1. address see page 1 9 Limited warranty and limitation of liability By continuous quality checks and production controls most modern electronics and high quality materials we guarantee that the tester will be free from defects in material and workmanship for two years This warranty does not cover batteries improper handling not intended purpose opening the hou sing improper storage or damages from accidents No other warranties such as fitness for a particular purpose will be given We are not liable for any indirect incidental or consequential damages or losses arising from any cause or theory 21 10 Accessories General information for test probes etc Only screwable SPB test probes from the manufac turer may be used e g insertion prods probes for overhead lines and extension test probes The test probe is attached with its sleeve to the test electrode of the voltage tester and bolted on under slight pressure The thread of the test probe thereby presses about 1 1 2 convolution on the conical part of the test electrode Attention The connection between test probe and voltage tester has to be controlled in each case Check function at a known voltage source or by continuity test Only a perfect mechanical connection ensures safe contact and thus an unambiguous voltage test For frequent use we recommend fitting the test electrodes of the voltage tester with an M 3 5 thread ask for info S
2. Load is depending on voltage and time For safety reasons it reduces automatically At 230 V and 20 C ambient temperature load is 31 mA for 15 seconds Afterwards the additional load becomes highly resistive After 30 s cool down the additional load is ready again 4 6 Resistance and continuity test When the device is switched off hold the test elec trodes together in order to perform the continuity test 000 kQ is indicated at the display Connect securely both test prods to the test point With resistance values between 0 1000 kQ the LCD in steps of 50 kQ indicates measurement values in With resistance values of more than 1000 KQ indication signalises overflow with OL and kQ Note The internal energy source is exhausted when the battery symbol amp appears during continuity tests About 100 test procedures are still possible see section 6 Note Maybe that after continuity tests and oFF indication a numerical value is indicated This value corresponds to the version of the current software 19 5 Technical data Nominal voltage range Nominal frequency range Measurment range Input resistance Current peak value On time Display SPB 500L 50 500 V AC DC SPB 1000L 50 1000 V AC DC 0 2000 Hz SPB 500L 24 500 V AC DC 2 5 5D SPB 1000L 24 1000 V AC DC 2 5 5D direct 500L 150 190 kQ at 500 V 500L at50V switch
3. The casing is made off an unbreakable solid rubber and protects the internal electronics against heavy shocks water and dust Thanks to its high degree of protection IP65 the Pr fball SPB L may even be used in rain The Pr fball SPB L works without battery the buffer cell for continuity tests is automa tically charged during voltage tests 1 1 Intended use This device is intended for use in applications as described in the operating instructions only Thus it is imperative to observe the notes on safety and the technical data in conjunction with the ambient conditions Any other form of usage is not permitted and can lead to accidents or destruction of the unit Any misuse will result in the expiry of all guarantee and warrantly claims 2 Safety Precautions The Pr fball SPB L voltage tester has been approved by VDE test authorities for application of the VDE GS symbol When used for its intended purpose the safety of the operator as well as that of the instrument is assured In order to maintain flawless technical safety condi tions and to assure safe use it is imperative that you read these operating instructions thoroughly and carefully before placing your instrument into service and that you follow all instructions contained therein Observe the following safety precautions gt The voltages indicated on the Pr fball SPB are rated voltages The voltage tester may only be used in systems working within
4. fer EG Konformit tserkl rung gem der EG Niederspannungs Richtlinie 2006 95 EG Anhang III B vom 12 Dez 2006 Hiermit erkl ren wir dass das nachstehend bezeichnete Produkte in ihrer Konzeption und Bauart sowie in der von uns in Verkehr gebrachten Ausf hrung den grundlegenden Sicherheits und Gesundheitsanforderungen der EG Richtlinie Niederspannung entspricht Bei einer mit uns nicht abgestimmten nderung des Produktes verliert diese Erkl rung ihre G ltigkeit Diese Erkl rung beinhaltet jedoch keine Zusicherung von Eigenschaften Hersteller Rudolph Tietzsch GmbH amp Co KG Willringhauser Str 18 D 58256 Ennepetal Beschreibung des elektrischen Betriebsmittels TypModei Pr fball SPB 500 L SPB 1000 L Funktion Zweipoliger Spannungspr fer f r Niederspannungsnetze Baujahr ab 2013 Es wird die bereinstimmung mit weiteren ebenfalls f r das Produkt geltenden Richtlinien Bestimmungen erkl rt EMV Richtlinie 2004 108 EG vom 15 Dezember 2004 ROHS Richtlinie 2011 65 EU vom 8 Juni 2011 WEEE Richtlinie 2012 19 EU vom 4 Juli 2012 Angewandte harmonisierte Norm Arbeiten unter Spannung Spannungspr fer Zweipoliger Spannungspr fer f r Niederspannungsnetze DIN EN 61243 3 VDE 0682 Teil 401 2011 02 EN 61243 3 2010 Jahreszahl der CE Kennzeichenvergabe 2013 Angabeildentit t zur Person des Unterzeichners Michael Tietzsch Gesch ftsf hrer
5. of 8 June 2011 WEEE Directive 2012 19 EU of 4 July 2012 Reference to the harmonized standards Live working Voltage detectors Two pole low voltage type EN 61243 3 2010 IEC 61243 3 2009 Year of the CE characteristic assignment 2013 Personal data of the signer Michael Tietzsch CEO 23 24
6. Einsatzbedingungen und H ufigkeit der Benutzung kann eine fr here Pr fung vom Anwender festgelegt werden Die Seriennummer mit Herstelldatum WWJJNN Woche Jahr Nummer ist auf der Vorder seite des Ger ts eingepr gt Wiederholungspr fungen werden vom Hersteller angeboten und durch eine Pr fplakette gekennzeichnet 8 Reparatur Eine Reparatur ist nur durch den Hersteller oder durch vom Hersteller ausdr cklich erm chtigte Werkst tten zul ssig Bei Besch digung des Ger tes Ausfall des Funktionstests nach Abschnitt 3 2 oder zur detaillierten berpr fung Kalibrierung wenden Sie sich bitte an service tietzsch de oder senden Sie das Ger t mit Fehlerbeschreibung an den Hersteller Adresse siehe Seite 1 9 Eingeschr nkte Garantie und Haftungsbeschr nkung Durch st ndige Qualit tskontrollen modernste Elektronik und hochwertige Werkstoffe gew hrlei sten wir dass dieser Pr fer f r die Dauer von 2 Jahren frei von Material und Fertigungsdefekten bleibt Diese Gew hrleistung gilt nicht f r Batterien unsachgem e Handhabung nicht bestimmungs gem e Verwendung ffnen des Geh uses falsche Lagerung oder Sch den durch Unf lle Es werden keine weiteren Garantien wie die Eignung f r bestimmte Anwendungen abgegeben Wir bernehmen keine Haftung f r Begleit oder Folgesch den oder Verluste gleich welche Ursache zugrunde liegt 10 Zubeh r Allgemeine Hinweise zu Priifspitzen etc Es d rfen
7. fungen mit vollst ndiger Anzeige auch bei v llig entladenem Akkumulator m glich Die zus tzlichen Pr ffunktionen Phase Drehfeld und Durchgang werden von einem integrierten Li Akku gespeist Dieser wird bei jeder Spannungspr fung automatisch geladen somit entf llt der Wechsel von Batterien Hinweis Die h ufige Nutzung der zus tzlichen Pr f funktionen kann ein zus tzliches Laden des Akkus erforderlich machen siehe Abschnitt 6 3 2 Priifen von Anzeige und Funktion Eigentest Nach DIN VDE 0105 100 m ssen Spannungspr fer mindestens unmittelbar vor und nach M glichkeit auch nach Gebrauch berpr ft werden Schritt 1 Pr fen der Leitung Funktion Halten Sie die beiden Pr felektroden zusammen Display zeigt 000 kQ an L sen Sie die Pr felektroden voneinander Auf dem Display wird OL kQ angezeigt Hierdurch wird die Gesamtfunktion des Ger tes berpr ft Hinweis Falls beim Zusammenhalten der beiden Pr felektroden das Batteriesymbol erscheint m ssen Sie den Akku laden siehe Abschnitt 6 Spannungspr fungen sind weiterhin auch bei leerem Akku m glich Schritt 2 Test der LV Anzeige berpr fen Sie die Funktion der LV Anzeige rote LED an einer bekannten Spannungsquelle AC und DC Der Spannungswert wird auf dem Display angezeigt Achtung F llt bei der Eigen berpr fung eine Anzeige auch nur teilweise aus oder wird keine Funktionsbereit schaft angezeigt darf der Spannungspr fer nicht mehr ve
8. integrierter Lithium Akku f r Funktionen Durchgang Phase Drehfeld wartungsfrei ohne Batterie SPB 500L CATIV500V SPB 1000L CAT IV 1000 V gt 12 kV 1 2 50 us 6 kV 15 45 Vollsilikon unzerbrechlich Anzeigeabdeckung aus schlagfestem Polycarbonat IP 65 Ger t bei Niederschlagen verwendbar PUR Mantelleitung 1000 V 1m IEC 61243 3 2009 EN 61243 3 2010 DIN EN 61243 3 2011 DIN EN 61326 274x 75 x47 mm Anzeigeteil 415g 6 Akku testen und laden Wenn beim Zusammenhalten der beiden Pr felek troden das Batteriesymbol erscheint m ssen Sie den Akku laden Stecken Sie hierzu die Pr felektro den des Pr fball in eine 230 V Steckdose so dass die Anzeige 230 V zeigt Lassen Sie den Pr fball so mindestens 10 Stunden in der Steckdose h ngen damit der Li Akku wieder v llig aufgeladen ist Die Einschaltdauer von 30 s ist hier ohne Bedeutung F hren Sie vor weiterer Benutzung des Ger tes den Funktionstest siehe Abschnitt 3 1 durch 7 Wartung 7 1 Allgemeine Informationen Der Pr fball ist v llig wartungsfrei Dennoch ist folgendes f r den sicheren Betrieb zu beachten Bewahren Sie Ihren Spannungspr fer stets in trockenem und sauberem Zustand auf Das Geh use k nnen Sie mit einem mit Isopropanol Alkohol oder Seifenwasser befeuchteten Tuch reinigen 7 2 Wiederholungspr fung Nach EN 61243 3 wird eine Wiederholungspr fung empfohlen Sie soll die Frist von 6 Jahre nicht berschreiten Je nach
9. nur aufschraubbare SPB Pr fspitzen etc vom Hersteller verwendet werden z B Kabeleinstech spitzen Freileitungspr fspitzen Verl ngerungsspit zen Die Verl ngerung wird mit der Muffe auf die Pr felektrode des Spannungspr fers aufgesteckt und unter leichtem Anpressdruck festgeschraubt Das Gewinde der Pr fspitze dr ckt dabei etwa 1 1 2 Gewindeg nge auf den konischen Teil der Pr felek trode Achtung Die Verbindung zwischen Pr fspitze und Spannungs pr fer ist jeweils zu kontrollieren berpr fen Sie die Funktion an einer bekannten Spannungsquelle oder mit dem Durchgangstest Nur eine einwandfreie mechanische Verbindung gew hrleistet sicheren Kontakt und damit eine eindeutige Spannungspr fung Bei h ufigem Einsatz empfehlen wir die Pr fe lektroden des Spannungspr fers zur Verbesserung der Verbindung mit Gewinde M 3 5 zu versehen Info anfordern Sicherheitshinweise gt Nur eingewiesenes Fachpersonal darf diese Ar beiten ausf hren Beachten Sie die Mindestab st nde zu anderen unter Spannung stehenden oder geerdeten Anlagenteilen und verwenden Sie pers nliche Schutzausr stung gem den landesspezifischen Unfallverh tungsvorschriften in Deutschland BGV A3 oder VDE 0105 100 gt Ger t nur an den Handhaben anfassen um die Anzeige nicht zu verdecken und die Verl nge rungsspitzen nicht zu ber hren gt Spannungspr fer und Pr fspitzen etc m ssen trocken und sauber sein gt S
10. these rated voltage ranges gt Faultless indication of display values is only guaranteed between 15 and 45 C gt Hold the instrument by the handgears only to avoid covering the display and not touching the test electrodes gt The maximum on period is 30 seconds gt Only qualified persons may carry out work with these device The user needs to be farmiliar with the risks for measuring voltage and compliance with safety regulations and the proper use of the voltage detector gt Workings may only be performed with appropri ate personal protective equipment Observe the minimum object distance to other plant components that are energized or earthed and use personal protective equipment as speci fied by national accident prevention regulations in Germany BGV A3 or VDE 0105 100 15 gt The function of the voltage tester must be checked briefly before and whenever possible after the use Carry out the function test and check the instrument at a known voltage source AC and DC If the indication of one or several systems fails in the course of checking the instrument must not be used again gt The red LED A LV indication only serves as a indication for hazardous voltage and not as measurement value gt With non pushed buttons this voltage detector may not permit to clearly indicate the absence of operating voltage in case of interference voltage because of its relatively high internal impedance When the ind
11. 2 Mich 4 8 Ennepetal den 11 69 Tietzsch User Instructions Pr fball SPB 500L SPB 1000L Voltage Tester Rudolph Tietzsch GmbH amp Co KG Willringhauser Stra e 18 D 58256 Ennepetal Fon 49 2333 75989 Fax 49 2333 75257 E Mail info tietzsch de www tietzsch de SPB L_BA_09 2013 Test electrodes Bargraph for voltage indication Load indication only SPB 500L LCD indication of voltage resistance polarity and phase sequence Type plate red LED N LV indication for voltages gt 50V AC 120 V DC 7 red LED POL for phase tester 8 Push button for load 9 1 AWUN au Handgear 0 Connecting line Symbols on the instrument A Attention Observe user instructions Ag Mark of approval from VDE test authority Indicates EC conformity TRon On time at highest nominal voltage RToff Recovery time after tests with highest nominal voltage A Device for live working QD Push button This devices may not be disposed with the domestic X waste WEEE 2012 19 EU Please contact service tietzsch de in regard to the return mE ofolddevices 14 1 Application The Pr fball SPB L is a two pole voltage tester with LCD and LED indication in accordance with DIN VDE 0682 part 401 EN IEC 61243 3 You can use the Pr fball SPB L to measure d c and a c voltages in the rated voltage ranges mentioned on the type plate determine polarity phase phase sequence and continuity
12. 6D Tietzsch Bedienungsanleitung User Instructions Prufball SPB 500L SPB 1000L Spannungsprifer Voltage Tester Rudolph Tietzsch GmbH amp Co KG Willringhauser Stra e 18 D 58256 Ennepetal Telefon 49 2333 75989 Telefax 49 2333 75257 E Mail info tietzsch de www tietzsch de SPB L_BA_09 2013 1 Priifelektroden 2 Balkengraph f r Spannung 3 Kontrollzeichen f r zugeschaltete Last nur SPB 500L 4 Display LCD f r Spannung Widerstand Polarit t und Drehfeld Typenschild rote LED A LV Anzeige f r Spannungen gt 50V AC 120 V DC rote LED POL f r Phasenpr fer Taster f r Last nur SPB 500L Handhabe 0 Verbindungsleitung au OON Symbole auf dem Ger t A Achtung Bedienungsanleitung beachten As Zeichengenehmigung durch VDE Pr fstelle EG Konformit tskennzeichnung TRon Einschaltdauer bei h chster Nennspannung RToff Erholzeit nach Pr fung mit h chster Nennspannung A Ger t zum Arbeiten unter Spannung Taster geschaltet werden WEEE 2012 19 EU Bei Fragen zur Altger te R cknahme wenden Sie sich bitte ps Dieses Ger t darf nicht mit dem Hausm ll entsorgt an service tietzsch de N 1 Anwendung Der Pr fball SPB L ist ein zweipoliger Spannungs pr fer mit LCD und LED Anzeige nach DIN VDE 0682 Teil 401 EN IEC 61243 3 Mit dem Pr fball SPB L k nnen Sie innerhalb des auf dem Typenschild angegebenen Nennspannungs bereiches Gleich und Wechselspannungen p
13. PB S ADA SPB srewable adapter with 4mm socket CAT IV 600 V CAT III 1000 V 84311 L SETR Test line 0 8 m with crocodile clip CAT III 1000 V red 81030 SP LED Leather bag 30x 12x6cm 81032 SP KLT Artifical leather bag 30x12x6cm 81035 SP KLT S600 Artifical leather bag for SPB and test probes to 600 mm 65x 17cm 81031 S HUELSE Plastic casing for extension test probes up to 600 mm 81041 SP 200 Test box 50 690 V for voltage tester Tietzsch C EC Declaration of Conformity in accordance with the EEC low voltage directive 2006 95 EG with appendix III B of 12 Dec 2006 Hereby we explain that those corresponds to below designated products in its conception and design as well as in circulation the execution the fundamental safety and health requirements of the Community directive low voltage brought by us In the case of a change of the product not co ordinated with us this explanation loses its validity This statement does not include a warranty of properties Manufactures name Rudolph Tietzsch GmbH amp Co KG Willringhauser Str 18 D 58256 Ennepetal Description of the electrical equipment ype model Pr fball SPB 500 L SPB 1000 L function two pole low voltage detector year of construction from 2013 on The agreement with further valid guidelines regulations following for the product is explained EMC Directive 2004 108 EG of 15 December 2004 ROHS Directive 201 1 65 EU
14. afety precautions for special accessories gt Only qualified personnel with appropriate protective equipment may do these workings Observe the minimum object distance to other plant components that are energized or earthed and use personal protective equipment as speci fied by national accident prevention regulations in Germany BGV A3 or VDE 0105 100 gt Hold the instrument by its handles only to avoid covering the display or touching the extension probes gt Voltage testers and test probes etc must be kept dry and clean gt Voltage testers and test probes etc may not be used when they are damaged Additional safety precautions for insertion prods gt Insertion prods may only be plugged to un covered single conductors otherwise there is risk to short circuit gt Insertion tests damage the cable insulation Tests may only be performed at test points that are sealable afterwards e g at junction sleeves 22 Available accessories Art no Type Description 81019 SPB G Thread on both electrodes 81020 SPB S500 Y Verl ngerungsspitze 500 mm isoliertes Edelstahlrohr Electrode Y 1000 V 81022 SPB S600 Y SPB extension 500 mm isulated stainless steel tube Electrode Y 1000 V 81028 SPB S900 Y SPB extension 900 mm GFK Electrode Y 1000 V 81021 SPB S20 A SPB insertion prod for underground cables 1000 V 81023 SPB S70 SPB pin prod flexible pin 3 x 63 mm CAT IV 600 V CAT III 1000 V 81029 S
15. ed 4 3 7 KQ 1000L 300 350 kQ at 1000 V 1000L au at50V direct lt 3 5 mA switched lt 300 mA 35 mA at 230 V RCD tripping TRon 30 s at 690 V RT of Max 240 s recovery time high impedance direct reading 1 red LED for voltage 1 red LED for phase test 1 LCD backlight low resistive connected additional display symbol for connected load only SPB 1000L Phase Phase sequence Polarity Continuity Power supply Overvoltage category Surge voltage strength Test voltage Operating temperatures Casing Protection category Connecting line Standards EMV requirements Dimensions Weigth 20 capacitive without accessible electrode tests possible with gloves arrows for phase sequence POL for phase unipolar voltage type 0 1000 kQ Voltage tests from the mains integrated Li accu for functions continuity phase phase sequence maintenance free without battery SPB 500L CAT IV 500V SPB 1000L CAT IV 1000 V gt 12 kV 1 2 50 us 6 kV 15 45 solid rubber EPDM unbreakable Display cover made of indestructible polycarbonate P 65 device can be used in moist environments PUR hose cable 1000 V 1m EC 61243 3 2009 EN 61243 3 2010 DIN EN 61243 3 2011 DIN EN 61326 274 x 75 x 47 mm display part 415g 6 Testing and charging the accu In case the battery symbol appears when holding the test electrodes together the accu needs to be recharged There
16. essstellen auf Die Spannung wird auf dem Display angezeigt Bei gef hrlichen Spannungen 2 50V AC 120V DC leuchtet die rote LED A Die zul ssige Einschaltdauer bei Spannungs pr fungen betr gt maximal 30 Sekunden Ausnahme Laden des Akkus an einer 230 V Steckdose siehe 4 1 Hinweis Die LV Anzeige rote LED und das Display bleiben auch bei leerem Akku funktionsbereit Gleich Wechselspannung Polarit t Die Art der Spannung wird durch die Symbole f r AC und f r DC dargestellt Liegt Minus bei Gleichspannungen an der mit gekennzeichneten Pr fspitze mit Anzeigeteil an so erscheint das Vorzeichen Liegt dort Plus an so erscheint kein Vorzeichen vor dem angezeigten Wert 4 3 1 Spannungen 50 500 V AC DC SPB 500L Spannungen 50 1000 V AC DC SPB 1000L Nennspannungsbereich nach IEC 61243 3 Das Ger t zeigt die Spannungsart AC DC und die H he der Spannung digital in Volt auf dem Display an 4 3 2 Spannungen gt 500 V AC DC SPB 500L Spannungen gt 1000 V AC DC SPB 1000L Vor berspannungen warnt die blinkende OL Anzeige In diesem Fall muss die Pr fung sofort abgebrochen werden 4 4 Phase und Drehfeldrichtung pr fen Die Pr fungen k nnen nur mit ungedr ckten Tastern durchgef hrt werden Achtung Diese Pr fungen funktionieren erst ab Spannungen von 165 V 50 Hz gegen Erde Bei diesen Pr fungen muss das Ger t an der Hand habe des Anzeigetei
17. fore plug the test electrodes of the Pr fball SPB L into a 230 V socket so that the display shows 230V Complete recharge of the Pr fball SPB L takes at least 10 hours In this context the on time of about 30 seconds is irrelevant Again perform the function test before putting the instrument into operation see section 3 1 7 Maintenance 7 1 General information The Pr fball SPB L is absolutely maintenance free Nevertheless observe the following information in order to maintain safe operation Always keep the voltage tester dry and clean The housing can be cleaned with a cloth dampened with isopropyl alcohol or soapy water 7 2 Repeated inspection According to EN 61243 3 it is recommended to carry out repeated examinations It should not exceed the time limit of 6 years Depending on operation conditions and frequency a previous inspection may be recommendable The serial number with the date of manufacturing WWYYNN Week Year Number is imprinted on the type plate on the frontside of the device Repeated inspections are offered by the manufacturer and indicated by the inspection plate 8 Repair Repair is only allowed by the manufacturer or expli citly authorized repair shops In case of damages on the device or failure of the function test according to section 3 2 or for detailed inspection calibration please contact service tietzsch de or send the device and a description of failure back to the manufacturer
18. gt Die rote LED A LV Anzeige dient nur als Warnung vor gef hrlichen Spannungen und nicht als Messwert gt Dieser Spannungspr fer kann bei ungedr ckten Tastern durch die relativ hohe Impedanz bei vor handenen St rspannungen die eindeutige Anzeige Betriebsspannung nicht vorhanden nicht erm glichen Wenn die Anzeige Spannung vorhanden bei einem Teil erscheint der als von der Anlage getrennt gilt wird empfohlen die Pr fung beim SPB 500L mit gedr ckten Tastern zugeschal teter Last oder beim SPB 1000L mit anderen Mitteln zu Wiederholen und den Zustand Betriebsspan nung nicht vorhanden nachzuweisen und festzustellen gt Bei Ermittlung von Au enleitern und der Dreh feldrichtung kann die Wahrnehmbarkeit der Anzeige beeintr chtigt sein z B bei ung nstigen Standorten wie Holztrittleitern oder isolierenden Fu bodenbel gen und bei einem nicht betriebs m ig geerdeten Wechselspannungssystem gt Unbefugte d rfen den Spannungspr fer nicht zerlegen gt Vor Verwendung des Pr fers ist das Geh use und die Messleitung auf Besch digungen zu berpr fen Wenn Besch digungen zu erkennen sind darf der Pr fer nicht mehr verwendet werden Bei starker Verschmutzungen ist der Pr fer vor der Verwendung zu s ubern gt Die Lagerung des Spannungspr fers muss in trockener und sauberer Umgebung erfolgen 3 Inbetriebnahme 3 1 Akku Durch das innovative Konzept des Pr fball SPB L sind Spannungspr
19. he Abschnitt 6 Hinweis Sollte bei Durchgangspr fungen nach der Anzeige OFF ein Zahlenwert in der Anzeige erscheinen ist dieser nicht von Bedeutung Dieser entspricht der Software Version des Ger tes 5 Technische Daten Typ Nennspannung Nennfrequenzbereich Messbereich Spannung Eingangswiderstand Strom Scheitelwert Einschaltdauer Anzeige Phase Drehfeld Polaritat Durchgang Stromversorgung Uberspannungskategorie Sto spannungsfestigkeit Pr fspannung Betriebstemperatur Geh use Schutzart Verbindungsleitung Normen EMV Anforderungen Ma e Gewicht SPB 500L 50 500 V AC DC SPB 1000L 50 1000 V AC DC 0 2000 Hz SPB 500L 24 500 V AC DC 42 5 5 D SPB 1000L 24 1000 V AC DC 42 5 5 D direkt 500L 150 190 kQ bei 500 V BOOL sissies bei 50V geschaltet 4 3 7 kQ 1000L 300 350 kO bei 1000 V 1000L i direkt lt 3 5 mA geschaltet lt 300 mA 35 mA bei 230 V RCD Ausl sung TRon 30 s bei 690 V RTor max 240 s Erholzeit hochohmig direkt anzeigend 1 rote LED f r Spannung 1 rote LED f r Phasenpr fer 1 LCD hintergrundbeleuchtet niederohmig geschaltet zus tzliches Anzeigesymbol f r die zugeschaltete Last nur SPB 1000L kapazitiv ohne Ber hrungselektrode Pr fung mit Handschuh m glich Pfeile f r die Drehfeldrichtung POL f r Phase einpolig Spannungsart 0 1000 kQ Spannungspr fung aus dem Netz
20. ication voltage present appears on a part that is expected to be disconnected of the installation it is recommended to repeat the test with pushed buttons with the SPB 500L or by an other means with the SPB 1000L that there is no operating voltage on the part to be tested gt With determination of phase conductors and phase sequence the perceptibility of the display may be impaired e g when using insulating protective gears in unfavourable locations for example on wooden ladders or insulating floor coverings as well as with unfavourable lighting conditions and in an improperly earthed AC voltage system gt The voltage tester may only be dismantled by authorised personnel gt Before using the device check the housing and connecting line for visible damage If damages are visible the voltage tester may not be placed into operation In case of strong dirt contamination the tester must be cleaned before use gt The tester has to be stored in a clean and dry environment 3 Putting into operation 3 1 Accu The innovative concept of the Pr fball SPB L allows voltage testing and indication even with entirely depleted accu For the additional test functions phase phase sequence and continuity energy is supplied by the integrated Li accu which recharges automatically during voltage tests Therefore battery replacement is not neccessary Note Frequent use of the additional test functions may need supplementary ba
21. irect and alternating voltage polarity The type of voltage is indicated by the symbols for AC and for DC When minus is connected to the test electrode with display part designated with then the leading sign appears When plus is connected then no leading sign appears left to the displayed value 4 3 1 Voltages 50 500 V AC DC SPB 500L Voltages 50 1000 V AC DC SPB 1000L Nominal voltage range in accordance with IEC 61243 3 The device indicates the type of voltage AC DC The voltage level is digitally indicated in Volt on the display 4 3 2 Voltages gt 500 V AC DC SPB 500L Voltages gt 1000 V AC DC SPB 1000L OL flashing in the display warns against voltages exceeding the nominal voltage range In this case the test procedure must be stopped immediately nn 4 4 Testing phase and phase sequence These tests can only be performed without push button actuation Attention These tests can be performed at a nominal voltage of at least 165 V 50 Hz against earth When performing these tests the device must be hold closely at the handgear of the display part Note You may wear insulating gloves when performing the tests Tests can be impaired by unfavourable locations for example on wooden ladders or insula ting floor coverings as well as in improperly earthed AC voltage systems 4 4 1 Phase test Determination of the phase conductor occurs by applying the test electr
22. ls fest umfasst werden Hinweis Es k nnen isolierende Handschuhe getragen werden Pr fungen k nnen durch ung nstige Standorte wie Holztrittleitern oder stark isolierende Fu boden bel ge und bei nicht betriebsm ig geerdeten Wechselspannungssystemen beeintr chtigt werden 4 4 1 Phasenpr fung Die Ermittlung des Au enleiters erfolgt durch An legen der mit gekennzeichneten Pr felektrode an den Leiter Wird POL auf dem Display angezeigt oder leuchtet die rote POL LED so ist der Leiter span nungsf hrend 4 4 2 Priifen der Drehfeldrichtung Das Drehfeld zwischen zwei Phasen im geerdeten Drehstromnetz wird durch Anlegen beider Pr fspitzen und Umfassen der Handhabe des Anzeigeteils wie folgt festgestellt Suchen Sie einpolig die Au enleiter siehe Phasenpr fung Legen Sie beide Pr fspitzen an zwei Au enleiter an Anzeige 400V Liegt die Phase L1 an der Pr fspitze mit Anzeige L1 und L2 an der anderen Pr fspitze so erscheint im LC Display der Pfeil I bei Rechtsdrehfeld Erscheint der Pfeil D so liegt ein Linksdrehfeld vor Das Pr fergebnisses ist durch Tauschen der beiden Pr fspitzen zu kontrollieren Hierbei muss die entgegengesetzte Drehrichtung angezeigt werden Falls 230 V statt 400 V angezeigt wird ist m glicher weise der Neutralleiter mit einer der beiden Pr fspit zen kontaktiert 4 5 Zusatzlast und Ausl sung von RCDs nur bei SPB 500L Der Pr fball SPB 500L kann d
23. ode L1 to the conductor The conductor is live when POL appears on the display and the red POL LED lights up 4 4 2 Testing phase sequence To determine the phase sequence between two phases in a earthed three phase current system apply both test electrodes clasp the handgear of the display part and proceed as follows Search for the phase conductors using one pole see phase test Apply both test electrodes to the two phase conductors display 400 V When phase L1 is applied to the test electrode marked L1 and L2 to the other test electrode R appears on the LC display for rotation is clockwise D is indicated direction of rotation is counter clockwise The test result has to be checked by exchanging the two test electrodes The opposite direction of rotation must be displayed If 230 V is displayed instead of 400 V the neutral conductor may have been contacted with one of the test electrodes 4 5 Additional load and RCD tripping only SPB 500L The Pr fball SPB 500L can activate 30 mA RCDs residual current operated protective device at 230V Therefore check the voltage between phase and grounding wire Display indicates 230 V Press both push buttons of the Pr fball SPB 500L RCD is activated and display goes out With the connection of load also inductive and capa citive interference voltages are suppressed Therefore press both push buttons The additional load is indicated by the m sign
24. pannungspr fer und Pr fspitzen etc d rfen nicht verwendet werden wenn Besch digungen zu erkennen sind Erg nzende Sicherheitshinweise f r Kabeleinstechspitzen gt Einstechp fungen d rfen nur an freigelegten Einzeladern von Kabeln durchgef hrt werden andernfalls besteht Kurzschlussgefahr gt Einstechpr fungen an Kabeln besch digen die Kabelisolierung Pr fungen d rfen nur an sp ter zu versiegeln den Stellen wie z B Verbindungsmuffen durch gef hrt werden Erh ltliches Zubeh r Art Nr Typ Beschreibung 81019 SPB G Gewinde an beiden Priifelektroden 81020 SPB S500 Y Verl ngerungsspitze 500 mm isoliertes Edelstahlrohr Elektrode Y 1000 V 81022 SPB S600 Y Verl ngerungsspitze 600 mm isoliertes Edelstahlrohr Elektrode Y 1000 V 81028 SPB S900 Y Verl ngerungsspitze 900 mm GFK Elektrode Y 1000 V 81021 SPB S20 A Einstechspitze f r Erdkabel 1000 V 81023 SPB S70 Stiftspitze flexibler Stift 3 x 63 mm CAT IV 600 V CAT III 1000 V 81029 SPB S ADA Aufschraubadapter mit 4 mm Buchse CAT IV 600 V CAT III 1000 V 84311 L SETR Pr fleitung 0 8 m mit Abgreifklemme CAT III 1000 V rot 81030 SP LED Ledertasche 30x 12 x 6 cm 81032 SP KLT Kunstledertasche 30x12x6cm 81035 SP KLT S600 Kunstledertasche f r SPB und Spitzen bis 600 mm 65x17 cm 81031 S HUELSE Plastikh lse f r Verl ngerungs spitzen bis 600 mm 81041 SP 200 Spannungsgeber 50 690 V Pr fbox f r Spannungspr
25. r fen die Polarit t ermitteln Phase Drehfeldrichtung und Durchgang feststellen Durch das unzerbrechliche Silikongeh use ist die Elektronik gegen harte St e Wasser und Staub gesch tzt Der Pr fball SPB L ist durch seine hohe Schutzart IP 65 auch bei Niederschl gen verwend bar Der Pr fball SPB L arbeitet ohne Batterie der Akku zur Durchgangspr fung wird bei Spannungs pr fungen automatisch wieder aufgeladen 1 1 Bestimmungsgem e Verwendung Das Ger t ist nur f r die in der Bedienungsanleitung beschriebenen Anwendungen bestimmt Hierzu sind besonders die Sicherheitshinweise und die technischen Daten mit den Umgebungsbedin gungen zu beachten Eine andere Verwendung ist unzul ssig und kann zu Unf llen oder Zerst rung des Ger tes f hren Diese Anwendungen f hren zu einem sofortigen Erl schen jeglicher Garantie und Gew hrleistungs anspr che des Bedieners gegen ber dem Hersteller 2 Sicherheitshinweise F r den Pr fball SPB L wurde von der VDE Pr fstelle die Genehmigung zum Benutzen des VDE GS Zeichens erteilt Bei bestimmungsgem er Anwendung gew hr leistet er sowohl die Sicherheit der bedienenden Person als auch die des Ger tes Um den sicherheitstechnisch einwandfreien Zu stand zu erhalten und die gefahrlose Anwendung sicherzustellen ist es unerl sslich dass Sie vor dem Einsatz Ihres Ger tes diese Bedienungsanlei tung vollst ndig lesen und diese in allen Punkten befolgen Bi
26. rwendet werden 4 Pr fen 4 1 Allgemeine Hinweise Der Spannungspr fer schaltet sich beim Anlegen einer Spannung ab 40 V automatisch ein Bei Durch gangspr fungen schaltet das Ger t automatisch auf Spannungspr fen um Um den Akku zu schonen schaltet sich das Ger t etwa 2 s nach der letzten Messung automatisch aus Hinweis zum SPB 500L Der Pr fball SPB 500L ist mit Tastern in beiden Handgriffen ausgestattet Spannung wird sowohl mit gedr ckten und unge dr ckten Tastern ber die LCD und LED Anzeige angezeigt Ohne Taster werden hochohmige und mit Tastern niederohmige Pr fungen durchgef hrt In extremen F llen kann eine Anzeige von induk tiven oder kapazitiven Spannungen erfolgen die bei Bet tigung beider Taster erlischt 4 2 Ger tetypen Nennspannungsbereiche Den Pr fball SPB L gibt es mit zwei Messbereichen SPB500L 50 500V SPB 1000L 50 1000 V Der Ger tetyp und Nennspannungsbereich ist auf dem Typenschild angegeben Nur der SPB 500L ist mit einer Zusatzlast ausgestat tet mit der 30 mA berstromschutzeinrichtungen RCDs ausgel st werden k nnen siehe 4 5 Spannungsart Drehfeldrichtung Balkengraph f r Spannung Spannungs Widerstandswert Typ rote LED POL f r Phasenpr fer Lastanzeige nur bei SPB 500L rote LED V Anzeige f r Spannungen 250VAC 120V DC 5 4 3 Spannung und Polaritat priifen Achtung Setzen Sie die beiden Pr fspitzen mit sicherem Kontakt auf die M
27. tte beachten Sie folgende Sicherheitsvorkehrungen gt Die Spannungsangaben auf dem Pr fball SPB L sind Nennwerte Der Spannungspr fer darf nur in Anlagen mit dem angegebenen Nennspannungsbereich benutzt werden gt Eine einwandfreie Anzeige ist nur im Tempera turbereich von 15 C bis 45 C sichergestellt gt Ger t nur an den Handhaben anfassen um die Anzeige nicht zu verdecken und die Pr felektro den nicht zu ber hren gt Die maximal zul ssige Einschaltdauer des Pr fballs betr gt 30 s gt Nur sachkundige Personen d rfen Arbeiten mit diesem Produkt duchf hren Der Benutzer muss mit den Gefahren der Spannungsmessung und den Einhaltungen der Vorsichtsmassnahmen und dem ordnungsgem en Gebrauch des Span nungspr fers vertraut sein gt Arbeiten d rfen nur mit entsprechender Schutz ausr stung durchgef hrt werden Beachten Sie die Mindestabst nde zu anderen unter Spannung stehenden oder geerdeten Anlagenteilen und verwenden Sie pers nliche Schutzausr stung gem den landesspezifischen Unfallverh tungsvorschriften in Deutschland BGV A3 oder VDE 0105 100 gt Spannungspr fer m ssen kurz vor und nach M glichkeit auch nach dem Einsatz auf Funktion gepr ft werden F hren Sie den Funktionstest durch und ber pr fen Sie das Ger t an einer bekannten Span nungsquelle AC und DC F llt hierbei die Anzeige eines oder mehrerer Systeme aus darf das Ger t nicht mehr verwendet werden
28. ttery charge see section 6 3 2 Testing display and function self test In accordance with DIN VDE 0105 100 voltage testers must be checked if they function correctly briefly before and whenever possible after the use for determining absence of voltage Step 1 Checking the line function Hold the test electrodes together The display shows 000 kQ Separate the test electrodes The display shows OL kQ Through this the overall functions have been tested 16 Note In case the battery symbol appears when holding the test electrodes together the accu needs to be recharged see section 6 Voltage tests can still be performed even when accu is entirely depleted Step 2 Test of the LV indication Check the function of the LV indication red LED at a known voltage source AC and DC At the same time the voltage value is indicated on the display Attention If one of the displays fails during the self test even if only partial failure occurs or if the instrument does not indicate a function standby the voltage tester may not be placed into operation 4 Testing 4 1 General Instructions The voltage tester switches on automatically when a voltage of at least 40 V is applied If the function continuity testing had been activated the device switches automatically over to voltage testing In order to extend battery life the instrument switches off automatically approximately 2 seconds after the last meas
29. urch eine integrierte Zusatzlast 30 mA RCDs Fi Schutzeinrichtungen bei 230V ausl sen Pr fen Sie hierzu die Spannung zwischen Phase und Schutzleiter Erde Die Anzeige zeigt ca 230 V Bet tigen Sie beide Taster des Pr fball SPB L der RCD Fi Schutzeinrichtung l st aus und die Anzeige erlischt Mit der Lastzuschaltung werden auch induk tive und kapazitive St rspannungen unterdr ckt Hierzu sind beide Taster zu dr cken Die zugeschal tete Last wird durch das Symbol mam signalisiert Die Last ist spannungs und zeitabhangig Sie regelt sich aus Sicherheitsgr nden selbstt tig herunter Bei 230 V und 20 C Umgebungstemperatur betr gt die Last etwa 15 s lang 31 mA Danach wird die Zusatzlast hochohmig Nach einer Abk hlphase von 30 s ist die Zusatzlast wieder bereit 4 6 Widerstand und Durchgang pr fen Zum Einschalten des Pr fers f r Durchgangspr fungen m ssen die Pr felektroden im ausgeschal teten Zustand zusammen gehalten werden 000 Q erscheint auf der LCD Setzen Sie die beiden Pr felektroden mit sicherem Kontakt auf die Mess stellen auf Bei Widerstandswerten von 0 1000 KQ wird der Messwert auf dem LCD in 50 kQ Schritten angezeigt Bei Widerstandswerten gt 1000 kQ geht die Anzeige in den Uberlauf und OL und KQ wird angezeigt Hinweis Erscheint w hrend der Durchgangspr fung das Batterie Symbol amp _ ist die interne Energiequelle ersch pft Es sind noch ca 100 Pr fungen m glich sie
30. urement Note for SPB 500L The Pr fball SPB 500L is equipped with push but tons on both handgears Voltage is indicated by LEDs and the LCD either with or without pressing the push buttons Without pressing the push buttons the instrument performs high resistance tests and while pressing them low impedance tests are performed In extreme cases indication of inductive or capa citive voltages may occur which disappears when both push buttons are pressed 4 2 Instrument types Rated voltage ranges The Pr fball SPB L is available in two measuring ranges SPB500L 50 500V SPB 1000L 50 1000 V Type of device and rated voltage range are stated on the type plate Only the SPB 500L is equipped with an additional load with which a 30 mA residual current operated protective device RCD can be activated see 4 5 Polarity Phase sequence Bargraph for voltage indication a Voltage resistance value Type LEDs for 50V AC 120 V DC Load indication 17 4 3 Testing voltage an polarity Securely contact the test electrodes with the test points Voltage is indicated on the display Attention When a hazardous voltage 50 V AC 120 V DC is impressed the red LED A lights up The maximum allowable on time for voltage testing is 30 seconds Exception When charging the accu at a 230 V socket see 4 1 Note The LV indication red LED and the display remain in working order even with empty battery D
Download Pdf Manuals
Related Search
Related Contents
Chief PXRUB flat panel wall mount APC AP8453 power distribution unit PDU Capa_Manual ADIP 257 Bang & Olufsen BEOCENTER 26-Jun User's Manual バッチプラントにおける設備保全(PDF:1MB) 2N ® Helios IP Vario MANUAL MIXER Freeway Digital Signage Operations Manual Flasher ARM User Guide Complete CH-101 EN FR SP 091211_NEW Copyright © All rights reserved.