1. IMPORTANTE IMPORTANT WICHTIG The generator must never be operated with the protective devices removed The heat produced by the generators may be very high according to the power generated Therefore do not touch the generator if you do not wear antiscorch gloves and after swit ching it off do not touch it until it has cooled down to ambient temperature DANGER OF SHORT CIRCUIT The degree of protec tion of the generator is IP23 It is therefore forbidden to sprinkle or place liquids con tainers on the electri cal parts Do not clean the insi de electric compo nents with compres sed air because this may cause short cir cuits or other anoma lies No person must wear fluttering clothes such as scarves bracelets etc near the machine and any garment must be fastened with elastic bands at its ends Keep away from the machine even if all the machine compo nents are protected When the machine is worn out contact the companies in charge of the disposal of ferrous material and do not throw away its parts into the environ ment In case of replace ment of spare parts use original spare parts only Make sure when starting up that coo ling air intake and discharge openings are free and unbloc ked Les g n rateurs ne doivent jamais et pour aucune raison fonction ner si les protections ont t enlev es Les altemateurs produi sent de l nergie calor
2. it is necessary to re it Apply a direct voltage of 10 50 Vde at the outlet of the rectifying bridge Make sure that the polarities red green are correct CHECKING THE DIODES Use an ohmmetre to check each diode Diodes must show continuity in one direction only This check can also be done using a battery and a light bulb this one must turn on only in one direction as shown in the figure IMPORTANCE OF THE DIRECTION OF ROTATION In order to achieve the performances declared it is neces sary to have the ge nerator rotating cloc kwise looking from DE bracket mettre la machine en charge r gler la vi tesse jusqu obtenir la tension d sir e supprimer la charge et r gler la tension en ajustant l entrefer Au cas o le g n ra teur ne s exciterait pas automatique ment il faudrait le r exciter en appli quant pendant quel ques instants une tension continue de 10 50 Vcd la sortie du pont redresseur en ayant soin de re specter la polarit rouge verte VERIFICATION DES DIODES Utiliser un ohmmetre pour tester individuel lement chaque diode Les diodes sont con ductrices du courant dans un seul sens Ce test peut tre fait en utilisant une batte rie et une lampe La lampe s allume dans un seul sens comme indiqu sur la sche ma IMPORTANCE DU SENS DE ROTA TION Pour obtenir les pre stations indiqu es il est n cessaire que l alternateur t
3. to di messa a terra sia efficiente ed in conformi ta con le direttive del paese dove il generato re sara installato Per il collegamento ter ra prevista anche la possibilit di utilizzare un foro presente sul coper chio posteriore che accessibile senza dover smontare la cuffia Le persone addette alla movimentazione devo no sempre indossare guanti da lavoro e scar pe antinfortunistiche Qualora il generatore o l intero impianto debba essere sollevato da ter ra gli operatori devono usare un casco protetti VO ATTENZIONE QUALORA IL GENE RATORE SIA STATO A LUNGO IMMAGAZ ZINATO PER EVITA RE DANNI DOVUTI ALL UMIDITA E CONSIGLIABILE VERI FICARE MEDIANTE MEGGER A 500V LA RESISTENZA D ISO LAMENTO DI TUTTI GLI AVVOLGIMENTI VERSO MASSA RO TORE COMPRESO VALORI RILEVATI DEVONO ESSERE SUPERIORI AD 1 MO EN60204 1 IN CASO CONTRARIO BISO GNA INVESTIRE GLI AVVOLGIMENTI CON UN GETTO D ARIA CALDA FINO A CHE NON SI OTTENGA IL VALORE SOPRA RI PORTATO Il generatore va installa to in un ambiente area to Se non c sufficiente aria oltre al mal funzio namento esiste pericolo di surriscaldamento La macchina stata progettata per garantire la potenza nominale in ambienti con temperatu ra massima di 40 C e altitudine inferiore ai 1000 metri EN60034 1 se non diversamente indicato Per condizioni diverse vedere il catalo go commerciale depliant I
4. Anzugsmoments von 16 7 Nm Abb 2 die mittlere Zugstange in ihi rem Sitz einstecken Abb 3 die mittere Zungstange blockieren und betr ein Anzugsmoment von 21 7 Nm auf die Schraubmutter aufbringen die seitlichen Schutznetze sowie das hinte re Abschlufsrost wieder aufse tzen und hierf r ein Anzu gsmoment von 3 5 7 Nm auf die Schrauben M5 aufbrin 4 gen Abb 4 ACOPLAMIENTO MECANICO En el caso de acoplamiento de un generador serie T20F con forma constructiva B3 B9 siga las instrucciones siguien tes montar la tapa anterior enci ma del motor sujet ndola con sus tomilos y aplicando un par de torque de 48 7 Nm si utiliza tomillos M10 o de 21 7 Nm si utiliza tomillos M8 fg 1 sujete el alternador en la ta pa fijando las cuatros tuercas M8 en los tirantes aplicando un par de torque de 16 7 Nm fig 2 introducir el tirante central en su lugar fig 3 Isujete el tirante central apli cando en la tuerca M8 un par de torque de 21 7 Nm vuelva a montar las redecillas de protecci n laterales y la reila de cierre posterior apli cando a los tomillos M5 un par gt torque de 3 5 7 Nm fig T20F Instruction Manual September 2013 rev 04 SCHEMA ELETTRICO WIRING DIAGRAM SCHEMA ELECTRIQUE SCHALTSCHEMA ESQUEMA ELECTRICO COLLEGAMENTO A TRIANGOLO DELTA CONNECTION CONNECTION TRIANGLE DREIECKSCHALTUNG CONEXION EN TRIA
5. PO BOX 1046 DRY CREEK 5094 SOUTH AUSTRALIA TEL 61 08 83498422 FAX 61 08 83498455 e mail aftersalesiQmeccalte com au FAR EAST MECC ALTE F E PTE LTD 19 KIAN TECK DRIVE SINGAPORE 628836 TEL 65 62 657122 FAX 65 62 653991 e mail aftersalesCdmeccalte com sg INDIA MECC ALTE INDIA PVT LTD PLOT No 1 September 2013 rev 04 code 9513019058 755 NANHAI EAST ROAD JIANGSU HAIMEN ECONOMIC DEVELOPMENT AREA 226100 PEOPLE S REPUBLIC OF CHINA TEL 86 513 82325758 FAX 86 513 82325768 e mail aftersales Qmeccalte cn SANASWADI TALEGAON DHAMDHERE ROAD TALUKA SHIRUR DISTRICT PUNE 412208 MAHARASHTRA INDIA TEL 91 2137 619600 FAX 91 2137 619699 e mail aftersales Qmeccalte in DESCRIZIONE MACCHINA generatori della se re T20F sono a spazzole con regola zione coumpound sulle tre fasi a 2 poli Sono costruiti in con formit alle direttive 2006 42 2006 95 2004 108 e relative modifiche alle norme EN 60034 1 CEI 2 3 IEC 34 1 VDE 0530 BS 4999 5000 N F 51 111 coperchi sono pres sofusi in lega di allu minio ad alta resi stenza l albero in acciaio C45 con anel lo compensatore II grado di protezione e IP23 a richiesta possibile realizzare un grado di protezio ne superiore Gli isolamenti sono in classe H e gli avvol gimenti sono impre gnati con resine epossidiche tropica lizzate La produzione di se rie soddisfa la norma tiva VDE 0875 grado K e i requi
6. duit cependant au bout de 10 minu tes de fonctionne ment de l alternateur Dans le cas ou l on d sire diminuer la tension il faudra en lever une spire par secteur du transfor mateur en v rifiant successivement si la nouvelle valeur de la tension d bit e en charge soit satisfai sante Dans le cas ou cela ne le serait pas r p ter l op ration ju squ ce que l on ob tienne la valeur d si r e Conseils utiles Pour un cart mini mum de tension entre pleine charge et vi de ind pendamment du facteur de puis sance et de l cart de vitesse du moteur d entra nement il faut b belasten Sie den Generator f r einige Sekunden mit einer Last von min 30 der Nominallast C l sen Sie die Ein stellschrauben 1 d Vergr sserung des Luftspalts um die Spannung zu erh hen Verkleine rung um die Span nung herabzusetzen e festziehen der Einstellschrauben 1 SPANNUNGSEINST ELLUNG UNTER LAST Um die Span nungseinstellung un ter Last zu regeln ist ist es m glich die Windungszahl 2 des Compoundtrafos zu ver ndem Beachten Sie dass bei kalter Maschine und glei cher Last die Span nung bis zu 5 bei cos p 0 8 und bis zu 10 bei cos 1 ansteigen kann Die se Erh hungen der Spannung reduzieren sich dann innerhalb 10 Minuten Laufzeit auf die H lfte ihres Wertes Falls egal bei welchem Span nungswert eine Ab senkung der Span nung gew nscht
7. s Mecc Alte Avant une quelconque intervention sur l altema teur s assurer que le mo teur avec lequel est ac coupl laltemateur ne doit pas tre en fonction nement et oul ny a au cun pi ces en fonction nement ATTENTION L NSTALLATEUR Fl NAL EST RESPON SABLE DE LA MISE EN PLACE DE TOUTES LES PROTECTIONS NE CESSAIRES DISPOSITIFS DE PRO TECTION ET DE COUPURE PROTEC TIONS CONTRE LES CONTACTS DIRECTS ET INDIRECTS PRO CONTRE LES SURCHARGES ET LES SURTENSIONS ARRET D URGENCE ETC POUR RENDRE CONFORME LE MATE RIEL ET SON IMPLAN TATION AUX NORMES DE SECURITE INTER NATIONALES ET EURO PEENNES EN VIGUEUR Schmierung tung mu der Hauptmo tor an den der Generator angeschlossen ist au er MECHANISCHE WARTUNGS FACHMANN identifiziert den Personen typ der mit der mechani Se Wartung beauftragt ist setzt eine volle Kenntnis und Verst ndnis der im Bedienungshandbuch des Herstellers enthalte nen raus zus tzlich zu den spezifischen Kompeten zen was die Aufstellungs Einstellungs Wartungs Reinigungs und oder Re paraturarbeiten betrifft Diese Qualifikation Informationen vo ELEKTRISCHE WARTUNGS FACHMANN Identifiziert den Personen typ der mit der elektri schen Wartung beauftragt ist Diese setzt eine vole Kenntnis und Verst ndnis der im Bedienungshandbuch des Herstellers enthalte nen raus zusatzlich zu den spezifischen Kompeten zen was die Eing
8. 6 3 EN61000 6 1 the above mentioned re gulation is complied with INTRODUCTION The T20F alternators comply with the EEC 2006 42 2006 95 2004 108 directives and their amendments there fore they pose no danger to the opera tor if they are instal led used and main tained according to the instructions given by Mecc Alte and provided that the sa fety devices are kept in perfect working conditions DESCRIPTION DE LA MACHINE Les alternateurs de la Serie T20F sont ba gues avec r gulation compound sur les trois phases 2 p les Les alternateurs T20F sont construits en conformit aux direc tives 2006 42 2006 95 2004 108et leurs modifications aux normes EN 60034 1 CEl 2 3 34 1 VDE 0530 BS4999 5000 N F 51 111 Les flasques sont en aluminium coul a haute resistance l ar bre est en acier C45 avec rondelle de blo quage Le grade de protec tion est IP23 sur de mande il est possible de r aliser un grade de protection sup rieure Les isolements sont de classe H et les en roulements im pr gn s de r sines poxy tropicalis es La production en s rie est conforme la norme VDE 0875 de gr K et aux condi tions essentielles re quises de s curit im pos es par la directi ve euro enne sur la compatibilit lectro magn tique la con formit cette der ni re est garantie par l application des nor mes europ enne EN 61000 6 3 EN610
9. EN 60034 1 This machine must be put into service until the machine in which it is intented to be incorporeted into has been declared in conformity with provisions of 2006 42 directives d crite comme dans la docu mentation ci jointe et dans nos archives est conforme aux directives 2006 42 la directi ve 2006 95 la directive 2004 108 aux normes euro p ennes EN 12100 1 EN 12100 2 EN ISO 14121 1 EN 60204 1 EN 61000 6 3 EN 61000 6 1 EN 60034 1 L utilisation l alternateur n est pas autoris e avant que l ensamble alternateur et sy steme d entrainement soit d clar conforme aux disposi tions de la directive 2006 42 CEE Ragione sociale Legal name Raison sociale Firmenname Nombre legal Indirizzo sede Headoffice address Adresse du siege Hauptsitz Direcci n Codice fiscale Fiscal code Numero R C Steuernummer Codigo fiscal Partita IVA VAT Reg Number NumeroTVA USTID Nr N mero de IVA Numero di telefono Telephone number Numero de telephone Telephonnummer Tel fono Numero di fax Fax number Numero de fax Faxnummer N mero de fax E Mail Web site wie in der Dokumentation im Anhang und in unseren Archiven beschrieben bereinstimmt mit den der Richtlinie 2006 42 der Richtli nie 2006 95 der Richtlinie 2004 108 und den europ ischen Normen EN 12100 1 EN 12100 2 EN ISO 14121 1 EN 60204 1 EN 61000 6 3 EN 61000 6 1 EN 60034 1 Der Betrieb der o g Maschine nach dem Zusamm
10. aplicacion de las normas europeas EN 61000 6 3 EN61000 6 1 ACLARACION Los generadores de la serie T20F respon den a las directivas CEE 2006 42 2006 95 2004 108 y a sus respectivas mo dificaciones por lo tanto no se presentan peligros para el ope rador si instalados usados y mantenidos seg n las instruccio nes dadas por la Mecc Alte y con la condici n que los di spositivos de seguri dad sean mantenidos en una condici n de perfecta eficiencia September 2013 rev 04 Per questa ragione Occorre attenersi scrupolosamente alle istruzioni indicate in questo manuale Per qualsiasi comuni cazione citare sem pre il tipo e il codice del generatore Non disperdere l im ballo nell ambiente ma rivolgersi alle agenzie di smalti mento PRESCRIZIONI DI SICUREZZA Durante la consulta zione del presente manuale d uso e ma nutenzione troverete alcuni simboli questi hanno un preciso si gnificato qui di segui to illustrato IMPORTANTE Segnala al personale interessato che l ope razione descritta pre senta un rischio che pu avere come con seguenza un danno alla macchina se non effettuata nel ri spetto delle normati ve di sicurezza PERICOLO Segnala al personale interessato che l ope razione descritta pre senta un rischio imme diato che ha come conseguenza lesioni gravi o morte se non effettuata nel rispetto delle normative di si curezza ADDETTO ALLA MOVIMENTAZION
11. conductores de corriente en un solo sentido Esto puede hacerse utili zando una pila o bien una bateria y una lampara La lampara se ilumina en un solo sentido como indica el esquema IMPORTANCIA DEL SENTIDO DE ROTACION Para obtener los da tos declarados es necesario que el ge nerador gire en senti do horario visto de sde el lado de acople INCONVENIENTI PROBLEMS PANNES CAUSE CAUSES CAUSES COME INTERVENIRE REMEDIES QUE FAIRE ST RUNG FALLOS URSACHE CAUSAS GEGENMARNAHMEN REMEDIOS Controllare i giri e portarli al valore nominale Controllare e sostituire GENERATORE NON SI ECCITA GENERADOR DOES NOT EXCITE L ALTERNATEUR NE S AMORCE PAS GENERATOR ERREGT SICH NICHT EL ALTERNADOR NO SE EXCITA Velocit ridotta Ponte diodi guasto Guasto negli avvolgimenti Low speed Broken diode bridge Winding breakdowns Vitesse trop lente Pont de diode cass Bobinage d t rior s Reduzierte Gescwindingkeit Defekter Gleichrichter Defekt an den Wicklungen Velocidad reducida Puente diodos averiado tabella Check RPM and set at nominal value Check and replace Check windings resistance according to the table R gler la vitesse Le tester et le changer V rifier les valeur l aide du tableau berpr fen und Ersetzen Controllare la resistenza degli avvolgimenti come da Die Drehzahl berpr fen und sie auf ihren Norminalwert bringen Den Widerstand der Wicklungen gem Tabelle
12. es erforderlich sicher zustellen daf die Er dungsanlage leistung sfahig ist und mit den Vorschriften des Landes in dem der Generator in stallert wird berein stimmt Hinsichtlich der Erdung ist auf der oberen Seite des hinteren Deckels ein zug ngliches Loch vor gesehen so da die Haube nicht abgenom men werden mu Die f r den Transport zust ndigen Personen haben stets Ar beitshandschuhe und Schuhwerk gem den Unfallverh tungsvor schriften zu tragen So fem der Generator oder die gesamte Anlage vom Boden angehoben wer den m ssen haben die Arbeiter einen Schu tzelm zu verwenden ACHTUNG WENN DER GENE RATOR BER EL NEN L NGEREN ZEITRAUM HINWEG EINGELAGERT WORDEN WAR UM IHN VOR FEUCH TIGKEIT ZU SCH TZEN EMPFIEHLT ES SICH MITTELS MEGGER MIT 500V DEN ISOLATIONS WIDERSTAND AL LER WICKLUNGEN GEGEN MASSE EINSCHLIERLICH L UFER ZU BER PR FEN DIE GE MESSENEN WERTE M SSEN BER 1 MO EN60204 1 LIEGEN Der Generator mu in ei nem bel fteten Raum in stalliert werden Wenn keine ausreichende Bel ftung gegeben ist besteht die Gefahr fehle rhaften Funktionierens und der Uberhitzung Das Ger t wurde entwic kelt um die Nennlei stung in Ambienten mit einer maximalen Tem peratur von 40 C und einer H he unter 1000 Meter EN60034 1 zu garantieren wenn nicht anders angegeben bei anderen Bedingungen bitte im Handelskatalog Prospekt nachschla
13. gen T20F Instruction Manual Por lo tanto es necesario que la instalaci n de puesta a tierra sea efi ciente y en conformidad con las directivas del pa s donde el generador ser montado Para la conexi n a masa se provee sobre la parte superior de la tapa po sterior un orificio accessi ble sin tener que de smontar la copertura Las personas dedicadas al transporte deber n usar siempre guantes de trabajo y zapatos de se guridad Siempre que el generador o el equipo completo sea elevado del suelo los operadores deber n usar cascos de protecci n ATENCION SI ACASO EL GENE RADOR HAYA ESTA DO DEPOSITADO UN LARGO PERIODO DE TIEMPO PARA EVI TAR DANOS DEBIDO A LA HUMEDAD SE ACONSEJA VERIFI CAR MEDIANTE UN MEGGER A 500 V LA RESISTENCIA DE AISLACION DE TO DOS LOS BOBINA DOS CON RESPECTO A MASA INCLUIDO EL ROTOR LOS VALO RES MEDIDOS DEBEN SER SUPERIORES A 1 MO EN60204 1 EN CASO CONTRARIO SE DEBE APLICAR UNA RAFAGA DE Al RE CALIENTE A LOS BOBINADOS HASTA QUE SE OBTENGA EL VALOR ANTES MEN CIONADO El generador debe ser instalado en un ambien te aireado Si no hay su ficiente ventilaci n adem s del mal funcio namiento existir el peli gro de sobrecalenta miento El mecanismo ha sido dise ado para garantizar la potencia nominal en ambientes con una tem peratura m xima de 40 C y en altitud inferior a 1000 metros EN60034 1 salvo indicaciones di stintas p
14. have a small des moteurs ther Generell weist das regulacion de los mo lazione della velocit dei motori di trascina mento presenta in generale una leggera caduta di velocit tra vuoto e carico per ci raccomandabile regolare la velocit a vuoto di un 3 4 su drop in speed between no load and loaded conditions We therefore recom mend setting no load speed 3 4 above nominal speed miques est tel qu il y a une diff rence de vitesse entre vide et charge Nous recommandons de r gler la vitesse vide 3 ou 4 des sus de la vitesse no minale pour avoir Regelsystem der An triebsmotoren einen leichten Abfall der Geschwindigkei bei Last gegen ber Leer lauf daher ist es ra tsam die Geschwin digkeit bei Leerlauf 3 4 h her zu stellen Nals die Nominalge tore termicos es tal que exsiste una dife rencia de velocidad entre vacio y carga Recomendamos re gular la velocidad sin carga a un 3 4 por encima de la veloci dad nominal por periore alla velocit pleine charge la vites schwindigkeit hacer a pieno carga nominale se nominale la velocidad REGOLAZIONE VOLTAGE REGLAGE DE LA EE ha REGULACION DE DELLA TENSIONE REGULATION AT TENSION A VIDE LA TENSION EN A VUOTO NO LOAD Afin de r gler la ten LUN ua VACIO Per la regolazione For the no load volta sion vide il faut agir Para la regulacion de della tensione a vuo to si dovr agire sul traferro del trasfor mat
15. n des medios de leventamiento des m todos y des caracteri sticas de barrachera y de movimentaci n securidad September 2013 rev 04 MANUTENTORE MECCANICO Identifica il tipo di opera tore a cui riservato l intervento trattato Questa qualifica presup pone una piena cono scenza e comprensione delle informazioni conte nute nel manuale d uso del costruttore oltre che competenza specifica per effettuare gli inter venti di installazione regolazione zione pulizia e o ripara zione MANUTENTORE ELETTRICO Identifica il tipo di opera tore a cui riservato l intervento trattato Questa qualifica presup pone una piena cono scenza e comprensione delle informazioni conte nute nel manuale d uso del costruttore oltre che competenza specifica per gli interventi di natu ra elettrica di collega mento regolazione manutenzione e o ripa razione E in grado di operare in presenza di tensio ne all intemo di armadi e quadri elettrici PRESCRIZIONI DI SICUREZZA Nel caso di interventi straordinari e su autoriz zazione scritta del servi Zio assistenza rivolgersi ai centri autorizzati Mecc Alte Prima di qualsiasi inter vento sul generatore assicurarsi che il motore primario a cui collega to non sia in funzione e che non ci siano parti in movimento ATTENZIONE L INSTALLATORE FINALE E RESPONSA BILE DELLA PREDI SPOSIZIONE DI TUTTE LE PROTEZIONI DISPOSITIVI D
16. power Statore Rotore Auxiliary winding Rating Excitation Air volume Noise Weight power Puissance Puissance triphase Stator Rotor enroulement auxiliaire Puissance Exitation Volume d air Bruit Poids Monophase Leistung Leistung Dreiphasig Estator Hilfs wicklung Leistung Erregung Luftmenge Gerausch Gewicht Einphasig Potencia Potencia trifasica Bobinado auxiliar Potencia Excitation Volumen de aire i monofasica kVA La La m3 min T20FS 130 T20FS 160 T20F 200 14 3 12 T20F Instruction Manual September 2013 rev 04 3600 RPM 120 208V 60Hz Regolatore compound Compound regulator Regulation compound Compound regler Regulador compound Potenza Potenza trifase Avvolgimento ausiliario Potenza Eccitazione Volume d aria Rumore Peso monofase Three phase Single phase power Statore Rotore Auxiliary winding Rating Excitation Air volume Noise Weight power Puissance Puissance triphase Stator Rotor enroulement auxiliaire Puissance Exitation Volume d air Bruit Poids Monophase Leistung Leistung Dreiphasig Estator Hilfs wicklung Leistung Erregung Luftmenge Gerausch Gewicht Einphasig Potencia Potencia trifasica Bobinado auxiliar Potencia Excitation Volumen de aire i monofasica L3 T20FS 130 11 6 0 404 T20FS 160 SOE 0 365 T20F 200 DIMENSIONI DI INGOMBRO OVERALL DIMENSIONS ENCOMBREMENT BAUMASSE DIMENSIONES MAXIMAS dimensions in mm FORMA FORM FORME B3 B14 DADO NUT ECR
17. wird kann durch abwickeln von einer Windung gleichm ig an jeder Spule ein entspre chender Wert reali siert werden Nach Uberpr fung der Spannung muss gegebenenfalls der Vorgang wiederholt werden um ein zufrie denstellendes Ergeb nis zu bekommen Bemerkung Um den Unterschied zwischen Last und Leerlaufspannung zu reduzieren unabh n gig von cosphi und Drehzahlunterschie den belasten Sie den generator und stellen Sie die Geschwin digkeit so ein bis die T20F Instruction Manual b aplicar por unos segundos una carga no inferior del 3096 de la potencia nominal aflojar las tuercas de cierre 1 d aumentar el en trehierro para aumen tar la tension o vice versa disminuirlo para bajar la tension e apretar bien las tuercas de cierre 1 REGULACION DE LA TENSION EN CARGA Para la regulacion de tension en carga es posible modificar el numero de espiras 2 del transformador de tension Tengase presente que con una carga equilibrada normalmente se ob tiene una sobre elevacion de la ten sion que puede lle gar en el caso de maquina fria hasta 5 con cos 0 8 y hasta al 10 con cos g 1 De todas formas tales sobreelevacio nes de tension se reducen de la mitad dentro de los prime ros 10 minutos de funcionamiento del generador En caso se desee reducir la tension se debera remover una espira por columna en el transformador verifi cando cada vez si
18. 00 6 1 INTRODUCTION Les alternateurs de la s rie T20F r pondent aux directives CEE 2006 42 2006 95 2004 108 et leurs mo difications Toutefois ils ne pr sentent au cun danger pour l uti lisateur si linstalla tion l utilisation les manutentions suivent les instructions four nies par Mecc Alte et condition que les di spositifs de protection soient tenus en par fait tat de marche MASCHINEN BESCHREIBUNG Die Generatoren der Serie T20F haben Stromabnehmer mit Compound Regulie rung auf den drei Pha sen mit 2 Polen Die Generatoren T20F sind in Uberenstim mung mit den Bestim mungen 2006 42 so wie mit 2006 95 und 2004 108 und deren entsprechenden An derungen en und den Normen EN 60034 1 CEl 2 3 IEC 34 1 VDE 0530 BS 4999 5000 N F 51 111 Die Deckel sind aus einem sehr wider standsf higen Alumi niumdruckguf ange fertigt die Welle aus C45 Stahl mit kom pensator ring Die Schutz klasse ist IP23 auf Anfrage kann auch eine hohere Schutzklasse realisiert werden Die lsolie rung entspricht Klasse H und die Wicklungen sind mit Tropen Epoxidharz im pragniert Die Serrien produktion entspricht der Bestimmung VDE 0875 Grad und den wesentlichen Si cherheitsanforderun gender europ ischen Richtilinie hinsichtlich elektromagnetischer Kompatibilit t die Ubereinstimmung mit dieser Richtlinie wird durch die Anwerdung der europ ischen Nor men EN 61000 6 3
19. 3 5 7 Nm to the M5 screws fig 4 7 ACCOUPLEMENT MECANIQUE En cas de montage d un g n rateur s rie T20F ayant la forme constructive B3 B9 suivre les instructions suivan tes monter le couverde avant sur le moteur en la fixant avec les vis pr vues cet effet et en appliquant un couple de serrage de 48 7 Nm si on utilise des vis M10 ou de 21 7 Nm en cas de vis M8 fig 1 bloquer l altemateur sur le couvercle en fixant les quatres crous M8 sur les tirants en appliquant un couple de serra ge de 16 7 Nm fig 2 enfiler le tirant central dans son logement fig 3 bloquer le tirant central en appiquant l crou M8 un couple de serrage de 21 796 Nm remonter les grilles de protection laterales et la grille de fermature arri re en appli quat aux vis M5 un couple desserrage de 3 5 7 Nm figure 4 GEFAHR PELIGRO MECHANISCHER ANSCHLUR Bei Anschlu einses Genera tors der Serie T20F mit Bau form B3 B9 m ssen die fol genden Answeisungen befolgt werden den vorderen Deckel auf den Motor stzen und ihn mit Hilfe entsprechenden Schrauben und einem Anzu gsmoment von 48 7 fe stziehen wenn Schrauben M10 verwendet werden oder aber mit einem Anzugsmo ment von 21 Nm bei Ver von Schrauben M8 2 den Umwandler auf dem eckel befestigen und ihn mit Hilfe der vier Schraubmuttem M8 an den pude befe stingen bei Aufbringen eines
20. E Identifica il tipo di operatore a cui ri servato l intervento trattato Questa qualifica pre suppone una piena conoscenza e com prensione delle infor mazioni contenute nel manuale d uso del costruttore oltre che competenze spe cifiche dei mezzi di sollevamento dei metodi e delle carat teristiche d imbraga tura e della movimen tazione in sicurezza IMPORTANTE IMPORTANT WICHTIG Therefore a strict observance of these instructions is requi red Always indicate the generator type and code when contac ting Mecc Alte or the authorized after sales service centres Any packing mate rials should be dispo sed of via correct waste disposal me thods Do not discard waste materials into the enviroment SAFETY REQUIREMENTS In consulting this use and maintenance manual you will find several symbols which have a specific meaning as illustra ted below IMPORTANT This symbol warns the personnel con cerned that the de scribed operation may cause damages to the machine if it is not carried out accor ding to the safety standards DANGER This symbol wams the personnel concemed that the described operation may imme diately cause serious injuries or death to the personnel if it is not carried out according to the safety stan dards HANDLER This symbol identifies the type of operator in charge of the ope ration described This qualification requires a
21. E END BRACKET B14 FLASQUE AVANT B14 VORDERES GEHAUSE B14 TAPA ANTERIOR B14 0391700143 C COPERCHIO ANTERIORE B9 DRIVE END BRACKET B 9 FLASQUE AVANT B9 VORDERES GEHAUSE B9 TAPA ANTERIOR B9 INDUTTORE ROTANTE ROTOR ASSY ROUE POLAIRE ROTOR INDUCTOR ROTANTE VENTOLA VENTILATEUR L FTERRAD VENTILADOR 0392000033 17 USCINETTO ANTERIORE FRONT BEARING ROULEMENT AVANT VORDERES LAGER COJINETE ANTERIOR 0390302532 6306 2RS 6306 2RS 6306 2RS 6306 2RS 6306 2RS CUSCINETTO POSTERIORE REAR BEARING ROULEMENT ARRIERE HINTERES LAGER COJINETE POSTERIOR 0390302511 6205 2RS 6205 2RS 6205 2RS 6205 2RS 6205 2RS MORSETTIERA AUSILIARIA E BORNES AUXILIARES NEBEN KLEMBRETT REGLETA 0391100110 PONTE RADDRIZZATORE RECTIFYNG 1 PHASE BRIDGE PONT REDRESSEUR BRUCKENGLEICHRICHTER PUENTE RECTIFICADOR 9910390115 MONOFASE SKB25 08 SKB25 08 MONOPHASE SKB25 08 EINPHASIG SKB25 08 SKB25 08 27 VARISTORE VARISTOR VARISTOR VARISTOR VARISTOR 9910384005 TIRANTE CENTRALE SECURING STUD TIGE CENTRALE ZENTRIESSTIFT TIRANTE CENTRAL S RETINA PROTEZIONE PROTECTION SCREEN GRILLE DE PROTECTION SCH TZGITTER REJILLA DE PROTECCION ANELLO COMPENSATORE FIXING RING RONDELLE DE BLOQUAGE COMPENSATOR RING ANILLO COMPENSADORES 0390100211 mm Nella richiesta di pezzi di ricambio specificare il tipo e il codice dell alternatore When requesting spare parts always indicate the altemator s type and code Pour toute demande de pieces detach es pri re de mentionner le type et le co
22. EN61000 6 1 gew hr leistet VORWORT Die Generatoren en tsprechen den EG Bestim mugen 2006 42 2000 95 2004 108 und deren entsprechenden An derunen aus diesem Grunde stellen sie kei nerlei Gefahr f r den Bediener dar sofern sie in Ubereinstim mung mit den von Mecc Alte vorge schriebenen Answei sungen installiert ver wendet und gewartet werden und unter der Bedingung da die Schutzvorrichtungen stets in einem voll funktionst chtigen Zu stand gehalten wer den T20F Instruction Manual DESCRIPCION MAQUINA Los generadores de la Serie T20F son ce pillos con regulaci n compound sur tres fa Se a 2 polos Los generadores T20F est n construi dos en conformidad a las directivas 2006 42 2006 95 2004 108 y sus modi ficas normas EN 60034 1 CEI 2 3 IEC 34 1 VDE 0530 BS 4999 5000 N F 51 111 Las tapas son fundi das a presi n en una aleaci n de aluminio de alta resistencia el eje en acero C45 con anillo El grado de pro teccion es IP23 a pedido es posible realizar un grado de proteccion superior Los aislamientos son de clase H y los reve stimientos est n im pregnados de resina de ep xido tropicali zado La prodiccion de serie satisface la normativa VDE 0875 grado K y los requi sitos esenciales de seguridad impuestos por la directiva euro pea sobre la compati bilidad electroma gn tica la conformi dad con esta ultima est garantizada por la
23. FRANCE MECC ALTE INTERNATIONAL S A Z E LA GAGNERIE 16330 ST AMANT DE BOIXE TEL 0545 397562 FAX 0545 398820 e mail aftersales Q meccalte fr ESPANA MECC ALTE ESPANA S A C RIO TAIBILLA 2 POLIG IND LOS VALEROS 03178 BENIJOFAR ALICANTE TEL 096 6702152 FAX 096 6700103 e mail aftersales Qmeccalte es U S A AND CANADA MECC ALTE INC 1229 ADAMS DRIVE MCHENRY Il 60051 TEL 815 344 0530 FAX 815 344 0535 e mail aftersales Qmeccalte us CHINA Member of CISQ Federation RINA Certified Quality System ALTERNATORI SERIE T20F MANUALE PER L USO E LA MANUTENZIONE GB T20F SERIES ALTERNATORS USE AND MAINTENANCE MANUAL F ALTERNATEURS SERIE T20F MANUEL POUR L ENTRETIEN ET LA MANUTENTION D GENERATOREN DER BAUREIHE T20F HANDBUCH FUR DIE BEDIENUNG UND WARTUNG E ALTERNADORES DE LA SERIE T20F MANUAL PARA EL USO Y MANTENIMIENTO UNITED KINGDOM MECC ALTE U K LTD 6 LANDS END WAY OAKHAM RUTLAND LE 15 6RF TEL 1572 771160 FAX 1572 771161 e mail aftersales Qmeccalte co uk MECC ALTE S p A Via ROMA 20 36051 CREAZZO VICENZA ITALIA Tel 39 0444 396111 Fax 39 0444 396166 E Mail aftersales omeccalte it Web site www meccalte it MECC ALTE ALTERNATOR HAIMEN LTD Po Aus INSULATION SYSTEM DEUTSCHLAND MECC ALTE GENERATOREN GmbH ENSENER WEG 21 D 51149 K LN TEL 02203 503810 FAX 0 22 03 50 37 96 e mail aftersalesOmeccalte de AUSTRALIA MECC ALTE ALTERNATORS PTY LTD 10 DUNCAN ROAD
24. I SEZIO NAMENTO PROTEZIO NI CONTRO CONTAT TI DIRETTI E INDIRETTI PROTEZIONI CONTRO SOVRACORRENTI E SOVRATENSIONI AR RESTO DI EMERGEN ZA ECC NECESSARIE PER RENDERE CON FORME IL MACCHINA RO E L IMPIANTO UTILIZZATORE ALLE VIGENTI NORME DI SICUREZZA INTERNA ZIONALI EUROPEE IMPORTANTE IMPORTANT WICHTIG MECHANICAL SERVICE MAN This symbol identifies the type of operator in charge of the operation described This qualifica tion requires a complete knowledge and under standing of the informa tion contained in the manufacturers instruc tion manual as well as specific skills necessary to perform installation adjustment maintenan ce cleaning and or repair operations ELECTRICAL SERVICE MAN This symbol identifies the type of operator in charge of the operation described This qualifica tion requires a complete knowledge and under standing of the informa tion contained in the manufacturers instruc tion manual as well as specific skills necessary to perom electrical operations such as connections adjust ment maintenance and or repair The electrical service man must be able to work even in case electrical cabinets and panels are live SAFETY REQUIREMENTS In case of exceptional operations and upon written request of servi cing operations please apply to Mecc Alte au thorized centers Before any cleaning lubrication or maintenan ce operation ensure that the gener
25. MPORTANTE IMPORTANT WICHTIG This is the reason why you must make sure that the grounding sy stem is in good condi tions and in compliance with the regulations of the country where the generator will be instal led For ground connection there is hole in the upper part of the end bracket which is accessible wi thout having to remove end cover The people in charge of the handling must al ways wear work gloves and safety shoes In ca se the generator or the whole plant must be lif ted from the floor the operators must wear a safety helmet PLEASE NOTE IN CASE THE ALTER NATOR HAS BEEN STORED FOR A LONG TIME AND IN ORDER TO AVOID DAMAGES CAUSED BY HUMIDITY WE SUGGEST THAT THE INSULATION RESI STANCE OF ALL WIN DINGS TO GROUND BE CHECKED BY MEANS OF A 500V MEGGER INCLUDING THE ROTOR THE RE SULTING DATA MUST BE HIGHER THAN 1 MO EN60204 1 IF DATA ARE NOT H GHER THAN SAID VA LUE BLOW WARM AIR OVER THE WIN DINGS TILL THE ABO VE MENTIONED VA LUE IS OBTAINED The generator must be installed in an airy room If there is not enough air a malfunction or an ove rheating may occur The machine was desi gned to guarantee the nominal power in envi ronments with a maxi mum temperature of 40 C at altitudes lower than 1000 m as ENG0034 1 unless otherwise specified for different operating condi tions see the commer cial catalogue brochure Pour cette raison s as s
26. NGULO ROSSO RED ROUGE ROT ROJO gt z 2 COLLEGAMENTO A STELLA STAR CONNECTION CONNECTION ETOILE STERNSCHALTUNG CONEXION EN ESTRELLA REGOLATORE REGULATOR REGULATEUR REGLER REGULADOR GENERATORE GENERATOR VERDE GREEN VERT GRUN IMPORTANZA THE IMPORTANCE IMPORTANCE DE DIE WICHTIGKEIT IMPORTANCIA DE DELLA VELOCITA OF SPEED LA VITESSE DER DREHZAHL LA VELOCIDAD La frequenza e la Frequency and volta La fr quence et la Die Frequenz und die La frecuencia y la tensione dipendono ge depend directly on tension d pendent de Spannung sinddirekt tension dependen de direttamente dalla ve la vitesse de rotation von der Drehzal ab la velocidad de rota rotational speed This dl locit di rotazione IMPORTANTE must be kept as con Celleci doit tre main ist es cion Esta debe ser perci necessario pesa stant as possible on tenue la plus constan GE wis S in mantenida lo mas che sia mantenuta il its nominal value no te possible quelle 9 constante posible en pi possibile costante matter what the load que soit la charge auf ihrem Nominal wert gehalten wer su valor nominal sea al suo valore nomina Drive motor speed G neralment le unabh nging cual sea General le con qualsiasi cari control system gene st me de r gulation von jeglicher Last mente el sistema de co ll sistema di rego rally
27. OU MUT TER TUERCA M8 UNI 5587 15 Ma 5 16x24 ANS B15 2 OADO NJT ECROU MUTTER TUERCA M10 UNI 5588 25 Nm Gravit t 5255 3955 4255 185 Centre de gravit Schwerpunkt T20FS 420 360 285 5 295 5 385 5 115 NO Cantas de aravedad T20F Instruction Manual September 2013 rev 04 Tipo Type L P T20FS 130 T20FS 160 T20F 200 Centro di gravita 210 203 213 FORMA FORM FORME MD35 KHN em mm wa TUERCA MB UNI 5597 15 Nm 5 16x24 ANS B1B 2 2 C DADO MAT ECROU MUTTER TUERCA M10 UNI 588 25 Nm Giunti a disco Disc coupling Acc disque Scheibenkupplung Centro di gravita Gravity center Centre de gravit Schwerpunkt NN dq Q n fori 1 d id band oia ntori at Centros de gravedad 1 id 20 6 60 T20FS 130 T20FS 160 T20F 200 meyer o 241 3 22225 8 45 dimensions in mm FORMA FORM FORME J609b DADO NUT ECROU MJTTER TUERCA MB UNI 5587 15 Nm 5 16x2 amp ANSI B18 2 2 DADO NUT ECROU MUTTER TUERCA M10 UN 5588 25 Nn Centro di gravita Gravity center Centre de gravit Schwerpunkt 146 165 4192 T20F 400 3255 335 5 425 5 155 139 YES Centros de gravedad 163 6 1 T20FS 130 T20FS 160 T20F 200 T20FS 360 285 5 295 5 385 5 115 NO 177 8 196 85 4216 14 T20F Instruction Manual September 2013 rev 04 DICHIARAZIONE DI CONFORMITA CE FORMA FORM FORME B9 c30 CE CONFORMITY DECLARATION DADO N
28. Reducida velocidad con carga Ge TENSION EXACTA EN VACIO PERO BAJA CON CARGA Carga demasiado elevada ET y h gase la intervenci n que TENSIONE ESATTA A VUOTO MA ALTA A CARICO Velocit elevata a carico Controllare i giri e regolare PROPER NO LOAD VOLTAGE BUT HIGH VOLTAGE AT LOAD High speed Check and regulate RPM TENSION VIDE CORRECTE MAIS TROP LEV E EN CHARGE R gler la vitesse EXAKTE SPANNUNG BEI LEERLAUF JEDOCH HOHE BEI LAST Erh hte Geschwidigkeit Bei Last Die Umdrehungeng berpr fen und regulieren TENSI N EXACTA EN VACIO PERO ALTA CON CARGA Elevada velocidad con carga Contr lense las revoluciones y aj stense Controllare le connessioni Verificare l uniformit di rotazione Check connections Check for uniform rotation speed V rifier les contacts V rifier l uniformit de rotation Die Anschl sse berpr fen Die Gleichmafigkeit der Rotation berpr fen Contr lense las conexiones Averig ese la uniformidad de rotacion Sostituire Verificare e riparare Replace Check and repair Le remplacer Le v rifier et le changer ventuellement Ersetzen Uberpr fen und reparieren Contatti incerti Irregolarit di rotazione Poor contacts Uneven rotation Mauvais contacts Vitesse instable Unsichere Kontakte Ungleichm ftige Rotation Contactos incostantes Irregularidad de rotaci n Cuscinetti avariati Accoppiamento difettoso Broken bearings Poor coupling Roulement cass Accouplement d fectueux De
29. UT ECROU MUTTER TUERLA MB UNI 5587 15 Nm 5 16x24 ANSI B18 2 2 DADO NUT ECROU MUTTER TUERCA M O0 UNI 5588 25 T20FS 130 T20FS 160 T20F 200 DECLARATION DE CONFORMITE CE Centro di gravita Gravity center Centre de gravit Schwerpunkt Centros de gravedad H CE KONFORMITATS ERKL RUNG dimensions in mm DECLARACION DE CONFORMIDAD CE Noi dichiariamo sotto la nostra sola responsabilit che la macchina We declare under our sole responsability that machine Nous declarons sous notre responsabilit que la machine Type T20F unterunsere da die Wir erk ren Verantwortlichkeit Maschine Nosotros declaramos bajo nuestra exlusiva responsabili dad que la m quina come descritta nella documen tazione allegata e nei nostri archivi in conformit con le direttive 2006 42 alla direttiva 2006 95 alla direttiva 2004 108 alle norme europee EN 12100 1 EN 12100 2 EN ISO 14121 1 EN 60204 1 EN 61000 6 3 EN 61000 6 1 EN 60034 1 Questa macchina non pu essere messa in servizio prima che la macchina in cui sar assemblata sia stata dichiarata conforme alle dispo sizioni della direttiva macchine 2006 42 CEE as described in the attached documentations and in our archives in conformity with Directive 2006 42 Directive 2006 95 Directive 2004 108 and European norms EN 12100 1 EN 12100 2 EN ISO 14121 1 60204 1 EN 61000 6 3 61000 6 1
30. ara conocer condiciones diferentes de las indicadas vea el cat logo comercial folleto September 2013 rev 04 generatori non devono mai e per nessuna ragio ne funzionare con le protezioni rimosse generatori sviluppano calore anche elevato in funzione della potenza generata Pertanto non toccare il generatore se non con guanti antiscot tatura e attendere una volta spento che esso raggiunga la temperatura ambiente PERICOLO DI CORTO CIRCUITO generatore costruito con grado di protezione IP23 pertanto fatto divieto di spruzzare o di mettere contenitori di liquidi sopra le parti elet triche Non pulire con aria com pressa le parti elettriche inteme poich possono verificarsi corto circuiti o altre anomalie Nele vicinanze della macchina non ci devono essere persone con indumenti svolazzanti tipo sciarpe foulard bracciali ecc e qualsiasi indumento deve essere chiuso con elastici alle estremit Anche se la macchina protetta in tutte le sue parti evitare di sostare nelle sue vicinanze Alla fine del periodo di vita dela macchina rivolgersi alle agenzie di smaltimento materiali ferrosi e non disperdeme parti nell ambiente In caso di sostituzione di pezzi di ricambio richie dere esclusivamente ricambi originali Nella messa in servizio aver cura che le apertu re di aspirazione e scari co dell aria di raffredda mento siano sempre libere
31. as die Transport und Anhebemittel die Eigen schaften der Transports chlingen und der siche ren Bewegung betrifft T20F Instruction Manual Por esta raz n es necesario adecuarse a la perfecci n a las instrucciones indica das en este manual Para cualquier tipo de comunicacion indicar siempre el tipo y el codigo del generador No dejar que el em balaje se pierda en el ambiente dirigirse siempre a cualquier agencia que trate el reciclaje de residuos PRECAUCIONES DE SEGURIDAD Cuando consulte este manual de uso y ma nutenci n ver de terminados s mbolos con un Significado presiso el cual en contrar ilustrado a continuaci n IMPORTANTE Signa a el personal interesado que el operation descrita presenta une riesgo que puede hacer como consecuencia une da o a la maqui na se no efectuada en el respecto de les normatives de securi dad PELIGRO Signa a el personal interesado que el ope ration descrita presen ta une riesgo que puede hacer como consecuencia une da o a la maquina l siones serios o muerte se no efectua da en el respecto de les normatives de securidad APLICADO A LA MOVIMENTATION Identifica el tipo de ope rador la cual es reserva do el intervenci n tarta do Esta calificaci n presu pone una llena conoci miento y comprensi n des informaci nes con tenidos en el manual para uso de el construc tor de la parte de all que competencia espe cificaci
32. asforma tore di regolazione Si tenga presente che con un carico equilibrato si ha nor malmente una so praelevazione della tensione che ar rivare nel caso di macchina fredda fino al 5 con cos 0 8 e fino al 10 con cos 1 Tali soprae levazioni di tensione si riducono comun que a met entro i primi 10 minuti di funzionamento del generatore Qualora si voglia diminuire la tensione si dovr togliere una spira per colonna dal trasfor matore verificando successivamente se il nuovo valore della tensione erogata a carico sia soddisfa cente Qualora non lo fosse ripetere l ope razione fino a che non viene raggiunto il valore desiderato Consigli utili per un minore scarto di tensione tra vuoto e carico indipenden temente dal fattore di potenza e dallo scar to di giri del motore primo bisogna met tere la macchina a l TRAFERRO NR TRAFERRO AIR GAP b apply for a few seconds a load of not less than 30 of the nominal power loosen up the tightening bolts 1 d increase the air gap to increase the voltage decrease it to reduce voltage 6 retighten the bolts 1 UI VOLTAGE REGU LATION AT LOAD To regulate voltage at load it is possible to modify the number of wire turns 2 of the regulating tran sformer Take note that with a balanced load normally there is a voltage increase which can reach in the case o
33. ator is stationary and discon nected from the power supply CAUTION THE FINAL INSTAL LER IS RESPON SABLE FOR THE INSTALLATION OF ALL THE PROTEC TIONS SECTIONING DEVICES PROTEC TIONS AGAINST DIRECT AND INDI RECT CONTACTS OVERCURRENT AND OVERVOLTAGE PROTECTIONS EMERGENCY STOP ETC NECESSARY FOR THE MACHINE TO COMPLY WITH THE EXISTING IN TERNATIONAL EUROPEAN SAFETY REGULATIONS PREPOSE MECANIQUE Identifi le type de ope rateur dont il est reserv l intervention trait Cette qualification sup pose une pleine connai sance et compr hension des renseignement con tenu dans le manuel d in struction du constructeur plus loin que comp ten ces sp cifiques pour ef fectuer les interventiones d installation regulation manutention nettoyage et ou r paration PREPOSE ELECTRIQUE Identifi le type de ope rateur dont il est reserv l intervention trait Cette qualification sup pose une pleine connai sance et compr hension des renseignement con tenu dans le manuel d in struction du constructeur plus loin que comp ten ces sp cifiquede nature lectrique de liaison re gulation manutention et ou r paration Il est en degr de agir en pr sence de ension l interieur des armoi res et tableaux lectri ques PRESCRIPTIONS DE SECURITE En cas des interventio nes extraordinaires et sur autorisation crite du service et assistance saddreser aux centres autoris
34. berpr fen Contr lense las revoluciones y ll vense al valor nominal Contr lense y substit yase Contr lense la resistencia de los arrollamientos como Averia en los arrollamientos resulta en la tabla T20F Instruction Manual September 2013 rev 04 INCONVENIENTI PROBLEMS PANNES CAUSE CAUSES CAUSES COME INTERVENIRE REMEDIES QUE STORUNG FALLOS URSACHE CAUSAS FAIRE GEGENMARNAHMEN REMEDIOS delecta eccessi Controllare i giri e regolare TENSIONE ALTA A VUOTO Guastohelirasformatore Controllare la resistenza degli avvolgimenti come da tabella Excessive speed Check and adjust RPM A Regulator transformer breakdown Check winding resistance as for table Vitesse trop rapide TENSION VIDE TROP LEV E Transformateur de r gulation d truit berh hte Geschwindigkeit Defekt an den Transformator R gler la vitesse V rifier les valeur l aide du tableau Die Drehzahl berpr fen und regulieren HOHE SPANNUNG BEI LEERLAUF Den Widerstand der Wicklungen gem Tabelle berpr fen Excesiva velocidad Contr lense las revoluciones y aj stense ALTA TENSION EN VACIO Averia en el trasformador Contr lense la resistencia de los arrollamiento regulador como resulta en la tabla Controllare i giri e regolare Controllare e sostituire Controllare la resistenza degli avvolgimenti come da tabella Velocit ridotta TENSIONE BASSA A VUOTO Diodi del ponte guasti Guasto negli avvolgimenti Low speed Check a
35. complete knowledge and un derstanding of the information contained in the manufacturer s instruction manual as well as specific skills about the hoisting means slinging me thods and features and safe handling procedures Pour cette raison il faut se conformer scrupuleuseent aux instructions indiqu es dans ce manuel Pour toute demande citer toujours le type et le code de l alter nateur Ne pais jeter l embal lage dans la nature mais s adresser un centre de recyclage PRESCRIPTIONS DE SECURITE Au cours de la con sultation du pr sent manuel d utilisation et d entretien vous trou verez des symboles dont la signification pr cise est expliqu e ci apr s IMPORTANT Signe au personnel interess que l opera tion d crite presente une risque qu il peut avoir comme con s quence une doma ge la machine si n effectu pas dans le respect des normes de securit DANGER Signe au personnel interess que l opera tion d crite presente une risque qu il peut avoir comme con s quence l siones graves ou mort si n ef fectu pas dans le respect des normes de securit PR POS A LA MOUVEMENTATION Identifi le type de ope rateur dont il est reserv l intervention trait Cette qualification sup pose une pleine connai sance et compr hension des renseignement contenu dans le manuel d instruction du construc teur plus loin que comp tences sp cifi ques de moyens du s
36. de de l alternateur Bei Ersatzteilbestellung bitte immer die Teilbenennung den Typ und den code des Wechselstromgenerators angeben En cada pedido de pizas de recambio especificar siembre el tipo y el codigo del alternador kkk kkk kkk kkk ESSE DRIVE END BRACKET MD 35 FLASQUE AVANTMD35 VORDERES GEHAUSE 35 ANTERIOR MD 35 16 T20F Instruction Manual September 2013 rev 04
37. el nuevo valor de la tension generada es satisfactorio En caso no lo sea repetir la operacion hasta obte ner el valor deseado Consejos utiles Independientemente del factor de potencia y de las diferencias en los rpm del motor primero para una menor diferencia de tension entre vacio y en carga se aconseja poner la maquina September 2013 rev 04 carico regolare la velocit fino ad otte nere la tensione volu ta disinserire il carico e regolare la tensione agendo sul traferro Nel caso in cui il generatore non si autoeccitasse occor 777 rera rieccitarlo appli alcuni cando per istanti all uscita del ponte raddrizzante una tensione conti N nua di 10 50 Vdc avendo cura di rispet tare le polarit rosso verde VERIFICA DEI DIODI Con un ohmmetro controllare ogni sin golo diodo che dovr indicare continuit in un solo senso oppu re con una pila e una lampadina inverten do la polarit della pila la lampadina si deve accendere in un solo senso come da figura IMPORTANZA DEL SENSO DI ROTAZIONE Per ottenere le pre stazioni dichiarate necessario che il generatore ruoti in senso orario visto dal lato di accoppiamen to excite IMPORTANTE IMPORTANT WICHTIG red voltage remove the load and regula te voltage by ad justing the air gap If the generator is not able to reach a self excitement condition
38. enbau darf nur dann erfolgen wenn die Vorschriften der Maschinenri chtlinien 2006 42 EWG einge halten werden MECC ALTE S p A Via Roma 20 36051 Creazzo VI Italy 01267440244 01267440244 0444 396111 0444 396166 info meccalte it www meccalte com 15 como descripta en la docu mentaci n adjunta y en nue stros archivos est de acuer do con las directivas 2006 42 con las directivas 2006 95 con las directivas 2004 108 y las normas europeas EN 12100 1 EN 12100 2 EN ISO 14121 1 EN 60204 1 EN 61000 6 3 EN 61000 6 1 EN 60034 1 Esta m quina no puede ser puesta en servicio antes que la m quina resultante con la cual ser acoplada sea decla rada conforme con los disposi ciones de la directiva m quina 2006 42 CEE T20F Instruction Manual September 2013 rev 04 ELENCO PARTI DI RICAMBIO LIST OF SPARE PARTS LISTE DES PIECES DETACHEES ERSATZTEILLISTE LISTA PARTES DE REPUESTO CHIUSURA POSTERIORE REAR SEAL TOLE DE FERMETURE ARRIERE HINTERER DECKEL CIERRE POSTERIOR 0390700011 CUFFIA TERMINAL BOX LID COUVERCLE KLEMMENKASTENDECKEL TAPA 0390501015 TRASFORMATORE REGULATING TRASFORMATEUR COMPOUND COMPOUND TRANISFORMER DE COMP TRANSFORMATOR EE MORSETTIERA PLACA DE BORNES UTILIZZAZIONE TERMINAL BOARD PLANCHETTE A BORNES KLEMMENBRETT TERMINAL 9909915060 CARCASSA CON STATORE FRAME AND STATOR CARCASSE AVEC STATOR GEH USE MIT STATOR CARCASA CON ESTATOR COPERCHIO ANTERIORE B14 DRIV
39. f a cold unit up to 596 with 0 8 power factor and up to 10 with unity power factor Such voltage increases however drop down to half their value within the initial 10 minutes of the alter nator s operation At any rate if a volta ge decrease is desi red a wire turn per each transformer column will need to be removed and then the voltage output will need to be checked to be found satisfac tory in case it is not so one must repeat this operation until the desired voltage value is reached Recommendations to reduce the diffe rence between load and no load voltage independently of power factor and RPM differences first load the machine adjust speed until you obtain the desi b Appliquer pendant quelques secondes une charge quiva lente de 3096 de la vi tesse nominale Desserrer les crous de serrage 1 d Augmenter l entre fer pour augmenter la tension ou le r duire pour diminuer la ten sion 6 bien resserrer les crous de serrage aq R GLAGE DE LA TENSION EN PLEI NE CHARGE Pour le r glage de la tension pleine char ge il est possible d a gir sur le nombre des spires 2 du transfor mateur de r gulation Il est noter qu avec une charge quili br e une augmenta tion de la tension peut alors se produire et ce dans le cas d une machine froide ju squ 5 avec un cos 0 8 et jusqu 10 avec un cos de 1 Cette surtension se r
40. fekte Lager Falsche Kupplung TENSIONE INSTABILE UNSTABLE VOLTAGE TENSION INSTABLE SCHWANKENDE SPANNUNG TENSI N INESTABLE GENERATORE RUMOROSO NOISY GENERATOR ALTERNATEUR BRUYANT GER USCHE AM GENERATOR Coijnetes averiados Acoplamiento defectuoso Substit yase GENERADOR RUIDOSO Averig ese y rep rese T20F Instruction Manual September 2013 rev 04 CARATTERISTICHE CHARACTERISTICS CARACTERISTIQUES TECNISCHE MERKMALE CARACTERISTICAS 3000 RPM 230 400V 50Hz Regolatore compound Compound regulator Regulation compound Compound regler Regulador compound Potenza Potenza trifase Avvolgimento ausiliario Potenza Eccitazione Volume d aria Rumore Peso monofase Three phase Single phase power Statore Rotore Auxiliary winding Rating Excitation Air volume Noise Weight power Puissance Puissance triphase Stator Rotor enroulement auxiliaire Puissance Exitation Volume d air Bruit Poids Monophase Leistung Leistung Dreiphasig Estator Hilfs wicklung Leistung Erregung Luftmenge Gerausch Gewicht Einphasig Potencia Potencia trifasica Bobinado auxiliar Potencia Excitation Volumen de aire i Peso monofasica LJ MD35 C Kg 11 6 T20FS 130 14 3 kVA T20F 200 Regolatore compound Compound regulator Regulation compound Compound regler Regulador compound Potenza Potenza trifase Avvolgimento ausiliario Potenza Eccitazione Volume d aria Rumore Peso monofase Three phase Single phase
41. ifi que directement propor tionnelle la puissance utilis e Ainsi ne pas toucher l altemateur ou bien avec des gants appropri s et attendre que celuici une fois arr t soit de nou veau la temp rature ambiante DANGER DE COURT CIRCUIT L alternateur est con struit avec un grade de protection IP23 il est formellement d conseill d asperger ou de mettre tout r cipient contenant du liquide sur les parties lectriques Ne pas nettoyer avec l air comprim les parties electriques internes car Ton pourrait provoquer un court circuit ou autres anomalies Dans le voisinage de la machine il ne doit y avoir aucune person ne portant des v te ments flottants type charpe foulard ect quelque soit le v te ment il doit tre fer m avec un lastique l extr mit La machine est pro t g e dans tout son environnement viter de rester dans son voisinage A la fin de la p riode de vie de la machine s adresser aux orga nismes de recyclage du mat riel concern En cas de change ment de tout compo sant il est indispen sable de les rempla cer par les pi ces d origine S assurrer que les couvercles de ventila tion ne sont pas obstru es Die Generatoren d rfen unter keinen Umstanden ohne Schutzelemente in Betrieb genommen werden Die Generatoren entwic ken Warme auch in erh htem Ma e jeweils in Abh ngigkeit von der erzeugten Leistung Au
42. n regulaci n manu tenci n limpieza y ou re paraci n MANUTENDOR ELECTRICO Identifica el tipo de ope rador la cual es reserva el intervenci n tarta O Esta calificaci n presu pone una llena conoci miento y comprensi n des informaci nes con tenidos en el manual pa ra uso de el constructor de la parte de alla que competencia especifica ci n por efectuar los in tervenci ones de natura electrica de coligamien to regulaci n manuten ci n y ou reparaci n Es en grado de trabajar en presencia de ten sion a los intemo des armarios y cuadros electricos PRECAUCIONES DE SEGURIDAD En caso de interven cines extraordinarios su autorizaci n escritura du servicio assistencia revolverse a los centros autorizado Mecc Alte Antes de cualquier tipo de operaci n sobre el generador el motor pri mario al cual esta aco plado no sea en funcio namiento y que no exi stan piezas faltantes en movimiento ATENCION EL INSTALADOR FINAL ES RESPONSABLE DEL MONTAJE DE TODAS LAS PROTECCIONES DISPOSITIVOS DE SECCIONAMIENTO PROTECCIONES CON TRA CONTACTOS DI RECTOS INDIREC TOS PROTECCIONES CONTRA SOBRECOR RIENTE Y SOBRETEN SION PARADA DE EMERGENCIA ETC NECESARIAS PARA PRODUCIR LA CON FORMIDAD DE LAS MA QUINAS Y LA INSTALA CION CON LAS NOR MAS VIGENTES DE SE GURIDAD INTERNACIO NALES Y EUROPEAS September 2013 rev 04 Per questa ragione assicurarsi che l impian
43. nd adjust RPM LOW NO LOAD VOLTAGE Broken diodes on bridge Check and replace Breakdown in windings Check winding resistance as for tables Vitesse trop lente R gler la vitesse TENSION A VIDE TROP BASSE Pont de diode d truit V rifier et changer Bobinage d t rior V rifier les valeur l aide du tableau Die Drehzahl berpr fen und regulieren Uberpr fen und ersetzen Den Widerstand der Wicklungen gem Tabelle berpr fen Reduzierte Geschwindigkeit Defekt an den Dioden Fehlerhafte Wicklungen NIEDRIGE SPANNUNG BEI LEERLAUF Contr lense las revoluciones y aj stense Contr lense y substituyase Contr lense la resistencia de los arrollamiento como resulta en la tabla Reducida velocidad Diodos del puente averiados Arrollamientos averiados Velocit ridotta a carico Controllare i giri e regolare TENSIONE ESATTA A VUSOTOMABASSA Carico troppo elevato Controllare ed intervenire Low speed at load Check and regulate RPM PROPER NO LOAD VOLTAGE BUT LOW VOLTAGE AT LOAD Load too big Check and change BAJA TENSI N EN VACIO Vitesse en charge incorrecte V rifier et r gler la vitesse TENSION A VIDE CORRECTE MAIS BASSE EN CHARGE Charge trop importante V rifier la charge EXAKTE SPANNUNG BEI LEERLAUF JEDOCH NIEDRIGE Reduzierte Geschwindigkeit bei pio Umdrehungen berpr fen und regulieren Last 9 dono LAST Zi hohe asi Uberpr fen und eingreifen Contr lense las revoluciones y aj stense A
44. ore di regolazione nel seguente modo a regolare la veloci t del motore a vuoto circa il 4 superiore della velocit nomi nale ge regulation it is ne cessary to work on the regulation tran sformer air gap in the following way a regulate engine speed at no load about 4 higher than nominal speed sur l entrefer du tran sformateur de r gula tion de la mani re suivante a R gler la vitesse du moteur vide en viron 4 audessus de la vitesse nomina le LEERLAUF Um die Spannung im Leerlauf einzustellen ist es notwendig den Luftspalt am Com poundtrafo nach fol gender Beschreibung einzustellen a die Motordrehzahl bei Leerlauf auf circa 4 ber Nominalge schwindigkeit einstel len T20F Instruction Manual la tension en vacio se tendra que ajustar el entrehierro del tran sformador de regula cion de la siguiente manera a regular la veloci dad del motor en va cio a aproximadaente un 4 mas de la ve locidad nominal September 2013 rev 04 b applicare qualche secondo un carico non minore del 30 della potenza nominale C allentare i dadi di serraggio 1 d aumentare il tra ferro per aumentare la tensione o dimi nuirlo per diminuire la tensione 6 richiudere bene i dadi di serraggio 1 REGOLAZIONE DELLA TENSIONE A CARICO Per la regolazione della tensione a cari co possibile agire sul numero delle spi re 2 del tr
45. oul vement des m thodes et des ca ract risiques d ligage et du mouvementation en s curit Aus den oben gen nanten Grunden ist es erforderlich sich streng an die in die sem Handbuch ange gebenen Answeisun gen zu halten F r Mitteilungen ist der Generatrorentyp und der Code anzu geben Die Verpackung ist durch die entspre chenden den Entsor gungsunternehem zu entsorgen SICHERHEITS VORSCHRIFTEN Beim Lesen dieser Gebrauchs und War tungsanleitung finden Sie einige Symbole zu finden diese habe eine ganz genaue Bedeutung die im Folgenden erl utert wird WICHTIG Signalisieren Sie dem zust ndigen Perso nal da die be schriebene Arbeit ein Risiko darstellt wel ches Sch den an der Maschine zur Folge haben kann falls die Arbeit nicht unter voller Beachtung der Sicherheitsvorschrif ten erfolgt GEFAHR Signalisleren Sie dem zust ndigen Personal da die beschnebene Arbelt ein Risiko dar stelli wetches schwere Verletzungen oder sogar den Tod zur Folge haben kann falts die Arbeit nicht unter voller Beachtung der Sicherheitsvorschriften erfolgt TRANSPORT BEAUFTRAGTER Identifiziert den Perso nentyp der mit dem Transport bzw der Bewegung der Maschi ne beauftragt ist Diese Qualifikation setzt eine volle Kenntnis und Ver st ndnis der im Be dienungshandbuch des Herstellers enthaltenen Informationen voraus zus tzlich zu den spezifi schen Kompetenzen w
46. ourne dans le sens horaire vu du c t de l accou plement gew nschte Span nung vorhanden ist Last abklemmen und die Spannung mittels Luftspalt einstellen Falls der Stromerzeu ger sich nicht erregen sollte wird es n tig ihn durch die Anwen dung einer fortlaufen den Spannung 10 50 Vdc am Au sgang der gleichrich tenden Br cke wiede raufzuregen die Po larit ten m ssen beachtet werden rot grun DIODEUEBERPRUE FUNG Mit einem Ohmeter jede einzige Diode kontrollieren die Ste tigkeit in einer eizigen Richtung zeigen wird Entweder mit einer Batterie oder mit ei ner kleinen Lampe beim Umkehren der Batteriepolaritaet muss die kleine Lam pe sich in einer einzi gen Richtung en tzuenden wie abgebildet DIE WICHTIGKEIT DER DREHRICHTUNG Um die ausgewiese ne Leistung zu errei chen ist es notwen dig den Generator von der Antriebsseite aus gesehen im Uhr zeigersinn anzutrei ben bajo carga regular la velocidad hasta obte ner la tension desea da quitar la carga y regular la tension ajustando el en trehierro Caso el generador no se autoexcitase se debe excitarlo apli cando por algunos instantes a la salida del puente endereza dor una tensi n con t nua de 10 50 Vdc teniendo el cuidado de respetar las polari dades rojo verde VERIFICACIONES DE LOS DIODOS Utilisar un ohmniome tro para comprobar individualemente cada diodo Los dio dos son
47. riffe elektrischer Natur betrifft wie Anschl sse Einstel lung Wartung und oder Reparaturen ualifikation Informationen vo Er ist in der Lage auch Arbeiten im Inneren von Schaltschr nken und tafeln wenn diese unter Span auszuf hren nung stehen SICHERHEITS VORSCHRIFTEN Im Fal von au er gew hnlichen Eingriffen und auf schriftliche Best tigung des techn Services sich an die auto risierten dienstzentren von Mecc Alte wenden Vor jedem Kunden Eingnff f r Reinigung oder War Betrieb gesetzt werden er stillstehen und von seinen Energiequel len isoliert werden ACHTUNG DER ENDMONTEUR IST VERANTWORTLICH FUR DIE VOSTELLUNG UND VORBEREITUNG ALLER S C H U T Z VORRICHTUNGEN TRENNVORRICHTUNGE N SCHUTZVORRI CHTUNGEN GEGEN DI REKT UND INDI RETKONTAKT SCHU TZVORRI HTUNGEN GEGEN UBERSTROM UND BENNUNG NO TAUS ETC DIE MA SCHINE UND DIE ANLA GE DES ANWENDERS AN DIE GULTIGEN IN TERNATIONALEN UND EUROP ISCHEN SICHE RHEITSVORSCHRIFTEN ANZUPASSEN T20F Instruction Manual MANUTENDOR MECANICO Identifica el tipo de ope rador la cual es reserva do el intervenci n tarta do Esta calificaci n pre supone una llena conoci miento y comprensi n des informaci nes con tenidos en el manual pa ra uso de el constructor de la parte de all que competencia especifica ci n por efectuar los in tervenci nes de instala co
48. s diesem Grunde ist die Maschine nur mit Ver brennungsschutzhandsc huhen zu ber hren Ist die Maschine ausge schaltet ist abzuwarten da diese wieder Um gebungstemperatur annimmt GEFAHR VON KURZSCHLUSSEN Der Generator ist mit einem Schutzgrad IP23 konstruiert daher ist es verboten die elektr schen Teile zu bespri tzen oder Beh lter mit Fl ssigkeiten auf diese zu stellen Die innenliegenden Elektrotele niemals mit pressluft reinigen da sich Kurzschl sse oder ande re St rungen daraus ergeben k nnten In der N he der Maschi nen d rfen sich keine Personen aufhalten die nicht anliegende Klei dungsoder Schmuck stucke tragen wie zB Schals T cher Armb n der usw Jedes Klei dungsst ck mu an den Gelenken durch Gummis geschlossen werden Auch wenn die Maschine vollst ndig abgesichert ist ist der Aufenthalt in ihrer N he zu vermeiden Am Ende der Le bendsdauer der Maschi nen hat man sich an die Entsorgungsunterneh men f r Esenmaterialen zu wenden Teile d rfen nicht einfach weggewor fen werden M ssen Teile au sgewechselt werden sind ausschlie lich origi nal Ersatzteile anzufor dem Bei der Inbetriebnahme ist zu gew hrleisten da die offhungen f r die ansaugung bzw f r den austritt der k hlluft immer frei bleiben Bajo ning n motivo ni por ninguna raz n los generadores deben ser utlizados con las protec ciones retiradas Los generadore
49. s produ cen calor y el mismo puede ser elevado en funci n de la potencia generada por lo tanto no tocar la m quina si no se posee guantes antique maduras despu s de un tiempo de haber deteni do el generador hasta que el mismo alcance la temperatura ambiente PELIGRO DE CORTO CIRCUITO El generador est con stuido con grado de protecci n P23 por lo tanto se prohibe salpicar o colocar recipientes con l quido sobre las partes el ctricas No limpiar con aire com primido las partes electri cas intemas debido a la posibilidad de causar corto circuitos cual quier otro tipo de proble ma En pr ximidades de la m quina no deber haber personas con indumentaria volante como pulseras bufan das etc Qualquier otro tipo de indumentaria deber ser fijada con el sticos en las extremi dades Si bien la m quina est protegida en todas sus partes evitar de pararse cerca de la misma Al final del periodo de vida til de la m quina dirigirse a una agencia de reciclaje de materia les ferrosos de manera de no perder partes en el ambiente En caso de sustituci n de partes de repuesto exigir exclusivamente repuestos originales En la puesta in servicio asegurarse que las aberturas de aspiracion y descarga del aire de refrigeracion se encuentren siempre libres de obstaculos T20F Instruction Manual September 2013 rev 04 PERICOLO DANGER ACCOPPIAMENTO MECCANICO Nel ca
50. siti es senziali di sicurezza imposti dalla direttiva europea sulla compa tibilit elettromagneti ca la conformit a quest ultima garan tita dall applicazione delle norme europee EN 61000 6 3 EN61000 6 1 PREMESSA generatori della se rie T20F rispondono ale direttive CEE 2006 42 2006 95 2004 108 e relative modifiche pertanto non presentano peri coli per l operatore se installati usati mantenuti secondo le istruzioni fornite dalla Mecc Alte e a condi zione che i dispositivi di sicurezza siano te nuti in perfetta effi cienza MACHINE DESCRIPTION T20F Series alterna tors are three phase compound regulation alternators with bru shes 2 poles T20F alternators are made in compliance with the 2006 42 2006 95 2004 108 directives and their amendments and the EN 60034 1 CEI 2 3 IEC 34 1 VDE 0530 BS 4999 5000 N F 51 111 The end brackets are diecast in high resi stance alluminum al loy the shaft is in C45 steel and is fitted with fixing ring The mechanical pro tection level meets standard IP23 upon request higher levels of protection can be supplied The H cass insula tion and windings are impregnated with tro picalized epoxy re sins The standard genera tors comply with the specification VDE 0875 degree and with the basic safety requirements of the European regulation on electromagnetic compatibility by ap plying the European standards EN 61000
51. so di accoppiamento di un generatore serie T20F avente forma costruttiva B3 B9 seguire le seguenti istru zioni montare il coperchio ante riore sul motore fissandolo con le apposite viti e applican do una coppia di serraggio di 48 7 se si impiegano vit M10 o 21 7 Nm nel caso di viti M8 fig 1 bloccare l alternatore sul co perchio fissando i quattro dadi M8 sui tiranti applicando una coppia di a 16 7 Nm fig 2 inserire il tirante centrale nel la sua sede fig 3 bloccare il tirante centrale applicando sul dado M8 una coppia di serraggio pari a 21 7 Nm rimontare le reti ne di protezione laterali e la griglia di chiusura posteriore applicando sulle vii M5 una coppia di serraggio pari a 3 5 7 Nm fig 4 MECHANICAL COUPLING When ooupling with an T20F series generator having a B3 B9 form follow the instructions below mount the front cover on the motor fixing it with the appro priate screws and applying a tightening torque of 48 Nm if using M10 screws or 2147 Nm for M8 screws fig 1 lock the altemator into the cover by fixing the four M8 nuts onto the bolts applying a tightening torque of 16 7 Nm fig 2 insert the central bolt into its housing fig 3 lock the central bolt by ap plying a tightening torque of 2117 Nm to the M8 nut reassemble the lateral protec tive nets and the rear closing grid by applying a tightening torque of
52. urer que l installation de mise la terre fonctionne bien et soit en conformit avec les directives du pays ou le g n rateur sera install Pour le raccordement la masse il est pr vu sur la partie sup rieure un trou accessible sans avoir d monter le cou verde Les personnes em ploy es la manutention doivent avoir des gants et des chaussures de s curit Dans le cas ou l altemateur ou le groupe lectrog ne doivent tre soulev de terre les op rateurs doivent utili ser un casque de protec tion ATTENTION AU CAS OU LES AL TERNATEURS AU RAIENT S JOUR N S LONGUEMENT EN MAGASIN IL EST CONS ILL DE CONTROLER LES R SISTANCES DL SOLEMENT DE TOUS LES ENROU LEMENTS LA MASSE Y COMPRIS LE ROTOR LA VA LEUR RELEV E DOIT TRE SUP RIEUR 1 MO EN60204 1 DANS LE CAS CONTRAI RE IL EST N CES SAIRE DE R CHAUFFER LES BOBINAGES EN IN SUFLANT DE L AIR CHAUD L altemateur doit tre in stal dans un endroit a r Si la quantit dar nest pas suffisante outre un mauvais fonc tionnement il existe aus si un risque de surchauf fe La machine a t concue afin de garan tir la puissance nomi nale dans des lieux ayant une temp ratu re maxima de 40 C et une altitude inf rieure 1000 m tres EN60034 1 sauf in dication diff rente pour des conditions diff rentes consulter le catalogue commer cial d pliant Aus diesem Grunde ist