Home
MANUALE OPERATIVO OPERATING MANUAL
Contents
1. HOUSING ur al SHIELD ww s GND LI LI DI I SIGNAL T U LP REVO TEMPERATURE INPUT Warning inputs 4 and 3 on request only The temperature inputs are fit for PT100 to 2 wires probes they must not be used for other applications Each input is calibrated on the 098 5 range the probe is excited to 5Vdc with 2 2mA the typical error with B Class probes is 1 5 the type and the length of the cables connection from the probe to the instrument could influence the reading With the 0009 password it enters in the temperature menu with the I4 Temp and I3 Temp parameters the original temperature could be modified while with the I4 Reset and Reset parameters the original temperature could be restored The temperature modification must be performed in the positive temperature field the 14 3 Temp parameters show the original temperature always the operator must modify this temperature with the desired temperature the effect of the modification has effect on the negative field also The original temperature modification doesn t modify the input calibration but it moves the calibration straight line on the X axle of the plain this characteristic corrects the errors inserted from the wiring Pag 44 4 anuale operativo Operating manual MO MP4 504 R9 TRASMETTITORI AMPLIFICATI a 2 o 3 fili AMPLIFIED
2. SCHERMO protetto con guaina SHIELD protected with jacket EXCITATION SIGNAL Schermo saldato al corpo del connettore Shield welded to the body of the connector Pag 43 MP4 M anuale operativo Operating manual MO MP4 504 R9 INGRESSO in TEMPERATURA Attenzione a richiesta solo sugli ingressi 4 e 3 Gli ingressi in temperatura sono idonei per sonde PT100 a 2 fili non devono essere usati per altre applicazioni Ogni ingresso calibrato tra 0 98 5 C la sonda eccitata a 5Vdc con 2 2 l errore tipico con sonde in Classe di 1 5 il tipo e la lunghezza dei cavi di collegamento tra la sonda e lo strumento pu influenzare la lettura Con la password 0009 si entra nel menu della temperatura con i parametri I4 Temp e I3 Temp si pu modificare la temperatura originale mentre con i parametri 14 Reset e Reset si pu ripristinare la temperatura originale La modifica della temperatura deve essere eseguita nel campo positivo i parametri 1413 Temp mostrano sempre la temperatura originale l operatore deve modificare questa temperatura con la temperatura desiderata l effetto della modifica ha effetto anche sul campo negativo La modifica della temperatura originale non modifica la calibrazione dell ingresso ma sposta la retta di calibrazione sull asse X del piano questa caratteristica corregge gli errori introdotti dal cablaggio
3. COMANDI DI LETTURA READING COMMANDS MESSAGGIO MESSAGE RISPOSTA ANSWER SET POINT 1 SET POINT 1 lt gt IISNNNNN lt cr gt SET POINT 2 SET POINT 2 211 lt gt IISNNNNN lt cr gt SET POINT SET POINT 3 lt gt IISNNNNN lt cr gt SET POINT 4 SET POINT 4 411 lt gt IISNNNNN lt cr gt SET POINT 5 SET POINT 5 P5II lt cr gt IISNNNNN lt cr gt SET POINT 6 SET POINT 6 P6II lt cr gt IISNNNNN cr 7 SET POINT 7 711 lt gt IISNNNNN lt cr gt SET POINT 8 SET POINT 8 P8II lt cr gt IISNNNNN lt cr gt SET POINT 9 SET POINT 9 P9II lt cr gt IISNNNNN lt cr gt SET POINT 10 SET POINT 10 POII lt cr gt IISNNNNN lt cr gt DELTA POINT 1 HYSTERESIS 1 01112 lt gt IINNNN lt cr gt DELTA POINT 2 HYSTERESIS 2 0211 lt gt IINNNN lt cr gt DELTA POINT 3 HYSTERESIS 3 0311 lt gt IINNNN lt cr gt DELTA POINT 4 HYSTERESIS 4 0411 lt gt IINNNN lt cr gt DELTA POINT 5 HYSTERESIS 5 D5II lt cr gt IINNNN lt cr gt DELTA POINT 6 HYSTERESIS 6 D6II lt cr gt IINNNN lt cr gt DELTA POINT 7 HYSTERESIS 7 D7II lt cr gt IINNNN lt cr gt DELTA POINT 8 HYSTERESIS 8 0811 lt gt IINNNN lt cr gt DELTA POINT 9 HYSTERESIS 9 D9II lt cr gt IINNNN lt cr gt DELTA POINT 10 HYSTERESIS 10 DOII lt cr gt IINNNN lt cr gt Pag 29 MP4 Manuale operativo Operating manual MO MP4 504 R9 VALORE TOTALE TOTAL VAL
4. POWER SUPPLY Per garantire le prescrizioni di sicurezza si deve installare un fusibile esterno sulle fasi N e L dell alimentazione di rete Fusibile esterni 2 x 50mA 250V Ritardati 123458789 1 ensure safety rules an external fuse for each net feeding phase N and L must be installed External Fuse 2 x 50mA 250V Delays Alimentazione di rete 115 230Vac Alimentazione 24Vdc 1 Terra PE 1 Terra PE 2 Fase N 2 0 Volt 3 Fase L 3 24Volt Power supply 115 230Vac Power supply 24Vdc 1 Earth PE 1 Earth 2 PhaseN 2 0 Volt 3 Phase L 3 24Volt Pag 42 MP4 Manuale operativo Operating manual MO MP4 504 R9 CELLE DI CARICO TRASDUTTORI 2 o 3 mV V 4 fili LOAD CELLS and TRANSDUCERS 2 or 3 mV V 4 wires 1 SEGNALE Bianco Colori riferiti al cavo standard AEP 1 SIGNAL White Colors are referred to AEP standard cable 2 SEGNALE Giallo 2 SIGNAL Yellow 3 ECCITAZIONE Rosso 3 EXCITATION Red 4 ECCITAZIONE Nero 4 EXCITATION Black Lo SCHERMO deve essere collegato al The SHIELD must be connected to the metal metallic DB9 male metallico metallizzato DB9 maschio della cella di carico o trasduttore connector of the load cell or transducer HOUSING EXCITATION SIGNAL STRAIN GAUGE FULL BRIDGE
5. CONTENITORE CASE TYPE SCATOLA CASE NORYL UL94 V O PANNELLI ANT POST FRONT BACK PANELS UL94 V 2 Pag 7 MP4 Manuale operativo Operating manual MO MP4 504 R9 Hardware Lo strumento gestito da un Microcontrollore che controlla tutte le periferiche esterne Le indicazioni sono mostrate su un LCD grafico la programmazione dei parametri si esegue dalla tastiera oppure via seriale a richiesta i dati sono memorizzati in modo permanente dinamometri sono alimentati a 5Vdc mentre i trasduttori a 15Vdc Convertitore Analogico Digitale 18 bits Componente intelligente in tecnologia sigma delta amplifica e campiona il segnale ad una frequenza di 72Hz Per le celle di carico il valore campionato in modo raziometrico mentre per i trasduttori il valore campionato in modo proporzionale al segnale di riferimento del convertitore Microcontrollore Unit ad 8 bit in tecnologia flash controlla tutto il sistema attraverso le sue periferiche interne Elabora il segnale campionato dal convertitore A D gestisce gli ingressi analogici il display la tastiera la comunicazione Seriale l uscita Analogica gli ingressi digitali ed le uscite a relay Software Il programma filtra i dati campionati calcola le misure calcola il valore dell uscita analogica e dei set point esegue misure di Picco la soppressione dello Zero e la somma delle misure degli ingressi La gestione del software Multitasking Hardware
6. R Load max 5000 Risoluzione 15 bit L uscita pu indicare valori superiori al F S fino a 24mA L uscita 4 20mA varia da 0 4mA per indicare valori negativi TENSION OUTPUT CHARACTERISTICS R Load min 10KQ Resolution 16 bit at 0 10V 15 bit at 10V CURRENT OUTPUT CHARACTERISTICS R Load max 5000 Resolution 15 bit Output can indicate higher values than F S up to 24mA 4 20mA output varies from 0 4mA to show negative values Pag 49 MP4 Manuale operativo Operating manual MO MP4 504 R9 USCITA SERIALE RS232C RS485 SERIAL OUTPUT RS232C or RS485 Lo strumento ha una sola porta seriale si pud collegare un PC PLC Instrument has a single serial port a PC PLC can be connected to alla RS232 oppure alla RS485 La connessione optoisolata non sono RS232 or to RS485 The connection is optoinsulated the hardware gestiti i segnali hardware di handshake handshake signals are not managed ON RS232 Enable ON RS485 Enable Attenzione Warning Il Deep switch all interno dello strumento The Deep switch is into the instrument 1234 Non usare la combinazione 1 2 3 4 ON 1234 Do not use the combination 1 2 3 4 ON RS485 gt Pag 50 MP4 Manuale operativo Operating manual MO MP4 504 R9 USCITA STAMPANTE PRINTER OUTPUT Stampante da pannello a 24 colonne formato della carta 56mm 24 columns built in printer 56mm paper size Modo di sta
7. SELEZIONE DELL INGRESSO ANALOGICO DEI CANALI SELECTION OF CHANNELS ANALOG INPUT In questa pagina si seleziona il tipo di ingresso analogico da associare al canale Valori selezionabili 2mV 3mV 0 10V 4 20mA 0 20mA DISABLE DISABLE canale disabilitato Note Quando si seleziona DISABLE il canale viene escluso dal sistema la velocita di conversione del sistema viene divisa sul numero di canali abilitati Il canale n 1 non pu essere disabilitato L ingresso 0 10V gestisce sia segnali 0 10V che segnali 10V Il valore selezionato deve corrispondere al segnale del trasduttore collegato all ingresso analogico lo strumento configura In this page operator select the type of analog input to be associated to channel Selectable values 2mV 3mV 0 10V 4 20 0 20mA DISABLE DISABLE channel disabled Notes When DISABLE is selected channel is excluded from the system system conversion speed is divided among the number of channels enabled Channel nr 1 cannot be disabled The 0 10V input manages both 0 10V and 10V input signal Selected value must correspond to the signal of the transducer connected to analog input instrument automatically set the analog automaticamente l ingresso analogico per gestire il segnale input to manage the selected signal selezionato INPUT C1 2 INPUT C2 0 10V Pagina di impostazione del tipo di Ingresso Analogico INPUT C3 4 20 Analog Input type setting
8. INDICATORE DIGITALE A 4 CANALI 4 CHANNELS DIGITAL INDICATOR MPA MANUALE OPERATIVO OPERATING MANUAL MO MP4 504 R9 ATEXO PINSYINEAP Dasa Rigis Production Quality o rtifi d 6 Cento SIT 98 TOV ATEX 553793 Q 41126 Cognento MODENA Italy Via Bottego 33 A Tel 39 059 346441 39 059 346437 email aep aep it Internet http www aep it MP4 Manuale operativo Operating manual MO MP4 504 R9 DICHIARAZIONE DI CONFORMITA CE Costruttore AEP transducers s r l Indirizzo Via Bottego 33 A 41126 Cognento MODENA Italia DICHIARA CHE IL SEGUENTE PRODOTTO Nome del prodotto MP4 Tipo Indicatore Digitale a 4 ingressi Anno di costruzione 2005 Opzioni questa dichiarazione copre tutte le opzioni specificate nel catalogo di vendita CONFORME ALLE SEGUENTI DIRETTIVE 2004 108 CE 2006 95 CE 2002 95 CE 2002 96 CE E CONFORME ALLE SEGUENTI NORME EN 61010 1 2001 EN 61326 1 2007 E CONFORME AL REGOLAMENTO n 1907 2006 REACH Il prodotto e stato provato nella configurazione tipica di installazione descritta nel manuale di istruzioni Il prodotto soddisfa i requisiti delle Norme citate sulla base dei risultati delle prove e delle valutazioni descritte nel Fascicolo Tecnico lo sottoscritto dichiaro che il prodotto sopra descritto soddisfa i requisiti delle Direttive delle Norme e dei Regolamenti sopra citati 41126 Cognento MODENA Lioi Giova
9. The instrument is managed by a microcontroller which controls all the external peripherals The indications are showed on a graphic LCD the parameters programmation is performed through the keyboard or through serial output on request data are stored in a permanent way The dynamometers are fed at 5Vdc while the transducers at 15Vdc Analog Digital Converter 18 bits A intelligent components sigma delta technology amplifies and samples the signal at a frequency of 72Hz For the load cells the value is sampled in a ratiometric way while for pressure transducers the value is sampled in a way proportional to the converter reference signal Microcontroller 8 bit unit in flash tecnology which controls the whole system through its internal peripherals It processes the signal sampled by the A D converter manage the analog inputs the display the keyboard the serial communication the analog output the digital inmputs and the relay outputs Software The program filters the sampled data calculates the measurements the analog output and set points value performs Peak measurements the Zero suppression and the sums of the inputs measurements Software management is Multitasking Pag 8 MP4 Manuale operativo Operating manual MO MP4 504 R9 DATI TECNICI TECHNICAL DATA CAMPO DI MISURA STANDARD STANDARD MEASUREMENT RANGE t2mV V x3mV V RISOLUZIONE INGRESSO 2mV V 2mV V INPUT RESOLUTION 50 000 div DIVISIO
10. USCITE A RELAY OPZIONALI Le uscite a relay opzionali sono 8 SP3 5 4 SP5 SP6 SP7 SP8 SP9 e 5 10 RELAY OUTPUTS ON REQUEST Relay outputs on request are 8 SP3 SP4 SP5 SP6 SP7 SP8 SP9 SP10 HHHH 7 8 9 101112131415 161718 ino ino A XL clap wep sap ll 115Vac 0 5A oppure 48Vdc 0 5A Portata massima dei contatti con carico resistivo Max contacts rate with resistive load 115Vac 0 5A or 48Vdc 0 5A A Pag 47 MP4 Manuale operativo Operating manual MO MP4 504 R 9 INGRESSI DIGITALI Gli ingressi digitali opto isolati eseguono le funzioni sottoelencate DIGITAL INPUTS Optoinsulated digital inputs perform the functions listed below INP 1 Ingresso digitale ZERO morsetto 6 INP 1 ZERO digital Input terminal 6 INP 2 Ingresso digitale PRINT morsetto 7 INP 2 PRINT digital input terminal 7 INP 3 Ingresso digitale HOLD morsetto 8 INP 3 HOLD digital Input terminal 8 SP1 SP2 Pag 48 MP4 Manuale operativo Operating manual MO MP4 504 R 9 USCITA ANALOGICA ANALOG OUTPUT 12 3 1 if il E dE dE IL ox Uscita Correntes ezza Current Outpu R Load CARATTERISTICHE USCITA in TENSIONE min 10KQ Risoluzione 16 bit a 0 10V 15 bit a 10V CARATTERISTICHE USCITA in CORRENTE
11. Intervallo di tempo tra le archiviazioni Valori selezionabili 0001 99999 secondi 0000 Disabilitato START DL Inizia l archiviazione dei dati Valori selezionabili Y N Y Start modifica lo stato della funzione STOP DL Arresta l archiviazione dei dati Valori selezionabili Y N Y Stop N non modifica lo stato della funzione TX DATA Attiva la trasmissione dei dati archiviati via seriale Attenzione Prima di attivare la funzione si deve impostare il tempo di archiviazione TIME gt 0 Prima di attivare la trasmissione dei dati archiviati si deve fermare la funzione STOP DL La trasmissione dei dati archiviati avviene in modo continuo dal 1 fino al 90 dato l intervallo di trasmissione tra i dati circa 0 25 secondi DATA LOGGER This function allows to store in the permanent memory 90 values for each input with the programmable storing time when the 90 value is stored the function automatically stops The function records the instrument switches off and automatically starts again at the switch on with a new interval time Stored data are set to zero only at function beginning TIME MEM waiting time between a storage and the other Selectable values 0001 9999 seconds 0000 Disabled START DL To start the storage of sampled data Selectable values Y N Y start N it does not change the function status STOP DL To stop the storage of sampled data Selectable values Y N Y stop N it does not change the funct
12. the filter is common for all inputs La frequenza di misuara di ogni ingresso data dalla Frequenza di The measurement frequency of each inputs is given from Measurement Misura indicata in tabella e dal numero di ingressi abilitati Frequency displayed in the table and from enabled inputs number Esempio Example Filtro 1 Ingressi abilitati 4 frequenza di misura per ingresso Filter 1 enabled Inputs 4 measurement frequency per input 36 4 9Hz 36 4 9Hz FILTER 4 ZOOM CH DISAB Pagina di impostazione del Filtro Digitale PEAK CH1 DISAB Digital Filter setting page PASSWORD 0000 TABELLA FILTRI FILTERS TABLE Filtro Digitale Digital Filter 1 2 3 4 5 Base Tempi Time Table 28ms 56ms 220ms 440 5 880 5 Frequenza di Misura Measurement Frequency 36Hz 18Hz 4 5Hz 2 25Hz 1 125Hz Funzione ZOOM F1 ZOOM F1 function Funzione ZOOM MAN ZOOM MAN function Funzione TOTAL TOTAL function Pag 20 MP4 Manuale operativo Operating manual MO MP4 504 R9 ZOOM TOTAL tasto F1 ZOOM TOTAL F1 key Valori selezionabili 124 DISAB disabilitato TOTAL somma valori Selectable values 1 4 DISABzdisabled TOTAL values sum Descrizione Lo ZOOM si abilita impostando il numero di ingresso Description Operator can enable the Zoom by setting the input number desiderato accertarsi che l ingresso scelto sia un ingresso abilitato per wanted be sure that wanted input is a input enabled to disable the disabili
13. D7IINNNN lt cr gt lt gt 0000 9999 ISTERESI 8 HYSTERESIS 8 D8IINNNN lt cr gt lt gt 0000 9999 ISTERESI 9 HYSTERESIS 9 D9IINNNN cr lt gt 0000 9999 ISTERESI 10 HYSTERESIS 10 DOIINNNN cr lt gt 0000 9999 ZERO ABILITATO ZERO ENABLED ZEll lt cr gt lt gt ZERO DISABILITATO ZERO DISABLED ZDll lt cr gt lt gt ARRESTO SUL CANALE STOP ON THE CHANNEL SCIIC lt cr gt lt gt C channel 1 4 MANUALE AUTOMATICO MANUAL AUTOMATIC MAIIN lt cr gt IIACK lt cr gt N 1 0 Auto RISOLUZIONE di MISURA RDIICNNN lt cr gt lt gt C channel 1 4 MEASUREMENT RESOLUTION NNN 1 2 5 10 20 50 100 FILTRO DIGITALE DIGITAL FILTER FDIIN lt cr gt lt gt N 1 5 FONDO SCALA CANALI FSIICNNNNN lt cr gt IIACK lt cr gt C channel 1 4 CHANNELS FULL SCALE NNNNN 00000 50000 PUNTO DECIMALE DECIMAL POINT DPIICN lt cr gt lt gt C channel 1 4 0 4 RIPRISTINO CALIBRAZIONE di FABBRICA CRIIC lt cr gt lt gt C channel 1 4 COMPANY CALIBRATION RESTORATION DATA LOGGER STATUS DLIIN lt cr gt IIACK lt cr gt N 1 Start N 0 Stop DATA LOGGER STORAGE TIME TLIINNNNN lt cr gt lt gt 1 99999 sec Pag 28 MP4 Manuale operativo Operating manual MO MP4 504 R9
14. FILTER ZOOM CH PEAK PASSWORD 4 DISAB Pagina di impostazione del Picco POS Peak setting page 0000 C1 1000 0 kg C2 100 00 kg C3 10 000 kg C4 1 5000 kg Indicazione con la funzione di Picco attiva Indication with the Peak function active 99 Pag 23 MP4 Manuale operativo Operating manual MO MP4 504 R9 PASSWORD PASSWORD Password 0005 si accede al Menu dell uscita Analogica dell uscita Seriale del Data Logger Password 0007 si accede al Ment di personalizzazione e calibrazione dei singoli canali con la Tara il Fondo Scala il Punto decimale l Unit di misura il Ripristino della calibrazione di fabbrica Password 0009 si accede al Menu della Temperatura questo Menu accessibile solo con l ingresso n 4 configurato con l unit di misura C In questo Menu ci sono quattro parametri due per l ingresso n 4 e due per l ingresso n 3 ogni ingresso ha un parametro per modificare la temperatura indicata ed uno parametro per ripristinare la temperatura originale pag 37 Password 3464 si accede al Men che seleziona il tipo di ingresso analogico da associare ad ogni singolo canale gli ingressi selezionabili sono 2mV 3mV 0 10 4 20 Disable Password 0005 to enter into Analog output Serial output and Data Logger Menu Password 0007 to enter into the personalization and calibration Men of the single channels with Full Scale Decimal Point measurement Unit company F
15. by the printer to program its internal Clock Calendar by pressing Enter key the instrument sends to the printer the data set DATE HOUR 01 01 01 00 00 Pagina impostazione Data Ora Clock Calendar setting page INTESTAZIONE DEL REPORT DI STAMPA PRINT REPORT HEADING In questa pagina si impostano i 3 campi di 16 caratteri per l intestazione del report di stampa si possono impostare lettere e numeri oppure spazi L intestazione stampata in formato grande In this page the operator set the 3 fields of 16 characters each for the print report heading letters and numbers or spaces can be set The heading is printed in a large format HEADING AEP TRANSDUCERS VIA BOTTEGO 33 COGNENTO MODENA Pagina impostazione Intestazione report di stampa Print report heading setting page Pag 32 MP4 Manuale operativo Operating manual MO MP4 504 R9 IMPOSTAZIONE CON PASSWORD 0007 SETTINGS THROUGH 0007 PASSWORD SOPPRESSIONE DELLA TARA TARE SUPPRESSION Questa funzione permette la soppressione della Tara del sistema generalmente intesa come la struttura pesatrice La forza generata dalla struttura pesatrice considerata dallo strumento come lo Zero del sistema Attenzione E consigliabile che la forza generata dalla struttura pesatrice sia inferiore al 5096 della portata delle celle di carico tuttavia possibile sopprimere fino al 8096 della portata delle celle questa possibili
16. maintenance in case of faulty functioning please contact the supplier Clean occasionally instrument front panel with a non abrasive cloth soaked with non corrosive substancies Maintenance shall be done by authorized personnel only Pag 13 MP4 Manuale operativo Operating manual MO MP4 504 R9 INDICAZIONI esempi DISPLAYS examples All accensione lo strumento mostra il modello e la versione software fig 1 l indicazione dura circa 3 secondi quindi lo strumento si posiziona sulla pagina principale ed pronto a rispondere ai comandi dell operatore fig 2 Nel caso si verifichi un funzionamento diverso da quello sopra descritto consultare a pag 53 54 Messaggi Errore Ricerca Guasti Indicazione dei Dati Le indicazioni vengono mostrate su un LCD grafico retro illuminato di risoluzione 128x32 dots posto sul pannello anteriore dello strumento Dati e messaggi sono visualizzati in modo grafico MP4 fig 1 accensione Rel 2 20 pict 1 starting SETP 1 C1 05000 SETP 2 C2 1000 0 fig 3 esempio prima pagina Men SETP 3 150 00 pict 3 example of first page Men SETP 4 C4 20 000 At its starting instrument displays both model and software version pict 1 Such display takes approx 3 seconds then instrument goes to the main page and it is ready to perform operator instructions commands pict 2 If something different from above described procedures happens please go to pages 53 54
17. ritornare alla pagina principale pag 14 Come Impostare i Parametri 1 SET mostra la pagina successiva 2 posiziona il cursore lampeggiante sul campo da modificare 3 incrementa la cifra selezionata dal cursore lampeggiante se tenuto premuto dopo 2 secondi incrementa rapidamente il valore se il cursore sul segno lo modifica 4 decrementa la cifra selezionata dal cursore lampeggiante se tenuto premuto dopo 2 secondi decrementa rapidamente il valore se il cursore sul segno lo modifica ENTER memorizza il dato passa al parametro successivo SETTING MENU Instrument if anything different is specified by the customer is supplied with default configuration page 11 in order to costomize the instrument it is necessary to set below listed parameters How to set the instrument 1 In the main page press set key on the display the first Menu page appears pag 15 2 Press ENTER key to access the parameters inside the page 3 Press SET key to move forward of a page to exit from the Menu press repeatedly the SET key until the main page appears again page 14 How to set parameters 1 SET show the next page 2 set flashing cursor on the field to be modified 3 to increase the digit selected by the flashing cursor if keapt press after 2 seconds it rapidly increases the value if the cursor is on the sign it changes it 4 to decrease the digit selected by flas
18. singolarmente programmabili ogni ingresso idoneo ricevere segnali provenienti da Strain Gauge a ponte intero oppure da trasduttori con uscita amplificata in tensione o corrente indicato per la misura di forze peso e pressione Il controllo della misura sui 4 ingressi avviene per commutazione la frequenza di campionamento proporzionale al filtro selezionato Realizzato per essere impiegato in sistemi di misura statica e dinamica in ambiente industriale dove necessario acquisire pi trasduttori indipendenti simultaneamente Strumento di accuratezza 0 01096 ha una risoluzione standard di 50 000 divisioni ed una risoluzione interna di 100 000 divisioni Idoneo ad utilizzare celle di carico dinamometri da 350 7000 con collegamento a 4 fili trasduttori con uscita 0 10V 10V 0 20mA o 4 20mA potenziometri L indicatore pu funzionare in modo Manuale con tutta la velocit di conversione indirizzata su un singolo ingresso oppure in Automatico con il controllo dei 4 ingressi ad una velocita di conversione di 1 4 per ogni ingresso In Manuale possibile azzerare singolarmente gli ingressi analogici con il tasto di Zero mentre in Automatico possibile azzerare tutti gli ingressi analogici con l ingresso remoto di Zero L indicatore dispone della funzione di Data Logger che permette la memorizzazione in memoria Eeprom di 90 valori per ogni ingresso MP4 digital indicator is a instrument with 4 singularly programmable analog
19. ET POINT 1 P1IICSN SET POINT 2 SET POINT 2 P2IICSN SET POINT 3 SET POINT 3 P3IICSN SET POINT 4 SET POINT 4 P4IICSN SET POINT 5 SET POINT 5 P5IICSN SET POINT 6 SET POINT 6 P6IICSN SET POINT 7 SET POINT 7 P7IICSN SET POINT 8 SET POINT 8 P8IICSN SET POINT 9 SET POINT 9 P9IICSN SET POINT 10 SET POINT 10 POIICSN NNNN lt cr gt lt gt C channel 0 4 NNNN lt cr gt lt gt 0 Setpoint Disabled NNNN lt cr gt lt gt 1 4 Setpoint Enabled NNNN lt cr gt IIACK lt cr gt S sign or NNNN lt cr gt IIACK lt cr gt NNNNN 00000 50000 NNNN lt cr gt lt gt NNNN lt cr gt lt gt NNNN lt cr gt lt gt NNNN lt cr gt lt gt NNNN lt cr gt lt gt ISTERESI 1 HYSTERESIS 1 D1IINNNN lt cr gt lt gt 0000 9999 ISTERESI 2 HYSTERESIS 2 D2IINNNN lt cr gt lt gt 0000 9999 Pag 27 MP4 Manuale operativo Operating manual MO MP4 504 R9 ISTERESI 3 HYSTERESIS 3 D3IINNNN lt cr gt lt gt 0000 9999 ISTERESI 4 HYSTERESIS 4 D4IINNNN lt cr gt lt gt 0000 9999 ISTERESI 5 HYSTERESIS 5 D5IINNNN cr lt gt 0000 9999 ISTERESI 6 HYSTERESIS 6 D61INNNN lt cr gt lt gt 0000 9999 ISTERESI 7 HYSTERESIS 7
20. ISABLE Seriale Disabilitata PRINTER Stampante Abilitata Protocollo 9600 N 8 1 TRANSM Trasmissione continua dei dati Protocollo 9600 N 8 1 IDENTITY Numero di identificazione dello strumento Valori selezionabili 00 31 TIME TX Tempo di pausa tra trasmissioni continue Valori selezionabili 0000 9999 secondi Note PRINTER abilita la gestione della stampante se il parametro TIME TX 0 la stampa avviene chiudendo l ingresso INP 2 se il parametro TIME gt 0 la stampa avviene in automatico ogni NNNN secondi Quando si seleziona la funzione TRANSM si deve impostare anche il tempo di pausa TIME TX tra una trasmissione e l altra All accensione la comunicazione seriale viene attivata in ritardo per SERIAL OUTPUT At instrument power on Serial Interface is activated later in order to enable digital indicator to stabilize itself during the pause instrument response is the string IINAK lt cr gt SERIAL Baud rate and selectable outputs Protocol Baud N 8 1 Selectable values DISABLE 4800 9600 19200 PRINTER TRANSM DISAB Printer Disabled PRINTER Printer Enabled Protocol 9600 N 8 1 TRANSM Continuos transmission Protocol 9600 8 1 IDENTITY Instrument identification number Selectable values 00 31 TIME TX Transmissions continuons pause time Selectable values 0000 9999 seconds Notes PRINTER enables the printer management if the parameter TIME TX 0 printing occurs by closing the INP 2 input if the
21. NI INTERNE INTERNAL DIVISIONS 100 000 div DINAMOMETRI COLLEGABILI CONNECTABLE DYNAMOMETERS 6 12 by 350 7002 TRASDUTTORI COLLEGABILI CONNECTABLE TANSDUCERS 4 by 30mA ECCITAZIONE DINAMOMETRI DYNAMOMETERS EXCITATION 5Vdc 3 ALIMENTAZIONE TRASDUTTORI TRANSDUCERS EXCITATION 15Vdc VELOCITA DI CONVERSIONE CONVERSION SPEED 18Hz x 4ch MAX VELOCITA di CONVERSIONE solo ingresso1 MAX CONVERSION SPEED input 1 only 72Hz small size display RESISTENZA Ingresso Analogico da Strain Gauge Strain Gauge Analog Input RESISTANCE gt 100MQ RESISTENZA Ingresso Analogico amplificato Amplified Analog Input RESISTANCE gt 100KQ CLASSE DI PRECISIONE ACCURACY CLASS lt 0 01 ERRORE DI LINEARITA LINEARITY ERROR lt 0 01 TEMPERATURA LAVORO NOMINALE NOMINAL TEMPERATURE RANGE 0 50 C TEMPERATURA LAVORO MASSIMA MAX TEMPERATURE RANGE 0 50 C TEMPERATURA DI STOCCAGGIO STORAGE TEMPERATURE RANGE 20 60 C EFFETTI VARIAZIONI DI TEMP 10 C EFFECTS A TEMP VARIATION 10 C a sullo zero a on zero lt 0 005 b sul fondo scala b on full scale lt 0 005 CAMPO DI INDICAZIONE INDICATION RANGE max 50000 div FUNZIONE DI ZERO ZERO FUNCTION 100 Pag 9 MP4 Manuale operativo Operating manual MO MP4 504 R9 RISOLUZIONE PROGRAMMABILE PROGRAMMABLE RESOLUTION 125102050100 DECIMALI PROGRAMMABILI PROGRAMMABLE DECIMAL POINTS 4 FILTRI DIGITALI PROGRAMMABILI PROGRAMMABLE DIGITAL FILTERS 5 INGRESSI REMOTI OPTOISOLATI OPTOINSULATED REMOTE INPUTS Zer
22. TRANSMITTERS at 2 or 3 wires HOUSING SHIELD A U 2 wires Transmitter 4 20 Pin 7 Pin 9 SIGNAL Out HOUSING HOUSING 71 SHIELD SHIELD E I _ E ISIGNAL4 1 ISIGNAL _ U U ee all p el 3 wires Transmitter 3 wires Transmitter 4 20 5Volt 10Volt Pin 5 EXC 0 Volt Pin 5 EXC 0 Volt Pin 7 EXC Pin 7 Pin 9 SIGNAL Out Pin 6 SIGNAL Out Lo SCHERMO deve metallico metallizzato DB9 maschio del trasmettitore al connettore The SHIELD must be connected to the metal metallic DB9 male connector of the transmitter Pag 45 MP4 Manuale operativo Operating manual MO MP4 504 R9 USCITE A RELAY STANDARD RELAY OUTPUTS STANDARD Le uscite a relay standard sono SP1 SP2 The standard relay outputs are SP1 and SP2 Portata massima dei contatti con carico resistivo Max contacts rate with resistive load 115Vac 0 2A oppure 48Vdc 0 2A 115Vac 0 2A or 48Vdc 0 2A Pag 46 MP4 Manuale operativo Operating manual MO MP4 504 R9
23. Temperatura opzionale password 0009 Temperature modify on request password 0009 36 Selezione ingresso analogico dei canali password 3464 Selection of channels analog inputs password 3464 37 Funzioni Descrizione Functions Descriptions Zero Zero 38 Hold e Stampa Hold and Print 39 Istruzioni per il montaggio Mounting instructions 41 Collegamenti Connections Alimentazione Power supply 42 Celle di carico e trasduttori a 4 fili Load cells and transducers with 4 wires 43 Ingresso in Temperatura opzionale Temperature input on request 44 Trasduttori con uscita amplificata a 2 o 3 fili Transducers with amplified output and with 2 or 3 wires 45 Uscite a relay standard Relay output standard 46 Uscite a relay opzionali Relay output on request 47 Ingressi Digitali Digital Input 48 Uscita Analogica Analog Output 49 Uscita Seriale Serial Output 50 Uscita Stampante Printer Output 51 Messaggi errore Ricerca guasti Error Messages Troubleshooting 52 Pag 3 4 Manuale Operating manual MO MP4 504 R9 TARGA DI IDENTIFICAZIONE informazioni per l identificazione i principali dati di configurazione i simboli di conformit e smaltimento la data di produzione IDENTIFICATION PLATE Sul contenitore dello strumento sono marcate in modo indelebile tutte le On the instrument enclosure are marked in indelible mode all the information for
24. Total 1111 5 kg If Input1 value 550 0 kg and Input2 value 561 5 kg gt Total 11 5 kg C1 550 0 kg C2 561 5 kg C3 10 00 bar C4 150 0 bar 1 Pagina indicazione standard dei valori Standard values indication page 1111 5 ic TOTAL Indicazione del Totale degli ingressi C1 C2 C1 C2 inputs Total indication Pag 22 MP4 Manuale operativo Operating manual MO MP4 504 R9 PICCO tasto F1 Funzionamenti selezionabili DISAB POS NEG DISAB Picco disabilitato POS Picco Positivo NEG Picco Negativo Descrizione Il Picco si abilita impostando il funzionamento desiderato e disabilitando la funzione ZOOM per disabilitare il Picco selezionare DISAB Il tasto F1 attiva disattiva la funzione se questa stata abilitata nel Menu Attenzione Le funzioni ZOOM TOTAL e PICCO sono alternative tra loro perch entrambe gestite dal tasto F1 se entrambe sono abilitate la sola funzione gestita lo ZOOM TOTAL Selectable functioning DISAB POS NEG DISAB Disabled Peak POS Positive Peak NEG Negative Peak Description The Peak enables by setting the wanted functioning and by disabling the ZOOM function select DISAB to disable the Peak F1 key enables disables the function if this has been activated in the Menu Warning ZOOM TOTAL and PEAK functions are alternative between them because they are both managed by F1 key if both are anabled the only function managed is the ZOOM TOTAL
25. UE TOII cr PUNTO DECIMALE DECIMAL POINT DPIIC lt cr gt FONDO SCALA INGRESSI INPUTS FULL SCALE FSIIC lt cr gt IICNNNNN lt cr gt FILTRO DIGITALE DIGITAL FILTER FDII lt cr gt IIN lt cr gt RISOLUZIONE RESOLUTION RDIIC lt cr gt IICNNN lt cr gt DATA LOGGER STATUS DLII lt cr gt IIN lt cr gt N 1 Start N 0 Stop DATA LOGGER STORAGE TIME TLII lt cr gt IINNNNN lt cr gt IINNN lt cr gt VALORE della MISURA DAII lt cr gt Total 59 chars MEASUREMENT VALUE IISNNNNNNUUUSNNNNNNUUUSNNNNNNUUUSNNNNNNUUUTTTTTTT UUUPPPP cr where S sign NNNNNN value UUU unit TTTTTTT arithmatic sum PPPP continuons Tx counter DATA LOGGER STORAGE RLII lt cr gt Total 59 chars DATA READ 90 data IISNNNNNNUUUSNNNNNNUUUSNNNNNNUUUSNNNNNNUUUTTTTTTT UUURRRR lt cr gt where S sign NNNNNN value UUU unit TTTTTTT arithmatic sum all null RRRR record number IISNNNNNN UUU lt cr gt IICN lt cr gt NNN 000 100 Pag 30 MP4 Manuale operativo Operating manual MO MP4 504 R9 DATA LOGGER Questa funzione permette di archiviare in memoria permanente 90 valori per ogni ingresso con il tempo di archiviazione programmabile alla archiviazione del 90 valore la funzione si arresta automaticamente La funzione registra gli spegnimenti dello strumento riparte automaticamente alla riaccensione con un nuovo intervallo di tempo L azzeramento dei dati archiviati avviene solo all inizio della funzione TIME MEM
26. Z characters is off pict B In Manual mode to enable the function press ZERO key to disable it keep ZERO key pressed for about 5 seconds In Automatic mode to enable the function close ZERO remote input INP 1 to disable it keep ZERO input closed for about 5 seconds 1 C2 0000 0 kg C3 000 00 kg C4 00 000 kg 0000 kg 2 Z fig A funzione di Zero abilitata su tutti i canali 2 pict A Zero function enabled on all channels 2 C1 C2 1000 0 kg C3 150 00 kg C4 20 000 kg 5000 kg 11 fig B funzione di Zero disabilitata su tutti i pict B Zero function disabled on all channels Pag 38 MP4 Manuale operativo Operating manual MO MP4 504 R9 FUNZIONE DI HOLD La funzione di HOLD disponibile come ingresso digitale remoto INP 3 L attivazione disattivazione della funzione si ottiene chiudendo aprendo l ingresso associato L attivazione della funzione blocca l indicazione dello strumento anche se la misura varia la disattivazione sblocca l indicazione dello strumento L attivazione della funzione viene indicata sul display con il carattere H HOLD FUNCTION HOLD function is available as remote digital input INP 3 Function activation deactivation is obtained by closing opening the input associated Function activation locks instrument indication even if the measurement changes function deactivation unlocks instrument indications Function activation is showed on the display through the H char
27. a rete elettrica la protezione dalle sovracorrenti deve essere eseguita con fusibili esterni pag 43 Fissare con le viti i connettori dei trasduttori DB9 allo strumento pag 44 45 46 Collegare i segnali di I O alle apposite morsettiere pag 47 48 49 50 Alimentare la rete elettrica L accensione deve essere fatta da personale istruito Per una migliore accuratezza della misura consigliabile che lo strumento raggiunga la sua stabilit termica 15 minuti POWER ON Instrument does not have any switch Connect the instrument to the electric net protection against overcurrent shall be performed through external fuses page 43 Fix through the screws the transducers connectors DB9 to the instrument pages 44 45 46 Connect I O signals to the apposite therminal boards pages 47 48 49 50 Feed the electric net Power must be done by authorized personnel only For a better reading accuracy it is advisable that the instrument reach his thermal stability about 15 minutes SPEGNIMENTO POWER OFF Togliere alimentazione alla rete elettrica Disconnect the electric net MANUTENZIONE MAINTENANCE Lo strumento non richiede manutenzione periodica in caso di mal funzionamento contattare il fornitore Occasionalmente pulire il pannello anteriore con panno non abrasivo imbevuto di sostanze non corrosive La manutenzione deve essere fatta da personale informato Instrument does not require periodic
28. a setting page 18 AUTO Instrument takes back the automatic control of enabled inputs the values are in a small graphic format move the cursor from left to right only for enabled settings afters last digit it moves back to the beginning lighted on the Questo tasto esegue due funzioni 1 In pagina principale F1 attiva o disattiva la funzione abilitata nel Men Zoom o Picco 2 All interno del Menu esegue la funzione di Enter ENTER conferma dato memorizza il dato impostato ed accede al parametro successivo del Men Pag 16 This key has two functions 1 In main page F1 activates or deactivates the function enabled in the Men Zoom or Peak 2 Inside the Menu it performs Enter function ENTER data confirmation it stores the data set and moves to the next parameter of the Menu MP4 Manuale operativo Operating manual MO MP4 504 R9 MENU IMPOSTAZIONI Lo strumento se non diversamente specificato dal cliente viene fornito con la configurazione di default pag 11 per personalizzare lo strumento necessario configurare i parametri di seguito elencati Come configurare lo strumento 1 Nella pagina principale premere il tasto SET sul display compare la prima pagina del Men pag 15 Premere il tasto ENTER per accedere ai parametri all interno della pagina Premere il tasto SET per avanzare di una pagina per uscire dal Men premere ripetutamente il tasto SET fino a
29. acter C1 5000 kg C2 1000 0 kg C3 150 00 kg C4 20 000 kg Esempio funzione di Hold attiva Active Hold function example FUNZIONE DI STAMPA Lo strumento stampa un report di misure composto da intestazione data numero progressivo misura rilevata dagli ingressi attivi unita di misura ed orario Il massimo numero di misure per ogni report 255 dopodich lo strumento chiude il report la stampa successiva inizia con l intestazione e la numerazione riprende da 001 Impostando TIME 0000 la stampa avviene chiudendo per 100mS l ingresso digitale INP 2 chiudendo INP 2 per 5sec viene stampata la misura e chiuso il report Impostando TIME gt 0000 la stampa avviene in automatico ogni NNNN sec dopo la 255 misura lo strumento chiude il report La stampa successiva l inizio di un nuovo report Stampante 190 53 0001 Pag PRINT FUNCTION Instrument prints a measurement report consisting of heading date time progressive number measurement of active channels The max measurement number for each report is 255 after this instrument automatically closes the report and starts with the letter head and the numeration resumes from 001 By setting TIME 0000 printing occurs by closing for 100mS the INP2 digital input by closing INP2 for 5sec it is printed the measurement and then closed the report By setting TIME gt 0000 printing automatically occurs every NNNN sec after the 255 measurement the in
30. are il cursore lampeggiante sul canale desiderato 1 Move the flashing cursor to the wanted channel 2 Con i tasti di incremento decremento impostare il valore 2 Through the increase decrease keys set the wanted value desiderato 3 Repeat step 1 2 for all channels which have to be changed 3 Ripetere i punti 1 e 2 per tutti i canali desiderati C1 1 D P C2 2 Esempi di impostazione del Punto Decimale D P C3 3 Decimal Point setting examples D P C4 4 UNITA DI MISURA MEASUREMENT UNITS In questa pagina si imposta l Unit di Misura di ogni singolo canale In this page operator select the Measurement Unit of each cannel Unit di Misura selezionabili Selectable Measurement Units 9 kg t N daN kN kgf tf bar psi div mV V mA mm m 9 t daN KN kgf tf bar psi div mV V mA mm m UNIT C1 kg UNIT C2 kg Esempi di impostazione dell Unit di Misura UNIT C3 kg Measurement Unit setting examples UNIT C4 kg Pag 35 MP4 Manuale operativo Operating manual MO MP4 504 R9 RIPRISTINO DELLA CALIBRAZIONE DI FABBRICA Questa funzione permette di ripristinare la calibrazione originale di fabbrica di ogni singolo canale nel caso che le modifiche apportate al canale non corrispondano pi alle esigenze di uso Come ripristinare la calibrazione di fabbrica COMPANY CALIBRATION RESTORE This function allows to restore the original company calibration on each single channel in those cases when chan
31. e the bar associated to the SetPoint is activated pict B SetPoint indication In the main page on the display right side pict B it is indicated the SetPoint status The bar position on the line indicates to which channel the SetPoint is associated a 3 pixel bar indicates that SetPoint in enabled but not active a 5 pixel bar indicates that SetPoint is abled and active a 1 pixel bar indicates that SetPoint is disabled Note At instrument starting SetPoints are activated later in order to enable the digital indicator to stabilize itself SETP 1 C1 05000 SETP 2 C2 1000 0 SETP 3 C3 150 00 SETP 4 C4 20 000 fig A esempio prima pagina men SetPoint pict A first page SetPoint menu example C1 5000kg C21000 0kg fig B SP1 SP2 SP3 SP4 sono attivi C3150 00kg pict B SP1 SP2 SP3 SP4 are active C420 000kg Pag 18 MP4 Manuale operativo Operating manual MO MP4 504 R9 ISTERESI 1 10 HYSTER 1 10 Valori Impostabili 0000 9999 NNNN valore Descrizione Determina il valore di disattivazione del Set Point n Val disattivazione val Set Point n val Isteresi n Viene disattivata l uscita a relay R n e viene spento sul display in pag principale la barra corrispondente al Set Point Selectable values 0000 9999 NNNNN value Description To calculate Set Point n deactivation value Deactivationn value Set Point n value Hysteresis n value R n relay output is deactivated and on
32. ent within the measure range ERR 6 The indicator detects a negative signal too low that it manage or the input is open Check both the connections of analog input and the transducer output signal RICERCA GUASTI TROUBLE SHOOTING Lo strumento non si accende Controllare che i cavi di alimentazione siano collegati Verificare che la rete sia alimentata Lo strumento visualizza in modo intermittente la pagina di introduzione modello e versione software Problema elettrico contattare il fornitore Lo strumento visualizza scritte prive di significato oppure non visualizza nulla pur se correttamente alimentato Probabile problema sul display o sul microcontrollore contattare il fornitore Lo strumento visualizza error 1 error 2 error 4 poi parte dall inizio Probabile guasto di una periferica interna contattare il fornitore Pag e Instrument does not switch on Check whether feeding cables are connected Check whether electric net is fed e Instrument dysplays in an intermittent way the introduction page software version and model This is an electric problem please contact the supplier e Instrument display meaningless writings or it does not display anything even if correctly fed Possible problem either on display or on microcontroller please contact the supplier e Instrument displays error 1 error 2 error 4 then starts from the beginning Possible fault on an internal peripheral please contact t
33. error messages troubleshooting Data Display Indications are displayed by a graphic backlighted LCD display with a 128x32 dots resolution located on instrument front panel Messages and data are displyed in a graphic mode C1 5000 0 kg C2 3500 0 kg fig 2 pag principale C3 2000 0 kg pict 2 main page C4 1000 0 kg Nota SetPoint sono segnalati disabilitati Note The SetPoints are indicated as disabled FILTER 4 fig 4 pagina di accesso ai Menu ZOOM CH DISAB protetti da password PEAK DISAB pict 4 Password protected Menu PASSWORD 0000 access page Pag 14 MP4 Manuale operativo Operating manual MO MP4 504 R9 DESCRIZIONE dei TASTI KEYS DESCRIPTIONS comandi per utilizzare lo strumento sono formati da 5 tasti posti sul pannello frontale dello strumento Le funzioni dei tasti sono indicate dalla grafica sul pannello Commands for indicator use consist of a 5 keys placed on instrument front panel Keys functions are showed by the graphic on the panel Questo tasto esegue due funzioni 1 In pagina principale entra in Menu per l impostazione dei parametri pag 18 2 Allinterno del Menu mostra la pagina successiva dopo l ultima pagina ritorna alla pagina principale MENU visualizza i parametri Premendo il tasto Enter si passa al parametro successivo Premendo il tasto si incrementa il valore indicato dal cursore lampeggiante premendo il tasto si decrementa il valore ind
34. esso 1 di conseguenza per avere una somma corretta l operatore deve avere sull ingresso 1 il valore espresso con un numero di decimali minore o uguale agli altri ingressi Il tasto F1 attiva disattiva la funzione se questa stata abilitata nel Men Questa funzione riduce la velocit di conversione dello strumento noi consigliamo l uso con filtri digitali superiori al 2 Esempio Input1 2mV Input2 2mV Input3 10V Input4 4 20mA Quando la funzione TOTAL attiva esegue valore Input valore Input2 Se valore Input1 550 0 kg e valore Input2 561 5 kg Total 1111 5 kg Se valore Input1 550 0 kg e valore Input2 561 5 kg gt Total 11 5 kg TOTAL When the function is active the instrument performs the algebraic sum of sampled values from enabled inputs that are identical in term of analog input type to input 1 reference input The position of both decimal point and measurement unit is the same of input 1 therefore in order to have a correct sum on input 1operator must have a value expressed with a number of decimal lower or equal to other inputs F1 key enables disables the function if this has been activated in the Men This functions reduces the conversion speed of the instrument we advise the use with digital filter higher than 2 Example Input1 2mV 2 2 Input3 10V Input4 4 20mA When TOTAL function is active performs Input1 value Input2 value If Input1 value 550 0 kg and Input2 value 561 5 kg gt
35. ges made do not correspond more to the operator requirement How to restore company calibration 1 Posizionare il cursore lampeggiante sul canale desiderato 1 Move the flashing cursor to the wanted channel 2 Selezionare Y e premere il tasto Enter 2 Select Y and press Enter key 3 Ripetere i punti 1 e 2 per tutti i canali desiderati 3 Repeat step 1 and 2 for all channels which have to be changed RESET C1 N RESET C2 N Pagina del ripristino della Calibrazione di fabbrica RESET C3 N Company Calibration restore page RESET C4 N IMPOSTAZIONE CON PASSWORD 0009 opzionale SETTINGS THROUGH 0009 PASSWORD on request MODIFICA della TEMPERATURA TEMPERATURE MODIFY 14 Temp modifica della temperatura originale ingresso 4 vedi pag 45 14 Reset ripristino della temperatura originale ingresso 4 Temp modifica della temperatura originale ingresso 3 vedi pag 45 Reset ripristino della temperatura originale ingresso 3 I4 Temp original temperature modify input 4 see page 45 I4 Reset original temperature restore input 4 I3 Temp original temperature modify input 3 see page 45 I3 Reset original temperature restore input 3 14 TEMP 14 RESET I3 TEMP I3 RESET 23 2 N Pagina del Menu della Temperatura 25 0 Temperature Menu page N Pag 36 MP4 Manuale operativo Operating manual MO MP4 504 R9 IMPOSTAZIONI CON PASSWORD 3464 SETTINGS THROUGH 3464 PASSWORD
36. he supplier 52
37. hing cursor if keapt press after 2 seconds it rapidly increases the value if the cursor is on the sign it changes it 5 ENTER to store the data move to next parameter Pag 17 MP4 Manuale operativo Operating manual MO MP4 504 R9 SET POINT 1 10 SET POINT 1 10 Valori Impostabili 50000 C ingresso S segno NNNNN valore Formato Cn SNNNNN fig A CO SetPoint disabilitato C1 4 SetPoint abilitato sull ingresso selez Descrizione Quando il valore campionato raggiunge il valore del SetPoint n viene attivata l uscita a relay corrispondente e sul display in pagina principale viene attivata la barra associata al SetPoint fig B Indicazione dei SetPoint In pagina principale sulla Dx del display fig B viene indicato lo stato dei SetPoint La posizione delle barre verticali sulla riga indica a quale canale 6 associato il SetPoint una barra di 3 pixel indica che il SetPoint abilitato ma non attivo una barra di 5 pixel indica che il SetPoint abilitato e attivo una barra di 1 pixel indica che il SetPoint disabilitato Nota All accensione i SetPoint vengono attivati in ritardo per permettere allo strumento di stabilizzarsi Selectable values 50000 S sign NNNNN value Format Cx SNNNNN CO SetPoint disable 1 4 SetPoint enabled on selected input Description When sampled value reaches the SetPoint n value the corresponding relay output is activated and on the display in the main pag
38. icato dal cursore lampeggiante premendo il tasto si ruota il cursore da Sx a Dx This key has two functions 1 In main page to enter into the Menu for parameters setting page 18 2 Inside the Men its shows the next page after last page it goes back to the main page MENU to display the parameters By pressing Enter key next parameter appears By pressing key it increases the value indicated by the flashing cursor by pressing amp key it decreases the value indicated by the flashing cursor by pressing 4 key it turns the cursor from left to right Questo tasto esegue due funzioni 1 In pagina principale attiva il funzionamento Manuale 2 All interno del Menu incrementa la cifra selezionata dal cursore lampeggiante MAN lo strumento si arresta sul canale attivo in quel momento ad ogni pressione del tasto MAN viene attivato il canale successivo se la funzione di ZOOM disabilitata il dato viene mostrato in formato grafico grande f incrementa la cifra carattere selezionata dal cursore lampeggiante Pag 15 This key has two functions 1 main page it activates Manual function 2 Inside the Menu it increases the selected digit flashing cursor MAN Instrument stops itself on the channel presently active by pressing MAN key it activates the next channel if ZOOM function is disabled data is showed in a large graphic format t it increases the digit characte
39. ilita segnale d ingresso Input Signal Sensitivity 2mV V Fondo Scala Full Scale 150 000 div Risoluzione Resolution 1 Filtro digitale Digital filter 4 CONFIGURAZIONE DI DEFAULT DEFAULT CONFIGURATION Protocol 9600 N 8 1 10 3 INDIRIZZO STRUMENTO 00 INSTRUMENTADDRESS 00 4 1 div no FONDO SCALA STRUMENTO 50000 INSTRUMENT FULL SCALE 50000 CODIFICA PER L ACQUISTO PURCHASE CODE EMP4 Alimentazione A230 230Vac A115 115Vac D24 24Vdc UA Analog output US Serial output UAS Analog Serial output A230 230Vac UA uscita Analogica 115 115Vac US uscita Seriale D24 24Vdc UAS Analogica Seriale Pag 11 MP4 Manuale operativo Operating manual MO MP4 504 R9 TRASPORTO TRANSPORT La componentistica 6 elettronica In caso di trasporto imballare adeguatamente lo strumento Attenzione ai forti urti e all umidit The device is made of electronic components In case of transport pack it carefully Pay attention to both strong shocks and humidity CONSEGNA DELIVERY Lo strumento viene collaudato in ogni particolare configurato e calibrato con i dati di default pag 11 oppure con le specifiche del cliente Instrument is tested in any of its parts it is supplied configurated and calibrated according to default data page 11 or customer specification POSIZIONAMENTO Lo strumento da pannello Non da tavolo Posiziona
40. inputs or channels each input is suitable to receive signals coming from full bridge strain gauges or from transducers with amplified output either in tension or in current it is ideal for the measurement of forces weight and pressure The measurement control on the 4 inputs happens through a switching the sampling frequency is proportional to the selected filter It has been realised to be used in both static and dynamic measurement systems of industrial environment where it is necessary to acquire several indipendent transducers simultaneously Instrument with a 0 010 accuracy MP4 has a standard resolution of 50 000 divisions and an internal resolution of 100 000 divisions Suitable to be used with 350 700 ohm load cells or dynamometers with a 4 wires connection transducers with 0 10V 10V 0 20mA or 4 20mA output potenziometers The indicator can work either Manual mode with the whole conversion speed addressed on a single input or in Automatic mode with the control of the 4 inputs at a conversion speed of a 1 4 for each input In Manual mode it is possible to singularly reset the analog inputs through the Zero key while in Automatic mode it is possible to reset all the analog inputs with the Zero remote input The indicator is equipped with Data Logger function which allows the storing in Eeprom memory of 90 values for each input Pag 5 MP4 Manuale operativo Operating manual MO MP4 504 R9 Questa funzione permet
41. ion status TX DATA To activate the transmission of the data stored through the serial Warning Before the operator activates the function he shall set the storing time TIME gt 0 Before operator activates the stored data transmission he has to stop the function STOP DL Stored data transmission is performed in a continuous way from 15 to 90 data transmission interval between the data is about 0 25 seconds TIME MEM START DL STOP DL TX DATA 0000 N Pagina impostazioni Data Logger N Data Logger setting page N Pag 31 MP4 Manuale operativo Operating manual MO MP4 504 R9 IMPOSTAZIONI PER LA STAMPANTE ATTENZIONE Quando si seleziona l uscita seriale SERIAL PRINT lo strumento rende accessibile la pagina di impostazione della Data Ora e la pagina per l impostazione dell intestazione del report di stampa queste pagine compaiono avanzando nelle pagine successive SETTING FOR PRINTER WARNING When SERIAL PRINT serial output is selected instrument makes the Data Time setting page available as well as the page for setting the print report heading these pages appear by moving forward in the next pages IMPOSTAZIONE DATA ORA CLOCK CALENDAR SETTING In questa pagina si imposta la Data Ora che la stampante usa per configurare l Orologio Calendario interno alla pressione del tasto Enter lo strumento invia alla stampante i dati impostati In this page the operator set Date Time used
42. mpa Termico Printing mode Thermal dot line Modello FT190 S3 0001 Printer model FT190 S3 0001 PRINTER DB25 Female MP4 Terminals 254567891 Pag 51 MP4 Manuale operativo Operating manual MO MP4 504 R9 MESSAGGI ERRORE ERR 1 ERR 2 ERR 4 Errore su periferica interna ERROR MESSAGES ERR 1 ERR 2 4 Error on internal peripheral UPPER L indicatore rileva un segnale positivo superiore al 150 del Fondo Scala Portare il segnale all interno del campo di misura UPPER The indicator detects a positive value higher than 150 of Full Scale Take back the measurement within the measure range ERR 5 L indicatore rileva un segnale positivo troppo alto oppure l ingresso aperto Verificare i collegamenti dell ingresso analogico ed il segnale d uscita del trasduttore ERR 5 The indicator detects a positive signal too high that it can t manage or the input is open Check both the connections of analog input and transducer output signal LOWER L indicatore rileva un segnale negativo superiore al 15096 del Fondo Scala Portare il segnale all interno del campo di misura ERR 6 L indicatore rileva un segnale negativo troppo basso oppure l ingresso aperto Verificare i collegamenti dell ingresso analogico ed il segnale d uscita del trasduttore LOWER The indicator detects a negative value higher than 15096 of Full Scale Take back the measurem
43. nni Data 31 07 2009 pog C DECLARATION OF CONFORMITY Manufacturer AEP transducers s r l Address Via Bottego 33 A 41126 Cognento MODENA Italy DECLARES THAT THE FOLLOWING PRODUCT Product name MP4 Type Digital Indicator at 4 inputs Year of manufacturing 2005 Options this declaration covers all the options specified in the sales catalogue CONFORM TO THE FOLLOWING DIRECTIVES 2004 108 CE 2006 95 CE 2002 95 CE 2002 96 CE CONFORMS TO THE FOLLOWING NORMS EN 61010 1 2001 EN 61326 1 2007 CONFORMS TO THE REGULATION n 1907 2006 REACH The product has been tested in the typical installation configuration as described in the instruction manual Above described product meets the requirements of mentioned Norms basing on both test results and considerations listed in the technical file I declare that the product defined above meets the requirements of the Directives of the Norms and Rules above mentioned 41126 Cognento MODENA Date 31 07 2009 Lioi Giovanni Tee Mensa Non eus Pag 1 MP4 Manuale operativo Operating manual MO MP4 504 R9 INDICE GENERALE Targa di Identificazione Usi non previsti Smaltimento Introduzione Diagramma a blocchi Dati Tecnici Dati di Riferimento Configuraz di default Codifica acquisto Trasporto Consegna Posizionamento Installazione Accensione Spegnimento Manutenzione Indicazioni esempi Descrizione dei Tasti Menu Impostazioni Se
44. o Print Hold ALIMENTAZIONE GENERALE GENERAL POWER SUPPLY 230Vac 10 FREQUENZA FREQUENCY 50 60Hz POTENZA MASSIMA MAX POWER ACCEPTED 10VA CARATTERISTICHE dei RELAY carico resistivo RELAY CHARACTERISTICS resistive load 110Vac 1A or 48Vdc 1A GRADO DI PROTEZIONE solo pannello frontale PROTECTION CLASS front panel only 40 EN 60529 DIMENSIONI AxLxP mm DIMENSIONS HxLxD mm 96x96x159 DIN43700 DIMA DI FORATURA AxL mm HOLE GAUGE HxL mm 88x90 PESO WEIGHT approx 0 8 kg OPZON OPTIONS ALIMENTAZIONE POWER SUPPLY 115Vac 10 or 24Vdct10 STAMPANTE DA PANNELLO 24 colonne RS232 PANEL PRINTER 24 Columns RS232 Model FT190 S3 0001 USCITA SERIALE RS232 RS485 SERIAL OUTPUT RS232 RS485 19200 9600 4800 Baud RS232 lunghezza del cavo RS232 cable length max 20m RS485 lunghezza del cavo RS485 cable length max 1000m USCITA ANALOGICA IN TENSIONE IN TENSION ANALOG OUTPUT 0 10V resolution 16 bit RL min 10KQ RL 10KQ 10V resolution 15 bit USCITA ANALOGICA IN CORRENTE IN CURRENT ANALOG OUTPUT 0 20mA resolution 15 bit RL max 5000 RL max 5000 4 20mA resolution 15 bit INGRESSO IN TEMPERATURA solo ingressi 4 e 3 TEMPERATURE INPUT inputs 4 and 3 only 2 wires PT100 probe type Pag 10 MP4 Manuale operativo Operating manual MO MP4 504 R9 DATI DI RIFERIMENTO REFERENCE DATA Temperatura Temperature 23 C Umidita relativa Relative humidity 50 Sensib
45. one del Fondo Scala se il valore indicato non After having performed the Full Scale if the value displayed does not coincide con il valore di carico si pud modificare a piacere il Fondo Scala coincide with the load value Full Scale can be changed until wanted fino a raggiungere l indicazione desiderata indication is reached Come impostare il Fondo Scala How to set the Full Scale 1 Posizionare il cursore lampeggiante sul canale desiderato 1 Move the flashing cursor to the wanted channel 2 Con i tasti di incremento decremento impostare il valore 2 Through the increase decrease keys set the wanted value desiderato 3 Repeat step 1 and 2 for all the channel which shall be changed 3 Ripetere i punti 1 e 2 per tutti i canali desiderati 5000 0 350 00 Esempi di impostazione del Fondo Scala dei canali 20 000 Channels Full Scale setting example 1 0000 Pag 34 MP4 Manuale operativo Operating manual MO MP4 504 R9 PUNTO DECIMALE DECIMAL POINT Il Punto Decimale la risoluzione del valore che compare sul display Decimal Point is value resolution which appears on the display espresso nell Unit di Misura In questa pagina si imposta il Punto expressed in the Measurement Unit In this page the decimal Point of decimale per ogni singolo canale each channel is set Valori selezionabili 0 4 Selectable values 0 4 Come impostare il Punto Decimale How to set the Decimal Point 1 Posizion
46. page INPUT C4 DISABLE Pag 37 MP4 Manuale operativo Operating manual MO MP4 504 R9 FUNZIONE DI ZERO La funzione di ZERO serve per azzerare l indicazione di ogni canale dello strumento il valore indicato prima dell abilitazione della funzione viene sottratto al valore campionato il risultato 0 viene mostrato sul display la funzione agisce su tutto il campo di misura 100 Lo stato della funzione viene memorizzato all accensione la funzione riprende lo stato precedente allo spegnimento Quando la funzione abilitata sulla riga del display associata ad ogni canale viene acceso il carattere Z fig A quando disabilitata il carattere Z spento fig B In Manuale per abilitare la funzione premere il tasto ZERO per disabilitarla tenere premuto il tasto ZERO per 5 secondi In Automatico per abilitare la funzione chiudere l ingresso remoto di ZERO INP 1 per disabilitarla tenere chiuso l ingresso di ZERO per 5 secondi ZERO FUNCTION ZERO function is used to reset the indication of each instrument channel the value displayed before function activation is decucted from sampled value the result 0 is showed on the display function acts on the whole measurement field 100 Function status is stored at instrument power on function takes again the status had before the power off When function is enabled on the display line associated to each channel Z character lights A when is disabled
47. parameter TIME TX gt 0 printing automatically occurs every NNNN seconds When TRANSM function is selected pause time TIME TX between a transmission and the other shall be set SERIAL IDENTITY TIME TX 19200 00 Pagina impostazione Uscita Seriale 00 Serial Output setting page Pag 26 MP4 Manuale operativo Operating manual MO MP4 504 R9 COMUNICAZIONE SERIALE La comunicazione seriale avviene per mezzo di caratteri in codice ASCII Caratteri di controllo ASCII CHAR 36 Inizio stringa lt cr gt ASCII CHAR 13 Fine stringa ACK ASCII CHAR 6 Comando riconosciuto ASCII CHAR Numero di Identificazione vedi pag 27 Nota Quando viene riconosciuto un comando di scrittura lo strumento risponde con la stringa IIACK cr quando viene riconosciuto un comando di lettura lo strumento risponde con l informazione richiesta SERIAL COMMUNICATION Serial communication is made through chars in ASCII codes Control chars ASCII CHAR 36 String beginning lt cr gt ASCII CHAR 13 String end ACK ASCII CHAR 6 Recognized command Il ASCII CHAR Identification Number see page 27 Note When a writing command is recognized the instrument answers with the string HACK lt cr gt when a reading command is recognized instrument answers with required information COMANDI DI SCRITTURA WRITING COMMANDS MESSAGGIO MESSAGE RISPOSTA ANSWER VALORE VALUE SET POINT 1 S
48. r selected by flashing cursor MP4 Manuale operativo Operating manual MO MP4 504 R9 Questo tasto esegue due funzioni ZERO 1 In pagina principale pag 14 attiva o disattiva la funzione di Zero pag 39 2 All interno del Menu decrementa la cifra selezionata dal cursore lampeggiante ZERO azzera lo strumento Quando attiva si accende il simbolo Z nella riga corrispondente sul display V decrementa la cifra carattere selezionata dal cursore lampeggiante Questo tasto esegue due funzioni 1 In pag principale attiva il funzionamento Automatico 2 All interno del Menu ruota il cursore lampeggiante da Sx a Dx per l impostazione dei dati pag 18 AUTO lo strumento riprende il controllo automatico degli ingressi abilitati i valori sono in formato grafico piccolo ruota il cursore da Sx a Dx solo per le impostazioni che lo prevedono dopo l ultima cifra ritorna all inizio This key has two functions 1 In main page page14 it activates or deactivates Zero function page 39 2 Inside the Menu it decreases amp the selected digit of flashing cursor ZERO it resets the instrument When it is enabled Z symbol is corresponding row on the display WV it decreases the digit character selected by flashing cursor This key has two function 1 In main page it activates the Automatic functioning 2 Inside the Menu it moves the flashing cursor from left to right for dat
49. re in luogo illuminato e adeguatamente protetto dagli agenti atmosferici POSITIONING Instrument is designed for built in purposes equipment It must be housed in a light up position and protected by atmospherics agents It isnt a desktop INSTALLAZIONE INSTALLATION Questo strumento stato prodotto in conformit alle norme per la Compatibilita Elettromagnetica e la Sicurezza delle Apparecchiature a Bassa Tensione affinch esse siano rispettate necessario eseguire i collegamenti elettrici secondo quanto indicato nel presente manuale e dalle marcature presenti sullo strumento Lo strumento da pannello per il montaggio utilizzare gli appositi accessori forniti con lo strumento pag 42 L installazione deve essere eseguita da personale istruito This instrument has been manufactured according to both EMC Electromagnetic Compatibility regulations and to Low Voltage fittings Safety in order to have such rules respected it is necessary to perform electrical connections according to what mentioned in this manual and to what written on instrument labels Instrument is designed for built in purposes for its mounting use the accesories supplied with the instrument page 42 Installation shall be done by authorized personnel only Pag 12 MP4 Manuale operativo Operating manual MO MP4 504 R9 ACCENSIONE Lo strumento non dispone di interruttore Collegare lo strumento tramite l apposita morsettiera all
50. sso AN ZERO si modifica il punto di Zero Il tempo di salita dell uscita dipende dal filtro usato 0 velocit All accensione l Uscita Analogica viene attivata in ritardo per permettere allo strumento di stabilizzarsi AN OUT available outputs NOTHING 10 210 0 20mA 4 20 Cn 124 channel associated to the analog output NOTHING disabled output 0V AN ZERO to change the Zero point of tension analog output Selectable value 0000 9999 AN FS analog output Full Scale Selectable value 00000 50000 AN AMPL to change the output signal amplitute Selectable values 000 00 109 00 Notes analog output varies in a way proportional to its full scale value the output signal amplitude can be changed by acting on the AN AMPL step by acting on AN ZERO step the Zero point can be changed Output risetime depends on filter used 0 speed At instrument power on analog output is activated later in order to enable the indicator stabilize itself AN OUT C1 AN ZERO AN FS AN AMPL DISAB 0000 Pagina impostazione Uscita Analogica 5000 0 Analog Output setting page 000 00 Pag 25 MP4 Manuale operativo Operating manual MO MP4 504 R9 USCITA SERIALE permettere allo strumento di stabilizzarsi durante la pausa lo strumento risponde IINAK lt cr gt SERIAL Baud rate ed uscite selezionabili Protocollo Baud N 8 1 Valori selezionabili DISABLE 4800 9600 19200 PRINTER TRANSM D
51. strument closes the report The next printing is the beginning of a new report Printer model FT190 S3 0001 39 MP4 Manuale operativo Operating manual MO MP4 504 R9 AEP TRANSDUCERS VIA BOTTEGO 33 COGNENTO MODENA 18 11 05 TEST CH VALUE 001 1 1500 3 001 2 100 35 001 500 0 001 4 20 00 TEST VALUE 002 1 1500 0 002 2 100 30 002 3 50041 002 4 19 99 TEST CH VALUE 060 1 1500 2 060 2 100 32 060 3 499 9 060 4 20 00 pee TEST CH VALUE kg 120 1 1500 1 bar 120 2 100 33 ma 120 3 500 0 120 4 20 01 M dT TEST CH VALUE kg 255 1 1500 0 bar 255 2 100 30 ma 255 3 500 0 255 4 20 00 continua 3 Pag 40 UNIT HOUR kg 15 00 kg bar ma UNIT HOUR kg 16 00 kg bar ma Esempio di report di stampa Report print example UNIT HOUR kg 18 15 kg bar ma 4 Manuale Operating manual MO MP4 504 R9 ISTRUZIONI PER IL MONTAGGIO Top view MOUNTING INSTRUCTIONS Back view Nota Eseguire un foro nel pannello Dima di foratura 89x91mm Inserire lo strumento nel foro applicare gli accessori in dotazione per il fissaggio avvitare finch lo strumento non stabile Note Make a hole in the panel Hole gauge 89x91mm Insert the instrument into the hole mount fixing accessories and screw until instrument is steady Pag 41 MP4 Manuale operativo Operating manual MO MP4 504 R9 COLLEGAMENTI CONNECTIONS ALIMENTAZIONE
52. t per riduce il campo di pesatura Come eseguire la Tara 1 Posizionare il cursore lampeggiante sul canale desiderato 2 Selezionare Y e premere il tasto Enter 3 Ripetere i punti 1 e 2 per tutti i canali desiderati This function allows system tare suppession generally intended as weighing structure The force generated by weighing structure is considered by the instrument as system Zero Warning It is recommendable that force generated by weighing structure is lower than 5096 of load cells rate By the way it is possible to suppress up to 80 of the load cells rate even if this possibility reduces the weighing field How to perform the Tare 1 Move the flashing cursor to the wanted channel 2 Select Y and press Enter key 3 Repeat step 1 and 2 for all the channels which shall be changed TARE C1 TARE C2 TARE TARE C4 Pagina impostazione della Soppressione Tara Tare Suppression setting page 2222 Pag 33 MP4 Manuale operativo Operating manual MO MP4 504 R9 FONDO SCALA DEI CANALI CHANNELS FULL SCALE In questa pagina si imposta il Fondo Scala di ogni singolo canale this page the Full Scale of each channel can be set the Full Scale normalmente il Fondo Scala coincide con la portata nominale della cella usually coincides with the nominal rate either of the load cell or of the di carico o del trasduttore applicato al canale pressure connected to the channel Eseguita l impostazi
53. t Point Isteresi dei Set Point Risoluzione Filtri Digitali Zoom Total somma valori Picco Password Uscita Analogica password 0005 Uscita Seriale password 0005 Comunicazione Seriale password 0005 Data Logger password 0005 Impostazioni per la stampante password 0005 Soppressione della Tara password 0007 Fondo Scala degli ingressi canali password 0007 GENERAL INDEX Identification Plate Unauthorized uses Disposal Introduction Block diagram Technical Data Reference Data Default Configuration Purchase code Transport Delivery Positioning Installation Power On Power Off Maintenance Displays examples Keys description Setting Menu Set Point Set Points Hysteresis Resolution Digital Filters Zoom Total sum values Peak Password Analog Output password 0005 Serial Output password 0005 Serial communication password 0005 Data Logger password 0005 Printer settings password 0005 Tare suppression password 0007 Inputs channels Full Scale password 0007 Pagina Page Pag 2 MP4 Manuale operativo Operating manual MO MP4 504 R9 Punto Decimale password 0007 Decimal Point password 0007 35 Unita di Misura password 0007 Measurement Units password 0007 35 Ripristino della Calibrazione di fabbrica password 0007 Company Calibration restoration password 0007 36 Modifica della
54. tare lo Zoom selezionare DISAB per abilitare la somma dei valori Zoom select DISAB to enable values sum please select TOTAL see selezionare TOTAL vedi pag 23 page 23 ZOOM La funzione di Zoom mostra il valore dell ingresso associato in ZOOM Zoom function shows the value of associated input in a bigger formato grafico grande tutti gli altri ingressi sono ugualmente gestiti graphic format all other inputs are managed as well even if their value is anche se non viene mostrato il valore not displayed F1 key enables disables the function if this has been Il tasto F1 attiva disattiva la funzione se questa stata abilitata nel activated in the Men Men FILTER 4 ZOOM CH 2 PEAK CH1 DISAB PASSWORD 0000 C1 1000 0kg C2100 00kg C3 10 000 kg C4 1 5000 kg 1000 0 ZOOM CH2 Pag 21 Pagina di impostazione della funzione di ZOOM ZOOM function setting page Indicazioni dei valori senza la funzione di Zoom Value indications without Zoom function Indicazione del canale 2 con la funzione di Zoom Channel 2 indication with Zoom function MP4 Manuale operativo Operating manual MO MP4 504 R9 TOTAL Quando la funzione attiva lo strumento esegue la somma algebrica dei valori campionati di tutti gli ingressi abilitati che sono uguali come tipo di ingresso analogico all ingresso 1 ingresso di riferimento La posizione del decimal point e l unit di misura la stessa dell ingr
55. te di gestire in automatico prove di durata da 1 a 99999 secondi lo start lo stop il tempo di memorizzazione e la trasmissione via seriale dei dati memorizzati sono gestiti da tastiera da comandi seriali L interfaccia seriale RS232C RS485 opzionale optoisolata si pu programmare e gestire lo strumento da PC per l uso in sistemi evoluti L uscita Analogica opzionale e optoisolata ed indirizzabile su uno dei 4 ingressi disponibili programmabile per le uscite 10V 10V 0 20mA 4 20mA ha il Fondo Scala indipendente dal Fondo Scala dell ingresso Lo Zero e l ampiezza dell uscita Analogica possono essere regolati da tastiera Lo strumento in opzione pu avere uno o due ingressi dedicati solo alla Temperatura gli ingressi sono idonei al collegamento di una sonda PT100 a 2 fili Gli ingressi digitali sono optoisolati e sono adibiti al controllo remoto delle funzioni di Hold Print opzionale Zero Set point hanno l uscita a relay ed hanno la soglia di attivazione e l isteresi di disattivazione programmabile This function enables to automatically manage tets whose duration varies from 1 ap to 99999 seconds the start the stop the storing time and the serial transmission of the stored data are managed through the keyboard or through serial commands RS232C RS485 interface on request is optoinsulated can be programmed and then make the instrument be managed by a PC for its use in advanced systems Analog output on req
56. the display in main page the bar corresponding to the Set Point n is switched off HYSTER 1 0001 0 HYSTER 2 000 10 Esempi di Isteresi programmate HYSTER 3 00 010 Examples of programmed hysteresis HYSTER 4 0 0010 RISOLUZIONE DI MISURA MEASUREMENT RESOLUTION Valori selezionabili 1 2 5 10 20 50 100 Ogni canale ha la sua Risoluzione di misura Note Definisce la costante di incremento delle ultime cifre 1 2 5 ecc Questo sistema viene implementato per aumentare la stabilit della misura in applicazioni dinamiche a scapito della precisione di lettura Cn ingresso 1 4 Selectable values 1 2 5 10 20 50 100 Each channel has its measure Resolution Notes Operator defines the increase constant of the last two digits 1 2 5 etc This system is implemented to increase measurement stability in dynamic application at the expense of reading accuracy ingresso 1 4 RESOL C1 001 RESOL C2 002 Esempi di Risoluzioni programmate RESOL C3 005 Programmed Resolution examples RESOL C4 010 Pag 19 MP4 Manuale operativo Operating manual MO MP4 504 R9 FILTRI DIGITALI DIGITAL FILTERS Valori di filtro selezionabili 1 5 0 off Selectable filter values 1 5 0 off Descrizione Description Il filtro digitale si inserisce selezionando un valore 0 vedi tabella il The operator can insert a digital filter by selecting a value 0 see filtro comune per tutti gli ingressi table
57. the identification the main configuration data the symbols of conformity and waste disposal the production date USI NON PREVISTI A Ambienti con atmosfera esplosiva Ambienti con gas infiammabili corrosivi A UNAUTHORIZED USES Environments with explosive atmosphere Inflammable or corrosive gas environments SMALTIMENTO DISPOSAL A Lo strumento una apparecchiatura professionale conforme alle Direttive 2002 95 CE RoHS e 2002 96 CE RAEE deve essere smaltito separatamente come rifiuto elettrico ed elettronico In paesi diversi dalla Comunit Europea deve essere smaltito come rifiuto elettrico ed elettronico in accordo con le leggi del paese dove lo strumento commercializzato Prima di rimuovere lo strumento togliere l alimentazione poi scollegare i cavi instrument is professional apparatus compliant to the Directives 2002 95 CE RoHS and 2002 96 CE WEEE then it must be disposed separately as electric and electronic waste In different countries of European Community it must be disposed as waste electric and electronic in accord to the laws of the country where the device is commercialized Before to remove the instrument you disconnect first the power supply and after the cables Pag 4 MP4 Manuale operativo Operating manual MO MP4 504 R9 INTRODUZIONE INTRODUCTION L indicatore digitale MP4 6 uno strumento con 4 ingressi analogici o canali
58. uest is optoinsulated and can be addressed to one of the 4 available inputs it programmable for 10V 10V 0 20mA and 4 20mA outputs it has the full scale independent from the input full scale Zero and analog output amplitude can be adjusted through the keyboard The instrument on request could have one or two Temperature dedicated inputs only fit to the PT100 probe two wires connection Digital outputs are optoinsulated and are dedicated to the remote control of Hold Print on request and Zero functions Set points have a relay output while the activation treshold and the deactivation are programmable L AEP transducers si riserva il diritto qualora lo ritenesse necessario di apportare modifiche di qualsiasi genere senza alcun obbligo di preavviso dati contenuti questo manuale sono indicativi la ditta declina ogni responsabilit per errori o discordanze dal presente AEP transducers holds the right to make any change when necessary without notice The data contained in this manual are just indicative and the manufacturer declines any responsibility for errors or discrepancies with respect to this manual Pag 6 MP4 Manuale operativo Operating manual MO MP4 504 R9 DIAGRAMMA A BLOCCHI BLOCKS DIAGRAM LOADCELL DRIVER EEPROM REMOTE inpur uC Lt H RS232 SERIAL RS485 INTERFACE DISPLAY TRANSDUCER FEEDER
59. ull Scale restoration Password 0009 to enter into Temperature Menu this Menu is accessible with the 4 input formatted with the C measure unit only In this Menu there are four parameters two for the n 4 input and two for n input each input has one parameter for modify the displayed temperature and one parameter for restore the original temperature page 37 Password 3464 to enter into the Men which selects the type of analog input to be associated to each single channel selectable input are 2mV amv 0 10V 4 20mA Disable FILTER ZOOM CH PEAK CH PASSWORD 4 DISAB Esempio di impostazione della Password 0005 DISAB example of 0005 Password setting 0005 24 Pag MP4 Manuale operativo Operating manual MO MP4 504 R9 IMPOSTAZIONI CON PASSWORD 0005 PASSWORD 0005 SETTINGS USCITA ANALOGICA ANALOG OUTPUT AN OUT uscite disponibili NOTHING 10 10 0 20mA 4 20mA Cn 1 4 canale associato all uscita analogica NOTHING uscita disabilitata OV AN ZERO modifica il punto di Zero dell Uscita Analogica in tensione Valori impostabili 0000 9999 AN FS fondo scala dell Uscita Analogica Valori impostabili 00000 50000 AN AMPL modifica l ampiezza del segnale d uscita Valori impostabili 000 00 109 00 Note L uscita analogica varia in modo proporzionale al suo valore di fondo scala si pu modificare l ampiezza del segnale d uscita agendo sul passo AN AMPL agendo sul pa