1. p Dimensiones 96 x 96 x 81 5 Peso 350 gr Material caja ABS autoextinguible Color caja Gris Antracita Frontal IP54 IP65 opcional Agujero de panel Panel cut out 92 0 08 Dimensions 96 x 96 x 81 5 Weight 350 gr Case material Self exting ABS Case colour Anthracite grey Frontal IP54 IP65 optional Opcionales Optionals O Alimentaci n Auxiliar Auxiliary Supply 9 18V dc 18 36V dc 36 72V dc or 90 140Vdc CMM96 con entradas de corriente aisladas CMM96 with isolated inputs current Protector Frontal IP65 Frontal Protector IP65 O Tarjeta 2 64 rel s con contacto conmutado 2 or 4 Relays change over contact board O Tarjeta 2 4 rel s con contacto conmutado Control externo cuenta horas 1 2 or 4 Relays change over contact board External Control Count hour 1 Visualizacion de Medidas Measures Navigation El CMM96 CH mide y visualiza 36 valores Para facilitar su visualizaci n y control est n organizados en 5 p ginas The CMM96 CH masures and displays 36 values In order to make easy his display s and control are organized in 5 pages Funciones de Teclado Keyboard Functions Podemos movernos y realizar distintas funciones entre las distintas p ginas We can move and to do different functions between the different pages Avanza P gina Page Forward A Visualiza valores Pico Valle correspondientes a las medidas d
2. Para el c lculo del desequilibrio en tensi n se usan las tensiones fase fase fase neutro en funci n de la configuraci n Si las tres tensiones o las tres corrientes son inferiores al 10 del final de escala sus desequilibrios respectivos ser n 0 For the unbalance computation voltage measures fase to fase or fase to neutral are used in function of the configuration If the three voltages or the three currents are lower than the 10 of the full scale their respectives unbalences will be zero Visualizacion de Alarmas Alarms Indication El CMM96 MD dispone de 4 alarmas programables 4 leds nos indicaran respectivamente el estado de cada una de ellas The CMM96 MD has 4 programmables alarms 4 leds shows us respectivily the estate of every one of them Valley Unb Current Led Apagado No hay Alarma lt Led Off No Alarm Led Parpadeando Hay situaci n de Alarma pero se esta temporizando la conexi n Blinking Led We have alarm but it is delaying Led Encendido Hay Alarma Led ON Alarm Daigramas de Conexi n Wiring Diagrams 26 25 24 23 22 21 20 19 18 17 16 15 S L E L n E n L NO COM NO COM NO COM NO COM RL1 RL2 RL3 RL4 L1 a 400V 400Hz Red Trif sica 3 hilos 3 Phase 3 wire AUXILIARY SUPPLY 3 DE J La medidas de corriente deben hacerse a trav s de transformadores de corriente Current measurements should be done trough current transformers 26 25 24 23 22 21 20 19 18 17 16 15 S
3. L y E L NO COM NO COM NO COM NO COM RL1 RL2 RL3 RL4 L1 a 400V 400Hz O AUXILIARY SUPPLY Y 11 12 Red Trif sica 3 hilos 3 Phase 3 wire Aux Supply L1 A L2 B L3 C La medidas de corriente deben hacerse a trav s de transformadores de corriente Current measurements should be done trough current transformers Red Trif sica 4 hilos 3 Phase 4 wire AUXILIARY SUPPLY a E 11 12 3N 3E Aux Supply L1 A L2 B L3 C La medidas de corriente deben hacerse a trav s de transformadores de corriente Current measurements should be done trough current transformers Configuraci n del CMM96 CH CMM96 CH configuration Password Pulsando ambas teclas a la vez durante 10 segundos permite introducir un pass word de 4 d gitos ste tiene la funci n de inhabilitar el acceso a la configuraci n del equipo Para deshabilitarlo bastar con repetir el proceso pero ahora el valor introducido debe coincidir con el que lo bloque El n mero de password es solicitado dos veces consecutivas P51 y P50 para evitar errores de entrada Valores por Defecto Pulsando ambas teclas a la vez durante 20 segundos los valores de defecto f brica reempazar n a los programados a Y E E Password Pressing simultaneously both keys during 10 second a 4 digits password can be set in order to control the acces configuration options To disable this password simply repeat the process but no
4. manual disconnection For UnLATCH press during 3 seconds the key
5. Ch2 Ch3 Three programmable Count hour The user can select what measure control every counter and the trigger value Voltage level current level frequency level or for external digital input We can to have for example First Counter shows the amount of hours that our system was working the second counter the hour s number that the current in any phase has been bigger than 150 Amps and finally the third shows the hour s number that the frequency has been bigger than 55 Hz Counter hour are individually resetables and also can be individually protected against reset Memory Storage of the all peak and valley value measures and the Counter hours The CMM96 CH use and advanced generation memory technology thus avoiding the value loss in case of a power supply lack and annulling the inconveniences of using of a battery supplied systems 4 Programmables Alarms ls possible for example to program the first relay for have an alarm when any voltage Phase 1 2 or 3 became bigger than 250V or lower than 190V the second when any current became bigger to 500A during more than 30 seconds the third when the current unbalance achieve the 30 and finally the fourth relay will be connected when the Counter Hours 3 achieve 300 hours Maintenance Function Security and Reliability Instruments of the CMM96 Series have been tested in laboratories and check at industrial environments and have successfully passed the most rigorous tests involving amb
6. EMMO96 CH mn mAN E Manual de Usuario User s Manual PN 430029003 REV A Funciones y caracter sticas principales Vin Van Vin Via Va War l 1 l 2 Vavg Aavg Hz Medida en verdadero valor eficaz de las tensiones simples o compuestas asi como de las corrientes de fase Tensi n y corriente promedio de las tres fases average Frecuencia con una resoluci n de 0 1Hz y en el rango de 20 a 600Hz Unb V Unb C Desequilibrio de las tensiones y de las corrientes Este valor es muy importante si desean realizarse protecciones de sistemas susceptibles a los desequilibrios Asismismo es muy til a la hora de hacer mantenimientos preventivos en motores Ch1 Ch2 Ch3 Tres cuenta horas programables El usuario puede definir que par metro sirve de consigna para su respectivo contador Voltage corriente frecuencia o por entrada digital Podemos tener por ejemplo un primer contador que nos indique el total de horas que el equipo ha estado funcionado un segundo el n mero de horas que la corriente en cualquier fase a sido superior a 150A y el tercero el n mero de horas que la frecuencia ha sido superior a 55Hz Los cuenta horas son reseteables independientemente y es posible protegerlos individualmente para que no puedan ser puestos a cero Memorizaci n de los valores pico y valle de todos los par metros asi como los tres cuenta horas Estos quedar n guardados a n con p rdida de la alimentaci n auxiliar El CMM96 utiliza un sis
7. assigned to the alarm or 2 or 3 or ALL 1 2 amp 3 or UN unbalance between them N mero de Cuenta horas Hour Counter number Selecciona el cuenta horas asociado a la alarma 1 2 3 Select here the hour counter assigend to the alarm 1 2 or 3 VvUvivvv Pa a a a I 0 m J gt v viv v vv v v v NOTE Si tipo de alarma es por frecuencia fase 1 If type alarm is frequency phase 1 Punto decimal Decimal point Selecciona la posici n del punto decimal Select the decimal point position Comparaci n Comparation Selecciona el tipo de comparaci n Comparation type Hi Cuando es superado When the value is exceded O Cuando es inferior When the value is lowered NE Cuando esta fuera de zona When the value is out of zone p o Ny E Ejemplo Example Queremos alarma cuando el CH2 alcance 60 50 horas We want alarm when the CH2 achieve 60 50 hours Chog ATT 9999 L or Valor de alarma Alto High alarm value Si se ha seleccionado comparaci n por i por ZONE If Hi or ZONE comparation has been selected Valor de alarma Bajo Low alarm value Si se ha seleccionado comparaci n por L por ZONE IF LO or ZONE comparation has been selected Valor en horas Hour Value Retardo a la conexi n Connection delay Retardo en segundos desde la aparici n de la alarma hasta la conexi n de sta D
8. e la p gina actual v Show Peak amp Valley values corresponding to the actual page measures A Resetea valores Pico Valle correspondientes a las medidas de la p gina actual gt Reset Peak amp Valley values corresponding to the actual page measures V Peak Voltage L1 Voltage L1 Valley Voltage L1 Peak Voltage L2 Voltage L2 Valley Voltage L2 Peak Voltage L3 Voltage L3 Valley Voltage L2 Peak Current L1 Current L1 Valley Current L1 Peak Current L2 Current L2 Valley Current L2 Peak Current L3 Current L3 Valley Current L2 Los Cuenta horas son autoescala l M nima Indicaci n 0 001h gt 3 6 seg Cuenta Horas 1 M xima Indicaci n 9999h gt 416 dias Count Hour 1 The Count hour are auto scale Minimum Indication 0 001h gt 3 6 sec Maximum Indication 9999h gt 416 days Cuenta Horas 2 Count Hour 2 Conversi n centesimal sexsagesimal Cuenta Horas 3 Centesimal to sexsagesimal conversion Count Hour 3 5 409h gt 5h 0 409 x 60 min 5h 24min Voltage Average Peak Average V V1 V2 V3 3 Valley Average V Current Average Peak Average 11 12 13 3 Valley Average Peak Freq Ph1 Frequency Ph1 Valley Freq Ph1 C lculo desequilibrio Unb computation A 5 x 252 at lax d2 Ib x d3 I0xX Desequilibrio D x 100 D el mayor d1 2 3 Unb Unbalance D the bigger d1 2 3 ZA Peak Unb Voltage Voltage Unb 4 Wh Valley Unb Voltage Peak Unb Current Current Unb 4 A
9. elay time in seconds for the connection from the moment that the alarm apear Retardo a la desconexi n Desconnection delay Retardo en segundos desde la desaparici n de la alarma hasta la desconexi n de sta Delay time in seconds for the disconnection from the moment that the alarm desapear Enclavamiento Latch option Define si la alarma permanecer enclavada a n cuando desaparezca la condici n que la ha generado Define whether the alarm relay must remain latched after a trip once the alarm condition has already disappeared Ver Nota 1 See Note 1 Seguridad de Fallo Failure Safety Elegir entre las dos modalidades de estado del contacto Con seguridad de fallo 3 5 y sin NO Select among two relay states With power loss failure safety 325 or without NG Configuraci n modificable Modificaction enabled Programado en G impide la modificaci n de los par metros anteriores en 4 5 habilita la modificaci n Set at MG it avoids any modificaction of the above parameters Set at YES it enables their modification Nota 1 Note 7 DESENCLAVAR ALARMAS UNLATCH ALARMS Si en una alarma tenemos activada la opci n de LATCH cuando se produzca sta el rel se quedar enclavado y aunque las condiciones de alarma desaparezcan as permanecer Para desbloquearlo se deber pulsar durante 3 segundos la tecla If we have an alarm with the LATCH option actived once the alarm has been actived it remains at this state requiring then for a
10. ient conditions electrical noises electromagnetic disturbances vibrations etc Caracter sticas T cnicas Technical Data Alimentaci n Auxiliar Auxiliary Supply Tensi n y tolerancia 230 400V 10 15 Voltage and Tolerance Margen de Frecuencia 35 450Hz Frequency band Consumo 5VA Consumption Consumo con tarjeta rel s TVA Consumption with relays card Circuito de Medida Measuring Circuit Tensi n Nominal 400V F N 565 F F Nominal Voltage Frecuencia 35 450HzZ Frequency band Corriente Nominal 5A Nominal Current Sobrecarga Permanente 1 2 In Continuous Overload Consumo circuito Corriente 0 6VA Current circuit consumption Precisi n Accuracy Tensi n y Corriente CI 0 5 2dig Voltage and Current Frecuencia 0 01Hz Frequency Cuenta horas 1h a o year Count Hour Display Display 3 x 4 digits Display Color Red High Efficiency Colour Ciclo de Presentaci n 1xseg 1xsec Display rate Leds Auxiliares 10 Auxiliar Leds Condiciones Ambientales Environmental conditions 40 70 C 10 65 C Temperatura Almacenamiento Temperatura de Uso Storage Temperature Operation Tempearture Normas de Dise o Design Standards IEC 1010 IEC 348 IEC 664 IEC 801 EN 50081 2 EN 50082 2 Dimensiones y datos mec nicos Dimensions amp Mechanical Data 96 0 81 5 5 3 Brida de sujecci n Holding piece
11. r Trigger value that active de hour counter Habilitaci n Deshabilitaci n de Reset Reset Enable Disable Para cada cuenta horas podemos definir si ser reseteable por teclado Reset of each count hour can be selected individually by keyboard A Resetea los cuenta horas que tienen habitado el Reset Y Reset the count hour that have the Reset enabled Ejemplo Example Y Queremos que el cuenta horas 1 cuente el tiempo que la corriente de cualquier fase super los 200A este valor no podr ser reseteado We want that the hour counter 1 count the time that any current is bigger than 2004 this value can t will be reseted E DI D e a a a ia e a a a a ji it a a ia ia n na o N 153 Configuraci n Habilitada Configuration Enabled Programado en no impide la modificaci n de cualquiera de los par metros anteriores en Yes habilita la modificaci n Set at no it avoids any modification of the above parameters Set at yes it enables their modification Configuraci n de las Alarmas Alarms Configuration Tipo de Alarma Alarm Type Selecciona la medida asociada a la alarma Select the electrical parameter assigned to the alarm Voltaje Voltage Corriente Current Maki Frecuencia Frequency ueia Cuenta horas Count hour 19PE VOLI LURR FREU Fase Phase Selecciona la fase asociada a la alarma l Z 3 ALL 1 2 y 3 UNB desequilibrio entre ellas Select the phase
12. tema de memoria de ltima generaci n que no precisa de bateria externa con lo que no est sujeto a los problemas de mantenimiento tipicos de otros sistemas 4 alarmas programables Es posible por ejemplo programar el primer rel para tener alarma cuando cualquiera de las tres tensiones sean superiores a 250V o inferiores a 190V el segundo cuando cualquier corriente sea superior a 500A durante m s de 30 seg el tercero cuando el desequilibrio en corriente sea superior al 30 finalmente el cuarto rel nos dar alarma cuando el cuenta horas 3 supere la 300horas Funci n de Mantenimiento Seguridad y Fiabilidad Los instrumentos de la serie CMM96 han sido ensayados en laboratorio de acuerdo a las ltimas normativas y directivas y contrastados en ambientes industriales superando con xito las pruebas m s severas de condiciones ambientales ruidos el ctricos conducidos perturbaciones electromagn ticas radiadas vibraciones etc Functions and Main Characteristics Via Van Vin Va Vo Va d 1 l 2 Vavg Aavg Hz True RMS measurement of the phase to phase or phase to neutral voltage and phase s currents Three phase voltage and current average Frequency with 0 1 Hz resolution and in the 20 to 600Hz range Unb V Unb C Voltage and Current Unbalance computation This value is very important if we want to protect electrical or electronic equipment Also is very useful in order to do predictive maintenance in electrical motors Ch1
13. type measurement Selecciona la visualizaci n de tensi n Select the voltage type displayed y gt INTA Fase Fase Phase to phase Fase Neutro Phase to neutral Primario de Transformador de Corriente Primary Current Transformer Valor de Primario de Intensidad Primary Current value Usando el valor de primario y la posici n del punto decimal podemos conseguir distintas indicaciones Using the primary current value and the decimal position is possible to have different indications for the same primary Current Transformer 50 5A Indication1 58 Indication2 58 0 Punto Decimal Decimal Point Posici n del punto decimal para la indicaci n de la corriente Decimal point position for the current indicaction Q lt lt q S P gina Inicial Initial Page P gina Inicial que se visualizar al conectar el CMM96 Initial Page showed when the CMM is powered on c 0 I mn ni Par metro de Control Control parameter Define que medida controlar el funcionamiento de cada Cuenta horas Select the measure that will control every Hour counter z gt MS Voltaje Voltage HPA Corriente Current nais Frecuencia Frequency a JE PI Entrada digital externa External digital Input Es necesario disponer de la tarjeta de 2 4 reles control CH You should have the 2 or 4 relays CH control auxiliary card Valor de trigger Trigger Value Valor por encima del cual el cuenta horas se activa
14. w the number introduced should be the same that was used for enable The password number should be entered twice P51 8 P5 in order to avoid mistakes Default Setup Values Pressing simultaneously both keys during 20 second default setup values replace user configured ones Configuraci n memm e Configuration Pulsando esta tecla durante 3 segundos y si el password no est activado Pressing this key during 3 second and if the password protection is not entraremos en el men de configuraci n del equipo Ahora y con el uso de enabled we enter in the configuration menu Now using the keys we can las teclas podremos navegar por el diagrama de configuraci n y alarmas navigate for the configuration and alarms tree Acepta el valor y desplaza una posici n a la izquierda en el rbol Accept value and move one position at left on the tree Baja una posici n en el rbol Move one position down on the tree Desplaza una posici n a la derecha en el rbol Move one position right on the tree Introducir un valor Setting a value Para mover ciclicamente por los 4 digitos pulsar To cyclically move along the four digits press the key Para modificar el valor del digito seleccionado pulsar repetidamente To modify the value of the selected digit repeatedly press the key Introducir el valor de los 4 digitos usando ambas teclas Set the desired 4 digits value using both above keys Tipo de medida en Tensi n Voltage