1.    Fogmaker      Service Manual    Water Based Fire Suppression System for  Enclosed Spaces       Fogmaker North America    Post Address  Delivery Address  Tel  610 265 3610 info FMNA net  150 Gordon Dr 150 Gordon Dr Fax  610 265 8327 www FMNA net  Exton  PA 19341 Exton  PA 19341   9 30 13    8011 002 Service Manual   Rev C       Note that only components from Fogmaker   may be used  If other components are used  Fogmaker    will not guarantee the system function     Components in this manual marked with an asterisk     are not UL listed     Control Plan for the Suppression Unit    The suppression unit shall be serviced at least semiannually by qualified  trained  and authorized  personnel according to the Control Plan in this Service Manual  Every fifth year the piston accumulator   PA  shall be serviced and the suppression fluid shall be replaced  Every tenth year the PA will need to  be rebuilt and hydrostatic pressure tested  The service of the system may only be performed by  authorized personnel     Control Plan for Weekly Inspection   A visual inspection of the system components is to be performed every week to ensure that the  suppression unit is not leaking and has not sustained damage  Any repairs are to be completed by  authorized personnel     Control Plan for Daily Inspection   Confirm that the piston accumulator is charged by confirming that the indicator for the pressure gauge is  located in the green swept area  For hydro pneumatic activation units  the indica
2.  in the Operation and Installation Manual     Control if Safety Screw is Not Engaged into the Release Valve    Confirm that the detection system for the Hydro Pneumatic Activation option is activated and  that the safety screw is removed from the Piston Accumulator Release Valve  Refer to the  Operation and Installation Manual for activation deactivation instructions     8011 002 Service Manual     Rev C    1 2    1 3    1 4    2 1    3 2    3 3    FMNA Fire Suppression System    Inspection Report     Installation Report    Service Report                               Service Technician Order    Date Work Site  Customer   of Nozzles     Piston  Accumulator  Address Serial 4  PA Gauge  City  State  Zip Reading  Contact Name Detector Serial    Detector Gauge  Contact Phone Reading  Vehicle  End User Year Model  Vehicle         Vehicle Mfg  nozzles       Piston Accumulator  PA        Contact FMNA Engineering or OEM for correct number  amp  placement of    YES NO NA       Control Fixture  Vibration Damage       Are all mounting locations of the PA intact with no signs of wear or breakage        Control Protection Box   Labels       Is the protection box intact with no signs of wear or breakage        Are all labels visible and legible        Control Leakage   Corrosion       Is there any indication of leakage or corrosion around the PA couplings valve connections        Change of Service Interval Label   Control of Gauge Pressure       Is the service interval date label changed f
3. amage to the protective tube or protective coil  and that it is secure according to the Operation and Installation Manual   Check clamps for wear and tightness     Control for Labels on the Detection Tube    Confirm that the red colored    FIRE DETECTOR  labels  Part   FM 8206  are legible and located on  the detection tube  Replace these labels if they are damaged or missing     5  Alarm Panel   Alarm Device   Cables     Check for Slackness  Breakage  and Cracks    Check that there is no excessive slackness in the cables and that all joints and cables are  undamaged     Function Test   Fire Simulation     For Electronically Monitored Units     Confirm that the green indicator light is on   Refer to the Alarm Panel Manual for instructions on testing to confirm that the contact switches  on the detection cylinder and the piston accumulator will indicate a fire condition     8011 002 Service Manual     Rev C    6 1    6 2    6 3    6 4    9 30 13    6  Other Items  Control for Suppression Unit Enclosure  Check to ensure that the enclosure is unchanged since the last inspection     Installation and Operation Manual   Owner s Manual    A copy of the Operation and Installation Manual  number 8010 0022 Rev F  and a copy of the  Owner s Manual  number 8012 001 Rev A  is to accompany each unit at all times   Replace if missing or incomplete     Activation Labels   Control Labels    Confirm that the activation control labels are visible and legible in accordance with the  instructions
4. d           Are the protective covers for the nozzles in position and clean  If not  replace with new ones           Are all nozzles properly positioned per First Article Inspection and free of obstructions              9 30 13  8011 002 Service Manual     Rev C    3 4    4 2    4 3    4 4       Control for Breakages   Cracks on Hydraulic Hoses       Are all hoses secure and in good condition           Are all hoses and tubing connections tight with no possibility for leaks                                                           Detection System YES NO NA  Control for Detection Gas Cylinder   Detection Fluid Cylinder   Are all mounting locations of the detection bottle intact with no signs of wear or damage    Is the pressure gauge indicating in the green area on the detection bottle and is the pressure reading recorded on this form    Control for Detection Tube   Clamps   Is the routing and fixture of the detection tube free from wear or other damage    Is there any area of the detection tubing unprotected    Is the detection tube free of abrasions and secured  and does nothing contact the tube through the protective coil  etc     Are all tubing connections tight with no possibility for leaks    Control for Damage to Protective Tube   Protective Coil  Spiral    Is there any wear  pinching  or other damage to the protective tube or protective coil    Is the protective coil secure and are the ends properly bent according to the Installation Manual    Control for Labels on th
5. e Detection Tube   Are the Red  FIRE DETECTOR    labels clearly visible on the detection tube  Replace as needed    Alarm Panel    Alarm Device    Cables  YES NO NA       Check for Slackness   Breakage   Cracks       Function Test   Fire Simulation  Is the green light illuminated on the control panel and does there appear to be no evidence of tampering     Is there any slack in the cables and are all joints cables undamaged        Has the control panel been tested per the instructions on the panel        Other    YES    NO    NA       Is all electrical wiring intact and showing no sign of wear or damage        Are all control labels up to date and visible           Check if customer would like the system manuals sent electronically and notify customer service                 Additional Comments                                            Service Tech  Printed  Customer Name  Printed   Signature Customer Signature  Company Date   Date       Note  It is the customer s responsibility to ensure that all service checks are performed in accordance to Fogmaker North America s  guidelines as indicated in the Operation and Installation Manual  Services and or maintenance must be performed by a Fogmaker trained     certified technician  It is the responsibility of the customer to correct any problems as indicated by this document to ensure the proper    function of the system     9 30 13  8011 002 Service Manual     Rev C          
6. ease valves     Change of Service Interval Label   Control of Gauge Pressure    Upon completion of the service inspection  update the service interval label information by  attaching a new label with the correct month towards the arrow  Check the location of the  indicators on the pressure gauges and note their positions on the inspection report  Note  The  indicator on the pressure gauges for the piston accumulator and the detection cylinder should be  located in the green swept area  If deviations occur  contact Fogmaker  or an authorized service  provider     2  Maintenance of Mechanical Cable Activation Components     Before servicing  ensure the safety screw is installed in the release valve    Check that all the releases are sealed and that all the cables run easily without damage to the  wire cables or the release valve components that can affect their function    Remove the protective cover on the release valve and free the wire cable so that it is possible to  test its function    Spray lubricating oil CRC 5 56 or the equivalent on the valve mechanism    Restore the wires and valve as well as sealing the releaser again     3  Suppression Unit   Hydraulic Hose  Distribution System    Control for Vibration Damage   Wear    Visually inspect the suppression unit to confirm that there is no damage or wear to any of the  hoses or the piping and components in the unit     Control for Braces  Clamps   Tightness    Visually inspect and confirm that braces do not display any i
7. ndications of wear and that the  piping system components are tightened to the requirements in the Operation and Installation  Manual  number 8010 0022    Confirm that all connections are tight    If leakage is suspected  the suppressing unit must be test pressurized according to the Installation  Manual     8011 002 Service Manual     Rev C    3 3    3 4    4 1    4 2    4 3    4 4    5 1    5 2    9 30 13    Control for Protective Covers for Nozzles    Visually confirm that the protective covers for the nozzles are in position and are clean  If not   inspect nozzle before replacing with a new cover  Nozzle covers for  8L flow nozzles are yellow in  color  covers for 1 2L flow nozzles are orange in color     Control for Breakages   Cracks on Hydraulic Hoses    Visually check hydraulic hoses for wear  deterioration  cracks  or breakages that can result in  faults or leakage when the suppression unit is operated     4  Detection System    Control for Detection Gas Cylinder   Detection Fluid Cylinder    Check the condition and the fixture of the cylinder  The gauge pressure shall be in the green area   If not  contact Fogmaker  for consultation     Control for Detection Tube   Clamps    Check the routing and fixture of the detection tube so that no wear or other damage can occur   Check that nothing is rubbing the detection tubing through the protective coil     Control for Damage to Protective Tube   Protective Coil  Spiral     Check that there is no wear  pinching  or other d
8. or next inspection        For annual inspections only  is the annual inspection label replaced as required for warranty        Is the pressure gauge indicating in the green area on the PA and is the pressure reading recorded on this form        Is the safety screw for the release valve located on the PA removed and is the system active        Cable Activation   Electric Activation   BEFORE PERFORMING ANY WORK ON ACTIVATION  RE INSERT THE SAFETY SCREW     YES    NO    NA       Checking the Cable or Electric Activation        Is the manual or electric punch  properly installed and properly connected        For cable activation  inspect the handle lever for proper sealing and or damage        Lubricate cables and handle assembly  if applicable        Check cables and harness connections on electrical punch     if applicable        Confirm the pull pin can be removed on the manual button        Hydraulic Hose  Distribution System     YES    NO    NA       Are there any indications of damage wear on any of the hoses or pipes in the system     Control for Vibration Damage   Wear       Are the stainless pressure lines free of kinks and nicks        Control for Braces  Clamps   Tightness       Are all braces or clamps secure per the installation instructions and in good condition        Are all connections tightened per the requirements in the installation instructions        Control for Protective Covers   Proper Positioning of Nozzles       Are the proper number of nozzles installe
9. tor for the pressure  gauge located on the detection cylinder shall also be located in the green swept area  The pressures do  not need to be checked if the PA and the detection cylinder have the electronic monitoring  option     Control Plan for Semi Annual Service    1  Piston Accumulator   Detection Cylinder    1 1 Control for Mounting Vibration Damage to the Piston Accumulator    Visually inspect all mounting components for any damage to the piston accumulator and the  suppression unit s peripheral equipment   Also confirm that there are no indications of mechanical damage or damage due to vibration     1 2 Control of the Protecting Box   Labels    Visually inspect the condition of the protecting box to confirm that it is protecting the piston  accumulator satisfactorily and that the mounting components and assemblies are intact   Visually inspect the labels and markings on the suppression unit to confirm that they are legible  and visible     9 30 13  8011 002 Service Manual     Rev C    1 3    1 4    2 1    3 1    3 2    9 30 13    Replace the markings and labels with new ones if required   Confirm that the date of installation is less than 5 years from the date of manufacture  If the  suppression unit is older than 5 years  perform the 5 year service     Control for Leakage   Corrosion    Visually inspect the suppression unit to confirm there is no leakage or indications of corrosion   corrosion deposits located on the piston accumulator couplings  connections  and rel
    