Bedienungsanleitung - Driescher • Wegberg
Contents
1. VDE 0670 Teil 303 Hochspannungs Lastschalter Sicherungs Kombination VDE 0670 Teil 1000 Gemeinsame Bestimmungen f r Hochspannungs Schalt ger te Normen VDE 0632 Teil 415 Spannungspr fsysteme Entwurf DRIESCHER e WEGBERG General Information Use as Intended The switchgear DRIESCHER LDTMW is a tested medium voltage switchgear for indoor applica tions with general purpose switches The arcing chambers of the switches are working like the principle of hard gas in a closed system The medium voltage switchgear of LDTMW type was exclusively designed for the distribution of electric energy with currents up to 630 A and voltages of up to 12 kV 50 60 Hz Another or an extended use is not considered as a use according to its purpose The producer does not guarantee for damages resulting from it The risk is exclusively in the hands of the user Standards and Specifications Specifications of the German Trade Associa tion BGV A1 VBG1 General specifications BGV A2 VBG4 Electrical systems and equipment Standards DIN VDE 0101 Power installations excee ding AC 1kV EN 50110 1 Operation of electrical in stallations IEC 60129 Alternating current discon nectors and earthing swit ches IEC 60282 1 High voltage fuses IEC 60298 A C metal enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV IEC 60265 1 High voltage switchgear IEC 60420 High voltage alternatin
2. e Kabelende nach Montageanweisung des Kabelgarnituren Herstellers absetzen und Kabelgarnitur montieren Montieren Sie die Phase L1 und verschrauben Sie das Kabelhalteeisen so da das Kabel senkrecht nach unten ragt Montieren Sie dann Phase L2 und zum Schlu Phase L3 DRIESCHER e WEGBERG Connection Cable Connection All the cable connection points were designed as flat connections according to DIN 6206 and the type was type tested in the connection area The most suitable ones are air insulated indoor terminals of different trademarks in connections with flat cable sockets To facilitate cable work the cable box carrier is adjustable Respect the safety regulations of EN 50110 1 and BGV A2 Ground the high tension cable and cause a short circuit on one end On the switchgear that shall be connected e _ switch off the switch disconnector e switch on the earthing switch Insert an insulating protective plate into the opened position of the switch disconnector Sequence of Phases e L1lefthand e L2 center e LS right hand Open the doors of the cubicles For this pur pose turn and open the locking anticlockwise Adjust the cable box carrier according to the cable terminals Prepare the cable ends e Lead the relative cable end from the ca ble canal or the cable mezzanine into the cable connection area Prepare the cable end according to the assembly instructions of the cable pro d
3. 8 O Bei Absicherung von Transformatoren mit einer Bemessungs If transformers are secured with a rated power of Leistung von gt 1000kVA und lt 2000kVA sind andere Siche gt 1000kVA und lt 2000kVA other sizes for the fuses rungs Baugr ssen erforderlich Bitte nehmen Sie R cksprache are necessary Please contact Messrs Driescher mit der Fa DRIESCHER LDTMW 17 DRIESCHER e WEGBERG Abmessungen und Gewichte Dimensions and Weights SE i ge a DI b lt a S o 5 wl L va vo a Rh A 48 500 i 48 _ kel B 596 i Schnitt A A y B 2mm mit Blechtrennw nden l 4mm mit Kunststofftrennw nden B _ 596 E M i tell i N N bo Veg A LA Uri E L N I Hr N D L E HHH 3 4 l TI JI I E Ee C
4. Claims under the warranty must be reported in writing complete with the contract number im mediately after the defect is discovered The warranty is render null and void in the event of improper handling use not as intended impermissible equipment faulty erection incorrect or nonprofessional connection of medium voltage cables or the auxilia ry control lines Driescher HV H R C fuses accessories and re placement parts are specially constructed and te sted in time consuming test series We expressly point out that replacement parts not supplied by the manufacturer and the accessory parts not re commended by the manufacturer are also not approved by the manufacturer Installing and using third party products may negatively affect structurally specified properties of products and may impair the safety of persons switchgear or other material resources The written approval of the manufacturer is required before installing third party products The manufacturer assumes absolutely no liability for damage resulting from the unapproved use of third party products or arbitrary changes or con versions of our products or accessories Duration of Warranty The warranty is valid for 12 months starting with delivery LDIMW l DRIESCHER e WEGBERG Kundendienst F r s mtliche technischen Ausk nfte ber DRIESCHER Produkte und deren systemtechni sche Anwendungen steht Ihnen unser Kunden dienst zur Verf gung Trete
5. If there is a block in the mechanical movement the joints and the supports of the drive mechanics should be treated with a creeping spray oil All the screws of the electric contact connections have to be checked and eventually tightened The maximum admissible tightening torque of the fixa tion screws M12 with pressure discs is 40 Nm Independently from the used switchgear type the user should take care that the station rooms are clean and dry After maintenance there have to be performed some test operations before setting the switchgear to work LDTMW 39 DRIESCHER e WEGBERG Hinweise aus der Praxis Gegen aufsteigende Feuchtigkeit aus dem Erdreich mu der KabelanschluBraum bei of fenem Fundament unterhalb der Schaltanlage aufgef llt und versiegelt werden Eine andere M glichkeit ist eine Abdeckung des Kabelanschlu raumes mit einer ca 30 mm dicken Hartschaumplatte Zus tzliche Ma nahmen bei erschwerten kli matischen Bedingungen z B Schwitzwasser bildung e Einbau einer hygrostatisch gesteuerten Heizung 60 Watt pro Feld im Kabelan schlu raum e Anpassung der L ftungsquerschnitte an die Trafoverlustleistung Das System sollte so bemessen sein da auch bei Schwachlastbetrieb eine ausreichende Klimatisierung erm glicht wird Pr fen der Schaltanlage Pr fen Sie die Schaltanlage auf ordnungsgem en Zustand vor der ersten Inbetriebnahme nach einer nderung oder Instandsetzung der
6. Schaltfeldt r Offnen LDIMW Switch disconnector lever cannot be plugged in Earthing switch lever cannot be plugged in Transformer switch disconnector cannot be switched on No free actuation of the switch disconnector type SEA in case one striker pin blows Door of the cubicle cannot be opened Locking between switch disconnector and earthing switch Earthing switch is activated Locking between switch disconnector and earthing switch Switch discon nector is acti vated Free actuation of the transformer switch disconnector performed by means of HV HRC fuses with striker pin or trip coll HRC fuse is not correctly mounted on the holder HRC fuse actua tion force not corresponding to the medium class according to VDE 0670 Part 4 Locking between earthing switch and door of the cubicle Switch off the earthing switch Then the lever can be plugged in Switch off the switch disconnector Then the lever can be plugged in Turn switch disconnector lever anticlockwise into the final position Then the trans former switch disconnector can be switched on Replace the HV HRC fuses Check if tension is present on the trip coil eventually discover the cause of trouble Insert the HV HRC fuse into the holder so that the striker pin is directed upwards Use HV HRC fuses with at least 50 N of actuation force and 20 mm of minimum st
7. 6 KUNDENDIENS ee 8 CUSTOMER SERVICE u aaa 7 SICHERHEITSVORSCHRIFTEN 2222022222020000200002n00 9 SAFETY REGULATIONS 8 AUEGEMEINES au ie eisernen 9 GENERAL INFORMATION 8 REENEN 10 EN sn ee ae 9 ARBEITEN AN MITTELSPANNUNGS WORKING ON MEDIUM VOLTAGE SWITCHGEAR 10 SCHALTANLAGEN anfassen 11 FIVE SAFETY RULES pupii nei nnd 11 F NF SICHERHEITSREGELN nennen 12 SAFETY INSTRUCTIONS FOR TRANSPORT SICHERHEITSHINWEISE F R TRANSPORT ASSEMBLY OPERATION AND MAINTENANCE 12 MONTAGE BETRIEB UND WARTUNG 19 DESCRIPTION innen 13 BESCHREIBUNG 2 u2u42420 0 40 nnnnan an anna an anne nn ann 14 GENERAL VC RITA STE E REIT ETRE TE 13 ALCOENENE Saas ee 14 ARC LIMITING DEVICE spurl 14 ST RLICHTBOGENBEGRENZER nase 15 OXERAEME aperta 15 BERSICHT Susann ee i 16 TECHNICAL DATA 16 TECHNISCHE DATEN 17 RATED VALUES lia ili 16 BEMESSUNGSGR REN lisa in a 17 AV ARG FUSES artnet 16 HH SICHERUNGSEINSATZE nennen 17 DIMENSIONS AND WEIGHT 17 ABMESSUNGEN UND GEWICHTE EEN TO ASSEMBLY nee 19 MONTAGE E 19 DISCHARGE AND TRANSPORT CARE ER EA ER 19 ABLADEN UND TRANSPORTIEREN 19 INSTALLATION OF THE SWITCHGEAR 20 MONTAGE DER SCHALTANLAGE 20 COUPLING THE TRIP SHAFT OF THE ARC LIMTING KUPPELN DER AUSL SEWELLEN DES DEVICE IN CASE OF SINGLE CUBICLES 24 ST RLICHTBOGENBEGRENZER BEI CONNECTION sens
8. Ausbildung Kenntnisse und Erfahrungen sowie Kenntnisse der einschl gi gen Bestimmungen die ihm bertragenen Arbeiten beurteilen und m gliche Gefahren erkennen kann gt Die Elektrofachkraft mu von dem f r die Sicherheit der Schaltanlage Verantwortli chen berechtigt sein die jeweils erforder lichen Arbeiten und T tigkeiten auszuf hren DRIESCHER e WEGBERG Work on Medium Voltage Switchgear Only qualified electrical technicians as per defi nition in EN 50110 1 are permitted to put into service work on or operate medium voltage switchgear in each case in compliance with the pertinent valid IEC regulations 5 safety rules as per the EN 50110 1 safety regulations accident prevention regulations Operating and accessory parts must always be available for and accessible to the qualified elec trical technician and must be in proper condition They are not to exhibit any damage Replace damaged operating and accessory parts by tested or approved DRIESCHER parts Responsibilities and operating sequences for operation and maintenance must be regulated and must be adhered to Qualified electrical technicians According to EN 50110 1 a qualified electrical technician is a person who can evaluate the work assigned to him or her and can recognize pos sible damages on the basis of his or her techni cal training know how and experience BS The qualified electrical technician must be authorized by the person r
9. B F J e M ll I LL Bild 3 LDIM Anschlu Kabelanschlu S mtliche Kabelanschlu stellen sind als Flachan schlusse nach DIN 6206 ausgebildet und in der Anschlu zone typgepr ft Geeignet sind luftisolierte Innenraum Endverschl sse der verschiedenen Fabrikate in Verbindung mit Flachkabelschuhen Zur Erleichterung der Kabelarbeiten ist das Kabel halteeisen verstellbar Beachten Sie die Sicherheitsvorschriften VDE 0105 und BGV A2 Erden und schlie en Sie das anzuschlie ende Hochspannungskabel einseitig kurz An der anzuschlie enden Schaltanlage e Schalten Sie den Lasttrennschalter aus e Schalten Sie den Erdungsschalter ein Schieben Sie eine isolierende Schutzplatte in die ge ffnete Stellung des Lasttrennschalters ein Phasenfolge e L1links e L2 Mitte e L3 rechts ffnen Sie die Schaltfeldt ren Drehen und ffnen Sie dazu den Verschlu gegen den Uhrzeigersinn Kabelhalteeisen entsprechend des Kabel endverschlusses einstellen Bereiten Sie das Kabelende vor e Entsprechendes Kabelende aus dem Ka belkanal oder Kabelzwischenboden in den Kabelanschlu raum f hren
10. Bedienung und Wartung der Mit telspannungs Schaltanlage beauftragt ist mu die Montage und Betriebsanleitung die Sicherheitsvorschriften und die Sicher heitshinweise der einzelnen Kapitel und Ab schnitte gelesen und verstanden haben Um Bedienungsfehler zu vermeiden und einen st rungsfreien Betrieb der Mittelspannungs Schaltanlage zu gew hrleisten mu die Montage und Betriebsanleitung dem Betreiber Bediener stets zug nglich sein Neben dieser Montage und Betriebsanleitung den Sicherheitsvorschriften und den Texten die durch Sicherheitssymbole gekennzeichnet sind sind folgende allgemeine Vorschriften f r die Handha bung der Mittelspannungs Schaltanlage bindend Anschlu bedingungen der rtlichen Energie versorgungsunternehmen EVU Europ ische Sicherheitsvorschriften EU Norm Sicherheit von Maschinen Ger ten und Anlagen In L ndern au erhalb der EU die entspre chenden Sicherheitsvorschriften Handling These Operation and Assembly Instructions should make it easier for the owner operator to perform the work safely and properly and to carry out the main tenance on the medium voltage switchgear Everyone assigned transport installation commis sioning operation and maintenance duties on the medium voltage switchgear must have read and understood the Operation and Assembly Instructions the safety regulations and the safety notes in the individual chapters and sections To avoid opera
11. Schaltkurbel ist nur bei ausgeschaltetem Lasttrennschalter m glich Erdungsschalter einschalten Drehen Sie die Schaltkurbel im Uhrzeigersinn Schalterstellungsanzeiger senkrecht Erdungsschalter ausschalten Drehen Sie die Schaltkurbel gegen den Uhr zeigersinn Schalterstellungsanzeiger waage recht DRIESCHER e WEGBERG Switching of the earthing switch D Before switching on the earthing switch make sure that the switchgear is not under tension The three pole earthing switch is equipped with a rapid actuation and for this reason it resists against short circuits Actuation Insert the switching crank with side b into the drive bush of the earthing switch BS The plug in of the switching crank is pos sible only with a switched off switch disconnector Switching on the earthing switch Turn the crank clockwise vertical switch position display Switching off the earthing switch Turn the switching crank anticlockwise ho rizontal switch position display JI LDTMW 31 DRIESCHER e WEGBERG Austausch der HH Sicherungseinsatze Verwenden Sie nur HH Sicherungseinsatze nach VDE 0670 Teil 4 mit einem Kappendurchmesser bis 88 mm Der Schlagstift der Sicherung mu der Klasse mittel 50N gt 20mm nach VDE 670 Teil 4 entsprechen Tauschen Sie stets alle Sicherungseins tze aus auch wenn nicht alle geschaltet haben Vorsch digungen der Schmelzleiter m glich Tauschen
12. Sie HH Sicherungseins tze wie folgt aus Lasttrennschalter des Sicherungsfeldes ausschalten und gegen Wiedereinschalten sichern Spannungsfreiheit feststellen Erdungsschalter einschalten Mit der einschenkeligen Bedienungszange 1 Zubeh r geeignet f r Sicherungseins tze mit Kappendurchmesser von 40 bis 88 mm set zen Sie den HH Sicherungseinsatz ein oder nehmen den HH Sicherungseinsatz heraus Sicherungseins tze k nnen hei sein BS Beachten Sie bei Transformator Lasttrennschalter mit Freiausl sung SEA die Lage des Schlagstiftes des HH Sicherungseinsatzes Pfeil zeigt nach oben Verschlie en Sie die T r Schalten Sie den Erdungsschalter aus Schalten Sie den Lasttrennschalter des Siche rungsfeldes ein Replacement of the HV HRC fuses Please use only HV HRC fuses according to VDE 0670 Part 4 with cap diameters up to 88 mm The striker pin of the fuse must be according to the medium class of VDE 0670 Part 4 50 N gt 20 mm minimum stroke Please always replace all fuses even if not all of them have blown The fuse elements could probably be damaged Replace the HV HRC fuses as follows Switch off the switch disconnector of the fuse cubicle and secure it against reactivation Make sure that the switchgear is not under tension Switch on the earthing switch With the single leg operation pincers 1 suit able for fuses with cap diameters from 40 to 88 mm insert or remov
13. all the assembly operations have been correctly performed Check the mechanical functions Switch on off the switch disconnector and the earthing switch Check the switch position display and check the switch position by an immediate visual examination KS The switch disconnector can be switched only with a switched off earthing switch and the earthing switch only with a switched off switch disconnector Check the HV HRC fuses see chapter Replacement of the HV HRC fuses Further Checks Check the additional equipment if present e The connection sockets for capacity tension displays have to be equipped during operation with cover taps or dis play appliances e Resetthe short circuit display e Check the operation of the motor drive in case of a combination of the switch disconnector with the motor drive see Option section LAN Ground the cable or transformer cubicles with free cable connections with the relative earthing switch observe the switch position and eventually secure it with a lockout de vice and a warning plate option LDIMW 27 DRIESCHER e WEGBERG Bedien und Zubeh rteile Schaltkurbel Zubeh r f r Erdungsschalter und Lasttrennschalter mit integriertem Schl s sel f r Schnellverschlu Bedienungsanleitung Spannungsanzeigeger t Option isolierende Schutzplatte Zubeh r m ssen im Schaltanlagenraum oder im Neben raum bersichtlich und griffbereit li
14. and operates the switch und schaltet den Schalter ein bzw aus disconnector ON OFF Der Schaltwinkel f r das EIN AUS Schalten des The switching angle for the switching on and off Lasttrennschalters ist werksseitig eingestellt of the switch disconnector is predetermined in the factory Der Motorantrieb ist f r den Anschlu an Gleich spannung ausgelegt F r den Betrieb mit Wech The motor drive is designed for direct current selspannung wird ein Gleichrichter eingesetzt supply For the operation with alternate current a rectifier has to be used Technische Leistungsdaten Die Motorspannung ist auf dem Leistungsschild der Anlage angege Technical data The motor voltage is indicated on ben the label of the switchgear Netzspannung V l i Laufzeit system voltage max input cycle time Stromauf Leistungs EIN AUS V current ON OFF nahme aufnahme ca S Approx ef Ba Z30 AG 230AC_ 0 ode 0 36 42 1210 4 1178 47 oe 41 1108 A 60 DC 48 DC 0 69 24 DC Notentriegelung 11 8 48DC 069 34 13 10 13 10 24 DC 1 41 13 10 13 10 Emergency Unlocking In case of a fault on the motor drive the switch can Bei einer St rung an dem Motorantrieb kann der be manually actuated with the crank Schalter mit der Schaltkurbel von Hand bet tigt For this purpose the gear of the motor drive first werden has to be unlocked You unlock the gear by ex Dazu mu das Getriebe des Motorantriebes zuvo
15. bus bar section an insulating barrier according to IEC 60298 can be mounted The insulating barrier has to be inserted with an open switch disconnector and closed cubicle door For this scope the insulating barrier is completely introduced from above in an angle into the slot between the upper blend and the door observe the marking LDTMW 33 DRIESCHER e WEGBERG Kapazitive Schnittstelle Option Spannungsfreiheit feststellen ber die kapaziti ve Schnittstelle nach VDE 0682 Teil 415 Die Pr fung auf Spannungsfreiheit nach HR System 70 90 V am Me punkt bei 2 5 uA erfolgt mit kapazitiven Spannungsanzeigeger ten an den Me buchsen L1 L2 L3 BS Benutzen Sie nur Pr fger te nach VDE 0682 Teil 415 Entwurf f r HR Systeme Beachten Sie die Montage und Betriebs anleitung der Pr fger tehersteller und VDE 0682 Teil 415 Entwurf Pr fen Sie die Pr fger te vor Gebrauch auf Funktion Schutzst psel entfernen Spannungsanzeigeger t nach Montage und Betriebsanleitung des Herstellers mit Me buchsen verbinden und auf Spannungsfreiheit pr fen Nach der Pr fung Spannungsanzeigeger t von den Me buchsen trennen Schutzst psel auf Me buchsen stecken um das Verschmutzen der Me buchsen zu ver hindern 4 Keine Kurzschlu stecker verwenden Die Schutzfunktion der spannungsbegrenzen den Sollbruchstelle wird bei Verwendung von Kurzschlu steckern unwirksam Funktionspr fung siehe Skizze auf nachfolgen
16. der Auslosewellen des Stor lichtbogenbegrenzer bei Einzelfeldliefe rung LDTM Schaltfelder mit St rlichtbogenbegrenzer sind untereinander mit je einer Kupplung versehen Bild 3 Ke Bei im Werk komplettierten Anlagen ist die Welle bereits gekuppelt Vor Inbetriebnahme der Schaltanlage ist daher darauf zu achten da die Kupplung der Ausl se wellen zweier benachbarter Schaltfelder funkti onst chtig ist Achten Sie darauf da die Ausl sewellen aller Schaltfelder vor Inbetriebnahme ge kuppelt sein m ssen um die Funktion des St rlichtbogenbegrenzers zu sichern F r Sch den und Betriebsst rungen die sich aus dem Nichtkuppeln der Ausl sewellen ergeben bernehmen wir keine Haftung Nach Montage der Schaltanlage Zylinderschraube des Kuppelteils I sen und Kuppelteil nach links in das benachbarte Schaltfeld schieben Bild 1 Kuppelteil ber die Ausl sewelle bis vor sp rbaren Anschlag schieben auf Leichtg ngigkeit achten Zylinderschraube vor der Ausl sewelle in Kuppel teil fest andrehen Bild 2 Ausl sewelle auf Leichtg ngigkeit pr fen Die Ausl semechanik des St rlichtbogen begrenzers wurde im Werk optimal eingestellt Nehmen Sie daher keine Ver n derungen an der Aul semechanik vor da es ansonsten zu Fehlverhalten oder Nichtan sprechen f hren kann Zylinderkopfschraube DIN 912 M5x20 Sockethead_cap_screw Coupling of the Drive Shafts of the Arc limiting device fo
17. on the switch disconnector Turn the switching crank clockwise Vertical position of the switch display Switching off the switch disconnector Turn the switching crank anticlockwise Horizontal position of the switch display EIN ON Sichern gegen Wiedereinschalten Bringen Sie Antriebsabdeckung Option an Machen Sie nach einer Freiausl sung des Trans formator Lasttrennschalters Typ SEA den Schalter wie folgt einschaltbereit Stecken Sie die Schaltkurbel in die Antriebs buchse des Lasttrennschalters Drehen Sie die Schaltkurbel gegen den Uhr zeigersinn bis zum h rbaren Einrasten in die Endstellung Der Schalter ist einschaltbereit 30 Safeguarding against Reclosing Cover the drive opening optional After a free actuation of the transformer switch disconnector type SEA prepare the switch for a new ON operation as follows Plug in the crank into the drive bush of the switch disconnector Turn the crank anticlockwise until it audibly clicks into its end position The switch is ready for operation LDTM Schalten des Erdungsschalters D Stellen Sie vor dem Einschalten des Er dungsschalters die Spannungsfreiheit fest Der dreipolige Erdungsschalter ist mit einer Schnelleinschaltung ausger stet und damit kurz schlu einschaltfest Bet tigung Stecken Sie die Schaltkurbel mit der Einsteckseite b in die Antriebsbuchse des Erdungsschalters BS Das Aufstecken der
18. operation and mainte nance of the medium voltage switchgear con tained in these Operation and Assembly In structions are current as of the day of printing and are stated to the best of our knowledge on the basis of our experience and know how We accept liability for any errors or omissions to the exclusion of further claims within the scope of the agreed warranty Claims for com pensation for damage are excluded regardless of the legal basis for those claims unless they are the result of intent or gross negligence Translations are made to the best of knowled ge Liability of any kind shall therefore not be accepted for faults made in the translation even if the operating instructions are translated by us or by a third party Solely the Germany text which can be made available on request shall prevail at ambient temperatures gt 40 C take care of the reduction factors 6 LDIM Gewahrleistung Diese Montage und Betriebsanleitung enthalt alle erforderlichen Hinweise und ist vor Inbetriebnahme der Schaltanlage sorgfaltig durchzulesen F r Sch den und Betriebsst rungen die sich aus der Nichtbeachtung der Montage und Betriebs anleitung ergeben bernehmen wir keine Haftung Gew hrleistungsanspr che sind sofort nach der Feststellung des Mangels unter Angabe der Auf tragsnummer schriftlich anzumelden Die Gew hrleistung erlischt bei unsachgem er Behandlung nicht bestimmungsgem er Verwendung unz
19. 1 PR FEN DER SCHALTANLAGE s s sssenneeenneesenerernreesenne 40 ANNEX A en lalla 42 FEHLERBEHEBUNG u a a 41 LDTM SWITCHGEAR WITHOUT ARC LIMTING DEVE eek 42 4 LDIM Allgemeines Bestimmungsgem e Verwendung Die DRIESCHER LDTMW Schaltanlage ist eine typgepr fte Mittelspannungs Schaltanlage f r In nenraumanwendung mit Mehrzwecklasttrenn schaltern Die L schkammern des Schaltger tes arbeiten als geschlossenes System nach dem Hartgas Prinzip Die Mittelspannungs Schaltanlage vom Typ LDTMW ist ausschlie lich zum Schalten und Ver teilen elektrischer Energie mit Str men bis 630 A bei Spannungen bis 12 kV 50 60 Hz bestimmt Eine andere oder dar ber hinausgehende Ver wendung gilt als nicht bestimmungsgem F r hieraus resultierende Sch den haftet der Hersteller nicht Das Risiko tr gt allein der Betreiber Benutzer Normen und Vorschriften Vorschrift der Berufsgenossenschaft BGV A1 VBG1 BGV A2 VBG4 Allgemeine Vorschriften Elektrische Anlagen und Be triebsmittel DIN VDE Bestimmungen DIN VDE 0101 Errichten von Starkstro manlagen mit Nennspan nungen ber 1 kV DIN VDE 0105 Betrieb von elektrischen Anla gen VDE 0670 Teil 2 Wechselstromtrennschalter Erdungsschalter VDE 0670 Teil 4 Hochspannungssicherungen VDE 0670 Teil 6 Metallgekapselte Wechsel strom Schaltanlagen f r Be messungsspannungen ber 1kV bis einschlie lich 52 kV VDE 0670 Teil 301 Hochspannungs Lastschalter
20. Die isolierende Schutzplatte ist bei ge ffnetem Lasttrennschalter und geschlossener Zellent r einzuschieben Dazu die isolierende Schutzplatte von oben ange winkelt in den Schlitz zwischen Oberblende und T re einf hren und ganz einschieben Markierung beachten DRIESCHER e WEGBERG Measures after an Activation by means of the Sensor of the arc limting device If the pressure sensor positioned on the roof of the switchgear is activated once after the assembly work in occasion of a functional check the pre tensioned energy storing device activates the rapid earthing switches in the supply fields Important For a reset the following measures have to be taken in the single cable cubicles Put off all the switch disconnectors Put on all the drive shaft of the earthing switches by means of the lever Put the drive shaft of the earthing switches into the OFF position by means of the lever The earthing switches are in OFF position now and the pre tensioned energy storing device thus ready for use Note The manual switching from ON to OFF can be performed as usual despite of the preset drive Insulating barrier Accessories To safeguard the cable connection area against the
21. Einsteckseite a f r Schnellverschlu Einsteckseite b f r Erdungsschalter Einsteckseite c f r Lasttrennschalter Schalterstellungsanzeiger Die Schalterstellungsanzeiger geben in Verbin dung mit dem Blindschaltbild den Schaltzustand von Lasttrennschalter und Erdungsschalter an IN Vergewissern Sie sich ber die tats chli che Schalterstellung durch einen Blick durch die Sichtscheibe Schalten des Lasttrennschalters Kabelfeld Typ F Das Ein und Ausschalten des Lasttrennschalters erfolgt ber eine Schaltkurbel Die eingebaute Federsprung Schaltvorrichtung sorgt f r sicheres Ein und Ausschalten unabh ngig von der Bedie nungsgeschwindigkeit Transformatorfeld Typ SEA Der Lasttrennschalter mit Freiausl sung Typ SEA verf gt ber einen Federkraftspeicher der mit dem Einschalten gespannt wird Die Freiausl sung erfolgt Uber HH Sicherungen mit Schlagstift der Klas se mittel entsprechend VDE 0670 Teil 4 ber Ausl semagnet DRIESCHER e WEGBERG Switching Operations The operations are performed with a switching crank Accessories and an integrated key for rapid locking Switching lever for earthing switch and switch disconnector with integrated key for the rapid lok king 1 plug in side a for rapid locking plug in side b for earthing switch plug in side c for switch disconnector Switch position indicator The switch position indicators together with the mimic diagr
22. H N 584 H he H Transport Height H Transport gewicht gewicht Ringschaltfelder 1435mm 132kg Cable Cubicle 1435mm 132kg Trafoschaltfelder 1535mm 136kg Transformer 1535mm 136kg Cubicle 18 LDTM Montage Be Erdungsschalter m ssen aus Sicher heitsgr nden w hrend des Transports und w hrend der Montage in EIN Stellung blei ben Bringen Sie vor der Inbetriebnahme alle Erdungsschalter mit der Schaltkurbel in AUS Stellung Abladen und Transportieren Beachten Sie die Sicherheitshinweise und Unfall verh tungsvorschriften BS Beachten Sie da die Schaltanlage nicht liegend auf der R ckwand transportiert werden darf BS Verwenden sie zum He ben und Trans portieren der Schaltanlage Hebe zeug Lastaufnahme mittel und Anschlagmit tel mit ausreichender Kraft Befestigen Sie An schlagmittel nur an den vorgesehenen Kra nungsvorrichtungen Abladen und Transportieren der Schaltanlage mit Kran oder Hubstapler Anschlagen der Anschlagmittel mit Sicher heitshaken nur an den kopfseitig angebrachten Kranungsvorrichtungen Benutzen Sie Anschlagmittel mit gleicher L n ge Der Winkel darf einen Wert von 90 nicht berschreiten Achten Sie auf gleichm ige Gewichtsvertei lung Nach dem Abladen die Schaltanlage auf Besch digungen pr fen das Zubeh r laut Lieferschein auf Vollst ndig keit kontrollieren Dokumentieren und melden Sie Transportsch den sofort dem Spediteu
23. Montage und Betriebsanleitung Operation and Assembly Instructions Mittelspannungs Medium Voltage Switchgear Lastschaltanlage Type LDTMW Typ LDTMW Air insulated Luftisoliert Rated voltage up to 12 kV Bemessungsspannung bis 12 kV Rated current 630 A Bemessungsstrom 630 A 05 2002 DRIESCHER e WEGBERG 2 LDTM F r diese Druckschrift behalten wir uns alle Rechte vor Mi br uchliche Verwendung wie insbesondere Vervielf ltigung und Weitergabe an Dritte ist auch auszugsweise nicht ge stattet Angaben und Abbildungen unverbindlich nderungen vorbehalten DRIESCHER e WEGBERG 2002 DRIESCHER e WEGBERG We reserve all rights for this publication Misuse especially dupli cation and transfer to third parties is prohibited even in case of excepts Text and illustrations are not binding We reserve the right to make revisions DRIESCHER e WEGBERG 2002 LDIMW 3 DRIESCHER e WEGBERG INHALT CONTENS INHALT ala 4 GONTENS una la 3 ALLGEMEINES ege a 5 GENERAL INFORMATION 11 4 BESTIMMUNGSGEM RE VERWENDUNG 5 USE AS INTENDED spilli 4 NORMEN UND VORSCHRIETEN 5 STANDARDS AND SPECIFICATIONS 4 BETRIEBSBEDINGUNGEN _ iii 6 SERVICE CONDITIONS reina 5 HAFTUNGSBESCHRANKUNGEN c 6 RESTRICTIONS ON RELIABILITY 0 5 GEW HRLEISTUNG nenne 7 WARRANT Y inietta
24. Schaltanlage mindestens alle 4 Jahre BGV A2 Best tigen Sie den ordnungsgem en Zustand der Schaltanlage schriftlich in einem Pr fbuch Bedienteile bzw Zubeh rteile wie Schaltkurbel Schaltsperre Option Spannungsanzeigeger t isolierende Schutzplatte m ssen bersichtlich und griffbereit im Schaltanlagen oder Nebenraum vor handen sein Besch digte Bedienteile ggf durch gepr fte oder zugelassene DRIESCHER Bedienteile austau schen Pr fen Sie die Spannungsanzeigeger te f r Be messungsspannungen ber 1 kV mindestens alle 6 Jahre auf Einhaltung der in den elektrotechni schen Regeln vorgegebenen Grenzwerte Beachten Sie die Herstellerbedingungen f r Span nungsanzeigegerate Practical Hints Against humidity rising from the soil the cable connection area with an open base under the switchgear has to be filled and sealed Another possibility is a cover of the cable connection area with a 30 cm thick plate of hard foam Additional measures for extreme climatic conditions i e formation of condensate e Installation of a hygrostatically driven heating 60 Watts per cubicle in the cable connection area e Adaptation of the ventilation cross sections to the loss capacitive of the transformer The system should be designed in the way that also with a low load duty a sufficient conditioning is possible Testing the Switchgear Check the proper state of the switchgear before the first
25. Sicherheitsvorschriften und vorschriften beachten Unfallverh tungs Montagearbeiten pr fen Kontrollieren Sie ob alle Montagearbeiten ord nungsgem durchgef hrt wurden Mechanische Funktionen pr fen Schalten Sie den Lasttrennschalter und Er dungsschalter ein aus Kontrollieren Sie die Schalterstellungsanzeiger und beobachten Sie die Schalterstellung durch unmittelbare Sichtkontrollle Be Der Lasttrennschalter l t sich nur bei ausgeschaltetem Erdungsschalter schalten bzw der Erdungsschalter nur bei ausge schaltetem Lasttrennschalter Kontrollieren Sie die HH Sicherungseins tze siehe Kapitel Austausch der HH Sicherungs eins tze Sonstige Kontrollen Pr fen Sie die Zusatzeinrichtungen falls vor handen e Anschlu buchsen f r kapazitive Span nungsanzeigeger te m ssen w hrend des Betriebes mit Abdeckstopfen oder Anzei geger ten ausger stet sein e Kurzschlu anzeiger zur ckstellen e Funktion des Motorantriebes bei Last trennschalter Kombination mit Motoran trieb pr fen siehe Kapitel Option LAN Erden Sie die Kabelfelder oder Siche rungsfelder deren Kabelanschl sse frei bleiben mit zugeh rigem Erdungsschalter Schalterstellung beachten und ggf durch Schaltsperre mit Warnschild Option si chern DRIESCHER e WEGBERG Operation Setting to Work Observe the safety regulations and the anti accident rules Check the assembly operations Please check if
26. am show the switch condition of switch disconnector and earthing switch IN To make sure of the real switch position take a look trough the window Switching of the Switch disconnector Cable cubicle Type F The switching on and off of the switch disconnector is performed by means of a switching crank The integrated spring assisted mechanism provides for safe switching on and off independently from the operational speed Transformer cubicle Type SEA The switch disconnector with free activation type SEA includes an energy storing device with resort that is under tension during activation The free activation is performed by means of HV HRC fuses with striker pin of the medium class according to IEC 60282 1 by means of an trip coil LDTMW 29 DRIESCHER e WEGBERG Betatigung Stecken Sie die Schaltkhebel mit der Einsteck seite c in die Antriebsbuchse des Lasttrenn schalters er Das Aufstecken der Schaltkurbel ist nur bei ausgeschaltetem Erdungsschalter m glich Lasttrennschalter einschalten Drehen Sie die Schaltkurbel im Uhrzeigersinn Schalterstellungsanzeige senkrecht Lasttrennschalter ausschalten Drehen Sie die Schaltkurbel gegen den Uhr zeigersinn Schalterstellungsanzeige waagerecht Actuation Plug in the switch crank with the plug in side c into the drive bush of the switch disconnector BS The plug in of the crank is possible only with a switched off earthing switch Switching
27. ausl sung des Last trennschalters Typ SEA beim Ansprechen des HH Sicherungs einsatzes Schaltfeldt r l t sich nicht ffnen Verriegelung zwischen Last trennschalter und Erdungsschalter Erdungsschalter ist eingeschaltet Verriegelung zwischen Last trennschalter und Erdungsschalter Lasttrennschalter ist eingeschaltet Freiausl sung des Transforma tor Lasttrenn schalters erfolgte durch HH Siche rungseins tze mit Schlagstift oder durch Magnet ausl ser HH Sicherungs einsatz ist falsch in die Halterung eingesetzt HH Sicherungs ausl sekraft entspricht nicht der Klasse mit tel nach VDE 0670 Teil 4 Verriegelung zwischen Er dungsschalter und Schaltfeldt r Erdungsschalter ausschalten Anschlie end ist der Schaltkurbel aufsteckbar Lasttrennschalter ausschalten Anschlie end ist der Schaltkurbel aufsteckbar Lasttrennschal ter Schaltkurbel gegen den Uhr zeigersinn in die Endstellung drehen An schlieBend ist der Transformator Lasttrennschalter einschaltbereit HH Sicherungsein s tze tauschen Pr fen ob Spannung am Magnetausl ser ansteht ggf Ursache ermit teln HH Sicherungs einsatz so in die Halterung einset zen da der Schlagstift nach oben zeigt HH Sicherungs eins tze mit mindestens 50 N Ausl sekraft und 20 mm Mindest hub des Schlag stiftes einsetzen Erdungsschalter einschalten Anschlie end l t sich die
28. der Seite Bei bekannter Betriebsspannung U Wiederholungspr fung In festen Zeitabst nden durch o g Funktionspr fung bei bekannter Be triebsspannung Letzte Wiederholungs Funkti onspr fung siehe Aufdruck am Koppelteil Capacitive Interface option With the capacitive interface check if the switch gear is not under tension see IEC 61243 5 The check if the switchgear is not under voltage 70 90 V at the measuring point with 2 5 uA is performed with capacitive voltage display devices on the measuring bushes L1 L2 L3 Be Please only use test appliances corre sponding to IEC 61243 5 for HR Systems Observe the operating manual of the pro ducer of the test appliances and IEC 61243 5 Check the test appliances for proper operation before usage Remove the protective taps Connect the tension display device according to the operating manual of the producer with the measuring bushes and check if the switchgear is not under tension After the check separate the tension display device from the measuring bush Plug the protective taps into the measuring bushes to avoid the formation of dirt D Do not use any short circuit plugs The protective function of the declared breaking point that limits voltage becomes invalid with the use of short circuit plugs Functional Check see sketch on following page With a predetermined operating voltage U Repeated Check in fixed intervals with the above mentioned fu
29. e 25 EINZELFELDLIEFERUNG anne 24 OPERATION esseesseeseeeoeneoeneornrerreerreorrrerrrerrrerrrne 27 ANSCHLU ich 25 SETTING TO WORK N 27 BETRIEB EEN 27 SWITCHING OPERATIONS nn 29 INBETRIEBNAHME nenne 27 SWITCHING OF THE SWITCH DISCONNECTOR 29 SCHALTVORG NGE u ana 29 SWITCHING OF THE EARTHING SWITCH 31 SCHALTEN DES LASTTRENNSCHALTERS 29 REPLACEMENT OF THE HV HRC FUSES 32 SCHALTEN DES ERDUNGSSCHALTERS 31 MEASURES AFTER AN ACTIVATION BY MEANS OF AUSTAUSCH DER HH SICHERUNGSEINSATZE 32 THESENSOR u a aa 33 MARNAHMEN NACH AUSLOSUNGEN DURCH DEN INSULATING BARRIER ACCESSORY 33 ST RLICHTBOGENSENSOR 33 CAPACITY INTERFACE OPTION 34 ISOLIERENDE SCHUTZPLATTE ZUBEH R 33 MOTOR DRIVE OPTION 36 KAPAZITIVE SCHNITTSTELLE OPTION 34 TRIP COIL OPTION assai 38 MOTORANTRIEB OPTION nennen 36 SHORT CIRCUIT DISPLAY OPTION 38 MAGNETAUSL SER OPTION 38 MAINTENANCE ii 39 KURZSCHLURANZEIGER OPTION nennen 38 SERVICING Ria 39 INSTANDHAL TUNG seen KN ENKEN KN ENNEN EN ENKEN Kn A0 PRACTICAL HINTS iaia 40 WARIUNG li 39 TESTING OF THE SWITCHGEAR 40 HINWEISE AUS DER PRAXIS 40 RESOLVING PROBLEMS aan 4
30. e of switch job number serial number model year rated voltage and rated current value Specifying these items ensures that you will recei ve the correct information or required replacement parts Fritz Driescher KG Spezialfabrik f r Elektrizit tswerksbedarf GmbH amp Co Postfach 1193 41837 Wegberg Germany Industriestrasse 2 41844 Wegberg Germany Tel 49 2434 811 Fax 49 2434 81 446 www driescher wegberg de e mail info driescher wegberg de We reserve the right to make technical changes during the further development of the switchgear discussed in these In structions for Operation Consequently no claims can be based on the data illustrations and descriptions in these Instructions for Operation 8 LDTM Sicherheitsvorschriften Allgemeines Die in der Montage und Betriebsanleitung enthal tenen Hinweise zu Transport Montage Inbetriebnahme Bedienung Wartung der Mittelspannungs Schaltanlage m ssen unbe dingt beachtet werden Wichtige sicherheitstechnische Hinweise sind durch folgende Symbole gekennzeichnet LA Warnung vor einer Gefahrenstelle D Warnung vor elektrischer Spannung BS Weist auf Richtlinien und Vorschriften hin Diese Symbole finden Sie bei allen Hinweisen in dieser Montage und Betriebsanleitung bei denen Gefahr f r Leib und Leben besteht Befolgen Sie diese Hinweise um Unf lle und Be sch digungen der Mittelspannungs Schaltanlage zu vermeiden N
31. e the HV HRC fuse The fuses may be hot BS With the transformer switch disconnector with free trip mechanism type SEA please observe the position of the striker pin of the HV HRC fuse arrow must point upwards Lock the door Switch off the earthing switch The switch disconnector is ready for operation 32 LDTM Ma nahmen nach Ausl sungen durch den Storlichtbogensensor Wird der im Anlagendach befindliche Drucksensor nach abgeschlossener Montagearbeit zur einmali gen Funktionskontrolle betatigt so losen die vor gespannten Kraftspeicher die Schnellerder in den Einspeisefeldern aus Zur Wiederherstellung der Ausl sebereitschaft sind in den einzelnen Kabelfeldern folgende Ma nah men unbedingt notwendig Alle Lasttrennschalter ausschalten Die Antriebswelle aller Erdungsschalters mit tels Schaltkurbel in EIN Schaltstellung brin gen Antriebswelle der Erdungsschalters mittels Schaltkurbel in AUS Stellung bringen Die Erder sind ausgeschaltet und die Kraftspeicher vorgespannt und somit wieder ausl sebereit Hinweis Die manuelle EIN und AUS Schaltung kann trotz des vorgespannten Antriebes wie blich vorge nommen werden Isolierende Schutzplatte Zubeh r Zur Sicherung des Kabelanschlu raumes gegen den Sammelschienenraum l t sich eine isolieren de Schutzplatte nach VDE 0670 Teil 6 einbringen
32. ear The reactive pressure of the pressure sensor is in a safe distance below the burst pressure of the enclosure LDTMW 15 DRIESCHER e WEGBERG Overall View Ubersicht CO 5 Se d 3 D i i 13 1 Typenschild 1 2 Sichtscheibe 2 3 Blindschaltbild mit Schaltstellungsanzeigen 3 4 Schaltstellungsanzeige f r Lasttrennschalter 4 5 Antriebsbuchse f r Lasttrennschalter 5 6 Schaltstellungsanzeige f r Erdungsschalter 6 7 Antriebsbuchse f r Erdungsschalter T 8 Kabelschaltfeld 8 9 Transformatorschaltfeld 9 10 Einschubf hrung f r isolierende Schutzplatte 10 11 Beschriftungsschild 11 12 Anzeiger fur St rlichtbogenbegrenzer Option 12 13 Me buchsen mit Schutzst psel f r kapazitive 13 Spannungsanzeige bzw Phasenvergleich Option oder Mef buchsen f r Summen stromwandler Option 16 LDTM SZ d 4 G ra O Fr A A O O Pi T Su GB e 6 _ es e o Ra o je x N7 o type label window blind diagram with switch position display position display of switch disconnector drive socket for switch disconnector position display of earthing switch drive socket for earthing switch Cable cubicle transformer cubicle Insert guide for insulating plate label Display for arc lim
33. eben diesen Hinweisen sind Sicherheitsvorschriften Unfallverh tungsvorschriften Richtlinien und anerkannte Regeln der Technik sowie s mtliche Instruktionen dieser Montage und Betriebsanleitung zu beachten DRIESCHER e WEGBERG Safety Regulations General Information It is imperative that the notes in these Operating Instructions regarding transport assembly putting into service operation maintenance jobs of the medium voltage switchgear be adhered to Important instructions such as safety notes are identified by means of the following symbols Warning of a danger area D Warning of electrical voltage BS Refers to guidelines and specifications You will find these symbols with all notes in these Operating and Assembly Instructions which prevent damage to the switchgear or endangerment of per SONS Follow these notes to avoid accidents and damage involving the medium voltage switchgear Aside from these notes comply with safety specifications accident prevention regulations guidelines and recognized rules of technology as well as all instructions and notes in these Opera tion and Assembly Instructions LDIMW 9 DRIESCHER e WEGBERG Handhabung Diese Montage und Betriebsanleitung soll dem Betreiber Bediener das sichere und sachgerechte Arbeiten sowie die Wartung der Mittelspannungs Schaltanlage erleichtern Jede Person die mit Transport Installation Inbe triebnanme
34. egen e Hilfs und Steuerspannung zuschalten e Alle getroffenen Schutzma nahmen wie Kurz schlu und Erdungsverbindungen so aufhe ben da keine Gef hrdung f r Personen und Sachen auftritt Bedienpersonal unterrichten H ndigen Sie dem Bedienpersonal Elektrofach kraft vor Inbetriebnahme der Schaltanlage die Montage und Betriebsanleitung aus Das Bedien personal mu bei bernahme der Schaltanlage mit allen Einzelheiten der Bedienung vertraut sein Operative Parts and Accessories manual crank Accessories for earthing switch and switch disconnector with integrated key for rapid lock manual of usage voltage display option insulating plate Accessories must be present in the room of the switchgear or a nearby room ready for use Apply the drive tension All the taken protective measures as short circuit and earthing connections have to be suspended in a way that there is no danger for persons or objects Information of the Operators Before the start of the switchgear hand over the manual of usage to the operators electric experts At the delivery of the switchgear the operators must get familiar with all the details of operation 28 LDTM Schaltvorgange Die Betatigung erfolgt mittels eines Schaltkurbels Zubeh r mit integriertem Schl ssel f r Schnell verschlu Schaltkurbel f r Erdungsschalter und Lasttrenn schalter mit integriertem Schl ssel f r Schnellver schlu 1
35. entfernen lagen sowie Erweiterungsrahmen f r 1 2 und 3 Felder lieferbar Es sind Grundrahmen f r 2 und 3 feldige Anlagen sowie Erweiterungsrahmen f r 1 2 und 3 Felder lieferbar gt 140 B o NI i oO B 1 d ES hii Bild 21 1 Grundrahmen einer dreifeldigen Anlage g dA 77 KERLE d 2 d d FA Es 4 J fe 2 Deg EE gt A Es gelten folgende Ma e und Gewichte Es gelten folgende Ma e und Gewichte Anbauwandrahmen AWR Ip mm pg 500 16 A WR f r 1 Feld A WR ta Feld A WR f r 2 Felder 1165 A WR f r 2 Felder 1165 A Wr f r 3 Felder A Wr f r 3 Felder LDTMW 21 DRIESCHER e WEGBERG Aufhangen der Schaltfelder H ngen Sie die Schaltfelder bzw die Schalt anlage mit einem Hebeger t auf den vorbe reiteten Grundrahmen A H ngen Sie die Schaltanlage nur an ebene und lotrechte Grundrahmen auf um ein Ver spannen der Schaltfelder zu vermeiden Un ebenheiten der Wand mussen ausgeglichen werden Ke Beachten Sie die Sicherheitshinweise Abladen und Transportieren Halten Sie die Mindestma e ein BS Bei Schaltanlagen die als Einzelfelder geliefert werden m ssen die Einzelfelder am Aufstellungsort am vorderen und hinteren L ngsholm verschraubt werden jeweils 4 Schrauben M8 Bei Transport und Aufh ngen der Anlage da rauf achten da der im Anlagendach befindli che Sensor nicht durch u ere Einwirk
36. esponsible for the safety of the switchgear to perform the work LDTMW 11 DRIESCHER e WEGBERG Funf Sicherheitsregeln 1 Freischalten Kabelfelder und Sicherungsfelder der Schalt anlage an denen gearbeitet wird mit zugeh rigen Schaltern beidseitig freischalten Gegen Wiedereinschalten sichern Abgrenzen des Arbeitsbereichs z B durch Flaggen und Absperrseile mit Warnschildern um Verwechslungen mit unter Spannung ste henden Schaltfeldern auszuschlie en Hinweisschilder an den freigeschalteten Fel dern anbringen Was wurde freigeschaltet Grund der Freischaltung Wer hat freigeschaltet Durch geeignete Verriegelung z B Vorh nge schlo das Wiedereinschalten verhindern Spannungsfreiheit pr fen Spannungspr fer auf einwandfreie Funktion pr fen und die Spannungsfreiheit feststellen Erden und Kurzschlie en Mit Hilfe des Erdungsschalters bzw mit Er dungs und Kurzschlie vorrichtung ber Er dungsbolzen die jeweiligen Kabelenden erden und kurzschlie en Benachbarte unter Spannung stehende Teile abschranken oder abdecken Bei Innenraum Schaltanlagen ohne Trenn w nde die Arbeitsstellen von den angrenzen den Schaltfeldern durch geeignete Abgren zungen z B Trennw nde absperren Gefahren bei Nichtbeachtung der Sicherheitshin weise Die Nichtbeachtung der Sicherheitshinweise f hrt zur Gef hrdung von Personen und zur Besch di gung der Schaltanlage Dies f hrt zum Verlust jeglicher Sc
37. g cur rent switch fuse combina tions IEC 60694 Common specifications for high voltage switchgear and controlgear standards IEC 61243 5 Voltage detecting systems LDTMW 5 DRIESCHER e WEGBERG Betriebsbedingungen Normale Betriebsbedingungen Die Schaltanlage ist f r normale Betriebsbedin gungen von Innenraum Schaltger ten und Schalt anlagen bei folgenden Umgebungstemperaturen ausgelegt I Hochstwert 60 C Tiefstwert 25 C Sonder Betriebsbedingungen Nach VDE 0670 Teil 1000 konnen von den nor malen Betriebsbedingungen abweichende Be triebsbedingungen zwischen Hersteller und Betrei ber vereinbart werden Zu jeder Sonder Betriebsbedingung mu der Hersteller vorher be fragt werden Hinweis zu etwaigen klimatischen Sonder Betriebsbedingungen Beim Betrieb von Schaltanlagen in Gebieten mit hoher Luftfeuchte und oder starken kurzzeitigen Temperaturschwankungen besteht die Gefahr von h ufigen Tauniederschl gen Zur Vermeidung unzul ssiger Kondensationserscheinungen und sich dadurch m glicherweise ergebender Korrosi on sind in Absprache mit dem Hersteller Gegen ma nahmen z B elektrische Heizung zu ergrei fen Haftungsbeschr nkungen Alle in dieser Montage und Betriebsanleitung ent haltenen technischen Informationen Daten und Hinweise f r die Installation Bedienung und War tung der Schaltanlage entsprechen dem Stand der Drucklegung und erfolgen unter Ber cksichtigung unserer bisherigen Erfahr
38. hadensersatz anspr che und kann folgendes nach sich ziehen Versagen wichtiger Funktionen der Schaltan lage Versagen vorgeschriebener Wartung und Instandhaltung Verletzung von Personen durch gef hrliche elektrische Spannungen Methoden zur Five Safety Rules 1 Isolate Isolate the cable cubicles and transformer cubicles where the work is being performed with corresponding switches 2 Secure against switchgear being reclo sed Separate the working range i e by using flags and closing ropes with warning pla tes to exclude confusions with cubicles which are still under voltage Set up an information sign on the disabled cubicles indicating what was isolated reason for the isolating name of the person who isolated Secure the switchgear in a suitable manner e g padlock the drive to prevent them from being turned back on 3 Checkabsence of voltage Check to make certain that the voltage te ster is functioning properly and that there is no voltage present 4 Earth and short circuit Using the earthing switch or an earthing and short circuiting device earth and short circuit the pertinent cable ends via short circuit bolts 5 Set up barriers around neighbouring parts that are live or cover them up On indoor switchgears without division walls limit the working areas from the nearby switching cubicles by adequate di visions i e separation walls Risks if safety instructions are not complied
39. hould make sure that the sensor mounted on the roof is not activated by external influences Gs The perfect function of the pressure sensor is only guaranteed if the dis tance between the roof of the switchgear and the ceiling of the station is at least 50 mm Mounting the busbars The busbars 22 LDTM DRIESCHER e WEGBERG Sechskantschraube M12x55 DIN 933 Spannscheibe 12 DIN 6796 gt Sechskantmutter M12 DIN 934 HI A N N e CHI dEr ee L PR iaa 7 DT i TA 52 Del b i A Schaltanlage erden Klemmst ck nach 14HB14559 Bild 23 1 Sammelschienenanschlu Earthing of the Switchgear Verbinden Sie die Erdungsschraube Grund rahmen Schaltanlage mit der Stationserde I Erdungen in Wechselstromanlagen f r Bemessungspannungen Mindestquerschnitte kV Strombelast barkeit von Erdungsleitungen siehe VDE 0101 LDIMW Connect the earthing screw base frame of the switchgear with the earthing of the sta tion For earthings in switchgears with AC and for rated voltages higher than 1 KV minimum see VDE 0101 regarding minimum cross sections and current ca pacity of earthing connections 23 DRIESCHER e WEGBERG Kuppeln
40. m zu behandeln Bei einer Schwerg ngigkeit im mechanischen Be wegungsablauf sollten die Gelenkstellen und Lager der Antriebsmechanik mit einem kriechf higen Spr h l behandelt werden S mtliche Schrauben der elektrischen Kontaktver bindungen m ssen berpr ft und gegebenenfalls angezogen werden Das maximal zul ssige An zugsdrehmoment der Befestigungsschrauben M12 mit Druckscheiben betr gt 40 Nm Unabh ngig vom verwendeten Anlagentyp sollte der Betreiber darauf achten da die Stationsr u me sauber und trocken sind Nach der Wartung sind vor der Inbetriebnahme einige Probeschaltungen durchzuf hren DRIESCHER e WEGBERG Maintenance Maintenance The maintenance cycle of LDTM switchgears is determined by the user and depends on various operating conditions Maintenance Manual 4 Provide for a free operation of the switch gear according to the five safety rules Please remove dust and dirt from the insulation components of the switchgear Please use fluff free clothes Use no detergents as sprays pastes and other solutions They might damage the insulating sur faces Eventual insulation damages discovered during the cleaning procedure have to be removed Please contact the assistance service for this Check the terminals The sliding capacitiy of the contact system of the switch disconnectors and earthing switches has to be checked The contact surfaces have to be treated only with solid paraffin
41. n Schwierigkeiten an unseren Produkten auf wenden Sie sich bitte an die zust ndige Vertretung oder an das Herstellerwerk Geben Sie bitte bei R ckfragen oder Ersatzteilbe stellungen folgende auf dem Typenschild angege bene Daten an Schaltanlagentyp Auftragsnummer Fabrikationsnummer Baujahr Bemessungsspannung strom und Bemessungs Durch Angabe dieser Daten ist gew hrleistet da Ihnen die richtigen Informationen oder die ben tigten Ersatzteile zugehen Fritz Driescher KG Spezialfabrik f r Elektrizit tswerksbedarf GmbH amp Co Postfach 1193 41837 Wegberg Deutschland Industriestra e 2 41844 Wegberg Deutschland Telefon 02434 81 1 Telefax 02434 81446 www driescher wegberg de e mail info driescher wegberg de Technische nderungen im Rahmen der Weiterentwicklung der in dieser Montage und Betriebsanleitung behandelten Schalt anlage behalten wir uns vor Aus den Angaben Abbildungen und Beschreibungen dieser Montage und Betriebsanleitung k nnen daher keine Anspr che hergeleitet werden Customer Service Our Customer Service is at your disposal for all technical information regarding DRIESCHER pro ducts and their systems engineering applications If difficulties with our products arise please contact the responsible representative or the manufactu ring factory If you have any questions or if you wish to order replacement parts please specify the following data shown on the nameplate typ
42. nctional check and a predetermined operating voltage Last repeated functional check see marking on the coupling part 34 LDTM DRIESCHER e WEGBERG MeBaufbau zur Wiederholungs Funktionspr Measuring Arrangement for the Re fung nach VDE 0682 Teil 415 Abschnitt 5 26 2 peated Functional Check according to IEC 61243 5 Section 5 26 2 Mef punkt Measuring point 7 Me strom measuring current Koppelteil MeBbeschaltung Coupling measuring circuit Z 36 MQ Im gt 2 5 uA U V3 0 45Un Bei U U folgt I gt 3 2 uA Phasengleichheit feststellen Check the Phase Parity D F hren Sie die kapazitive Phasenver D Perform the capacitive phase compari gleichsmessung vor dem ersten Zuschal son measurement before the first use of ten eines unter Spannung stehenden Ka a cable that is under tension bels durch Remove the protective taps from the Entfernen Sie die Schutzst psel der MeBbuch measuring bushes sen Subsequently connect measuring bushes Verbinden Sie nacheinander MeBbuchsen L 1 L1 L2 L2 L3 L3 of the relative ca L1 L1 L2 L2 L3 L3 der betreffenden Kabel ble ends with the phase comparison de abg nge mit dem Phasenvergleichsgerat vice Stellen Sie die Phasengleichheit fest Check the phase parity Stecken Sie die Schutzst psel auf die Me Put the protective caps onto the meas buchsen uring bushes BS Benutzen Sie nur Pr fger te nach VDE Please only
43. ontblenden erfolgt mit Schnellverschl ssen Der T ranschlag kann je nach Bedarf links bzw rechtsseitig eingerichtet und nachtr glich ge ndert werden x bei Umgeungstemperaturen gt 40 C Reduktionsfaktoren ber cksichtigen Description General The Driescher switchgear type LDTMW was designed for all types of indoor applications for mounting at a wall The switchgear is suitable for ambient tem peratures of 25 C up to 60 C The integrated arc limiting device gives a maximum of the passive and active safety The switchgear is a building of single cubicles The cubicles can be equipped with general pur pose switches short circuit poof earthing switches and HRC fuses With its modular composition of single cubicles the switchgear can be constructed in any com bination and subsequently extended The LDTMW switchgear is principally designed for any type of rooms in power stations i e for cellar garage plastics concrete tower and steel lamination stations For the observation of the switching appliances windows are foreseen The locking of the front cover is performed by quick release locks The door stroke can be on the left or on the right hand according to the needs and can be subsequently changed at ambient temperatures gt 40 C take care of the reduction factor 14 LDTM Storlichtbogenbegrenzer LDTMW Schaltanlagen sind standardm ig mit St rlichtbogenbegrenzer ausger stet Hierzu is
44. or the switchgear in the section on dimensions and weights Ma L Anzahl Felder 600mm breit 76mm 12KV 728mm Achten Sie bei Innenraum Stationen auf aus reichende Breite der G nge und Zugangs r ume um freie Bewegung und Transport zu erm glichen Mindestbreite des Bedienganges 800 mm Die Mindestbreite des Bedienganges darf nicht unterschritten bzw durch in den Gang hineinragende Teile eingeengt werden Stellen Sie die Schaltanlage so auf da Ausg nge und T ren von Innenraumstationen frei zug nglich sind Fluchtwege innerhalb der Station nicht mehr als 20 m betragen Stellen Sie die Schaltanlage nicht in explosi onsgef hrdete oder staubexplosionsgef hr dete R ume auf Aufstellungsempfehlungen LDTM Schaltanlagen sind standardm ig mit ei nem St rlichtbogenbegrenzer ausger stet der eine raumunabh ngige Aufstellung erm glicht number of cubicles 600mm width measure 76mm 728mm 12KV In case of indoor stations please make sure that there is a sufficient width between the corridors and the access areas for movement and trans port Minimum width of the user passage 800mm The minimum width of the user passage must be respected and shall not be narrowed by parts that extend into the passage Please position the switchgear in a way that exits and doors of indoor stations can be ea
45. r Single Field Supplies LDTM cubicles with an arc limiting device are inter linked by a coupling Figure 3 In case of switchgears that have been completed in the factory the shaft has al ready been coupled Before setting to work of the switchgear you should thus make sure that the coupling of the shafts in the two nearby switching cubicles are in a perfect functional state BS Please make sure that the drive shafts of all cubicles are coupled before the start of the switchgear to guarantee the operation of the arc limiting device For damages and troubles during operation that result from the lacking coupling of the drive shaft we do not assume any responsibility After the assembly of the switchgear loosen the cylindrical screw of the coupling part and move the coupling part left hand into the nearby cubicle Figure 1 Move the coupling part across the drive shaft up to the sensible stop provide for an easy gliding and tighten the cylindrical screw in front of the drive shaft in the coupling part Figure 2 Check the easy gliding of the drive shaft The triggering of the arc limiting device was adjusted optimal at the factory Never change these settings because mistakes or not actuating are possible H SZ lt Bild 1 al EL DI A Bild 2 24 Ser R ra Se I deg
46. r tracting the unlocking bolt 1 and turning it until it entriegelt werden Sie entriegeln das Getriebe clicks by 90 indem Sie die Entriegelungsklinke 1 herauszie The unlocking bolt 1 is situated in the right front hen und bis zur Einrastung um 90 drehen frame of the switchgear on the height of the motor Die Entriegelungsklinke 1 befindet sich an dem drive rechten Seitenholm der Schaltanlage in H he des The switching processes are then performed as Motorantriebes am jeweiligen Schaltfeld with a manual switch operation Die Schaltvorg nge erfolgen dann wie bei einem handbet tigten Schalter 36 LDTM DRIESCHER e WEGBERG Stromlaufplan Motorantrieb Wiring diagram motor drive ti Ka la SC s X10 3 3 1 E AC AC A j de 1 L 4 i rot red schwarz black L ra Gleichrichter V1 entf llt bei DC Anwendung Rectifier V1 not at DC Voltage Widerst nde R1 R4 nur bei 220VDC Resistances R1 R4 only at 220VDC Legende legend Fern vor Ort remote local ZU BE OFF Taster EIN Momentary contact ON Endschalter AUS Position switch OFF Endschalter EIN Position switch ON S8 Erderverriegelung Interlock to earthing switch LDTMW Q1 S1 Q1 S2 X3 EVI 34 FERN EIN REMOTE ON X1 9 FERN AUS REMOTE OFF 11 K4 AI 3 DRIESCHER e WEGBERG Magnetauslo
47. r und der Firma DRIESCHER DRIESCHER e WEGBERG Assembly For safety reasons the earthing switches must be in ON position at the time of transport and working Setup all earthing switches in OFF position via switch crank when the switchgear is set into work Discharge and Transport Respect the safety hints and the anti accident regu lations Be Please observe that the switchgear cannot be transported lying on the rear wall BS For the lifting and the transport of the switch gear please use a lifting device a load absorp tion device and a fixing device with a sufficient force Fix the fixation means only on the predisposed lifting devices Discharge and transport of the switch gear with a crane or a lifting carriage Fixation of the fixation means with safety hooks only on the lifting device at top of the switchgear Use fixing means of the same length The angle must not exceed a value of 90 Please provide for an equal weight bal ance After discharge Check the switchgear for damages Control if according to the delivery note the accessories are complete Document and signal transport damages imme diately to the carrier and to DRIESCHER LDTMW 19 DRIESCHER e WEGBERG Montage der Schaltanlage Platzbedarf Platzbedarf der Schaltanlage entnehmen Sie dem Kapitel Abmessungen und Gewichte Mounting of the Switchgear Necessary space Please check the space that is needed f
48. rleistung der St rlichtbogenfestigkeit sind diese mit einem Abdeckblech gesichert 38 Short Circuit Display option For the installation of short circuit displays copper extension flaps with 30 mm width overall meas ure 80 mm can be supplied as an option They allow the installation of mechanical pneumatic or liquid displays Display with the dimensions 96x48mm according to DIN are able for mounting in the front openings up or down They are insertable from the front of the cubicle To garranty the arc fault strength the circuit displays are secured with a cover LDIM Instandhaltung Wartung Der Wartungsturnus fur LDTM Anlagen liegt im Ermessen des Betreibers er ist abhangig von den unterschiedlichen Betriebsbedingungen Wartungsanleitung D Schalten Sie die Anlage unter Beachtung der funf Sicherheitsregeln frei Befreien Sie alle Schaltanlagen Isolationsbauteile gr ndlich von Staub und Schmutz Verwenden Sie dazu flusenfreie T cher Verwenden Sie keine Reinigungsmittel wie Sprays Pasten und sonstige L sungsmittel solche k nnen die Isolieroberfl che besch digen Eventuell bei der Reinigung erkennbare Isolations sch den m ssen beseitigt werden Wenden Sie sich hierzu ggf an den Kundendienst berpr fen Sie die Endverschl sse Die Gleitf higkeit des Kontaktsystems der Lasttrennschalter und Erdungsschalter ist zu ber pr fen Die Kontaktgleitfl chen sind nur mit Paraf fin in fester For
49. roke of the striker pin Switch on the earthing switch Then the door can be opened 41
50. rstdrucks der u eren Kapselung Hinweise zu Kupplung der Ausl sewellen Siehe 24 DRIESCHER e WEGBERG Arc limiting devices As a standard the LDTMW switchgears have an arc limiting device There are integrated pressure sensors in the roof which work on tripping shaft in the back wall of every cubicle This combination is also integrated in cubicles without an active earthing switch i e trans former cubicles etc The single tripping shafts are being connected and work onto the preset drives of the earthing switches In case of an arc fault the earthing switches of the incoming cubicles are actuated By the activation of the earthing switch the arc fault is transformed into a galvanic short circuit and the arc is extinguished The function of the pressure sensor is only given when the space between the roof of the switchgear and the ceiling of the room is minimum 50mm The manual activation and disactivation of a pre set drive can be performed as usual Switch disconnectors and earthing switches can be in terlocked The locking however permits the acti vation of the earthing switch for the arc limiting device independently from the switching state of the whole switchgear The tripping shaft for act ing the preloaded drives of the earthing switches in the cable cubicles is made of single shaft parts which can be coupled This modular con struction of the switchgear permits a simple ex tension of the switchg
51. ser Option Der Magnetausl ser Hilfsausl ser ist nicht f r 100 Einschaltdauer ausgelegt deshalb den Stromkreis immer ber den Hilfsschalter abschal ten Bei DC 24 60V und bei AC 110 230V wird 1 Hilfsschalter zur Unterbrechung verwendet der beim Ausschalten des Lasttrennschalters ffnet Bei DC 110 220 V werden zus tzlich ein Trip coil option The trip coil auxiliary coil is not designed for 100 ON time so always shut OFF the circuit via the auxiliary switch In the case of DC 24 60 V and AC 110 230V one auxiliary switch is used for the inter ruption it opens when the switch is switched OFF In the case of DC 110 220 V a second auxi liary switch and a suppression capacitor is also Hilfsschalter und ein Entst rkondensator ver employed wendet DC 24 60 V DC 110 220 V AC 110 230 V avoe 24v DC 100 ED LJ 100 ED I S01 Lem a S01 a m pe X114 2 3 L C01 L L1 N Fa Erox Rita PME 271M 330nF 250V AC 630V DC KurzschluBanzeiger Option F r den Einbau von Kurzschlu anzeigern sind 30 mm breite Verl ngerungslaschen aus Kupfer Stichma 80 mm lieferbar Sie gestatten den Einbau von mechanischen pneumatischen oder Fl ssigkeits Anzeigern Anzeigeger te mit DIN Abmessungen 96x48 mm lassen sich oben oder unten in die jeweiligen Aus schnitte des Rahmen von vorne einstecken Zur Gew h
52. sily accessed flight paths within the station are no more than 20 m Please do not position the switchgear in rooms exposed to an explosion risk or to a dust ex plosion risk Positioning Recommendations As a standard LDTM switchgears are equipped with an arc fault limiting device that enables a positioning in any possible space 20 LDTM DRIESCHER e WEGBERG Wandmontage des Grundrahmen Mounting Die Schaltanlage ist f r eine Wandmontage kon struiert worden Die Schaltfelder werden mittels eines Grundrahmen an der Wand befestigt so da eine freie Kabelf hrung unterhalb der Felder m g lich ist Die Montage der Schaltfelder erfolgt gene rell so hoch da bei Anschlu mit Einleiterkabeln keine Kabelgrube erforderlich ist Befestigen Sie den Grundrahmen entspre chend dem Bild 21 1 an der Wand BS Gleichen Sie Unebenheiten durch geeignete Unterlagen aus Benutzen Sie zur Rahmenbefestigung f r das Mauerwerk geeignete Befestigungselemente Please place the switchgear only on z B f r Betonw nde den Kompaktd bel Typ plain and horizontal concrete bases or interme HKDM10 der Fa Hilti mit Schrauben M10 diate frames with a sufficient carrying capacity to avoid the deformation of the cubicles Nach der Montage konnen die beiden Langsholme 1 und 2 entfernt werden F r evtl nachtr gliche Anlagenerweiterungen empfiehlt sich den L ngs Es sind Grundrahmen f r 2 und 3 feldige An holm 2 grunds tzlich zu
53. start after a modification or maintenance of the switchgear atleast every 4 years BGV A2 Confirm the perfect state of the switchgear in writing in the test report Operating parts and accessories as levers lockout devices option tension display device insulating cover plate have to be available ready for use in the room of the switchgear or nearby Replace damaged components eventually with tested or approved DRIESCHER Parts Check the tension display devices for nominal voltages of over 1 kV at least every 6 years in relation to the observance of the limit values established in the electro technical regulations Observe the regulations of the producer for ten sion display devices 40 LDTM DRIESCHER e WEGBERG Fehlerbehebung Troubleshooting Beachten Sie bei der Fehlerbehebung alle in der Montage und Betriebsanleitung aufgef hrten Si cherheitshinweise Die Fehlerbehebung d rfen nur Elektrofachkr fte gem Definition in DIN VDE 0105 durchf hren For the troubleshooting please observe all the safety hints of the operating manual The troubleshooting shall be performed only by qualified electrical staff according to the definition in DIN VDE 0105 M gliche Ursa Abhilfe che 4 Lasttrennschal ter Schaltkurbel l t sich nicht aufstecken Erdungsschalter Schaltkurbel l t sich nicht auf stecken Transformator Lasttrennschalter l t sich nicht einschalten Keine Frei
54. t ein Drucksensor im Dach von jedem Schaltfeld angeordnet der auf eine in der R ck wand angebrachten Ausl sewelle wirkt Diese Kombination ist ebenfalls in Schaltfelder oh ne aktiven Erdungsschalter z B Transformatorfel der usw eingebaut Die einzelnen Ausl sewellen werden miteinander verbunden und wirken auf die vorgespannten Er dungsschalterantriebe die im St rlichtbogenfall die Erdungsschalter der Einspeisefelder zuschalten Durch die Ausl sung des Erdungsschalters wird der St rlichtbogenfehler in einen galvanischen Kurzschlu umgewandelt der St rlichtbogen verl scht lt Die Funktion des Drucksensors ist nur dann gew hrleistet wenn der Abstand zwischen dem Dach der Schaltanlage und der Stationsdecke mindestens 50 mm betr gt Die manuelle EIN und AUS Schaltung kann bei vorgespanntem Antrieb wie blich vorgenommen werden Lasttrennschalter und Erdungsschalter k nnen gegeneinander verriegelt sein Die Verrie gelung l t allerdings die EIN Schaltung des Er dungsschalters zur St rlichtbogenbegrenzung unabh ngig vom Schaltzustand der Gesamtanlage zu Die zur Bet tigung der in den Kabelfeldern vorgespannten Erdungsschalterantriebe ben tigte Ausl sewelle ist ber Kupplungen aus einzelnen Wellenabschnitten aufgebaut Dieser Modulaufbau der Schaltanlage erlaubt ohne gr eren Aufwand eine Erweiterung der Schaltanlage Der Ansprech druck des Drucksensors liegt in sicherem Abstand unterhalb des Be
55. the Operating Instructions Respect the safety rules for the lifting and the transport of the switchgear LDIMW Use a lifting device transport and fixation means with a sufficient load capacity Fix the fixation means only on the pre scribed points Ropes chains or other fixation means have to be equipped with safety hooks Do not use damaged or worn ropes Do not knit together ropes and chains and do not fix them on sharp angles Do not lift loads over the heads of per SONS 13 DRIESCHER e WEGBERG Beschreibung Allgemeines Die DRIESCHER Schaltanlage Typ LDTMW ist f r eine Innenraummontage zur Wandaufh ngung vorgesehen Die Schaltanlage ist bei Umgebungstemperaturen von 25 C bis 60 C einsetzbar Durch integrierte St rlichtbogenbegrenzer wird ein H chstma an passiver und aktiver Sicherheit erreicht Die Schaltanlage ist aus Einzel Schaltfeldern auf gebaut Die Schaltfelder k nnen mit Mehrzweck Lasttrennschaltern kurzschlu einschaltfesten Erdungsschaltern und HH Sicherungen ausger stet werden Aus einzelnen Feldern baukastenartig zusammen gesetzt kann die Anlage beliebig kombiniert und sp ter erweitert werden Die LDTMW Schaltan lage ist grunds tzlich f r alle Arten von Stations r umen geeignet z B f r Keller Garagen Kunststoff Beton Turm und Stahlblechstatio nen Zur Beobachtung der Schaltger te sind Sichtfen ster vorgesehen Die Verschlie ung der Fr
56. ting device measuring sockets for the capacitive volt age indication and the phase comparison Option or measuring sockets for summati on current transformer Option DRIESCHER e WEGBERG Technische Daten Technical Data Bemessungsgr en Rated values Bemessungsspannung 12 kV Rated voltage Bemessungs Kurzzeitstrom 20 KA Rated short time current Bemessungs Einschaltstrom 50 KA Rated short circuit making current Bemessungs Lastausschaltstrom 630 A Rated mainly active load breaking current Bemessungs Ringausschaltstrom 630 A Rated closed loop breaking current Bemessungs Kabel und 25 A Rated cable and line charging Freileitungsausschaltstrom breaking current Bemessungs Ausschaltstrom unter Erd 300 A Rated breaking current under earth schlu bedingungen leakage condition Bemessungs Stehwechselspannung 28 32kV RAS DONEITESNEDEN MIN Tg 75 85 kV gt Rated lightning impulse withstand voltage 60 70kV 10 A Rated no load transformer breaking current Ambient temperatures bei Umgebungstemperaturen gt 40 C Reduktionsfaktoren ber cksichtigen at ambient temperatures gt 40 C take care of the reduction factor HH Sicherungseinsatze HV HRC fuses Die Tabelle gibt Absicherungsempfehlungen f r The table gives safety recommendations for DRIESCHER HH Sicherungseins tze the DRIESCHER HV HRC fuses sungsleistung Rated current of HRC Fuses Rated trans former power 7 2 kV 12 kV e 292 mm e 292 mm min max min max 125 200
57. tor errors and to ensure troublefree operation of the medium voltage switchgear the Operation and Assembly Instructions must always be accessible to the owner operator Aside from these Operation and Assembly Instructi ons the safety regulations and the texts identified by safety symbols the following general specifications are binding for handling the medium voltage switchgear connection conditions of your local power supply companies European safety regulations EU standard Safety of Machines Devices and Systems the pertinent safety regulations in countries out side of the EU 10 LDTM Arbeiten an Mittelspannungs Schalt anlagen Betrieb Arbeiten und Bedienung an Mittelspan nungs Schaltanlagen d rfen nur Elektrofachkr fte gem Definition in VDE 0105 ausf hren unter Beachtung der jeweils g ltigen VDE IEC Vorschriften 5 Sicherheitsregeln nach VDE 0105 Sicherheitsvorschriften Unfallverhutungsvorschriften Bedien und Zubeh rteile m ssen jederzeit f r die Elektrofachkraft vorhanden zug nglich und in ordnungsgem em Zustand sein Sie d rfen keine Besch digungen aufweisen Ersetzen Sie besch digte Bedien und Zubeh r tele durch gepr fte oder zugelassene DRIESCHER Teile Zust ndigkeiten und Bedienungsabl ufe f r Be dienung und Wartung m ssen geregelt sein und eingehalten werden Elektrofachkraft Als Elektrofachkraft laut VDE 0105 gilt wer auf Grund seiner fachlichen
58. ucer and assemble the set of cables Assemble phase L1 and screw the cable box carrier in a way that the cable extends vertically downwards Assemble phase L2 and finally phase L3 LDTMW 25 DRIESCHER e WEGBERG berpr fen Sie den Zustand der Endver schl sse z B Oberfl chenbeschaffenheit ordnungsgem e Anordnung der Kabelschuhe und Klemmverbindungen Bei Kleinendver schlussen m ssen die Klemmschrauben der Schlauchschellen nach vorn oder hinten ange ordnet sein Beachten Sie die Sicherheits und Montage hinweise des Herstellers der Kabelgarnituren Befestigen Sie die Endverschl sse an der mitgelieferten oder bauseitig angebrachten Kabelhalteeisen Beachten Sie die Phasenfolge Befestigen Sie die Kabel so an den Anschlu kontakten des Schaltger tes da keine me chanischen Spannungen auf die Kontaktan schluBlaschen einwirken 26 LDTM Check the state of the terminals i e the state of the surfaces the right fixation of the cable sockets and the clamps With small terminals the binding screws of the tube clamps have to be disposed in a front or a rear row Respect the safety and assembly instructions of the cable producer Fix the terminals on the supplied cable box carrier or at site available Respect the sequence of phases Fix the cables in a way that on the connec tion contacts of the switches no mechanical tensions are exercised on the contact con nection flaps Betrieb Inbetriebnahme
59. ul ssigen Betriebsmitteln fehlerhafter Aufstellung falschem oder nicht fachgem sem Anschlu der Mittelspannungskabel bzw der Hilfs Steuerleitungen Driescher HH Sicherungen Zubeh r und Ersatz teile sind speziell konstruiert und in aufwendigen Testreihen erprobt worden Wir weisen ausdr cklich darauf hin da nicht vom Hersteller gelieferte Ersatzteile sowie die vom Her steller empfohlenen Zubeh rteile auch nicht vom Hersteller freigegeben sind Der Einbau und die Verwendung von Fremdprodukten kann unter Um standen konstruktiv vorgegebene Eigenschaften der Produkte negativ ver ndern und die Sicherheit f r Person Schaltanlage oder andere Sachwerte beeintr chtigen Vor Einbau von Fremdprodukten ist die schriftliche Genehmigung des Herstellers erforderlich F r Sch den die aus der ungenehmigten Verwen dung von Fremdprodukten resultieren sowie sich aus eigenm chtigen Ver nderungen oder Um bauten an unseren Produkten oder Zubeh r erge ben ist jede Haftung des Herstellers ausgeschlos sen Gew hrleistungsdauer Die Gew hrleistung dauert 12 Monate ab Ausliefe rung DRIESCHER e WEGBERG Warranty These Operation and Assembly Instructions contain all required notes and must be read through carefully before placing the medium vol tage switchgear into service We accept no liability for damage and operational disruptions resulting from failure to comply with the Operation and Assembly Instructions
60. ungen ausgel st wird KS Die einwandfreie Funktion des Drucksen sors ist nur dann gew hrleistet wenn der Abstand zwischen dem Dach der Schalt anlage und der Stationsdecke mindestens 50 mm betr gt Montage der Sammelschienen Die Sammelschienen sind entsprechend Ihrer Phasenkennzeichnung zu montieren L1 links L2 mitte L3 rechts Verwenden sie zum Anschlu der Rundleiter die mitgelieferten Klemmst cke und stellen Sie die Verbindung entsprechend dem Bild 23 1 her Die Sammelschienenst cke reichen von der rechten Klemmstelle des Klemmst cks zur linken Klemmstelle des Klemmst cks im Nachbarschaltfeld In den Endfeldern mussen jeweils die freien Klemmstellen mit Futterst cken best ckt wer den Das Anzugsdrehmoment der Schrauben mu 40Nm betragen Installation Hang on the switchgear with lifting carriage on the predetermined frame A H ngen Sie die Schaltanlage nur an ebene und lotrechte Grundrahmen auf um ein Ver spannen der Schaltfelder zu vermeiden Un ebenheiten der Wand m ssen ausgeglichen werden ui Please observe the safety hints dis charge and transport Please respect the minimum dimensions Gs In the case of switchgears that have to be supplied as single cubicles the single cubicles have to be screwed on the in stallation site on the front and on the rear longitudinal cross beam each time with 4 M8 screws While transporting and positioning the switchgear you s
61. ungen und Erkenntnisse nach bestem Wissen F r etwaige Fehler oder Unterlassungen haften wir unter Ausschlu weiterer Anspr che im Rahmen der im Hauptvertrag eingegangenen Gew hrlei stungsverpflichtungen Anspr che auf Schadens ersatz gleich aus welchem Rechtsgrund derartige Anspr che hergeleitet werden sind ausgeschlos sen soweit sie nicht auf Vorsatz oder grober Fahrl ssigkeit beruhen bei Umgeungstemperaturen gt 40 C Reduktionsfaktoren ber cksichtigen Service Instructions Standard service conditions The switchgear are designed for normal service conditions of indoor switchgear and switching sy stems at the following ambient temperatures Maximum value 60 C Lowest value 25 C Special Operating Conditions In accordance with IEC 60694 the manufacturer and the owner can agree to operating conditions that deviate from the standard conditions The manufacturer must be asked in advance about any special service condition Note on eventual Climatic Special Operating conditions If switchgear are operated in areas with a high air humidity and or strong rapid temperature oscilla tions there is the danger of frequent dew preci pitations To avoid inadmissible condensation phenomena and the resulting corrosion the rela tive preventive measures have to be agreed with the producer i e electric heating Restrictions on Liability All of the technical information data and notes about the installation
62. use test devices according 0682 Teil 415 Entwurf f r HR Systeme to IEC 61243 5 for HR Systems Please Beachten Sie die Montage und Betriebs observe the instructions of the producer anleitung der Pr fger tehersteller und VDE of the test appliances and IEC 61243 5 0682 Teil 415 Entwurf Pr fen Sie die Check the test appliances for proper Pr fger te vor Gebrauch auf Funktion operation before usage LDTMW 35 DRIESCHER e WEGBERG Motorantrieb Option Motor Drive Option Der Motorantrieb bernimmt prinzipiell die Funktion Principally the motor drive functions as a switch der Schaltkurbel Die grunds tzliche mechanische ing crank The principal mechanical function of Wirkungsweise des Schalterantriebes bleibt hier the switch drive is not influenced by this The von unber hrt Ebenso bestehen die Verriegelun locking devices principally act in the same way gen in prinzipiell gleicher Art Switch disconnectors equipped with motor drives Mit Motorantrieben ausger stete Lasttrennschalter can be switched on and switched off by the rele sind ber eine entsprechende Steuerung ein und vant control device ausschaltbar The motor drive with a gear is installed behind Der Motorantrieb mit Getriebe ist hinter dem rech the lateral traverse at right hand side of the cubi ten Seitenholm der Felder angebracht Er treibt cles It actuates by means of a chain wheel drive ber einen Kettenradantrieb die Antriebswelle an the drive shaft
63. with Failure to observe the safety notes leads to en dangerment of persons and damage to the switchgear This will culminate in the loss of any and all claims for compensation for damage and may cause the following injury of persons due to dangerous electri cal voltage failure of important functions of the switchgear failure of specified methods of maintenance and service 12 LDTM Sicherheitshinweise fur Transport Montage Betrieb und Wartung Der Betreiber sorgt daf r da alle Transport Montage Bedienungs und Wartungsarbeiten von Elektrofachkr ften ausgef hrt werden welche die Montage und Betriebsanleitung gelesen und ver standen haben Beachten Sie die Sicherheitshinweise f r das He ben und Transportieren der Schaltanlage Hebezeug Lastaufnahmemittel und Anschlag mittel mit ausreichender Tragf higkeit verwen den Anschlagmittel nur an den hierf r vorgesehe nen Stellen anschlagen Seile Ketten oder andere Anschlagmittel m s sen mit Sicherheitshaken ausger stet sein Keine angerissenen oder angescheuerten Seile verwenden Seile und Ketten nicht knoten und nicht an scharfen Kanten anlegen Lasten nicht uber Personen hinweg heben DRIESCHER e WEGBERG Safety instructions for transport as sembly operation and maintenance The owner must make certain that all transport operation and maintenance jobs are carried out by qualified electrical technicians who have read and understood