Z-8TC Collegamenti Elettrici S + + + + + + + +

image

Contents

1. Bit 15 8 Impostano il valore della velocit di comunicazione seriale baudrate 00000000 0x00 4800 Baud 00000001 0x01 9600 Baud 00000010 0x02 19200 Baud 00000011 0x03 38400 Baud 00000100 0x04 57600 Baud 00000101 0x05 115200 Baud 00000110 0x06 1200 Baud 00000111 0x07 2400 Baud Bit 7 0 CONF_CH1_CH2 Impostano il tempo di ritardo della risposta Rappresenta il numero di pause da 6 caratteri ciascuna da inserire tra la fine del messaggio Rx e l inizio del messaggio Tx Il valore di default 0x00 valore decimale 0 Configurazione Canali 1e2 40054 R W Valore caricato in caso di fault canale 5 40063 R W VAL_FAULT_5 espresso come 40007 Default 2000 0 Valore caricato in caso di fault canale 6 40064 R W espresso come 40008 Default 2000 0 VAL_FAULT_6 Valore caricato in caso di fault canale 7 40065 R W VAL_FAULT_7 c espresso come 40009 Default 2000 0 VAL_FAULT_8 Valore caricato in caso di fault canale 8 40066 R W espresso come 40010 Default 2000 0 Bit 15 Attivazione Canale 1 0 Canale 1 non attivo 1 Canale 1 attivo Bit 14 Attivazione Canale 2 0 Canale 2 non attivo 1 Canale 2 attivo Bit 13 Tipo dato restituito Canale 1 e Canale 2
2. Bit 7 4 Thermocouple Type of Channel 1 see THERMOCOUPLE TYPE Table Default Type J Bit 3 0 Thermocouple Type of Channel 2 see THERMOCOUPLE TYPE Table Default Type J 40055 R W CONF_CH3_CH4 Configuration of Channels 3 and 4 Bit 15 0 Register for the configuration of channels 3 and 4 See Register 40054 refering to channels 3 and 4 instead of channels 1 and 2 40056 R W CONF_CH5_CH6 Configuration of Channels 5 and 6 Bit 15 0 Register for the configuration of channels 5 and 6 See Register 40054 refering to channels 5 and 6 instead of channels 1 and 2 CONF_CH7_CH8 Configuration of Channels 7 and 8 40057 RIW Bit 15 0 Register for the configuration of channels 7 and 8 See Register 40054 refering to channels 7 and 8 instead of channels 1 and 2 CHAN8_TEN Channel 8 measurement tenths of C or 40010 tenths of uV Bit 15 0 Temperature of channel 8 in tenths of C or voltage in tenths of uV CHAN1_FLOAT_H Measurement of channel in floating point see 40011 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 1 in C or voltage in mV MSW of the float CHAN1_FLOAT_L Measurement of channel 1 in floating point see 40012 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperat
3. JUNCT_TEN_IN7_8 Cold Junction Temperature of channels 7 and 8 40031 R Bit 15 0 Cold junction temperature of channels 7 and 8 in tenths of C ERR_CH1 2_CH3 4 Errors Channels 1 2 MSB Channels 3 4 LSB 40037 R Bit 15 1 Power supply voltage error channels 1 and 2 Bit 14 1 Reception Error channels 1 and 2 Bit 13 1 EEPROM saving Error channels 1 and 2 Bit 12 1 EEPROM saving blocked channels 1 and 2 Bit 11 9 Reserved Bit 8 1 Reading Error CRC EEPROM chan 1 and 2 Bit 7 1 Power supply voltage error channels 3 and 4 Bit 6 1 Reception Error channels 3 and 4 Bit 5 1 EEPROM saving Error channels 3 and 4 Bit 4 1 EEPROM saving blocked channels 3 and 4 Bit 3 1 Reserved Bit 0 1 Reading Error CRC EEPROM chan 3 and 4 ERR_CH5 6_CH7 8 Errors Channels 5 6 MSB Channels 7 8 LSB 40038 R Bit 15 1 Power supply voltage error channels 5 and 6 Bit 14 1 Reception Error channels 5 and 6 Bit 13 1 EEPROM saving Error channels 5 and 6 Bit 12 1 EEPROM saving blocked channels 5 and 6 Bit 11 9 Reserved Bit 8 1 Reading Error CRC EEPROM chan 5 and 6 Bit 7 1 Power supply voltage error channels 7 and 8 Bit 6 1 Reception Error channels 7and 8 Bit 5 1 EEPROM saving Error channels 7 and 8 Bit 4 1 EEPROM saving blocked channels 7 and 8 Bit 3 1 Reserved Bit 0 1 Reading Error CRC EEPROM chan 7 and 8 RESET Module Reset 40041 R W Bit 15 0 Write value O
4. Bit 15 0 Temperature of channel 6 in C or voltage in mV MSW of the float CHAN6_FLOAT_L Measurement of channel 6 in floating point see 40022 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 6 in C or voltage in mV LSW of the float CHAN7_FLOAT_H Measurement of channel 7 in floating point see 40023 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 7 in C or voltage in mV MSW of the float CHAN7_FLOAT_L Measurement of channel 7 in floating point see 40024 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 7 in C or voltage in mV LSW of the float CHAN8_FLOAT_H Measurement of channel 8 in floating point see 40025 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 8 in C or voltage in mV MSW ofthe float CHAN8_FLOAT_L Measurement of channel 8 in floating point see 40026 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 8 in C or voltage in mV LSW ofthe float STATUS_INP Copy of register 40002 containing the status 40027 ofthe input channels JUNCT_TEN_IN1_2 Cold Junction Temperature of channels 1 and 2 40028 Bit 15 0 Cold junction temperature of channels 1 and 2 in tenths of C JUNCT_TEN_IN3_4 Cold Junction Temperature of channels 3 and 4 40029 Bit 15 0 Cold junction temperature of channels 3 and 4 in tenths of C JUNCT_TEN_I
5. CONVERTITORE PER TERMOCOPPIE Z 8TC CON ISOLAMENTO A SEI PUNTI Descrizione Generale Lo strumento Z 8TC un convertitore digitale per termocoppie con otto canali di misura isolati dall alimentazione e dalla linea di comunicazione seriale fino a 1 5 kV Lo stesso isolamento pari a 1 5 kV previsto tra canali facenti capo a gruppi diversi di morsetti II modulo dunque caratterizzato da un isolamento complessivo a sei punti In aggiunta esso caratterizzato da e Cablaggio facilitato dell alimentazione e del bus seriale per mezzo del bus alloggiato nella guida DIN e Configurabilita della comunicazione tramite DIP switch o via software e Comunicazione seriale RS485 con protocollo MODBUS RTU massimo 32 nodi e Protezione contro scariche ESD fino a 4 kV Elevata velocit di acquisizione e Misura di termocoppie J K E N S R B T e Misura degli ingressi disponibile nei seguenti formati rappresentazione floating point floating point inversa virgola fissa a 16 bit in decimi di grado con segno per la temperatura decine di uV perla tensione Canaliattivabili singolarmente e Valore programmabile in caso di fault o congelamento ultima lettura Per ciascuna coppia di ingressi relativi allo stesso gruppo di morsetti sono previste le seguenti impostazioni comuni e Misura impostabile in temperatura o mV e Filtro programmabile a otto livelli perla stabilizzazione della lettura e Reiezione prog
6. Inputs Thermocouple types J K E N S R B T Tables EN60584 1 ITS 90 Dependent on the thermocouple type see Thermocouples Range table Temperature Range Span mV 10 1 81 4 mV Impedance 10 MQ Total Error 14 bits ADC and 50 Hz Rejection 0 040 13 uV 15 bits ADC and 50 Hz Rejection 0 035 10 uV 14 bits ADC and 60 Hz Rejection 0 045 16 uV 15 bits ADC and 60 Hz Rejection 0 040 12 uV SENECA MI001230 E ENGLISH 1 16 Test Current lt 50 nA CMRR gt 155 dB tested port towards all the other ones atl DMRR 9 GND THERMOCOUPLES RANGE Range Error Range Error 210 1200 C 0 05 C 50 1768 C 0 02 C 200 1372 C _0 05 c R 50 1768 C 0 02 C 200 1000 C _0 02 c__ B 250 1820 c 0 03 C 200 1300 C 0 04 C 200 400 C 0 04 C Other Features ADC Settable to 14 or 15 bits Thermal Drift lt 100 ppm K Disturbance Rejection Settable to 50 Hz or 60 Hz Cold Junction Error lt 1 C Insulation Voltage 1500 Vac among input power supply and communication ports 1500 Vac among channels belonging to different groups of terminals Protection Degree IP20 Environmental conditions Temperature 10 65 C Saving of parameters in EEPROM guaranteed in range 0 50 C Humidity 30 90 not condensing Altitude up to 2000 m a s l 20 85 C Power Supply Fail RS485 Communicatio
7. Bit 6 1 Errore di ricezione canali 7 e 8 Bit 5 1 Errore salvataggio EEPROM canali 7 e 8 Bit 4 1 Salvataggio EEPROM bloccato canali 7 e 8 Bit 3 1 Riservati Bit 0 1 Errore lettura CRC EEPROM canali 7 e 8 RESET Reset del modulo 40041 R W Bit 15 0 Scrivendo il valore OxCCCC viene comandato il reset riavvio del modulo SENECA M1001230 I ITALIANO 13 16 Bit 15 0 Registro per la configurazione dei canali 5 e 6 Vedere il registro 40054 tenendo conto che in questo caso non si fa riferimento ai canali 1e 2 ma rispettivamente ai canali 5 e 6 Configurazione Canali7e8 40057 R W CONF_CH7_CH8 Bit 15 0 Registro per la configurazione dei canali 7 e 8 Vedere il registro 40054 tenendo conto che in questo caso non si fa riferimento ai canali 1e 2 ma rispettivamente ai canali 7 e 8 AUX SETTINGS Registro ausiliario configurazione 40058 R W ADDR 6 7 Registro per l impostazione dell indirizzo del modulo e del controllo di parit 40052 R W Bit 15 Interpretazione floating point 0 Viene trasmessa prima la word alta del floating point poi quella bassa 1 Viene trasmessa prima la word bassa del floating point poi quella alta Bit 14 8 Riservati non modificare Bit 7 Azione in caso di faultcanale 1 0 Il valore di temperatura tensione forzato al valore di fault programmato 1 Il va
8. 0 misura in C 1 misura inmV CHAN5_FLOAT_L Misura canale 5 in floating point vedi bit 15 40020 AUX SETTINGS 40058 Bit 15 0 Temperatura in C o tensione in mV del canale 5 LSW del float CHAN6_FLOAT_H Misura canale 6 in floating point vedi bit 15 40021 AUX_ SETTINGS 40058 Bit 15 0 Temperatura in C o tensione in mV del canale 6 MSW del float CHAN6_FLOAT_L Misura canale 6 in floating point vedi bit 15 40022 AUX SETTINGS 40058 Bit 15 0 Temperatura in C o tensione in mV del canale 6 LSW del float CHAN7_FLOAT_H Misura canale 7 in floating point vedi bit 15 40023 AUX SETTINGS 40058 Bit 15 0 Temperatura in C o tensione in mV del canale 7 MSW del float CHAN7_FLOAT_L Misura canale 7 in floating point vedi bit 15 40024 AUX_ SETTINGS 40058 Bit 15 0 Temperatura in C o tensione in mV del canale 7 LSW del float CHAN8_FLOAT_H Misura canale 8 in floating point word piu 40025 significativa Bit 15 0 Temperatura in C o tensione in mV del canale 8 MSW del float CHAN8_FLOAT_L Misura canale 8 in floating point vedi bit 15 40026 AUX SETTINGS 40058 Bit 15 0 Temperatura in C o tensione in mV del canale 8 LSW del float STATUS_INP Copia del registro 40002 contenente lo stato 40027 dei canali di ingresso GIUNTO_DEC_IN1_2 Misura temperatura giunto freddo canali1e2 40028 Bit 15 0 Temperatura in decimi di C del giunto freddo relativo ai canali 1 e 2 GIUNT
9. TX LED RED Steady Data are being transmitted through the RS485 communication port Serial interface For detailed information on RS485 serial interface consult the documentation provided by the website www seneca it in the section Prodotti Serie Z PC MODBUS TUTORIAL DIP SWITCH SETTING The instrument leaves the factory with all DIP switches configured in position 0 The settings of the DIP switches defines the module s communication parameters address and speed In all the following tables the indication corresponds to a DIP switch set in 1 ON no indication is provided when the DIP switch is set in 0 OFF SW1 1 2 2 I 9600 Baud _ 19200 Baud le 38400 Baud le e 57600 Baud ADDRESS sw1l3 al5lelzl Communication Parameters from EEPROM ______ jel FixedAddress 01 _ _________ ptt e aeaee o I Fixed Address 03 je FixedAddressso4 ___________ Fixed Address as from binary representation fejelelelele Fixed Address 63 NOT USED Iswifg Notused S I Leave to OFF position RS485 TERMINATOR O i I Terminator OFF I Terminator ON The default configuration is the following Address 1 38400 no parity 1 stop bit SENECA MI001230 E ENGLISH 5 16 DEFAULT SETTING OF INPUT CHANNELS The default configuration valid for each pair of channels belogging to the same group of terminals is the following En
10. 0 Hz Errore Giunto Freddo lt 1 C Tensione di isolamento 1500 Vac tra porte di alimentazione comunicazione e ingresso 1500 Vac tra canali relativi a gruppi di morsetti diversi Grado di protezione IP20 Condizioni ambientali Temperatura 10 65 C Salvataggio parametri in EEPROM garantito nel range 0 50 C Umidit 30 90 non condensante Altitudine 2000 sIm 20 85 C Alimentazione Fail Comunicazione RS485 Morsetti a vite estraibili a 4 vie max 1 5 mm passo 3 5mm Connettore posteriore IDC10 per barra DIN Jack frontale stereofonico 3 5 mm per connessione RS232 COM PBT colore nero 100 x 112 x 17 5 mm 140 g EN61000 6 4 2002 10 emissione elettromagnetica ambiente industriale EN61000 6 2 2006 10 immunit elettromagnetica ambiente industriale EN61010 1 2001 sicurezza Tutti i circuiti devono essere isolati con doppio isolamento dai circuiti sotto tensione pericolosa Il trasformatore di alimentazione deve essere a norma EN60742 Trasformatori di isolamento e trasformatori di sicurezza Temp Stoccaggio Segnalazioni LED Connessioni Contenitore Dimensioni Peso Normative CE valori sono validi alla frequenza di reiezione impostata con il filtro inserito 2 Per valori del disturbo tali che il picco del segnale d ingresso non ne superi l accettabilit Fino a 250 C si assume un valore di temperatura nulla SENECA M
11. 1 Even parity EVEN 00000010 Odd parity ODD BAUDR Register for the setting of the baudrate and of the response delay time 40053 R W Bit 15 8 Set the value of the serial communicati speed baudrate 00000000 0x00 00000001 0x01 00000010 0x02 00000011 0x03 38400 00000100 0x04 57600 00000101 0x05 115200 00000110 0x06 1200 Baud 00000111 0x07 2400 Baud 4800 9600 19200 Baud Baud Baud Baud Baud Baud Bit 7 0 CONF_CH1_CH2 Set the response delay time in characters that represents the number of pauses of 6 characters each to be entered between the end of the Rx message and the start of the Tx message Default value 0 Configuration of Channels 1 and 2 40054 R W Bit 15 Channel 1 Activation 0 Channel 1 is not active 1 Channel 1 is active Bit 14 Channel 2 Activation 0 Channel 2 is not active 1 Channel2 is active Bit 13 Type of returned Data Item Channels 1 and 2 0 Measurementin C 1 Measurementin mV CHAN5_FLOAT_L Measurement of channel 5 in floating point see 40020 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 5 in C or voltage in mV LSW of the float CHAN6_FLOAT_H Measurement of channel 6 in floating point see 40021 bit 15 of AUX SETTINGS register 40058
12. 8TC dispone di registri MODBUS a 16 bits words accessibili tramite comunicazione seriale RS485 o RS232 Nei prossimi paragrafi si descrivono i comandi MODBUS supportati e le funzionalit esprimibili dai vari registri Comandi MODBUS supportati Descrizione Lettura di registri a word fino a 32 per volta Lettura di registri a word fino a 32 per volta 06 Write Single Register Scrittura di un registro a word 16 Write Multiple Registers Scrittura di registri a word fino a 32 per volta Le due funzioni hanno lo stesso effetto Codice Funzione 03 Read Holding Registers 04 Read Input Registers Holding Registers registri Holding Registers a 16 bits hanno la seguente struttura Bit pi i Bit meno significativo Indice Bit significativo Vv y Vv 15 14 13 12 14 10 9 8 7 6 5 4 3 2 1 0 Word 16 bits Registro MODBUS La notazione Bit x y riportata in tabella indica tutti i bit dal x a y Ad esempio Bit 2 1 indica il bit 2 e il bit 1 e serve ad illustrare il significato delle varie combinazioni congiunte di valori dei due bit Da ricordare che sui seguenti registri possono essere eseguite le funzioni MODBUS 3 4 6 e 16 di lettura e scrittura singola e multipla valori contrassegnati con il simbolo sono quelli di default REGISTRO Descrizione IND R W MACHINE ID La parte alta del registro contiene l ID del 40001 R modul
13. GLISH 14 16 ARRE SENECA s r l j KNet Via Germania 34 35127 Z I CAMIN PADOVA ITALY 1S09001 2000 Tel 39 049 8705355 8705359 Fax 39 049 8706287 e mail info seneca it www seneca it MI001230 E ENGLISH 16 16
14. I001230 1 ITALIANO 2 16 Norme di installazione Il modulo progettato per essere montato su guida DIN 46277 in posizione verticale Per un funzionamento ed una durata ottimale necessario assicurare una adeguata ventilazione al ai moduli evitando di posizionare canaline o altri oggetti che occludano le feritoie di ventilazione Evitare il montaggio dei moduli sopra ad apparecchiature che generano calore consigliabile il montaggio nella parte bassa del quadro Collegamenti Elettrici PORTA SERIALE RS485 E ALIMENTAZIONE I collegamenti elettrici relativi al bus RS485 e all alimentazione sono disponibili esclusivamente utilizzando il bus per guida DIN Seneca collegamenti del connettore del bus per guida DIN sono visibili nella figura seguente RS485 GND RS485 A Power Supply AC Power Supply AC PORTA SERIALE RS232 Il cavo di connessione DB9 Jack stereo 3 5 mm pu essere assemblato come indicato nella figura seguente oppure acquistato come accessorio Si evidenzia inoltre che il GND della RS232 il medesimo della RS485 SENECA M1001230 I ITALIANO 3 16 INGRESSI Il modulo accetta in ingresso termocoppie di tipo J K E N S R B T Per i collegamenti elettrici si raccomanda l utilizzo di cavo schermato TC1 TC2 TC3 TC4 0 aaa Meee 2 4 12 3 4 5 6 7 8 TC5 TC6 TC7 TC8 AN A Parra er ee ZA 9 10 11 12 13 14 15 16 Le coppie di canali facenti parte dello
15. N5_6 Cold Junction Temperature of channels 5 and 6 40030 Bit 12 Cold junction Compensation Channels 1 and 2 0 not active 1 active Bit 15 0 Cold junction temperature of channels 5 and 6 in tenths of C Bit 11 Rejection to mains frequency Channels 1 and 2 0 50 Hz 1 60 Hz SENECA MI001230 E ENGLISH 15 16 Value loaded in case of fault on channel 1 40059 R W expressed as 40003 Default 2000 0 Value loaded in case of fault on channel 2 40060 R W expressed as 40004 Default 2000 0 Value loaded in case of fault on channel 3 40061 R W expressed as 40005 Default 2000 0 Value loaded in case of fault on channel 4 40062 R W expressed as 40006 Default 2000 0 Value loaded in case of fault on channel 5 40063 R W expressed as 40007 Default 2000 0 Value loaded in case of fault on channel 6 40064 R W expressed as 40008 Default 2000 0 Value loaded in case of fault on channel 7 40065 R W expressed as 40009 Default 2000 0 Value loaded in case of fault on channel 8 40066 R W expressed as 40010 Default 2000 0 VAL_FAULT_1 VAL_FAULT_2 VAL_FAULT_3 VAL_FAULT_4 VAL_FAULT_5 VAL_FAULT_6 VAL_FAULT_7 VAL_FAULT_8 TABLE THERMOCOUPLE TYPE FOR THE SETTING OF REGISTERS 40054 40057 THERMOCOUPLE TYPE THERMOCOUPLE T
16. O _DEC_IN3 4 Misura temperatura giunto freddo canali3e4 40029 Bit 15 0 Temperatura in decimi di C del giunto freddo relativo ai canali 3 e 4 GIUNTO_DEC_IN5 6 Misura temperatura giunto freddo canali5e6 40030 Bit 12 Compensazione Giunto Freddo Canale 1 e Canale 2 0 nonattiva 1 attiva Bit 10 1 Guasto alla TC collegata al canale 2 Bit 9 1 Guasto alla TC collegata al canale 3 Bit 8 1 Guasto alla TC collegata al canale 4 Bit 7 1 Guasto alla TC collegata al canale 5 Bit 6 1 Guasto alla TC collegata al canale 6 Bit 5 1 Guasto alla TC collegata al canale 7 Bit 4 1 Guasto alla TC collegata al canale 8 Bit 3 1 Errore Comunicazione con i canali 1 e 2 Bit 2 1 Errore Comunicazione con i canali 3 e 4 Bit 1 1 Errore Comunicazione con i canali 5 e 6 Bit 0 1 Errore Comunicazione con i canali 7 e 8 CHAN1_DEC Misura canale 1 in decimi di C o decine 40003 R di uV Bit 15 0 Temperatura in decimi di C del canale 1 o tensione in decine di uV CHAN2_DEC Misura canale 2 in decimi di C o decine 40004 R di uV Bit 15 0 Temperatura in decimi di C del canale 2 o tensione in decine di uV CHAN3_DEC Misura canale 3 in decimi di C o decine 40005 R diuV Bit 15 0 Temperatura in decimi di C del canale 3 o tensione in decine di uV CHAN4_DEC Misura canale 4 in decimi di C o decine 40006 R diuV Bit 15 0 Temperatura in decimi di C del canale 4 o tensio
17. YPE 17 6 5 4 TC for Channels 1 3 5 or 7 3 2 1 0 TC for Channels 2 4 6 or 8 Goo Wed _ OO OO 6g The value is memorized in EEPROM memory The effect is at the reset hardware or software of the module The value in registers 40059 40066 is copied respectively in registers 40003 40010 when the corresponding bit in register 40058 is 0 The same value is converted in floating point and copied on the corresponding floating register Disposal of Electrical amp Electronic Equipment Applicable throughout the European Union and other European countries with separate collection programs This symbol found on your product or on its packaging indicates that this product should not be treated as household waste when you wish to dispose ofit Instead it should be handed over to an applicable collection point for the recycling of electrical and electronic equipment By ensuring this product is disposed of correctly you will help prevent potential negative consequences to the environment and human health which could otherwise be caused by inappropriate disposal of this product The recycling of materials will help to conserve HE Natural resources For more detailed information about the recycling of this product please contact your local city office waste disposal service or the retail store where you purchased this product SENECA MI001230 E ENGLISH 12 16 SENECA MI001230 E EN
18. abling Both channels are enabled Type of returned Data C Cold junction Compensation Active Rejection 50 Hz ADC Filter ADC 15 bit Filter average Thermocouple Type J for both channels FILTER SETTING The filtering methods can be set for each pair of channels The filter consists of two independent low pass filters FIR Filter in running average able to increase the rejection of disturbances to the mains power line frequency and to reduce measuring noise IIR exponential Filter with programmable time constant able to dampen fluctuations If an input variation higher than the threshold T is detected both filters are forced to adapt rapidly to the new value stabilising it only later on The value of the threshold in voltage is fixed and equal to 0 75 mV The filter is set with the three least significant bits of registers MODBUS 40054 57 refer to section MODBUS REGISTERS The following is a table containing all settable filter types The propagation time 90 is indicated for each filter i e the maximum time between the step variation of the input and the variation of the number which represents it in the Modbus register including the interrogation time of the single register at 115 kbaud The times indicated are valid if both the following conditions are respected Rejection set to 50 Hz For 60 Hz rejection divide the times by 1 2 Only one of the two thermocouples of the same group is enabled If b
19. del float CHAN5_FLOAT_H Misura canale 5 in floating point vedi bit 15 40019 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 5 MSW del float SENECA M1001230 I ITALIANO 11 16 GIUNTO_DEC_IN7_8 Misuratemperatura giunto freddo canali7e8 40031 R Bit 15 0 Temperatura in decimi di C del giunto freddo relativo ai canali 7 e 8 ERR_CH1 2_CH3 4 ErroriCanali1 2 MSB Canali 3 4 LSB 40037 R Bit 15 1 Errore tensione alimentazione canale 1 e 2 Bit 14 1 Errore di ricezione canali 1 e 2 Bit 13 1 Errore salvataggio EEPROM canali 1 e 2 Bit 12 1 Salvataggio EEPROM bloccato canali 1 e 2 Bit 11 9 Riservati Bit 8 1 Errore lettura CRC EEPROM canali 1 e 2 Bit 7 1 Errore tensione alimentazione canali 3 e 4 Bit 6 1 Errore di ricezione canali 3 e 4 Bit 5 1 Errore salvataggio EEPROM canali 3 e 4 Bit 4 1 Salvataggio EEPROM bloccato canali 3 e 4 Bit 3 1 Riservati Bit 0 1 Errore lettura CRC EEPROM canali 3 e 4 ERR_CH5 6_CH7 8 Errori Canali 5 6 MSB Canali 7 8 LSB 40038 R Bit 15 1 Errore tensione alimentazione canale 5 e 6 Bit 14 1 Errore di ricezione canali 5 e 6 Bit 13 1 Errore salvataggio EEPROM canali 5 e 6 Bit 12 1 Salvataggio EEPROM bloccato canali 5 e 6 Bit 11 9 Riservati Bit 8 1 Errore lettura CRC EEPROM canali 5 e 6 Bit 7 1 Errore tensione alimentazione canali 7 e 8
20. ectric connections for power supply and RS485 bus can be made only by using the bus forthe Seneca DIN rail The connections of the bus connector are described on the following figure Power Supply AC RS485 GND RS485 A Power Supply AC RS232 SERIAL PORT Connection cable DB9 with a 3 5 mm stereo Jack can be assembled as indicated in the following figure orcan be bought as an accessory We advise you that the GND of the RS232 is the same of RS485 SENECA MI001230 E ENGLISH 3 16 INPUTS The module accepts at input the following types of thermocouples J K E N S R B T For the electrical connections we advise you to use screened cables TC1 TC2 TC3 TC4 0 aaa Meee 2 4 12 3 4 5 6 7 8 TC5 TC6 TC7 TC8 AN A para er 4 ZA 9 10 11 12 13 14 15 16 The pairs of channels belonging to the same group of terminals have the GND terminal internally connected and are not insulated each other Instead a 1 5 kV insulation is present among the input channels belonging to different groups of terminals Indications by LED on the frontal panel PWR LED GREEN Steady Power Supply is present ERR LED YELLOW Meanng Steady Fault insufficient power supply faulty channel faulty TC internal communication error signalled if the channel has been activated RX LED RED Steady Data are being received through the RS485 communication port MI001230 E ENGLISH 4 16 SENECA
21. if not authorized Contents of the present documentation refers to products and technologies described in it All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision SENECA s r l et Via Germania 34 35127 Z I CAMIN PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 I509001 2000 e mail info seneca it www seneca it SENECA MI001230 E ENGLISH 8 16 MODBUS REGISTERS Z 8TC has MODBUS 16 bits words registers accessible by RS485 or RS232 serial communication In the next paragraphs we shall describe the supported MODBUS commands and the functions of the registers Supported MODBUS Commands Code Function Description 03 Read Holding Registers Reading of word registers up to 32 at a time 04 Read Input Registers Reading of word registers up to 32 at a time 06 Write Single Register Writing of a word register 16 Write Multiple Registers Writing of word registers up to 32 at a time The two functions have the same effect Holding Registers The 16 bit Holding Registers have the following structure Most Significant Bit Bit Index Vv y Vv Least 15 14 13 12 14 10 9 8 7 6 5 4 3 2 1 0 E i Word 16 bits MODBUS Register Significant Bit In the table the notation Bit x y indicates all bits from x t
22. lore di temperatura tensione congelato all ultimo valore acquisito prima della segnalazione di fault Bit 6 Azione in caso di faultcanale 2 Come Bit 7 Bit 5 Azione in caso di faultcanale 3 Come Bit 7 Bit 4 Azione in caso di faultcanale 4 Come Bit 7 Bit 3 Azione in caso di faultcanale 5 Come Bit 7 Bit 2 Azione in caso di faultcanale 6 Come Bit 7 Bit 1 Azione in caso di fault canale 7 Come Bit 7 SENECA M1001230 I ITALIANO 15 16 Bit 0 Azione in caso di fault canale 8 Come Bit 7 Bit 15 8 Impostano l indirizzo del modulo Valori ammissibili da 0x00 a OxFF valori decimali nell intervallo 0 255 Default 1 Bit 7 0 Impostano il tipo di controllo sulla parit 00000000 nessuna parit NONE 00000001 parit pari EVEN 00000010 parit dispari ODD VAL_FAULT_1 Valore caricato in caso di fault canale 1 40059 R W espresso come 40003 Default 2000 0 Valore caricato in caso di fault _canale_2 40060 R W VAL_FAULT_2 espresso come 40004 Default 2000 0 Valore caricato in caso di fault canale 3 40061 R W espresso come 40005 Default 2000 0 VAL_FAULT_3 BAUDR Registro per l impostazione del baudrate e del tempo di ritardo della risposta 40053 R W Valore caricato in caso di fault canale 4 40062 R W VAL_FAULT_4 c espresso come 40006 Default 2000 0
23. n Storage temperature Signalling by LED Connections Removable 4 way screw terminals max 1 5 mm 3 5mm pitch Rear IDC10 connector for DIN rail 3 5 mm stereophonic front jack for RS232 COM connection Box PBT black Dimensions and weight 100 x 112 x 17 5 mm 140 g Standards EN61000 6 4 2002 electromagnetic emission industrial environment EN61000 6 2 2005 electromagnetic immunity industrial environment EN61010 1 2001 safety All circuits must be insulated from the other circuits under dangerous voltage with double insulation The power supply transformer must comply with EN60742 Insulated transformers and safety transformers The values are valid at the set rejection frequency with the filter ON For disturbance values such as the input signal peak does not exceed the limit of acceptability Up to 250 C the input is considered equivalent to a null temperature SENECA MI001230 E ENGLISH 2 16 Installation rules The module is designed to be installed in vertical position on a DIN 46277 rail In order to ensure optimum performance and the longest working life the module s must be supplied adequate ventilation and no raceways or other objects that obstruct the ventilation slots Never install modules above sources of heat we recommend installation in the lower part of the control panel Electric Connections POWER SUPPLY AND RS485 COMMUNICATION PORT The el
24. ne in decine di uV CHAN5_DEC Misura canale 5 in decimi di C o decine 40007 R diuV Bit 15 0 Temperatura in decimi di C del canale 5 o tensione in decine di uV CHAN6_DEC Misura canale 6 in decimi di C o decine 40008 R diuV Bit 15 0 Temperatura in decimi di C del canale 6 o tensione in decine di uV CHAN7_DEC Misura canale 7 in decimi di C o decine 40009 R diuV Bit 15 0 Temperatura in decimi di C del canale 7 o tensione in decine di uV Bit 15 0 Temperatura in decimi di C del giunto freddo relativo ai canali 5 e 6 MI001230 1 ITALIANO 10 16 SENECA SENECA M1001230 I ITALIANO 12 16 Bit 11 Frequenza Reiezione Canale 1 e Canale 2 0 50Hz 1 60 Hz SENECA M1001230 I ITALIANO 14 16 TABELLA TIPO TERMOCOPPIA PER IMPOSTAZIONE REGISTRI 40054 40057 TIPO TERMOCOPPIA BIT TIPO TERMOCOPPIA 1716 5 4 TC per Canali 1 3 507 3 2 1 0 TC per Canali 2 4 608 lo o o jo TCO __ _ Jo o e o TCJ Non implementate Non implementate valore conservato in EEPROM effetto si ha al riavvio hardware o software dello strumento 11 valore nei registri 40059 40066 viene ricopiato rispettivamente nei registri 40003 40010 quando il bit corrispondente del registro 40058 sia a 0 Lo stesso valore viene convertito in floating point e ricopiato nel registro float relativo al canale Smaltimento dei rifiuti elettrici ed elet
25. ne programmate come segue Indirizzo 001 VELOCITA 38400 Baud PARITA nessuna NUMERO BIT 8 STOP BIT 1 La programmazione del modulo pu essere effettuata anche attraverso il connettore frontale COM facendo attenzione ad impostare i seguenti parametri per il collegamento Indirizzo 001 Velocit 2400 Baud PARITA nessuna STOP BIT 1 La porta di comunicazione COM si comporta esattamente come quella del bus RS485 eccetto che per i parametri di comunicazione come gi descritto Inoltre ha priorit sulla porta RS485 e viene chiusa dopo 3 s di inattivit Pannello Frontale e Posizione Led 1234 5 6 7 8 Errore Presenza alimentazione ERR PWR Ricezione RS485 O O Trasmissione RS485 COM O Z 8TC 9 101112 13 14 15 16 SENECA MI001230 1 ITALIANO 7 16 Dimensioni e Ingombri 17 5mm Questo documento di propriet SENECA srl La duplicazione e la riproduzione sono vietate se non autorizzate Il contenuto della presente documentazione corrisponde ai prodotti e alle tecnologie descritte dati riportati potranno essere modificati o integrati per esigenze tecniche e o commerciali Il contenuto della presente SENECA s r l Via Germania 34 35127 Z I CAMIN PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 I509001 2000 e mail info seneca it www seneca it SENECA M1001230 I ITALIANO 8 16 REGISTRI MODBUS Il modulo Z
26. o 24 Bit 15 8 La parte bassa la revisione firmware Bit 7 0 STATUS_INP Stato dei canali d ingresso 40002 R Bit 15 1 Guasto ai canali 1 e 2 Bit 14 1 Guasto ai canali 3 e 4 Bit 13 1 Guasto ai canali 5 e 6 Bit 12 1 Guasto ai canali 7 e 8 Bit 11 1 Guasto alla TC collegata al canale 1 SENECA MI001230 1 ITALIANO 9 16 Filtro Canali 1 e 2 per dettagli fare riferimento alla sezione IMPOSTAZIONE FILTRO 000 Non inserito 001 Filtro in media Altre impostazioni in IMPOSTAZIONE FILTRO Bit 10 8 Bit 7 4 Tipo Termocoppia Canale 1 vedere Tabella TIPO TERMOCOPPIA Default Tipo J Bit 3 0 Tipo Termocoppia Canale 2 vedere Tabella TIPO TERMOCOPPIA Default Tipo J 40055 R W CONF_CH3_CH4 Configurazione Canali3e4 Bit 15 0 Registro per la configurazione dei canali 3 e 4 Vedere il registro 40054 tenendo conto che in questo caso non si fa riferimento ai canali 1e 2 ma rispettivamente ai canali 3 e 4 40056 R W CONF_CH5_CH6 Configurazione Canali5e6 CHAN8_DEC Misura canale 8 in decimi di C o decine 40010 di uV Bit 15 0 Temperatura in decimi di C del canale 8 o ten
27. o different groups of terminals The instrument is therefore characterized by a six points global insulation Furthermore the module has e Facilitated wiring of power supply and serial bus by means of the bus housed in the DIN rail e Communication can be configured by DIP switch or software e RS485 serial communication with MODBUS RTU protocol 32 nodes maximum e Inputs protected against ESD discharges up to 4 kV e High acquisition speed e Measurement of thermocouples J K E N S R B T e Measurement of the inputs available in the following formats floating point representation reverse floating point fixed dot at 16 bits in tenths degrees with sign fortemperature tenths of uV for voltage e Channels independently activable e Programmable value in case of fault or freezing of last reading For each pair of inputs belonging to the same group of terminals the following common settings are possible e Measurement in temperature or mV Filter programmable at eight levels to stabilise reading e Rejection programmable at 50 Hz or 60 Hz Three selectable acquisition speeds two at 14 bits one at 15 bits e Cold Junction Compensation Technical Specifications Power Supply Consumption 10 40 Vdc or 19 28 Vac 50 60 Hz max 0 6 W RS485 1200 115200 Baud RS232 2400 Baud Address 1 Parity NO Data bits 8 Stop bits 1 Serial Communication Ports Protocol MODBUS RTU Inputs
28. o y For example Bit 2 1 indicates bit 2 and bit 1 and serves to illustrate the meaning of the various united combinations of the values of the two bits Remember that MODBUS functions 3 4 6 and 16 of single or multiple writing and reading can be executed in the following registers Default values are indicated with the symbol REGISTER Description ADD R W MACHINE ID Bit 15 8 contain the module s ID 24 40001 R Bit 7 0 contain the firmware s revision STATUS_INP Status of input channels 40002 R Bit 15 1 Fault on channels 1 and 2 Bit 14 1 Fault on channels 3 and 4 Bit 13 1 Fault on channels 5 and 6 Bit 12 1 Fault on channels 7 and 8 Bit 11 1 Fault on the TC connected to channel 1 SENECA MI001230 E ENGLISH 9 16 Bit 10 1 Fault on the TC connected to channel 2 Bit 9 1 Fault on the TC connected to channel 3 Bit 8 1 Fault on the TC connected to channel 4 Bit 7 1 Fault on the TC connected to channel 5 Bit 6 1 Fault on the TC connected to channel 6 Bit 5 1 Fault on the TC connected to channel 7 Bit 4 1 Fault on the TC connected to channel 8 Bit 3 1 Communication Error with channels 1 and 2 Bit 2 1 Communication Error with channels 3 and 4 Bit 1 1 Communication Error with channels 5 and 6 Bit 0 1 Communication Er
29. oth thermocouples are enabled the propagation times approximately are doubled FILTER SAMPLING PROP TIME 90 Bits ADC 000 48 010 141__ Average exp 8s 179ms 110 11 179 ms 11 179 ms 110 1 Default Value SENECA 14 20 010 1 1 11 1 11 1 1 5 5 5 5 5 5 MI001230 E ENGLISH 6 16 Programming For the product s programming and or configuration tools consult the website www seneca it During initial programming the EEPROM SW3 8 in OFF position default setting values originally programmed as follows can be used Address 1 SPEED 38400 baud PARITY none BIT NUMBER 8 STOP BIT 1 The module can also be programmed through the front connector COM while paying attention to set the following connection parameters Address 1 Speed 2400 Baud PARITY none STOP BIT 1 The COM communication port behaves in the same way as the RS485 bus port except for the communication parameters described above It also has priority over the RS485 serial port and closes after 3 seconds of inactivity Frontal Panel and Led Position 123 4 5 6 7 8 Error Presence of Power Suppl ERR PWR RS485 Data Receiving OO RS485 Data Transmission RX TX COM O Z 8TC 9 101112 13 14 15 16 SENECA MI001230 E ENGLISH 7 16 Dimensions and Overall dimensions 17 5mm This documentis property of SENECA srl Duplication and reprodution are forbidden
30. pidamente al nuovo valore per intervenire solo successivamente a stabilizzarlo Il valore della soglia fisso in tensione e pari a circa 0 75 mV Il filtro viene impostato tramite i tre bit meno significativi dei registri MODBUS 40054 57 fare riferimento alla sezione REGISTRI MODBUS Di seguito si riporta una tabella con tutti i tipi di filtraggio impostabili Per ciascuno di questi viene inoltre riportato il tempo di propagazione 90 cio il tempo massimo che trascorre tra la variazione a gradino dell ingresso e la variazione del numero che la rappresenta nel registro Modbus compreso il tempo di interrogazione del singolo registro a 115 kbaud tempi riportati in tabella valgono se sono rispettate entrambe le seguenti condizioni Reiezione a 50 Hz Se a 60 Hz dividere i tempi riportati per 1 2 Abilitazione di una sola delle due termocoppie del gruppo Se entrambe le termocoppie sono abilitate itempi con buona approssimazione raddoppiano TEMPO PROP 90 BitADC Hz TIPO lt s gt s 000 14 48 Nonpresentel 45ms 45ms Media exp 8s 179ms 179 ms 179 ms Valore di default 15 15 10 15 Ea i cl 945 il SSHECA M1001230 I ITALIANO 6 16 Programmazione Per i tool di programmazione e o configurazione del prodotto consultare il sito www seneca it Durante la prima programmazione possibile utilizzare le impostazioni di default da EEPROM SW1 3 8 in posizione OFF che sono all origi
31. rammabile a 50 Hz o 60 Hz Tre diverse velocit di acquisizione selezionabili due a 14 bit una a 15 bit Compensazione giunto freddo Caratteristiche Tecniche Alimentazione 10 40 Vdc o 19 28 Vac 50 60 Hz Consumo max 0 6 W Porte di Comunicazione Seriale RS485 1200 115200 Baud RS232 2400 Baud Indirizzo 01 Parit NO Dati 8 bit Stop bit 1 Protocollo MODBUS RTU Ingressi Ingresso Termocoppia di tipo J K E N S R B T Tabelle EN60584 1 ITS 90 Range di temperatura Dipendente dal tipo di termocoppia vedere Tabella Range Termocoppie Span mV 10 1 81 4 mV Impedenza 10 MQ Errore complessivo ADC 14 bit e Reiez 50 Hz 0 040 13 uV ADC 15 bite Reiez 50 Hz 0 035 10 uV ADC 14 bit e Reiez 60 Hz 0 045 16 uV ADC 15 bite Reiez 60 Hz 0 040 12 uV SENECA MI001230 1 ITALIANO 1 16 a Test lt 50 nA CMRR gt 155 dB porta in prova verso tutte le altre a GND DMRR 2 gt 60 dB RANGE TERMOCOPPIE Ammesso Linearizzazione Ammesso A Il J 210 1200 C 0 05 C Linearizzezione 50 1768 C 0 02 C kK 200 1372 c 005 C R 50 1768 C 0 02 C 200 1000 C __0 02 c__ B 250 1820 c 0 03 C 200 1300 C 0 04 C 200 400 C 0 04 C Altre Caratteristiche ADC Impostabile a 14 o 15 bit Deriva Termica lt 100 ppm K Reiezione ai disturbi Impostabile a 50 Hz o a 6
32. ror with channels 7 and 8 CHAN1_TEN Channel 1 measurement tenths of C or 40003 R tenths of uV Bit 15 0 Temperature of channel 1 in tenths of C or voltage in tenths of uV CHAN2_TEN Channel 2 measurement tenths of C or 40004 R tenths of uV Bit 15 0 Temperature of channel 2 in tenths of C or voltage in tenths of uV CHAN3_TEN Channel 3 measurement tenths of C or 40005 R tenths of uV Bit 15 0 Temperature of channel 3 in tenths of C or voltage in tenths of uV CHAN4_TEN Channel 4 measurement tenths of C or 40006 R tenths of uV Bit 15 0 Temperature of channel 4 in tenths of C or voltage in tenths of uV CHAN5_TEN Channel 5 measurement tenths of C or 40007 R tenths of uV Bit 15 0 Temperature of channel 5 in tenths of C or voltage in tenths of uV CHAN6_TEN Channel 6 measurement tenths of C or 40008 R tenths of uV Bit 15 0 Temperature of channel 6 in tenths of C or voltage in tenths of uV CHAN7_TEN Channel 7 measurement tenths of C or 40009 R tenths of uV Bit 15 0 Temperature of channel 7 in tenths of C or voltage in tenths of uV MI001230 E SENECA ENGLISH 10 16 Filter of channels 1 and 2 for details refer to the FILTER SETTING section 000 Not present 001 Average filter Other settings in FILTER SETTING Bit 10 8
33. sione in decine di uV CHAN1_FLOAT_H Misura canale 1 in floating point vedi bit 15 40011 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 1 MSW del float CHAN1_FLOAT_L Misura canale 1 in floating point vedi bit 15 40012 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 1 LSW del float CHAN2_FLOAT_H Misura canale 2 in floating point vedi bit 15 40013 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 2 MSW del float CHAN2_FLOAT_L Misura canale 2 in floating point vedi bit 15 40014 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 2 LSW del float CHAN3_FLOAT_H Misura canale 3 in floating point vedi bit 15 40015 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 3 MSW del float CHAN3_FLOAT_L Misura canale 3 in floating point vedi bit 15 40016 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 3 LSW del float CHAN4_FLOAT_H Misura canale 4 in floating point vedi bit 15 40017 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 4 MSW del float CHAN4_FLOAT_L Misura canale 4 in floating point vedi bit 15 40018 registro 40058 AUX SETTINGS Bit 15 0 Temperatura in C o tensione in mV del canale 4 LSW
34. stesso gruppo di morsetti hanno il terminale di massa internamente connesso e non sono isolati tra loro E invece garantito un isolamento pari a 1 5 kV tra canali relativi a gruppi di morsetti diversi Indicazioni tramite LED sul frontale LED PWR VERDE Significato Indica la presenza dell alimentazione LED ERR GIALLO Significato Acceso Guasto alimentazione insufficiente canale guasto TC guasta errore di comunicazione interna segnalati se il canale corrispondente attivato LED RX ROSSO Significato Indica la ricezione di dati sulla porta di comunicazione RS485 SENECA M1001230 I ITALIANO 4 16 LED TX ROSSO Indica la trasmissione di dati sulla porta di comunicazione RS485 Interfaccia Seriale Per informazioni dettagliate sull interfaccia seriale RS485 fare riferimento alla documentazione presente nel sito www seneca it nella sezione Prodotti Serie Z PC MODBUS TUTORIAL IMPOSTAZIONE DEI DIP SWITCH Configurazione di Fabbrica Lo strumento esce dalla fabbrica configurato con tutti i DIP switch in posizione 0 La posizione dei dip switch definisce i parametri di comunicazione del modulo indirizzo e velocit In tutte le tabelle seguenti l indicazione corrisponde a DIP switch in 1 ON nessuna indicazione corrisponde a DIP switch in 0 OFF VELOCIT swill ooo O O 9600 Baud j 19200 Baud 38400 Baud 57600 Baud W1 ies lafsfe zls y y O Parame
35. tri di comunicazione da EEPROM _ e Indirizzo fisso01 SSS i aoaea I eje Indirizzo fisso 03 fel Indirizzo fisso04 _ ____________ LX X X X X _Indirizzo fisso come da rappresentazione binaria jejejejeje Indirizzo fisso 63 an swi o Non usato S O Lasciare in posizione OFF TERMINAZIONE RS485 I Nessuna Terminazione di linea Terminatoredilineainserito La configurazione di default la seguente Indirizzo 1 38400 no parity 1 bit di stop SENECA M1001230 I ITALIANO 5 16 IMPOSTAZIONE DI DEFAULT CANALI INGRESSO La configurazione di default valida per ciascuna coppia di canali relativi allo stesso gruppo di morsetti la seguente Abilitazione Entrambi i canali abilitati Dato restituito C Compensazione giunto freddo Attiva Reizione 50 Hz ADC Filtro ADC 15 bit con filtro in media Tipo Termocoppia J per entrambi i canali IMPOSTAZIONE FILTRO Per ogni gruppo di canali possibile impostare le modalit di filtratura Il filtro composto da due filtri passa basso indipendenti Filtro FIR in media mobile in grado di aumentare la reiezione ai disturbi alla frequenza di rete e di ridurre il rumore di misura Filtro IIR esponenziale con costante di tempo programmabile in grado di smorzare le fluttuazioni Se viene rilevata una variazione dell ingresso superiore alla soglia S entrambi i filtri vengono forzati ad adeguarsi ra
36. tronici applicabile nell Unione Europea e negli altri paesi con servizio di raccolta differenziata Il simbolo presente sul prodotto o sulla sua confezione indica che il prodotto non verr trattato come rifiuto domestico Sar invece consegnato al centro di raccolta autorizzato per il riciclo dei rifiuti elettrici ed elettronici Assicurandovi che il prodotta venga smaltito in modo adeguato eviterete un potenziale impatto negativo sull ambiente e la salute umana che potrebbe essere causato da una gestione non conforme dello smaltimento del prodotto Il riciclaggio dei materiali contribuir alla conservazione delle risorse naturali Per ricevere ulteriori informazioni pi dettagliate Vi invitiamo a contattare l ufficio preposto nella Vostra citt il servizio per lo smaltimento dei rifiuti o il fornitore da cui avete acquistato il prodotto SENECA s r l KNet Via Germania 34 35127 Z I CAMIN PADOVA ITALY ISO9001 2000 Tel 39 049 8705355 8705359 Fax 39 049 8706287 e mail info seneca it www seneca it M1001230 I ITALIANO 16 16 CONVERTER FOR THERMOCOUPLES Z 8TC WITH 6 POINT INSULATION General Description __ na The Z 8TC instrument is a digital converter for thermocouples with eight measuring channels which are insulated from the power supply and from the serial communication line up to 1 5 KV The same 1 5 kV insulation is present among the input channels belonging t
37. ure of channel 1 in C or voltage in mV LSW ofthe float CHAN2_FLOAT_H Measurement of channel 2 in floating point see 40013 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 2 in C or voltage in mV MSW ofthe float CHAN2_FLOAT_L Measurement of channel 2 in floating point see 40014 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 2 in C or voltage in mV LSW of the float CHAN3_FLOAT_H Measurement of channel 3 in floating point see 40015 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 3 in C or voltage in mV MSW of the float CHAN3_FLOAT_L Measurement of channel 3 in floating point see 40016 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 3 in C or voltage in mV LSW of the float CHAN4_FLOAT_H Measurement of channel 4 in floating point see 40017 bit 15 of AUX_SETTINGS register 40058 Bit 15 0 Temperature of channel 4 in C or voltage in mV MSW of the float CHAN4_FLOAT_L Measurement of channel4 in floating point see 40018 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 4 in C or voltage in mV LSW ofthe float CHAN5_FLOAT_H Measurement of channel 5 in floating point see 40019 bit 15 of AUX SETTINGS register 40058 Bit 15 0 Temperature of channel 5 in C or voltage in mV MSW ofthe float
38. xCCCC to reset the module Additional Configuration Register 40058 R W AUX SETTINGS Bit 15 Floating point interpretation 0 The high word of floating point is transmitted first then the low word 1 The low word of floating point is transmitted first then the high word Bit 14 8 Reserved and not modifiable Bit 7 Action in case of fault on channel 1 0 The temperature voltage value is forced to the programmed fault value 1 The temperature voltage value is frozen at the last acquired value before fault is signalled Bit 6 Action in case of fault on channel 2 As Bit 7 Bit 5 Action in case of fault on channel 3 As Bit 7 Bit 4 Action in case of fault on channel 4 As Bit 7 Bit 3 Action in case of fault on channel 5 As Bit 7 Bit 2 Action in case of fault on channel 6 As Bit 7 Bit 1 Action in case of fault on channel 7 As Bit 7 Bit 0 Action in case of fault on channel 8 As Bit 7 SENECA MI001230 E ENGLISH 11 16 SENECA MI001230 E ENGLISH 13 16 ADDR 6 7 Register for the setting of the module s address and parity control 40052 R W Bit 15 8 Set the module s address Permissible values from 0x00 to OxFF decimal values in the interval of 0 255 Default address 1 Bit 7 0 Set the type of parity control 00000000 No parity NONE Default 0000000

Download Pdf Manuals

image

Related Search

Related Contents

ONKYO ABX-100 docking speaker  Model ACC34AC Signal Conditioner/Converter (AC)  User-Manual - Pdfstream.manualsonline.com  Crowcon C-Test Gas (Bump) Test and Calibration Station  User Manual - Xsquare 2.2  1 > 31 mars 2012  Bedienungsanleitung Instruction Manual KG 220.4 A++ N  Bedienungsanweisung Emissions-Analyse  Samsung AR09HSFNCWKN Наръчник за потребителя  B&B Electronics EIR-M-SC network media converter  