Home

Perfecto2 Service Manual

image

Contents

1. 45 Replacing eost teo 45 SECTION REGULATOR 47 Replacing Regulator ceo Ra en Repo 47 Adj sting t dtr eon tr aep d echec inde Tod sept 49 SECTION 12 EXCHANGER ASSEMBLY Replacing Heat Exchanger Assembly 50 Part No 1154245 3 Perfecto 5 TABLE OF CONTENTS SECTION 3 CONTROL PANEL 000000000000000000000000000000000000000000000000000000 52 Removing Control Pariell 52 SECTION 14 COOLING 66 54 Replacing 54 SECTION 15 BOARD 6 66 57 Replacing 57 SECTION 16 OO Replacing the iis iiaa a 60 SECTION 17 SWITCH OT Replacing On Off 61 SECTION 18 FLOWMETER
2. Both fittings on heat exchanger assembly Detail N Replace any tubing that appears cracked worn etc 8 Re install cabinet Refer to Removing Cabinet on page 22 Refer to Typical Product Parameters page 7 for concentration levels If low concentrations are observed refer to Troubleshooting on page 15 Part No 1154245 75 Perfecto SECTION 23 LEAK TEST DETAIL A Valve Hose Valve Hose Connections STEP 6D Connections STEP 6D Hose Hose Connections to Connections Top Fittings of Sieve p Fittings Beds STEP 6C of Sieve Beds 5 6 Sieve Bed Sieve Bed Hose fitting on Center Port of 4 Manifold Assembly STEP 6B Hose Connections to Hose Bottom Fittings Connections to of Sieve Beds Bottom Fittings STEP 6 of Sieve Beds STEP 6C Sieve Bed Hose Connection At 4 way Valve manifold Assembly STEP 6A DETAIL B 4 Way Valve Manifold Assembly DETAIL Check Valves Fitting Product Cap Tank A Check all hoses Heat Exchanger valves attached Assembly Fitting FIGURE 23 1 Leak Test Perfecto 76 Part No 1154245 SECTION 23 LEAK TEST 4 Way Valve Function Test NOTE For this procedure refer to FIGURE 23 1 on page 76
3. 22 SECTION 6 PREVENTIVE MAINTENANCE 6666 23 Cleaning the Cabinet d n 23 Replacing the Outlet HEPA Filter sissscicsscisinsssesssuscusiaahiscdidussesssccuecdshasadeaususnesbucstecssdonsscduedeadeualdtesseasueers 24 Check the Outlet HEPA Filter 24 Replace the Outlet HEPA Filters toto eot fiip 24 Replacing the Compressor Inlet HEPA Filter 25 Replacing the Muffler Assembly 25 Cleaning the Heat Exchanger ai aa 28 SECTION 7 COMPRESSOR sccccccccccccccccccccoccscoocccocoscocosccsocecosocesseees Replacing Compressor Assembly 30 Replacing Capacitor EE E E 32 Rebuilding the Thomas Model 2660 550 33 Removing Compressor and Compressor Heads 34 Rebuilding the COHmp BSSOD 4d 37 SECTION 8 P E VALVE 41 Replacing REDE NUBE 41 SECTION 9 SIEVE BEDS 43 Replacing Sieve Bes 43 SECTION 10 VALVES
4. EX T 2 Sul S LI eee Capacitor ie Wrap Capacitor Terminals Spade Connectors connect here FIGURE 7 2 Replacing Capacitor Perfecto 32 Part No 1154245 SECTION 7 COMPRESSOR Rebuilding the Thomas Model 2660 Compressor A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE This kit is designed for rebuilding the Thomas Model 2660 Series compressor The model number is located on the front of the compressor Compressor number for this kit is 2660CHI39 111 If the compressor has a different model number than those listed this kit will not work The Thomas 2660 Series Compressor Rebuild Kit p n 1153686 contains the following DESCRIPTION QUANTITY Teflon Piston Cups 2 Aluminum Piston Sleeves Flapper Valves Intake and Exhaust Valve Keepers O Ring Sleeve Valve Plate Gaskets Head Mounting Screws Valve Screws Valve Restraints NIN Al NM NY BA NY Piston Cup Retainer Screws Tools Required Torque wrench that has an Nm or inch pound scale for head screws set screws flapper valve screw and pipe plugs e Torx T 25 drive for torque wrench for head screws Torx T 27 drive for torque wrench for retainer screws 1 8 inch Allen wrench attachment for torque wrench for eccentric set screw 5 32 inch Allen wrench attachment for to
5. 62 Replacing MM 62 SECTION 19 METER 63 Replacing Hour 63 SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY 64 Replacing 4 Way Valve and or Manifold Assembly serene 64 Replacing Pilot Valve Poppets and 5 67 SECTION 21 PURITY INDICATORS 6 7 SensO s Alarm Indicators s c otto 70 eir 70 IRCSPO2AW Indicator Lights ExplalatiGri 70 IRCSPAW Indicator Lights Explanation 70 SECTION 22 TIMING 72 Autotuning Model 72 Manual Tuning Model IRCSPAW 74 SECTION 23 LEAK TEST ccccccccccccccccccccccccccccccccccccsccccccccccccocccccccses 7 D Leak WeSC heat obe a caasa 75 4 Way Valve Function E 77 SECTION 24 ALARM TEST 79 Alarm ang Sensor
6. tube 25 Secure the manifold exhaust tube to the F tube with a tie wrap 26 Install cabinet Refer to Removing Cabinet on page 22 Part No 1154245 65 Perfecto SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY Manifold Exhaust Tube Clamp 4 Way Valve Manifold Assembly Vinyl Tube DETAIL DETAIL B Manifold Assembly 4 Way Valve 4 Way Manifold Assembly NOTE The numbers above indicate the mounting screw torque sequence pre torque to 1 1 0 2 Mounting M 10 2 inch lbs then torque to 2 5 0 2 N Screws M 22 2 inch lbs FIGURE 20 1 Replacing 4 Way Valve and or Manifold Assembly Perfecto 66 Part No 1154245 SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY Replacing Pilot Valve Poppets and O Rings A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 20 2 on page 69 1 Unplug unit 2 Remove cabinet Refer to Cabinet on page 22 3 Remove 4 way valve manifold assembly Refer to Replacing 4 Way Valve and or Manifold Assembly on page 64 4 Locate pilot valve on 4 way valve manifold assembly 5 Hold pilot valve stem with the flat blade screwdriver and turn the 9 16 inch locknut counterclockwise one complete turn 6 Unscrew the
7. On Invacare Technical Service for further assistance Use the chart in Preventive Maintenance on page 23 to record date and number of hours when preventive maintenance was performed on the concentrator or any repairs made OXYGEN CONCENTRATOR Refer to Service Manual DIAGNOSTIC ALARM SYSTEM ADJUSTMENTS BY UNAUTHORIZED PERSONNEL VOIDS WARRANTY LED FLASHES ALARM RED GREEN PROBABLE CAUSE BEEP AT START UP 0 NO PROBLEM SYSTEM SHORT BEEP WITH LONG PAUSE MAIN POWER LOSS CONTINUOUS LOW PRESSURE MAJOR LEAK CONTINUOUS HIGH PRESSURE NO SWITCHING CONTINUOUS TIME OUT FAILURE COMPRESSOR CONTINUOUS PILOT VALVE CIRCUIT CONTINUOUS 73 SHUTDOWN LOW 02 CONTINUOUS PE VALVE COIL CONTINUOUS EEPROM FAILURE CONTINUOUS 3 OXYGEN SENSOR FAILURE PERFORMANCE SPECIFICATION ao 0 1 1 1 1 2 2 2 Flow 0 5 to 5 0 L min Flow 2 0 to 10 0 L min Oxygen Concentration 95 6 to 87 Oxygen Concentration 94 to 87 1115180 REV D Part No 1154245 83 Perfecto SECTION 25 SIEVE BED PRESSURE CHECK SECTION 25 SIEVE BED PRESSURE CHECK Checking Sieve Bed Pressure A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing Disassembly NOTE For this procedure refer to FIGURE 25 1 1 Turn power off O and unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Turn unit so the back faces you R
8. Wires Back of Hour Meter Control Panel Retaining Clips Hour Meter Housing FIGURE 19 1 Replacing Hour Meter Part No 1154245 63 Perfecto SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing CAUTION This is a maintenance free valve Opening the valve will void any and all warranties applicable to the valve Replacing 4 Way Valve and or Manifold Assembly NOTE For this procedure refer to FIGURE 20 1 on page 66 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Cut the one tie wrap that secures the manifold exhaust tube to tube Remove the manifold exhaust tube from tube Cut the two tie wraps that secure tube to the 4 way valve manifold assembly Remove tube from the 4 way valve manifold assembly WN dc Using a hose clamp tool remove the clamps that secure the vinyl tubes to the 4 way valve manifold assembly 9o Remove the vinyl tubes from both sides of the 4 way valve manifold assembly 9 Note the orientation of the 4 way valve manifold assembly before removing for correct re installation 10 Lift 4 way valve manifold assembly up and out of the base of the concentrator 11 Disconnect spade connectors located on the side of the 4 way valve assemb
9. BIIAIVS JO NOI LO3dSNI HOV3 NO Qquooau JDNVNALNIVW Maintenance Record Ive 7 Prevent FIGURE 6 29 Perfecto Part No 1154245 SECTION 7 COMPRESSOR SECTION 7 COMPRESSOR A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing Replacing Compressor Assembly NOTE For this procedure refer to FIGURE 7 1 on page 31 and FIGURE 7 2 on page 32 Unplug unit Remove the cabinet Refer to Removing Cabinet on page 22 Cut the tie wrap that secures the intake hose to the compressor assembly Detail A Disconnect intake hose from compressor assembly Detail A Remove compressor wires from wire clamps or tie wraps not shown Disconnect compressor connector from the main harness connector not shown Disconnect capacitor wires from the top of the capacitor Detail B Disconnect brass nut from compressor Detail B SON d o xp OUT die UM On the backside of the Perfecto loosen the clamp that secures the vinyl tube to the manifold assembly and remove the vinyl tube from the manifold assembly Detail 10 On front side of the Perfecto pull heat exchanger with vinyl tube out of base assembly Detail D 11 Remove the four mounting screws that secure the compressor to the base assembly Detail 70 12 Tilt compressor assembly forward and lift out 13 Reverse STEPS
10. The 4 way valve used in Perfecto Series Concentrators does have an acceptable tolerance of leakage per RexRoth By nature of the valve design it is possible for the valve to experience small leaks and still operate without affecting the overall performance of the unit The valve is assembled where the components that make up the valve Snap together The only screws in the valve are for securing the valve to the manifold assembly According to RexRoth there is an acceptable leak specification of 60 cc per minute at 137 89 kPa 20 p s i on each valve Valves that have leaks within this specification will function properly without any adverse effects to the performance of the concentrator A leak in the amount of 60 cc or less would be indicative of the type of small leak you would notice where the end caps connect to the main body or where the three pieces of the main body connect together A 60 cc leak would not be noticeable when examining the system pressure swings Leaks greater than 60 cc are indicative of cracks in the end caps or a blown seal where the end cap connects to the main body of the valve These leaks are detected by either reading the system swing pressures noticing two consecutive swings not being equal or by hearing an audible leak every other cycle Leaks of this extreme nature indicate the valve needs to be replaced Valves should only need to be replaced when the following conditions exist 1 A visible
11. switch and wiring connections before installation Refer to FIGURE 17 1 Detail A and Detail B below CAUTION DO NOT install the On Off I O switch upside down Universal Off O symbol should be at bottom and Universal On I symbol should be at the top Possible damage to the concentrator may result if not properly installed 6 Reverse STEP 4 to secure new On Off switch 7 Reinstall control panel Refer to Removing Control Panel on page 52 8 Reinstall cabinet Refer to Removing Cabinet on page 22 DETAIL A ON On Off Front View Switch OF DETAIL B Spade Connector On Off from Brown Wire Aa Switch attached here gt SS 5 LA cua q Spade Connectors from White Wires Circuit Breaker 77 here FIGURE 17 1 Replacing On Off Switch Part No 1154245 61 Perfecto SECTION 18 FLOWMETER SECTION 18 FLOWMETER Replacing Flowmeter A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 18 1 on page 62 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 gt Note location of the PVC tubing for accurate replacement after new flowmeter is installed Remove control panel Refer to Removing Control Panel on page 52 Remove palnuts that secure flowmeter to the control panel Remo
12. E 17460 Celr Girona Tel 34 0 972 49 32 00 Fax 34 0 972 49 32 20 contactsp invacare com www invacare es France Invacare Poirier SAS Route de St Roch F 37230 Fondettes Tel 33 0 2 47 62 64 66 Fax 33 0 2 47 42 12 24 contactfr invacare com www invacare fr Ireland Invacare Ireland Ltd Unit 5 Seatown Business Campus Seatown Road Swords County Dublin Ireland Tel 353 1 810 7084 Fax 353 1 810 7085 ireland invacare com www invacare ie Italia Invacare San s r l Via dei Pini 62 I 36016 Thiene VI Tel 39 0445 38 00 59 Fax 39 0445 38 00 34 italia invacare com www invacare it Nederland Invacare BV Celsiusstraat 46 NL 6716 BZ Ede Tel 31 0 318 695 757 Fax 31 0 318 695 758 nederland invacare com csede invacare com www invacare nl Norge Invacare AS Grensesvingen 9 Postboks 6230 Etterstad N 0603 Oslo Tel 47 0 22 57 95 00 Fax 47 0 22 57 95 01 norway invacare com island invacare com www invacare no Osterreich Invacare Austria GmbH Herzog Odilostrasse 101 A 5310 Mondsee Tel 43 6232 5535 0 Fax 43 6232 5535 4 info invacare austria com www invacare at Sverige amp Suomi Invacare AB Fagerstagatan 9 S 163 91 Spanga Tel 46 0 8 761 70 90 Fax 46 0 8 761 81 08 sweden invacare com finland invacare com www invacare se Switzerland Invacare Benkenstras
13. Replace compressor Refer to Shutdown Control Panel Replacing Compressor Assembly on Indicators SensO ONLY page 30 RED On Faulty capacitor Replace capacitor Refer to Replacing YELLOW Off Capacitor on page 32 GREEN Off Bad motor windings Replace compressor Worn seals Rebuild top end of compressor Refer For SensO2 units the RED to Rebuilding the Thomas Model indicator will signal extremely 2660 Compressor on page 33 low purity and will be Replace compressor accompanied by a continuous Bad bearings Replace fittings or tubing audible alarm and a system Leak at fittings or tubing Replace relief valve shutdown Repairs are Leaky or defective relief valve DO NOT use extension cords required Insufficient voltage outlet Heat exchanger a Leak at tubing or body chamber Replace or retighten b Inspect tubing and heat Replace or retighten tubing Replace exchanger heat exchanger Refer to Replacing Heat Exchanger Assembly on page 50 Regulator cracked or leaking Replace Refer to Replacing Regulator on Exhaust muffler dirty or plugged Replace Refer to Replacing the Muffler Fan Not operating Unit overheating Leads to fan disconnected Reconnect b Faulty fan b Replace Refer to Replacing Cooling Fan on page 54 Sieve beds defective Replace Refer to Checking Sieve Bed Pressure on page 84 Tubing kinked or blocked Repair or replace P C board Check
14. before activating an alarm Environmental factors such as low voltage high altitude or age of the machine will affect the time required to reach 85 2 If the oxygen level is not above 85 2 within the first 30 minutes the oxygen concentration alarm sequence will activate and the unit will shut down When oxygen concentration is above 85 2 the sensor measures oxygen purity every 10 minutes If a reading falls below 85 2 a YELLOW light will illuminate If the oxygen purity falls below 73 3 the RED light Alarm Shut Down mode will activate Part No 1154245 13 Perfecto SECTION 3 PNEUMATIC DIAGRAM SECTION 3 PNEUMATIC DIAGRAM Perfecto Oxygen Concentrator Ouput Output HEPA Filter Check Flowmeter Valve Patient Output Pressure Oxygen Sensor Regulator SensO7 models Only x c Pressure Sensor A 15 Product Tank Check Valves Inlet i Fg E 1 7 7 7 Cabinet i t pag rmm Filter 1 Vi ompressor Fog Inlet Filter E i Sieve Sieve i Bed Valve Bed 4 Pod way As Compressor Valve Y Solenoid i Perfecto 14 1154245 SECTION 4 TROUBLESHOOTING SECTION 4 TROUBLESHOOTING Normal Operation No Problems Internal Status Indicators RED Off GREEN Off Unit plugged in power switch on Single beep on start up Pow
15. valve coil Resistance Replace P E coil if shorted or open Or 80 ohms 10 resistance check Refer to Replacing P E RED Two Flashes Valve on page 41 GREEN Three Flashes Defective valve Replace P E valve Refer to Replacing P E Control Panel Indicators Valve pase YELLOW Off GREEN Off Defective P C board Replace P C board Refer to Replacing Unit plugged in power switch P C Board on page 57 on continuous audible alarm Compressor shut down on continuous audible alarm Part No 1154245 17 Perfecto SECTION 4 TROUBLESHOOTING SYMPTOM PROBABLE CAUSE SOLUTION Unit not operating Alarm P C board Failure Replace P C board Refer to Replacing P C On or Off Board on page 57 Internal Status Indicators RED Two Flashes GREEN Four Flashes Or RED Two Flashes GREEN Five Flashes Low Concentration NOTE Cabinet filters dirty Clean or replace Refer to Cleaning the Check for O purity using a Cabinet Filter on page 23 Replacing the calibrated Oxygen Analyzer Outlet HEPA Filter on page 24 and at Test Point oxygen Replacing the Compressor Inlet HEPA outlet of the concentrator Filter on page 25 Compressor inlet filter dirty Replace inlet filter Refer to Replacing the Internal Status Indicators Compressor Inlet HEPA Filter page 25 RED Two Flashes Compressor GREEN One Flash73 a Defective
16. 3 12 to install new compressor assembly 14 Secure compressor to base assembly with four screws and springs Torque screws to 3 4 N M 30 x 5 in Ibs 15 Reinstall the cabinet Refer to Removing Cabinet on page 22 16 Run unit and inspect for leaks Refer to Leak Test on page 75 Perfecto 30 Part No 1154245 SECTION 7 COMPRESSOR DETAIL A DETAIL B Tie Wrap Brass Nut Capacitor Capacitor Wires Intake Hose Compressor attach here DETAIL C DETAIL 0 Mounting Screws Mounting Screws 4 71 e Grommets Vinyl Tube Clamp Manifold Assembly FIGURE 7 1 Replacing Compressor Assembly Part No 1154245 3l Perfecto SECTION 7 COMPRESSOR Replacing Capacitor NOTE For this procedure refer to FIGURE 7 2 1 Unplug the unit 2 Remove the cabinet Refer to Removing Cabinet on page 22 3 Using needlenose pliers disconnect the spade connectors from the capacitor terminals Cut the tie wrap that secures the capacitor to the base of the concentrator Remove the capacitor from the concentrator base Install new capacitor by reversing STEPS 3 6 ND Re install the cabinet Refer to Removing Cabinet on page 22 ASI Ne xut 1 5 7 o Y 2e by s f 7N 9 YN A 0 i 0 Sh X S 1 dd Qi
17. FIGURE 16 1 on page 60 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Locate the transformer located on the sound box Code all wires before disconnecting for proper re connections Remove the two mounting screws that secure the transformer to the soundbox Note orientation of transformer on soundbox before removing for proper reinstallation Remove the existing transformer and discard 8 9 Install new transformer in orientation noted in STEP 7 Connect all wires as noted from STEP 4 10 Reinstall cabinet Refer to Cabinet on page 22 Location of DETAIL A ransformer Transformer odd Assembly Screws FIGURE 16 1 Replacing the Transformer Perfecto 60 Part No 1154245 SECTION 17 SWITCH SECTION 1 7 ON OFF SWITCH Replacing On Off Switch A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 17 1 on page 61 1 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Remove control panel Refer to Removing Control Panel on page 52 Remove and code the four spade connectors from back of existing On Off switch N Compress retaining grips on back of existing On Off switch and push switch out through front of control panel NOTE Ensure proper orientation of the On Off
18. Leak Test on page 75 16 Reinstall cabinet Refer to Removing Cabinet on page 22 DETAIL DETAIL Mounting Screws A Wrap 7 5 Control Panel Ya inch Tubing STEP 7 Circuit Breaker STEP 9 Hour Meter On Off Switch STEP 9 5 9 Mounting Screws FIGURE 13 1 Removing Control Panel Part No 1154245 53 Perfecto SECTION 4 COOLING FAN SECTION 14 COOLING FAN Replacing Cooling Fan A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 14 1 on page 56 1 Unplug unit Remove cabinet Refer to Cabinet on page 22 Remove control panel Refer to Removing Control Panel on page 52 gt N Remove compressor inlet HEPA filter Refer to Replacing Compressor Inlet HEPA Filter on page 25 Remove three mounting screws that secure resonator housing to soundbox Two mounting screws are installed in the top The other mounting screw is located on the backside of the housing near the bottom Detail A D Move the resonator housing back slightly for access to the cooling fan Disconnect the intake hose the compressor assembly if necessary Detail A 7 Disconnect spade connectors from fan terminals on side of cooling fan NOTE The cooling fan is fastened to the soundbox with f
19. cabinet Refer to Removing Cabinet on page 22 Plug the unit in and turn the power on I Locate the P C board pr owe N Wait for the main valve shift to indicate one of the following Ifthe P C board is new the front panel RED indicator light will slowly blink indicating autotune has initiated Ifthe P C board is used and has performed autotuning before press and release the small push button on the P C board The front panel RED indicator light will slowly blink indicating the unit is autotuning and automatically adjusting the valve timing 6 Setthe output flow to 5 0 L min 7 The GREEN onboard diagnostic light will flash the current value of the P E valve timing number 8 Place the cover back on the unit but DO NOT install the cover screws Let the unit run until autotuning is completed 9 When autotuning is complete the RED front panel indicator light will change from a slow blinking to a flashing of the final P E valve timing number Perfecto 72 Part No 1154245 SECTION 22 TIMING 10 Turn the unit off and then back on The timing value is stored in memory for future use 11 If the unit is turned off before an autotune cycle is completed the P E valve timing will not be stored or updated If the board is new autotuning MUST be successfully completed before the unit can be placed into service 12 After a successful autotune run the unit for 30 minutes and verify that the oxygen
20. crack is noted on either of the end caps or main body of the 4 way valve regardless of the amount of leak 2 A large leak is present on the valve that causes an imbalance in the sieve bed swing pressures Example Sieve Bed 1 pressure swings from 96 52 kPa 14 p s i to 110 32 kPa 16 p s i within 7 20 seconds and Sieve Bed 2 pressure swings from 89 63 kPa 13 p s i to 110 32 kPa 16 p s i slowly and may take as long as 25 30 seconds before shifting times over 30 second will shut down automatically 3 Valve will not shift and the pilot valve solenoid and circuit board are working properly NOTE The concentrator s P C B should exhibit an error code for High Pressure Failure 1 RED 2 GREEN NOTE The best method to test the 4 way valve operation is by measuring the unit pressure swings This can easily be done at the HomeFill port with a 0 206 84 kPa 0 30 5 1 pressure gauge and a fill line adapter Upon starting the unit should build pressure up to 110 32 kPa 16 p s i for output flows 3 L min and below or 21 p s i for output flows 4 L min and above before its initial shift After the initial shift the unit should shift consistently in equal amounts of time 1 second time recorded in seconds Part No 1154245 77 Perfecto SECTION 23 LEAK TEST 4 ears K 4 S 69 x 4 Check each end cap for cracks and for major leaks You sho
21. fade pesci tuens 79 Power Loss Ala Mane dier epe PP ane E 79 low Pressure ci Ae Dad teo aeu chos bti iS ded a 79 Tiles Testo aid copo Om deeem dele de uve m 80 High rises e 80 Oxygen SENSO RETE RN 81 Valve Coil Test 83 SECTION 25 SIEVE BED PRESSURE CHECK ccccccccccccccccccccccccccccsees OF Checking Sieve 84 Disassembly oes eoque oa nO teet E 84 Piressure Testing iucunde cts cintas eiie cit 84 CUSTOMER SERVICE AND WARRANTY INFORMATION 87 Perfecto 4 Part No 1154245 SPECIAL NOTES SPECIAL NOTES Signal words are used in this manual and apply to hazards or unsafe practices which could result in personal injury or property damage Refer to the table below for definitions of the signal words SIGNAL WORD MEANING A DANGER Danger indicates an imminently hazardous situation which if not avoided will result in death or serious injury Warning indicates a potentially hazardous situation which if not avoided could result in death or serious injury WARNING Caution indicates a potentially hazardous situation which if CAUTION not avoided may result in property damage or minor injury or both NOTICE THE I
22. it will also rock from side to side Screw Access Hole Screw hidden This is a feature of the WOB L Piston FIGURE 7 4 Removing Compressor and Compressor Heads Rebuilding the Compressor Fan Connecting Rod and Eccentric Assembly Piston Cup Part No 1154245 35 Perfecto SECTION 7 COMPRESSOR O ring Intake Valve Keeper and Valve Keeper Strip NOTE For this procedure refer to FIGURE 7 5 1 Remove the O ring intake valve flapper and valve keeper strip from the bottom of the valve plate Discard all 2 Clean the bottom of the valve plate with a clean soft cloth Valve Flapper Screw Valve Keeper Strip O Ring Intake Valve Flapper FIGURE 7 5 Removing Compressor and Compressor Heads Rebuilding the Compressor O ring Intake Valve Keeper and Valve Keeper Strip Exhaust Valve Flapper Valve Restraint and Valve Keeper Strip NOTE For this procedure refer to FIGURE 7 6 1 Remove the exhaust valve flapper valve restraint and valve keeper strip from the top of the valve plate Discard all 2 Clean the top of the plate with a clean soft cloth Gasket NOTE For this procedure refer to FIGURE 7 6 1 Remove the old gasket from the top of the valve plate and discard 2 Clean the valve plate with a clean soft cloth Perfecto Valve Flapper Screw Gasket Valve Keeper Strip Exhaust Valve Flapper Valve SSS Restr
23. meter reads 0 volts when unit is turned on replace P C board Check spade connectors on pilot valves or 2 and connectors on P C Unit plugged in power switch b Disconnected wire on continuous alarm board Compressor shut down Replace P C board Unit requires retiming after P C board replacement Refer to Replacing P C Board on page 57 c Shifting valve at pressures greater than 25 p s i for Perfecto 4 way Valve a Not shifting Check voltage If voltage rises to approximately 24 volts D C when unit shuts down P C board is functioning properly Replace the valve if shorted or open Refer to Replacing 4 Way Valve and or Manifold Assembly on page 64 Replace 4 way valve Refer to Replacing 4 Way Valve and or PM Manifold Assembly on page 64 c Coil resistance Coil should read 175 ohms x 20 b Bad coil Perfecto 16 Part No 1154245 SECTION 4 TROUBLESHOOTING SYMPTOM PROBABLE CAUSE SOLUTION LOW PRESSURE Compressor inlet filter dirty or Replace compressor inlet filter Refer to Internal Status Indicators plugged Replacing the Compressor Inlet HEPA RED One Flash Filter on page 25 GREEN One Flash Compressor Or a Leaks at fittings or tubing Replace or repair RED One Flash b Leaking or defective relief valve Repair leak or replace GREEN Three Flashes c Insufficient voltage at outlet DO NOT use extension cords Use another outlet Control P
24. or P C board circuitry has failed 1 With the unit running and flow set at 5 L min disconnect in line connector shown in FIGURE 24 2 The main valve coil alarm should activate within 40 seconds Refer to SensO2 Alarm Threshold on page 82 for shutdown mode FIGURE 24 2 3 Replace tubing and tie wrap NOTE If any alarm fails to perform to specification contact Invacare Technical Service Perfecto 80 Part No 1154245 SECTION 24 ALARM TEST Location of In Line Connector In Line Connector FIGURE 24 2 High Pressure Test Oxygen Sensor NOTE For this procedure refer to FIGURE 24 3 on page 82 Alarm sequence occurs when concentration levels fall below a preset value typically 73 3 or 85 2 This failure indicates a catastrophic failure of any component mechanical or electrical 1 Turn unit on 1 Set output flow at 5 L min 2 Monitor the level 3 With the level greater than 85 after five minutes the GREEN panel indicator light will remain illuminated Part No 1154245 81 Perfecto SECTION 24 ALARM TEST 4 Slowly adjust flow beyond maximum rated flow until you can achieve a concentration level greater than 75 but less than 84 Within 30 minutes the YELLOW panel indicator light will illuminate and the unit will continue to run 5 Clamp off the 1 8 inch oxygen sensor tubing between the oxygen sensor and the product tank regulator A WARNING U
25. panel Refer to Removing Control Panel on page 52 Reinstall compressor inlet HEPA filter Refer to Replacing the Compressor Inlet HEPA Filter on page 25 Plug unit in and check for leaks Refer to Leak Test on page 75 Run unit for at least 30 minutes If unit runs properly replace cover If not call Invacare Technical Service Reinstall cabinet Refer to Cabinet on page 22 Part No 1154245 55 Perfecto SECTION 4 COOLING FAN DETAIL DETAIL Rubber Grommet Cooling Fan Mounting Screws oe Intake Hose Compressor Assembly Mounting Screw Fan Terminals Spade Connectors attach here Soundbox Resonator Housing DETAIL D Cooling Cooling Fan Rubber Grommets Rubber Grommets Larger recessed area to be installed in fan NOTE Cooling fan removed from rubber grommets to show proper installation of grommets in soundbox Smaller recessed area to be installed in soundbox FIGURE 14 1 Replacing Cooling Fan Perfecto 56 Part No 1154245 SECTION 15 BOARD SECTION 15 BOARD Replacing P C Board A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing CAUTION Follow these pre cautions to prevent damage to the P C boards Before handling any boards you need to be properly g
26. pilot valve stem assembly from the manifold while leaving the coil with yoke and locknut intact on stem 7 Remove pilot valve poppet from inside the pilot valve stem CAUTION DO NOT remove the coil yoke from the coil The washer between the bottom of the yoke and the bottom of the coil MUST not be removed Otherwise components may be damaged in reassembly 8 Set aside the coil with yoke and pilot valve stem assembly with the wires still intact A WARNING DO NOT use sharp tools to remove O ring from plastic manifold opening Damage to the plastic manifold and or plastic manifold airflow passage may occur Damage to airflow may result in improper oxygen delivery and harm to the user Refer to Detail A in FIGURE 20 2 9 Remove poppet and O ring from manifold opening Detail A 10 Discard old poppet and O ring 11 Install new O ring into the opening in the plastic manifold housing Detail A CAUTION DO NOT overtighten pilot valve stem when installing it into plastic manifold Damage to the rubber O ring and or plastic manifold may occur Part No 1154245 67 Perfecto SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY 12 Install new slotted poppet into the bottom of the pilot valve stem with tapered end facing to the bottom 13 Install pilot valve stem and new slotted poppet with coil with yoke and locknut intact into manifold opening 14 Use a flat blade screwdriver and tighten pilot val
27. pull the stem on the compressor relief valve out as far as it will go and hold it 3 The low pressure alarm should activate within 30 seconds Refer to SensO2 Alarm Threshold on page 82 for shutdown mode Test Two 1 With unit running set flow at maximum rating 2 Remove the pressure sensor tubing tie wrap from the top of the product tank not shown 3 The low pressure alarm should activate within 30 seconds Refer to SensO2 Alarm Threshold on page 82 for shutdown mode 4 Replace tubing and tie wrap Part No 1154245 79 Perfecto SECTION 24 ALARM TEST Time Out Test NOTE For this procedure refer to FIGURE 24 1 1 With unit off disconnect the compressor connector from the main wiring harness 2 Plug unit in and turn power on 1 3 The Time Out Failure alarm should activate within 40 seconds Refer to SensO2 Alarm Threshold on page 82 for shutdown mode 4 Replace tubing and tie wrap NOTE If any alarm fails to perform to specification contact Invacare Technical Service Relief Valve Pull Out O Stem to Simulate Leak i MT Compressor FIGURE 24 1 Low Pressure Test Time Out Test High Pressure Test NOTE For this procedure refer to FIGURE 24 2 on page 81 High Pressure Occurs when pressure in product tank rises beyond a preset value typically 158 58 kPa 6 89 23 p s i 1 54 Main Valve Coil Alarm sequence occurs when the main valve coil connection
28. running for a minimum of 30 minutes at a time Shorter periods of operation may reduce maximum product life A product should NEVER be left unattended when plugged in Make sure the Perfecto is Off when not in use DO NOT connect the concentrator in parallel or series with other oxygen concentrators or oxygen therapy devices Keep the oxygen tubing cord and unit out from under such items as blankets bed coverings chair cushions clothing and away from heated or hot surfaces including space heaters stoves and similar electrical appliances Part No 1154245 9 Perfecto SECTION IMPORTANT SAFEGUARDS Radio Frequency Interference This equipment has been tested and found to comply with EMC limits specified by IEC EN 60601 1 2 These limits are designed to provide a reasonable protection against electromagnetic interference in a typical medical installation Other devices may experience interference from even the low levels of electromagnetic emissions permitted by the above standards To determine if the emissions from the Perfecto is causing the interference turn the Perfecto Off If the interference with the other device s stops then the Perfecto is causing the interference In such rare cases interference may be reduced or corrected by one of the following measures e Reposition relocate or increase the separation between the equipment e Connect the equipment into an outlet on a circuit different from that to whi
29. 2 kPa 16 p s i output flows 3 L min and below The time between cycles is dependent on altitude flow rate and internal environmental factors A valve opens just prior to the shift of the 4 way valve This allows highly concentrated oxygen to enter the just exhausted bed from the top This additional pressure allows the bed to start its cycle at a higher pressure The P E valve will close just after the shift of the 4 way valve If main power is lost the Battery Free Power Loss Alarm will sound a short BEEP with a long pause after All units are equipped with a diagnostic alarm system that signals if the pneumatic pressure or electrical systems malfunction The troubleshooting guide in this manual explains the alarm system signals and reasons in detail Refer to Troubleshooting on page 15 SensO Oxygen Sensor Technology Ceramic Zirconia Sensor Technical Description The oxygen being produced by the concentrator flows out of the product tank and into the flowmeter A small flow of oxygen produced by the unit is sent through a precision orifice to the oxygen sensor mounted on the printed circuit board As the oxygen enters the sensor it passes through a screen and contacts the sensing disk Electric current flowing through a metal film resistor heats the disk in excess of 300 C Oxygen molecules contact the electrode of the disk and pick up extra electrons to become oxygen ions These oxygen ions are attracted to the el
30. 5 TABLE OF CONTENTS TABLE OF CONTENTS SPECIAL NOTES D FEATURES 6 TYPICAL PRODUCT PARAMETERS 66 7 SECTION IMPORTANT SAFEGUARDS 9 Important Safeguards 2 ni aai iii 9 Radio Frequency Interference 10 SECTION 2 INSTALLATION SEQUENCE OF OPERATION Verification of Battery Free Power Loss Sequence of Operation tess SensO Oxygen Sensor Technology Ceramic Zirconia Sensor sss 12 Description 12 Operating Sequeice 12 SECTION 3 PNEUMATIC DIAGRAM 00000000000000000000000000000000000000000000000 14 SECTION 4 TROUBLESHOOTING 0000000000000000000000000000000000000000000000000000 5 SECTION 5 CABINET 00000000000000000000000000000000000000000000000000000000000000000000 22 Removing mM
31. Continuous Audible Alarm Sieve GARD Compressor Shut down IRCSPAW INDICATORS LABEL STATUS INDICATOR LIGHTS SYMBOL LED SYSTEM OKAY GREEN Indicator Light SYSTEM FAILURE RED Indicator light Continuous Audible Alarm Sieve GARD Compressor Shutdown Call a qualified technician Perfecto 8 Part No 1154245 SECTION IMPORTANT SAFEGUARDS SECTION IMPORTANT SAFEGUARDS Important Safeguards In order to ensure the safe installation assembly and operation of the Perfecto concentrator these instructions MUST be followed A WARNING This section contains important information for the safe operation and use of this product A DANGER Risk of electric shock DO NOT disassemble Refer servicing to qualified service personnel No user serviceable parts TO REDUCE THE RISK OF BURNS ELECTROCUTION FIRE OR INJURY TO PERSONS DO NOT place or store product where it can drop into water or other liquid DO NOT reach for product that has fallen into water Unplug IMMEDIATELY A spontaneous and violent ignition may occur if oil grease or greasy substances come in contact with oxygen under pressure These substances MUST be kept away from the oxygen concentrator tubing and connections and all other oxygen equipment DO NOT use any lubricants unless recommended by Invacare Operating Information For optimum performance Invacare recommends that each concentrator be on and
32. N It may be necessary to remove compressor inlet HEPA filter Refer to Replacing the Compressor Inlet HEPA Filter on page 25 Check Valve Cut PVC Tubing below Check Valve to install Tap in Kit Product Tank FIGURE 25 1 Disassembly Pressure Testing NOTE For this procedure refer to FIGURE 25 2 on page 85 1 Connect pressure gauge to the x 2 inch silicone tubing with connector p n 1131392 2 Remove plug in HomeFill port in back of concentrator 3 Connect x 2 inch silicone tubing with connector to port Perfecto 84 Part No 1154245 SECTION 25 SIEVE BED PRESSURE CHECK 4 Check each connection to make sure it is tight 5 Turn the concentrator On 1 NOTE Adjust the concentrator to MAXIMUM rated liter flow to 5 L min NOTE Wait approximately five minutes to allow system pressures to achieve proper equilibrium before testing 6 The pressure in the concentrator should rise within 20 seconds to144 79 kpa 2 07 kPa 21 p s i g 0 3 p s i g and shift the 4 way valve to the opposite sieve bed 7 After the 4 way valve shift the pressure in the concentrator will drop to 82 74 13 79 12 p s i g 2 p s i g before rising within 20 seconds to 144 79 2 07 kPa 21 p s i g 0 3 and shift the 4 way valve to the opposite sieve bed 8 If pressure reading is 144 79 kpa 2 07 kPa 21 p s i g 0 3 p s i g when both valve shifts are made proceed to STEP 10 9 I
33. NFORMATION CONTAINED IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE A DANGER DO NOT SMOKE while using this device Keep all matches lit cigarettes candles or other sources of ignition out of the room in which this product is located and away from where oxygen is being delivered NO SMOKING signs should be prominently displayed Textiles and other materials that normally would not burn are easily ignited and burn with great intensity in oxy gen enriched air Failure to observe this warning can result in severe fire property damage and cause physical injury or death Part No 1154245 5 Perfecto FEATURES FEATURES FRONT VIEW Oxygen Purity Indicator Lights Fault and Power Indicator Lights SensO5 Model Only Oxygen Outlet Flowmeter Circuit Breaker Power Switch Hour Meter ACCESSORIES NOT SHOWN PreciseRy Pediatric Flowmeter Accessory IRCPF16AW HomeFill home oxygen compressor IOH200AW This outlet fitting is to be used only for filling oxygen cylinders with the HomeFill home oxygen compressor The outlet fitting does not affect concentrator performance Refer to the HomeFill owner s manual part number 1145804 Northern 1145805 Southern 1145806 Scandinavian for connection and operating instructions When not in use the plug provided with the concentrator should be inserted into the outlet fitting For more information about the HomeFill cont
34. SECTION 6 PREVENTIVE MAINTENANCE Cleaning the Heat Exchanger A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 6 6 on page 28 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 CAUTION Use care not to deform heat exchanger when installing removing or cleaning 3 Remove excess dirt using compressed air or vacuum 4 Reinstall cabinet Refer to Cabinet on page 22 Heat Exchanger FIGURE 6 6 Cleaning the Heat Exchanger Perfecto 28 Part No 1154245 SECTION 6 PREVENTIVE MAINTENANCE SERIAL NO IRC MODEL NO sipak 10 194 skop 194 sunoy pz o1 sunoy 087 97 9 10 194 54 194 sunou pz 8 o1 5 085 ALON JONUDp 9214495 Jo uon2es 01 5501 1934 JU 40 3193 Vd3H PRNO 4 3 4 24 5 2945 SUNOH 08 9 5 5 5507 294D 9 snop 4
35. Service Manual Perfecto Oxygen Concentrator HomeFill Compatible Model IRC5PO2AW Sensored Model IRC5PAW Non Sensored MUST be performed by a qualified technician DEALER Keep this manual The procedures in this manual C 0120 For more information regarding Invacare products parts and services please visit www invacare eu com Yes you can A WARNING DO NOT OPERATE THIS EQUIPMENT WITHOUT FIRST READING AND UNDERSTANDING THIS MANUAL IF YOU ARE UNABLE TO UNDERSTAND THE WARNINGS CAUTIONS AND INSTRUCTIONS CONTACT INVACARE TECHNICAL SERVICES BEFORE ATTEMPTING TO USE THIS EQUIPMENT OTHERWISE SERIOUS INJURY OR PROPERTY DAMAGE MAY RESULT WARNING Invacare products are specifically designed and manufactured for use in conjunction with Invacare accessories Accessories designed by other manufacturers have not been tested by Invacare and are not recommended for use with Invacare products PERFECTO PARTS COMPATIBILITY The Platinum concentrator and the Perfecto concentrator share many similar components However there are some components that are NOT cross compatible and they are specific to each model Parts that can be used for Perfecto repairs are listed in the Perfecto parts catalog form number 08 076 Please reference this catalog before replacing any parts Use of incorrect parts could result in injury or property damage Perfecto 2 Part No 115424
36. act your Invacare dealer Outlet Fitting Power Inlet Perfecto 6 Part No 1154245 TYPICAL PRODUCT PARAMETERS TYPICAL PRODUCT PARAMETERS Electrical Requirements 230 VAC 10 253 VAC 207 VAC 50 Hz Sound Level 39 5 dBA Average Altitude Up to 1828 m 6 000 ft above sea level without degradation of concentration levels Not recommended for use above 1828 m 6 000 ft Oxygen Output 95 6 to 87 at 0 5 to 5 L min Concentration Levels NOTE Stated concentration levels achieved after initial warm up period approximately 30 minutes Maximum Outlet Pressure 34 5 kPa 3 45 kPa 5 p s i 0 5 p s i Flow Range 0 5 to 5 L min For flowrates less than L min we recommend the use of the Invacare Pediatric Flowmeter IRCPFI6AW Accessory Potential Obstruction Alert The concentrator detects a condition that may indicate a poten tial obstruction of the output oxygen Rapid Audible Alarm Beeping this alarm is deactivated when accessories are connected May be associated with a flow setting of 0 5 L min or less Average Power Consumption 280 W Operating 3 L min Pressure Relief Mechanism Operational at 241 kPa 24 1 kPa 35 p s i 3 5 p s i Change in maximum recommended flow 0 7 L min when back pressure of 7kPa is applied Cabinet Outlet HEPA and Compressor Inlet Safety System Current overload or line surge shutdown High temperature compressor shutdown High Pressure Alarm w compressor
37. age 47 5 Remove the two mounting screws on top corners of P C board 6 Position new board Part No 1154245 57 Perfecto SECTION 15 BOARD 7 10 11 12 13 Secure new board in place with existing mounting screws Be sure all tie wraps removed from tubing connections are replaced Do the following A Connect wiring harnesses to P C board B Connect pressure sensor tubing to product tank C For concentrators that have O2 sensor connect the oxygen sensor tubing to regulator fitting Reinstall control panel Refer to Removing Control Panel on page 52 Run concentrator to ensure unit operates to specifications After replacing P C board retiming may be necessary Refer to Timing on page 72 Check for leaks at pressure sensor tubing on product tank cap Refer to Leak Test on page 75 Reinstall cabinet Refer to Removing Cabinet on page 22 Perfecto 58 Part No 1154245 SECTION 15 BOARD Control Panel Wiring Harnesses Connect Here Oxygen Sensor Tubing IRCSPO2AW only Board Mounting Screw Mounting Screw Pressure Sensor Tubing FIGURE 15 1 Replacing P C Board Part No 1154245 59 Perfecto SECTION 16 SECTION 16 TRANSFORMER Replacing the Transformer A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to
38. aint FIGURE 7 6 Removing Compressor and Compressor Heads Rebuilding the Compressor Exhaust Valve Flapper Valve Restraint and Valve Keeper Strip 36 Part No 1154245 SECTION 7 COMPRESSOR Rebuilding the Compressor NOTE Before reassembly wipe any residue from all components with a clean soft cloth Gasket NOTE For this procedure refer to FIGURE 7 6 on page 36 1 Install new gasket seating the gasket firmly in the groove at the top of the valve plate with your finger or blunt object CAUTION Make sure that the gasket is not twisted when seated in the groove of the top of the valve plate Exhaust Valve Flapper Valve Restraint and Valve Keeper Strip NOTE For this procedure refer to FIGURE 7 6 on page 36 1 Install the new exhaust valve flapper valve restraint and valve keeper strip to the top of the valve plate with the valve flapper screw NOTE Torque flapper screws to 1 36 N M 12 inch lbs O ring Intake Valve Flapper and Valve Keeper Strip NOTE For this procedure refer to FIGURE 7 5 on page 36 1 Install the new valve keeper strip on top of the new intake valve flapper so that the word UP is visible Fasten with the valve flapper screw 2 Install the new O ring seating it firmly into the groove with your finger or blunt object NOTE Torque flapper screws to 1 36 N M 12 inch lbs Piston Cup NOTE For this procedure refer to FIGURE 7 4 on page 35 1 Place cylinder sleeve over
39. anel Indicators d Worn cup seals or gaskets Rebuild top end of compressor Refer RED On to Rebuilding the Thomas Model YELLOW Off 2660 Compressor on page 33 GREEN Off Heat exchanger a Leak at tubing or body chamber Replace or retighten Unit plugged in power switch b Inspect tubing and heat Replace or retighten tubing Replace exchanger heat exchanger Refer to Replacing Compressor shut down Heat Exchanger Assembly on Failure to cycle due to low page 50 pressure Regulator cracked or leaking Replace regulator Refer to Replacing Regulator on page 47 P E valve leaking Replace P E Valve Check voltage at P E valve connector on 24 volt D C scale The P E Valve activates or energizes approximately one second prior to the activation of the 4 way valve with approximately 24 volts If voltage is in excess of 24 volts consistently replace the P C board Refer to Replacing P C Board on page 57 If the P C board voltage acts normally replace the P E valve Refer to Replacing P E Valve on page 41 Note Check for leaks starting at the compressor output through all the pneumatic connections Major leaks will cause system pressures to remain below adequate shift exhaust pressures and will cause compressor shutdown Defective Parts Defective main valve coil a Replace main valve Internal Status Indicators b Replace main valve coil RED One Flash GREEN Five connector Flashes Defective P E
40. ansformer assembly Refer Control Panel Indicators to Replacing the Transformer on RED Off page 60 YELLOW Off GREEN Off Power Switch ON Continuous audible alarm Unit Operating Internal repairs required Replace SensO circuit board Refer to Internal Status Indicators Replacing P C Board on page 57 RED Three Flashes GREEN One Flash Control Panel Indicators RED Off YELLOW Flashing GREEN On Potential Obstruction Alert System leak Repair leak in product tank regulator less than 0 5 L min Defective check valves Replace check valves Refer to Replacing Check Valves on page 45 Part No 1154245 21 Perfecto SECTION 5 CABINET SECTION 5 CABINET Removing Cabinet A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 5 1 1 Unplug unit 2 Remove the four mounting screws that secure cabinet assembly to the base assembly 3 Liftthe cabinet straight up NOTE When required vacuum inside of the cabinet and exposed foam insulation 4 Tore install cabinet reverse STEPS 2 3 Cabinet Assembly Mounting Screws Mounting Screws Base Assembly FIGURE 5 1 Removing Cabinet Perfecto 22 Part No 1154245 SECTION 6 PREVENTIVE MAINTENANCE SECTION 6 PREVENTIVE MAINTENANCE A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electri
41. cal outlet before servicing A WARNING The Invacare concentrators are specifically designed to minimize routine preventive maintenance Only qualified personnel should perform preventive maintenance on the concentrator NOTE At a minimum preventive maintenance MUST be performed according to the maintenance record guidelines In places with high dust or soot levels maintenance may need to be performed more often Refer to Troubleshooting on page 15 for plugged filter symptoms and to Preventive Maintenance Record on page 29 Cleaning the Cabinet Filter NOTE For this procedure refer to FIGURE 6 1 on page 24 NOTE There is one cabinet filter located on the back of the cabinet 1 Remove the filter and clean as needed NOTE Environmental conditions that may require more frequent inspection and cleaning of the filter include but are not limited to high dust air pollutants etc 2 Clean the cabinet filter with a vacuum cleaner or wash in warm soapy water and rinse thoroughly 3 Dry the filter thoroughly before reinstallation CAUTION DO NOT operate the concentrator without the filter installed Part No 1154245 23 Perfecto SECTION 6 PREVENTIVE MAINTENANCE Filter FIGURE 6 1 Cleaning the Cabinet Filter Replacing the Outlet HEPA Filter Check the Outlet HEPA Filter NOTE The outlet HEPA filter can be checked during preventive maintenance or between patients by performing the following proce
42. ch the other device s is connected Avoid creation of any spark near medical oxygen equipment This includes sparks from static electricity created by any type of friction Perfecto 10 1154245 SECTION 2 INSTALLATION SEQUENCE OF OPERATION SECTION 2 INSTALLATION SEQUENCE OF OPERATION Verification of Battery Free Power Loss Alarm Check the Perfecto concentrator for proper operating conditions 1 If theunit has been in below freezing temperatures allow it to warm up to room temperature before operating 2 The concentrator may need to be turned on for four to five seconds to charge the Battery Free Power Loss Alarm Connect power cord to outlet and turn the concentrator on Turn flow control knob counterclockwise and flow will begin IMMEDIATELY Set flow rate to five L min Let the unit run for 30 minutes then turn unit off 3 Unplug the power cord and press On Off VO switch to the On 1 position An intermittent audible alarm will sound This confirms proper operation of the Battery Free Power Loss Alarm Turn On Off switch Off O 4 Connect power cord to outlet and turn on concentrator Unit will beep on start up 5 Check the oxygen concentration per specifications after 30 40 minutes running time Sequence of Operation Turning On I the power switch applies 230 VAC to the compressor motor hour meter transformer cooling fan and the printed circuit P C board Room air enters the compressor
43. concentration output of the unit is within specification 13 If the oxygen output concentration is not within specification rerun the autotune again 14 Reinstall the cover screws NOTE PC board is exploded away from control panel for clarity There is no need to remove P C Board from control panel Board FIGURE 22 1 Autotuning Model IRCBPO2AW Only Part No 1154245 73 Perfecto SECTION 22 TIMING Manual Tuning Model IRCSPAW Only NOTE For this procedure refer to FIGURE 22 2 1 Turn power off and unplug the unit Remove cabinet Refer to Removing Cabinet on page 22 Plug unit in but DO NOT turn on until instructed to below Locate the timing switch on the board e N Insert a small common or flathead screwdriver into adjustment screw of the timing switch Set the timing switch initially at the number 7 position Turn unit on 1 and set to max flow setting Wait 15 minutes for unit to stabilize If after 15 minutes of run time concentration is below specification change setting to the number 6 position 10 Let unit run ten minutes If concentration is lower still change the setting to position g NOTE You will find that the concentrator will perform better at either the higher or lower setting The normal adjustment range is between timing positions 3 and A 11 Continue to change setting one step at a time up or down until
44. concentrator IRCSPAW Indicator Lights Explanation RED light A Total Unit Shut Down Switch IMMEDIATELY to a back up oxygen supply Call Supplier IMMEDIATELY GREEN light VO On Off System okay Perfecto 70 Part No 1154245 SECTION 21 PURITY INDICATORS Model IRCBSPO2AW Model IRCS5PAW Sens a Below Normal Auto Shut Down Normal FIGURE 21 1 Display Control Panel Part No 1154245 71 Perfecto SECTION 22 TIMING SECTION 22 TIMING A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing Use extreme care when making adjustments to the timing switch DO NOT allow screwdriver or your hands to contact the P C Board when unit is plugged in and or on Turn unit off and unplug before adjusting timing switch Electrical shock is possible To accommodate the varying tolerances when replacing components an adjustable timer is used to control the shift time of the pressure equalization P E valve The SensO board allows for automatic microprocessor controlled adjustments of the P E shift times Non SensO boards allow for manual adjustment Autotuning Model IRCBPO2AW Only A WARNING DO NOT push the autotune button while powering up Otherwise the factory settings will be erased NOTE For this procedure refer to FIGURE 22 1 on page 73 1 Turn power off O and unplug the unit Remove
45. djustment screw While reading pressure gauge do one of the following Turn pressure adjustment screw clockwise to increase output pressure or Turn pressure adjustment screw counterclockwise to decrease output pressure Adjust until pressure reads a steady 34 5 3 45 kPa 5 0 5 p s i Allow the concentrator to run for ten minutes Retest the pressure by performing STEPS 6 9 to ensure proper operation Once required pressure is achieved reinstall cabinet Refer to Removing Cabinet on page 22 Refer to Troubleshooting on page 15 if you are unable to adjust or maintain 34 5 3 45 kPa 5 0 5 p s i Part No 1154245 49 Perfecto SECTION 12 EXCHANGER ASSEMBLY SECTION 12 EXCHANGER ASSEMBLY Replacing Heat Exchanger Assembly A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 12 1 on page 51 NOTE The heat exchanger assembly contains three components heat exchanger nine inch vinyl tube and connecting component 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 CAUTION Use care not to deform heat exchanger when installing removing or cleaning e Disconnect brass nut that secures the heat exchanger assembly to the compressor Detail A On the backside of the Perfecto loosen the clamp that secures the vinyl tube to the manifold assemb
46. dure 1 Turn the concentrator on and adjust the flowmeter to the maximum flow of the unit 2 Observe the flowmeter s flow indicator while connecting a 15 24 m 50 ft cannula tube to the outlet barb of the concentrator not shown 3 If the flow indicator fluctuates the outlet HEPA filter may need replacement Refer to Troubleshooting on page 15 Replace the Outlet HEPA Filter NOTE For this procedure refer to FIGURE 6 2 NOTE Perform this procedure during preventive maintenance or between patients depending on the outlet HEPA filter check results 1 Unplug the unit 2 Remove the cabinet Refer to Removing Cabinet on page 22 3 For easier access to the outlet HEPA filter remove the compressor inlet HEPA filter by grasping the compressor inlet filter pull outward and up until filter is dislodged from rubber base FIGURE 6 3 4 With a flat head screwdriver remove the tubing from both sides of the existing outlet HEPA filter by prying the tubing away from the outlet HEPA filter 5 Discard existing outlet HEPA filter 6 Connect tubing to both sides of the new outlet HEPA filter as shown below 7 Install cabinet Refer to Removing Cabinet on page 22 Perfecto 24 Part No 1154245 SECTION 6 PREVENTIVE MAINTENANCE Tubing Outlet HEPA Filter Tubing FIGURE 6 2 Replace the Outlet HEPA Filter Replacing the Compressor Inlet HEPA Filter NOTE For t
47. ectrode on the bottom of the zirconia sensing disk Because of the crystal structure of the zirconia only oxygen ions can pass through When the oxygen ions reach the bottom electrode the extra electrons are released from the oxygen ions and oxygen molecules return to the air The number of electrons is directly related to the oxygen concentration The electrons travel to the P C board where they are counted and the oxygen concentration reading is calculated A microprocessor on the P C board contains software that interprets the signal being received from the sensor It compares the signal to clinically acceptable limits Signals outside of the clinically acceptable limits generate responses in the form of lights audible indicators and or system shut down Operating Sequence Once the power switch has been turned I the SensO circuit will wait five minutes for the concentrator to begin producing clinically acceptable oxygen and the oxygen sensor to stabilize The GREEN light will illuminate indicating normal system operation while the oxygen sensor is warming up Perfecto 12 Part No 1154245 SECTION 2 INSTALLATION SEQUENCE OF OPERATION After five minutes if the oxygen purity exceeds 85 2 the GREEN light will continue to illuminate If the oxygen level is not above 85 2 after the first five minutes the system will continue to monitor the and wait for a maximum of 30 minutes from start up to reach 85 2
48. er loss No Problems Internal Status Indicators RED Off GREEN Off Unit unplugged power switch on alarm off Power loss Internal Status Indicators RED Off GREEN Off Unit plugged in power switch alarm off battery Free circuit drained No power at outlet Power cord Frayed Broken or damaged spade Spade connector from power cord loose or disconnected inside back of unit On Off switch a Disconnected wire b Faulty switch Circuit breaker tripped Part No 1154245 15 System Okay Battery Free Circuit drained Plug in cord and turn power switch ON 1 to recharge Check electrical outlet with a table lamp or voltmeter set on VAC scale If outlet isn t working check protective device in home s electrical panel or consult an electrician Also ensure that unit is properly plugged in DO NOT use extension cords Move to another outlet or circuit Reattach cord Replace power cord connectors on plug Reattach connector Check all electrical connections to the ON OFF switch for any disconnected wires If the concentrator does not come on at all and wiring is intact color code and remove wires one at a time Remove and replace with new one Transfer wires from old switch to new switch one at a time to the matching contact Reset breaker NOTE Breaker may trip to safeguard concentrator during a power surge If breaker trips IMMEDIATELY there is a p
49. ered trademark of Textron Inc Phillips is a registered trademark of Phillips Screw Company RexRoth is a registered trademark of BOSCH REXROTH AG GERMANY Rev D 11 12
50. f pressure in the concentrator does not fall into the specifications listed above refer to Troubleshooting on page 15 10 Turn the concentrator off O 11 Disconnect pressure gauge from HomeFill port and reinstall plug Pressure Gauge x 2 inch Back of Silicone Tubing Concentrator with Connector HomeFill Port or 4 1 FIGURE 25 2 Pressure Testing Part No 1154245 85 Perfecto Perfecto 86 Part No 1154245 CUSTOMER SERVICE AND WARRANTY INFORMATION CUSTOMER SERVICE AND WARRANTY INFORMATION Terms and conditions of the warranty are of general terms and conditions particular to the individual countries in which this product is sold Belgium amp Luxemburg Invacare nv Autobaan 22 B 8210 Loppem Tel 32 0 50 83 10 10 Fax 32 0 50 83 10 11 belgium invacare com www invacare be Danmark Invacare A S Sdr Ringvej 37 DK 2605 Br ndby Tel 45 0 36 90 00 00 Fax 45 0 36 90 00 01 denmark invacare com www invacare dk Deutschland Invacare GmbH Alemannenstrafse 10 D 88316 Isny Tel 49 0 75 62 7 000 Fax 49 0 75 62 7 00 66 kontakt invacare com www invacare de European Distrbutor Organisation Invacare Kleiststrafse 49 D 32457 Porta Westfalica Tel 49 0 57 31 754 540 Fax 49 0 57 31 754 541 edo invacare com www invacare eu com Espana Invacare SA c Areny s n Pol gon Industrial de Celr
51. he Compressor Compressor Compressor Head Plate Valve Plates Part No 1154245 SECTION 7 COMPRESSOR Fan NOTE For this procedure refer to FIGURE 7 4 1 Using two flat blade screwdrivers pry the fan off of the motor shaft under the center housing DO NOT pry under the fan blades NOTE Note position orientation of fan for reassembly Connecting Rod and Eccentric Assembly NOTE For this procedure refer to FIGURE 7 4 1 Rotate shaft to align eccentric s set screw with the access hole in the bottom of the compressor housing 2 Insert the 1 8 inch Allen wrench into the access hole in the bottom of the compressor housing 3 Loosen set screw 1 4 turn 4 Rotate connecting rod to top dead center 180 and slide the connecting rod eccentric assembly off the shaft through the opening in the housing 5 Secure the rod assembly in a fixture 6 Remove the sleeve from the connecting rod and discard Piston Cup NOTE For this procedure refer to FIGURE 7 4 1 Remove the torque screw discard from the piston cup retainer retain for reassembly 2 Remove the piston cup discard and wipe debris from the top of the connecting rod with a clean damp cloth Cylinder Sleeve NOTE Partial Torque Screw compressor shown Nee OW Piston Cu Rx C gt m di lt S Rod Top Connecting Rod Eccentric Fan NOTE As the piston travels up and Eccentric Set down
52. he manifold exhaust tube from the grommet Top of Manifold Exhaust Tube G lt 1 pu Rubber Grommet Tube ai Q Bottom of Manifold Exhaust Tube FIGURE 6 4 Replacing the Muffler Assembly Push the muffler assembly down through the opening in the sound box 6 7 Cut the two tie wraps around the muffler assembly 8 Separate the muffler assembly Detail A in FIGURE 6 5 9 Inspect the components to ensure they are clear 10 Do one of the following e Replace exhaust canister and throttling muffler if plugged or restricted e Install only new throttling muffler if exhaust canister is in good condition 11 Install new existing muffler assembly by reversing STEPS 2 10 Perfecto 26 Part No 1154245 SECTION 6 PREVENTIVE MAINTENANCE 12 Reinstall cabinet Refer to Removing Cabinet on page 22 5 2 p AD gt CY Top of Manifold V ENT Exhaust Tube M Sound Box EX N 0 BN E Bey 2652 Rubber Grommet gt Tie Wraps Throttling Muffler Exhaust Canister DETAIL Muffler Body 8 Tie Wrap Throttling _ Muffler Exhaust Assembly Muffler Muffler Grommet Grommet Exhaust Canister FIGURE 6 5 Replacing the Muffler Assembly Part No 1154245 27 Perfecto
53. his procedure refer to FIGURE 6 3 on page 25 NOTE Perform this procedure as needed depending upon the environment the concentrator is used in 1 2 Unplug unit Remove the filter access panel with air scoop by pressing down on center tab and pulling panel out Grasp the compressor inlet HEPA filter pull outward and up until filter is dislodged from rubber base Discard the existing compressor inlet HEPA filter Install new compressor inlet filter by inserting the filter into the rubber base Push the filter down until the rubber base touches the edge of the filter Reinstall the filter access panel Compressor Inlet 2 HEPA Filter x a WAN SHS Center s ie i N Filter Access Panel with Air Scoop Rubber Base FIGURE 6 3 Replacing the Compressor Inlet HEPA Filter Replacing the Muffler Assembly NOTE For this procedure refer to FIGURE 6 4 on page 26 and FIGURE 6 5 on page 27 Part No 1154245 Perfecto SECTION 6 PREVENTIVE MAINTENANCE NOTE Perform this procedure as needed depending upon the environment the concentrator is used in 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 3 Cut tie wrap that secures the bottom of the manifold exhaust tube to the F tube 4 Remove the bottom of the manifold exhaust tube from tube 5 Disconnect and remove the top of t
54. icators A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 21 1 on page 71 Operation The Perfecto with SensO Concentrator is equipped with an oxygen purity indicator This feature monitors the purity level of the oxygen generated by the concentrator If purity falls below alarm thresholds indicator lights on the control panel will illuminate NOTE Concentrator may be used during the initial start warm up time approximately 30 minutes while waiting for the purity to reach maximum When the unit is turned on the GREEN light will come on SYSTEM greater than 85 After five minutes the oxygen sensor will be operating normally and will control the indicator lights depending on oxygen concentration values The explanation of the indicator light functions are listed below IRC5PO2AW Indicator Lights Explanation NOTE Indicator lights are visible only when lit GREEN light O gt Normal Operation YELLOW light A Call supplier IMMEDIATELY You may continue to use the concentrator unless instructed otherwise by your supplier Be certain that backup oxygen is nearby RED light A Total unit shutdown Switch IMMEDIATELY to backup oxygen supply Call supplier IMMEDIATELY GREEN light with YELLOW light flashing Call supplier IMMEDIATELY Oxygen sensor malfunctioning you may continue to use the
55. led IMMEDIATELY plug the P E valve tubing to prevent sieve bed contamination 7 Install new Valve assembly IMMEDIATELY by reversing STEPS 3 5 8 Reinstall the compressor inlet HEPA filter Refer to Replacing the Compressor Inlet Filter on page 25 NOTE Retiming of the concentrator is necessary Refer to Timing on page 72 NOTE To ensure proper orientation the out port barb should face to the left side sieve bed when viewing from behind the unit 9 Run unit and check for leaks Refer to Leak Test on page 75 10 Reinstall cabinet Refer to Removing Cabinet on page 22 Part No 1154245 41 Perfecto SECTION 8 VALVE Part No 1154245 Sieve Bed Connectors Attach Here are not shown 7 Valve Terminals Spade 4 pA Valve Tubing P gt gt gt gt 2 S CX lt gt Y ac SE wee er ui 8 Ot A TES 9 e LL E oO gt d c gt iuo z a 9 t SECTION 9 SIEVE BEDS SECTION 9 SIEVE BEDS Replacing Sieve Beds A DANGER To prevent electrical shock AWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 9 1 on page 44 NOTE ALWAYS replace sieve beds in pairs
56. liers Tie wraps e Ground strap cuff Unplug unit Remove cabinet Refer to Cabinet on page 22 1 2 3 Cut the two tie wraps that secure the control panel to the sieve beds Detail A 4 Cut the two tie wraps that secure the P E valve assembly to the control panel not shown 5 Remove the two mounting screws that secure the control panel to the sound box Detail B 6 Remove the inch I D tubing from the top and bottom barbed fittings of the flowmeter Detail B 7 Cut tie wrap and remove I D tubing from the patient outlet barbed fitting behind the control panel Detail B 8 Remove the two mounting screws that secure the P C board to the control panel NOTE Before performing STEP 9 code all wires to ensure correct reinstallation 9 Remove spade connectors from circuit breaker hour meter and On Off switch Jumper wire harness from On Off switch to circuit breaker does not have to be removed 10 Remove the hour meter Refer to Replacing Hour Meter on page 63 Perfecto 52 Part No 1154245 SECTION 13 PANEL 11 Remove the On Off switch Refer to Replacing On Off Switch on page 61 12 Remove the circuit breaker by twisting the locknut on the outside of the control panel 13 Discard existing control panel 14 Install new control panel by reversing STEPS 3 12 15 Run unit and check for leaks at pressure sensor tubing on product tank cap Refer to
57. ly Not shown 12 Remove the four mounting screws that secure the 4 way valve manifold assembly together Detail A 13 Replace the necessary component s i e 4 way valve manifold or both 14 Loosely install mounting screws through 4 way valve and into manifold assembly NOTE Ensure the manifold gasket is in place on 4 way valve before installing Perfecto 64 Part No 1154245 SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY CAUTION Torque sequence and specification MUST be adhered to or possible damage to the 4 way valve could result 15 Tighten mounting screws in the sequence described below Detail B 16 Pre torque the mounting screws to 1 1 0 2 N M 10 inch lbs 2 inch Ibs using the torque sequence 17 The mounting screws can be now be torqued to 2 5 0 2 N M 22 2 inch Ibs in the same sequence 18 Connect spade connectors located on the side of the 4 way valve assembly 19 Position the 4 way valve manifold assembly in the base of the concentrator on the foam block in the orientation noted in STEP 9 20 Slide the vinyl tubes onto each side of the manifold valve assembly 21 Using hose clamp tool secure the vinyl tubes to 4 way valve manifold assembly with the clamps 22 Install the F tube into the 4 way valve manifold assembly 23 Secure the F tube to the 4 way valve manifold assembly with two tie wraps 24 Install the manifold exhaust tube into the
58. ly and remove the vinyl tube from the manifold assembly Detail Remove heat exchanger assembly by pulling vinyl tube through sound box gt Reverse STEPS 3 5 to install new heat exchanger Run unit and check for leaks Refer to Leak Test on page 75 ND Reinstall cabinet Refer to Removing Cabinet on page 22 Perfecto 50 Part No 1154245 SECTION 12 EXCHANGER ASSEMBLY Heat Exchanger Assembly Compressor DETAIL B lt tres lt IN N N ANE Manifold Assembly Sound Box FIGURE 12 1 Replacing Heat Exchanger Assembly Part No 1154245 51 Perfecto SECTION 13 PANEL SECTION 13 CONTROL PANEL Removing Control Panel A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing Before handling any P C boards you need to be properly grounded to prevent static damage to the components of the board A Static Cuff MUST be worn and properly grounded using an alligator clip Electrical conduit or a water pipe is normally sufficient when a known good ground is not available Care should be taken to ensure that the alligator clip contacts with bare metal surface NOTE For this procedure refer to FIGURE 13 1 on page 53 Tools Required Diagonal cutters e Flathead screwdriver inch ratchet 4 inch socket and V4 inch extension e P
59. n original orientation Secure into position using a rubber mallet Valve Plate NOTE For this procedure refer to FIGURE 7 3 on page 34 1 With the sleeve located and firmly seated on the housing replace the valve plate in the same manner as it was 2 Repeat STEP 1 for other valve plate NOTE Make sure the top edge of the sleeve locates in the O ring groove in the bottom of the valve plate CAUTION Make sure that the O ring is not twisted when seated in the groove of the bottom of the valve plate Compressor Heads NOTE For this procedure refer to FIGURE 7 3 on page 34 1 Place the heads on top of the valve plates 2 Tighten the head screws in a criss cross pattern to 4 2 N M 40 inch lbs Perfecto 38 Part No 1154245 SECTION 7 COMPRESSOR Compressor A WARNING To avoid personal injury or property damage rotate the fan by hand prior to connecting the unit to a power source Check for suction at the air inlet by placing your finger over the port as you rotate the fan You should feel a slight suction with each rotation of the fan If you DO NOT feel a suction but you feel or hear a thump as you turn the fan DO NOT connect the unit to a power source Review the assembly procedure for possible error NOTE For this procedure refer to FIGURE 7 7 on page 40 1 Reinstall compressor Refer to Replacing Compressor Assembly on page 30 2 Run unit and check for leaks around compressor hoses and compre
60. nch Allen Wrench Pressure Regulator Mounting Screws Pressure Sensor Tubing Product Tank NOTE For adjusting the regulator there is no need to remove the control panel NOTE Regulator shown was used before 07 01 12 for sensored concentrators and before 09 01 12 for non sensored concentrators Location of Product Tank FIGURE 11 1 Perfecto Replacing Regulator 48 Part No 1154245 SECTION REGULATOR Adjusting Regulator NOTE For this procedure refer to FIGURE 11 1 1 2 Turn unit on 0 Install pressure gauge onto oxygen outlet NOTE Use a 0 3 4 N M 30 p s i pressure gauge NOTE Check O pressure at oxygen outlet It should read a steady 34 5 3 45 kPa 5 0 5 p s i If pressure is not in specification proceed to STEP 3 If pressure falls within specification no adjustment is needed 3 4 5 6 10 11 12 13 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Plug unit in and turn power switch on 1 Using the access hole located on the control panel locate the pressure adjustment screw in center of pressure regulator top Perform one of the following A Regulators before 07 01 12 Sensored or 09 01 12 Non Sensored Insert a 5 32 inch Allen wrench into the pressure adjustment screw B Regulators after 06 30 12 Sensored or 08 31 12 Non Sensored Insert a 3 32 2 5 mm Allen wrench into the pressure a
61. ndicators RED Off YELLOW On GREEN On After 30 minutes of run time unit operates normally oxygen purity within normal range GREEN or YELLOW panel indicator should illuminate Perfecto 20 Place unit at least 30 5 cm 12 from any wall DO NOT place unit on pile or shag carpeting that may restrict air flow Clean or replace Refer to Cleaning the Cabinet Filter on page 23 Reconnect leads Replace fan Refer to Rebuilding the Thomas Model 2660 Compressor on page 33 Install fan with air flow arrow pointing down Clean heat exchanger Replace heat exchanger Refer to Replacing Heat Exchanger Assembly on page 50 Replace compressor Refer to Replacing Compressor Assembly on page 30 Replace capacitor Refer to Replacing Capacitor on page 32 Replace compressor Replace compressor Replace compressor Have line voltage inspected by certified electrician voltage regulator may be required and is obtainable from your local electric company Replace P C board Refer to Replacing P C Board on page 57 Unit may need retiming after P C board replacement Refer to Timing on page 72 Part No 1154245 SECTION 4 TROUBLESHOOTING SYMPTOM PROBABLE CAUSE SOLUTION Unit Not Operating Transformer assembly Internal Status Indicators a Assembly connector Reattach connector RED Off disconnected GREEN Off b Faulty transformer assembly Replace tr
62. nt is within spec 5 p s i 0 5 max 34 4 kPa 6 89 replace flowmeter Refer to Replacing Flowmeter on page 62 Outlet HEPA filter a Dirty or plugged a If low flow conditions persist replace outlet HEPA filter Refer to Replacing the Outlet HEPA Filter on page 24 Unit Excessively Loud Pneumatic exhaust a Muffler cracked damaged or a Replace Refer to Replacing the missing Muffler Assembly on page 25 Muffler tubing disconnected or b Reconnect or replace tubing damaged Compressor inlet filter missing and or Replace compressor inlet filter Refer orange sticker removed to Replacing the Compressor Inlet HEPA Filter on page 25 Compressor removed a Replace Compressor Refer to Replacing Compressor Assembly on page 30 Incorrect style of inlet filter a Replace with factory OEM sound aftermarket reduced style inlet HEPA filter Part No 1154245 19 Perfecto SECTION 4 TROUBLESHOOTING SYMPTOM PROBABLE CAUSE SOLUTION Unit Overheats Base exhaust vent plugged or restricted Cabinet filters dirty or blocked Fan a Leads to fan disconnected b Defective fan c Fan installed upside down Heat exchanger a Dirty or plugged b Damaged Compressor a Defective Faulty capacitor Bad motor windings Worn seals Bad bearings Line voltage excessive surge Oxygen Purity P C board defective Good Internal Status Indicators Control Panel I
63. our rubber grommets on each corner 8 Lift cooling fan up and dislodge the rubber grommets from the soundbox Detail B Remove rubber grommets from the existing cooling fan Detail 10 Note the orientation of the installed rubber grommets There are two recessed areas on the rubber grommet The larger recessed area of the grommet is installed in the fan The smaller recessed area is installed in the sound box 11 Inspect rubber grommets for damage If damage is found do not use Order new rubber grommets before installing fan 12 Install rubber grommets into new cooling fan with larger recessed area installed in the fan Detail C CAUTION Fan MUST be positioned properly so air from the fan blows DOWN onto the compressor see air flow arrow on back of fan or damage to the unit will occur 13 Position cooling fan onto soundbox Detail B 14 Pull rubber grommets down into the sound box Detail D Perfecto 54 Part No 1154245 15 16 17 18 19 20 21 22 23 SECTION 4 COOLING FAN Connect spade connectors to fan terminals on side of cooling fan Detail B Move resonator housing back into position Detail A Secure the resonator housing to the soundbox with the three mounting screws Two in the top and one on the back near the bottom of the housing Detail A If necessary reconnect the intake valve on the compressor assembly Reinstall control
64. pressure at product tank Pressure a Shifts at wrong pressures should rise to 144 79 kPa 21 p s i at shift point If not replace P C Board Refer to Replacing P C Board on page 57 Perfecto 18 Part No 1154245 SECTION 4 TROUBLESHOOTING SYMPTOM PROBABLE CAUSE SOLUTION Low Concentration Flowmeter Continued a Flowmeter opened beyond a Return flow to maximum setting maximum flow rate b Cracked or broken fitting b Replace fitting c Input tubing leaking or loose c Repair or replace Refer to Replacing Flowmeter on page 62 Timing To accommodate for varying tolerances when replacing components an adjustable timer is used to control the shifting of the Pressure Equalization P E valve Refer to Timing on page 72 P E valve a Bad coil a Replace P E valve b Restrictor blockage b Replace P E valve Refer to Replacing P E Valve on page 41 Inspect P C board restrictor tubing Replace P C board Unit may need for kinks or tears retiming after board replacement Refer to Replacing P C Board on page 57 Fluctuating Flow Regulator Flowmeter a Incorrectly set regulator a Check pressure at oxygen outlet b Flowmeter malfunction Adjust regulator b If flow is still unstable check for leaks starting at the compressor outlet fitting through all pneumatic connections If no leaks are found and flow is still fluctuating replace the regulator If pressure at test poi
65. robable short in the unit Check for pinched or charred wires If the breaker does not trip run unit for approximately two hours The circuit breaker should be less than 10 ohms If breaker trips again there is an internal problem Contact Invacare Technical Service Perfecto SECTION 4 TROUBLESHOOTING SYMPTOM PROBABLE CAUSE SOLUTION Power Loss board Continued a P C board damaged Replace P C Board Refer to Internal Status Indicators Replacing P C Board on page 57 RED Off b Loose or damaged connector Repair or replace connector GREEN Off Unit plugged in power switch alarm off Battery Free circuit drained Internal Power Transformer assembly Loss Senso a Faulty Replace Refer to Replacing the Internal Status Indicators Transformer on page 60 RED Off b Connector loose or Reattach connector GREEN Off disconnected Alarm may or may not beon Faulty wiring Replace transformer assembly Refer Control Panel Indicators to Replacing the Transformer on RED Off page 60 YELLOW Off P C board faulty Replace P C board Unit requires retiming GREEN Off after P C board replacement Refer to Fan operates Compressor Replacing P C Board on page 57 not operating High Pressure P C board Internal Status Indicators a Malfunction Set flow to max L min for concentrator Check voltage across RED One Flash Pilot Valve on volt DC scale If GREEN Two Flashes
66. rod top with smooth edge facing up 2 Place piston cup on rod top making sure it is centered 3 Place retainer on top of piston cup and seat retainer in rod top pocket making sure the retainer and cup align properly along with screw holes gt Insert new screw into rod top and torque to 3 39 30 inch lbs Connecting Rod Eccentric Assembly NOTE For this procedure refer to FIGURE 7 4 on page 35 1 With gloved hand or clean cloth pre form piston cup if necessary 2 Gently slide cylinder sleeve up and over cup to fully form it Part No 1154245 37 Perfecto SECTION 7 COMPRESSOR CAUTION DO NOT lubricate or use oil on any moving parts The compressor eccentric uses a precision sealed bearing DO NOT crimp the piston cup when you replace the sleeve If the cup is crimped it MUST be replaced 3 With bearing side of connecting rod eccentric assembly facing the center motor of the compressor slide the assembly onto the shaft bringing it flush to the motor bearing NOTE Make sure the eccentric set screw is positioned over the flat of the shaft 4 Using the access hole tighten set screw to 4 2 40 inch lbs Detail A of FIGURE 7 4 5 Hold the sleeve down to the housing with one hand and slowly rotate the eccentric with the other hand to ensure all the components are aligned properly Fan NOTE For this procedure refer to FIGURE 7 4 on page 35 1 Reinstall the fan onto the shaft i
67. rounded to prevent static damage to the components of the board A Static Cuff MUST be worn and properly grounded using an alligator clip Electrical conduit or a water pipe is normally sufficient when a known good ground is not available Care should be taken to ensure that the alligator clip contacts with bare metal surface When removing quick disconnect terminals DO NOT pull on wire itself as damage to the connection may occur Hold down the P C board with one hand and pull upward with other hand with a slight rocking motion to remove the terminals Before installing any P C boards ensure that all insulators are in place NOTE For this procedure refer to FIGURE 15 1 on page 59 1 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Remove control panel Refer to Removing Control Panel on page 52 gt Do following A Disconnect wiring harnesses from PC board A WARNING DO NOT remove oxygen sensor tubing from P C board Remove from regulator ONLY DO NOT remove the pressure sensor tubing from P C board Remove from top of product tank only Damage to oxygen sensor assembly or pressure sensor could occur A faulty sensor may result in improper oxygen delivery and harm to the user B Disconnect pressure sensor tubing from product tank not P C Board C For concentrators that have O2 sensor disconnect the oxygen sensor tubing from regulator fitting Refer to Replacing Regulator on p
68. rque wrench e Flat blade screwdriver attachment or 1 4 inch hex socket for torque wrench for flapper valve screw Two flat blade screwdrivers Rubber Mallet Phillips screwdriver attachment for torque wrench for retainer screws CAUTION DO NOT lubricate or use oil on any moving parts The compressor eccentric uses a precision sealed bearing Therefore additional lubrication is not necessary Part No 1154245 33 Perfecto SECTION 7 COMPRESSOR Removing Compressor and Compressor Heads Compressor 1 Unplug concentrator and carefully remove compressor from concentrator Refer to Replacing Compressor Assembly on page 30 Compressor Head Plate NOTE For this procedure refer to FIGURE 7 3 1 Clean loose dirt from the outside of the compressor 2 Use the Torx T 25 torque wrench and loosen the eight head screws 3 Note head placement before removing compressor head plate 4 Remove the compressor head plate Valve Plates NOTE For this procedure refer to FIGURE 7 3 1 Note the position of the plates before removing 2 Lift off the valve plate on one side 3 Repeat for the other side NOTE Note the position of the tab on valve plate for reassembly NOTE To avoid confusion ONLY service one end of the compressor at a time Perfecto 34 Head Screws Compressor Head 1 Plate Compressor FIGURE 7 3 Removing Compressor and Compressor Heads Rebuilding t
69. se 260 CH 4108 Witterswil Tel 41 0 61 487 70 80 Fax 41 0 61 487 70 81 switzerland invacare com www invacare ch United Kingdom Invacare Limited Pencoed Technology Park Pencoed Bridgend CF35 5HZ Tel 44 0 1656 776222 Fax 44 0 1656 776220 UK invacare com www invacare co uk Portugal Invacare Lda Rua Estrada Velha 949 P 4465 784 Le a do Balio Tel 351 0 225 1059 46 47 Fax 351 0 225 1057 39 portugal invacare com www invacare pt Part No 1154245 87 Perfecto 0120 Invacare Corporation www invacare eu com USA One Invacare Way Elyria Ohio USA 44036 2125 440 329 6000 800 333 6900 Technical Services 440 329 6593 800 832 4707 EU Representative Invacare GmbH KleiststraBe 49 D 32457 Porta Westfalica Deutschland Tel 49 0 5731 754 0 Fax 49 0 5731 754 52191 Part No 1154245 Invacare Rehabilitation Equipment Suzhou Co Ltd No 435 Xieyu Street SIP Suzhou Jiangsu PRC 215026 Tel 86 5 12 62586180 Fax 86 512 62586167 2012 Invacare Corporation All rights reserved Republication duplication or modification in whole or in part is prohibited without prior written permission from Invacare Trademarks are identified by and All trademarks are owned by or licensed to Invacare Corporation or its subsidiaries unless otherwise noted Teflon is a registered trademark of DuPont Corp Torx is a regist
70. se care not to cut oxygen sensor tubing when clamping the oxygen sensor tubing 6 Within 30 minutes the Oxygen Sensor Alarm should activate and the RED panel light indicator will illuminate The compressor will shut down with the alarm 8 inch 1 0 Oxygen Sensor Tubing Clamp Off Flow FIGURE 24 3 Oxygen Sensor SENSO ALARM THRESHOLD LABEL STATUS INDICATOR LIGHTS SYMBOL SYSTEM OKAY GREEN Indicator Light O2 over 85 2 Between 73 3 YELLOW Indicator light to 85 2 A YELLOW Solid B YELLOW Flashing Sensor Failure Call a qualified technician SYSTEM FAILURE RED Indicator light Below 73 3 Continuous Audible Alarm Sieve GARD Compressor Shutdown Call a qualified technician Perfecto 82 Part No 1154245 SECTION 24 ALARM TEST P E Valve Coil Test NOTE For this procedure refer to FIGURE 24 4 NOTE P E Valve Coil Alarm sequence occurs when the P E Valve Coil connection or P C Board Circuitry has failed 1 With the unit running and flow set at 5 L min remove one YELLOW wire from the valve coil The valve coil alarm should activate within 10 seconds Valve 2 Reinstall cabinet Refer to Removing Cabinet on page 22 NOTE If any alarm fails to perform to specification contact Invacare Technical Service Yellow Wires FIGURE 24 4 Valve Coil Test NOTE If problems arise during test contact
71. shut down Low Pressure Alarm w compressor shutdown Battery Free Power Loss Alarm SensO Oxygen System SensO Model Potential Obstruction Alert Shipping Weight 23 kg kg 50 Ibs 2 Ibs Operating Ambient 50 F 95 F 10 35 C at 20 60 relative humidity Temperature Oxygen Output Less than Ambient 3 C 6 F Cabinet Impact Resistant flame retardant plastic cabinet that conforms to UL 94 V0 Part No 1154245 7 Perfecto TYPICAL PRODUCT PARAMETERS Electrical No extension cords Placement No closer than 30 5 cm 12 inches from any wall furniture drap eries or similar surfaces Tubing 2 1 7 ft cannula with a maximum 15 2 50 ft of Crush Proof Tubing DO NOT pinch Relative Humidity 20 to 60 Time of Operation Up to 24 hours per day Recommended Storage and Shipping Temper 29 C to 65 C 20 F to 1509 at 15 95 relative humidity ature Standards and Regulatory Listing IRCSPO2AW IRC5PAW IEC EN61000 3 2 IEC EN61000 3 3 IEC EN 60601 1 Al A2 IEC EN 60601 1 2 IRC5PO2AW Models Only 1508359 CE marked model IRCSPO2AW IRCSPO2AW INDICATORS LABEL O PURITY INDICATOR LIGHTS SYMBOL LED SYSTEM OKAY GREEN Indicator Light 02 85 2 Between 73 3 YELLOW Indicator light 8596 2 A YELLOW Solid B YELLOW Flashing Sensor Failure Call a qualified technician SYSTEM FAILURE RED Indicator Light Below 73 43
72. ssor Inlet HEPA Filter removed from illustration for clarity FIGURE 9 1 Replacing Sieve Beds Perfecto 44 Part No 1154245 SECTION 10 VALVES SECTION 10 VALVES Replacing Check Valves A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 10 1 on page 46 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 NOTE Replace one or both check valves when performing this procedure The check valves are one way directional and can be checked by passing air through them Air should flow in one direction only 3 It may be necessary to remove the compressor HEPA inlet filer Refer to Replacing the Compressor Inlet HEPA Filter on page 25 4 Remove the tie wrap securing the lower 4 inch PVC tubing to the product tank 5 Remove not shown securing the upper inch PVC tubing to barb ont he sieve bed not shown A WARNING The check valves are one way directional and MUST be installed correctly The letters VAC are printed on the check valves The check valves MUST be installed with the on the underside of the check valve Low system pressures and eventual bed contamination will result if check valves are not properly installed CAUTION DO NOT puta check valve on the regulator outlet tubing Otherwise damage may result The regulator outlet
73. ssor tubes Refer to Leak Test on page 75 3 Take pressure readings to ensure proper system pressures Refer to Checking Sieve Bed Pressure on page 84 Part No 1154245 39 Perfecto SECTION 7 COMPRESSOR NOTE Compressor is shown assembled Compressor parts are shown exploded along direction of arrows COMPRESSOR PARTS LEGEND 1 Connecting Rod Eccentric amp Bearing Assembly 10 Valve Restraint 2 Piston Cup 11 Valve Keeper Strip 3 Screw Piston Cup Retainer 12 Valve Flapper Intake amp Exhaust 4 Piston Cup Retainer 13 Valve Plate 5 Cylinder Sleeve 14 Screw Valve Flapper 6 Head 15 O Ring Valve Plate 7 O Ring Head Gasket 16 Fan Gray 8 Screw Head 17 Fan Black 9 Valve Plate Assembly FIGURE 7 7 Compressor Exploded View Perfecto 40 Part No 1154245 SECTION 8 P E VALVE SECTION 8 P E VALVE Replacing P E Valve A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 8 1 on page 42 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 3 Remove the compressor inlet filter Refer to Replacing the Compressor Inlet HEPA Filter on page 25 4 Remove spade connectors from valve terminals 5 Remove tie wraps from valve tubing 6 Remove PE valve assembly from tubing CAUTION If P E valve is not to be instal
74. the concentration is the highest value achievable 12 Once concentration has reached specification retiming is complete 13 Reinstall cabinet Refer to Removing Cabinet on page 22 Control Panel P C Board Et 03 26 Manual Timing Switch FIGURE 22 2 Manual Tuning Model IRCBPAW Only Perfecto 74 Part No 1154245 SECTION 23 LEAK TEST SECTION 23 LEAK TEST A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing Leak Test NOTE For this procedure refer to FIGURE 23 1 on page 76 1 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Plug in unit Turn the concentrator on 1 N Let concentrator run for 20 minutes A WARNING Apply small amount of leak test solution to fittings only Avoid all other components DO NOT leak test 4 way valve body Carefully leak test for pressure leaks around sieve bed hoses at 4 way valve DO NOT allow leak test solution to enter into 4 way valve and system D With leak test solution or equivalent soapy water leak test the following A The two sieve bed hose connection at the 4 way valve manifold assembly Detail A Leak test the hose fitting on center port of 4 way valve manifold assembly Hose connections to top and bottom fittings of sieve beds P E valve hose connections Hose fittings at product tank cap and check valves Detail B
75. to ensure that both beds are in optimum condition 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 3 Remove compressor inlet HEPA filter Refer to Replacing the Compressor Inlet HEPA Filter on page 25 B Remove tie wraps and disconnect valve tubing and check valve tubing from top of sieve beds 5 Remove the four large tie wraps two on each sieve bed 6 Tilt sieve beds back and lift up Rest sieve beds on rear of base N Using a hose clamp tool remove the clamp and reinforced tubing from bottom of both sieve beds and remove sieve beds CAUTION DO NOT remove plastic caps from new sieve bed fittings until ready to install new beds Severe sieve contamination can occur if uncapped beds are exposed to air 8 Remove plastic caps from the top and bottom fittings of the new sieve beds 9 Install new sieve beds reversing STEPS 3 8 10 After replacing sieve beds retiming is necessary Refer to Timing on page 72 11 Run unit and check for leaks Refer to Leak Test on page 75 12 Reinstall cabinet Refer to Removing Cabinet on page 22 Part 1154245 43 Perfecto SECTION 9 SIEVE BEDS Valve Check Valve Tubing Assembly _ Check Valve Tubing Tie Wraps Tie Wraps Tie Wrap Valve Tubing Valve ubing Tie Wraps Tie Wrap Clamp Sieve Bed Reinforced Tubing attaches HERE not shown NOTE Compre
76. tor from electrical outlet before servicing NOTE For this procedure refer to FIGURE 11 1 on page 48 1 Unplug unit 2 Remove cabinet Refer to Removing Cabinet on page 22 3 concentrator models with the SensO unit ONLY remove the 1 8 inch tubing to oxygen sensor housing 4 Remove the four mounting screws that secure regulator to product tank cap 5 Remove regulator from product tank lid ensuring that the O rings are removed 6 Clean mounting surface of product tank cap 7 Install the two rings for the NEW regulator onto the ports underside of the NEW regulator before installation A WARNING Ensure proper installation of regulator Note flow arrow on regulator This MUST face toward the regulator outlet tubing or flow will be interrupted causing system shutdown 8 Install new regulator onto product tank cap by reversing STEPS 3 and 4 9 Torque mounting screws to 56 11 5 1 inch Ibs 10 On units with SensO reinstall 1 8 inch tubing to oxygen sensor housing 11 Adjust regulator pressure if necessary Refer to Adjusting Regulator on page 49 12 Run unit and check for leaks Refer to Leak Test on page 75 13 Reinstall cabinet Refer to Removing Cabinet on page 22 Part No 1154245 47 Perfecto SECTION REGULATOR DETAIL REGULATORS AFTER 07 01 12 SENSORED AND 09 01 12 NON SENSORED Pressure Regulator Top Pressure Adjustment Screw 5 32 i
77. tubing is identified by the flow arrow on the side of the regulator which points to it 6 Position the check valve assembly so is on the underside of the check valve to ensure proper orientation 7 Use two tie wraps not shown to secure the inch PVC tubing to the product tank and to the barb on the sieve bed where previously removed 8 Secure the check valve s by installing new tie wraps to the 1 4 inch PVC tubing where previously removed NOTE Ensure check valves are not crossed Left barb product tank check valve goes to left barb on sieve bed Right barb product tank check valve to right barb on sieve bed Part No 1154245 45 Perfecto SECTION 10 VALVES 9 Reinstall compressor inlet HEPA filter Refer to Replacing the Compressor Inlet HEPA Filter on page 25 10 Run units and check for leaks Refer to Leak Test on page 75 11 Reinstall cabinet Refer to Removing Cabinet on page 22 Location of Product Tank Upper PVC Inlet Tubing Connect to barb on sieve bed Check Valve Regulator Outlet Tubing Check Valve Lower 4 PVC Inlet Regulator WT Tubing Connect to product tank Tie wrap Flow Arrow Product Tank FIGURE 10 1 Replacing Check Valves Perfecto 46 Part No 1154245 SECTION REGULATOR SECTION REGULATOR Replacing Regulator A DANGER To prevent electrical shock ALWAYS disconnect concentra
78. uld NOT use leak detector on the valve 4 Way Valve Use 0 206 84 kPa 0 30 p s i pressure gauge to monitor system pressure swings and also record the amount of time it takes to achieve a shift full charge and full purge FIGURE 23 2 4 Way Valve Function Test Perfecto 78 Part No 1154245 SECTION 24 ALARM TEST SECTION 24 ALARM TEST Alarm and Sensor Tests A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing Check alarms periodically for proper function Power Loss Alarm With the unit running remove the line cord from power source The power loss alarm mode should sound the audible alarm IMMEDIATELY or within 30 seconds NOTE With the unit unplugged and inoperable for a short period of time the battery free circuit will be drained If power failure alarm does not sound with unit unplugged and power switch on the battery free circuit is drained It will recharge when unit is plugged in and switched on Low Pressure Test NOTE For this procedure refer to FIGURE 24 1 on page 80 1 There are two separate failure modes for Low Pressure Low producttank pressure Pressure in tank drops below a preset value typically 48 26 kPa 7 p s i Failure to reach the set point pressure within a prescribed time limit or Timeout Failure Test One 1 With unit running set flow at maximum rating 2 When the main valve switches
79. ve flowmeter from front of control panel Install new flowmeter reversing STEPS 4 5 Reinstall control panel Refer to Removing Control Panel on page 52 DUM e Run unit and check for leaks where 1 4 PVC tubing engages flowmeter barbed fittings Refer to Leak Test on page 75 10 Reinstall cabinet Refer to Removing Cabinet on page 22 Flowmeter Barbed Fittings Back of Flowmeter Palnuts Flowmeter Control Panel FIGURE 18 1 Replacing Flowmeter Perfecto 62 Part No 1154245 SECTION 9 HOUR METER SECTION 19 HOUR METER Replacing Hour Meter A DANGER To prevent electrical shock ALWAYS disconnect concentrator from electrical outlet before servicing NOTE For this procedure refer to FIGURE 19 1 1 Unplug unit Remove cabinet Refer to Removing Cabinet on page 22 Remove control panel Refer to Removing Control Panel on page 52 N Remove and label the two hour meter connectors and wires connected to back of hour meter Spread retaining clips on hour meter housing that secure hour meter to control panel Remove hour meter by pushing meter through front of control panel Install new hour meter reversing STEPS 4 6 Reinstall control panel Refer to Removing Control Panel on page 52 g Reinstall cabinet Refer to Removing Cabinet page 22 Hour Meter Hour Meter Housing AN Hour Meter NS gt Connectors lt a gt
80. ve stem clockwise until snug Torque to 2 82 565 25 inch Ibs 5 inch Ibs 15 Install new label onto pilot valve coil yoke 16 Position pilot valve coil with yoke at an approximate 90 angle to the right as viewed from the front of valve 17 Use the flat blade screwdriver and hold the pilot valve stem in place 18 Tighten locknut clockwise with the 9 16 inch wrench until snug to secure the stem and coil with yoke DO NOT overtighten Torque to 2 26 34 20 inch lbs 3 inch Ibs CAUTION DO NOT overtighten locknut when installing it onto pilot valve stem Damage to the plastic manifold may occur 19 Plug power cord in and turn concentrator ON I to ensure proper operation 20 Reinstall cabinet Refer to Removing Cabinet on page 22 21 If any difficulties are encountered in this installation contact Invacare Technical Service at 800 832 4707 Perfecto 68 Part No 1154245 SECTION 20 4 WAY VALVE MANIFOLD ASSEMBLY DETAIL A Manifold Opening O Ring Air Flow Passage Assembled View Exploded View NOTE DO NOT disassemble Locknut Spade Connectors attach here Leave Wire Connectors Intact Valve Pilot Valve Stem Slotted Pilot Valve Poppet Stem Valve Tapered End FIGURE 20 2 Replacing Pilot Valve Poppets and O Rings Part No 1154245 69 Perfecto SECTION 21 PURITY INDICATORS SECTION 21 PURITY INDICATORS SensO Alarm Ind
81. via the cabinet filter and the compressor inlet filter The air is compressed by the WOB L pistons in the compressor to a pressure of 144 79 kPa 21 p S i As increased pressure creates increased temperature a heat exchanger is used to lower the temperature before the air enters the 4 way valve It is then channeled to a sieve bed containing the adsorption material Restriction downstream of the sieve bed causes pressure to build up inside the sieve bed which is necessary for the adsorption process A small amount of relatively pure oxygen enters the top of the second bed through a restrictive leak in the pressure equalization P E valve with the balance entering a storage tank The nitrogen removed is exhausted back from the bed through the 4 way valve into room air A muffler is located at the exhaust end of the valve to muffle the sound of the exhaust as it exits the concentrator The oxygen not being used to exhaust is channeled into the storage tank The pressurized oxygen is regulated down to 34 4 kPa 5 p s i enters an accurate flow measuring device flows through Outlet HEPA filter and check valve then out to the patient Part No 1154245 11 Perfecto SECTION 2 INSTALLATION SEQUENCE OF OPERATION The electrical activation of the 4 way Valve is accomplished every 8 to 15 seconds by the pressure sensor and P C Board electronics when the pressure reaches a set point of 144 79 kPa 21 p s i output flows 4 L min and above or 110 3

Download Pdf Manuals

image

Related Search

Related Contents

Sharp FU440E air filter  NOVY Inductie Pro  R&S ZVA Service Manual  - E-Theses  001-022 STILO ITA  

Copyright © All rights reserved.
Failed to retrieve file