MN 55126 USA Fax No 651 490 3824 LIMITATION OF WARRANTY AND LIABILITY effective June 2011 For country specific terms and conditions outside of the USA please visit www tsi com Seller warrants the goods sold hereunder under normal use and service as described in the operator s manual shall be free from defects in workmanship and material for 24 months or if less the length of time specified in the operator s manual from the date of shipment to the customer This warranty period is inclusive of any statutory warranty This limited warranty is subject to the following exclusions and exceptions a Hot wire or hot film sensors used with research anemometers and certain other components when indicated in specifications are warranted for 90 days from the date of shipment b Pumps are warranted for hours of operation as set forth in product or operator s manuals c Parts repaired or replaced as a result of repair services are warranted to be free from defects in workmanship and material under normal use for 90 days from the date of shipment d Seller does not provide any warranty on finished goods manufactured by others or on
7. HE PURCHASE PRICE OF THE SOFTWARE IN NO EVENT SHALL SELLER BE LIABLE FOR LOST PROFITS OR ANY SPECIAL CONSEQUENTIAL OR INCIDENTAL DAMAGES SELLER SHALL NOT BE RESPONSIBLE FOR INSTALLATION DISMANTLING OR REINSTALLATION COSTS OR CHARGES No Action regardless of form may be brought against Seller more than 12 months after a cause of action has accrued The goods returned under warranty to Seller s factory shall be at Buyer s risk of loss and will be returned if at all at Seller s risk of loss Buyer and all users are deemed to have accepted this LIMITATION OF WARRANTY AND LIABILITY which contains the complete and exclusive limited warranty of Seller This LIMITATION OF WARRANTY AND LIABILITY may not be amended modified or its terms waived except by writing signed by an Officer of Seller Service Policy Knowing that inoperative or defective instruments are as detrimental to TSI as they are to our customers our service policy is designed to give prompt attention to any problems If any malfunction is discovered please contact your nearest sales office or representative or call Customer Service department at 44 0 149 4 459200 UK 800 874 2811 USA or 1 651 490 2811 International CONTENTS CHAPTER 1 UNPACKING AND PARTS IDENTIFICATION 1 CHAPTER 2 PREPARING PAN200 SYSTEM FOR AIR DUCT LEAK TESTING 5 CHAPTER 3 PERFORMING A DUCT LEAKAGE TEST
8. age test 2 Increase the blower speed until the desired static pressure is achieved 3 When the static pressure has stabilized select Run Test and press lt 4 4 The display will show the readings on the right Leakage Factor and Leak Rate will update in real time while other parameters will remain constant LEAKAGE TEST Surface Area Static Pressure Flow Device Leakage Class Test Length Run Test LEAKAGE TEST Leakage Factor x xx Leak Limit X XX Leak Rate X XX Status OK Flow Device Flow Grid Baro Pressure 20 20 Temperature 20 C Time 9 55 Standard TestXXX Sample 0 Sample Saved 1 Stop Save Print If the Leak Factor and Leak Rate are sufficiently stable press the START soft key or the key to begin the leak test Pressing the ESC key will exit back to the previous screen 5 After the leak test is complete the Model 9565 P will prompt you to press the SAVE or PRINT soft key You can also press the ESC key here to back out to the previous screen without saving the data After completing leakage testing for a section of duct you can move on to the next section Performing a Duct Leakage Test 15 Troubleshooting Guide Symptom Recommended Action Fan motor will not run e Check the power connection e Circuit Breaker may have tripped Static pressure reading on 5825 e Check the connections IS Zero Static pressure reading on 5825 e Leakage rate is too high is too low Check fo
9. any fuses batteries or other consumable materials Only the original manufacturer s warranty applies e Unless specifically authorized in a separate writing by Seller Seller makes no warranty with respect to and shall have no liability in connection with goods which are incorporated into other products or equipment or which are modified by any person other than Seller The foregoing is IN LIEU OF all other warranties and is subject to the LIMITATIONS stated herein NO OTHER EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR PARTICULAR PURPOSE OR MERCHANT ABILITY IS MADE WITH RESPECT TO SELLER S BREACH OF THE IMPLIED WARRANTY AGAINST INFRINGEMENT SAID WARRANTY IS LIMITED TO CLAIMS OF DIRECT INFRINGEMENT AND EXCLUDES CLAIMS OF CONTRIBUTORY OR INDUCED INFRINGEMENTS BUYER S EXCLUSIVE REMEDY SHALL BE THE RETURN OF THE PURCHASE PRICE DISCOUNTED FOR REASONABLE WEAR AND TEAR OR AT SELLER S OPTION REPLACEMENT OF THE GOODS WITH NON INFRINGING GOODS TO THE EXTENT PERMITTED BY LAW THE EXCLUSIVE REMEDY OF THE USER OR BUYER AND THE LIMIT OF SELLER S LIABILITY FOR ANY AND ALL LOSSES INJURIES OR DAMAGES CONCERNING THE GOODS INCLUDING CLAIMS BASED ON CONTRACT NEGLIGENCE TORT STRICT LIABILITY OR OTHERWISE SHALL BE THE RETURN OF GOODS TO SELLER AND THE REFUND OF THE PURCHASE PRICE OR AT THE OPTION OF SELLER THE REPAIR OR REPLACEMENT OF THE GOODS IN THE CASE OF SOFTWARE SELLER WILL REPAIR OR REPLACE DEFECTIVE SOFTWARE OR IF UNABLE TO DO SO WILL REFUND T
10. ard Description BS EN 12237 2003 EU Ventilation for buildings Ductwork Strength and leakage of circular sheet metal ducts BS EN 1507 2006 EU Ventilation for buildings Sheet metal air ducts with rectangular section Requirements for strength and leakage DW 143 EU HVAC A practical guide to Ductwork leakage testing SMACNA HVAC Air U Duct construction leakage Duct Leakage Test manual First edition 1985 classification expected leakage rates for sealed and unsealed ductwork duct leakage test procedures recommendations on use of leakage testing types of test apparatus and test setup and sample leakage analysis US or EU Based Eurovent 2 2 EU Air leakage rate in sheet metal air distribution systems TSI has made every effort to accurately reflect the standards referenced Please refer to the actual standards for more detailed information and to make the best interpretation of each statement 21 The scope of the standards listed above includes many items other than duct leakage This summary however is limited to duct leakage testing EU Standards Ductwork classification and maximum air leakage Note that EN1507 EN12237 Eurovent 2 2 and DW 143 all have the same formula to determine fmax the Air Leakage Limit although DW 143 uses units of l s m whereas others use m s m e EN 1507 rectangular ductwork Static Pressure Limit ps Pa Tightness Limit fmax pressure class s Negative 100
11. ct leakage tester by For positive pressure high flow testing remove the low flow nozzle if it is installed Then connect the grey cast aluminum cam lock connector to the outlet side of the blower per Figure 6 Close both cam lock Fan Cam Lock arms at the same time Outlet Connector to ensure proper fit Figure 6 Positive Pressure Connect the free end of High Flow Set Up the 16 ft 5 m silicone tube to the pressure tap marked DUCT PRESSURE P3 on the black square box Finally verify that the FLOW GRID MODE pressure taps on the inlet tubes are connected to the FLOW GRID pressure taps 1 e P1 to P1 and P2 to P2 For positive pressure low flow testing add Fan Inlet the low flow nozzle to the blower inlet if it is not installed per Figure 7 Then connect the grey cast aluminum cam lock connector to the outlet side of the blower per Figure 6 Low Flow Nozzle Close both cam lock arms at the same time Figure 7 Positive Pressure to ensure proper fit Low Flow Set Up Connect the free end of the 16 ft 5 m silicone tube to the pressure tap marked DUCT PRESSURE P3 on the black square box Chapter 2 c For negative pressure high flow testing remove the low flow nozzle if it 1s installed Then connect the grey cast aluminum cam lock connector to the inlet side of the blower per Figure 8 Close Fai Cam Lock both cam lock arms at Inlet Connector the same time to ensure p
12. d to be followed Air tightness leakage class to be achieved Amount of ductwork to be tested such as the complete system or a Statistical sample 1 Select the section of the ductwork to be tested 2 Calculate the surface area of the ductwork of the section to be tested 3 Temporarily seal the all openings of the ductwork except one which will be connected to the PAN200 duct leakage tester 4 Position the PAN200 unit as close to the remaining opening in the ductwork as possible to minimize the flexible tubing needed Minimize bends in the flexible tubing to reduce the pressure loss giving the best performance 5 Make sure the Fan Control Switch on the Fan Speed Controller is in the OFF position and the multi turn Fan Speed Control potentiometer is fully turned counter clockwise using the pictures of the VFD in Figure as a reference Plug the cord into the PANDA unit as shown in Figure 2 and Figure 3 Then connect the other end of the cord to a suitable electrical supply CAUTION Remove the power cord from the PANDA duct leakage tester before tilting it to the vertical position to avoid damaging the cord Fan Speed Control GENESIS Fan Control Switch On Off Switch 110 V 230 V Figure 1 110V and 230V Fan Speed Controllers Note The control pad on the Fan Speed Controller has been disabled Figure 2 Receptacle for Figure 3 Connected Power Cord Power Cord 6 Chapter 2 6 10 Preparin
13. del PAN221 110 110 to 120 V 1 Phase 50 60 Hz 16A Weight 71 kg 157 lbs Dimensions L x W x H 1 180 mm x 660 mm x 510 mm 44 5 in x 26 in x 20 in 9565 P and 5825 See specification sheets for details on individual instruments Model instruments included Model instruments NOT included Specifications subject to change without notice Panda Fan Performance Graph metric units G a o s gt N vn v s a vn 100 150 Volume Flow I s 18 Appendix A Panda Fan Performance Graph imperial units 11 10 9 8 7 bb 3 E 3 a a 9 5 de o a 4 3 2 1 0 0 50 100 150 200 25 00 Volume Flow CFM Specifications 19 20 This page intentionally left blank Appendix A Appendix B Leakage Testing Standards Highlights Different standards are used throughout the world to specify duct air tightness and leakage requirements The PAN200 duct leakage test system has a duct leakage application to automatically compare the actual leakage flow with the maximum allowed leakage flow for EN and SMACNA standards Field technicians can also use the duct leakage application to determine actual leakage flow and manually compare it to maximum leakage from another standard The PAN200duct leakage test system cannot determine the appropriate leakage classification for a given duct Standards Supported Stand
14. ers to project documents However the SMACNA standard does include a sample test report that includes o Test date and place o Test personnel and witness o Building and project reference o Duct section tested o Specified leakage class test pressure and duct construction pressure class o Measurements of Ductwork surface area Leakage flow and calculations required to determine leakage flow Leakage Testing Standards Highlights 27 28 This page intentionally left blank Appendix B Appendix C Typical Setup sn JO uoissiuued eunjeuBis urejqo pue 1 us S9 uo sile p p 0984 g ule qo yuowqonp apisul peoejd 3ejjeg exouis G Buipeai yo uo pue ainssaid 1s Ajddeay 2 s qqnq O1 Z 0 MOJJE pue JO Uu9JIAS 9 JO YOO pue SJUIO 1840 quied J8 eM pue deos p 1s 1 Jepun uu ls s s l nuluu G 104 1 s UIEJUIEWy S Syeo e5o djeu ued SZUNSSSId JOAO 0 jou Ged Bye en9 0j euin Mojje KAuesseoeu y je s y p Sjuiof 1940 19M ji uejnonied puey noA Guiuuru j884 SNINSVM ejeJ eBexeo yo peas e qipne eq pinous syeaj Buiuunu Bu 3S83 uj u lsi1 Z eunsseud 1591102 0 Bu 1s jsn pe pue o uuoo Z sjuiof ynouyjip pue sBuiuedo sseooe syuejq je 300 L Jeeus 358 ejedaJg SXV31 ANIJ OL MOH 1S31 do 39N3N03S gt Es JeAOWAI JO osea 2 JOJ SS999 y m eoejd I j jueiueAuoo je yuejg E s9 jepun YJOMJONP U 0 poeuip p o uuoo eq pinoys eJ
15. g PAN200 System for Air Duct Leak Testing Fit the primary duct adapter spigot black sheet metal with rubber bung to one end of the 4 in 100 mm diameter flexi tube Make an air tight seal using one of the over lock straps and lever locking cam provided as shown in Figure 4 Adjust the fit of the over lock strap with a screwdriver Securely attach the black i primary duct adapter ji AL spigot flexi tube assembly to Figure A Fec D CIWGIK the opening on the ductwork to Connected to Primary Adapter i NA Jue XT TAM HET SGN be pressure tested Spigot Bung not shown If the static pressure tap on the black Primary Duct Adapter is P hsa open to the duct connect the AT 16 ft 5 m long blue silicone tube to it as shown in Figure 5 If the static pressure tap on the black Primary Duct Adapter is not open to the duct drill a 4 mm hole in the duct and insert about 6 inches 10 mm of the silicone tube into the es Figure 5 Connecting Pressure duct Seal around the hole with Tubing to Tap on Primary Duct putty Adapter Bung not shown Connect the other end of the 4 in 100 mm flexi tube to the cam lock connector grey cast aluminum without nozzle Make an airtight seal using the other over lock strap and lever locking cam provided Adjust the fit of the over lock strap with a screwdriver Determine if you are going to perform a high or low flow testing and positive or negative testing Set up the du
16. ls download them from TSI s website www tsi com Measuring Duct Static Pressure 1 Turn ON the Model 5825 2 Zero the Model 5825 pressure sensor with both ports open to the atmosphere 3 Connect the port on the Model 5825 to P3 to measure the duct static pressure see Figure 6 4 Leave the port on the Model 5825 open to the atmosphere Note Refer to the Model 5825 Operation and Service Manual for instructions on using data logging to automatically record the duct static pressure Measuring Duct Leakage Flow I Turn ON Model 9565 P Zero the Model 9565 P pressure sensor with both ports open to the atmosphere Connect the Model 9565 P to the PAN200 by connecting the and ports on the Model 9565 P to the P1 and P2 ports located inside the black box of the PAN200as shown in Figure 10 Figure 10 Connecting Instruments to PANDA Tester in High Flow Mode Connect the thermocouple to the Model 9565 P Insert the thermocouple probe into the blower inlet through the hole marked TC1 as shown in Figure 11 Thermocouple Hole Figure 11 Thermocouple Insertion Hole Turning on the PAN200 Duct Leakage Tester I Switch the PANDA unit on a For 230V models position the Mains Power switch of the inverter to the ON position to power the Inverter speed controller The Fan motor is not energized b 110V models do not include a separate power switch The PANDA unit is turned on
17. r leaks using soap bubbles or smoke pallets Required static pressure cannot Alternatively test a smaller be achieved with motor speed section of the ductwork control settings at the maximum Leak Flow on 9565 P shows e Check the pressure tube flashing XXX XX connections to the 9565 P meter e Leak flow is too low Use low flow nozzle adapter 16 Chapter 3 Appendix A Specifications Pressure Measurement 5825 Range 3 735 Pa 15 in W G Resolution 0 1 Pa 0 001 in W G Accuracy 1 of reading 1 Pa 0 005 in W G Actual duct static range 2 500 Pa 10 in W G at Zero Flow Volume Flow Measurement 9565 P Wilson radial flow grid High leakage range 10 to 200 l s 36 to 720 m hr 21 to 424 cfm 15 mm conical inlet Low leakage range 1 to 13 l s nozzle adapter 3 6 to 46 9 m hr 2 to 27 5 cfm Resolution 0 01 l s 0 01 m hr 0 01 cfm AGCOULBOY Sassssctisiust ne etc lass 2 596 of reading 0 01 l s 0 04 m hr 0 02 cfm Temperature Measurement 9565 P K Type thermocouple probe To EN60584 IEC 584 Barometric Pressure Measurement 9565 P Ripe 690 to 1 241 hPa 517 5 to 930 87 mm Hg 20 36 to 36 648 in Hg ACCURACY uya aputa 2 of reading Power Requirements Model PAN221 220 to 240 V 1 Phase 50 60 Hz 10A Mo
18. roper fit Figure 8 Negative Pressure High Flow Set Up Connect the free end of the 16 ft 5 m silicone tube to pressure tap marked DUCT PRESSURE P4 on the black square box Finally verify that the FLOW GRID MODE pressure taps on the inlet tubes are connected to the FLOW GRID pressure taps 1 e P1 to P1 and P2 to P2 d For negative pressure vow Flow low flow testing add Nozzle the low flow nozzle to the blower inlet if it is not installed Then connect the grey cast aluminum cam lock connector to the low flow nozzle per Figure 9 Close both cam lock Fan Cam Lock arms at the same time Inlet Connector to ensure proper fit Figure 9 Negative Pressure Connect the free end of Low Flow Set Up the 16 ft 5 m silicone tube to pressure tap marked DUCT PRESSURE P4 on the black square box Preparing PAN200 System for Air Duct Leak Testing This page intentionally left blank Chapter 2 Chapter 3 Performing a Duct Leakage Test The PAN200 duct leakage test system includes a Model 5825 Micromanometer and a Model 9565 P Ventilation Meter During duct leakage testing the Model 5825 Micromanometer measures the duct static pressure while the Model 9565 P Ventilation Meter measures the airflow rate Refer to the Operation and Service Manuals for the Model 5825 Micromanometer and the Model 9565 P Ventilation Meter to use these instruments in other applications If you do not have the manua
19. s and measuring instruments Air temperature and barometric pressure during the test Building and project reference Design of installed ductwork including dimensions thickness of materials types of stiffening length type of duct tubes and fittings assembly method and distance of hangers supports o Required air tightness class and design operating pressure of the installed ductwork Installer of ductwork Manufacturer of the ductwork Measured values of 1 Ductwork surface area A 2 Total joint length L 3 Test pressure ptest 4 Leakage flow rate q corrected for temperature and barometric pressure 5 Pressurizing time Appendix B o Calculated values of 1 Leakage factor f 2 Air leakage limit fmax according to the formulas given in table above at the measured test pressure Prest o Air tightness class achieved e For tests including several test pressures it is recommended to plot the leakage factors as a function of test pressure in a diagram together with the air leakage limit curve US Standards Ductwork classification and maximum air leakage y do 5 Ac dae Duct Class 2 inwg 4 6 10 inwg Seal Class C B Transverse Joints Seams Sealing Transverse Applicable Joints Only Voimtsand and All Wall Seams Penetrations Leakage Class Rectangular Seg EE a Round Metal Maximum air leakage is then defined as F C p where F Maximum air leakage cfm 100 ft Cr
20. selected as negative tests as indicated by e Test Length or duration of leakage test usually 5 minutes pA Increase the blower speed until LEAKAGE TEST the desired static pressure is Leakage Factor x xx Bene eds Leak Limit X XX 3 When the static pressure has Leak Rate stabilized select Run Test and Status press lt 4 Flow Device Flow Grid Baro Pressure 20 20 4 The display will show the readings on the right Leakage Temperature 20 C Factor and Leak Rate will Time 9 55 update in real time while other Standard TestXXX parameters will remain constant la If the Leakage Factor and Leak Sample Saved 1 Rate are sufficiently stable press the START soft key or the key to begin the leak test Pressing the ESC key will exit back to the previous screen 5 After the leak test is complete the Model 9565 P will prompt you to press the SAVE or PRINT soft key You can also press the ESC key here to back out to the previous screen without saving the data After completing leakage testing for a section of duct you can move on to the next section 14 Chapter 3 Instrument Operation if SMACNA Test Protocol is Selected 1 Enter key parameters a Surface Area of ductwork section to be tested Static Pressure of test as measured by Model 5825 micromanometer Flow Device as Nozzle or Flow Grid Leakage class as a number from 1 to 48 Typical values are 3 6 12 24 or 48 Test Length or duration of leak
21. unsseud ones s inse uu yey Jejeuioueui y w014 qn y eunsseud jonp jo sBuipeai yoauooul s lou PIOAP 0 J9pJO u 1sej pue sBuiddej jueuunujsur yuejq o JequiauiaM spue syeaj ou seu onp ejqixej Sy jeu uedo je yo yuejg t pue pajees 9391105 9Je suonoeuuoo pua ujoq jeu eins eyew pue uunuululuu e 0 ujBue deay X314 sjuiof 9 qissoooeul uM ayes jeroeds exe epe 29 30 This page intentionally left blank Appendix C Appendix D Procedure for Using Smoke Pellets in Leakage Testers As shown in the sketch below a rubber bung is fitted into the hole in the duct adapter which holds the wire coil When a smoke pellet is required to be used remove the bung and fit a pellet into the wire coil as shown in the sketch Light the pellet and immediately plug into the hole in the duct adapter and proceed with the test The pellet should emit dense white smoke for up to a minute ud Duct Pellet Holder Q Smoke Pellet Y ai me i i i i Flexible Ducting Duct Adapter L A A Z A A K 31 32 This page intentionally left blank Appendix D TSI Incorporated 500 Cardigan Road Shoreview MN 55126 U S A USA Tel 1 800 874 2811 E mail answers tsi com Website www tsi com UK Tel 44 149 4 459200 E mail tsiuk tsi com Website www tsiinc co uk France Tel 33 491 118764
22. ustable over lock straps 13 ft 4 m long 6002667 4 in 100 mm plastic flexible duct 20 in 500 mm silicone AFL9020004 tubes red 1 1 2 1 2 Part Number Reference Picture 20 in 500 mm silicone AFL9020005 tubes blue N 16 ft 5 m silicone tube AFL9020005 Smoke cap holder AFL71549801 assembly Smoke pellets AFL9004167 Instrument adapter AFL82859401 1 Operation and User s 6005007 manual 2 Chapter 1 The following two instruments should be used in conjunction with the PANDA unit 9565 P Multi function Refer to Operation and Service Instrument His Manual TSI P N 6004851 supplied with the instrument for additional parts supplied as standard 5825 Refer to Operation and Service Micromanometer E i Manual TSI P N 1980568 supplied with the instrument for additional parts supplied as standard Unpacking and Parts Identification 3 This page intentionally left blank Chapter 1 Chapter 2 Preparing PAN200 System for Air Duct Leak Testing The following procedure should be followed carefully so that safe and accurate leakage testing can be achieved Successfully completing a duct leakage test requires certain information be compiled prior to starting the test Refer to Appendix B for a discussion of standards relating to duct leakage testing The list below indicates the information required Type of leakage test to be performed Positive or negative Leakage standar