Installation Manual Manuel d`installation

image

Contents

1. 088L3380 01 01 05 2007 088L3380 01 01 05 2007 20 Danfoss can accept no responsibility for possible errors in catalogues brochures other printed materials and website information Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alteration can be made without subsequent changes being necessary in specifications already agreed upon All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are registered trademarks of Danfoss A S All rights reserved Danfoss Inc 6711 Mississauga Road Suite 410 Toronto ON a n O S S L5N 2W3 aad E EEE BRINGING WARMTH TO LIFE www DanfossLX com Copyright 2007 Danfoss Inc 088L3380 01 01 05 2007 Printed in Canada
2. Le logiciel gratuit de Danfoss disponible aupr s de www DanfossLX com pourra vous aider quant au plan d implantation Etape 2 TRANSFERT DU PLAN AU PLANCHER Dessinez le plan sur le faux plancher de la pi ce Dessinez la place occup e par tous les meubles non install s encore D roulez les quelques premiers pieds de LXmat Marquez l emplacement du lieu de connexion entre le cable d alimentation et le cable de chauffage rouge Cette connexion doit se trouver a l int rieur du ciment a pose simplifi e ou du ciment autonivelant Si vous avez un thermostat capteur au plancher p ex LXstat 430 marquez l emplacement du capteur qui devrait se trouver au milieu des deux cables de chauffage soit a environ 25 cm 10 po a l int rieur du tapis aussi pr s que possible du thermostat Etape 3 POSEDU CONDUIT DU CAPTEUR recommended in conduit part 19809099 Il faut installer le conduit flexible du capteur compris entre le b ti mural du thermostat et le capteur au cas o il serait n cessaire de changer le capteur Ce conduit doit tre frais dans le faux plancher Taillez un canal d environ 5 16 po de profond et 5 16 po de large dans le plancher et dans le mur jusqu au thermostat en vue d y ins rer le conduit du capteur Ce conduit doit aller du thermostat vers le milieu du plancher se terminant au moins 10 po du mur Il est important de placer le conduit du capteur entre deux fils de chauffage rouges Au moyen de
3. Step 9 ENJOY THE COMFORT OF Danfoss LX The LX floor heating system is now ready to use Increase the floor temperature gradually and adjust it until it reaches a comfortable level depending on the type of room and your personal preferences How to claim this warranty EXTENDED WARRANTY THE FOREGOING WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED ON THE PART OF DANFOSS DANFOSS DISCLAIMS ANY WARRANTY EXPRESS OR IMPLIED OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE DANFOSS NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON FIRM OR CORPORATION TO ASSUME FOR IT ANY OTHER LIABILITY IN CONNECTION WITH SALE OR PRODUCT DANFOSS SHALL NOT BE HELD RESPONSIBLE FOR DAMAGE TO PERSON OR PROPERTY CONSEQUENTIAL LOSS LOSS OF PROFIT LOSSES ON GOODS IN STORE OR THE LIKE WHICH MIGHT ARISE OUT OF THE FAILURE OF THE EQUIPMENT DELIVERED IRRESPECTIVE OF THE CAUSE INCLUDING FAULTY MANUFACTURE Contact the company s Customer Service department and provide the following information 1 2 3 4 5 Nature of the manufacturing defect Date of purchase and if already installed date ofinstallation If installed name of electrician and flooring installer Resistance readings taken by installer Proof of purchase and serial number from product label Our Customer Service department will provide you with an authorization number and advise you on the next steps to complete your warranty claim 088L3380
4. 01 01 05 2007 Disclaimer This warranty gives you specific legal rights and you may also have some legal rights which may vary from state to state or province to province Danfoss hereby disclaims and it is as a condition of the sale that there are no implied warranties Some states and provinces do not allow limitations on an implied warranty so the above limitation may not apply to you Manufacturer Mail Danfoss Inc 6711 Mississauga Rd Suite 410 Toronto ON L5N 2W3 Phone 905 285 2050 Fax 1 866 676 8062 905 285 2055 088L3380 01 01 05 2007 Dispositif de chauffage de plancher DanfossLX ATTENTION Il est important que cette nappe chauffante soit install e uniquement par un lectricien agr qui conna t le calibrage le mode d installation la construction et le fonctionnement des syst mes de chauffage de plancher ainsi que les risques y associ s Le tapis chauffant a t con u des fins de chauffage par dessous le plancher seulement Nota L installation doit se faire conform ment aux instructions du fabricant et aux codes nationaux et locaux Elle doit respecter la section 424 J American National Standards Institute National Fire Protection Association ANSI NFPA70 le National Electric
5. This will allow the sensor to be easily replaced in the unlikely event of failure The sensor and or tube needs to be installed between the thermostat wall box and the sensor position The conduit tube must be partially countersunk into the subfloor Cut a channel in the floor and wall up to the thermostat large enough to accommodate the sensor conduit The conduit has to go from the thermostat and minimum of 10 away from the wall towards the middle of the floor 088L3380 01 01 05 2007 088L3380 01 01 05 2007 IMPORTANT the sensor conduit must be centered in the cable loop between two red heating wires Use duct tape to close the end of the conduit so that thinset can t penetrate the conduit Use duct tape to hold the sensor conduit into the groove to prevent it from floating up when the mortar or thinset is poured If the sensor is installed directly in the mortar bed use duct tape to secure to subfloor Step 4 PREPARE SUBFLOOR SURFACE Clean and vacuum the floor thoroughly and remove dust and debris from the floor that may damage the heating cable or reduce adhesion Ensure that the subfloor is secure and stable Carefully fill in all cracks to prevent any potential damage to the new tiles resulting from shifts in the subfloor Optional To ensure maximum adhesion apply a primer or sealer as recommended by the thinset or self leveling cement manufacturer If using a primer ensure that the entire floor
6. is covered Allow the primer to dry thoroughly before proceeding to the next steps Step 5A MEASURE THE RESISTANCE Use a digital ohm meter to measure the resistance of the LX mat and compare it to the resistance listed on the product label Record the measured resistance on the warranty card Documenting the resistance at each stage of installation is required for warranty purposes 088L3380 01 01 05 2007 Step 5B INSTALLTHE LX MAT An adhesive has been added to the bottom of the mat which will prevent the mat from moving during installation Start by placing the mat such that the connection point and the temperature sensor are in their intended positions and bring the power cable to the thermostat or connection box Begin rolling the LX mat evenly across the floor outside the areas that you marked previously The adhesive on the mat is made such that the mat may be moved several times before it loses its adhesiveness When you reach the next wall cut the grey mesh turn the mat and begin rolling inthe desired direction NEVER CUT OR SHORTEN THE RED HEATING CABLE Ensure that the LX mat is in full contact with the subfloor at all times Avoid walking on the heating mat If this is not possible use shoes with soft soles When approaching obstacles toilets cabinets etc carefully remove some of the red heating cable directly from the grey mesh and lead the cable around the obstacle In some cases pieces of the grey
7. HERMOSTAT The connection of the power supply and the LXstat GFCI thermostat must be done by a qualified electrician in accordance with the National Electrical Code NEC and the Canadian Electrical Code CEC The electrician should also feed the sensor cable into the installed conduit and connectit to the thermostat A final resistance reading must be taken and recorded on the warranty certificate It is important for the homeowner to mail in the certificate immediately after installing the LX mat and thermostat Failure to do so could void the manufacturer s warranty The warranty is subject to the guarantee conditions listed on the warranty certificate 088L3380 01 01 05 2007 Step 8 RECORD INFORMATION AND AFFIX LABELS Measure the resistance and record it on the provided warranty card Compare the resistance values with values listed on pg 12 and or on the cold lead Label 1 Productidentification label The eight digit product code provided on the LX mat label must be recorded on the warranty certificate Label 2 Electric panel label This label is to be placed inside the electric panel On this label record the name of the room where the heating cable has been installed Label 3 The warning label The warning label must be placed in the room where the heating cable has been installed preferably on the floor The label should be kept in the room at least for the duration of the construction or renovation of the floor
8. IMPORTANT Panfots DO NOT CROSS OR CUT THE RED CABLE REMEMBER TO MEASURE VERIFY AND RECORD THE RESISTANCE et ee 7 o al Steph o e Installation Manual Electric Heating Mats Manuel d installation Tapis chauffants lectriques Danfoss L 4 BRINGING WARMTH TO LIFE Table of Contents LX Floor Heating System Typical Installations and Cautions General Installation Guidelines META aerrcemesanase 088L3380 01 01 05 2007 3 Sp cificationS isexcurmsmarira ran ira 11 Installations types et mises en garde 12 Instructions d installation d ordre g n ral 13 Garantie arre 18 Danfoss LX Floor Heating System CAUTION It is important that this equipment is installed only by qualified electricians who are familiar with the proper sizing installation construction and operation of floor warming system and the hazards involved The heating mat is designed for under floor heating purposes only Note The installation shall be in accordance with the manufacturer s instructions and national and local codes The installation shall be in accordance with Part 424 J American National Standard Institute National Fire Protection Association ANSI NFPA70 National Electrical Code NEC and Canadian Electrical Code CEC Part 1 Danfoss recommends GFCI for heating cable in normally wet areas i e bathrooms showers kitchens LX Mat Specifi
9. al Code et la Premi re partie du Code canadien de l lectricit Vous devez vous servir d un dispositif de protection contre les d fauts de terre ou d un dispositif de courant r siduel dans les salles de bains et autres pi ces LXmat Sp cifications Type Twin conductor Connexion 120 V Voltage 120V 240V Output 12W sq ft 130 W m2 Phase Noir Heating Element Size Width 2 Neutre Bleu Length Refer to product label Terre Blindage Height approx 1 8 4 mm Cold Lead 10 3 0 m Bending radius Minimum 3 4 19 mm Connexion 240 V Wire insulation FEP TeflonTM Casing PVC Phase Noir Max Allowable Temp 212 F 100 C Phase Bleu Min Installation Temp 40 F 5 C Terre Blindage nenne _ ee Remember to measure resistance en Little Buzzer f da E7 The resistance should be measured between the two conductors blue and black Compare the measured resistance to the resistance listed on the product label on the power lead Record the resistance on your warranty card 088L3380 01 01 05 2007 11 Directly on plywood Directly on concrete Danfoss LX typical installations and applications ig Danfoss LX I Thin set cement adhesive Sa O Ceramic tiles Thermostat sensor ES Thinset cement adhesive Plywood on joists Joists Insulation optional Ceramic tiles Danfos
10. cations Type Twin conductor Voltage 120V 240V nen 2 Output l 12W sq ft 130 W m Phase Black Heating Element Size Width 2 Neutral Blue Length Refer to product label Ground Shield Height approx 1 8 4 mm Cold Lead 10 3 0 m Bending jadine Minimum 3 4 19 mm Connection 240V Wire insulation FEP Teflon Casing PVDF Phase Black u AOS Temp 212 F 100 C Phase Blue Min Installation Temp 40 F 5 C Ground Shield Note Operating the 240V mat at 208V reduces power output to approximately 9W sq ft 25 reduction WARNING EN Remember to measure resistance ee Little Buzzer f te The resistance should be measured between the two conductors blue and black Compare the measured resistance to the resistance listed on the product label on the power lead Record the resistance on your warranty card 088L3380 01 01 05 2007 Directly on plywood Directly on concrete Danfoss LX typical installations and applications Ceramic tiles Thermostat sensor ES Thinset cement adhesive in Danfoss LX Plywood on joists Joists Insulation optional Ceramic tiles Thin set cement adhesive Danfoss LX Thermostat sensor Concrete Alternative method self leveling cement is recommended for large surfaces and the following floor materials engineered wood laminate fl
11. clamation dans le cadre de la garantie Communiquez avec le service a la client le de la compagnie et fournissez les renseignements suivants 1 Nature du d faut de fabrication 2 Date d achat et si l installation a d j t effectu e date de l installation 3 Si l installation a d j t effectu e nom de l lectricien et du poseur de recouvrement de plancher 4 Relev s de r sistance consign s par le poseur 5 Preuve d achat et num ro de s rie indiqu s sur l tiquette du produit Notre service la client le vous donnera un num ro d autorisation et vous indiquera les d marches suivre pour effectuer une r clamation dans le cadre de la garantie 088L3380 01 01 05 2007 Avis de non responsabilit La pr sente garantie vous conf re des droits juridiques bien pr cis Il est possible que vous disposiez d autres droits juridiques qui peuvent varier entre les provinces ou les tats Danfoss d nie par la pr sente ce qui constitue une condition de vente toute garantie implicite Certaines provinces et certains tats ne permettent pas les restrictions relatives aux garanties implicites il est donc possible que cette restriction ne vous concerne pas Fabricant Adresse postale Danfoss Inc 7880 Tranmere Dr Toronto ON L5S 1L9 T l phone 905 676 6000 T l copieur 905 676 0279 18
12. colle a chaud fixez le conduit dans le canal II est important de le fixer au plancher afin de l emp cher de 13 088L3380 01 01 05 2007 IMPORTANT the sensor conduit must be centered in the cable loop between two red heating wires Use duct tape to close the end of the conduit so that thinset can t penetrate the conduit Use duct tape to hold the sensor conduit into the groove to prevent it from floating up when the mortar or thinset is poured If the sensor is installed directly in the mortar bed use duct tape to secure to subfloor Etape 4 PREPARATION DE LA SURFACE DU FAUX PLANCHER Assurez vous que le faux plancher est solidement fix et qu il ne bougera pas Remplissez les fissures afin de pr venir tout dommage ult rieur aux carreaux en raison d un d placement du plancher Nettoyez le faux plancher passez soigneusement l aspirateur etenleveztoute poussi re et tous les d bris qui pourraient endommager le c ble de chauffage ou r duire l adh sion En option Afin d assurer une adh sion maximale appliquez un appr t ou un scellant selon les recommandations du fabricant du ciment pose simplifi e ou autonivelant Si vous utilisez un appr t assurez vous de couvrir tout le plancher Laissez l appr t s cher compl tement avant de passer aux tapes suivantes Step 5A MEASURE THE RESISTANCE Use a digital ohm meter to measure the resistance of the LX mat and compare it to the resistance listed on th
13. e product label Record the measured resistance on the warranty card Documenting the resistance at each stage of installation is required for warranty purposes 14 088L3380 01 01 05 2007 Etape 5B INSTALLATION DELX MAT Au moyen d un ohmmetre num rique mesurez la r sistance de LX mat et comparez la a la r sistance indiqu e sur l tiquette du produit Inscrivez la r sistance mesur e sur le certificat de la garantie Il est n cessaire aux fins de garantie de documenter la r sistance mesur e chaque tape de l installation Le dessous du tapis est adh sif afin de l emp cher de bouger pendant l installation Commencez en pla ant le tapis de fa on que le point de connexion et le capteur de temp rature se trouvent au bon endroit et amenez le c ble d alimentation vers le thermostat ou la bo te de connexion Commencez d rouler LX mat uniform ment sur le plancher en d passant les d marcations d j trac es L adh sif du tapis est con u de fa on permettre de d placer le tapis plusieurs fois avant qu il perde de son efficacit Lorsque vous arrivez au mur oppos coupez la maille grise tournez le tapis et commencez le d rouler danslesens contraire NE COUPEZ JAMAIS NI NE RACCOURCISSEZ LE C BLE DE CHAUFFAGE ROUGE Assurez vous que LX mat est toujours en plein contact avec le faux plancher vitez de marcher sur le tapis chauffant Si cela n est pas possible portez des chaussures semel
14. e certificat de garantie tiquette pourle panneau lectrique Cette tiquette doit tre appos e sur le panneau lectrique Y inscrire le nom de la pi ce o l on a install le c ble de chauffage Etiquette de mise en garde L tiquette de mise en garde doit tre plac e dans la piece ou l on a install le cable de chauffage de pr f rence sur le plancher Cette tiquette doit rester dans la piece pendant toute la dur e de la construction ou de la r novation du plancher Etape 9 APPRECIEZ LE CONFORT DU TAPIS LX DANFOSS Vous pouvez maintenant utiliser le systeme de chauffage DE de plancher LX Augmentez la temp rature graduellement jusqu ce que vous atteigniez un niveau confortable selon le type de piece et vos pr f rences 17 EXTENDED WARRANTY THE FOREGOING WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED ON THE PART OF DANFOSS DANFOSS DISCLAIMS ANY WARRANTY EXPRESS OR IMPLIED OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE DANFOSS NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON FIRM OR CORPORATION TO ASSUME FOR IT ANY OTHER LIABILITY IN CONNECTION WITH SALE OR PRODUCT DANFOSS SHALL NOT BE HELD RESPONSIBLE FOR DAMAGE TO PERSON OR PROPERTY CONSEQUENTIAL LOSS LOSS OF PROFIT LOSSES ON GOODS IN STORE OR THE LIKE WHICH MIGHT ARISE OUT OF THE FAILURE OF THE EQUIPMENT DELIVERED IRRESPECTIVE OF THE CAUSE INCLUDING FAULTY MANUFACTURE Pour effectuer une r
15. ent a pose simplifi e ou du produit autonivelant et apr s l installation du carrelage et comparez toutes les consignations aux indications du tableau sur le produit e N oubliez pas de v rifier si la tension d alimentation correspond la tension de LXmat e N oubliez pas d apposer les tiquettes tel qu il est indiqu dans les instructions e N oubliez pas de mettre du ciment a pose simplifi e ou un produit autonivelant e Pour utilisation l int rieur seulement Pour toute autre question ou tout conseil communiquez avec l usine Les structures m talliques ou mat riaux servant au soutien ou a l installation de LXmat Danfoss doivent tre mises la terre conform ment a la norme C22 1 article 10 de la CSA et conform ment au National Electrical Code 12 Instructions d installation d ordre g n ral bouger lors du versement d un compos autonivelant 088L3380 01 01 05 2007 Etape 1 PLAN D IMPLANTATION Tracez un plan ou un croquis de la pi ce en y incluant tout accessoire permanent comme la toilette la baignoire les appareils m nagers les armoires etc Indiquez toutes les dimensions afin d tablir le plancher disponible et l emplacement du thermostat LXstat Prenez note que le thermostat doit tre plac a une distance d au moins quatre pieds de la douche ou de la baignoire afin d viter de l exposer a l eau et pour que personne ne puisse y toucher de la douche ou de la baignoire
16. le souple Lorsque vous approchez d obstacles toilette armoire etc enlevez soigneusement une partie du c ble de chauffage rouge de la maille grise et acheminez le c ble autour de l obstacle Dans certains cas le maillage gris sera compl tement enlev N oubliez pas le c ble rouge ne doit jamais tre sectionn Au moyen de colle thermofusible ou d un mince ruban adh sif fixez le c ble au plancher 15 088L3380 01 01 05 2007 BR928A05 Etape 6 INSTALLATION DU RECOUVREMENT DE PLANCHER Mesurez la r sistance du tapis et inscrivez la dans le tableau figurant sur le certificat de garantie Il est hautement recommand de prendre des photos de LXmat une fois celui ci install avant de poser le recouvrement AVANT DE CONTINUER ASSUREZ VOUS QUE LE CONDUIT DU CAPTEUREST BIEN INSTALL Voir l tape 3 Si vous posez des carreaux couvrez les c bles de chauffage d une couche de ciment pose simplifi e en suivant les directives du fabricant des carreaux Assurez vous que le mortier pose simplifi e couvre toute la hauteur du c ble de chauffage lors de la pose du carrelage Si vous posez un plancher de bois de bois d ing nierie ou du parquet lamellaire il est recommand de communiquer avec le fabricant du recouvrement Pour les planchers de bois il est recommand de poser au moins 3 16 po de ciment autonivelant sur le c ble chauffant Assurez vous que toute humidit que renferme le ciment a
17. mesh will be cut away entirely Remember to never cut the red cable Use hot melt glue or a thin strip of tape tosecure the loose cable to the floor 088L3380 01 01 05 2007 BR928A05 Step 6 INSTALL FLOOR COVERING Measure the resistance in the mat and record it on the warranty certificate It is highly recommend to take photographs of the installed LX mat before installing the flooring ENSURE THAT THE SENSOR CONDUIT HAS BEEN PROPERLY INSTALLED BEFORE PROCEEDING see Step 3 In the case of tiles proceed with the installation of the tiles by covering the heating cables with a layer of thin set cementas directed by the tile manufacturer Ensure that the thin set mortar covers the entire height of the heating cable as the tiles are installed In the case of a wood engineered or laminate floor covering it is recommended that the flooring manufacturer be contacted For wooden floors a minimum of 3 16 in of self leveling cement over the heating cable is recommended Ensure that all moisture in the self leveling cement has been fully eliminated in accordance with the drying times recommended by the manufacturer consult the manufacturer for exact drying time Once the thin set cement has dried measure the resistance in the mat and record it on the warranty certificate The LX mat must not be turned on until the thin set cement has fully dried A minimum of seven 7 days is recommended Step 7 CONNECT POWER SUPPLY AND T
18. oating floors vinyl linoleum and carpet Warning Consult the manufacturer for information on special installation requirements for wood laminate and vinyl or linoleum flooring Caution e Read the instructions carefully before installing LX mat e It is not recommended to install LX mat using a thermostat without a floor temperature limiter particularly when another heater is installed in the room e Do not install LX mat in walls or ceilings e The mat must be embedded in mortar thinset concrete or similar material e The minimum installation temperature is 40 F 5 C e Never cut the red heating wire e It is recommended to use copper wire only Never install the LX mat such that two red heating wires touch cross or overlap 088L3380 01 01 05 2007 Remember to always measure verify and record the actual resistance throughout the installation process out of the box after installation before thin set cement or self leveler application and after installation of floor tiles and compare all reading to the ratings on the product table Remember to check that the supply voltage matches the voltage of the LX mat Remember to place the labels as written in this instruction Remember to use a cement based thin set or self leveling product Only for indoor installation Please consult the factory for any other questions or advice Metal structures or materials used for the support of o
19. r on which the Danfoss LX mat is installed must be grounded in accordance with CSA Standard C22 1 section 10 and the NEC General Installation Guidelines Step 1 PLAN LAYOUT Make a sketch layout or a floor plan of the room include all permanent furnishings such as toilets bathtubs appliances cabinetry etc Indicate all dimensions required to determine the available floor area and the position of the LX thermostat TIP Danfoss recommends installation is documented with photos to note the location of connections and the sensor Step 2 TRANSFER LAYOUT TO FLOOR Draw an outline of the layout on the room floor including a foot print of all furnishings that are not yet installed Unroll the first few feet of the LX mat The starting point of the cable must be placed within 10 ft fromthe thermostat Mark the position of the connection point between the power lead and the red LX heating cable This connection must be concealed in thinset orself leveling cement When using a floor temperature sensing thermostat mark the sensor position in the middle of 2 heating cables about 10 in 25cm away from the wall within the heated area as close as possible to the thermostat Step 3 INSTALL SENSOR recommended in conduit part 19809099 If using a floor temperature sensing thermostat install the sensor now either in conduit tube or directly to the subfloor It is recommended that the sensor be installed in conduit tube
20. s LX Thermostat sensor Concrete Autre fa on il est recommand d utiliser du ciment autonivelant sur une grande surface ainsi que sur les mat riaux de recouvrement suivants bois d ing nierie parquet lamellaire parquetflottant vinyle linol um et tapis Mise en garde Pour obtenir de l information sur les exigences d installation particuli res des rev tements en bois en parquet lamellaire en vinyle ou en linol um consulter le fabricant Attention e Avant d installer LXmat lisez avec soin les instructions d installation e Il n est pas recommand d installer LXmat sans thermostat avec dispositif limitant la temp rature du plancher tout particuli rement lorsqu il y a un autre dispositif de chauffage dans la pi ce e N installez pas LXmat dans le mur ou le plafond e Le tapis doit tre encastr dans du mortier un m lange de mortier du b ton ou autre mat riau semblable e Latemp rature minimale d installation est de 5 C 40 F e Ne coupez pas le fil de chauffage rouge e l est recommand d utiliser uniquement du fil de cuivre e N installez pas LXmat de fa on que les deux fils de chauffage rouges se touchent se croisent ou se chevauchent 088L3380 01 01 05 2007 e N oubliez pas de continuellement mesurer v rifier et inscrire la r sistance tout au long du processus d installation au moment de l ouverture de la boite apres l installation avant la pose de cim
21. utonivelant s est bien vapor e conform ment aux dur es de s chage recommand es par le fabricant pour obtenir la dur e exacte du s chage communiquezavec le fabricant Une fois le ciment pose simplifi e s ch mesurez la r sistance du tapis et inscrivez la sur le certificat de garantie LXmat ne doit pas tre allum avant le s chage complet du ciment pose simplifi e On recommande une dur e de s chage d au moins sept 7 jours tape 7 CONNEXION DE L ALIMENTATION EN COURANT ET DU THERMOSTAT La connexion de l alimentation et du thermostat LXstat GFCI doit tre effectu e par un lectricien agr conform ment au National Electrical Code et au Code canadien de l lectricit L lectricien doit aussi amener le c ble du capteur dans le conduit et le connecter au thermostat Il faut prendre un relev de la r sistance et inscrire cette valeur sur le certificat de garantie Il est important que le propri taire conserve cette page en lieu s r aux fins de consultation L lectricien doit galement remplir le certificat sinon la garantie du fabricant pourrait tre annul e La garantie est assujettie toutes les conditions indiqu es sur le certificat 16 088L3380 01 01 05 2007 tape 8 CONSIGNATION D INFORMATION ET APPOSITION DES ETIQUETTES Etiquette d identification du produit Le code du produit comportant huit chiffres et figurant sur l tiquette de LXmat doit tre inscrit sur l