        LOVE CONTROLS DIVISION - Dwyer Instruments, Inc.
         Contents
1.   C     Input  PTC thermistor  10009   25  C     Outputs  One 16A SPST relay   250 VAC  resistive  One 8A  SPST relay   250 VAC resistive    Horsepower Rating  HP   1 3 HP    Power Requirements  12 VAC DC  24 VAC DC  115 VAC  230  VAC depending on model    Accuracy  1  of full scale    Display  3 digit and sign  red LED    Resolution  0 1     lt 100     1    100       Memory Backup  Nonvolatile memory    Ambient Operating Temperature  32 to 158  F  0 to 70  C    Storage Temperature   4 to 176  F   20 to 80  C    Dimensions  3 x 1 27 64 x 2 7 16 in    Front Panel Rating   P64    Weight  2 3 oz  65 g     Agency Approvals  CE  UR     Maintenance  cleaning and repair   After final installation of the unit  no routine maintenance is  required  Clean the surface of the display controller with a soft and  damp cloth  Never use abrasive detergents  petrol  alcohol or sol   vents  All repairs must be made by authorized personnel     LOVE CONTROLS DIVISION  DWYER INSTRUMENTS INC   P O  BOX 338   MICHIGAN CITY  INDIANA 46361  U S A     Phone  219 879 8000 www love controls com  Fax  219 872 9057 e mail love love controls com    page 2    List of parameters    Description Units Range  SP1 Set Point 1 Degrees r4 to r6  SP2 Set Point 2 Degrees r5 to r7  r0 Dependency SP1 SP2 Range ind dep  rl Differential for SP1 Degrees 0 1 to 20 0  r2 Differential for SP2 Degrees 0 1 to 20 0  r3 Band differential Degrees 0 1 to 20 0  r4 Lowest value for SP1 Degrees  99 9 to r6  r5 Lowest value for SP2 De
2.  L  V  LOYE           Bulletin E 90 TSS2    Series TSS2 Dual Stage Temperature Switch       Specifications   Installation and Operating Instructions    outi out2       The TSS2 is an electronic temperature controller designed for  ON OFF control or Neutral Area Control  They can be provided  with 1 or 2 probes  both PTC range  58 to 3022 F  according to  parameter P5 and it provides with two output relays plus an alarm  buzzer  The unit controls cooling  heating or both  since its relays  can be setup for direct or reverse operation  The user is able to  program 34 different parameters including set points  hysteresis   configuration of alarms and probe adjustment using the silicone  front keypad  The unit features error warning and password pro   tection     Each suffix can take the following values     MODEL CODE  TSS2    OUTPUTS T  2   2 OUTPUTS  DISPLAY COLOR  0 RED  SUPPLY VOLTAGE  1 115 VAC  2   230 VAC  3   12 VAC DC UNITS  4   23 VAC DC 0     F  1   C    NOTE  Unit must be mounted away from vibration  impacts  water  and corrosive gases        Cut hole in panel 71 x 29 mm  2 80 x 1 14 inches     e Apply silicone  or rubber gasket  around the perimeter of the hole  to prevent leakage    e Insert unit into hole of panel       Slide removable fitting clips onto unit from the back until secure  to panel    e Wiring diagram is displayed on the top of the unit    e Note  DO NOT INSTALL PROBE CABLE NEAR POWER  CABLES     SPECIFICATIONS   Probe Range   58 to 302  F  50 to 150
3.  if they have been    setup correctly     Press SET   DOWN to exit setup or wait for 1 minute     Description   SP1 Set Point 1   SP2 Set Point 2   r0 Dependency SP1   SP2   rl Differential for SP1   r2 Differential for SP2   r3 Band differential 1 0   r4 Lower value for SP1   r5 Lower value for SP2   r6 Higher value for SP1   r7 Higher value for SP2   r8 Regulation or operating mode  AO Alarm differential   A1 Maximum alarm probe 1   A2 Maximum alarm probe 2   A3 Minimum alarm probe 1   A4 Minimum alarm probe 2   A5 Alarm verification time   A6 Alarm probe 1 selection   A7 Alarm probe 2 selection   cO Minimum relay stop time   c1 Operation relay 1   c2 Operation relay 2   c3 Default operation relay 1   c4 Default operation relay 2   PO Temperature scale selection  P1 Calibration of probe 1   P2 Calibration of probe 2   P3 Decimal point   P4 Probe to be displayed   P5 Number of probes   HO Reprogramming   H1 Keyboard protection   H2 Operation LED OUT1   H3 Operation LED OUT2   H4 Address for serial communication  H5 Access code to parameters    Factory value  10 0   10 0   ind    yes  sdl    no  dir  dir    Operating modes Relay 2 with c2 inv   Mode ON OFF1  On1  with r0 ind  Temperature of probe 1  lt  SP1 SP2 r2    gt relay 2 ON    Relay 1 with cl dir  Temperature of probe 1  gt  SP1 SP2    gt relay 2 OFF  Temperature of probe 1  gt   SP1 r1    gt relay 1 ON  Temperature of probe 1  lt   SP1    gt relay 1 OFF    Figure 2       Mode ON OFF2  On2   Output 1 works as in indepe
4.  order of relay 2  Specifies the ON OFF point of  relay 2  Variable between r5 and r7   rO   Dependency between SP1 and SP2  Only for mode ONOFF1  ind   order for relay 2  SP2    dep   order for relay 2  SP1 SP2     r1   Differential or hysteresis for relay 1  Temperature differential between  ON OFF of relay 1 in ON OFF control   r2   Differential or hysteresis for relay 2  Temperature differential between  ON OFF of relay 2 in ON OFF control   r3   Band differential  Temperature differential between ON OFF of relays  1 and 2 in neutral area control  For relay 1 it is added to SP1 and for relay  2 it is subtracted from SP1   r4   Lowest value for SP 1   r5   Lowest value for SP2   r6   Highest value for SP1   r7   Highest value for SP2   r8   Regulation or operating mode  Selection of the operating mode   AO  Alarm differential  It is the temperature differential between the alarm  On and Off cycle   Al  Maximum alarm probel   A2   Maximum alarm probe2   Maximum alarm ON when probe 2 higher than SP2 A2  Maximum alarm OFF when probe 2 lower than SP2 A2 A0   A3   Minimum alarm probel   Minimum alarm ON when probe 1 lower than SP1 A3  Minimum alarm OFF when probe 1 higher than SP1 A3 A0   A4   Minimum alarm probe2   Minimum alarm ON when probe 2 lower than SP2 A4  Minimum alarm OFF when probe 2 higher than SP2 A4 A0     A5  Alarm verification time  Time from the alarm event until it trips   A6   Alarm probe 1 selection   AHL Maximum and minimum alarm probe 1 enabled   Ano No al
5. Keyboard protection   To change the sets  enter into parameter and exit again  The  protection setting is momentarily released  It switches on again  1 minute after the last time a key was pressed   Yes  Keyboard Protected   No Keyboard non protected   H2   Operation of LED OUTI1   dir  On when relay 1 is ON   inv  On when relay 1 is OFF   H3   Operation of LED OUT2   dir  On when relay 2 is ON   inv  On when relay 2 is OFF   H4   Serial communication address  Address for computer  connection   H5   Parameter entry code  Factory set as 0     Message display   Under normal operation  the temperature of the probe selected by  P4 will be displayed  the following messages may also appear   eErr Memory reading error    eErP Error of the probe not shown on the display    eAH1 Maximum temperature alarm  probe 1    eAL1 Minimum temperature alarm  probe 1    eAH2 Maximum temperature alarm  probe 2    eAL2 Minimum temperature alarm  probe 2      000 Open probe    e     Shorted probe    Pressing SET with UP it displays the probe not selected by P4   When the probe not selected by P4 is displayed  it alternates its  value with message Sd1 or Sd2 depending if it is probe 1 or probe 2   The display blinks when waiting for a value confirmation     LED indications   Outl  Indicates relay 1 On or Off as per parameter H2  If H2 dir   with relay 1 On  LED lit  if H2 inv  with relay 1 On  LED off  It blinks  when SP1 is displayed    Out2  Indicates relay 2 On or Off as per parameter H3  If H3 di
6. arms probe 1   AH Maximum alarm probe 1 enabled   AL Minimum alarm probe 1 enabled   A7   Alarm probe 2 selection   AHL Maximum and minimum alarm probe 2 enabled   Ano No alarms probe 2   AH Maximum alarm probe 2 enabled   AL Minimum alarm probe 2 enabled     lampe mum       EP14  gP AtA    c0   Minimum relay stop time  Minimum time from the disconnection  of a relay until it can be switched on again     c1   Operation relay 1  Selection between direct or reverse  operation for relay 1   c2   Operation relay 2  Selection between direct or reverse  operation for relay 2   c3   Default operation relay 1  In case of failure of probe 1   oPn  relay 1 will remain open   Clo  relay 1 will remain closed   c4   Default operation relay 2  In case of failure of probe 1  for all  modes excepting ON OFF2  or in case of failure of probe 2  for  mode ON OFF2    oPn  relay 2 will remain open   Clo  relay 2 will remain closed   PO   Temperature scale selection   P1   Calibration of probe 1  Offset degrees to be added to probe 1   P2   Calibration of probe 2  Offset degrees to be added to probe 2   P3   Decimal point  If the displayed value of the probes is desired  with decimals or not   P4   Probe to be displayed  Probe always on the display  The other  probe can be seen pressing the keys SET UP   Sd1  probe 1   sd2  probe 2   P5   Number of probes  If P5 1  there is not ON OFF2 mode  If  selected  it will operate as ONOFF1   HO   Reprogramming  Parameter to reprogram the thermostat   H1   
7. grees  99 9 to r7  r6 Highest value for SP1 Degrees r4 to 302  r7 Highest value for SP2 Degrees r5 to 302  r8 Regulation or operating mode Range Onl1 On2 nEU  A0 Alarm differential Degrees 0 1 to 20 0  Al Maximum alarm probe 1  1  Degrees 0 1 to 99 9  A2 Maximum alarm probe 2  2  Degrees 0 1 to 99 9  A3 Minimum alarm probe 1  1  Degrees 0 1 to 99 9  A4 Minimum alarm probe 2  2  Degrees 0 1 to 99 9  A5 Alarm verification time h m     0 0 to 18 0  A6 Alarm probe 1 selection Range AHL Ano AH AL  A7 Alarm probe 2 selection Range AHL Ano AH AL  c0 Minimum relay stop time Minutes 0 to 240  cl Operation relay 1 Range dir inv  c2 Operation relay 2 Range dir inv  c3 Default operation relay 1 Range Opn Clo  c4 Default operation relay 2 Range Opn Clo  PO Temperature scale selection Range 2C  2F  P1 Calibration of probe 1 Degrees  20 0 to 20 0  P2 Calibration of probe 2 Degrees  20 0 to 20 0  P3 Decimal point Range no yes  P4 Probe to be displayed Range sd1 sd2  P5 Number of probes Range 1 2  HO Reprogramming Range 0  H1 Keyboard protection Range no yes  H2 Operation LED OUT1 Range dir inv  H3 Operation LED OUT2 Range dir inv  H4 Address for serial communication Numeric 0 to 999  H5 Access code to parameters Numeric 0 to 999      Jh m are data in format XX Y where XX are hours and Y tens of minutes    1 referred to set 1    2 referred to set 2     Parameter descriptions  SP1   Operation order of relay 1  Specifies the ON OFF point of  relay 1  Variable between r4 and r6   SP2   Operation
8. ndent ON OFF control  Figure 1 and 2    but output 2 works as follows   Relay 2 with c2 dir   Relay 1 with cl inv  Temperature of probe 2  gt   SP2 r2    gt relay 2 ON  Temperature of probe 1  lt   SP 1 r1    gt relay 1 ON Temperature of probe 2  lt  SP2    gt relay 2 OFF  Temperature of probe 1  gt  SP1    gt relay 1 OFF    Figure 2       Relay 2 with c2 inv   Temperature of probe 2  lt  SP2 r2    gt relay 2 ON  Temperature of probe 2  gt  SP2    gt relay 2 OFF    Relay 2 with c2 dir   Temperature of probe 1  gt   SP2 r2    gt relay 2 ON  Temperature of probe 1  lt  SP2    gt relay 2 OFF       Neutral Area Mode  nEU    Relay 1   Temperature of probe 1  gt   SP1 r3    gt relay 2 ON  Temperature of probe 1  lt  SP1    gt relay 2 OFF       Relay 2 with c2 inv   Temperature of probe 1  lt  SP2 r2    gt relay 2 ON    Temperature of probe 1  gt  SP2    gt relay 2 OFF Relay 2  Temperature of probe 1  lt  SP1 r3    gt relay 2 ON    Temperature of probe 1  gt  SP1    gt relay 2 OFF       Mode ON OFF1  On1  with rO dep     Output 1 works as in independent ON OFF control  Figure 1 and 2   Operation in case of error    but output 2 works as follows  If probe 1 fails  the operation is through c3   See Parameter   Relay 2 with c2 dir  description     Temperature of probe 1  gt   SP1 SP2 r2    gt relay 2 ON If probe 2 fails  the operation is through c4   See Parameter   Temperature of probe 1  lt  SP1 SP2    gt relay 2 OFF description     In case of memory failure  both relays will remain 
9. open     Copyright 2008 Dwyer Instruments  Inc  Printed in U S A  6 08 FR  R7 443509 00 Rev  1   LOVE CONTROLS DIVISION Phone  219 879 8000 www love controls com  DWYER INSTRUMENTS INC  Fax  219 872 9057 e mail love love controls com    P O  BOX 338   MICHIGAN CITY  INDIANA 46361  U S A     
10. r   with relay 2 On  LED lit  if H3 inv  with relay 2 On  LED off  It blinks  when SP2 is displayed     Setting SP1 and SP2   e Press and release SET  The current value of order 1 is displayed   SP1 and led OUT1 blink    e Press UP or DOWN to increase or decrease the value    e Press SET to confirm the new value  The actual value of order 2 will  be displayed  SP2 and LED OUT2 blink    e Press UP or DOWN to increase or decrease the value    e Press SET to confirm the new value and exit     Parameter setup     Press SET for 8 seconds  Value 0 will blink    eWith UP and DOWN input the code  factory set as 0       Press SET to confirm the code  If correct  the label of the first  parameter will be displayed    eWith UP or DOWN go to the desired parameter in the parameter  list      Press SET to see the value    eWith UP or DOWN change the value to the new value as desired      Press SET to confirm and exit again to the parameter list   Also to  exit to the list without parameter modification     Press SET   DOWN to exit setup or wait for 1 minute     Resetting the keyboard code  You can setup to 0 the keyboard code switching the unit off and on  while pressing the SET key     Buzzer disconnection  Pressing SET with DOWN turns off the buzzer alarm  The message  of alarm continue appearing in the display     Reprogramming factory values  HO     eAccess to parameter HO as explained in parameter setup       Value 0 will be displayed     Press SET for 8 seconds  Pro will be displayed
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Manual Tom4 nou.pub    Halsey Taylor 8744083084 Use and Care Manual  TA Instruments Nano ITC protocol Ian Kleckner Foster Lab  DC MOTOR SPEED CONTROLLER  Oregon Scientific PE326PM User's Manual  Balance Balcar "U" BI-CABLE 10505 User's Manual  Instruzioni per l`uso  Mode d`emploi du formulaire de vote.  Final Documentation - University of Central Florida    Copyright © All rights reserved. 