PXM10 User's guide
Contents
1. Figure 5 3 Pop up window with event Figure 5 4 Pop up window with unacknowledged alarm 19 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 The display shows a time stamp the object name the notification text and the alarm priority In the case of alarm messages you can display the Alarm list directly see Section 5 2 Deleting a pop Press Esc to delete a pop up window without affecting the up window alarm 5 2 Displaying the alarm list Alarms Diff pressure moni gm Outside air filter A Plant control A Figure 5 5 The Alarms menu alarm list The alarm LED lights up and flashes Step Procedure 1 Display the alarm list either by use of the alarm button or by selecting the Alarms option PRC Contr l Air handling unit Heat generation Alarms Settings Figure 5 6 Plant data screen 2 The alarm list opens Unacknowledged alarms and alarms that have been acknowledged but not yet reset are displayed here Each line contains the object name and the alarm symbol All the associated information can be displayed by use of the Info button 20 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 Note that for each object only the current alarm i e the last alarm received is displayed Acknowledged alarms and reset alarms are removed from the PXM10 display Exception Acknowled
2. Figure 2 15 Time schedule graph 2 3 3 Symbols The following is a list of all the symbols used in the display and their meanings The same symbol may represent different entries or have a different meaning depending on the context Symbol Description it Favorite objects These are defined at the engineering stage Pop up window Alarm or event Alarm list Uncleared alarm neither acknowledged nor reset Uncleared but acknowledged alarm Alarm cleared but not acknowledged ROR PF Alarm cleared acknowledged but not reset D Info window Info symbol dh Override Manually overwritten forced value F Cursor Only used in Scheduler graphs Wildcards Only used in Scheduler gt Special period Description in Section 6 2 13 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 Building Automation 3 Commissioning the PXM10 The PXM10 is used for local operation of a compact or modular DESIGO PX automation station No user login is required The PXM10 allows you to work at the Basic and Standard operating levels All the objects from these operating levels are mapped in the device Note Favorite objects are defined at the engineering stage and mapped separately Step Action 1 Mount the PXM10 on the housing of the modular automation station or Connect the PXM10 to the compact or modular automation station with a PXA C1 cable 2 After a few seconds
3. which consists of a maximum of four alohanumeric lines of text Graphs are only displayed in the Scheduler menu If there are more lines than can be displayed at once this is indicated by the scroll arrows 11 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 Highlighted line Outlined text Building Automation A line highlighted in inverse video light print on dark background indicates an option associated with one or more hierarchically subordinate lines you can display these with the push dial Monday Tuesday Figure 2 11 Text lines one of which is highlighted If a line of text is outlined this indicates that you are at the lowest level and you can only read but not edit the value on this line Use the Esc button to navigate back to the next higher level E a supply air 31 9 E Figure 2 12 Outlined text at the lowest level Pop up A pop up is a dialog box used to display an alarm or an event The alarm button provides direct access to the list of pending alarms PxC Contr 61 co Bru D 11 22 xHir handling unit gt Figure 2 13 Pop up display for an alarm PAL Contre El co Hy D 11 25 xHir handling unit Figure 2 14 Pop up display for an event 12 34 Siemens Building Technologies PXM10 operator unit CM110397en 31 08 2004 Graphs Time schedules are displayed in graph form Monday From SS ar oe 12 00 su
4. 13 POUR 12 WOkng ACA ura a 11 Bee panel serine pt 10 lt A aa araea raa aiai 6 8 Event Enable DOD EE EE casa 16 FO 19 VONIS EEE EE EE EE NE 19 GVA IEN 13 HOUSING EE E 7 INFO DUO E eee 9 NET UNION eee 15 Keys ES 8 VED uppe 9 Beete EE 15 MENING ua 11 31 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 Operator controls Printing Convention 6 Parallel Operation HER 14 POP AT 0 RE PE EE EN EE 12 BE ER ER PE OR EN EEE 20 POD UP WINDOW ua 19 Printing conventions 6 Redaing and editing values 17 Schedule Special Denda 26 SNE 23 Seng hed 8 RER 16 Setting the object view 16 Selling he ME saa 16 SEG ED Re Caen ete 15 Special PENGA ua 26 NAN 29 ONO SA 28 Symbol MAMA 13 Favorite objects ee 13 Forced EE 13 PTO WINGO Wasa etait ace Mare eters ae ae ee 13 PO UD WINDOW EE 13 WIdC Aisa 13 le Ter 29 32 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 33 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 Siemens Building Technologies Ltd Building Automation Gubelstrasse 22 CH 6301 Zug SWITZERLAND Tel 41 41 724 24 24 Fax 41 41 724 35 22 www sbt siemens com Siemens Building Technologies PXM10 operator unit Building Automation 2004 Siemens Building Technologies Ltd Subject to alteration CM110397en 31 08 2004
5. display panel Bold text is used to denote the exact text which appears in the display e g Main menu or Settings 1 3 2 Labeling of the push dial and buttons The main operator control element the push dial is not named on the housing The Acknowledge function OK is integrated into the push dial The Info and Esc buttons are labeled accordingly on the housing The Alarm button is not named on the housing but can be identified by the alarm symbol Examples Press the Info button or more briefly Confirm with OK 1 3 3 Notes Caution The symbol shown here acts as a warning in cases where an action may result in permanent loss of data D Important This indicates an important statement which requires your special attention Note A Note qualifies an immediately preceding statement or statements 6 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 2 Display and control elements 2 1 Layout SIEMENS Figure 2 1 Housing Key 1 Info button 2 Display panel 3 Push dial 4 Alarm button with alarm LED 5 Esc button 7 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 2 2 Push dial and buttons 2 2 1 Push dial Figure 2 2 Push dial The push dial is the main operator control element Rotary action By rotating the dial you can move
6. extended alarms 22 SN adr 23 Day ege TEEN 23 Editing an existing profile 24 Adding a new entry coccccccnnccnncnnnnccnncnnnnncnncnnnnncnnnos 25 Special PENOAS ss 26 GI ad taa 28 Adding a NEW entry coccccccnnccnncncnnccnncnnnnnnnncnnancnnnnss 29 10 ES EE 31 PXM10 operator unit CM110397en Contents 31 08 2004 D Important 1 About this manual 1 1 Target readers This user s guide is written for the users of the plant and for service engineers It is assumed that the users of the manual will have the necessary understanding of the system and plant 1 2 Content The descriptions in this manual cover the commissioning basic configuration and use of the PXM10 operator unit As there may be significant differences between one plant and another and between one object and another it follows that it is not possible to provide a description which is generally applicable to every individual case The question of exactly which objects are integrated with which values in a plant is determined in the engineering phase according to the individual needs of the plant operator The descriptions in this manual are intended as examples only and are designed to clarify the basic operating principles of the PXM10 operator unit 5 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 1 3 Printing conventions 1 3 1 Text in
7. from top to bottom of the text field and set or modify setpoints Push action By pushing the dial you can navigate to the next level down and acknowledge a selected option or input this function is equivalent to selecting OK 2 22 Esc button Figure 2 3 Esc button Pressing the Esc button lets you abandon a process you have already started e g editing a value navigate to the next higher level or close a pop up window 8 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 2 2 3 Info button Figure 2 4 Info button You can use the Info button to display a pop up window containing all the available information about the selected line You can close the pop up window by pressing the Info button or Esc button again 2 2 4 Alarm button with alarm LED Figure 2 5 Alarm button with alarm LED The alarm LED lights up or flashes when an alarm or event is tripped in the system The alarm button takes you straight to the alarm list Alarm LED ca Sym Event response bols Flashing Pending alarm unacknowledged pop up window and alarm list SE __ Incoming event pop up window only event pop up Incoming event pop up window only only Wa Pending alarm acknowledged and extended alarm acknowledged but not reset alarm list CON EC Note Alarms are operated by use of the push dial see Section 5 9 34 Siemens Building Technologies PXM10 operator uni
8. the display will light up and the opening screen will appear The PXM10 is now ready for operation SIEMENS Phi 002 01 Parc 02 20 032 Figure 3 1 Opening screen 3 Either open the plant data with OK or Press the alarm button to go directly to the alarm list Notes The PXM10 and PXM20 can be used in parallel for operation and monitoring of a PXC U automation station by mounting the PXM10 directly on the automation station and connecting the PXM20 to the MMI tool socket with a PXA C1 cable 14 34 Siemens Building Technologies PXM10 operator unit CM110397en 31 08 2004 Logout Caution If the PXM10 connection is interrupted briefly it may take up to 15 seconds for the polling cycle to resume The display can be re enabled by operating any of the operator controls There is no need to log out Wait 30 seconds before reconnecting 3 1 Settings on the device Dat Contre HI Air handling unit Heat generation Alarms Settings Figure 3 2 Display showing plant data Step Procedure 1 Press OK to open the Settings menu Settings Contrast Time 11 13 Date 2 Br D Event popup Inactive Settings Time 11 16 Date oo DC H i Event popup Inactive Both Figure 3 3 Individual entries 2 Get individual values by rotating the dial and acknowledge the settings with OK You can also use OK to move from one input field to the next within a value 15 34 Siemens Building Technologies PXM10 operator uni
9. SIEMENS amp SIEMENS PXM10 DESIGO PX PXM10 operator unit User s guide Version 2 3 CM110397en een Siemens Building Technologies Building Automation 2 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 Contents 1 ABOUT TIS Ma al union 5 1 1 Target e EE 5 1 2 Go E GE 5 E3 Printing conventions 6 1 3 1 Text in display panel rrrrnnnnnnnnnronnnnnnnvnnnnrnnnnnnen 6 132 Labeling of the push dial and buttons 6 1 3 3 NO Le 6 2 Display and control elements 2 7 2 1 A EE 7 2 2 Push dial and buttons cccccoccccccoccnccconnncnoncnnnnos 8 2 2 1 PUG als io asas 8 2 2 2 ED 8 2 2 3 MIO DUNO A ne 9 2 2 4 Alarm button with alarm LED oocccccocccccc 9 2 3 Display panel unicas 10 2 3 1 MENUS nd 11 2 3 2 VV ONGING Aid eres 11 2 3 3 O IDOI EE 13 3 Commissioning the PXMi0 14 3 1 Settings ON the device 15 4 Reading and editing values 17 4 1 Example Setting a setpoint 17 5 Alarms and events cccccccssseeeeeceeseeeeseaaeeeeees 19 5 1 POP UP WINDOWS aS 19 5 2 Displaying the alarm Jet 20 53 Acknowledging alarms 21 3 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation Contents 31 08 2004 9 4 6 1 6 1 1 6 1 2 6 2 6 2 1 6 2 2 4 34 Siemens Building Technologies Building Automation Resetting
10. ge with OK If a value is made up of two or more input fields the input focus will then switch to the next field Confirm with OK or press Esc to cancel Press the Esc button to return automatically to the Setpoints screen Figure 4 2 Note 18 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 5 Alarms and events Difference The LED display in the alarm button lights up in response to between alarm incoming alarms and events and in the case of alarms and event starts flashing Events do not require acknowledgement nor do they appear in the alarm list 5 1 Pop up windows If an alarm or event occurs while the PXM10 is in operation you will be notified accordingly in a pop up window Figure 5 1 If the PXM10 is only switched on after the occurrence of the alarm or event there will be no pop up window These alarms do however appear in the alarm list Activating event If you want to be notified of events in a pop up window you pop up windows can activate this option under Settings gt Event popup Settings Settings Contrast S Event popup Time 11 29 Date 28 Hr B event popup Inactive Figure 5 1 Settings screen Figure 5 2 Activate event pop up window A pop up window contains the main information about the event or alarm concerned PRC Contr fi PRC Contre Al 28 Hr Ba 11 25 28 Hr Ba 11 22 xHir handling unit gt xHir handling unit gt
11. ged extended alarms which require a reset continue to be displayed in the alarm list until they are reset 5 3 Acknowledging alarms Step Procedure 1 Highlight the required alarm in the alarm list Figure 5 3 A The bell symbol shows the status of the alarm see the symbol in Section 2 3 3 2 Acknowledge the next alarm Alarns Diff pressure monit ae H B 11 32 acknowledge Figure 5 7 Prompt for acknowledgement Use the push dial to select No or Yes and acknowledge with OK The alarm LED will stop flashing and switch off The bell symbol is marked with a tick representing acknowledged Fret With extended alarms which require a reset once the fault has been cleared the alarm LED stays on see Section 5 4 3 Acknowledge the next alarm or Press Esc to close the alarm list Note Basic alarms disappear when the fault has been cleared they do not require acknowledgement 21 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 Caution 22 34 5 4 Resetting extended alarms Extended alarms additionally require a reset Delete the associated pop up window by pressing Esc The alarm can only be reset after the fault has been cleared Step Procedure 1 Navigate to the Alarms option Figure 5 4 Confirm with OK The alarm list opens Figure 5 3 Highlight the required alarm and confirm with OK Clear the fault Open the alarm li
12. heduler Day Profile Special Period Figure 6 10 Special period 26 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 A window opens containing the following options e New entry Define a new special period e Others Edit an existing special period Special Period Hew entry Others 29 0r H Figure 6 11 Special period screen 3 Continue as described in Section 6 2 1 Others or as in Section 6 2 1 Adding a new entry 27 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 6 2 1 Others Step Procedure 1 Open the required entry and confirm with OK Special Period Hew entry Others 29 Hr Ag Figure6 12 Existing entry under Others 2 Edit the individual values as required and confirm with OK 29 0r H i Special Type of da Date Date 29 867 48 Priority 13 Figure 6 13 Individual entries Caution The date type and priority should be modified only by a fully trained person 28 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 Note Caution Wildcards 6 2 2 Adding a new entry Step 4 Procedure In the Special period field highlight the New entry option and confirm with OK Special Period Heu entry Others Figure 6 14 The New entry screen will appear Heu entry Frofile Special Type of da Da
13. light the required day and click OK to open it Day Profile Monday Tuesday Wednesday e Thursday Figure 6 3 A screen appears with a graph representing the day profile Monday Figure 6 4 Day profile PXM10 operator unit CM110397en 31 08 2004 Step Siemens Building Technologies Siemens Building Automation Procedure Click OK to open the input window Entry State Orn Delete entry Figure 6 5 Input fields for the day profile Rotate the dial to set the required time and switch status Move to the next input field by pressing OK in each case Finally confirm the inputs with OK Adding a new entry Procedure Highlight the Day Profile option and click OK to open it Scheduler Day Profile Special Period Figure 6 6 Highlight the required day and open it with OK Cay Profile Monday Tuesday Wednesday e Thursday Figure 6 7 25 34 PXM10 operator unit CM110397en 31 08 2004 A screen appears with a graph representing the day profile Monday Heu entry ee gar 42 00 2 00 Figure 6 8 Rotate the push dial until the cursor marks New entry and then define the new switching operation Entry State Orn Delete entry Figure 6 9 6 2 Special periods The Special period option is used to define individual days which deviate from those defined in the Day profile Step Procedure Highlight the Special period option and open it with OK Sc
14. st again Select the required alarm and confirm with OK Alarms D LEIT pressure monit O O1 B G IN 29 Hr B 11 32 Figure 5 8 Resetting an alarm 7 Use the push dial to select No or Yes 8 Confirm with OK to reset the alarm 9 The alarm disappears from the alarm list Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 Siemens Building Automation 6 Scheduler The Scheduler consists of a Day profile option for 7 day programs and a Special period option for exceptions e Inthe Day profile you can define switching operations to be repeated week after week e Inthe Special period menu you define individual days which deviate from those defined in the day profile Note The names and locations of these time schedules are defined on a plant specific basis The following illustrations are examples only 6 1 Day profile In the Day profile you can define separate switching periods for each day of the week which are then repeated week after week special Period Heu entry Others e Hl D 2 Figure 6 1 23 34 Siemens Building Technologies PXM10 operator unit CM110397en 31 08 2004 6 1 1 Editing an existing profile Step Procedure 1 24 34 Siemens Building Technologies Building Automation Highlight the Day Profile option and click OK to open it Scheduler Day Profile Special Period Figure 6 2 In the Day profile menu high
15. t CM110397en Siemens Building Automation 31 08 2004 Step Procedure 3 When the last value has been acknowledged the plant data screen is displayed automatically Contrast 100 High 0 Low Default 50 Time Digital display format hh mm Date Digital display format dd mm yy Event pop up Active inactive View Favorites Both Both lets you display both the Favorite objects and all the objects in the Standard user view 16 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 4 Reading and editing values 4 1 Example Setting a setpoint The screenshots below illustrate which values you can edit and which you can only read Setpolnts Actual values Get Po int f EA i E d Setpoint E 24 4 C Supply sir 31 9 C Room tenpe 16 6 L Figure 4 1 Highlighted values can be edited Figure 4 2 Outlined values are read only Step Procedure 1 Navigate to the required setpoint the relevant line is highlighted 2 Select setpoint with OK 3 A dialog box opens in which you can set the value Setpolnts Setpoint for heating Figure 4 3 Setting a manual setpoint with one input field only Settings 11 15 EE 15 Figure 4 4 Setting the time with two input fields 17 34 Siemens Building Technologies PXM10 operator unit CM110397en Siemens Building Automation 31 08 2004 Rotate the dial to set the required value in the input field Acknowled
16. t CM110397en Siemens Building Automation 31 08 2004 2 3 Display panel SIEMENS PXN10 s i 002 01 Bot U2 20 03 Figure 2 6 Opening screen The PXM10 has a five line display It can be used to view all the visible elements of a plant with values or other information Figure 2 7 shows the layout of the display The areas of the display and the symbols used are described in the next section The push dial and buttons used for navigation and editing are adjacent to the display panel set into the housing itself These buttons are described in Section 2 2 Menu line Day Profile Working area with four Monday lines of text one of Tuesday which is highlighted bednesda4 e Thursday Figure 2 7 Layout of display with one line of text highlighted 10 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 Exception Note 2 3 1 Menu line Settings Figure 2 8 Menu line The line at the top of the display shows you the menu in which you are currently located The menu line is underlined separating it from the rest of the display with a horizontal line Under Scheduler gt Special period you will see the entry Others which as a submenu is also underlined Special Period Heu entry Others ie H x Figure 2 9 Submenu 2 3 2 Working area Monday Tuesday Wednesday y Thursday Figure 2 10 Working area Below the menu line is the working area
17. te Priority 15 Figure 6 15 Open the individual entries Rotate the push dial to set the required values Move to the next input field by pressing OK in each case The profiles are defined individually at the engineering stage The date type and priority should be defined only by a fully trained person Confirm inputs with OK and use the Esc button to back out again You can use wildcards when entering the date type week amp day and the date Each wildcard represents any value in the day month or year To enter wildcards rotate the push dial anticlockwise until the wildcard stars appear Wildcards Siemens Building Technologies Siemens Building Automation 29 34 PXM10 operator unit CM110397en 31 08 2004 appear in the display panel in the form of the symbol shown to the left Example A new special period is to be defined which is to take effect on New Year s Day i e on 1 January of every year The calendar year values change annually You should therefore enter the date as follows 01 01 30 34 Siemens Building Technologies PXM10 operator unit CM110397en Building Automation 31 08 2004 7 Index Ae ME le Te EE ele EE 17 Ae ube te rase 9 Alarm EP sida 9 Alarm list BIS DA VIN EE 20 Aam po Dl e RE 19 Alarms ene Ee 21 HESSE Lee 22 Alat O eones 2h amsn ce 19 Buttons EN 8 Panting CONV CMON EE 6 COMMISSIONING ee 14 CONTAS EE 16 A A Mega 23 ENG 24 New Va EE 25 BET 0 EEE EEI NN 10 Ur
Download Pdf Manuals
Related Search
Related Contents
5 Gallon Vertical Portable Air Tank K462取扱説明書を見る Manuale d`uso User manual Zenith VCP354 VHS VCR RAVE Water Sports Equipment User Manual decima resolucion de modificaciones a las rcgmce para 2011 y sus PCG-505E - Sony Europe Final Report - EE Senior Design instructions for use bedienungsanleitung mode d'emploi Copyright © All rights reserved.