GTR-220 User manual
Contents
1. WT Sensor Brand Setting VDO 120 KD 120 WGI 900131 KP130 YB 054 KL 3967250 MHI98 SUSUKI PRO SCD User Define Description Setup water temperature sensor brand FL sensor Brand Setting FUEL_LEVEL 100 User Define Description Setup fuel sensor brand Chk Before Start Setting Disable Enable Default Enable Description Setup the system to check sensors during controller boot up Cel Or Feh Setting 0O 1 F C Default 1 Description Setup water temperature unit in Fahrenheit or Celsius P S I or Bar Setting 0 1 BAR PSD Default PSI Description Setup oil pressure unit in Bar or PSI 26 20 21 Exercise Funct Exercise Funct Setting Disable Enable Default Enable Description Activates exerciser function Date week Depend Setting 0 1 Date Week Default 0 Description Setup monthly exercise by date or week Date Set Point Setting 1 31 date Default 1 Description Setup date of monthly exercise Week Set Point Setting 0 6 week Default 1 Description Setup week of monthly exercise Hour Set Point Setting 0 23 hour Default 12 Description Setup the starting hour of the exercise Minute Set Point Setting 0 59 minute Default 0 Description Setup the starting minute of the exercise Running Inteval Setting 0 510 minute Default 4 Description Setup the duration
2. Sensors Options LFL value Alarm Setting Disable Enable Default Enable Description Activates low fuel warning L F L Set point Setting 6 55 Default 45 Default When fuel level is below setting controller displays warning message H EL Set Point Setting 35 99 Default 95 Description When fuel level is above setting controller displays warning message LOP Value Fun Setting Disable Enable Default Enable Description Activates low oil pressure warning LOP Set Point Setting 15 60 PSD Default 26 Description When oil pressure is below setting controller displays warning message HWT Value Fun Setting Disable Enable Default Enable Description Activates high water temperature protection HWT Set Point Setting 85 110 C Default 104 Description When water temperature is above setting controller displays warning message OP Escape Motor 25 10 11 12 13 14 15 Setting Disable Enable Default Enable Description Disconnect starter motor when oil pressure reaches setting Esc OP Set Point Setting 25 65 PSI Default 39 Description Disconnect starter motor when oil pressure reaches setting OP Sensor Brand Setting VDO 10 Bar KD 10 Bar YG 962 N 010 B2 KL 3967251 MHI 10 Bar DATCON 10 Bar SUSUKI 10 Bar VDO 5 Bar KP 6 Bar User Define Description Setup oil pressure sensor brand
3. 1500 5 1600 5 2000 5 2500 5 3000 5 3200 5 4000 5 5000 5 6000 5 Default 500 5 Description Setup the current transformer ratio 2 Over load Detect Setting Disable Enable Default 0 Description Activates overload protection 3 Overload Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 2 Description Setup the action when overload occurs 4 O L set point Range 1 31 0 4 5 0 A 0 8 10 0 A 1 2 15 0 A 1 6 20 0 A 2 4 30 0 A 3 2 40 0 A 4 0 50 0 A 4 8 60 0 A 5 0 75 0 A 6 4 80 0 A 8 0 100 0 A 12 0 150 0 A 16 0 200 0 A 20 0 250 0 A 24 0 300 0 A 22 32 0 400 0 A 40 0 500 0 A 48 0 600 0 A 50 0 750 0 A 64 0 800 0 A 72 0 900 0 A 20 80 0 1000 0 A 96 0 1200 0 A 120 0 1500 0 A 128 0 1600 0 A 160 0 2000 0 A 200 0 2500 0 A 240 0 3000 0 A 252 0 3200 0 A 320 0 4000 0 A 400 0 5000 0 A Description When current is above setting the controller outputs trip signal Overload Delay Setting 10 300 Second Default 260 Description When overload occurres timer starts before activating protection Short Detect Setting Disable Enable Default 0 Description Activates AC short protection Short protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 1 Description Setup the action when AC short occurs Short set point Setting 1 31 0 1
4. 460 90 23 B Ifthe engine revolution is 1500 and total count of fly wheel teeth in one second is 4437 input pulse the R P M numerator should be set to 45 and R P M denominator should be set to 133 Solution 1500 4437 0 338 The R P M calculation formula is as below R P M Input pulse revolution numerator revolution denominator 1500 4437 45 133 C If the teeth count of engine flywheel is 118 Assume the rated rpm of Gen set is 1500 rpm Then the 1500 rpm 50hz gt 30 rpms per second also generate 30 x 118 3540 electronic signals Then 1500 3540 0 423 75 177 0 423 set the R P M numerator to 75 and R P M denominator to 177 RPM Escape Motor Setting Disable Enable Description Disconnect starter motor by RPM setting RPM Esc Setpoint Setting 300 900 RPM Default 480 Description Disconnect starter motor when RPM reaches setting RPM Disp Source Setting 1 Alternator 2 Frequency Default Alternator Description Converts the RPM from frequency or alternator speed O S Detection Setting Disable Enable Default Enable Description Activates over speed protection O S Set Point Setting 1350 2100 RPM 24 19 Default 1920 Description If engine speed is higher than setting controller shuts down the engine only if over speed is enabled Over Speed Delay Setting 1 10 Second Default 4 Description When over speed occurres timer starts before activating protection
5. Type Setting NC NO Default NO Description Setup the switch type to normally close or normally open H W T Sw Delay Setting 1 9 5 Seconds Default 5 Description When high water temperature occurres timer starts before activating protection L O P Detection Setting Disable Enable Default Enable Description Activates low oil pressure protection O P switch type Setting NC NO 14 11 Default NO Description Setup the switch type to normally close or normally open L O P Sw Delay Setting 0 2 6 0 Seconds Default 3 Description When low oil pressure occurres timer starts before activating protection Auxilary Input Auto Input Delay Setting 0 2 5 Seconds Default 1 Description Time delay for AUTO start InputO Detect Setting Disable Enable Default Enable Description Activates Aux 0 function Input0 Name Setting 1 13 1 Emergency Stop 2 Over Frequency 3 Low battery Voltage 4 System Fault 5 High fuel level 6 System trip 7 Insulation fail 8 Heat Fan out 9 Pre Alarm 10 Charge fail 11 Over Load 12 Low water temperature 13 Preheat Default 7 Description Define the function for AUX 0 input In 0 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when AUX 0 activates In0 Switch Type Setting NC NO Default NO Description Setup AUX 0 to normally close or normally open Inpu
6. of each exercise Maintain Maintain Funct Setting Disable Enable Default Enable Description Activates service reminder function Maintain Protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop 27 22 23 Default 2 Description Setup the action when service reminder reaches setting Maintain Coded Setting 0 99 Default 12 Description Setup Second digit of service password Maintain Code 1 Setting 0 99 Default 15 Description Setup first digit of service password Maintain Dncount Setting 0 1275 hour Default 1200 Description Setup the duration between each service Reverse Power Reverse PowerDet Setting Disable Enable Description Activates Reverse power detection R P protect Setting 1 4 1 Warning 2 Alarm 3 Trip 4 Stop Description Setup the action when reverse power occured R P Set Point Setting 0 1084 0 KW Description Setup the reverse power upper limit Uppder limit changes with AC voltage setting and CT ratio R P Delay Setting 1 20 Seconds Description When reverse power reaches setting timer starts before activating protection OverLoad Protect Over Load Detect Setting Disable Enable Description Activates over load detection Overload protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop 28 Description Setup the action when over load occured 3 O Load Setpoint Setting 0 08 20 0 KW
7. 0 1 30 0 KW 0 1 40 0 KW 0 1 50 0 KW 0 1 60 0 KW 0 1 75 0 KW 0 1 80 0 KW 0 2 100 0 KW 0 3 150 0 KW 0 4 200 0 KW 5 0 250 0 KW 6 0 300 0 KW 8 0 400 0 KW 10 0 500 0 KW 12 0 600 0 KW 14 700 0 KW 15 0 750 0 KW 16 0 800 0 KW 18 0 900 0 KW 20 0 1000 0 KW 24 0 1200 0 KW 30 0 1500 0 KW 32 0 1600 0 KW 40 0 2000 0 KW 50 0 2500 0 KW 60 0 3000 0 KW 64 0 3200 0 KW 80 0 4000 0 KW 100 0 5000 0 KW 120 6000 KW 24 Description Setup the Earth fault amperage limit 4 Over Load Delay Setting 1 20 Seconds Description When Earth fault reaches setting timer starts before activating protection Other l Protect Pending Setting 1 30 seconds Default 10 5 Description Time delay for displaying warning or error messages after engine starts 2 Language Setting O 1 Default 1 Description Choose between English or Chinese language 3 Comm address Setting 0 255 00H FFH Default 01H Description Multiple Genset networking via RS 485 requires individual address for each controller 4 Notin AUTO Setting Disable Enable Description When GTR 220 is in OFF mode controller triggers alarm 5 Contrast Adjust Setting 1 19 Description Set the contrast of LCD screen
8. 20 0 A 0 1 30 0 A 0 1 40 0 A 0 1 50 0 A 0 1 60 0 A 0 1 75 0 A 0 1 80 0 A 0 2 100 0 A 0 3 150 0 A 0 4 200 0 A 5 0 250 0 A 6 0 300 0 A 8 0 400 0 A 10 0 500 0 A 12 0 600 0 A 14 700 0 A 15 0 750 0 A 16 0 800 0 A 18 0 900 0 A 20 0 1000 0 A 24 0 1200 0 A 30 0 1500 0 A 32 0 1600 0 A 40 0 2000 0 A 50 0 2500 0 A 60 0 3000 0 A 64 0 3200 0 A 80 0 4000 0 A 100 0 5000 0 A 120 6000 A Description When current is above the setting controller outputs trip signal 9 Short Delay Setting 0 1 1 0 Second 18 1 Default 0 4 Description When AC short occurres timer starts before activating protection RPM RPM Mul Factor Setting 1 200 Default 60 Description Please use value calculated in next parameter setting 2 RPM Div Factor 23 Setting 1 200 Default 40 Description The R P M numerator and denominator are the ratio of engine revolution versus total number of fly wheel teeth or the RPM of fly wheel versus the RPM of alternator charger For example Set up the RPM numerator and the denominator to 1 to find input pulse from the LCD A Ifthe engine revolution is 1800 and alternator revolution is 460 input pulse the R P M numerator could be set to 90 1800 20 and R P M denominator could be set to 23 460220 Solution 1800 460 3 913 The R P M calculation formula is as below R P M Input pulse RPM numerator RPM denominator 1800
9. GTR 220 User manual OJ monicon TEL 04 2238 0698 FAX 04 2238 0891 Web Site http www monicon com tw E mail sales monicon com tw 1 1 Panelidescr ptions u ai 4 A Circuit Breaker status LED cuina libido ad linda leeis eta 4 B Setup Keypad nen euer IRRE 5 Ze Operation keypads ii dns 6 I Manual 22 a Be a em c BE EEE 6 2r AUTOR en af se eh te ars Er MATRER Sd DEP tos VENEN 6 4 OS nie A A s aasan qasa seis 6 A TON 6 07 E a I LA ut t 6 3 Rear connectors E M 7 4 Wiring DIS6rant l J a uhu ea 8 MENS M M 9 6 SPO CHICA ON u u een hehe 10 Ze Engine Crank Settings sr coe a anne 12 S Engine IIR 12 9 Hour Meten A X 14 I0 Sensors Switche u naar 14 11 Auxslary Input ee eines 15 12 Aux lary Output ae 17 13 CAN BUS JI939 enc 18 14 Ereq uen ey aa q EE E E E 18 15 Battery er tpi nente da ds 20 10 AC Vollase eC M 71 sS 20 17 AC Current e a 22 IS dung SEERE 23 EAN ee RIS IO HEREIN RD NES 25 20 Exercise UDCA aoo e aS tpa e auda SEES Ve SEES RE SEES SEE SEES ESS UE TE ER EE Rape paest 27 2 21 Malntalzh h I all A A 27 22 Reverse POWE aie ec etes de aeo ricos 28 23 OverLoad Protect ss u l ee eee en sa eo neus ea aol suu Sua aUo sanc eeto eesis reseo E enden 28 24 Oth
10. att set point Setting 8 4 12 16 8 24 V Default 10 8 20 Description When battery voltage is below setting controller displays low DC volt warning H Batt Set point Setting 12 16 8 24 33 6 V Default 14 4 28 4 Description When battery voltage is above setting controller displays high DC volt warning Weak Batt Detect Setting Disable Enable Default 1 Description Activates weak battery protection W Batt Set point Setting 4 8 8 4 9 6 16 8 V Default 6 9 6 Description When battery voltage is below setting controller displays battery warning Charge failed Setting 9 6 14 4 19 2 28 8 V Default 12 6 22 6V Description When voltage is out of range controller displays charge fail AC Voltage System AC volt Setting 110 120 190 208 220 380V 440 480 660 3300 4 160 6600 7620 11400 Default 380V 20 10 Description Setup Genset AC voltage Hi ACV Detect Setting Disable Enable Default 1 Description Activates high voltage protection Hi ACV protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when high voltage occurs Hi ACV set point Setting 110 132 120 144 190 228 208 250 220 264 380 456 V Default 122 122 210 242 242 418 Description When AC voltage is above the setting the controller outputs trip signal Hi ACV Delay Setting 0 5 5 Seconds Default 1 5 Description When high voltage occ
11. ction H F set point Setting 50 60 60 72 Hz Default 55 66Hz Description When AC frequency is higher than setting controller shuts down the engine and display high frequency error if high frequency is enable Hi Freq Delay Setting 1 9 Seconds Default 2 Description When high frequency occurres timer starts before activating protection Low freq Detect Setting Disable Enable Default Enable Description Activates low frequency protection L F protection Setting 1 Warning 2 Alarm 3 Trip 4 shutdown Default 3 Description Setup the action when low frequency occurs L F set point Setting 40 50 48 60 Hz Default 45 56Hz Description When AC frequency is lower than setting controller outputs trip signal Low freq Delay Setting 1 9 seconds Default 3 Description When low frequency occurres timer starts before activating protection Mini Freq Det Setting Disable Enable Default 1 Description Activates Extreme low frequency protection M F Set Point Setting 15 30 Hz 15 16 Default 20 Description When sudden drop of frequency belows setting low frequency protection automatically disables and engine operates at idle speed Battery System DC volt Setting 12 24 V Default 24 Description Setup DC voltage in 12V or 24V Batt Fault Alarm Setting Disable Enable Default 1 Description Activates battery error protections L B
12. d 19 Short circuit 20 Low battery 17 21 High DC volt 22 Aux INO Activat 23 Aux INI Activat 24 Aux IN2 Activat 25 Aux IN3Activat 26 Sen Fault Alarm 27 HWT Value Alarm 28 LOP Value Alarm 29 LFL Value Alarm 30 HFL Value Alarm 31 System not in 32 System in AUTO AUTO 33 Manual Start 34 AUTO Start 35 Standby 36 Pre heat 37 Pre add fuel 38 Cranking 39 Crank rest 40 System in normal 41 System Alarm 42 System Trip 43 Stop inteval 44 Cooling interval 45 Reverse power Default 3 Description Setup the function for AUX output 0 Output 1 function Setting 1 45 Default 3 Description Setup the function for AUX output 1 Output 2 function Setting 1 45 Default 4 Description Setup the function for AUX output 2 Output 3 function Setting 1 45 Default 5 Description Setup the function for AUX output 3 13 CAN BUS J1939 1 J1939 Setting Disable Enable Default Enable Description Enables Canbus 2 Brand Selection Range Caterpillar Cummins Chrysler Detroit Diesel Deutz GM Isuzu Iveco JCB John Deere Logger MAN MTU Perkins Scania SISU Standard Steyer VM Volvo 14 Frequency 1 System Frequency 10 Setting 50 60 Hz Description Setup Genset frequency in 50Hz or 60Hz Hi freq Detect Setting Disable Enable Default Enable Description Activates high frequency prote
13. display Genset voltage current display KW gt KVAR gt KWH gt KVARH gt P F RPM Running hours Battery voltage display Exerciser Water temperature Oil pressure display 1024 Event log and 64 Error record B Remote access L 2 3 4 Start stop and reset Parameter settings Genset monitoring Error code access C Front panel L 2 3 4 Manual start Stop Auto ATS Mains OFF simulation Reset D Protections Engine Generator 1 High water temperature 1 Over load 2 Low oil pressure 2 Short 3 Low coolant 3 High voltage 4 Over crank 4 Low voltage 5 Over speed 5 High frequency 6 Low fuel 6 Low frequency Battery 1 Low voltage 2 High voltage 3 Charge fail 4 Under voltage E Specification DC input 8 36 VDC Power consumption Max 24 W Voltage measurement 0 500VAC 0 2 Current measurement 0 5A CT ratio 0 2 Frequency measurement 0 80 Hz 0 02 Charger or pickup voltage 5 V 70 V peak to peak Charger or pickup frequency 62 Hz 5KHz Relay output 10 A 30 VDC Output 3 Max 1A Communication protocol A Power environment Communication protocol B Modbus master Communication protocol Working temperature 10 C 60 C Dimension W H D 216mm 144 mm 89 mm Opening W H 210 mm 138 mm Weight 1 Kg 11 7 Engine Crank Settings 1 Detect Frequency Setting Disable Enable Default Enable Description Detect p
14. er A m 29 1 Panel descriptions A Circuit Breaker status LED Indication of circuit breaker status Genset Indicators When ATS transfers load from Mains to the Genset the LED turns ON if connector 26 detects signal from ATS switch 4 B Setup Keypad 8808900 1 In password entry mode this keypad represents the first digit 2 Under PARAMETER setting this keypad switches to the next parameter 1 In password entry mode this keypad represents the second digit 2 Under PARAMETER setting this keypad switches to previous parameter 1 In CODE entry mode this keypad represents the third digit 2 Under PARAMETER setting this keypad increases the setting value 1 In CODE entry mode this keypad represents the fourth digit 2 Under the PARAMETER setting mode this keypad reduces the setting value Enter or exit the parameter setting mode Confirm and save the settings These keypads alternately change the display of Genset information evenlog and error code 2 Operation keypads J Ol IN r Manual AUTO OFF RESET Preheat Event Log 1 Manual Press manual keypad for 2 seconds to start the engine Then LCD shows pre heat function after pre heat engine starts immediately If engine fails to start the GTR 220 returns to the OFF mode The pre heat state may not perform if parameter setting is O second If Pre fuel is activated the fuel outputs before crank procedure AUTO In t
15. er press reset button Trip then shut Setting Disable Enable Default Enable Description When error occurred timer starts before shutdown the engine Trip Duration Setting 30 900 Seconds Default 780 Description When error occurred RUN LED flashes and controller outputs error signal if error is not cleared within setting system initiates Genset shutdown Cooling Time Setting 0 1250 Seconds Default 310 Description Set engine cooling time for normal Genset shutdown Engine cooling time is disabled during malfunction shutdown Freq versus RPM Setting 0 200 Description To conver RPM from frequency divide RPM by frequency 1800rpm 60HZ 30 30 is the ratio for this setting Man Inst Stop Setting Disable Enable Default Enable Description Manual shutdown the Genset without cooling down the engine 9 Hour Meter 1 2 3 4 ACC Seconds Setting 0 59 Seconds Default 0 Description Set the hour meter in seconds ACC Minutes Setting 0 59 Minutes Default 0 Description Set the hour meter in minutes ACC Hour Setting 0 99 Hour Default 0 Description Set the hour meter in hours ACC 100Hour Setting 0 99 100 Default 0 Description Set the hour meter in 100 hours scale 10 Sensors Switche 1 H W T Detection Setting Disable Enable Default Enable Description Activates high water temperature protection W T Sw
16. he Auto mode the GTR 600 starts the engine by ATS signal and then the LCD shows preheat if pre heat function is enabled After pre heat the engine starts to crank If engine fails to start the system returns to the pre heat state and then start to crank the engine again For example if the conditions and parameter settings are given as follows l stop duration is 10 seconds crank attempt is 3 times The engine cranks for 10 seconds and then rest for 10 seconds after 3 attempts the LCD shows the over crank and triggers the alarm OFF Switch to OFF stops the engine and then stop appears on the LCD The idle also appears on the LCD if the idle function is enabled After 10 seconds of delay depends on the setting the engine stops completely and idle icon disappears Reset Press reset to clear error and deactivates alarm The LCD turns red when errors are detected and then stops the engine and shows the error messages on the LCD Press and hold 4 clears error and switches into OFF mode Preheat Press the keypad to manually activate the pre heat output under OFF or AUTO mode If the generator is running the pre heat function is prohibited Event Log Press to display 1024 event records 3 Rear connectors LED LED2 GEN VOLTS MAINS VOLTS CURRENT 11 12 13 Com Pin Description DESC CAE 2 Bat
17. resence of frequency before cranking the engine Detect oil press Setting Disable Enable Default Enable Description Detect presence of oil pressure before cranking the engine Crank Inteval Setting 5 40 seconds Default 10 Description Set the duration of each crank period Crank attempts Setting 1 10 Default 3 Description Set total number of crank attempts Escape Up Limit Setting 15 30 Hz Default 20 Description Frequency above setting disconnects starter motor Engage Low Limit Setting 15 30 Hz Description Frequency below setting activates crank procedure OP Build up Time Setting 0 2 2 0 Seconds Default 0 6 Description Time delay after activation of oil pressure switch before disconnecting starter motor Check oil pressure before crank must be enabled Idle Inteval Setting 0 600 Seconds Default 300 Description Duration of engine idle 8 Engine Settings 1 PreAdd Fuel Time Setting 0 0 5 0 seconds 12 Default 3 Description Activates fuel pump before initiating crank procedure Pre heat Time Setting 1 20 Seconds Default 0 Description Duration of Preheat before engine crank Energied To Stop Setting 1 30 seconds Default 10 Description Output duration for stop solenoid to shut down the engine Failed to Stop Setting 1 10 Seconds Default 4 Description Time delay before crank procedure after us
18. scription Setup the action when AUX 2 activates In 2 Switch type Setting NC NO Default NO Description Setup AUX2 to normally close or normally open 16 Input 2 delay Setting 0 2 5 0 Seconds Default 0 4 Description When AUX 2 input activates timer starts before activating protection 17 Input 3 Detect Setting Disable Enable Default Enable Description Activates Aux 3 function 18 Input 3 Name Setting 1 13 1 Low fuel 2 Over Frequency 3 Low battery Voltage 4 System Fault 5 High fuel level 6 System trip 7 Insulation fail 8 Heat Fan out 9 Pre Alarm 10 Charge fail 11 Over Load 12 Low water temperature 13 Preheat Default 8 Description Define function for AUX 3 19 In 3 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 2 Description Setup the action when AUX 3 activates 20 In 3 Switch type Setting NC NO Default NO Description Setup AUX 3 to normally close or normally open 21 Input 3 delay Setting 0 2 5 0 Seconds Default 0 4 Description When AUX 3 input activates timer starts before activating protection 12 Auxilary Output 1 Output 0 function Setting 1 45 1 All errors 2 System trip 3 Preheat 4 Idle 5 Reset 6 Main breaker ON 7 Main breaker hold 8 Genset normal 9 Engine running 10 Over crank 11 Over speed 12 Over frequency 13 Low frequency 14 Low oil 15 High water 16 High AC voltage pressure switch temperature switch 17 Low AC voltage 18 Overloa
19. t 0 delay Setting 0 2 5 0 Seconds Default 0 6 Description When AUX 0 input activates timer starts before activating protection Input 1 Detect Setting Disable Enable Default Enable 10 11 12 13 14 15 Description Activates Aux 1 function Input Name Setting 1 13 1 Battle Switch 2 Over Frequency 3 Low battery Voltage 4 System Fault 5 High fuel level 6 System trip 7 Insulation fail 8 Heat Fan out 9 Pre Alarm 10 Charge fail 11 Over Load 12 Low water temperature 13 Preheat Default 5 Description Define function for AUX 1 In1 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when AUX 0 activates In 1 Switch type Setting NC NO Default NO Description Define AUXI type to normally close or normally open Input 1 delay Setting 0 2 5 0 Seconds Default 1 0 Description When AUX 1 input activates timer starts before activating protection Input 2 Detect Setting Disable Enable Default Enable Description Activates Aux 2 function Input 2 Name Setting 1 13 1 Low coolant level 2 Over Frequency 3 Low battery Voltage 4 System Fault 5 High fuel level 6 System trip 7 Insulation fail 8 Heat Fan out 9 Pre Alarm 10 Charge fail 11 Over Load 12 Low water temperature 13 Preheat Default 3 Description Define function for AUX 2 In 2 Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 2 De
20. tery B 3 Battery B 4 Ground GND 5 Starter output Crank 6 Fuel output Fuel 7 Stop output STOP 8 User define Output 3 Out 3 9 User define Output 2 Out 2 10 User define Output 1 Out 1 11 User define Output 1 Out 1 12 User define Output 0 Out 0 13 User define Output 0 Out 0 18 User define input 4 In 4 19 User define input 3 In 3 20 User define input 2 In 2 21 User define input 1 In 1 22 ATS input ATS 23 User define input 0 In 0 Tal Rxl Tx2 Rx2 24 Low oil pressure switch L O P 25 High water temperature switch H W T 28 Pickup Pickup 29 Pickup Pickup 49 Genset CTI U Il 50 Genset CT2 V D 51 Genset CT3 W I3 52 Genset CT N COM 53 Sensor V Sensor V 54 Sensor GND Common 55 Oil Pressure sensor Oil press 56 Oil temperature sensor Oil Temp 57 Water temperature sensor Coolant Temp 58 AUX temperature sensor Auxiliary U Genset voltage U R V Genset voltage V S W Genset voltage W T N Genset voltage N N J5 1 CANBUS HI CAN H J5 2 CANBUS LOW CAN L J5 3 CANBUS GND CAN GND J5 4 RS 485 D 485 A J5 5 RS 485 D 485 B 4 Wiring Diagram 5 Dimension 81 mm 144 mm 209 mm 156 mm 216 mm 9 6 Specification A Function vonaurunn SSS Parameter settings Mains OFF warning Fuel level sensing Frequency
21. urred timer starts before activating protection Low ACV Detect Setting Disable Enable Default 1 Description Activates low voltage protection Low ACV protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when low voltage occurs Low ACV setpoint Setting 78 110 84 120 134 190 146 208 154 220 266 380 V Default 108 108 172 198 198 342 Description When AC voltage is below setting controller outputs trip signal Low ACV Delay Setting 0 5 5 Seconds Default 2 5 Description When low voltage occurred timer starts before activating protection Mini ACV Detect Setting Disable Enable Default 1 Description Activates extreme low voltage protection 21 11 Mini ACV Setpoint Setting 34 88 36 96 58 152 62 166 66 176 114 304 V Default 56 60 96 110 110 190 Description When sudden drop of AC voltage blows setting low voltage protection is disabled 12 ACV Escape Motor Setting Disable Enable Description Disconnect starter motor by Genset voltage 13 Esc ACV Setpoint Setting 44 100 48 108 76 172 84 188 88 198 152 342 V Default 72 72 124 124 132 228 Description Disconnect starter motor when AC Voltage reaches disconnection setting 17 AC Current 1 Current Ratio Range 1731 20 5 30 5 40 5 50 5 60 5 75 5 80 5 100 5 150 5 200 5 250 5 300 5 400 5 500 5 600 5 700 5 750 5 800 5 900 5 1000 5 1200 5
Download Pdf Manuals
Related Search
Related Contents
SC1602A Serial LCD Module maintenance - Polaris Brasil Kenwood KM010 BroadBand PowerShield® User Manual Documentation Direction 205 Groupe A 1600 Bedienungsanleitung FMN B122plus SC846 X9 Universal Air Shroud Users Guide_1.0.book droit et enregistrer la cible sous Princess 332771 steam cleaner Copyright © All rights reserved.