Home
        Service Manual - PHD Powerhouse
         Contents
1.                GPO S   GB   GO   GBP BB   NIL  b  Le  N   LAT le   Lo     Tl T   N  LA ls  te  N ta  LE   itc  DO              iM H  OUTPUT  iA  INPUT  GND   Faith  BATT     fi  OUTPUT  5 A  INPUT GNDI Hi it  BATT                                     Ol                   BELA a  a          APACHE       No Lio Lz0 L30  um  B  R GR    Diagram 7 paralleled system of the    s 3 units connect line diagram    7 2 Three or more units paralleled system diagnosis program     Three or more units paralleled system diagnosis program is similar to two units  paralleled system  the difference is single unit exit program and paralleled system  recover program     D Single unit exit program    A  Turn off all UPS from panel    B  Turn off the failure UPS bypass  power  battery and output breaker    C  Pull out the failure UPS paralleled line  set the UPS to single unit  act  as 4 2 2 in the manual    D  Turn on the other UPS from the panel  if the load is bigger than one unit output nominal  load  the load should be turned off or reduced       Paralleled system recover program    A  Turn off the load  turn off all the UPS from the panel and turn off their  output breaker    B  Turn off the bypass  power  and battery breaker of all the UPS    C  Connect the paralleled line and set the UPS that used to be failure to  paralleled mode    D  Turn on power  bypass breaker of all the UPS  and turn on the battery breaker    after the rectifier start normally  turn on all UPS from the panel     50    
2.      3 6 4W GND    Battery voltage     VDC   Charge current  A     12V X 29 348V    Voltage  Vac  L   N  220 L L 380    Mains input normal  automaticly synchronize the mains  Mains failure  50    Frequency  Hz  ae     Three line 100      load imbalance  lt 2   allow 100  imbalance    Sd stabilization    linear load THD lt 3   125  rated load  15 minute   150  rated load  1 minute        E Capacity  KVA     Maintain bypass Provide no transfer time maintain bypass switch  Start up function Support DC start up function    Three phase input voltage  input frequency  three phase output voltage  load     LCD displa  si battery voltage  battery charge and discharge current and so on    LED display UPS working status and failure indication  Alarm function Input abnormal  battery low  over load  failure    Communication provide stem point communication and RS232 RS485  achieve UPS  function aptitude supervise    Battery testing  detail see in LCD display working battery testing control page    function introduction        output short circuit  over load  over temperature  battery low   output over  Protection  voltage   low voltage    Meets standard GB T 7260 3 2003  Noise  dB   Cooling mode Ventilator    Working  0 40  temperature CC     Relative humidity 0   95     95   No condensation      condensation    Dimension   wide    X length xX 1200 X 800 X 1600  height   mm     Weight  Ko  1180 1300      The index fluctuation forgives a not another line to notify            Tab 2 2 Techni
3.      ese     OV EE ER H i       ULC    Von p 23 2V    9  005  OSkHz    EE N basal eel Pe ee i    mr Ma SD re EE EK i RARE Inti i   lola  i eed reni 3          The square wave signal of diagram 5 14 main board 9 KHzseses measure and its wave    30    B  Test the PWM board  3 board  IC3 1P  7P signal with a oscillograph  the wave should  be two anti phase 9KHz triangle wave  as shown in figure 5 13  It can be tested with a  multimeter  the value tested should be 2 1 0 2Vac  0 1 0 1VDC  GND connect to right  pin of R54         T1  Vp p 13 5 0 3 V f 9  00   0  OB kHz    Picture 5 13 Triangle wave signal test and waveform    C  Press    ON    key to turn on the UPS  test the three phase PWM board IC9 1P   the waveform should be sine wave and there is a slow start period  the phase  differ between any two of the three sine wave of PWM board should be 120      It can be tested with a multimeter  the value should be 1 0 0 2Vac  0 1   0  IVDC  GND connect to right pin of R54      a a i    H p       31       i        ARE oe ia EE EE EE N N EER EN N  EEUE Fr Ja re A alas siii    Figure 5 14 PWM board sine signal test and waveform    D  Test left pin of R113  R115  R104  R107 of the three PWM board  the waveform is SPWM  wave  its Vp p is 12  1V  as shown in figure 5 15  It can be tested with a multimeter  the value is  6 2 0 2Vac  6 2  0 2VDC        YVp p l1l2Yy  A    9KHx    PRE TE JE    Figure 5 15 PWM board SPWM signal test and waveform    E  Test inverter driver board four SPWM driv
4.   Is the battery bad     Replace the battery    Y    Replace the DC contactor       Is the DC contactor    bad      Y  Is the rectifier voltage    Replace the fan control board    sampling hall bad     Replace the main board    Inverter test    i      end    37    5 4 2 Program describe     It is very possible that the symptom caused by battery bad  especially for the UPS that has  been used for more than three years       Battery test  The UPS has battery test function  in the panel LCD there is a battery test  function menu  there are three items in it  as shown in figure below  Choose the GENERAL  TEST or DEEP TEST  the UPS will discharge the battery and test it  if the battery is bad  the  panel LCD will display alarm message     HANUAL TEST  BATTERY MANAGEMENT STATUS   OFF     gt  HANUAL TEST  gt  ABOART TEST  BOOST CHARGE GENERAL TEST    DEEP TEST         Test the DC contactor  Test the voltage between the two control pins of the DC  contactor with a multimeter  the value should be 197 2VDC  and the voltage between two  contact pin should be 0  else the DC contactor should be damage      Test the rectifier voltage sampling hall  Check the rectifier voltage that  panel LCD display  if the value is much smaller than it is tested in fact  the  rectifier voltage sampling hall should be bad     5 5 Symptom 5  In utility mode UPS is normal  but the battery breaker will    trip when it is turned on in battery mode     Abnormal symptom  Diagnosis ready program  Replace DC conta
5.  17  42 2 main board DIP SWitCh Seting arr 18  4 2 3 rectifier control board DIP switch setting oro 19  4 3 Potennal iumetion intfoduciloni        scorci lele i ata 19  4 TE ONO board  Eee 19  SOZZI ille lia 19  APA M 010  110 ERE ME 20  ER ES DE   K controll na SE tele rel Ao taht ee rela aaa eaa Aes eae 20  LODO clelia 21   4 4 Main board indicate light introduce  ese ee nenna ena RR Ee E ee ee ee ee ee ee ee ee ee ee ee 21  5  Some familiar symptoms and diagnosis program                      ee ee ee ennen ennen eee e ener eee ener reeeee 22    SMP ONLINE 22  After turn on the power breaker or bypass breaker  the panel PHASE light is on and the    buzzer Deep  Oh vvs 22  NPD 22  Daas DNS OT NNN 23  POSE 23  5 3 Symptom 3  The UPS power breaker trip when it operation normally              rrrrrrrrrrrrrrnn 36  5 4 Symptom 4  When the utility is failure the UPS shutdown output and the panel BAT LOW  i  dicate e ER 37  DENN 37  DA PN Ne  38    5 5 Symptom 5  In utility mode UPS is normal  but the battery breaker will trip when it is  Cured  on i battery Mode  HP 38  5 6 Symptom 6  In utility mode UPS is normal  but the UPS battery low protection enable  when battery breaker is turned on in battery mode  and the panel BAT LOW light on and the    puzzer bee sella 39  Sue  DENS TOT ON  Fer 39  STEN 39   5 7 Symptom 7  The UPS switch to bypass  panel FAULT indicate light on and buzzer beeps   Conumualle  sc ee eee eee eli 40  S L1 Diagnosis propra ie iS N alee aed GE lille ila 41 
6.  312 PO ON rail 42    5 8 Symptom 8  Turn on the bypass  power breaker  turn on the UPS and protection enable as  s    mas hemmer 44    5 9 Symptom 9  The protection enable as soon as the UPS switch to inverter output after it is    red bout  0 ae 44   6  Series Connection Hot Standby System diagnosis program                      i 45  6 1 The standby UPS of series connection hot standby system diagnosis program                 45   6 2 The main UPS of series connection hot standby system diagnosis program                      46  62 TDAI PN PR 46  0 22 POR aM COSC US eee 46    Paralleled system didsnosis prosrani     cui bia 47  7 1 Two units paralleled system diagnosis programi                        iii 47  ide DE SI DOEL EEE ER 47   EV Prom  48   7 2 Three or more units paralleled system diagnosis program                        iii 50    1 Brief introduction    The ST5100 series UPS adopt advanced DSP control technique  they have a simple  operation interface and strong communication function  the module design is easy to maintenance   and it have good EMC design  which makes it become a excellent and high performance UPS  Its    technique specification is shown in the table below     Tab 2 1 Technique specification    en N ST5100   Specification EE CE 515100     100K ST5100     120K 515100   160K    Rectifier structure Three line phase control rectifier  Voltage range  Vac  380 25     Rectifier   frequency range 40 65   Hz    Synchronization   frequency range 50 15    Hz
7.  mistake  it can be reset according to 4  2  2 mentioned in the manual   B  It should be paralleled line poor contact or bad  turn off the UPS and    connect it again or replace it     5 8 Symptom 8  Turn on the bypass  power breaker  turn on the UPS and protection    enable as soon as the inverter start     Diagnosis program     1  Turn off the load  Turn off the bypass breaker  and turn off the UPS      Turn on the UPS again  if the symptom still exist  it should be inverter failure  Act as  5 6 mentioned in the manual     8  If the UPS start normally  test the voltage between CN2 1P and 3P on the PWM board     the value has a low start progress  then it should be inverter output SCR    SCR driver board failure     4  Proceed UPS diagnosis ready program        Replace the inverter output SCR  SCR driver board     6  Proceed system recover program     7  UPS function test     5 9 Symptom 9  The protection enable as soon as the UPS switch to inverter output  after it is turned on about 30 seconds   Diagnosis program      1  Turn off the load of the UPS  Turn off the bypass breaker  turn off the UPS      2  If the problem still exist  it should be inverter failure  act as 5 6 mentioned in the  manual      8  If it start normally  test the voltage between any two pins of the bypass breaker upper    44    pins  the value should be 20   30Vac  else the bypass SCR  SCR driver board or main board  should be bad     4  Proceed UPS diagnosis ready program        Replace bypass SCR  S
8.  parallel parallel Rectifier Inverter Main Output Battery    current current input output transformer current current  equal sample inductor inductor sample sample  inductor transformer hall hall    picture 3 10 ST5100 80   160K back sight  right sight picture    3 4 2 inverter radiator module    IGBT snubber Inverter DC  board  IGBT current  is below it  sampling hall  DC fuse   Inverter IGBT  current  samping hall   IGBT       ST5100 80   160K  three modules     Picture 3 11 inverter radiator module    14    3 4 3 rectifier and SCR radiator module    SCR snubber beer  Beard output SCR  Bypass SER  SCR  Inverter output  and bypass SCR  driving board  Rectifier  output current  Rectifier i  sampling hall  SCR driving   mr   5          board Mn   s1 oS       Rectifier   gt  re  lt       Ls  f a SCR  A i 7 si           mre     a Ed  Rectifier A E Af   ui ad  SCR snubber      board       ST5100 80   160K rectifier SCR radiator    picture 3 12 rectifier   bypass SCR radiator module    4  Function description    4 1 Function of system main parts    4 1 1 Rectifier control board function     1  AC input phase sequence wrong or phase lose test  When AC input phase  sequence wrong or phase lose  rectifier will stop working    Q  Input voltage test  When the AC input voltage is out of permited value  rectifier  will not work     8  Bypass input phase sequence wrong or phase lose test  When bypass input phase  sequence wrong or phase lose  rectifier control board DSP think that bypass 
9. CR driver board or main board     6  Proceed system recover program     7  Proceed UPS function test     6  Series Connection Hot Standby System diagnosis program    6 1 The standby UPS of series connection hot standby system diagnosis program     1  Press    off    key of the panel to turn off the UPS  Turn off the standby UPS utility and  bypass breaker   Q Turn off the main UPS bypass breaker     Operation as single unit trouble shooting program    4  When the standby UPS is normal  turn on the utility and bypass breaker  press    on    key to  turn on the UPS  turn on the battery breaker when the rectifier start normally  and turn on  the bypass breaker of the main UPS     45    6 2 The main UPS of series connection hot standby system diagnosis program    6 2 1 Diagnosis program   Abnormal phenomenon    Over load  output Reduce the load or    short circuit  check the output wire          sa 18 Hi I  Is the utility input Check the utility voltage     h l  normal  frequency  phase lose or    not in order    Confirm that if the battery is  full charge  is bad or is    connected correctly  correct it     Turn off the load and go to    abnormal UPS test program    Check the UPS function    End    6 2 2 Program describe     The program has been described before in the manual     46    7  Paralleled system diagnosis program    7 1 Two units paralleled system diagnosis program     7 1 1 Diagnosis program     Abnormal phenomenon    Over load  output Reduce the load or check       
10. E  After the UPS start normally  test the voltage between two UPS output with  same phase  the value should be less than 10Vac  as shown in figure 7 1  Turn  off the output breaker  test the voltage between two output breaker upper three  pins Al and A2  Bl and B2  Cl and C2  Turn on the two output breaker without  load  test the three live lines output current  and the value should be less  than 3A  as shown in figure 7 2  Turn off the utility cabinet power breaker   test the voltage two UPS output should be 50Hz and the voltage should be 220Vac   test the output current should less than 3A  Turn on the cabinet power breaker   add the UPS load  and test the two UPS output current  the difference should    less than 5  of nominal output current     51    
11. ER indicate  light on  30 seconds later it will switch from bypass to inverter output  and the BYPASS  light off  during the switch  test the UPS output with a multimeter  it should be  uninterruptible   F  Display function test  During the test program concerned previously  the UPS panel  LED LCD should display correctly     33    5 3 Symptom 3  The UPS power breaker trip when it operation normally    Pull out the line on the rectifier driver board    Abnormal symptom    Diagnosis ready program    that is connected to SCR  turn on the power    breaker again                 Will the UPS power Replace the rectifier  breaker jump again  control board  rectifier    driver board    Replace the rectifier SCR    Put on the driver board connect    line  turn on the power breaker            Will the UPS power       breaker jump again     X     Replace the UPS power breaker    Inverter test  UPS function test       36    5 4 Symptom 4  When the utility is failure the UPS shutdown output and the panel BAT LOW    indicate light is on     5 4 1 Diagnosis program    Abnormal symptom                        Is the UPS turned on or Turn on the UPS or reduce the load        lt     output overload     Check the battery cabinet breaker        Is the battery connected    Hy  battery connect line and UPS  normally      battery breaker    The utility long time faluree cause  Is the battery low  the battery low  when the utility  recover recharge the battery for 10    hours and it will be normal   
12. INDEX    E BierkmnbodiioliessGsge a 3   gt  Vors 6  Did  VE NENNE Ne 6  NE oi ER alia hd palesi alp leleine ERNE FEER ERE REE AE RER En Vi   2 3 TheWUPS eleetrical connceton diapram           ecieie a leda 7  URTI UT O aa IAA 9   iaia 9  3 1 1 ST5100 80  160KVA shape and dimension                      uren ennen ene renerne 9   30 1c 2  15100   200 10001    shape and diens TOR EE EE cues 9   2 Parel  NR 10   25 Terminal and bek EE SE AAS Sn 11  ENN 11  NN ENN 11   DA  2 Inverter FO Mode EE EE EE Ge 14   3 4 3  rectifier and SCR radiator DIE ns 15   A  URCHONSGESCL Pto Ne OR AE OR OE AR EE EE EE OE N 15  A Futetioiol system mal PN nei eerie ees 15   4  1 1 Rectifier control board Tune ss ss se ee ER ee Ee Se SE Me De Ge ceo 15   412 Main board TG ON  ONSE sigilli 16   41  PM Bod FUNC ELON OE eee el 16   A4 JA Display board  Ene ON ae 16   4 1 6 Inverter driver board  Inverter driver signal isolate and enlarge                           16    4 1 7 Bypass  inverter output SCR driving board  Bypass  inverter output SCR    diivei isolate sd Eee lana eee 16  4 1 8 Power board  Supply  12VDC   12VDC  30VDC  5VDC  24VDC power to the  SEE SR EE EE ORE EE REED PIER AIR IERI ON EE EIN EP aes 16  4 1 9 Power backup and transfer board  Power transfer    iii 16  AO PLN 16  4 1 11 Parallel board  Parallel control function                      iii 17   42 DIP switchsetting or each board ella beth 17  4 2 1 display control board board DIPswitch setup                          ennen en eeeeeere
13. UPS  function aptitude supervise    Battery  Detail see in the LCD display working battery testing control page  testing function introduction    Output short circuit  over load  over temperature  battery low voltage  output  Protection  over voltage  low voltage    Meets standard GB T 7260 3 2003  Noise  dB     Cooling mode Ventilator    Working  temperature  CC     Relative  0   95   No condensation  humidity    Dimension   wide    X length X 1200 Xx 800 X 1600  height   mm    mm   uni de ia iu ai       2  Working principle    2 1 Working principle diagram       gt   lt   NED  a     Maintenance switch    Bale 5  Bypass breaker    AC SOURCE    O    LOAD  An  BTG AC DC peace     9   Power breaker A Transformer  N        Battery  FE    2 2 Working mode    When the utility is normal  the rectifier convert the AC input to DC power  it supply the  inverter and charge the battery at the same time  Through the process of AC power changed to DC  power  the inverter can supply more reliable and pure power to load  as the rectifier can dispel the  problems of the portent  noise  unstable frequency and so on  When the utility is abnormal the  battery connected to DC BUS will supply power to inverter  to protect load from AC power  interrupting  when the inverter is failure  such as over temperature  short circuit  output voltage  abnormity  overload and so on   the inverter should shut off automatically  If the utility is normal  at this moment  the switch will switch to bypass power t
14. ctor              Does the battery breaker    Replace the battery  jump after it is turn breaker    System recover program    38    Program describe  System recover program   1  Turn on the power  bypass  output breaker      Turn the maintenance switch to    UPS    mode   8  Turn on the battery breaker after the panel  BAT LOW indicate light is off   4  Press panel    on    key to turn on the UPS     5 6 Symptom 6  In utility mode UPS is normal  but the UPS battery low protection enable  when battery breaker is turned on in battery mode  and the panel BAT LOW light on and the    buzzer beep continually     5 6 1 Diagnosis program     Abnormal symptom    Diagnosis ready program    Replace the DC buffer    resistance    System recover program    End       5  6 2 Program describe     Test the DC resistance  test the resistance of the DC resistance that is locked upon the fan    39    control boar with a multimeter  as shown in figure 5 22     direct current       Picture 5 22 Replace the DC buffer resistance    5 7 Symptom 7  The UPS switch to bypass  panel FAULT indicate light on and    buzzer beeps continually    40    5 7 1 Diagnosis program    Abnormal symptom    Check the main board indicate light  confirm       that which protection the UPS is in              Inverter output over voltage           Output over voltage     diagnosis program       low Inverter output low        Inverter output    voltage  voltage diagnosis program    Inverter Inverter over temperature        
15. d  output over voltage low  voltage  battery low  switch control  bus over current etc    4     PS failure appearances indicate   d 1 3 PWM board function introduce      1  Three phase inverter signal produce    2  Automatic equilibrium control     Current feedback and current limit protection     4 1 4 Display board function      D Some parameter value display     Battery test  charge control     System alarm signal display     4 1 5 Rectifier driver board  Rectifier driver signal isolate and enlarge   4 1 6 Inverter driver board  Inverter driver signal isolate and enlarge     4 1 7 Bypass  inverter output SCR driving board  Bypass  inverter output SCR  driver isolate and enlarge     4 1 8 Power board  Supply  12VDC   12VDC  80VDC  5VDC  24VDC power to the  system     4 1 9 Power backup and transfer board  Power transfer     4 1 10 Fans control board      D Fans speed control  full speed  half speed  stop      16      DC buffer    8  DC voltage isolate and sample      4  DC current isolate sample     4 1 11 Parallel board  Parallel control function     4 2 DIP switch setting of each board    4 2 1 display control board board DIPswitch setup       ID code setting  We can set the UPS ID code through display control board DIP  switch setting  it can be set according to the table below  For the UPS produced  after 2007 01 01 the DIP switch is cancel and it can be set from panel LCD    directly    Setting picture Setting picture       H            Panel 50 60Hz system identify se
16. e  put on the CN15 of main board     function test    A  Turn on the power breaker  the panel BAT LOW indicate light and RECTIFIER   indicate light on  turn on the bypass and output breaker  the panel BYPASS indicate light  on and buzzer beep continually  20s later the rectifier start normally  the BAT LOW  indicate light off  buzzer stop beeping  turn on the battery breaker  Turn on the UPS  the  inverter start to work  the panel rectifier indicate light on  30s later the inverter output   SCR is turned on  and the bypass SCR is turned off  the panel BYPASS indicate light off   the inverter supply to output    B  Switch function test  Turn off and turn on the UPS AC input power breaker of the power  cabinet  test the UPS output voltage on the terminal  it should be uninterruptible  as shown  in figure 5 21    C  Charge function test  Turn off the battery breaker  test voltage between the UPS  batterybreaker upper connector and BAT  of the terminal  the value should be 395  3VDC     as shown in figure 5 20       PIERROT  in    hm    ie AD 7 N    Yel f  y_             0000             Picture 5 20 measure of charge voltage    D  Operation with load function test  Turn on and turn off load  test the    34    voltage between any line of the three live lines and the neutral of the terminal  with a multimeter  the value should be 220Vact2   as shown in 5 19        The diagram 5 21 output voltage measure  E  Bypass function test  Press    OFF    key to turn off the UPS  the RECTIFI
17. eaker of the two UPS  turn on the battery breaker when the  rectifier start normally  press    on    key on the panel to turn on the UPS   F  After the UPS start normally  test the voltage between two UPS output with same  phase  the value should be less than 10Vac  as shown in figure 7 1  Turn on the  two output breaker without load  test the three live lines output current  and  the value should be less than 3A  as shown in figure 7 2  Turn off the utility  cabinet power breaker  test the voltage two UPS output should be 50Hz and the  voltage should be 220Vac  test the output current should less than 3A  Turn on  the cabinet power breaker  add the UPS load  and test the two UPS output current     the difference should less than 5  of nominal output current     48       Diagram 7 paralleled output of the    s 1 units press bad of measure            Diagram 7 the    s 2 output the current measure    The   units paralleled system connects line diagram     49    UPS1 UPS2                                                                                                                                                                                                                                                                                                       v JH  GND  Hi  GND   it  OUTPUT  i  INPUT    Hi   BATTERY  YAH  OUTPUT  f  l  INPUT    Hi   BATTERY   PERE M   TN ORE A HEN  GO EIE  GB IE    OB   OG   GB  EIS GN   GP GPO OG GO                                            
18. ectifier over    sampling hall  charge   9  a current sampling hall   rectifier SCR or rectifier    capacitor    Is the SCR connect Line the SCR again  line contact good  ensure that it is contact    good    Is the rectifier driver Replace the rectifier    signal normal  control board and    SCR  rectifier driver board damage  replace it     rectifier driver board          Is the Rectifier    normal      End    26    A  Rectifier control board utility sampling transformer and fuse test  Turn on the power  breaker  test the voltage between both sides of the fuse and    N   of CN6 on the board  with a multimeter  the value should be about 220 Vac  else the fuse should be damage   Test the voltage between cathode of V01  V02  V03 on the board and GND left pin of  C64A   the value should be about 30Vac  as shown in picture 5 6  If the value is wrong     the transformer should be damage  replace the rectifier control board     V01 V03 ess en ee          Ar EF      F n       ip meet etree SPE at      HAY Ur      picture 5 6 utility samping voltage test    B  Diagnosis of rectifier over voltage  Turn off the power or bypass breaker  turn on the  power breaker  test the rectifier output voltage with a multimeter  as shown in figure 5 5   If the voltage raise to 415VDC  and panel RETIFIER light off  FAULT light on  buzzer  beep intermittently  and the rectifier output voltage descend  it means that the rectifier  output is over voltage  it may caused by the damage of rectifier output 
19. er    C  If it is IGBT over current  carry out diagnosis ready program  act as   5 1 2 mentioned in the manual     D  Replace the IGBT current sampling hall  test IGBT  and replace the bad   one    E  Inverter test  act as 5 1 2 mentioned in the manual   if a board signal   is abnormal  turn of the UPS  discharge the DC capacitor and replace the    board        Picture 5  25 output current measure       Inverter overload or output phase unequal diagnosis     A  Expel the problem of the load first if there is short circuit or overload    43    1 TE    B  Test the current three phase output  as shown in figure 5 25   Calculate the actual load by Pn Un In  n 1 3   and compare to the load  displayed in panel LCD  if the difference is too much  over 50    the UPS  output current sampling hall should be bad    C  For output phase unequal fault  the UPS will operation normally without  load  the difference amount three phase output voltages should enlarge with  small load  and the UPS protection will enable with large load  Test the    voltage between three DC fuse with a multimeter to confirm that if the fuse    is bad   D  Proceed diagnosis ready program   E  Test IGBT     Inverter test  act as 5  1 2 mentioned in the manual   if a board signal  is abnormal  turn of the UPS  discharge the DC capacitor and replace  the board     G  System recover program       Paralleled line failure diagnosis program   A  In single system the problem may be caused by main board DIP switch  setting
20. er signal between each G and E with a  oscillograph  as shown in figure 5 16  It can be tested with a multimeter  the value  is 10 840  2Vac  5 20  2VDC     32       Figure 5 16 Inverter driver board SPWM driver signal    F  Turn off the UPS  turn off the power breaker  test the signal of V21   V32   of the main board  the ground line connect to R37 down pin  Turn on the power  breaker  the voltage V21  tested will be about 5VDC  the voltage V32  tested  will be OVDC  turn on the UPS 30 seconds later its protection will enable   buzzer beep continually  Turn off the UPS    G  Put on the CNI2 of power backup and transfer board  put on CN09 of the main  board  install three 5A fuse between the place the three inverter fuse    uninstalled before     Small insurance       MP     z i  atter   d i    Picture 5 17 ascend the small insurance tube try inverter    33    H  Turn on the power breaker  test the voltage between CN1 1P and 3P  it should  have a rise period  and stabilize at about 30Vac  as shown in figure 5 18   Test the voltage between any two upper pins of the bypass breaker with a  multimeter  the value should be 30 40Vac  else the bypass SCR or its control  board should be damaged        Picture 5 18 Measure the inverter feedback voltage     DUPS    I  Turn off the UPS  Turn off the power breaker  discharge the rectifier capacitor until its  voltage reduce to OVDC  install the inverter fuse again  turn on the bypass breaker  turn the  maintenance switch to    UPS    mod
21. ht bright   U  Phase indicates light  red   When the rectifier input  bypass input phase sequence wrong or  phase lose  the light bright     3 3 Terminal and breakers       80   160KVA    Input and  output N       BAT  BAT     200 400KVA    Picture 3 5 Terminal and breakers    3 4 Inside structure    3 4 1 UPS inside structure     D Main PCB    11    Power distribution Paralleled board    board    Rectifier control    board i  Display board    Main board    Display control board  PWM board       Power board    _ Ei    Fan control board    Power distribution board    Rectifier control board    Display board    Main board    PWM board    Display control board   l   i    Power board       200 400KVA    Picture 3 6 machine main electrocircuit board    2  Radiator module      12    Inverter    Rectifier    Bypass  and    output       Picture 3 7 ST5100 80  160K inverter module Picture 3 8 ST5100 80  160K rectifier module     bypass and output SCR module    Bypass and  inverter output    IGBT and its SCR    filter board  Rectifier SCR       Picture 3 9 200 400K VA inverter module  rectifier module  bypass and output SCR module    As above diagram  when we need to be replaced a component on the damage radiator module   we can remove the two screws fix on top and bottom of the radiator  and pull out the connect line    of the radiator module  turn off the line box  pull out lines insided then pull out the radiator    module     8  Main circuit inductor  transformer  Hall     13      
22. ht while mains input is normal    C  Rectifier indicate light  green   it bright when the rectifier working normal    D  Page up key  This key is    display upward   parameter setting      function repeat    E  Back page key left  Push this key to check the item LCD display or turn on background light  F  Turn over page key downward  Push this key mean  display downward     Parameter setting         G  Switch on key  Match with a usage with H while switch on    H  Confirm key  Push this key to confirm the function    I  Shut down key  Match with a usage with H while shut down    J  Confirm key  Usage while checking to seek the contents of LCD display    K  Return to key  Usage while checking to seek the contents of LCD display    L  The battery indicate light  green   When battery power supply  it bright    M  The inverter indicate light  green   When the inverter working normally  the light is bright   N  Output indicate light  green   The light is bright while there is output voltage    O  Bypass indicate light  green   Bypass power supply the light is bright    P  Maintenance bypass indicate light  green   When power is supplied by maintainance bypass the  light bright    Q  Failure indicate light  red   Rectifier  inverter  and bypass failure the light be bright    R  Overload indicate light  red   The light bright when UPS is overload    S  Battery low indicate light  red   The light bright when battery low     10    T  Bypass indicates light  red   Bypass output the lig
23. in board indicate light introduce     jas      Sj N sapa  rel   di     LED9 Wai 7 i Li dy DR  LED        Figure 4   6 Main control board indicate light    LEDI  red   When system appears inverter output over voltage protection  IGBT  over current protection or over current protection between two parallel  units  it will light  Pressing the panel    OFF    key can clear the protection    LED2  red   Inverter output low voltage fault light    LED3  red   Inverter over temperature indicate light    LED4  red   Inverter output over voltage indicate light    LEDS  red   It will light when the inverter does not work     LED6  red   When the system appear 200  rated overload  output phase unbalance     21    output over voltage or low voltage software protection the light will light   The protection can be cleared when the power  bypass  battery breaker are  turned off and then turned on again    LED7  red   Battery low indicate light  it lights when battery low or the moment  rectifier start    LED8  red   Parallel line fault indicate light     LED9  green   It will light when the system become synchronous     5  Some familiar symptoms and diagnosis program    5 1 symptom 1    After turn on the power breaker or bypass breaker  the panel PHASE light is on and the    buzzer beep continually     This is caused by the input AC power phase lose or phase wrong  turn off the power  breaker or bypass breaker  test the voltage between terminal AC input three phase LA  LB   LC to N  if one o
24. is failure at  this time  and send out a bypass failure signal to the inverter and request inverter not  allow bypass output     4  Bypass input voltage test  When the bypass input voltage is out os the permited  range  rectifier control board DSP think that bypass is failure at this time  and send out a    bypass failure signal to the inverter and request inverter not allow bypass output     15       Output over voltage  over current protection When the voltage  current of the  rectifier output exceeds permited range  rectifier will be shut down     6  Charge current too big protection When the charge current exceeds an enactment  value  the rectifier automaticly stops working     7  Boost charge float Charge voltage tiny adjust  Through adjust rectifier control  board RP6 and RP8 potential we can adjust the float charge voltage and boost charge  voltage  Float Charge voltage adjust range is 390   400 VDC  and boost charge voltage  range is 400   410 VDC    The charge current setting  The rectifier control board SW1 DIP can be used to set  charge current     9  The rectifier over temperature protection  The rectifier will stop working when the  temperature is too high    Rectifier six pulse control signal produce     4 1 2 Main board function introduce      1  DSP voltage stability control   Output frequency 50Hz 60Hz  synchronous frequency range setting  output voltage     phase synchronous tiny adjust function           Inverter protect function  over temperature  over loa
25. ld be 1 0 0 2VDC  1 4 0 2Vac     SZ    TE        qie Se FT  m ee        ai        ETE    ME    GE wa    EE neo  a      das bl  tere Hi    HM    to                  os  ad                 lt    la      rd             3          Oe i ae kHz ee sA es        LER FE    ee ee ee ne ee ee ee AN ee ee EE ee ee eee AE EEN ee eee ee eee EE ee ee ee EN EE EE ee ee AE DE EEN eee AAN eee eee EN eee eee AN EEN a    picture 5 10 rectifier driving sign test wave    28    F  SCR test  test the SCR any two pin between each of the pin 1 2 3 with a multimeter  the  resistance tested should not be short circuit  test pin 4 to 5 pin 6 to 7  the resistance should  be 10 100 2  as shown in figure 3 17     4  Three dots  of control 5  silcon   7   6       picture 5 11SCR test    G  Rectifier test  Turn off the power breaker  put on the CN12 of power backup and  transfer board  turn on the power breaker again  test the rectifier output voltage with a    multimeter  the value tested will rise slowly  and stabilize at 394 4VDC at last       The rectifier symptom that caused by inverter diagnosis program   A  Turn the maintenance switch to    BYPASS     Turn off the power  bypass and battery  breaker  discharge the rectifier capacitors with a 3KQ 10W resistance until its voltage  reduce to OVDC   B  Remove the inverter DC fuse  test the resistance between C1 and E2 of IGBT  as shown  in figure 5 12  the value should be more than 10K Q  else it should be IGBT or its filter  board damage   IGBT test  Test 
26. o supply power to load  when you are  maintaining  and the power must not be interrupted  you can shut off the inverter  and turn on the  maintenance switch  then turn off the rectifier and bypass breaker  At this mode  AC power goes  through maintenance switch to supply power to load  And at this time  there will be no any    electricity in the UPS inside  and the maintenance person can work without any danger     2 3 The UPS electrical connection diagram    d SE I    FS       3  UPS structure  3 1 Shape    3 1 1 ST5100 80  160KVA shape and dimension    Ft ER EET ES       picture 3 1 ST5100 80  160K shape    3 1 2 ST5100 200   400KVA shape and dimension                                                               2200     800    I l l   i             2                                                                                                 I  UA OT TEE CO aa I  fung HITTER SITT NN      2140   784          picture 3 3 ST5100 300  400KVA shape and dimension    3 2 Panel introduction                                        D SOC PHASE   Ne F    DOC BYPASS mg    a  SA   A  DOC BATT        x  Pd  DOC LOAD     NG   NAZ   n DOC FAULT      TEN MAINTENANCE  OE INPUT2 BYPASS  AN  gt                  2x 5                            ae    x od    5 6 6    4 D    Picture 3 4 Display panel                      pp                      A  LCD display  display UPS operation parameter and status  such as voltage  current  amount of  load etc     B  Mains indicate light  green   it brig
27. pacitance  and  transfer    board          Picture 5 23 inverter the output filter replace of an electric capacity      Inverter output low voltage diagnosis program   A  Turn off the UPS  test the voltage between two side of inverter DC fuse     if the value is not zero  the fuse should be bad     B  Diagnosis ready program  act as 5 1 2 mentioned in the manual      C  Test IGBT  Test the EIC2 to CI  E2 to E1C2 of IGBT with a multimeter in  diode mode  the first one tested with red pen   the value should be 0 3 0 6   test it contrary  the value should be     Test Gl to El  G2 to E2 of the  IGBT with a multimeter in capacitor mode  the value tested should be 30     40nF     42    _ G2  a RZ    El    Gl       Picture 5 24 IGBT examine    D  Inverter test  act as 5 1 2 mentioned in the manual   if a board signal   is abnormal  turn of the UPS  discharge the DC capacitor and replace the   board    E  System recover program     4  IGBT over current  paralleled over current diagnosis    A  Exit the paralleled system  act as paralleled system exit program  described in the manual    B  Turn on the failure UPS again  check the main board indicate light that   if the IGBT over current or paralleled over current light is on  the light   is on means that it is IGBT over current  else it should be paralleled over   current  turn off the UPS  Turn off all the breakers of the UPS  discharge   DC capacitor and replace the paralleled board and paralleled average current   sampling transform
28. que specifications    ST5100 P 80K ST5100 P 100K ST5100 P 120K ST5100 P 160K    Three line phase control rectifier    Rectifier  configuration  Voltage range   Vac     Rectifier inpu    380  25     frequency range 40 65   Hz     Synchronization    frequency 50 5        range  Hz     3 4AW GND    Battery voltage   VDC     12V X 29 348V    Refresh electric  30 40 40  current  A   304W  Voltage  Vac  L   N  220 L L  380  Frequency  Hz    Mains input normal  automaticly synchronize the mains  Mains failure  50   0 2   Three line 100           load imbalance i   2   allow 100  imbalance    voltage    stabilization    Parallel mode    parellel mode with equal current output and without principal and subordinate    Output current  unequalization  5   when units are  paralleled    Wave distortion linear load THD lt 3     Transient   bypass   transfer time   ms     System ss  efficiency dd    NER  MR 125  rated load  15 minute   150  rated load  1 minut  capacity 6 rated load  minute   6 rated load  1 minute     Maintain bypass Provide no transfer time maintain bypass switch  Start up function Support DC start up function    ioni Three phase input voltage  input frequency  three phase output voltage  load   ispla  pe battery voltage  battery charge and discharge current and so on                LED display UPS working status and failure indication  Alarm function Input abnormal  battery low  over load  failure    Communication provide stem point communication and RS232 RS485  achieve 
29. r two phase voltage is abnormal  it should be input phase lose  check the AC  input line  else it should be input phase wrong  exchange any two lines of the three phase line    and turn on the power breaker or bypass breaker     5 2 Symptom 2    The panel rectifier light is off  LCD display that rectifier is abnormal and the    buzzer beep Intermittently     22    5 2 1 Diagnosis program          UPS will shutdown rectifier    Keen  when the AC input is    9      frequency abnormal  abnormal  it will recover    when the AC input recover     N  Diagnosis ready program    Is  failure  The rectifier fault that is  s inverter failure      caused by inverter    diagnosis    N  Rectifier fault diagnosis    Inverter test  UPS function test        5 2 2 Program description       Utility voltage and frequency abnormal distinguish    When the input utility voltage or frequency is abnormal  turn on the power  breaker the panel rectifier light will be on  fault light will be off and the  buzzer will beep intermittently  Test the voltage between the input three phase  live line to neutral line  the value should be 165 275Vac  and the frequency  should be 40 65Hz  as shown in figure 5 1  else it should be utility voltage    or frequency abnormal     23    SRI DELE  AT LAT TE  OUTPUT           Tora       Picture 5 1 utility input measure    Diagnosis ready program   A  Press the panel    OFF    key to turn off the UPS   B  Turn on the maintenance bypass switch or turn it to    BYPASS      a
30. s shown  in figure 5 2   C  Turn off the power  bypass  battery and output breaker   D  Discharge the rectifier capacitor with a resistance of 3KQ 10W until    the voltage of capacitor reduce to 0 VDC  as shown in picture 5 3        Picture 5 3 rectifiers filters turn on electricity of an electrolysis electric capacity    AN Note  High voltage exists in the UPS  the programs should be carried out  before the parts are replaced      8  Inverter fault diagnosis  The inverter fault diagnosis  Remove the inverter DC  fuse  as shown in picture 5 4  Turn on the power breaker  if the rectifier start normally and  the panel rectifier light is on  test the voltage between the battery breaker upper part to     BAT     of the terminal with a multimeter confirm that the battery breaker is Turn off    as  shown in picture 5 5  If the voltage is 394 4VDC  then the rectifier is normal  the fault  should be caused by the inverter     24    Mas ha ad ad haa eee           Ml       Picture 5 4 Remove DC fuse Picture 5 5 Test the rectifier voltage    25      Rectifier fault diagnosis program and describe             Abnormal symptom              Y i  Is A01 sampling transformer Replace A01  rectifier  or fuse damage  control board    N  le tasie over x Replace rectifier control  voltage  board or fan control  board  N  y Temperature relay or its       Is    heat     rectifier over    connect line  SCR or its        connect line       Replace the damage    rectifier output current            Is r
31. short circuit  the output wire       Is the utility input N Check the utility voltage         normal  frequency and phase            Confirm that if the battery is          Is the battery       fully charge  is bad or is       normal          connected correctly  correct it        UPS is failure    Single unit exit program in       the paralleled system    Single unit diagnosis    program    Parallel system launching    program    47    7 1 2 Program describe      DSingle unit exit program in the paralleled system   A  Turn off the load of the UPS  press    off    key on the panel to turn off the two paralleled UPS   B  Turn off the power  bypass and battery breaker of the two UPS  and turn off paralleled output  breaker of the failure UPS   C  Remove the paralleled wire  set the SW2 switch of the main board of two UPS to make them  in single mode  as shown in 4 2 2 in the manual   D  Turn on the power  bypass breaker of the normal UPS  turn on the battery breaker when the  rectifier start normal  press    on    key on the panel to turn on the UPS     Paralleled system launching program   A  Turn off the load of the UPS  Turn off the paralleled output breaker of the normal UPS   B  Press    on    key on the panel to turn on two UPS   C  Turn off the power  bypass and battery breaker of the two UPS   D  Connect the two UPS with the paralleled wire  set the SW2 switch of the main board of two  UPS to make them in two unit paralleled system mode   E  Turn on the power  bypass br
32. temperature  diagnosis program       IGBT over current or        IGBT over current or  paralleled over current  paralleled over current            diagnosis program             N  Y  Inverter output overload  Inverter output overload  or phase unequal diagnosis  or phase unequal   program  N  Y    Paralleled line failure       Paralleled line failure     diagnosis program       UPS function test    End    41    5 7 2 Program introduction     D Confirm that which protection the UPS is in according to main board LED    display  Panel indicate light has been described before in the manual     Q  Inverter output over voltage diagnosis program     A     Press panel    off    key to turn off the UPS  test the voltage between  CN2 1P and 3P on the PWM board  as shown in figure 5 18  press panel     on    key to turn on the UPS  the voltage tested should rise and  stabilize at about 30Vac at last during the start process    If the voltage is too small or is zero then the inverter output  voltage sampling transformer on the power backup and transfer board  should be bad  if the value that voltage and frequency tested is variable   then the inverter output capacitor should be bad    Diagnosis ready program  act as 5 1 2 mentioned in the manual    Replace the bad power backup and transfer board or inverter output  capacitor  as shown in figure 5 23    Inverter test  system recover program  act as 5 1 2 and 5 4 mentioned    in the manual     inverter E i  output I    L     filter elf  ca
33. the E1C2 to C1  E2 to E1C2 of IGBT with a multimeter in diode mode the  first one tested with red pen   the value should be 0 3 0 6  test it contrary  the value  should be co  Test G1 to El  G2 to E2 of the IGBT with a multimeter in capacitor mode   the value tested should be 30   40nF  as shown in figure 5 13        picture 5   12 inverter radiator board test resistance    29    G2    E1C2 ag  El   E2  C1 Gl       Picture 5 13 IGBT measure    IGBT filter board test  Remove the board  test the resistance between Cl and E2 on the  board  the value should be more than 10 K 2  else it should be damage  Replace it        Inverter test  Remove the inverter fuse  pull out CN11  CN12 of power backup  and transfer board  pull out CN9  CN15 of main board    A  Turn on the power breaker  test Jl of main board with a oscillograph  the  waveform will be 9KHz square wave  the wave Vp p should be 23 2V  frequency  should be 9  00 0  05KHz  The oscillograph ground line can be connected to R37  down pin  as shown in figure 5 12  The signal can be tested with a multimeter   the value should be 11  10 0  2Vac  0  2 0  1VDC     BON er      f  e id mm    i DiE R  Ne F   i  i ife   ner Ladd KAAS KLARES RAMA LIZA   pur ora ILL agli IFRS d mer bd bed FILIALI       e   I  gt  og RS  pa     N         VERVET    Ed SON    Chi tS  gt    na  AY No a RA AA kl  ORAAL Re  ICI PI  VINE MT AS n GA ONE VIGEN Gr ry rev   TTI    sent mm tk MT SEK ee TEL    o  aas ee te    eterni Life Li ii et    mM Abbe         
34. tting  It is shown in the picture below   when the DIP switch SWI second pin as is turned to    ON    then it is set  to 50Hz identify system  if it is turned to    OFF      then it is set to    17    60Hz identify system  For the UPS produced after 2007 01 01 the SW1 is  cancel and the frequency identify system can be set from the panel LCD    ON    SUN  SWI    50Hz system  ON    HU  SWI  60Hz system    4 2 2 main board DIP switch setting    Main board has two DIP switch SW1  SW2  it can be used for parallel single  unit system setting and output 50 60Hz setting     Parallel single unit setting  As shown in the figure below     ON       SWZ    Parallel unit setting  ON       SW2    Single unit setting    d  50 60Hz output system setup   It can beset according to the picture below    For the UPS produced after 2007 01 01 it just need to be set from the  panel LCD   ON  SWI  50Hz output system setup  ON  SWI  60Hz output system setup    4 2 3 rectifier control board DIP switch setting    The UPS charge current canbe set through rectifier control board SW1  it is    shown in the table below   setting ST5100 P  80 160K    OFF OFF OFF 40A    Status OFF OFF 30A     For the 80 160KVA UPS produced after 2007 01 01 and 200 400KVA the charge current  can be set from panel LCD  for 80 160KVA the charge current setting range is 5 40A   for 200 400KVA charge current setting range is 5 80A        4 3 Potential function introduction    4 3 1 rectifier control board    RP8    SWI       pict
35. ure 4 1 rectifier control board electrical organ position  RP6  Adjust float charge voltage  it should be adjusted to 394 4VDC   RP8  Adjust boost charge voltage  it should be adjust to 405 5VDC     4 3 2 main board    SWI       Figure 4 2 Rectifier board potential and DIP switch  RP6  Adjust output B phase voltage     RP7  Adjust synchronous accuracy     19    RP8  Adjust output A phase voltage   RP9  Adjust output C phase voltage     R35  Adjust synchronous accuracy     4 3 3 PWM board  RP2  RP3  RP4  RP1       Figure 4 3 PWM board potential  RP1  Adjust triangle wave voltage  RP2  RP3  Adjust sine wave voltage  RP4   Handle equilibrium adjust     4 3 4 display control board    RPI  RP2  RP4  RP3  SW3  SWI       Fed Display control board potential  R23  Battery voltage display value adjust  R24  A phase output current display  value adjust  R25  B phase output current display value adjust  R26  C phase output  current display value adjust  R40     phase output voltage display value adjust   R42  B phase output voltage display value adjust  R41  C phase output voltage display  value adjust  RP1  CPU 5V power adjusts     20    4 3 5 power board    RP7  RPI  RP2  RP3 RP4  RPS  RP6       Figure 4 5 Power board potential  RP1  Adjust parallel board power  12V  RP2  Adjust SCR driver power 12V    RP3  Adjust main control board power 12V  RP4  Adjust main control board power   12V  RP5  Adjust DSP power 5V  RP6  Adjust LCD power 5V  RP7  Adjust parallel  board power 12V     4 4 Ma
36. voltage sampling  hall of fans control board or damage of rectifier control board  Replace the rectifier  control board or fans control board    C  Diagnosis of rectifier over heat  When the UPS over heat protection enable  test the  voltage between R75 with a multimeter  if the value is OVDC then it should be rectifier  over heat  it will be SVDC normally   The problem may caused by temperature relay  connect line contacting badly  temperature relay being bad  fans being bad or rectifier  SCR being bad etc    D  Diagnosis of rectifier over heat  When the rectifier over current protection enable   test the voltage between U9A 1P U12 1P or V8  and GND  C64A left pin   if the value is  about 5 VDC  it should be rectifier over current or over charge protection  as shown in  figure 5 8  It may caused by rectifier output current sampling hall  charge current    sampling hall  rectifier capacitor or rectifier SCR being bad     27       Picture 5 8 rectifier over current or charge over current protective test    E  Rectifier driver signal test  Turn off the power breaker  pull out CN12 of power backup  and transfer board  as shown in figure 5 9  Turn on the power breaker again  test left pin  of R98  R99  right pin of R100 R101 R102  upper pin of R103 to GND  left pin of C64A   as shown in figure 5 8  on the rectifier control board with a oscillograph  the signal  waveform tested should be 50Hz pulse group  as shown in figure 5 10  It can be tested  with a multimeter  the value shou
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
開啟原PDF  Rutland 914i Windcharger Owners Manual  anais6encontro - Universidade Federal de Minas Gerais  Verbatim M16-L500-C30-B38-D  Banner QS30H20 User's Manual  OpenCom X320  WebCenter Installation Guide - Product Documentation  Manuale - Punto Luce  HSD High Speed Data Acquisition  CB50-3260 明電4極同期発電機    Copyright © All rights reserved. 
   Failed to retrieve file