        Modelo 8500 - Chauvin Arnoux Group
         Contents
1.   12V  5 x 2 NiCd packs  1300mAH  Panasonic P 130SCR or equivalent    Battery Life   Up to 10 hrs  continuous operation   May be used while recharging  Low battery LCD indication     Charging Time  14 hrs typical  C 10 rate    Line Fuse  115V  1 0A  5 x 20mm  slow acting  230V  0 5A  5 x 20mm  slow acting      23  C   5  C  50 to 70  RH  full battery charge  no external fields or noise     Digital Transformer Ratiometer DTR  Model 8500 7    3 2 Mechanical  Connections  Cannon  XLR connectors  amp  large color coded industrial clips  Leads  15 ft  H  amp  X color coded  in carrying bag    Display  Dual line alpha numeric 3 875 x  875  with contrast adjustment  and backlight    Operating Temperature  0   to 50  C  32   to 122  F   0 to 90  RH  without condensation     Case  Heavy duty structural polypropylene  yellow   Dimensions  13 x 12 x 6   330 x 305 x 152mm   Weight  14 Ib  6 4kg      All specifications are subject to change without notice    3 3 Cable Identification                   RED BOOT   H  IDENTIFIER  CONNECTOR     CABLE SET   H  IDENTIFIER  BLACK BOOT  RED BOOT   X  IDENTIFIER  A    e    S 3 PIN  CONNECTOR  X CABLE SET W E  E    X  IDENTIFIER    BLACK BOOT    8 Digital Transformer Ratiometer DTR  Model 8500    CHAPTER 4    OPERATION    A WARNING  The Digital Transformer Ratiometer DTR  Model 8500  is designed for use on non energized   dead   transformers only   Make sure the test sample is completely disconnected from AC  power and is fully discharged     4 1 Co
2.   CHAPTER 5    MAINTENANCE    Use only factory specified replacement parts  AEMC  will not be held  responsible for any accident  incident  or malfunction following a repair  done other than by its service center or by an approved repair center     WARNING  To avoid electrical shock  do not perform any service  other than the operating instructions contained in this manual   unless you are qualified to do so          Do not allow water or other foreign substances into the case       Disconnect the unit from all circuits and test cables before opening the  case       Use caution with metallic tools that may short battery packs  power  supplies  etc     Digital Transformer Ratiometer DTR2 Model 8500 21        Repair and Calibration        North South America  Australia  New Zealand     To ensure that your instrument meets factory specifications  we recommend  that it be submitted to our factory Service Center at one year intervals for reca   libration  or as required by other standards or internal procedures     For instrument repair and calibration    You must contact our Service Center for a Customer Service Authorization  Number  CSA    This will ensure that when your instrument arrives  it will be  tracked and processed promptly  Please write the CSA  on the outside of the  shipping container  If the instrument is returned for calibration  we need to  know if you want a standard calibration  or a calibration traceable to N I S T    Includes calibration certificate plus reco
3.   transformers only  Make sure  the test sample is completely disconnected from AC power and is  fully discharged     Only qualified personnel should use the Model 8500     The DTR  must not be used in a manner in which any of its com   ponents  including test cables  are relied upon to provide protec   tion from electric shock  No high voltage insulation protection is  provided by any component of the DTR    Always make sure the  circuit is fully discharged before attaching any test cables     Do not touch  adjust  or reposition test cables while the DTR  is  conducting a test     Use caution on any apparatus  potentially high voltages and cur   rents may be present and pose a shock hazard    Safety is the responsibility of the user    Never open the instrument while it is connected to AC power or  when test cables are connected to transformers  equipment   circuits  etc        1 1 International Electrical Symbols    This symbol signifies that the instrument is protected by double or  reinforced insulation  Use only specified replacement parts when  servicing the instrument     the operator must refer to the user manual for instructions before  operating the instrument     Risk of electric shock  The voltage at the parts marked with this    4 This symbol on the instrument indicates a WARNING        that  A symbol may be dangerous     Digital Transformer Ratiometer DTR  Model 8500 3    1 2 Receiving Your Shipment    Upon receiving your shipment  make sure that the contents ar
4.  4 3 CT Test Mode Flow                                                       15  4 5 Displayed                                    16  4 6 Power Supply  er ep bee e eid 17   4 7 Changing Power Supply Setting from  115V to 230V or 230V to 115                                                  18  4 8 Tips for Making Precise Ratio Measurements                          19    49  Ratio  Tests 11  Rete ect ee oce te dece ee ez EE 19    4 10 Polyphase Connections                                   20  MAINTENANCE                         eee eernn eere nnne nnn nnn nnn nnns 21  Repair and Calibration    North South America  Australia  New Zealand                                22  Technical and Sales Assistance    North South America  Australia  New Zealand                                22  Repair and Calibration    Europe  Asia  Africa       mem te eee tera        23  Technical and Sales Assistance    Europe  Asia  Africa  ei nate ttt e e rad ei dit 23  Limited Warranty    etes ettet er ead iee ii ios 24  Warranty RepallS         tae aa Ee aces 24    Digital Transformer Ratiometer DTR  Model 8500    CHAPTER 1    INTRODUCTION    A  WARNING   N    These safety warnings are provided to ensure the safety of personnel  and proper operation of the instrument     Read the instruction manual completely and follow all safety infor   mation before attempting to use or service this instrument     The Digital Transformer Ratiometer DTR  Model 8500 is designed  for use on non energized     dead   
5.  The DTR  uses a maximum 44V excitation signal for testing  thus the  displayed excitation current value will almost always be a small fraction  of the tested transformer s no load excitation at full  rated  voltage  Most  transformers will require 100mA or less  some will require less than 1mA     Note  If you are presently using a ratiometer that employs    X    side   step up  excitation  e g  common hand cranked instrument   exci   tation currents displayed by the DTR  will  in most cases  be signifi   cantly lower  This is normal and results directly from the fact that in  most step down transformers  the H winding exhibits much higher  impedance than its associated X winding        4 3 5 VT PT Continuity Test    The Continuity Test function of the DTR  Model 8500 serves as a useful  means of identifying open primary and secondary windings  open circuit  breakers  and blown fuses  When selected  the DTR  alternately checks  for continuity between its X cables and between its H cables     The Continuity Test is selected when the user depresses the TEST button  at the Press  TEST  to Check Continuity prompt  The DTR   will display  the results of continuity checking  then enter a brief degaussing period   During this time  the message Pre Test Checks will be displayed       The DTR will indicate OPEN for tested circuits greater than 4kQ  and  CONT for those less than 4kO  A small percentage of transformers   e g  those with extremely high inductance or high winding resista
6.  de transporte y avise inmediatamente a su distribuidor dando una descrip   ci  n detallada de cualquier da  o     1 3 Embalaje    El instrumento puede ser embalado en dos formas dependiendo de si Ud   compr   una unidad con entrada para 115V  50 60Hz  Cat   2111 80  o  una unidad con entrada para 230V  50 60Hz  Cat   2116 21      El Medidor de Raz  n de Transformador Digital DTR   8500  ajustado en  f  brica para 115V  50 60Hz  Cat   2111 80  incluye bater  as NiCd  ins   taladas   cable de alimentaci  n para 115V  conjunto de cables de prueba  de 15 pies en un estuche de transporte  tarjeta de garant  a  amp  manual de  usuario     El Medidor de Raz  n de Transformador Digital DTR9 8500  ajustado  en f  brica para 230V  50 60Hz  Cat   2116 21  incluye bater  as NiCd   instaladas   cable de alimentaci  n con extremos desnudos  sin enchufe    conjunto de cables de prueba de 15 pies en un estuche de transporte   tarjeta de garant  a  amp  manual de usuario     28 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    1 3 1 Accesorios   Cables de prueba 9m  30 pies  en estuche de transporte    Cat  2118 47  Repuesto de cables de prueba 4 5m  15 pies                      Cat   2118 48  Bater  as de repuesto 12V NiCd  conjunto de dos                 Cat   2118 57    Fusible  conjunto de 5  0 5A 2250V   5 x 20mm  acci  n lenta   para entrada de 230V y placa principal                                Cat  2118 53    Fusible  conjunto de 5  1A  2125V   5 x 20mm  acci  n lenta 
7.  el circuito est   totalmente  descargado antes de conectar ning  n cable de prueba     No toque  ajuste  o mueva los cables de prueba mientras se  est   realizando una prueba con el DTR       Sea precavido ante cualquier equipo  puede haber altos vol   tajes y corrientes que representen un peligro de choque el  c   trico     La seguridad es responsabilidad del usuario     Nunca abra el instrumento mientras est   conectado a una  fuente de alimentaci  n AC o mientras los cables de prueba  est  n conectados a transformadores  equipos  circuitos  etc     Siempre inspeccione el instrumento y los cables de prueba  antes de usarlos  Reemplace las partes defectuosas inmedia   tamente con repuestos de f  brica solamente       Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 27    1 1 S  mbolos El  ctricos Internacionales     E  Este s  mbolo sefiala que el instrumento est   protegido mediante  una aislaci  n doble o reforzada  Al reparar el instrumento use s  lo  los repuestos especificados     A Este s  mbolo se  ala   CUIDADO  y pide al usuario que consulte el  manual de usuario antes de usar el instrumento        Riesgo de choque el  ctrico  Los voltajes en las partes marcadas  con este s  mbolo pueden ser peligrosos     1 2 Recepci  n De Su Embarque    Al recibir su embarque  aseg  rese que el contenido corresponde a la  gu  a de despacho  Avise a su distribuidor de cualquier   tem faltante  Si el  equipo llega dafiado  presente inmediatamente un reclamo a la empresa 
8.  s  lo para unidades de 115V         Cat  2118 54    Fusible  conjunto de 5  4A  gt 125V                                        Cat  42118 55   5 x 20mm  acci  n lenta     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 29    CAPITULO 2    PRESENTACI  N    2 1 Descripci  n    El DTR   Modelo 8500 es un medidor de raz  n de transformador digital port  til   robusto y liviano dise  ado para la prueba en terreno de transformadores de  potencia  de voltaje y de corriente  La operaci  n del DTR  Modelo 8500 es  totalmente autom  tica  No requiere calibraci  n  selecci  n de rango  uso de  manivela o un balanceo tedioso por parte del usuario   Durante cada ciclo de prueba  el DTR  autom  ticamente comprueba       Inversi  n de los cables H X   e Continuidad de los circuitos espiras bajo prueba     Condiciones de cortocircuito  alta corriente     Al completar un ciclo de prueba  el DTR  presenta      Raz  n de Espiras   la raz  n entre voltaje primario y secundario  en los terminales del transformador producida por la excitaci  n de  prueba     Corriente de Excitaci  n   La corriente de excitaci  n RMS en el  bobinado H producida por la excitaci  n de prueba durante una  carga despreciable del bobinado X asociado     Polaridad   Indica la polaridad  fase  de X relativa a H    La Raz  n de Espiras  Corriente de Excitaci  n  y Polaridad son par  metros    tiles para diagnosticar y predecir una variedad de fallas que se presentan  en los transformadores de potencia  de volt
9. 3  742 2346 or  603  749 6309   repair aemc com   Contacte su distribuidor autorizado   El coste por reparaci  n  calibraci  n est  ndar  y calibraci  n N I S T  est  n  disponibles     NOTA  Todos los clientes deber  n obtener el CSA  antes de devolver  el instrumento     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 47    5 2 Asistencia t  cnica y venta  Si tiene cualquier problema t  cnico  o requiere de ayuda para una ope   raci  n o aplicaci  n determinada con el instrumento  por favor ll  menos   correos  fax o e mail a nuestro servicio t  cnico    Chauvin Arnoux    Inc  d b a  AEMC  Instruments   200 Foxborough Boulevard   Foxborough  MA 02035  USA    Phone   508  698 2115  Fax  508  698 2118  E mail  techsupport aemc com    NOTA  No mande el instrumento a nuestra direcci  n de Foxborough  MA     5 3 Garant  a Limitada   El Modelo DTR   8500 esta garantizado por el periodo de un a  o desde  la fecha de su adquisici  n y solamente por defectos de fabricaci  n  Esta  garant  a limitada es dada por AEMC Instruments  no por el distribuidor al  cual fue comprado el instrumento  Esta garant  a puede ser cancelada si la  unidad a sido mal tratada o defectuosa por uso indebido  o por reparacio   nes no efectuadas por nuestro servicio t  cnico de AEMC Instruments   Para un mayor detalle de la cobertura de la garant  a y registracion  vaya  a www aemc com    Que puede hacer AEMC  Si el mal funcionamiento ocurre durante el  periodo del afio  deber   devolver la unid
10. Accessories and Replacement Parts Directly Online    Check our Storefront at www aemc com for availability       4 Digital Transformer Ratiometer DTR   Model 8500    CHAPTER 2    PRODUCT FEATURES    2 4 Description    The DTR  Model 8500 is a lightweight  rugged  portable digital transformer  ratiometer designed for onsite testing of power  potential and current trans   formers  Operation of the Model 8500 is fully automatic  No user calibra   tion  range selection  hand cranking or tedious balancing is required     During each test cycle  the DTR  automatically checks for           lead reversal    Continuity of tested circuits windings     Short circuit conditions  high current     Upon completion of a test cycle  the DTR  displays     Turns Ratio   the ratio of the primary to secondary voltage at the  transformer terminals due to test excitation    Excitation Current   the RMS excitation current in the H winding  due to test excitation during negligible loading of the associated X  winding    Polarity   indicates the polarity  phase  of X relative to H    Turns Ratio  Excitation Current and Polarity are useful parameters in diag   nosing and predicting a variety of faults that occur in power  potential and  current transformers     The Model 8500 will display the following messages     Incorrect Lead Connections     H XReversal  accidental step up misconnection     Short  excess excitation current     Open Circuits    Circuit Continuity    Low Battery    A The DTR   utiliz
11. El DIGITAL TRANSFORMER  RATIOMETER    El MEDIDOR DE RAZ  N DE  TRANSFORMADOR DIGITAL                                        User Manual             Manual de Instrucciones INSTRUMENTS             Statement of Compliance    Chauvin Arnoux    Inc  d b a  AEMCS  Instruments  certifies that this instrument has been calibrated  using standards and instruments traceable to  international standards     We guarantee that at the time of shipping your  instrument has met its published specifications     An NIST traceable certificate may be  requested at the time of purchase  or obtained  by returning the instrument to our repair and  calibration facility  for a nominal charge     The recommended calibration interval for this  instrument is 12 months and begins on the date of  receipt by the customer  For recalibration  please  use our calibration services  Refer to our repair  and calibration section at www aemc com     Serial     Catalog    2111 80   2116 21  Model    8500  115V    8500  230V     Please fill in the appropriate date as indicated     Date Received        Date Calibration Due        Chauvin Arnoux    Inc   d b a AEMC   Instruments  INSTRUMENTS www aemc com    Lee oa a e o  gt                   Table of Contents          Digital Transformer Ratiometer DTR  Model 8500    ENGLISA cok epe de ep ee UE tas 1  ESPA  OL costat oe bo    tutatus t LAINE DO EE 25  1  INTRODUCTION                                                                                 3  1 1 International El
12. ITULO 5    MANTENIMIENTO      Para su mantenimiento use s  lo repuestos especificados de f  brica       Evite choque el  ctrico  no intente realizar ning  n servicio si no est    calificado para hacerlo       Evite choque el  ctrico y o da  o al instrumento  no permita que entre  agua u otras sustancias extrafias a la carcasa  Desconecte la unidad  de todos los circuitos y cables de prueba antes de abrir la carcasa   Tenga cuidado con las herramientas met  licas que pueden corto cir   cuitar las bater  as  fuentes de poder  etc     5 1 Reparaci  n y Calibraci  n   Para asegurar que su instrumento cumple las especificaciones de la empresa   recomendamos que se mande a nuestro Servicio T  cnico en intervalos de  un afio para recalibrarlos  o por requerimientos de otro est  ndar o procesos  internos     Para reparaci  n o calibraci  n de instrumentos    Deber   contactar con nuestro Centro de Servicios para obtener el Numero  de Autorizaci  n del Servicio al Cliente  CSA    Este asegurara que cuando  recibamos el instrumento  ser   procesado r  pidamente  Por favor escriba el  CSA  por fuera del embalaje  Si el instrumento es mandado para calibraci  n   necesitamos saber el modelo de calibraci  n que desea  calibraci  n est  ndar  o calibraci  n para N I S T   Incluye certificado de calibraci  n mas la informa   ci  n recogida al ser calibrado      Chauvin Arnoux    Inc  d b a  AEMC  Instruments  15 Faraday Drive   Dover  NH 03820 USA    Tel   603  749 6434  Ext  360    Fax   60
13. SECONDARY  7200 240CT                 e NR          H RED      H BLACK     H BLACK    H  I     X BLACK          Note  Unlike other instruments  the DTR   Model 8500 does not  impose polarity restrictions or    forced    auto connections  thus there  are several valid hookups and virtually all transformer configu   rations can be tested  In all tests  a negative sign preceding the  displayed ratio indicates phase reversal  inverted polarity  of the  sensed X signal relative to the excitation signal at H  In using the  DTRS  always note the color code of test cable boots        10 Digital Transformer Ratiometer DTR   Model 8500    4 3 2 VT PT Testing    1  When the instrument is set for VT PT testing  the DTR  will display the  VT PT Test Mode Ready message after the initial power up sequence   This message indicates that the DTR  is now ready to execute a test     2  Press the TEST button once     WARNING  The test should not be performed while personnel are  handling transformer connections        3  Press  TEST  to Check Continuity is now displayed for three  3   seconds  If a continuity test is desired  the TEST button should be  pressed once at this time  The results of continuity testing will be  displayed as CONT or OPEN for both X and H connections  Refer to  VT PT Continuity Test  page 12  for more information     4  The next message displayed is  Ratio Testing  TEST  to Cancel  The  asterisk       will blink as testing proceeds  Testing may be cancelled at  this time 
14. a prueba de Continuidad queda seleccionada cuando el usuario pulsa el  bot  n TEST ante el mensaje Press  TEST  to Check Continuity  El DTR    mostrar   los resultados de la prueba de continuidad  entrando luego en un  breve periodo de desgaussiado desmagnetizaci  n   Durante este tiempo   se mostrar   el mensaje Pre Test Checks       EIDTR  indicar   OPEN  abierto  para los circuitos probados con m  s  de 4KO  y CONT continuo  para aquellos con menos de 4KO  Un  pequefio porcentaje de transformadores  por ejemplo  aquellos con  inductancia extremadamente alta o bobinados de alta resistencia   pueden aparecer como un circuito abierto para el DTR         La indicaci  n OPEN no cancelar   el ciclo de la prueba en curso y se  mostrar  n los resultados de la prueba de raz  n de todos modos     e Transformadores cuya disposici  n de los bobinados contiene caminos  paralelos  m  ltiples  por ejemplo  tipos con conexi  n Delta  pueden  dar la lectura CONT  cuando en realidad uno o m  s de los bobinados  pueden estar abiertos     38 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    44 CT    4 4 1 Ejemplo de Conexi  n CT    La prueba de raz  n en Transformadores de Corriente  CT  se realiza  conectando el conjunto de cables de prueba H al bobinado X  y uniendo  en corto el conjunto de cables de prueba X a trav  s de la abertura CT   como se ilustra abajo  Esto crea una configuraci  n de baja de voltaje en  que el bobinado X sirve de circuito primario y el conjunto de cabl
15. aci  n     Caja  Polipropileno estructural  amarillo  para trabajo pesado  Dimensiones  13 x 12 x 6   330 x 305 x 152 mm   Peso  14 Ibs  6 4kg     Todas las especificaciones y precios pueden variar sin previo aviso     3 3 Identificaci  n de Cables    Capuch  n Rojo  Identificador  H          Conector de  5 Patas     conn de Cables    H                      t Identificador  H   Capuch  n Negro    Capuch  n Rojo  Identificador  X     Mie Conector de    3 Patas    E        A    Conjunto de Cables    X                3  BR       El             Identificador  X   Capuch  n Negro    Medidor de Raz  n de Transformador Digital DTR  Modelo 8500 33    CAPITULO 4    UTILIZACI  N    ADVERTENCIA  El Medidor de Raz  n de Transformador Digital  DTR   Modelo 8500 est   dise  ado para ser usado en transformado   res no energizados solamente  Aseg  rese que el equipo a probar  est   completamente desconectado de la fuente de alimentaci  n AC  y est   totalmente descargado     4 1 Para realizar una prueba    1  Conecte los cables de prueba del DTR  a un transformador no ener   gizado de manera adecuada  Refi  rase a Ejemplos de Conexi  n   84 3 1 and 84 4 1      2  Encienda el DTR   y seleccione el modo de prueba adecuado  Refi     rase a Selecci  n de Modo m  s abajo     3  Cuando aparezca Ready  pulse el bot  n de prueba  TEST  para  comenzar  Luego de un breve ciclo de comprobaci  n  se mostrar  n  Raz  n  Polaridad y Corriente de Excitaci  n     Para informaci  n completa de la operaci  n 
16. ad a nosotros para reparaci  n   sin costo alguno  aseg  rese de mandarnos la Tarjeta de Registro  AEMC   Instruments  podr   decidir  reparar la unidad o reemplazarla     5 4 Garant  a de Reparaci  n  Que debe hacer para devolver el instrumento para ser reparado bajo la garant  a   Primero  adquiera el Numero de Autorizaci  n del Servicio al Cliente  CSA    por tel  fono o por fax desde nuestro Departamento de Servicios  ver direcci  n  adjunta   despu  s devuelva el instrumento con la autorizaci  n CSA firmada   Por favor escriba el CSA   en el exterior del embalaje  Devuelva el instru   mento  con los portes y seguros prepagados a    Chauvin Arnoux    Inc  d b a  AEMC   Instruments   Service Department   15 Faraday Drive   Dover  NH 03820 USA   Tel   603  749 6434  Ext  360    Fax   603  742 2346 or  603  749 6309   E mail  repairQaemc com  Advertencia  Para protegerse usted mismo por perdida del instrumento en  transito  le recomendamos que lo asegure   NOTA  Todos los clientes deber  n obtener el CSA  antes de devolver el  instrumento     48 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500     E  AEMC     INSTRUMENTS    08 08    99 MAN 100150 v8    Chauvin Arnoux    Inc  d b a  AEMC  Instruments  15 Faraday Drive   Dover  NH 03820 USA   Phone   603  749 6434   Fax   603  742 2346  www aemc com    
17. aje y de corriente     EI DTR  Modelo 8500 presentar   los siguientes mensajes     Conexi  n Incorrecta de los Cables de Prueba    Inversi  n H X  malconexi  n accidental de elevaci  n de voltaje     Corto  exceso de corriente de excitaci  n     Circuitos Abiertos    Continuidad de Circuito    Bater  a Baja    EI DTR   utiliza una avanzada t  cnica de medici  n  de bajo voltaje   por disminuci  n de voltaje  en que el bobinado de alto voltaje H se  somete a la excitaci  n de prueba  Esto se traduce en una mayor  seguridad para el operador y en una habilidad para probar una gama  m  s amplia de tipos y tama  os de transformadores     30 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    2 2 Descripci  n del Aparato    c TRANSFORMER RATIO  MODEL 8500                          Display   Indicador de Carga de la Bater  a  Entrada de Alimentaci  n AC  Porta Fusible de Alimentaci  n  Ajuste de Contraste del Display  Bot  n Pulsador de PRUEBA  Interruptor de Alimentaci  n    Conector de Cable    X    lado bajo  secundario                  Rom    Conector de Cable      lado alto  primario     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 31    CAPITULO 3    ESPECIFICACIONES    3 1  Electricas C        Rango de Razones   Autorango  0 8000 a 1500 0 1    Exactitud   Raz  n    10 a 1    0 2  de Lectura  Raz  n x 10 a 1000 a 1      0 196 de Lectura  Raz  n    1000 a 1     0 296 de Lectura    Sefial de Excitaci  n  Modo PT VT  44Vrms m  ximo  Modo CT  Nivel Autom  
18. anumesure   Reux   14130 Pont l Ev  que   France   Tel   33  2 31 64 51 43   Fax   33 2 31 64 51 09   www chauvin arnoux com     Or contact your authorized distributor         Technical and Sales Assistance     Europe  Asia  Africa    If you are experiencing any technical problems or require any assistance   with the proper use or application of this instrument  please contact     CHAUVIN ARNOUX  SCA   190  rue Championnet   75876 Paris Cedex 18   France  Tel   33  1 44 85 44 57  Fax   33  1 46 27 95 59  www chauvin arnoux com    Digital Transformer Ratiometer DTR  Model 8500 23        Limited Warranty              The Model 8500 is warranted to the owner for a period of one year from the  date of original purchase against defects in manufacture  This limited warranty  is given by AEMC  Instruments  not by the distributor from whom it was  purchased  This warranty is void if the unit has been tampered with  abused  or if the defect is related to service not performed by AEMC  Instruments     For full and detailed warranty coverage  please read the Warranty Cov   erage Information  which is attached to the Warranty Registration Card   if enclosed  or is available at www aemc com  Please keep the War   ranty Coverage Information with your records     What AEMC  Instruments will do    If a malfunction occurs within the one year period  you may return the  instrument to us for repair  provided we have your warranty registration  information on file or a proof of purchase  AEMC  I
19. by pressing the TEST button once  If the test continues  Ratio  and Excitation current will be displayed     5  Once test results are recorded  press the TEST button to reset for the  next test     This routine may be repeated as many times as needed without powering  down the unit     Digital Transformer Ratiometer DTR  Model 8500 11    4 3 3 VT Test Mode Flow Chart    Display Indication Operator  for           Mode Action    Version XXX  1999 Turn Unit On Indicates version of  Chauvin Arnoux Internal Firmware  AEMC  Instruments  e  N A  DTR   Model 8500 m  N A soa Model Identification      Replaces Above Indication  B      N A xx when Batteries Need  ow i ery Recharging    PT VT Test Mode no N A mem Indication of  Selected Mode  Calibrating m NA m Internal Calibraiton  Please Wait in Progress    VTIPT Test Mode Push TEST Now System Ready to     Ss  Ready to Initiate Testing Begin Testing    Comments        Test Cancel Option    Push TEST Now er             to Check Continuity m DC t  BE    Inuity or do nothing to skip pion ogs   Ratio Testing Pushi TEST Now Ratio Testing  to Cancel            TEST  to Cancel   in Progress with  Test in Progress    Push TEST Now to  Reset for Next Test    Ratio  60 00  1  Current  11 mA    12 Digital Transformer Ratiometer          Model 8500    4 3 4 VT PT Excitation Current    Excitation Current  displayed in milliamperes  is the RMS current in the H  winding due to test excitation  during negligible loading of the associated  X winding   
20. che  Cada vez que el DTR    se conecta a la energ  a AC  comienza un ciclo de recarga de 14 horas   Repetidas recargas de bater  as parcialmente descargadas no produce    42 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    dafio a las bater  as  Durante el ciclo de 14 horas  el indicador CHARGING  estar   encendido permanentemente  luego de este periodo  se entra en  un modo de carga de mantenci  n pulsada y el indicador se encender   y  apagar   pulsadamente     4 7 Cambiar el Voltaje de la Fuente de Poder de     Cuerpo Negro  Interruptor Rojo     Posici  n de Ajuste a 115V    115V a 230V o de 230V a 115V    Alimentaci  n  Fusible         Selector de Voltaje    de Alimentaci  n Etiqueta del Voltaje de Entrada     coincidente con el ajuste  del Voltaje de alimentaci  n        Interruptor Encendido Apagado    Paquete de Bater  as    Posici  n de Ajuste a 230V    El voltaje de la fuente de poder del instrumento puede ser cambiado de  115 a 230 volts mediante el siguiente procedimiento     1     ov d com    Apague el instrumento     Desconecte el instrumento de la l  nea y de todas sus entradas   Suelte los cuatro tornillos en su base    Extraiga el instrumento de la carcasa    Localice el interruptor cerca del transformador  vea el dibujo      Coloque el interruptor rojo en 115V o en 230V seg  n corresponda  La  posici  n del interruptor indica el voltaje de l  nea seleccionado     Reemplace el fusible por uno del valor de corriente apropiado  vea la  entrada de a
21. dor omentarios    Encienda la Unidad Indica versi  n        Version        1997   pm con el Bot  n    del Programa de  Chauvin TEST Presionado Instrucciones Interno  AEMC  Instruments Mantenga el Bot  n Identificaci  n  DTR  Model 8500 TEST Presionado del Modelo  Y Reemplaza el Mensaje de       A     AEMC  Instruments Mantenga el Bot  n     Arriba cuando las  Low Battery TEST Presionado Bater  as Necesitan    Y ser Recargadas    CT Test Mode m Suelte el Bot  n TEST s Indicaci  n del  Modo Seleccionado  Calibrating     NA    H Calibraci  n Interna  Please Wait en Curso    Y    Sistema Listo  CT             para  eaey a      Comenzar la Prueba          r   Pulse TEST Ahora Prueba de Raz  n en  Ratio Testing      TEST  to Cancel para Cancelar la      Curso con la Opci  n  i Prueba en Curso de Cancelar la Prueba  Pulse TEST Ahora para    Ratio  40 00   1  Current  35 mA    Reiniciar para la  Pr  xima Prueba    40 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    4 5 Mensajes Mostrados    Check for H lt  gt X Cable Reversal    Compruebe Inversi  n de los Cables H  lt  gt  X    El DTR  puede haber detectado una condici  n de elevaci  n de voltaje  potencialmente peligrosa al intentar probar el transformador tal como est    conectado  Compruebe las conexiones  HRoJo  amp               deber  an estar  conectados al bobinado de alto voltaje             8 XNEGRO deber  an estar  conectados al bobinado de bajo voltaje     High Excitation Current   Alta Corriente de Excitac
22. e  la secuencia de encendido     CT Test Mode Ready   Modo de Prueba CT Listo    Indica que el sistema est   listo para la prueba CT    X Circuit  OPEN  or CONT     Circuito X   ABIERTO      CONTINUO      Refi  rase a la secci  n Prueba de Continuidad VT PT    H Circuit  OPEN  or CONT     Circuito H   ABIERTO   o CONTINUO     Refi  rase a la secci  n Prueba de Continuidad VT PT    Low X Signal   Sefial X Baja     Revise los cables X por posibles cortocircuitos inadvertidos   El bobinado X puede estar en corto o el desconectador del  transformador puede estar abierto     Low H Signal   Se  al H Baja    Revise los cables H por posibles cortocircuitos inadvertidos   Revise los conectores de cables H en el panel frontal del DTR       4 6 Alimentaci  n    El DTR  Modelo 8500 puede ser usado hasta 10 horas con bater  as NiCd  totalmente cargadas  El DTR  tambi  n puede ser alimentado desde la  l  nea durante las mediciones  En este modo el DTR  tambi  n recarga las  bater  as NiCd     LOW BATTERY  BATERIA BAJA  se presenta cuando las bater  as inter   nas se aproximan a un voltaje bajo  Cuando se presenta  todav  a se puede  realizar un n  mero limitado de mediciones  aunque recomendamos recar   gar el DTR  lo antes posible  Si el voltaje de la bater  a cae muy bajo  el  DTR  bloquea cualquier operaci  n ulterior  En este modo bloqueado  el  DTR  apaga todas las funciones hasta que se conecta a la energ  a AC y  se recarga la bater  a     Recomendamos recargar el DTR  durante la no
23. e consis   tent with the packing list  Notify your distributor of any missing items  If  the equipment appears to be damaged  file a claim immediately with the  carrier and notify your distributor at once  giving a detailed description of  any damage  Save the damaged packing container to substantiate your  claim     1 3 Ordering Information    Digital Transformer Ratiometer Model 8500  115            Cat   2111 80  Includes ratiometer   factory preset 115V  50 60Hz input  NiCd batteries  installed   115V  power cord  set of 15 ft cables in a carrying bag  warranty card and user manual     Digital Transformer Ratiometer Model 8500  230V          Cat   2116 21   Includes ratiometer   factory preset 230V  50 60Hz input  NiCd batteries  installed   power  cord with stripped end  no receptacle plug   set of 15 ft cables in a carrying bag  warranty  card and user manual     1 3 1 Accessories and Replacement Parts    Test lead set  30 ft  in carrying bag                                       Cat   2118 47  Replacement set of test leads  15                                       Cat   2118 48  Replacement 12V NiCd batteries  set of two                        Cat  42118 57  Fuse  set of 5    5    2250                 Cat  42118 53   5 x 20mm  slow acting  for 230V power input and main board    F  se  set of 5  4A72425W        2 Dau      Cat  42118 54   5 x 20mm  slow acting  for 115V unit only    Fuse  set of 5  4A 7125V  iit ee ie te Cat  42118 55     5 x 20mm  slow acting     Order 
24. e high voltage winding  XRED      XBLACR should be attached to the low voltage winding     High Excitation Current  Check test cable connections for inadvertent short circuits  Check for  shorted transformer windings     Check Cables  amp  Connections   Verify that all test cable connections have been made correctly and are  firmly attached to the transformer terminals  Inspect transformer terminals  for dielectric coatings  fungus and corrosion     Low Battery  Low battery indication  Recharge the batteries immediately   Note  The DTR  can be operated during battery charging     Calibrating Please Wait  The DTR  always self calibrates upon power up  The DTR  will also  automatically self calibrate       atperiodic intervals    after 32 sequential test cycles have been performed      following the detection of any error in which the DTR  automati   cally cancels the test in progress    VT PT Test Mode  Operation mode used in VT PT testing  power up default mode    VT PT Test Mode Ready  Indicates system ready for VT PT testing    CT Test Mode Selected  Indicates user selection of CT Test Mode  Mode selected by depressing  and holding TEST button during power up sequence     16 Digital Transformer Ratiometer          Model 8500    CT Test Mode Ready  Indicates system ready for CT testing    X Circuit  OPEN  or CONT   Refer to the VT PT Continuity Test section    H Circuit  OPEN  or CONT   Refer to the VT PT Continuity Test section    Low X Signal  Check X cables for inadverten
25. ectrical                                                                3  1 2 Receiving Your                                      4  1 3 Ordering                                             4  1 3 1 Accessories and Replacement Parts                              4  2  PRODUCT FEATURES                                                                        5  2 4   Description  ona teret dte tete yE a dee eee eR ua ss 5  2 2 Control               5                  6  3  SPECIFICATIONS                                                                              7  3 1  Electrical     a te eed tite 7  3 2  Mechanical           Ginnie Debe ge 8  3 3 Cable Identification                                                                     8  4   OPERATION aa a A                                                                                                9  4 1 Conducting a Test    aee        9  4 2 Mode                                                              9  43 NT PR E  PEN 10  4 3 1 VT PT Example Connections                                       10  43 2 VTPT Testing                               eet etel 11  4 3 3      Test Mode Flow                                                       12  4 3 4  VT PT Excitation Current                                             13  4 3 5 VT PT Continuity Test                                                  13  A A A 14  4 4 1 CT Example Connections                                             14  442 CT Testing    ee C ER data 14  4
26. es an advanced  low voltage  step down measurement  technique in which the high voltage  H  winding is subjected to test  excitation  This results in greater operator safety and the ability to test  a much wider array of transformer types and sizes     Digital Transformer Ratiometer DTR  Model 8500 5    2 2              oN Oa Rom    Control Features    c TRANSFORMER RATIO  MODEL 8500                   Display   Battery Charge Indicator   AC Power Inlet   Line Fuse Tray   Display Contrast Adjustment   TEST Push button   Main Power Switch   Low side  X  cable connector  secondary     High side  H  cable connector  primary     Digital Transformer Ratiometer DTR  Model 8500    CHAPTER 3    SPECIFICATIONS    3 1 Electrical    Ratio Range  C        Autoranging  0 8000 to 1500 0 1    Accuracy   Ratio    10 to 1     0 296 of Reading  Ratio  lt  10 to 1000 to 1    0 1  of Reading  Ratio 2 1000 to 1     0 296 of Reading    Excitation Signal  PT VT Mode  44Vrms maximum  CT Mode  Auto Level 0 to 1A  0 1 to 5Vrms    Excitation Current Display  Range  0 to 1000mA  Accuracy  2       2mA    Excitation Frequency  70Hz    Display   LCD Character  20 x 2  large format  LED backlight  day night visible    Measurement Method  In accordance with ANSI IEEE C57 12 90    Power Supply    Dual operation  rechargeable NiCd battery  amp  115 230V  50 60Hz line  supply  DTR  may be changed from 115 230V by internal switch at any  time  Units available with factory presetting of 115V or 230V     Batteries 
27. es de  prueba X hace de bobinado secundario de una vuelta     TRANSFORMADOR DE CORRIENTE       X NEGRO    4 4 2 Prueba CT    1  Cuando el instrumento est   ajustado para una prueba CT  el DTR    mostrar   el mensaje  CT Test Mode Selected  despu  s de la secuen   cia de encendido inicial  Este mensaje indica que el DTR  est   listo  para realizar una prueba     2  Pulse una vez el bot  n TEST para comenzar el ciclo de prueba     3  El siguiente mensaje que se presenta es   Ratio Testing  TEST  to  Cancel    Prueba de Raz  n  TEST  para Cancelar   El asterisco        va a parpadear mientras dura la prueba  La prueba puede ser cance   lada en este momento pulsando una vez el bot  n TEST  Si la prueba  contin  a  se mostrar   la Raz  n y la Corriente de Excitaci  n     4  Una vez que los resultados de la prueba han sido registrados  pulse  el bot  n  TEST  para reiniciar para la pr  xima prueba       A NOTA  Hay CTs de baja masa  de baja raz  n donde el DTR  puede  no ser capaz de proporcionar la raz  n correcta  El mensaje de error  ser    High Excitation Current  alta corriente de excitaci  n      Al igual que en el Modo de Prueba VT PT  esta rutina puede ser repe   tida tantas veces como sea necesario sin apagar la unidad  El Modo de  Prueba CT permanece activo hasta que se apaga la unidad     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 39    4 4 3 Diagrama de Flujo del Mode de Prueba CT    Mensaje del Display Acci  n del               Para el Modo PT CT Opera
28. i  n    Revise las conexiones de los cables de prueba por posibles cortocircuitos  inadvertidos  Revise cortocircuitos en los bobinados del transformador     Check Cables  amp  Connections   Revise Cables  amp  Conexiones    Revise que todas las conexiones de los cables de la prueba han sido  hechas correctamente y est  n unidas firmemente al transformador   Inspeccione los terminales del transformador por posibles recubrimientos  con diel  ctricos  hongos y corrosi  n     Low Battery   Bater  a Baja    Indicaci  n de bater  a baja  Recargue las bater  as inmediatamente   Nota  El DTR  puede ser operado durante la recarga de las bater  as     Calibrating Please Wait   Calibrando Por Favor Espere    EI DTR  siempre se autocalibra luego de encendido  El DTR  tambi  n se  autocalibra    e aintervalos peri  dicos  e despu  s que se han completado 32 ciclos de prueba secuenciales    e luego de detectar cualquier error en que el DTR  autom  ticamente  cancela la prueba en curso    VT PT Test Mode   Modo de Prueba VT PT    Modo de operaci  n utilizado en las pruebas VT PT  modo preestablecido  al encender     VT PT Test Mode Ready   Modo de Prueba VT PT Listo    Indica que el sistema est   listo para la prueba VT PT     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 41    CT Test Mode Selected   Modo de Prueba CT Seleccionado     Indica la selecci  n del Modo de Prueba CT por el usuario  Este modo se  selecciona presionando y manteniendo presionado el bot  n TEST durant
29. i  n td AS 30   2 2 Descripci  n del                               31   3  ESPECIFICACIONES                                                                        32   331  DENS CUNGAS d usse tette ert 32   3 2                                  tub edge b cue vua 33   3 3 Identificaci  n de Cables                       sss 33   4  UTIIZAGI  N    ia 34   4 1 Para realizar una prueba                      34   4 2 Selecci  n de                          34   43  NTP A EE ESA 35   4 3 1 Ejemplos de Conexiones VT PT                                  35   43 2  Prueba VT PT iiie tate tt ctt eee tees 36   4 3 3 Diagrama de Flujo del Modo de Prueba VT PT           37   4 3 4 Corriente de Excitaci  n VT PT                                     38   4 3 5 Prueba de Continuidad VT PT                                     38   AA UO Tui ttai eb Niel o      e e    O 39   4 4 1 Ejemplo de Conexi  n CT                                             39   442    Prueba              eet e ed debes 39   4 4 3 Diagrama de Flujo del Mode de Prueba CT                40   4 5 Mensajes                   5                         41   4 6  Alimentaci  n   i ra         pe de nd 42  4 7 Cambiar el Voltaje de la Fuente de Poder de   115V a 230V o de 230V a 115                                                43   4 8 Consejos para Hacer Mediciones de Raz  n Precisas               44    Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 25    26    4 9 Prueba de Raz  n 1 1                  esses 45  4 10 Po
30. idor de Raz  n de Transformador Digital DTR2 Modelo 8500 37    4 3 4 Corriente de Excitaci  n VT PT    La Corriente de Excitaci  n  mostrada en miliamperes  es la corriente RMS  en el bobinado H causada por la excitaci  n de prueba  durante una carga  despreciable del bobinado X asociado     El DTR usa para las pruebas una sefial de excitaci  n de 44V m  ximo   luego el valor de la corriente de excitaci  n mostrado ser   casi siempre  una peque  a fracci  n de la excitaci  n sin carga del transformador bajo  prueba a un voltaje  nominal  total  La mayor  a de los transformadores  requerir  n 100mA o menos  algunos requerir  n menos de 1mA     Nota  Si Usted actualmente est   usando un medidor de raz  n que  emplea una excitaci  n por elevaci  n de voltaje en el lado  X   ejem   plo  instrumentos de manivela corrientes   la corriente de excitaci  n  mostrada por el DTR  ser    en la mayor  a de los casos  significati   vamente menor  Esto es normal y se produce directamente por el  hecho que en la mayor  a de los transformadores que bajan voltaje   el bobinado H presenta una impedancia mucho m  s alta que su  bobinado X asociado        4 3 5 Prueba de Continuidad VT PT    La funci  n de Prueba de Continuidad del DTR  Modelo 8500 sirve como  un medio   til para identificar bobinados primarios y secundarios abiertos   desconectadores abiertos  y fusibles quemados  Cuando se lo selecciona   el DTR  comprueba alternativamente la continuidad de sus cables X y de  sus cables H     L
31. la On Off Switch    Battery Pack          Power Supply  Voltage Selector   Black Body  Red Switch     115 V Setting Position  230 V Setting Position    Ea     Switch Position for Power    Su i         15V 20   3909    The instrument s power supply setting can be changed from 115 to 230V  by following the procedure below     1  Turn the power OFF and unplug instrument from all inputs and  power     Unscrew all four bottom screws   Remove instrument from case     Locate switch next to transformer  see drawing      gu Re seo  OMS    Set red switch 115V or 230V as appropriate   Switch setting indicates the selected supply voltage     6  Replace the fuse  see power inlet  with appropriate current rating   115V   1A  230V   0 5A    7  Carefully reinstall instrument into the case and fasten bottom screws     8  Remove old voltage label  Affix input voltage label  115V or 230V   under the AC power inlet     18 Digital Transformer Ratiometer         Model 8500    4 8 Tips for Making Precise Ratio Measurements    NOTE  The DTR is designed to test step down transformers  It works  with low voltage on the primary  limited to 40V max  If the secondary  reaches 40V before the primary  a safety feature stops the mea   surement  The recommended procedure to test step up transform   ers is to reverse the low and high leads and read the reverse ratio          Always verify the integrity of test cable connections and reposition test  clips as necessary  Inspect transformer terminals for dielect
32. lado primario extremadamente alta   No se requiere en la mayor  a de los transformadores de derivaci  n  variable ni en los reguladores     Al probar transformadores polif  sicos  tenga en mente que en algunos  casos  las razones medidas deben ser multiplicadas o divididas por  13  Refi  rase al   4 10 para los diagramas de conexiones polif  sicas y  las ecuaciones de raz  n asociadas     Medidor de Raz  n de Transformador Digital         Modelo 8500    4 9 Prueba de Raz  n 1 1    Se puede hacer una prueba sencilla para ensayar el funcionamiento del  DTR    Al conectar HRoJo a XroJo  y  separadamente  HNEGRO a XNEGRO   se simula un transformador 1 1  Al operar el DTR  con esta configuraci  n  se deber  a obtener una raz  n casi igual a 1 000  Si no se obtiene  el DTR    puede necesitar reparaci  n o calibraci  n     H ROJO X ROJO 1 1    H NEGRO X NEGRO    CONEXIONES EQUIVALENTE    Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 45    4 10 Polyphase Connections      TRANSFORMADOR   BOBINADO   BOBINADO  TIPO  BOBINADO DE   BOBINADO DE            VOLTAJE   VOLTAJE  VOLTAJE ALTO   VOLTAJE BAJO ALTO BAJO           12  AA    X  X       A A  STD          X  A A  REV    X  A Y  STD  A Y  REV  H   Y Y  POH STD  I Y Y  REV  Y A  STD   A       cH             H  X   YN  N   Hl          x     H  X  a  AM  H  A H  Xo  H   B 4 N  H  A H   H   B     C  H  X      B  H   H    Y  REV          B  2  3               46 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    CAP
33. limentaci  n   115V   1 A  230V   0 5A    Reinstale cuidadosamente el instrumento en la carcasa y asegure los  tornillos de su base     Remueva la etiqueta con el antiguo voltaje  Coloque una etiqueta con  el nuevo voltaje de entrada  115V o 230V  debajo de la entrada de  alimentaci  n AC     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 43    4 8 Consejos para Hacer Mediciones de Raz  n Precisas    NOTE  El DTR est   dise  ado para probar transformadores que  bajan voltaje  Opera con bajo voltaje en el primario  limitado a 40V  m  ximo  Si el secundario alcanza 40V antes que el primario  un  dispositivo de seguridad detiene la medici  n  El procedimiento  recomendado para probar transformadores que elevan voltaje es  invertir los terminales de baja y de alta y leer la raz  n inversa        44    Siempre verifique la integridad de las conexiones de los cables de  prueba y reubique las pinzas de prueba si es necesario  Inspeccione  los terminales del transformador por posibles recubrimientos diel  ctri   cos  hongos y corrosi  n     Durante el Modo de operaci  n VT PT  seleccione Continuity Test   Prueba de Continuidad  cuando sea posible  Adem  s de ser una  manera   til de probar bobinados y conexiones  esta prueba tiene el  beneficio adicional de disminuir el magnetismo remanente en el trans   formador bajo ensayo  Esto es importante primeramente en transfor   madores con una alta resistencia en serie  y en transformadores de  bajo KVA con una inductancia del 
34. lyphase                                              46  MANTENIMIENTO                                                                           47  5 1 Reparaci  n    Calibraci  n                                 47  5 2 Asistencia t  cnica y venta                                                        48  5 3 Garant  a Limitada                                                   ieri ii 48  5 4 Garant  a de Reparaci  n                                                          48    Medidor de Raz  n de Transformador Digital         Modelo 8500    CAPITULO 1  INTRODUCCI  N    ZN ADVERTENCIA   N    Estas advertencias de seguridad se entregan para garantizar la  seguridad del personal y la operaci  n adecuada del instrumento         Lea el manual de instrucciones completamente y siga toda su  informaci  n de seguridad antes de intentar usar o reparar este  instrumento     El Medidor de Raz  n de Transformador Digital DTR   Modelo  8500 est   dise  ado para ser usado en transformadores no   energizados solamente  Aseg  rese que el equipo a probar  est   completamente desconectado de la fuente de alimenta   ci  n AC y est   totalmente descargado     S  lo personal calificado deber  a usar el Modelo 8500     El DTR  no debe ser usado confiando en que cualquiera de sus  componentes  incluyendo los cables de prueba  proporciona  protecci  n contra un choque el  ctrico  Ninguno de los compo   nentes del DTR  proporciona protecci  n aislaci  n contra alto  voltaje  Siempre aseg  rese que
35. nce   may appear as open circuits to the DTR         An OPEN indication will not cancel the test cycle in progress and the  results of ratio testing will still be displayed       Transformers whose winding arrangement involves multiple  parallel  paths  e g  Delta connected types  may read CONT  when in fact one  or more windings may be open     Digital Transformer Ratiometer DTR  Model 8500 13    44 CT    4 4 1 CT Example Connections    Current Transformer  CT  ratio testing is performed by connecting the H  cable set to the X winding  and by shorting the X cable set through the  CT aperture  as depicted below  This creates a step down configuration  in which the X winding serves as the primary circuit  and the X cable set  serves as a one turn secondary winding     CURRENT TRANSFORMER       X BLACK    4 4 2 CT Testing    1  When the instrument is set for CT testing  the DTR  will display the CT  Test Mode Selected message after the initial power up sequence  This  message indicates that the DTR  is now ready to execute a test     2  Press the TEST button once to begin the test cycle     3  The next message displayed is  Ratio Testing  TEST  to Cancel  The  asterisk       will blink as testing proceeds  Testing may be cancelled at  this time by pressing the TEST button once  If the test continues  Ratio  and Excitation current will be displayed     4  Oncetest results are recorded  press the TEST button to reset for the  next test     NOTE  There are certain low mass  low ra
36. nducting a Test    1  Connectthe DTRS test cables in the proper manner to a non energized  transformer  Refer to Connection Examples  84 3 1 and 84 4 1      2  Turn the DTR  ON and select the proper test mode  Refer to Mode  Selection below     3  At Ready  press the test button to begin  Following a brief test cycle   Ratio  Polarity and Excitation Current will be displayed     Please refer to VT PT Testing and CT Testing sections of this manual for  complete operating information  84 3 2 and 84 4 2      4 2 Mode Selection    The operating mode of the DTR  is configured at power up of the instru   ment  The default test mode is VT PT  To enter the CT Test Mode  depress  the TEST button while turning the instrument on  and hold until CT Test  Mode Selected is displayed       Use the VT PT Test Mode for testing voltage and potential transformers   maximum 44V test excitation        Use the CT Test Mode for testing current transformers  maximum 5V  test excitation        The DTR  automatically reverts to the VT PT Test Mode when power is  turned off     Digital Transformer Ratiometer DTR  Model 8500 9    4 3  VT PT    4 3 1           Example Connections    Here is an example of connections to an ordinary 7200 120 240 distribution  transformer with center tapped secondary winding       Typical Connection       RATIO 60 00   1  PRIMARY SECONDARY  7200   240CT        lt      X RED  H RED  QZ X BLACK      1  X BLACK                    Alternate Connection  RATIO 30 00   1  PRIMARY 
37. nstruments will  at its  option  repair or replace the faulty material     REGISTER ONLINE AT     www aemc com             Warranty Repairs    What you must do to return an Instrument for Warranty Repair     First  request a Customer Service Authorization Number  CSA   by phone  or by fax from our Service Department  see address below   then return the  instrument along with the signed CSA Form  Please write the CSA  on the  outside of the shipping container  Return the instrument  postage or shipment  pre paid to    Chauvin Arnoux    Inc  d b a  AEMC   Instruments   Service Department   15 Faraday Drive   Dover  NH 03820 USA   Tel   800  945 2362  Ext  360     603  749 6434  Ext  360   Fax   603  742 2346 or  603  749 6309  repair aemc com    Caution  To protect yourself against in transit loss  we recommend you insure  your returned material     NOTE  All customers must obtain a CSA  before returning any  instrument     24 Digital Transformer Ratiometer DTR2 Model 8500    Tabla de Contenidos          ENGLISH cenar Dep eee 02 De eta ER      1   ESPA  OL    a EE EA  25   T  INTR0ODUCCI  N                                                                              27   1 1 S  mbolos El  ctricos Internacionales                                        28   1 2 Recepci  n De Su Embarque                                                    28   1 9  EMBAT        eee rette Renee      28   1 3 1    ACCOSOMOS nin eene ot ba aa to eo e Lee e 29   2  PRESENTACI  N nd 30   2 1    Descripc
38. omento pulsando el bot  n  TEST  una vez  Si la prueba  contin  a  se mostrar   la Raz  n y la Corriente de Excitaci  n     Una vez que los resultados de la prueba han sido registrados  pulse  el bot  n  TEST  para reiniciar para la pr  xima prueba     Esta rutina puede ser repetida tantas veces como sea necesario sin  apagar el instrumento     36    Medidor de Raz  n de Transformador Digital         Modelo 8500    4 3 3 Diagrama de Flujo del Modo de Prueba VT PT    Mensaje del Display Acci  n del  Para el Modo VT PT Operador    3    Indica version               1999 me Encienda la Unidad zm del Programa de  SE          Instrucciones Interno  AEMC  Instruments alli   N A  DTR   Model 8500 m       N A sas  dentificaci  n del Modelo    Comentarios    Y Reemplaza el Mensaje  e     AERC sree   YI m  i ser Recargadas    PT VT Test Mode N A Indicaci  n del  Modo Seleccionado    Calibrating N A Calibraci  n Interna  Please Wait en Curso    VT PT Test Mode Pulse TEST Ahora Sistema Listo para   Exi  A   Ready para Iniciar la Prueba Comenzar la Prueba    Y           Pulse TEST Ahora    Press  TEST  to para Comprobar     me Selecci  n de la Opci  n  Check Continuity Continuidad o no haga Prueba de Continuidad    nada para salt  rselo    Y         Pulse TEST Ahora Prueba de Raz  n en  Ri T  WEIT Mesi para Cancelar          Curso con la Opci  n  i la Prueba en Curso de Cancelar la Prueba  Pulse TEST Ahora    para Reiniciar  para la Pr  xima Prueba    Ratio  60 00  1  Current  11 mA    Med
39. por favor refi  rase a las sec   ciones Prueba VT PT y Prueba CT de este manual  84 3 2 and 84 4 2      4 2 Selecci  n de Modo    El modo de operaci  n del DTR  se configura al encender el instrumento   El modo de prueba preestablecido es VT PT  Para entrar al modo de  prueba CT  presione el bot  n TEST mientras enciende el instrumento  y  mant  ngalo presionado hasta que aparezca CT Test Mode Selected       Use el Modo de Prueba VT PT para probar transformadores de voltaje  y de potencia  excitaci  n de prueba de 44V m  ximo        Use el Modo de Prueba CT para probar transformadores de corriente   excitaci  n de prueba de 5V m  ximo        El DTR  autom  ticamente vuelve al Modo de Prueba VT PT al ser  apagado     34 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    4 3  VT PT    4 3 1 Ejemplos de Conexiones VT PT    He aqu   un ejemplo de conexiones a un transformador de distribuci  n  corriente 7200 120 240 con un bobinado secundario con derivaci  n cen   tral       Conexi  n T  pica    Raz  n 60 00 1    H ROJO       PRIMARIO SECUNDARIO  7200   240CT      De  gt   gt  cupo    ROJO  H ROJO  H NEGRO     u    X NEGRO      H NEGRO     X NEGRO    du         Conexi  n Alternativa    Raz  n 30 00 1    PRIMARIO SECUNDARIO    7200 240CT  HROJO DS  lt  ALE xRoJo    H NEGRO       lt      NEGRO       Nota  A diferencia de otros instrumentos  el DTR  Modelo 8500 no  impone restricciones de polaridad o auto conexiones    obligadas      luego hay varios tipos de conexiones 
40. rded calibration data      Chauvin Arnoux    Inc  d b a  AEMC  Instruments  15 Faraday Drive   Dover  NH 03820 USA  Tel   800  945 2362  Ext  360     603  749 6434  Ext  360   Fax   603  742 2346 or  603  749 6309  repair aemc com     Or contact your authorized distributor     Costs for repair  standard calibration  and calibration traceable to N I S T  are  available     NOTE  All customers must obtain a CSA  before returning any  instrument        LIr Technical and Sales Assistance       North South America  Australia  New Zealand     If you are experiencing any technical problems  or require any assistance with  the proper operation or application of your instrument  please call  mail  fax or  e mail our technical support hotline    Chauvin Arnoux    Inc    d b a  AEMC   Instruments   200 Foxborough Boulevard   Foxborough  MA 02035  USA   Phone   800  343 1391    508  698 2115   Fax   508  698 2118   techsupport aemc com   www aemc com    NOTE  Do not ship Instruments to our Foxborough  MA address     22 Digital Transformer Ratiometer         Model 8500                 Repair and Calibration     Europe  Asia  Africa   To ensure that your instrument meets factory specifications  we recommend    that it be submitted to our factory Service Center at one year intervals for reca   libration  or as required by other standards or internal procedures     For instrument repair and calibration     For instrument repair and or calibration  please call our European Repair  Center    M
41. ric coat   ings  fungus and corrosion       During VT PT Mode operation  select Continuity Test when possible   Besides being a useful way to check windings and connections  this  test has the added benefit of reducing magnetic remnants in the trans   former under test  This is important primarily in transformers with high  series resistance  and in low KVA transformers with extremely high pri   mary side inductance  It is not required in most tap change and regula   tor transformers       Whentesting polyphase transformers  keep in mind that in some cases   measured ratios must be multiplied or divided by V3  Refer to    4 10 for  polyphase connections diagrams and associated ratio equations     4 9 Ratio Test   1 1    A simple test can be conducted to test functionality of the DTR9  By  connecting HRED to XRED  and  separately  HBLACR to XaLack  a 1 1  transformer is simulated  Operation of the DTR  in this configuration  should yield a ratio very nearly equal to 1 000  If it does not  the DTR  may  require repair or calibration     H RED X RED           H BLACK X BLACK    CONNECTIONS EQUIVALENT    Digital Transformer Ratiometer DTR  Model 8500 19    4 10 Polyphase Connections    VOLTAGE   VOLTAGE  WINDING   WINDING      TRANSFORMER    TYPE    HIGH VOLTAGE   LOW VOLTAGE  WINDING WINDING          XFM  19  STD  A A  A A   Y   Y  REV    R  A  STD  Y Y  STD    Y Y  REV       Y A  STD    Y A  REV       z      7  8           20 Digital Transformer Ratiometer          Model 8500  
42. t short circuits   X winding may be shorted or transformer circuit breaker may be open     Low H Signal  Check H cables for inadvertent short circuits   Check H cable connector at DTR  front panel     4 6 Power Supply    The DTR  Model 8500 may be used for up to 10 hours on fully charged  NiCd batteries  The DTR  may also be line supplied during measurements   In this mode the DTR  also recharges the NiCd batteries     LOW BATTERY is displayed when the internal batteries approach low  voltage  When displayed  a limited number of measurements may still  be conducted  though we recommend recharging the DTR  as soon as  possible  If the battery voltage drops too low  the DTR  will lock out further  operation  In the lock out mode  the DTR  shuts down all functions until  AC power is applied and the battery recharged     We recommend recharging the DTR  overnight  Each time the DTR  is  connected to AC power  a 14 hour recharge cycle begins  Repeat charging  of partially discharged batteries will not result in battery damage  During  the 14 hr cycle  the CHARGING indicator will glow continuously  following  this period  a pulse trickle charge mode is entered and the indicator will  pulse on and off     Digital Transformer Ratiometer DTR  Model 8500 17    4 7 Changing Power Supply Setting from  115V to 230V or 230V to 115V                    LIAME TRANSFORMER FA       aa MODEL 8500          Power Input  Fuse    Input Voltage Label   to match power supply  voltage switch setting   
43. tico O   1A  0 1   5Vrms    Presentaci  n de Corriente de Excitaci  n   Rango  0   1000mA  Exactitud  2       2mA    Frecuencia de Excitaci  n  70Hz    Display  Caracteres LCD  20 x 2  formato grande  LED con iluminaci  n  posterior  visibles de d  a noche     M  todo de Medici  n  de acuerdo con ANSI IEEE C57 12 90  Alimentaci  n  Doble operaci  n  bater  a NiCd recargable  amp  l  nea de  115 230V  50 60Hz  Se puede cambiar el DTR  entre 115 230V mediante    un interruptor interno en cualquier momento  Unidades disponibles  preajustadas en f  brica a 115V o 230V     Bater  as  Paquetes de 5 x 2 NiCd  12V  1300mAH  Panasonic P 130SCR  o equivalente    Vida de la Bater  a   Hasta 10 hrs en operaci  n continua   Puede utilizarse mientras se recarga  Indicador LCD de bater  a baja     Tiempo de Carga  14 hrs t  picas  a velocidad C 10    Fusible de la Alimentaci  n   115V  1 0A  5 x 20mm  acci  n lenta  230V  0 5A  5 x 20mm  acci  n lenta      23  C   5  C  50 a 70  HR  bater  a cargada totalmente  sin campos externos o ruido     32 Medidor de Raz  n de Transformador Digital DTR  Modelo 8500    3 2  Mecanicas    Conexiones  Conectores Cannon  XLR  amp  pinzas industriales grandes  con c  digo de color    Cables de Prueba  15 pies  H  amp  X con c  digo de color  en un estuche de  transporte    Display  Alfa num  rico de doble l  nea 3 875 x  875  con ajuste de contraste  e iluminaci  n posterior    Temperatura de Operaci  n   0   a 50  C  32   a 122  F   O a 90  HR  sin condens
44. tio CT s where the DTR    may not be able to provide the correct ratio  The error message will  be  High Excitation Current      As in VT PT Test Mode  this routine may be repeated as many times as    needed without powering down the unit  The CT Test Mode remains active  until the unit is powered down     14 Digital Transformer Ratiometer DTR2 Model 8500    4 4 3 CT Test Mode Flow Chart    Display Indication Operator  for CT Test Mode Action    Turn Unit ith  en A 1997 Tem Pls le bul of  C   rnoux Depressed nternal Firmware    AEMC  Instruments           Hold TEST Butt  DTR  Model 8500 mum HO utton s   Model Identification    Y    e Replaces Above Indication     dels ments mem Hold TEST Button s when Batteries Need    i      Recharging  CTTestMode     Release TEST Button                             Selected Mode    Calibrating Internal Calibraiton  Please Wait in Progress  CT Test Mode Push TEST Now System Ready to  Ready to Initiate Testing Begin Testing   Ratio Testing EU TES MON   TEST  to Cancel    to Cancel E    Test in Progress  Ratio  40 00   1  Current  35 mA    Comments         Ratio Testing  in Progress with  Test Cancel Option    Push TEST Now to  Reset for Next Test    Digital Transformer Ratiometer DTR  Model 8500 15    4 5  Displayed Messages    Check for H      X Cable Reversal   The DTR may have detected a potentially hazardous step up condition  while attempting to test the transformer as connected  Verify connections   HRED 8 HBLACR should be attached to th
45. v  lidas y se puede probar vir   tualmente todas las configuraciones de transformadores  En todas  las pruebas  un signo negativo que precede la raz  n mostrada  indica una inversi  n de fases  polaridad invertida  de la se  al  detectada en X respecto de la se  al de excitaci  n en H  Al usar el  DTR     fijese siempre en el c  digo de color de los capuchones de  los cables de prueba     Medidor de Raz  n de Transformador Digital DTR2 Modelo 8500 35    4 3 2 Prueba VT PT    1     Cuando el instrumento est   ajustado para una prueba VT PT  el DTR    mostrar   el mensaje  VT PT Test Mode Ready  despu  s de la secuen   cia inicial de encendido  Este mensaje indica que el DTR  est   listo  para realizar una prueba     Pulse el bot  n TEST una vez  CUIDADO  No se debe realizar la  prueba mientras haya personal manejando las conexiones del trans   formador      Se mostrar   durante 3 segundos  Press  TEST  to Check Continuity    pulse  TEST  para comprobar la continuidad   Si se desea una prueba  de continuidad  se debe pulsar en ese momento el bot  n TEST una  vez  Los resultados de la prueba de continuidad se mostrar  n como  CONT continuo  o OPEN abierto  para ambas conexiones X y H  Para  m  s informaci  n refi  rase a Prueba de Continuidad VT PT  p  gina  12      El siguiente mensaje que se muestra es             Testing  TEST  to  Cancel    Prueba de Raz  n  TEST  para cancelar   El asterisco     va  a parpadear mientras dura la prueba  La prueba se puede cancelar  en este m
    