1. required To incorporate an easily accessible means of disconnecting from the mains supply Upon replacing the mains fuse make sure one of the same rating is used and with the power supply disconnected from the mains To provide the equipment with a protective enclosure in compliance with the Electrical Safety Regulations and Directives in the country where it is installed To use a mains connection cable with a cross section of at least Oo N 3 OPCIONES Regleta de bornes Conector DIN41612 H15 Regleta de faston OPTIONS C digo de pedido ECS 100 5XXX A ECS 100 5XXX B ECS 100 5XXX C Ordering code ECS 100 5XXX A ECS 100 5XXX B ECS 100 5XXX C Ternimal blocks Connector DIN41612 H15 Faston strip FRONTAL 3U 9TE para rack 19 NP 9197 BASE DE MONTAJE NP 9124 CLIP CARRIL DIN NP 9135 ACCESSORIES Ordering code Rack 19 FRONT PLATE 3U 9TE NP 9197 MOUNTIN BASE NP 9124 DIN RAIL CLIP NP 9135 3 4 15 02 2012 9502 113 7 CA 343 7 P SISTEMA DE ALIMENTACI N ININTERRUMPIDA CC 100W ECS 100 100W DC UNINTERRUPTIBLE POWER SUPPLY DECLARACI N DE CONFORMIDAD CE EC DECLARATION OF CONFORMITY El abajo firmante en representaci n de The undersigned representing the following Fabricante Manufacturer PREMIUM S A Direcci n Address C Dolors Aleu 19 21 2 2 08908 L Hospitalet de Llobregat SPAIN declara que el producto herewith declares that the product Tipo Type S A I CC DC U P S Model
2. SISTEMA DE ALIMENTACION ININTERRUMPIDA CC 100W ECS 100 100W DC UNINTERRUPTIBLE POWER SUPPLY CARACTERISTICAS GENERALES GENERAL FEATURES ss To e Desconexi n de la bater a por bater a baja e Battery cut off when battery low 3 res e Carga de la bateria a corriente constante e Battery constant current charging il e Selecci n de 4 niveles de corriente de e 4 Selectable current charging levels carga e Step mains to battery without voltage e Paso de red a bater a sin caidas de tensi n dips e Alarmas independientes de fallo fuente y e Independent alarms of supply fail and bater a baja battery low e Bater a no incluida e Battery not included MODELS Battery Charging current selection Corriente Nominal Flotaci n Paro A Current Nominal Floating Cut off i p E h 5073 7 35A 13 6V 2 4A 5077 3 68A 27 2V 0 25A 1 2A 5079 1 84A 54 4V 0 11A 0 15A 0 6A 24V 20V 48V 40V MODELOS Bater a Selecci n de la corriente de carga 5173 4 8A 5177 3 68A 24V 27 2V_ OV _ 05A 06A 1 2A 24A THC 1 84A BV AAV 40V 022A 03A 0 6A 1 2A Selecci n f brica Factory setting ENTRADA NP A SALIDA RR AMBIENTE ENVIRONMENTAL __ _ 70 C Po nom 2 95 with no condensation 500 000h 40 according to IEC61709 CEM EM SEGURIDAD SAFETY Salida Tierra Output Ground 500Vac 50Hz 1 min MEC NICA MECHANICAL A 5609 PA 100 x 160 x 45 mm CONTROL CONTROL FTE Alarma FALLO FUENTE act a por SUPPLY FAIL al
3. TIBLE POWER SUPPLY CONEXIONADO CONNECTIONS REGLETA DE BORNES TERMINAL BLOCKS Max 12A Terminal 4 32 Y VI 01 Y CONECTOR CONNECTOR DIN 41612 H15 Max 12A Terminal REGLETA DE FASTON FASTON 1 4 Max 18A Terminal 32 ETET Salida Salida Bater a Bater a Fallo fuente A Fallo fuente B Output Output Battery Battery Supply fail A Supply fail B Supply fail C Battery low A Battery low B Battery low C Ground PE Neutral Line Fallo fuente C Bateria baja A Bateria baja B Bateria baja C Tierra PE Neutro Linea Cuando se produce fallo fuente o bateria baja los contactos C A se cierran y C B se abren When supply fail or battery low contacts C A are switched on and C B are switched off NP 9197 amp a A NP 9124 Se vw NP 9135 gt e 1 e d www premium es Operation without mains supply When there is no mains supply the battery comes uninterruptedly into operation and the output current is obtained from the battery The output voltage will then depend on the battery discharge curve If the battery runs flat the low battery alarm will be triggered It will be disconnected from the output by way of a relay to prevent a deep discharge of the battery When the mains supply returns the UPS may take several minutes to supply the established battery charging current During this time the battery is charged with a s
4. arm works by Fallo de red sobrecarga o aver a de la fuente Mains failure overload or power supply fault Contactos de rel Relay contacts Tensi n m xima conmutable Maximum switching voltage 20Vac 24Vdc Potencia maxima conmutable Maximum switching power OOVA 24W Alarma BATER A BAJA act a por BATTERY LOW works by Descarga cruce o envejecimiento de la bater a Discharge ageing or short circuit Valor m nimo conmutable Minimum switching value mA O 1V PROTECCIONES PROTECTIONS SEA AA Contra sobrecargas y cortocircuitos Against overloads and short circuits Limitaci n de corriente Current limiting Del a bater a contra descargas profundas Battery protection against deep discharges Desconexi n de bater a Battery cut off Corriente m xima de ruptura Maximum switching current Protecci n de la bater a contra sobrecargas Battery protection against overloads Por fusible By fuse Contra Sobre corrientes de entrada Against Input over currents Fusible de entrada Input fuse www premium es 1 4 15 02 2012 9502 113 7 CA 343 7 SISTEMA DE ALIMENTACION ININTERRUMPIDA CC 100W ECS 100 100W DC UNINTERRUPTIBLE POWER SUPPLY lo DIAGRAMA DE BLOQUES BLOCKS DIAGRAM CHARGE MAX SELECTOR SUPPLY FAIL BATTERY LOW CARACTERISTICA DE CARGA CHARGING CHARACTERISTIC Corriente de carga Charging current 50 Tensi n Voltage Volumen de carga Charged volume HOURS 5 10 15 20 25 30 35 B
5. ater a Battery Plomo Lead V Carga V Charge 2 28V cel Carga charge 0 1C Temperatura Temperature 205 NP 5073 F 6 3x32 T 12A NP 5077 F 6 3x32T 6A Vout ADJUST NP 5079 F 6 3x32 T 3A SELECTOR CORRIENTE DE CARGA CHARGING CURRENT SELECTOR Suse DIMENSIONES DIMENSIONS www premium es DESCRIPCI N Esta serie consta de 3 modelos de alimentador cargador que en presencia de la tensi n de red suministra una tensi n estabilizada y al mismo tiempo que realiza la carga controlada de la bater a Esta gama es ptima para trabajar con bater as de plomo de 12V 24V y 48V de hasta 48Ah 24Ah y 12Ah respectivamente El equipo es formado por una fuente de alimentaci n conmutada y un circuito limitador de la corriente carga que proporciona una carga de bater a a tensi n constante con la corriente limitada Tambi n incorpora una circuiter a de alarmas que act an independientemente tanto por fallo de la red o de la fuente como por bater a baja Las salidas de las alarmas son los contactos conmutados y libres de tensi n de sendos rel s Funcionamiento con la red En presencia de la tensi n de la red la corriente de salida se obtiene directamente de la fuente de alimentaci n El valor de la corriente m xima de carga de la bater a es seleccionable por el usuario mediante un DIP switch ver figura La corriente de carga de la bater a m xima ser a lo sumo igual a la seleccionada o igual a
6. harging the battery in a controlled way The range is ideal for charging lead acid batteries of 12V 24V and 48V with capacities of up to 48Ah 24Ah and 12Ah respectively The device comprises a switched mode power supply and a charging current limiter circuit which provides for constant voltage battery charging with limited charging current It also incorporates an alarm circuitry which acts independently when mains or power supply failure or a low battery condition occurs The alarm outputs are the switched potential free contacts of relays Mains operation When the mains supply is on the output current is obtained directly from the power supply The maximum battery charging current can be selected by the user by means of DIL switch see figure The maximum battery charging current will be equal to the set current or equal to the rated current less the output current the floating voltage will be equal to the output voltage The system allows the temporary supply of an output current higher than the rated current The average of this additional current which is obtained from the battery should not exceed the charging current as otherwise the battery would finally discharge If the power supply has no output due to a mains voltage outage or to a failure in the power supply the supply failure alarm will be triggered 15 02 2012 9502 113 7 CA 343 7 SISTEMA DE ALIMENTACION ININTERRUMPIDA CC 100W ECS 100 100W DC UNINTERRUP
7. la nominal menos la destinada a la salida y la tensi n de flotaci n ser igual a la tensi n de la salida El sistema permite entregar temporalmente en la salida m s corriente que la nominal La media de esta corriente extra que se obtiene de la bater a no debe superar la corriente de carga ya que de lo contrario la bater a acabar a por descargarse Si la fuente de alimentaci n no diera salida tanto si ello es debido a la ausencia de la tensi n de la red como al fallo de la propia fuente se activar a la alarma de fallo de fuente Funcionamiento en ausencia de la red Al faltar la red la bater a entra en servicio sin interrupci n y la corriente de la salida se obtiene de la bater a entonces la tensi n de salida depende de la curva de descarga de la bater a Si la bater a se agota se activa la alarma de bater a baja y sta se desconecta de la salida por medio de un rel que evitar su descarga profunda Cuando regresa la red es posible que el SAI tarde unos minutos en entregar la corriente de carga de bater a establecida Durante este tiempo la bater a se carga con una corriente peque a hasta superar el estado de bater a baja En este instante se rearma la alarma de bater a baja se cierra de nuevo el rel y la bater a se carga normalmente DESCRIPTION This series consists of three models of a power supply charger which in the presence of mains voltage supplies regulated voltage while at the same time c
8. mall current until the low battery status is overcome At that moment the low battery alarm is reset the relay closes and the battery starts to charge normally INSTALACION Realizar el conexionado segun la tabla Si se requiere una corriente de carga de bateria distinta a la establecida en fabrica se puede cambiar mediante un destornillador peque o a trav s de la ranura de la tapa ver figura Para efectuar una comprobaci n r pida del estado de la bater a se recomienda parar la fuente ya que si sta est en marcha la alarma por bater a baja no se activar Por motivos de seguridad es necesario Incorporar un medio de desconexi n de la red el ctrica f cilmente accesible Para sustituir el fusible de red hacerlo por otro del mismo calibre y tipo con la fuente desconectada de la red Proporcionar al equipo una envolvente de protecci n conforme a las directivas de seguridad el ctrica del pa s donde sea instalado Utilizar un cable de conexi n a la red el ctrica con una secci n no menor de 0 75mm INSTALLATION Make the connections according to the table If the battery charging current required is different from the factory set this can be changed using a small screwdriver through the groove on the cover see figure To make a quick check of the state of the battery we recommend stopping the power supply because if this is running the low battery alarm would not be triggered For safety reasons it is
9. os Models ECS 100 5073 5077 5079 5173 5177 5179 es conforme con las disposiciones de las siguientes directivas CE is in conformity with the provisions of the following EC directive s e 73 23 CEE Baja tension Low voltage e 89 3836 CEE Compatibilidad electromagnetica Electromagnetic compatibility e 91 263 CEE Modificaci n modification 89 336 CEE e 92 31 CEE Modificacion modification 89 336 CEE y se han aplicado las normas y o especificaciones tecnicas siguientes and that standards and or technical specifications referenced overleaf have been applied e EN 60950 2005 Seguridad Equipos de tratamiento de la informacion Safety Information technology equipment e EN 61000 6 3 2007 Norma gen rica de emisi n Generic emission standard e EN 61000 6 2 2005 Norma gen rica de inmunidad Generic Immunity standard A o en que se coloc el marcado CE 2006 Year in which the CE marking was fixed Notas Notes Para el cumplimiento de esta declaraci n el producto debe usarse s lo para el fin que ha sido concebido teniendo en cuenta las limitaciones establecidas en el manual de instrucciones For the fulfillment of this declaration the product must be used only for the aim that has been conceived considering the limitations established in the instructions manual L Hospitalet de Llobregat 15 02 2012 Jordi Gazo Director Gerente Managing Director PREMIUM S A is an ISO9001 certified company by B
10. ureau Veritas www premium es 4 4 15 02 2012 9502 113 7 CA 343 7
Download Pdf Manuals
Related Search
Related Contents
Philips Coaxial cable SWV4123S ringworld2 Sikafloor®-156 - Distribuciones Villamar Manual del usuario Termo Anemómetro PCM Servicio ULTRA TRIO PLUS 14 クリプソ オアシス - CLUB T-fal to DSR160ASI HD Samsung Galaxy S Plus GT-I9001 8GB White NAPLES DAY BED - Home Decorators Collection Copyright © All rights reserved.