NFS-320/E/C OPERATING INSTRUCTIONS

image

Contents

1. ALS SILENCED indicator It also sends a SIGNALS SILENCED message to the LCD display printer and history file A subsequent alarm will then resound the system Notes 1 This unit is programmed to inhibit signal silence for seconds 2 This unit is programmed to automatically silence alarm signal after minutes Drill The NFS 320 E C waits for the Drill switch to be pressed for 2 seconds to prevent accidental activations then turns on all silence able circuits all FCM 1 modules bell circuits that are programmed silenceable and turns off the Signals Silenced LED It sends a Drill Activated message to the LCD display FDU 80 printer and History file System Reset Resets the control panel in standalone applica tions Resets panel when enabled in network applications Lamp Test Press and hold the switch to lamp test the LEDs Section 3 LED Indicators Controls Active Green LED which illuminates when the panel assumes control of local operation as primary display Turns off auto matically when another panel assumes control of local operation Power Green LED which illuminates when primary power is applied to the control panel Pre Discharge Red LED lights when any of the releasing zones have been activated but have not yet discharged a releasing agent turns off when no releasing zones are in the pre discharge state Discharge Red LED lights when any of the releasing zones are active and in the process of discharg
2. EM RESET is pressed Point Disabled Yellow LED that illuminates when one or more points are disabled The LCD will indicate which points have been disabled Turns off when points are re enabled Section 4 Audible Tone Indicator Alarm A continuous sounding tone Trouble Security A slow pulsating tone signal having an equal on and off time Supervisory A fast pulsating tone signal having an equal on and off time Section 5 Periodic Testing and Maintenance To ensure proper and reliable operation system inspection and testing should be scheduled monthly or as required by NFPA 72 or local fire codes A qualified Service Representative should perform testing Before Testing Notify fire department and or central alarm receiving station if alarm condition is transmitted Notify facility per sonnel of the test so alarm sounding devices are ignored during the test period After Testing Notify all fire central station and or building per sonnel when testing is complete Section 6 Local Service Representative NAME ADDRESS TELEPHONE NUMBER This sheet must be framed and mounted adjacent to the control panel NFS 320 E C Operator s Instructions P N 52748 A ECN 06 166 12 28 2006
3. NFS 320 E C OPERATING INSTRUCTIONS Section 1 Operating Information Normal Standby Operation 1 Green POWER indicator lit steadily 2 Red FIRE ALARM indicator off 3 Yellow TROUBLE indicators off Alarm Condition 1 Red FIRE ALARM indicator lit 2 Alarm signaling devices activated 3 Option module remote station or supplementary alarm relay acti vated 4 Alarm information visible on LCD display Alarm Reset After locating and correcting the alarm condition reset the control panel by pressing the SYSTEM RESET switch Trouble Conditions Activation of trouble signal under normal operation indicates a condition that requires immediate attention Contact your local service representative Silence the audible signal by pressing the ACKNOWLEDGE SCROLL DISPLAY switch The trouble indicator will remain illuminated Section 2 Switch Functions Acknowledge Scroll Display This silences the piezo sounder and changes all flashing conditions to steady Only one press is necessary regardless of the number of new alarms troubles or supervisory signals If the piezo is silenced it sends an acknowledge message to the printer and history file Acknowledge also automati cally sends a special command to silence piezo sounders on the FDU 80 and ACS Annunciators Signal Silence SIGNAL SILENCE performs all the functions of ACKNOWLEDGE In addition if an alarm exists it turns off all silence able circuits and illuminates the SIGN
4. ing a releasing agent turns off when no releasing zones are discharging a releasing agent Abort Active Yellow LED lights when an abort switch has been activated turns off when an abort switch has been pressed and its timer is still counting down Activation of a Manual Release Switch will override Predischarge Delay and override an active Abort Release Switch resulting in an immediate agent release Fire Alarm Red LED that flashes when one or more alarms occur Illuminates steadily after alarms are acknowledged turns off when SYSTEM RESET is pressed after alarm clears Pre Alarm Red LED that flashes when a pre alarm threshold is reached The LCD display indicates if it is an ALERT or ACTION pre alarm Security Blue LED that illuminates for a security alarm LED turns off after the alarm clears and SYSTEM RESET is pressed Supervisory Yellow LED that flashes when a Supervisory Haz ard Alert or Tamper condition occurs such as a sprinkler valve tamper condition The LED turns off when the Supervisory condition clears The Hazard Alert or Tamper indication will latch until reset System Trouble Yellow LED that flashes when one or more troubles occur Goes on steadily when ACKNOWLEDGE is pressed and turns off when all trouble conditions are cleared Will illuminate if the microprocessor watchdog timer fails CPU FAIL Signals Silenced Yellow LED that illuminates after SIGNALS SILENCED has been pressed Turns off when DRILL or SYST

Download Pdf Manuals

image

Related Search

Related Contents

StreetSmart.com User Guide  Whirlpool W10545083A User's Manual  Owner/User Manual  Watlow Electric ANAFAZE SYSTEM 32 User`s guide  Samsung SC5120 User Manual  SCシリーズ, 交流電圧・電流変換器  Page 1 Page 2 ごィ更用前に、 この取扱説明書を十分、 お読み下さい  i-GOVERNOR SYSTEM Instruction manual I G S 取扱説明書  235号(平成26年1月10日)  MODE D`EMPLOI SYSTÈMES DE MAINTIEN  

Copyright © All rights reserved.
Failed to retrieve file