        INSTALLATION & SERVICE MANUAL
         Contents
1.    EGD 1 amp S 01    INSTALLATION  amp  SERVICE MANUAL    DOUBLE WALL INDIRECT  WATER HEATER    To avoid damage or injury  there must be no materials  stored against the indirect water heater and proper care  shall be taken to avoid unnecessary contact  especially    by children  with the indirect water heater        Do not store or use gasoline or other flammable  liquids in the vicinity of this water heater or any  other appliance     For your family   s comfort  safety  and convenience  we  recommend this water heater be installed and serviced by a  plumbing professional     TABLE OF CONTENTS       Important Information              scccssscsscsssssccsssssccssssseeseeeses 1  General Information            scccssscccsssscsssssccessccessscessssscessese 3  Pre Installation              ss0c000   Water Connections   Electrical Connections             scsssccssssscssssecscssscesssccesssccees 8  Operating Instructions            ccscsscsssssssscsesssssesssseceeeees 10  Maintenance 5co5csaceansssceesecsveccousetssscepucesescssbecsesessesesescsons 13  Troubleshooting Guide              scssssscsscssssscssseesesseesserseees 14   IMPORTANT INFORMATION    The equipment must be installed in accordance with  those installation regulations required in the area  where the installation is to be made  These  regulations must be carefully followed in all cases   Authorities having jurisdiction shall be consulted  before installations are made     All wiring on water heaters installed in the
2.    Figure 2   Water Boiler Piping with Circulators VACUUM BREAKER    COLD WATER  SUPPLY               HOT WATER OUTLET          TEMPERATURE  AIR VENT CIRCULATOR AND PRESSURE  PRESSURE RELIEF VALVE    REDUCING  FROM BOILER SUPPLY     VALVE  ON   eeN   TO SPACE      R  HEATING ZONE S     SPACE HEATING  EXPANSION TANK CIRCULATOR            AIR SEPARATOR                 EXPANSION  TANK   IF NEEDED              SUPPLY        SUPPLY       Weegee  Pilabund    BOILER           RETURN i   TO BOILER RETURN    MAN     io y  INDIRECT   FIRED  WATER HEATER       FROM SPACE DRAIN VALVE  HEATING ZONE S         EGD 1 amp S 01       CONNECT STEAM BOILER  SUPPLY PIPING    Figure 3 represents a typical steam boiler connection diagram  Refer to the boiler installation manual or contact the boiler  manufacturer for an appropriate piping diagram  The use of a union  shut off valves  and a drain valve is recommended for  future service convenience  The use of an in line    Y       style strainer is required to prevent accumulation of sludge in the  water heater   s coil     Figure 3     Typical Steam Boiler Connections  connections available below the water line     VACUUM BREAKER  MINIMUM LOW COLD WATER P    WATER LINE HOT WATER OUTLET SUPPLY J    1    NPT MINIMUM PIPING  TO CIRCULATOR  TEMPERATURE  AND PRESSURE    RELIEF VALVE   FROM BOILER SUPPLY                                                     EXPANSION    WATER TANK  TEMPERATURE  IF NEEDED     LIMIT  Y STRAINER    Reena    6    MAX     SHU 
3.   Table 1 Water Heater Performance    Pressure Drop at  Rated Heat  Source Flow Rate   Feet of Head     Hot Water   Coil Heat  Availability   Transfer    MODEL   Minutes    Area  Sq Ft     NOTICE    If the boiler takes longer to heat up from a cold start  than the water availability as noted above  hot water  shortage may occur     Hot water availability is based off drawing 80  of  the heated tank volume at 4 gallons per minute flow  rate     The maximum heat transfer through the coil  heat  input  of the water heater at 240  F boiler water  supply temperature and 210  F potable water  temperature is 94 100 Btu hr for residential models  and 180 300 Btu hr for commercial models  Potable  water temperature is limited to below 210   F and  nominal water containing capacity is below 120  gallons for all single wall indirect models     Accordingly  per Part HLW  101 2  Section IV of the  ASME Boiler and Pressure Vessel Code  all  Lochinvar Single wall Indirect products are    exempted from compliance with the code        GENERAL INFORMATION    FEATURES    This water heater contains the following features     HEAT EXCHANGER     The heat exchanger  coil  has 3 4   NPT female fittings     Water heaters with a double wall heat exchanger meet the  Uniform Plumbing Code for installation in all potable water  systems  The double wall construction provides protection  in the event that either the potable or hydronic heat exchanger  barrier is penetrated  The fluid will move along in int
4.  UNTIL THE  LEAKAGE IS CORRECTED     Liquefied petroleum gas propane gas is heavier than air  and will remain at floor level if there is a leak  Basements   crawl spaces  closets  and areas below ground level will  serve as pockets for accumulation of leaking gas     This water heater is supplied with an adjustable  thermostat to control water temperature  Hot water  temperatures required for automatic dishwasher and  laundry use can cause scald burns resulting in serious  personal injury and or death  The temperature at which  injury occurs varies with the person   s age and the time  of exposure  The slower response time of disabled  persons increases the hazards to them  NEVER allow  small children to use a hot water tap or to draw their own  bath water  NEVER leave a child or disabled person  unattended in a bathtub or shower        EGD 1 amp S 01    Installation is not complete unless a pressure and  temperature relief valve is installed into the side of  the water heater  See the Water Connections section  of this manual for details     This water heater contains very hot water under high  pressure  Do not unscrew any pipe fittings or attempt  to disconnect any components of this water heater  without positively assuring the water is cool and has  no pressure  Always wear protective clothing and  equipment when installing  starting up  or servicing  this water heater to prevent scald injuries  Do not  rely on the pressure and temperature gauges to  determine the tempera
5.  USA must  be in accordance with the National Electrical Code and   or local regulations  or in Canada  installed in  accordance with the Canadian Electrical Code and or  local regulations        The following terms are used throughout this manual to bring  attention to the presence of hazards of various risk levels  or  to important information concerning product life     DANGER    Indicates an imminently hazardous situation  which   if not avoided  will result in death  serious injury  or  substantial property damage           Indicates a potentially hazardous situation  which  if  not avoided  may result in moderate  or minor injury  or property damage     AN CAUTION    Indicates a potentially hazardous situation  which  if  not avoided  could result in death  serious injury  or  substantial property damage     NOTICE    Indicates special instructions on installation   operation or maintenance  which are important but  not related to personal injury hazards     N DANGER    DO NOT store or use gasoline or other flammable   combustible  or corrosive vapors and or liquids in the  vicinity of this or any other appliance     IF YOUSMELL GAS   Q DO NOT try to light any appliance     Q DO NOT touch any electric switch  do not  use any telephone in your building    Q Immediately call your gas supplier from a  telephone in another building  Follow the  gas supplier   s instructions    O  Ifyou cannot reach your gas supplier  call  the fire department     DO NOT OPERATE THEAPPLIANCE
6.  installed to  allow for complete drainage of both the temperature  and pressure relief valve and the discharge line  The  discharge opening must not be subjected to blockage  or freezing  DO NOT thread  plug  or cap the discharge  line  It is recommended that a minimum clearance of  four  4  inches be provided on the side of the water  heater for servicing and maintenance of the  combination temperature and pressure relief valve     Do not place a valve between the combination  temperature and pressure relief valve and the tank        EGD 1 amp S 01       TEMPERATURE AND PRESSURE  RELIEF VALVE    Keep clear of the combination temperature and pressure  relief valve discharge line outlet  The discharge may be  hot enough to cause scald injury  The water is under  pressure and may splash  For protection against  excessive temperatures and pressure  install temperature  and pressure protective equipment required by local  codes  but not less than a combination temperature and  pressure relief valve certified by a nationally recognized  testing laboratory that maintains periodic inspection of  production of listed equipment or materials as meeting  the requirements of the Standard for Relief Valves and  Automatic Gas Shutoff Devices for Hot Water Supply  Systems  ANSI Z21 22 and the Standard CAN1 4 4  Temperature  Pressure  Temperature and Pressure Relief  Valves and Vacuum Relief Valves  The combination  temperature and pressure relief valve must be marked  with a maximum set pr
7.  or alter the water heater and   or controls     DO NOT operate the water heater if any external    part has been under water  Immediately call a  qualified service technician to inspect the appliance  and to replace any part of the control system that was  under water     This water heater is suitable for installation on  combustible flooring  DO NOT install this water  heater on carpeting     DO NOT operate this water heater without first being  certain it is filled with water     Flammable items  pressurized containers  or any  other potential fire hazardous articles must never be  placed on or adjacent to the heater  Containers of  flammable gases should not be stored or used in the  same room with this water heater     Hydrogen gas can be produced in an operating water  heater that has not had water drawn from the tank  for a long period of time  generally two weeks or  more   Hydrogen gas is extremely flammable  To  prevent the possibility of injury under these  conditions  we recommend that the water faucet be  opened for several minutes at the kitchen sink before  you use any electrical appliance that is connected to  the hot water system  If hydrogen is present  there  will be unusual sounds such as air escaping through  the pipes as hot water begins to flow  Do not smoke or  have open flame near the faucet at the time it is open     The maximum boiler water supply temperature to the  indirect heat exchanger must not exceed 240  F   116  C         EGD 1 amp S 01     
8.  supply piping  Mount the circulator making sure  the flow arrow points toward the water heater  The use of shut off valves and unions are recommended for future  service convenience  The use of an air separator and vent is recommended to eliminate air in the system  Pipe and  fittings between the boiler and indirect fired water heater must be 3   4    diameter or larger           Figure 1   Water Boiler Piping with Zone Valves VACUUM BREAKER  COLD WATER  HOT WATER OUTLET SUPPLY       TEMPERATURE   AIR VENT AND PRESSURE  CIRCULATOR   PRESSURE RELIEF VALVE    REDUCING  FROM BOILER SUPPLY     VALVE                   AIR SEPARATOR          EXPANSION  TANK   IF NEEDED             TO SPACE  HEATING ZONE S         SUPPLY    Fehon       eee    COLD WATER  SUPPLY            SPACE HEATING    BOILER  EXPANSION TANK ZONE VALVE           TE        RETURN        FROM SPACE  DRAIN VALVE  HEATING ZONE S        INDIRECT   FIRED  WATER HEATER    2  For a space heating system that utilizes CIRCULATORS  refer to Figure 2  The indirect fired water heater  connection labeled    FROM BOILER SUPPLY    should be piped to the boiler supply piping  Mount the circulator  making sure the flow arrow points toward the water heater  The use of shut off valves and unions are  recommended for future service convenience  The use of an air separator and vent is recommended to eliminate air  in the system  Pipe and fittings between the boiler and indirect fired water heater must be 3   4    diameter or larger  
9. Ueda    CIRCULATOR MOUNTED BOILER RETURN       CLOSE TO FLOOR        INDIRECT   FIRED  WATER HEATER    BOILER    DRAIN VALVE    NOTICE    Typical steam boiler without connections available below the water line is not recommended due to insufficient  water temperature  especially during warmer months when the space heating system is not operational  Boiler  water temperature at the bottom of a steam boiler can be 50  F lower than the boiler   s water temperature limit  setting during such periods        FILL BOILER SYSTEM    1  On new boiler installations  do not purge the boiler or  space heating system through the water heater  During  any boiler or space heating system flushing  cleaning   or purging  the water heater should be isolated to avoid  possible attack on the carbon steel coil by chemical  additives     2  Purge air from boiler water heater piping     3  Check system for leaks  Repair as necessary     ELECTRICAL CONNECTIONS    Install electric wiring in accordance with National Electric  Code or the Canadian Electrical Code and local regulations   See the boiler   s installation manual for wiring diagrams     Positively assure all electrical connections are    unpowered before attempting installation or service  of electrical components or connections of the water  heater or building  Lock out all electrical boxes with    padlock once power is turned off        EGD 1 amp S 01       When installed  the water heater must be electrically  grounded in accordance with 
10. collecting water  The drain pan can be purchased  from your plumbing professional  The drain pan must be  piped to an adequate drain  The piping must be at least    3 4 inch in diameter and pitched for proper drainage     Table 2   Clearance from Combustible Materials  Sides Rear    Table 3     Recommended Service Clearances    Non Piping Front T  amp  P Relief  Rear   Valve Side    Side  Thermostat   i fo          AN CAUTION    MOVE THE WATER HEATER TO A PERMANENT  POSITION BY SLIDING OR WALKING     fiw CAUTION    Do not drop water heater  Do not bump water heater  jacket against floor        Appliance Location  1  Boiler Location     Locate the indirect fired  water heater as close to the boiler as practical   2  Fixture Locations     For fastest delivery of hot water   place the indirect fired water heater close to points of  use     Additional Recommended Components   1  Shut off Valves     Allows isolation of water heater  from domestic water system and or boiler system during  service    2  Unions     Allows water heater movement during service  if adequate clearance cannot be provided    3  Thermal Expansion Tank     If the water heater is  installed in a closed water supply system  such as one  having a back flow preventer in the cold water line   provide thermal expansion control  Contact the water  supplier or local plumbing inspector for additional  information     EGD 1 amp S 01       NOTICE    For California installation this water heater must be  braced  anchore
11. d  or strapped to avoid falling or moving    during an earthquake  See instructions for correct  installation procedures  Instructions may be obtained  from California Office of the State Architect  400 P  Street  Sacramento  CA 95814        WATER CONNECTIONS    FAILURE TO INSTALLAND MAINTAIN A NEW   LISTED TEMPERATURE AND PRESSURE RELIEF  VALVE WILL RELEASE THE MANUFACTURER  FROMANY CLAIM WHICH MIGHT RESULT FROM  EXCESSIVE TEMPERATURE AND PRESSURES     Hydrogen gas can be produced in an operating  water heater that has not had water drawn from  the tank for a long period of time  HYDROGEN  GAS IS EXTREMELY FLAMMABLE  To prevent  the possibility of injury under these conditions   we recommend the hot water faucet be opened for several  minutes at the kitchen sink before you use any electrical  appliance that is connected to the hot water system  If  hydrogen is present  there will be an unusual sound such  as air escaping through the pipes as hot water begins to  flow  Do not smoke or have open flame near the faucet  at the time it is pen     Keep clear of the temperature and pressure relief  valve discharge line outlet  The discharge may be hot  enough to cause scald injury  The water is under  pressure and may splash     iy CAUTION    If sweat fittings are to be used  DO NOT apply heat  to the nipples on top of the water heater  Sweat the  tubing to the adapter before fitting the adapter to  the water connections  It is imperative that heat is  not applied to the nipples co
12. direct fired heater zoned with a  circulator     DOMESTIC HOT WATER PRIORITY    Two options are available  Priority and Non Priority     1  Priority     Demand for space heating is interrupted or  postponed until the domestic hot water demand is  satisfied  This option provides maximum delivery of  domestic hot water  Priority is recommended when     a  Boiler net output is 100 000 Btu per hour or less   or   b  When boiler output required to satisfy domestic  hot water demand is at least 50  of the boiler output  required to satisfy space heating demand   or   c  When an interruption in space heating can be  tolerated during a long domestic hot water draw     2  Non Priority     Boiler output is divided between space  heating and domestic hot water heating  Delivery of  domestic hot water can be reduced during simultaneous  space and domestic hot water heating operations   depending on such factors as boiler output  boiler over   sizing  number of space heating zones calling for heat   and the ratio of domestic hot water load to space  heating load     Component Location    This water heater must be located in an area where leakage  of the tank  water line connections  or the temperature  and pressure relief valve will not result in damage to the  area adjacent to the water heater or to lower floors of the  structure  When such locations cannot be avoided  a  suitable drain pan must be installed under the water  heater  The drain pan depth must be suitable for draining  and 
13. egrated  leak path within the heat exchanger  leaving the exchanger  through a weep hole located in the fittings  If a confirmed  leak occurs  contact the plumbing professional who installed  the water heater or the manufacturer  listed on the rating  plate  for additional guidance        This indirect fired water heater is appropriate for all  potable heating systems  even where a single wall  exchanger is not approved by the authority having  jurisdiction     ADJUSTABLE THERMOSTAT  The temperature may be  adjusted from approximately 80  F to approximately 160  F   The thermostat is factory set at 120  F  It is recommended  that lower temperatures be used to avoid the risk of  scalding  Refer to the    Warnings    and the section on  SCALDING in    Section VII     Operating Instructions     It  is further recommended  in all cases  that the water  temperature be set for the lowest temperature that satisfies  our hot water needs  This will also provide the most  energy efficient operation of the water heater and  minimizes scale formation     Setting the water heater temperature at 120  F will reduce the  risk of scalds  Some states require settings to specific lower  temperatures     TEMPERATURE SETTING  TO REDUCE SCALD    Install a discharge line so that water discharged from  the temperature and pressure relief valve will exit  within six  6  inches above  or any distance below   the structural floor and cannot contact any live  electrical part  The discharge line is to be
14. essure not to exceed the maximum  working pressure of the water heater  The combination  temperature and pressure relief valve must also have an  hourly rated temperature steam BTU discharge capacity  not less than the hourly rating of the water heater  The  supplied combination temperature and pressure relief  valve  when properly installed and unrestricted  will  discharge the maximum input produced by a 240  F   116  C  boiler supply temperature  A lower boiler supply  temperature will reduce the input required to be  discharged in the event of excessive potable water  temperatures     Install the combination temperature and pressure relief  valve into the opening provided and marked for this  purpose on the water heater     Some models may already be equipped or supplied with  a temperature and pressure relief valve  Verify that the  combination temperature and pressure relief valve  complies with local codes  If the temperature and  pressure relief valve does not comply with local codes   replace it with one that does     SACRIFICIAL ANODES   Two sacrificial anode rods have been installed in the tank  head to extend tank life  The anode rods should be inspected  annually to determine the amount of sacrificial decay and  replaced when necessary to prolong tank life  Water  conditions in your area will influence the time interval for  inspection and replacement of the anode rod  The use of a  water softener may increase the speed of anode consumption   More frequent inspec
15. heat source having a DOE  heating capacity of 55 000 BTU h     Answer   New Rating    98 gal hr x  55 000 BTU h   65 000 BTU h     98 gal hr x 0 846   83 gal hr    NOTICE    Increasing the boiler DOE heating capacity above    the values listed in Table 3 will not increase the rating  of the water heater        EGD 1 amp S 01       2  Circulator Sizing     Refer to Table 5 for the  corresponding pressure drop through the coil for the  given model  Calculate the pressure drop of all  straight pipe and fittings on the supply and return of  the water heater at the selected flow rate  Add the  piping fitting pressure drop to the pressure drop  through the water heater coil     Select a circulator that will provide an appropriate  flow rate at the combined pressure drop     SYSTEM ZONE CONTROL    The indirect fired water heater must be installed as a zone  separate from the space heating system  The domestic  hot water zone   s piping and circulator must be sized for a  minimum flow rate with all zones in use and a maximum  flow rate with only the water heater in use  For this  reason  the preferred method of zone control is with  circulators     1  Circulators     With space heating zones using  circulators  the indirect fired heater should be added  as an additional zone with a circulator    2  Zone Valves     Select a valve with a low pressure drop  to assure adequate flow through the water heater    3  Hybrid     The space heating zone can be zoned using  zone valves and the in
16. ing sure that the control is well covered and  that the plastic terminal shield has not been displaced   Replace the access panel  The water heater is now ready for  operation and the main switch can be closed        After the indirect fired water heater completes a heat up  cycle  check the water temperature at a faucet  Allow enough  water to flow to ensure that the water temperature reflects  the tank temperature  Adjust the water heater   s temperature  setting as necessary     Adjusting to a lower temperature setting will not  immediately affect water temperature  Draw sufficient water  or allow the water heater to remain idle until a heat up cycle  is initiated  After the heater   s heat up cycle is complete   check the water temperature at a faucet to determine if  further adjustment is necessary     Adjusting to a higher temperature may not immediately  affect water temperature  If a heat up cycle begins  allow  the heat up cycle to complete before checking the water  temperature  If a heat up cycle does not begin  draw  sufficient water or allow the water heater to remain idle until  a heat up cycle is initiated  After the heater   s heat up cycle  is complete  check the water temperature at a faucet to  determine if further adjustment is necessary     TEMPERATURE  DIAL    Figure 7   Thermostat    12    EGD 1 amp S 01       MAINTENANCE    This indirect fired water heater is intended to provide a  service life of many years  Components that require  service  however  
17. local codes or  in the  absence of local codes  with the National Electrical  Code  ANSI NFPA 70  and  or the CSA C22 1 Electric  Code     Failure to properly wire electrical connections to the  water heater may result in serious physical harm     Electrical power may be from more than one source   Make sure all power is off before attempting any  electrical work     The thermostat incorporates a manual reset temperature   limiting device  Please refer to the TROUBLESHOOTING  GUIDE section for manual reset operation  The thermostat  incorporates a manual adjustable temperature indicator to  change the potable water temperature  Please refer to WATER  TEMPERATURE ADJUSTMENT in the OPERATING  INSTRUCTIONS section for proper instruction in adjusting  water temperature  Turn off all power related to the boiler  and heating system before proceeding with the electrical  connections        The thermostat switch is a single pole  single throw device   The field connections shall be used as a control for one leg  of the electrical circuit  The thermostat switch can be used in  the range of 24 to 480 volts with a maximum current load of  15 amps  Any and all wiring shall be sized and installed to  satisfy the voltage and amperage used  All wiring shall be  done in accordance with all applicable local and state codes     GENERAL INSTALLATIONS    If a circulator is used to control the heating fluid flow from  the water heater to the boiler  a zone relay is required between  the water hea
18. may be subject to failure  Failure to use  the correct procedures or parts in these circumstances  may make the water heater unsafe     The owner should arrange to have the following inspections  and simple maintenance procedure performed by qualified  service personnel at the frequencies suggested     1  Boiler and Domestic Water Piping  Annual      Check  all piping for signs of leakage at joints  unions  and  shut off valves  Repair as needed    2  Temperature Pressure Relief Valve  Annual   The  temperature pressure relief valve should be checked  to ensure that it is in operating condition  To check  the relief valve  lift the lever at the end of the valve  several times  The valve should seat properly and  operate freely  If water does not flow  remove and  inspect for obstructions or corrosion  Replace with a  new valve of the recommended capacity as necessary   Do not attempt to repair the valve  as this could result  in improper operation and a tank explosion  In areas  with poor water conditions  it may be necessary to  inspect the temperature pressure relief valve more often  than once a year     If the temperature   pressure relief valve on the heater  discharges periodically or continuously  it may be due to  thermal expansion of water in a closed water supply system   or it may be due to a faulty relief valve      iw CAUTION    Before manually operating the valve  make sure that  a drain line has been attached to the valve to direct    the discharge to an open d
19. mostat senses stored water temperature drops  below desired setting     a  Domestic hot water priority only  Normally closed  contacts open to interrupt space heating        2  Thermostat satisfied   a  Thermostat contacts open  turning off domestic hot       water circulator and de energizing relay  Water temperature over 125  F  can Cause severe burns  b  Normally open contacts open  stopping boiler instantly or death from scalds   a Children  disabled and elderly  are at highest risk of bein  c  Domestic hot water priority only  Normally closed ented Pa g  contacts close  returning boiler control to space   i    heating  See instruction manual before  setting temperature at water  heater   Feel water before bathing or  showering   WATER TEMPERATURE Temperature limiting valves are    ADJ USTMENT available  see manual        Figure 6   Scald Warning    SCALDING Table 4 details the approximate relationship of water  This water heater can deliver scalding temperature temperature and time with regard to scald injury and may be  water at any faucet in the system  Be careful used as a guide in determining the safest water temperature  whenever using hot water to avoid scalding injury  for your applications   By setting the thermostat on this water heater to  obtain an increased water temperature  you may  create the potential for scald injury  To protect  against injury  you should install an ASSE approved  mixing valve  a device to limit the temperature of  water to protect agai
20. nst scald injury via mixing  hot and cold water supply  in the water system   This valve will reduce point of discharge  temperature in branch supply lines  Such valves  are available from the manufacturer of this water  heater or a local plumbing supplier  Please consult  with a plumbing professional     APPROXIMATE  TIME TEMPERATURE    RELATIONSHIPS IN SCALDS    125  F 1  to 2 minutes    130  F About 30 seconds    135  F About 10 seconds  140  F Less than 5 seconds  145  F Less than 3 seconds    150  F About 1 1   2 seconds  155  F About 1 second       Table 4   Scald Relationships    11    EGD 1 amp S 01       N CAUTION    Before adjusting the thermostat  turn off all  power supplied to the indirect fired water heater        The potable water temperature can be changed by adjusting  the thermostat  Before any work is done on the water heater   disconnect all power to the water heater and heat source   boiler  by opening the switch s  at the main electrical circuit  breaker or fuse box  Remove the access panel and fold the  insulation outward away from the control  Adjust the  thermostat dial using a screwdriver until the minimum  acceptable temperature is achieved  The thermostat has been  factory preset to 120  F  49  C   Remember that lower  temperature settings are more energy efficient  Rotate  the temperature dial clockwise    to increase water  temperature  Rotate the thermostat dial counter clockwise   to decrease the temperature setting  Replace the  insulation mak
21. ntaining a plastic liner        INSTALL  TEMPERATURE AND PRESSURE  RELIEF VALVE    Cif not factory installed     Temperature and pressure relief valve discharge piping  must be piped near the floor to eliminate potential of    severe burns  Do not pipe in any area where freezing  could occur  Do not install any shut off valves  plugs or  caps to the temperature and pressure relief valve or    piping        INSTRUCTIONS FOR POTABLE  CONNECTIONS    1  BEFORE PROCEEDING WITH THE INSTALLATION   CLOSE THE MAIN WATER SUPPLY VALVE  After  shutting off the main water supply  open a faucet to  relieve the water line pressure to prevent any water  from leaking out of the pipes while making the water  connections to the water heater  After the pressure  has been relieved  close the faucet  The COLD water  inlet and HOT water outlet are identified on the top of  the water heater  Make the proper plumbing  connections between the water heater and the  plumbing system to the house  Install a shut off valve  in the cold water supply line    2  If this water heater is installed in a closed water supply  system  such as one having a back flow preventer in  the cold water supply  provisions must be made to  control thermal expansion  DO NOT operate this water  heater in a closed system without provisions for  controlling thermal expansion  Warranties do not cover  damages from thermal expansions such as pressure  bulges and or deformities  A properly sized expansion  tank will alleviate most p
22. ormer primary side  The second leg of the primary  side is to be connected to    L2     120V neutral   The secondary  side of the transformer is to be connected to the zone valve  coil  The contact side of the zone valve is to be connected to  the boiler operating control  Connect the black wire on the  water heater to    L1     120V hot   see figure5   These  connections enable the water heater thermostat to control  the zone valve and the boiler operating control     Other installations may require slightly different wiring  arrangements  In all cases it is important to remember that  the thermostat on the water heater only controls one leg of  the system     OPERATING INSTRUCTIONS    Water heaters are heat producing appliances  To avoid  damage or injury there must be no materials stored against  the water heater  and proper care must be taken to avoid  unnecessary contact  especially by children  with the  water heater  UNDER NO CIRCUMSTANCES SHALL  FLAMMABLE MATERIALS  SUCH AS GASOLINE OR  PAINT THINNER BE USED OR STORED IN THE  VICINITY OF THE WATER HEATER OR IN ANY  LOCATION FROM WHICH FUMES COULD REACH THE  WATER HEATER     Installation or service of this water heater requires  ability equivalent to that of a licensed tradesman in  the field involved  Plumbing and electrical work are  required        10    EGD 1 amp S 01       SYSTEM START UP    Follow boiler installation instructions to place boiler in A D A N Gi E R    operation     SEQUENCE OF OPERATIONS    1  Ther
23. rain  Failure to take this  precaution could mean contact with extremely hot  water discharging from the valve during this checking  operation     Thermal expansion is the normal response of water when it  is heated  In a closed system  thermal expansion will cause  the system pressure to build until the relief valve actuation  pressure is equaled  Then the relief valve will open  allowing  some water to escape  slightly lowering the pressure  Contact  your water supplier or local plumbing inspector on how to  control this situation     ABOVEALL  DO NOT PLUG THE TEMPERATURE AND  PRESSURE RELIEF VALVE  THIS IS NOTA SOLUTION  AND CAN CREATE A HAZARDOUS SITUATION        13    3  Anode Inspection and Replacement   This water heater    is equipped with multiple sacrificial anodes  Anodes  protect the glass lined tank from corrosion by  sacrificing themselves through electrolysis  When the  anode material is consumed  there is no more protection  and corrosion of the tank accelerates  Inspection of  the anode every year allows you to identify a spent  anode and replace  Replace the anode when its  diameter is 3 8 of an inch  or every other year  which  ever is first  Aggressive  very hot and softened water  causes rapid consumption of the anode  requiring  frequent inspections  Anodes are available from your  distributor or from the manufacturer    To inspect or replace an anode    The anodes on this water heater are easily accessible  from the top of the heater making replacement 
24. roblems  Your water supplier  or local plumbing inspector should be contacted on  how to control this situation    3  After installation of the water lines  open the main water  supply valve and fill the water heater  While the water  heater is filling  open several hot water faucets to allow  air to escape from the water system  When steady  streams of water flow through the faucets  close them  and check all water connections for possible leaks    4  NEVER OPERATE THE WATER HEATER  WITHOUT FIRST BEING CERTAIN THAT IT IS  FILLED WITH WATER     INSTRUCTIONS FOR BOILER CONNECTIONS   The indirect fired heater connection labeled    To Boiler  Return    should be piped to the boiler return piping as close  to the boiler as possible and especially after any flow control  or check valves in the space heating return piping  The use  of a union and a shut off valve is recommended  The use of  a flow control or check valve is required to prevent back  flow through the water heater during operation of the space  heating system  Pipe and fittings between the boiler and  indirect fired water heater should be 3   4    diameter or larger     EGD 1 amp S 01       CONNECT  WATER BOILER    SUPPLY PIPING Maximum boiler water supply temperature to the  indirect heat exchanger MUST NOT exceed 240  F    116  C         1  Fora space heating system that utilizes ZONE VALVES  refer to Figure 1  The indirect fired water heater connection  labeled    FROM BOILER SUPPLY    should be piped to the boiler
25. simple  and quick     a  Turn the water heater electricity off for the zone  containing the indirect fired water heater  Flow  water until the discharge is cool or allow enough  time for the potable water to cool naturally  Connect  a hose to the drain valve  Locate the hose   s  discharge in an area where any remaining hot water  will not cause any damage or injury    b  Open the drain valve to flush any sediment out of  the bottom to the heater    c  Shut off the cold water supply  Make sure all hot  water fixtures and circulating pumps are turned off    d  Wait for water flow from the hose to stop  Remove  the anode using a socket of the appropriate size   Do not use an impact wrench    e  Inspect and replace the anode as required  Use  pipe tape or sealant when reinstalling the anode    f  Close the drain valve  Open a hot water fixture to  allow air to escape  Open the cold water supply to  the heater and allow the tank to fill    g  Check your anode and drain valve for leaks    h  Turn the water heater electricity on for the zone  containing the indirect fired water heater       Sediment  Annual  but harsh water quality may    dictate more frequent service   Depending on water  conditions  a varying amount of sediment may collect  in the tank  Levels requiring service are indicated by a  small temperature difference in the supply and return  lines  See also    Scale    below   Repeated flushing  usually clears such material  As a preventive measure   water should be dra
26. t too high  Adjust thermostat setting  See Section VII        too hot  Improper system plumbing  Compare plumbing to Section V        Improper system wiring  Compare wiring to Section VI        Insufficient hot Thermostat setting Adjust thermostat to higher setting     water  too low  See Section VII        Undersized boiler with Rewire for priority   no priority to domestic    hot water        Peak use of hot water Determine peak usage and compare to  is greater than tank storage tank capacity     capacity        Faulty tank thermostat  Replace thermostat        Boiler cycles Excessive demand  Reduce demand or consider larger tank        more than 5 Faulty thermostat  Replace thermostat        times per day Boiler high limit set too low  Increase boiler high limit setting     in summer        14    
27. ter thermostat and the boiler  Connect the  white wire on the water heater to one leg of the circulator   The second leg of the circulator is to be connected to    L2      120V neutral   Connect the white wire on the water heater  to one leg of the zone relay  The second leg of the zone relay  is to be connected to    L2     120V neutral   The contact side  of the zone relay is to be connected to the boiler operating  control  see figure 4   Connect the black wire on the water  heater to    L1     120V hot   These connections enable water  heater thermostat to control the circulator  the zone relay   and the boiler operating control     Figure 4     Electrical Connection with Circulator       WIRE NUT OR  EQUIVALENT       120V HOT       JUNCTION  BOX       I                 Me ee    WHITE    THERMOSTAT        L2    120V  NEUTRAL    CIRCULATOR    ZONE RELAY  HONEYWELL R4222  OR EQUIVALENT  m Aq       L2    120V  NEUTRAL    TO BOILER  OPERATING  CONTROL    EGD 1 amp S 01       Figure 5     Electrical Connection with Zone Valve    JUNCTION BOX       L1    120V 120VAC   24VAC  HOT     REUTRAL  ZONE  STEP DOWN  TRANSFORMER    WIRE NUT OR  EQUIVALENT                 END SWITCH    ZONE VALVE    TO BOILER CONTROL  CIRCUIT    If a zone valve to used to control the heating fluid flow from  the boiler to the water heater  a zone step down transformer  is required between the water heater thermostat and the zone  valve  Connect the white wire on the water heater to one leg  of the transf
28. tion of the anode is needed when using       softened  or phosphate treated  water  Contact the plumbing  professional who installed the water heater or the  manufacturer  listed on the rating plate  for anode replacement  information     PRE INSTALLATION    UNPACKING   INSPECT SHIPMENT carefully for any signs of damage  If  damage is noted  do not install the product  Contact the  shipper or manufacturer  All equipment is carefully  manufactured  inspected  and packed  Our responsibility  ceases upon delivery of the packaged water heater to the  carrier in good condition     NOTE  Any claims for damage or shortage in shipment must  be filed immediately against the carrier by the consignee     This water heater MUST be installed indoors out of the wind  and weather     IMPORTANT DECISIONS  REQUIRED  BEFORE INSTALLATION    SIZING   1  Boiler DOE Heating Capacity     The indirect fired  water heater will provide the rated performance only  if used in conjunction with a heat source with a DOE  heating capacity  Heat Output  at least as much as  the minimum noted in Table 3  If the heat source has  less capacity  the output of the tank will be reduced   To determine the approximate reduction in output  from the tank use the following formula     New Rating    maximum continuous draw rating  x    Actual Output of Heat Source  Minimum Output of Heat Source       For example  what would the continuous draw  rating be if a 50 gallon indirect fired water heater  were installed with a 
29. ture and pressure of the water  heater  This water heater contains components that  become very hot  Do not touch any components unless  they are cool     Improper installation  adjustments  alteration  service  or maintenance can cause property damage  personal  injury or loss of life  Failure to follow all instructions  in the proper order can cause personal injury or  death  Read and understand all instructions  including  all those contained in component manufacturer   s  manuals  which are provided with the appliance before  installing  starting up  operating  maintaining  or  servicing this appliance  Keep this manual and  literature in legible condition and posted near the  appliance for reference by owner and service  technician     This water heater requires regular maintenance and  service to operate safely  Follow the instructions  contained in this manual  Installation  maintenance   and service must be performed only by an experienced   skilled  and knowledgeable installer or service  agency     NOTICE    Insulation blankets are not required for this water  heater  This water heater meets or exceeds the  ASHRAE IES 90 1b standards with respect to  insulation and standby loss requirements     It is the responsibility of the installing contractor to  see that all controls are correctly installed and are  operating properly when the installation is complete     DO NOT operate the water heater with jumpered or  absent controls or safety devices     DO NOT tamper with
30. wn from the tank at the drain valve  until it runs clear       Scale  Annual   Hard water may cause scale to build     up on the outside of the heat exchanger coil  A water  softener will prevent this problem  See also    Sediment     above   Symptoms would be reduced recovery  capacity or reduced temperature differential between  boiler supply and return lines  Repeated flushing should  resolve the problem     EGD 1 amp S 01       TROUBLESHOOTING GUIDE    PROBLEM CAUSE SOLUTION    No hot water Boiler does not Refer to boiler installation instructions   at faucet  operate  Check main service switch     Check fused disconnect        Circulator does not Check power supply        operate  Replace as necessary        Temperature high Determine reason for trip   limit on thermostat Depress red    RESET       tripped  button on thermostat        Improper Adjust tank thermostat to  thermostat setting appropriate setting     or calibration  See Section VII       Zone valve does Check power supply        not open  if used   Replace as necessary        Electrical problem Check fuse and replace         relay  wiring  etc    Check circuit breaker and reset  if applicable         Check power supply        Scale build up  If boiler  circulator  and tank are operating   satisfactorily  coil may have scale coating     See Section VIII  Maintenance        Clogged cold water Clean or replace filter or strainer   filter or boiler supply    strainer  if used         Water at faucet Thermostat se
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Hotpoint TCEl 87B Experience Clothes Dryer User Manual  Nibe Ground Source Heat Pump Brochure  Fiche technique UE65JU7500 Samsung  SERVICE MANUAL - Wiki Karat  SEAT Portable System  LM1095R-2 - topwaydisplay.com  PRIMO VIAGGIO SIP 30  YASKAWA AC Drive-V1000 Option CANopen  view data sheet - Electro Rent Corporation  紙幣送り部の隙間調整方法    Copyright © All rights reserved. 