1. E 1 BOILER LOCATION EE 2 PROVIDE AIR FOR COMBUSTION AND VENTILATION eere 2 ELECTRICAL WIRING C een 3 GAS SUPPLY AND PIPING uuu aus a n ai 3 VENTING P 4 SAFETY DEVICES Ep tee duse le 8 FREEZE PROTECTION T 8 WARNING REGARDING CHILLED WATER SYSTEMS eese 9 PIPING OF BOILER TO THE SYSTEM FIG 3 n u 9 PLACING BOILER OPERATION nes asia E edis denter onte 11 CHECK OUT OF IGNITION SYSTEM SAFETY SHUT OFF DEVICE 11 LOW WATER TEMPERATURE SYSTEMS 11 INSTANTANEOUS WATER 13 PILOT AND MAIN BURNER FLAMES 13 OPERATION AND SERVICE denas 16 LIGHTINGINSTRUCTIONS H 17 TROUBLE SHOOTING GUIDE lt tirado Ea Du Heb 18 TYPICAL GAS TRAN u usus asa e a 19 ELECTRICAL DIAG dictu vnde dd ladies fam dass EN doc uan teen 19 EXPLODED VIEW M 22 BLUE FLAME REPLACEMENT PARTS LIST
2. ams Cus eepba ae 23 24 INTRODUCTION Camus Hydronics proudly introduces its Blue Flame Series of Water Heaters Hydronic Boilers These machines are thoughtfully designed for easy operation and maintenance We are confident that you will come to appreciate the benefits of our product 1 GENERAL INSTRUCTIONS The installation of this heater must conform to the requirements of the authority having jurisdiction or in the absence of such requirements to the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 Installation Codes All electrical wiring must be done in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code Part I CSA C22 1 Electrical Code Vent installations must be in accordance with Part 7 Venting of Equipment of the National Fuel Gas Code ANSI Z223 1 or Section 7 Venting Systems and Air Supply for Appliances of the CAN CGA B149 1 Installation Codes and applicable provisions of the local building codes When required by the authority having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 The qualified installer shall instruct the end user in the safe and correct operation of this appliance and s
3. 5 8 5 gt mo g 5 m g 5 o Outdoor Venting 92 P 11 14 30 gt L 220 99 80 P amp V e 486 DI 4 z z 5 gt ny 5 mi 3 Lj 6 1 1 Figure 1 7 SAFETY DEVICES 7 4 WATER FLOW SWITCH shipped loose A water flow switch is shipped loose and is to be installed in the outlet piping on all heating boilers and hot water supply boilers The flow switch is wired in series with the 24VAC safety control circuit A diagnostic light will be indicated on the control display on a low flow condition 7 2 LOW WATER CUTOFF If Equipped If this boiler is installed above radiation level a low water cut off device must be installed at the time of boiler installation Some local codes require the installation of a low water cut off on all systems Electronic low water cut offs are available as a factory supplied option on all models Low water cut offs should be tested every six months The normally open switch contact of the low water cutoff is to be wired in series with the flow switch A diagnostic light will be indicated on the control display on a low flow condition Cau
4. ANSI Z223 1 or Section 7 Venting of Equipment and Air Supply for Appliances of the CAN CGA B149 1 Installation Codes and applicable provisions of the local building codes Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure Horizontal runs of vent pipe shall be securely supported approximately every 4 feet to prevent sagging and maintain a minimum upward slope of 1 2 per foot from the boiler to the vent terminal When an existing boiler is removed from a common venting system the common venting system is likely to be too large for proper venting of the appliances remaining connected to it At the time of removal of an existing boiler the following steps must be followed with each 4 appliance remaining connected to the common venting system placed in operation while the other appliances remaining connected to the common venting system are not in operation a b c Seal any unused openings in the common venting system Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage restriction leakage corrosion or other deficiency which could cause an unsafe condition Insofar as is practical close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces o
5. attention to water flow rates will ensure that temperature rise does not exceed 35 19 4 The following table 2 is provided as a guide For application in areas known to have hard water conditions contact factory for recommendations TABLE 2 20 F 11 TEMP 30 F 16 7 TEMP 35 F 19 49C TEMP RISE RISE RISE Model 0 5 AP ft U S AP ft U S AP ft G P M G P M G P M BF 480 40 0 0 5 26 5 0 3 22 5 0 2 BF 660 55 0 1 1 36 5 0 5 31 0 0 4 BF 840 70 0 2 1 46 5 0 9 40 0 0 7 BF 1020 85 0 3 3 56 5 1 5 48 5 12 1200 p p 66 5 23 57 0 17 BF 1380 2 p 76 5 35 65 5 2 5 BF 1560 5 p 86 0 4 5 74 0 34 BF 1740 96 0 5 9 82 0 45 1950 E p 108 0 6 8 92 5 6 0 Contact Camus for recommendation If the boiler is installed above radiation level it must be provided with a low water cutoff device Figure 3 at the time of boiler installation Available from factory To eliminate trapped air install venting devices at high points in the system as well as in the piping on the suction of the pump and in the piping on the discharge of the boiler Use suitable pipe hangers or floor stands to support the weight of all water and gas piping Do not allow the boiler to run with inlet water temperature below 110 F The boiler must be installed so that the gas ignition system components are protected from water dripping spraying rain etc during appliance operati
6. is e Check wiring to switch flipped to ON e Check circuit breaker e Check fuse 2 Water flow light remains off e Ensure that pump is running e Check wiring to flow switch 3 Pilot sparks but does not light e Make sure that main manual valve is open e Follow lighting instructions to bleed air out of pilot line e Remove pilot burner and inspect for moisture or dirt in pilot or in pilot line 4 Pilot lights momentarily goes out and then sparks again repeatedly Observe pilot for proper flame Adjust if necessary e Remove pilot and ensure that spark electrode is clean and properly located 5 Pilot lights but main burner does not fire e Ensure that main firing valve is in OPEN position e Check wiring to valve from ignition control 6 Main burner lights but cycles off after a few minutes Make sure that high limit is set high enough to prevent short cycling e Adjust pilot pressure for steady flame e Remove pilot and clean ignition sensor 7 Boiler starts to whine as the temperature e Make sure that all air is bled from rise increases system e Make sure that the static pressure in cold system is at least 15 psig e Check temperature rise across boiler to ensure adequate water flow e f necessary increase static water pressure and decrease gas pressure 18 19 TYPICAL GAS TRAIN ain Appliance Valve 20 ELECTRICAL DIAGRAMS Each Blue Flame boiler will be provided wit
7. or more are considered seasonal operations It is recommended that before returning one of these units to service the proper operation of all controls be checked by a qualified service technician 16 17 LIGHTING INSTRUCTIONS 1 Turn off electric power to boiler 2 Close main manual valve and main firing valve and wait 5 minutes 3 Set primary system controller to desired temperature 4 Set main manual valve to pilot position 5 Turn on electric power to boiler The electrode at the pilot should begin to spark This can be observed with a mirror The pilot valve will open to permit gas flow to the pilot 6 There is a 15 second trial for ignition which is enough time to light the pilot if air is not present in the pilot line If pilot fails to light and you suspect air in the line close the main manual valve and repeat lighting steps 1 thru 5 7 Once the pilot lights it should envelope the ignition rod and ground strap Removing the pilot regulator cover and turning the adjustment screw can adjust the pilot 8 Open the main firing valve to allow gas to reach the main burners If the main burners fail to ignite turn the main firing valve off to see if the pilot is burning If not repeat lighting procedure steps 1 thru 7 TO TURN OFF BOILER Close main manual valve and main firing valve and turn off electric power to system 17 18 TROUBLE SHOOTING GUIDE SYMPTOM SOLUTION 1 Power light is not lit when switch
8. the ignition electrode using sandpaper Once the pilot appears to be properly set reinstall it into the boiler making sure to properly tighten the pilot line connection Once the spark is satisfactory open the pilot gas and allow the pilot burner to light Once air has been purged from the pilot line the pilot flame should appear almost instantly at the initiation of spark Cycle the pilot several times to confirm reliability A properly set pilot will appear blue and will engulf the ignition sensor and ground plate See figure 7 Flame Ground Plate Ignition Sensor Figure 7 Turn the gas control to ON and allow the main burner to light The pilot must not extinguish After running for 15 minutes cycle the boiler to ensure that the pilot remains stable 15 16 OPERATION AND SERVICE OPERATION Before operating the boiler the entire system must be filled with water purged of air and checked for leaks Do not use Stop leak or other boiler compounds The gas piping must also be leak tested Any safety devices including low water cutoff flow switch and high limit used in with this boiler must receive periodic inspection every six months to assure proper operation a low water cutoff of the float type should be flushed every six months All relief valves should be inspected and manually operated every six months For your safety follow the lighting and operating instructions below and on t
9. 3 210 3 21 2 1 740 000 21 2 2 3 210 3 21 2 1 950 000 210 2 3 210 3 21 2 6 VENTING Boilers for outdoor installation are intended to vent using a listed vent cap The BlueFlame windproof cabinet protects the unit from weather when fitted with the factory supplied air intake and UL approved vent cap 93 0297 it will be self venting and suitable for outdoor installation 1 Outdoor models must be installed outdoors and must use the air intake and vent cap supplied by Camus Hydronics Alternately a listed vent cap may be used along with the Camus supplied air intake Periodically check to ensure that air intake and vent cap are not obstructed Locate appliance at least 3 feet away from any overhang Locate appliance at least ten feet from building air intake Avoid installation in areas where runoff from adjacent building can spill onto appliance For outdoor installations always consider the use of a shelter such as a garden shed in lieu of direct exposure of the appliance to the elements The additional protection afforded by the shelter will help to minimize nuisance problems with electrical connections and will allow easier servicing of the appliance under severe weather conditions Q9 OP For indoor installations the draft hood provided with this boiler must be installed without alteration Vent installations must be in accordance with Part 7 Venting of Equipment of the National Fuel Gas Code
10. 4 0241 03 14 0241 04 14 0241 05 14 0241 06 14 0241 07 14 0241 08 14 0241 09 23 WARRANTY GENERAL Camus Hydronics Limited Camus extends the following LIMITED WARRANTY to the owner of this appliance provided that the product has been installed and operated in accordance with the Installation Manual provided with the equipment Camus will furnish a replacement for or at Camus option repair any part that within the period specified below shall fail in normal use and service at its original installation location due to any defect in workmanship material or design The repaired or replacement part will be warranted for only the unexpired portion of the original warranty This warranty does not cover failures or malfunctions resulting from 1 Failure to properly install operate or maintain the equipment in accordance with Camus manual 2 Abuse alteration accident fire flood foundation problems and the like 3 Sediment or lime buildup freezing or other conditions causing inadequate water circulation 4 Pitting and erosion caused by high water velocity 5 Failure of connected systems devices such as pump or controller 6 Use of non factory authorized accessories or other components in conjunction with the system 7 failing to eliminate air from or replenish water in the connected water system 8 Chemical contamination of combustion air or use of chemical additives to water HEA
11. 7 14 0133 08 14 0133 09 2 Left Front Post 14 0234 14 0234 14 0234 14 0234 14 0234 14 0234 14 0234 14 0234 14 0234 3 Left Rear Post 14 0235 14 0235 14 0235 14 0235 14 0235 14 0235 14 0235 14 0235 14 0235 4 Right Front Post 14 0236 14 0236 14 0236 14 0236 14 0236 14 0236 14 0236 14 0236 14 0236 5 Right Rear Post 14 0237 14 0237 14 0237 14 0237 14 0237 14 0237 14 0237 14 0237 14 0237 6 Front Panel Top 14 0238 01 14 0238 02 14 0238 03 14 0238 04 14 0238 05 14 0238 O6 14 0238 07 14 0238 08 14 0238 09 7 Front Panel Bottom 14 0239 01 14 0239 02 14 0239 03 14 0239 04 14 0239 05 14 0239 06 14 0239 07 14 0239 08 14 0239 09 8 Rear Panel 14 0222 01 14 0222 02 14 0222 03 14 0222 04 14 0222 05 14 0222 06 14 0222 07 14 0222 08 14 0222 09 9 Top Panel 14 0211 01 14 0211 02 14 0211 03 14 0211 04 14 0211 05 14 0211 06 14 0211 07 14 0211 08 14 0211 09 10 dr 14 0165 14 0165 14 0165 14 0165 14 0165 14 0165 14 0165 14 0165 14 0165 11 Side 2 14 0163 14 0163 14 0163 14 0163 14 0163 14 0163 14 0163 14 0163 14 0163 Inner Jacket 12 Draft Hood 14 0092 01 14 0092 02 14 0092 03 14 0092 04 14 0092 05 14 0092 06 14 0092 07 14 0092 08 14 0092 09 13 Flue Collector 14 0177 01 14 0177 02 14 0177 03 14 0177 04 14 0177 05 14 0177 06 14 0177 07 14 0177 08 14 0177 09 14 bu d 14 0189 01 14 0189 02 14 0189 03 14 0189 04 14 0189 05 14 0189 06 14 0189 07 14 0189 08 14 0189 09 15 Inner Fro
12. CO levels for complete combustion Light off smoothly Reasonably quiet while running Stable flame with minimum of lifting Blue flame with natural gas yellow tips with propane gas 13 4 AN x 4 ON NS N Figure 6 If burner characteristics do not match the above check for accumulation of lint and other foreign material at burner air inlets A qualified service technician should follow this procedure when burners need cleaning 1 Shut off power and close main manual gas valve e Allow burners to cool before removal 2 Loosen union and remove main burner tray assembly from boiler 3 Remove and thoroughly clean burners Check all ports and air channels for blockage 4 Reinstall the burners 5 Restore electrical power and gas supply to the boiler e Following the lighting instructions put the boiler back into operation e Check for gas leaks and proper boiler and vent operation 14 15 2 PILOT BURNER Turn the gas valve control knob counterclockwise to off position and allow the boiler to try for ignition Observe the spark making sure that it is strong and continuous If the spark is not acceptable the igniter will have to be removed This can be readily accomplished by first removing the burners tray assembly from the boiler as detailed in 15 1 The spark gap should be 1 8 to 3 16 Make sure that the electrode does not appear overheated or fouled with carbon It may be necessary to clean
13. IM Any claim under this warranty shall be made directly to Camus Hydronics Limited Canadian Head Office SERVICE LABOR RESPONSIBILITY Camus shall not be responsible for any labour expenses to service repair or replace the components supplied Such costs are the responsibility of the owner DISCLAIMERS Camus shall not be responsible for any water damage Provisions should be made that in the event of a water appliance or fitting leak the resulting flow of water will not cause damage to its surroundings Y i i Aq ts ig Name of Owner Name of Dealer Address Address Model No Serial No Date of Installation Date of Initial Operation 6226 Netherhart Road Mississauga Ontario L5T 1B7 CANADA 24 CAMUS Hydronics is a manufacturer of replacement parts for most copper finned water heaters The CAMUS CERTIFIED Seal assures you that Reliability Efficiency amp serviceability are built into every and heating ARAIIC single unit boilers as well CAMUS For more eens aSa supplier of specialty HVAC products Our service line is open 24 hours 7 days a week information on our innovative products from CAMUS Hydronics Limited call 905 696 7800 today CAMUS HYDRONICS LTD 6226 Netherhart Road Mississauga Ontario L5T 1B7 TEL 905 696 7800 FAX 905 696 8801
14. INSTALLATION OPERATION AND SERVICE MANUAL GAS FIRED COMMERCIAL COPPER TUBE BOILERS BLUE FLAME SERIES FOR HYDRONIC HEATING Models BFH 480 660 840 1020 1200 1380 1560 1740 1950 HOT WATER SUPPLY Models BFW 480 660 840 1020 1200 1380 1560 1740 1950 h W CERTIFIED WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death e Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance e WHAT TO DO IF YOU SMELL GAS o Donottry to light any appliance o Do nottouch any electrical switch do not use any phone in your building o Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instruction o lf you cannot reach your gas supplier call the fire department e Qualified installer service agency or the gas supplier must perform installation and service To the installer After installation these instructions must be given to the end user or left on or near the heater To the End User This booklet contains important information about this heater Retain for future reference 6226 Netherhart Road Mississauga Ontario L5T 1B7 99 0030 Rev 03 01 Table of Contents 10 11 12 13 14 15 16 17 18 19 20 21 22 GENERAL INSTRUCTIONS
15. T EXCHANGER If within TEN years after initial installation of the appliance a heat exchanger shall prove upon examination by Camus to be defective in material or workmanship Camus will exchange or repair such part or portion on the following pro rated limited warranty 1 Years one through five standard warranty 2 Years six through ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of the current list price This term is reduced to FIVE years if the appliance is used for other than hydronic space heating Heat Exchanger shall be warranted for 20 years from date of installation against Thermal Shock excluded however if caused by appliance operation at large changes exceeding 150 F between the water temperature at intake and appliance temperature or operating at appliance temperatures exceeding 230 F BURNER If within ONE year after initial installation of the appliance a burner shall prove upon examination by Camus to be defective in material or workmanship Camus will exchange or repair such part or portion ANY OTHER PART If any other part fails within one 1 year after installation or eighteen 18 months from date of factory shipment based on Camus records whichever comes first Camus will furnish a replacement or repair that part Replacement parts will be shipped f o b our factory HOW TO MAKE A CLA
16. by 2096 A snow screen should be installed to prevent snow and ice accumulation around the boiler Regular inspections should be made to ensure that air intake and vent are free of snow and ice 9 WARNING REGARDING CHILLED WATER SYSTEMS When a boiler is connected to an air conditioning system where the same water is used for heating and cooling the chiller must be piped in parallel with the boiler Appropriate flow control valves manual or motorized must be provided to prevent the chilled water from entering the boiler See figure 2 Supply y Return X X Chiller Q s Boiler Pump DOhFNha gt lt Figure 1 When a boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation the boiler piping system shall be equipped with a flow control valve or other automatic means to prevent gravity circulation of chilled water through the boiler Chilled water in the boiler will create condensate on the boiler tubes which will collect in the combustion chamber causing corrosion 10 PIPING OF BOILER TO THE SYSTEM FIG 3 Check all applicable local heating plumbing and building safety codes before proceeding Be sure to provide unions and gate valves at inlet and outlet to boiler so that it can be easily isolated for service This boiler is of a low mass design which provides for instant heat transfer Special
17. f the building Turn on the clothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed do not operate a summer exhaust fan Close fireplace dampers d e Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so that appliance operates continuously Test for spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous condition of use Any improper operation of the common venting system must be corrected so that the installation conforms to the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 Installation Codes When resizing any portion of the common venting system the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 Installation Codes Heat exchanger surfaces and vent piping should be checked every six months for deterioration and carbon deposits Remove all soot or other obstructions from the chim
18. h its own wiring diagram to guarantee that any options ordered with the unit are properly detailed The following diagrams 99 5020 and 99 5021 are provided as typical samples only 19 0 38 020G 66 DAC d 2 411 SOINDSOAH SNWYI SIN 1 1192 lt 0 S2 40 3140 099 088 44D MD HYAS INYTIATIE i830 2 a tupoy pp parodas 24 acu pasota aq zcuopds au pajddnz zo uppoa au 4n Aus 4 Q 840N HO v2 2 IND AF2 YA 14 HOAS 20 o 33 1206 66 DAT dota 1111 SIINOATAH ENWI qd SIN 33 0 54 40 3190 0661 OFS 1 24 5 NOLIN HOSS 3NY13311E INS FC 2 gx zurquaaduz u jopragou panoda aq acu pamatas aq au up padre 4n Aun gE Q S30N WADI NDLL33NMID v2 B IND AF2 HL YA 14 440 40 21 21 EXPLODED VIEW Model Key Description Item 480 660 840 1020 1200 1380 1560 1740 1950 Outer Jacket Base Panel 1 jen 14 0133 01 14 0133 02 14 0133 03 14 0133 04 14 0133 05 14 0133 06 14 0133 0
19. hall ensure that the heater is in safe working order prior to leaving the job site WARRANTY Factory warranty shall apply only when the boiler is installed in accordance with e Local codes standards ordinances and regulations e The printed instructions provided with the boiler and e Good industry practices Excessive water hardness causing a lime build up in the copper coils or tubes is not a fault of the boiler and is not covered by warranty Consult the factory for recommendations for use in hard water areas Using or storing corrosive chemicals in the vicinity of this boiler can rapidly attack the copper tubes and coils and voids warranty This boiler is intended to operate under non condensing conditions Inlet temperatures must be maintained at 110 F or higher Warranty is void if heater is allowed to operate in condensing mode Damage caused by freezing or dry firing voids warranty This boiler is not to be used for temporary heating of buildings under construction 2 BOILER LOCATION Install this boiler in a clean dry location with adequate air supply and close to a good vent connection Do not locate this boiler in an area where it will be subject to freezing The boiler must not be installed on carpeting and should be located close to a floor drain in an area where leakage from the boiler or connections will not result in damage to the adjacent area or to lower floors in the structure If necessary a suitable drain pa
20. he boiler To turn on main burners slowly turn manual main gas on after pilot is established Set primary system controller to desired temperature To turn off boiler close main manual gas valve close pilot manual valve and turn off electric power to system SERVICE Disconnect main power and turn off gas supply before servicing unit To remove and clean the burners follow the detailed procedure in section 15 of this manual After the first season of operation inspect the heat exchanger and venting Follow the detailed instructions in section 6 of this manual CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Any audible sounds in the equipment like pinging crackling or hissing are indications of scaling or lack of sufficient water flow Under these conditions the boiler must be shut down immediately and the heat exchanger and coils checked for damage If the exchanger is damaged from scaling it is not covered by warranty Should your equipment be subjected to fire flood or some other unusual condition turn off all gas and electrical supply If you are unable to turn off the gas call your gas company or gas supplier at once Do not put the unit back in operation until it has been checked by a qualified agency to ensure that all controls are functioning properly Units that are not operated for a period of 60 days
21. n should be installed under the boiler If the boiler is installed above the level of the building s radiation system a low water cutoff device must be installed in the boiler outlet at the time of installation Some local codes require the installation of a low water cutoff on all systems Locate the boiler so as to provide adequate clearance for inspection and service all around the unit It is recommended that 24 be provided for the top and sides and 48 for the front This boiler is suitable for alcove installation with minimum clearances to combustibles as follows TOP 12 SIDES 12 REAR 12 VENT 6 3 PROVIDE AIR FOR COMBUSTION AND VENTILATION Provisions for combustion and ventilation air must be in accordance with section 5 3 Air for combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 1 Installation Codes and applicable provisions of the local building codes The operation of exhaust fans compressors air handling units etc can rob air from the room creating a negative pressure condition leading to reversal of the natural draft action of the venting system Under these circumstances an engineered air supply is necessary If the heater is to be installed near a corrosive or potentially corrosive air supply the heater must be isolated from it and outside air should be supplied as per code Potentially corrosive atmosphe
22. ney and flue which might impede draft action Replace any damaged or deteriorated parts of the venting system A qualified service technician should follow this procedure when inspecting and cleaning the heat exchanger and vent pipe 1 2 Turn off electrical power and close main manual gas shut off and allow boiler to cool down Remove the boiler draft diverter and vent pipe running to chimney e Check heat exchanger vent and chimney for obstruction and clean as necessary Remove burner tray from boiler and vacuum top heat exchanger and coils Reinstall parts removed in steps 2 and 3 e Besure that vent pipe has proper pitch and is properly sealed Restore electrical power and gas supply to boiler e Place boiler in operation using lighting instructions provided e Check for gas leaks and proper vent operation Three venting options are available for this boiler See Figure 1 below for details 95 96 wh 88 9 08 24 we 42 99 744 we OE i Seg 18 Y SM BuruaA piepue1s 486 Vent oy s 96 4488 9 08 C we Eg 4445 AZ we DE 100p1nQ 7 d o
23. nt Panel 14 0112 01 14 0112 02 14 0112 03 14 0112 04 14 0112 05 14 0112 06 14 0112 07 14 0112 08 14 0112 09 16 Inner Rear Panel 14 0153 01 14 0153 02 14 0153 03 14 0153 04 14 0153 05 14 0153 06 14 0153 07 14 0153 08 14 0153 09 Support Front amp Rear 17 Refractory Support 14 0301 01 14 0301 02 14 0301 03 14 0301 04 14 0301 05 14 0301 06 14 0301 07 14 0301 08 14 0301 09 Beam 18 Heat Exchanger 16 0017 16 0017 16 0017 16 0017 16 0017 16 0017 16 0017 16 0017 16 0017 Support Frame Left Heat Exchanger 19 Support Frame 16 0001 16 0001 16 0001 16 0001 16 0001 16 0001 16 0001 16 0001 16 0001 Right Refractory 20 End Tile 17 0031 17 0031 17 0031 17 0031 17 0031 17 0031 17 0031 17 0031 17 0031 21 Rear Tile Set 17 0034 01 17 0034 02 17 0034 03 17 0034 04 17 0034 05 17 0034 06 17 0034 07 17 0034 08 17 0034 09 22 FrontTile Set Lower 17 0045 01 17 0045 02 17 0045 03 17 0045 04 17 0045 05 17 0045 06 17 0045 07 17 0045 08 17 0045 09 Burner 23 Burner Tray 66 0080 01 86 0080 66 0080 03 66 0080 04 66 0080 05 66 0080 06 66 0080 07 66 0080 08 66 0080 09 Assembly 02 Electrical 24 Electrical Control Box 14 0200 14 0200 14 0200 14 0200 14 0200 14 0200 14 0200 14 0200 14 0200 Outdoor Jacket 25 Outdoor Vent 14 0240 01 14 0240 02 14 0240 03 14 0240 04 14 0240 05 14 0240 06 14 0240 07 14 0240 08 14 0240 09 26 2 Panel 0241 01 14 0241 02 1
24. o operate at inlet gas pressures not exceeding psi 14 water column If higher pressures are present consult the gas company for correction When pressure testing the gas supply piping at pressures above psi the boiler and its individual gas shut off valve must be disconnected from the supply piping Provide a trap drip leg as close to the heater as possible Install a good joint union and manual shut off valve in the gas line near the heater to allow easy removal of the gas control assembly Provide gas pressures at inlet to boiler gas train as follows PROPANE NATURAL GAS Minimum inches water column 11 5 Maximum inches water column 11 7 The gas supply line must be of adequate size to prevent undue pressure drop and must never be smaller than the size of the connection on the heater Sizing based on Table 1 is recommended Before operating the boiler the complete gas train and all connections must be tested using soap solution TABLE 1 DISTANCE FROM NATURAL GAS METER OR PROPANE SECOND STAGE REGULATOR Input 0 100 FT 100 200 FT 200 300 FT Btu hr NAT E P NAT L P NAT L P 480 000 i 172 17 2 172 660 000 172 TA 2 1 2 2 1 7 840000 7 1g TA 2 27 2 1 020 000 2 18 21 2 2 21 2 2 1 200 000 21 2 2 21 2 2 3 21 2 1 380 000 21 2 2 21 2 2 3 21 2 1 560 000 210 2
25. on and service circulator replacement control replacement etc 10 11 PLACING BOILER IN OPERATION The Blue Flame boiler should be installed and started up by qualified personnel With the boiler off open makeup water valve and allow system to fill slowly Adjust the pressure regulator to provide at least 15 psig at the highest point in the system With all air vents open run system circulating pump for a minimum of 30 minutes with the boiler off Open all strainers in the circulating system and check for debris Check liquid level in expansion tank With system full of water at 15 psig the level of water in the expansion tank should not exceed 1 4 of the total volume with the balance filled with air Start up boiler following instructions provided Operate entire system including pumps and radiation for at least 1 hour Check water level in expansion tank If level exceeds 1 2 of tank volume air is still trapped in system Shut down boiler and continue to run pumps Within 3 days of start up recheck all air vents and expansion tank as described above 12 CHECK OUT OF IGNITION SYSTEM SAFETY SHUT OFF DEVICE After initial fill while the main burner is firing shut off gas to the pilot and clock the time taken for the main gas valve to shut down If the safety control is functioning properly power to the gas valve will be shut off within 4 seconds of the pilot gas being shut off If shut down takes longer ignition cont
26. res will result from exposure to permanent wave solution chlorinated waxes and cleaners chlorine water softening chemicals carbon tetrachloride halogen based refrigerants Freon cleaning solvents hydrochloric acid cements and glues masonry washing materials antistatic fabric softeners dry cleaning solvents degreasing liquids printing inks paint removers etc 4 ELECTRICAL WIRING All electrical wiring to the boiler must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code Part CSA C22 1 Electrical Code Provide disconnecting means of sufficient rating within sight of the boiler These heaters require an 115 V 60 hz supply Depending on the pump used a 15 amp breaker is usually sufficient Electrical connections must be made so that the circulator will operate before the gas valve can open At no time may the control system allow the burner to fire without water flowing in the system Use minimum 18 gauge conductor for 24 volt field wiring to boiler Splicing of wires is not recommended Use sealed tight conduit suitable for outdoor use for outdoor installations For low water cutoff and remote controller use terminal strip provided inside control panel Refer to wiring diagram provided with boiler 5 GAS SUPPLY AND PIPING This boiler is intended t
27. rol or gas valve may be defective 13 LOW WATER TEMPERATURE SYSTEMS In applications where the heating system requires supply water temperatures below 110 F a bypass line must be installed upstream of the boiler pump so that outlet water can be re circulated to raise the inlet temp to a minimum of 110 F Balancing valves preferably globe valves are used to adjust flow See figure 4 11 Figure 4 Adjustment procedure Fully open bypass and outlet valves With boiler running read the inlet temperature after 15 minutes If the inlet temperature is less than 110 F slowly close outlet valve until the inlet temperature climbs to 110 F If the inlet temperature is greater than 110 F but not greater than 140 F no further adjustment is required Check the inlet temperature after 5 minutes and make final adjustments 12 14 INSTANTANEOUS WATER HEATER An instantaneous water heater is designed to deliver hot water without the use of a storage tank It is suitable for applications with variable load such as restaurants condominiums apartments and motels See figure 5 Call Camus for further recommendations Figure 5 15 PILOT AND MAIN BURNER FLAMES To maintain safe operation and the greatest efficiency of the boiler check the main burner and pilot burner every six months for proper flame characteristics 15 1 MAIN BURNER The main burner figure 6 should display the following characteristics Acceptable CO and
28. tion remove jumper when connecting to 24 VAC circuit WARNING Be sure to LN C remove the jumper between Hand Pl Connection detail for placing L W C O in 24V circuit in series with flow switch ko T kT 247 FLOW SWITCH TH AIR SWITCH 7 3 RELIEF VALVE shipped loose This appliance is supplied with a relief valve sized in accordance with ASME Boiler and Pressure Vessel Code Section IV Heating Boilers The relief valve is to be installed in the vertical position and mounted in the hot water outlet No valve is to be placed between the relief valve and the appliance To prevent water damage the discharge from the relief valve shall be piped to a suitable floor drain for disposal when relief occurs No reducing couplings or other restrictions shall be installed in the discharge line The discharge line shall allow complete drainage of the valve and line Relief valves should be manually operated at least once a year 8 FREEZE PROTECTION Boiler installations are not recommended in areas where the danger of freezing exists unless precautions are taken Maintaining a mixture of 50 water and 50 propylene glycol is the preferred methods of freeze protection in hydronic systems This mixture will protect the boiler to approximately 35 37 C To maintain the s ame temperature rise across the boiler increase the G P M flow by 1596 and the head loss
Download Pdf Manuals
Related Search
Related Contents
InLine 16461Q power extension XXX man laser DW060 Euro part A.indd - Service après vente DELL M900HD WS-833 WS-832 WS-831 Soleus Air SG-DEH-25M-1 Dehumidifier User Manual FactoryTalk View Machine Edition User's Guide Gist of Contract User Manual Version 1.0 3A1060E - TrueCoat and TrueCoat Plus Operation, French Copyright © All rights reserved.