Hayward E-Command™ 4 Automation

image

Contents

1. Goldline Aqua Rite or Hayward Swimpure Chlorinator The ECOMMAND 4 can control one or more Goldline Aqua Rite or Hayward Swimpure chlorinators when additional sanitizing capacity is required A4 wire connection is used to communicate to the Aqua Rite Swimpure and can be wired up to 500 apart Any outdoor rated 4 conductor cable can be used Refer to the wiring diagrams below for proper wiring connection to the Aqua Rite Swimpure NOTE There must be only 1 primary unit All other Aqua Rite Swimpure units must be configured as second ary 4 GREEN 3 YELLOW 2 BLACK RED Jumper Removed For Secondary s Jumper Installed For Primary Factory Default Additional Aqua Rite Swimpure s if required Ecommand 4 Aqua Rite Aqua Rite or or Swimpure Swimpure Primary Secondary Primary Secondary jumper is located underneath small circuit board green GRN 49 lS GRN_ Aqua Rite YEL 3Q _ 5 VEL or black ECOMMAND 4 x 30 SEER has ene re Rep oWimpure 13 4 Configuration Setup After plumbing and wiring are complete the ECOMMAND 4 MUST BE CONFIGURED before at tempting to operate Configuration information is entered at the keypad and tells the ECOMMAND 4 what equipment is connected and how each should be controlled Accessing the Configuration Menus Configuring the ECOMMAND 4 requires that you naviga
2. 3 OUT lt e gt OUT IN gt a lt IN U LU l d l i IN OUT Common Common Pool suction and return Refer to the diagram below 2 Plumbing Spa system configuration These systems use a single filter pump and filter Pool or spa operation is controlled by two 3 way valves Faia High Voltage Relays Valve Outputs F r f Filter Pump Fmi Pool Spa Suction Sis NIS 7 Lights m Pool Spa Return Aux 1 EE Vave3 r Aux 2 m aAa COLOR WHEEL OP SOLAR TEMPERATURE SENSOR SOLAR BOOST PUMP CHECK VALVE POSS SSS SSS SSS 1 1 1 MAES CHECK 1 if optional Aqua Rite or 1 POOL SPA SUCTION VALVE HEATER SE oe ee VALVE Fiter aue G A his f CHECK VALVE an 1 prevents draining FILTER VALVE CELL SWITCH i of raised spas PUMP ry TG i RS r manuAL N NSSS ee ee eee POOL SWEEP VALV BOOST PUMP POOL SPA HEATER POOL SPA POOL VACUUM TEMPERATURE BYPASS MANUAL RETURN VALVE SENSOR VALVE VALVE VALVE i manual Two wav ly VALVE WATER ae FEATURE j L VALVE WATER ENERGY CHECI FEATURE FILTER Ptgvenis araining uM of raised spas ISOLAT
3. If applicable the homeowner will be prompted to enter separate pool and spa desired temperature settings Depending on the position of the pool spa suction valve the proper temperature setting will be used Solar Extend If Enabled the filter extend logic keeps the filter pump running beyond the normal turn off time if solar heat is still available When solar heat is no longer available both the solar valve pump and filter pump will turn off simultaneously Solar extend will NOT cause the filter pump to turn on it will only delay the turn off time when solar is operating Solar Priority If both Solar Control and Heater Control are enabled the Solar Priority feature will keep the conventional heater off whenever solar heat is available This provides the most cost effective way of heating the pool When solar heat is not available the conventional heater will operate normally 18 Allow Low Speed This menu only appears if the pool filter is configured for 2 speed or variable speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during solar heating except for the first 3 minutes after solar heat turns on Lights Config Push to access Lights options to view change_ lt gt Move to previous next configuration menu j j Rotates between Manual On Off default Countdown Timer Lights Function t
4. Manual On Off default the lights relay will alternate between turning on and off when the LIGHTS button is pressed There is no automatic control logic Countdown Timer te lights relay will turn on when the LIGHTS button is pressed The lights relay will turn off automatically after a programmed time see Timers Menu in Operation Manual The LIGHTS button can also be used to turn the output off Low Speed of a 2 speed Filter Pump the ECOMMAND 4 will turn on the lights relay whenever the low speed operation of the filter pump is required It is very important that the 2 speed filter pump option be selected under the Filter Config Menu for proper operation Timeclock the lights relay will turn on and turn off at the times set for the lights timeclock in the Timers Menu see Timers Menu in Operation Manual The LIGHTS button can also be used to turn the output on and off Solar the lights relay can operate a solar booster pump which will turn on when the filter pump is running and solar heat is available and the water is less than the desired temperature setting It is important to note that Solar Control must be enabled in the Solar Config menu for proper operation to occur 19 Super Chlorinate if Chlorinator is enabled this option allows the user to start a Super Chlorinate cycle when the Lights button is pressed rather than using the Settings Menu Note that only one button can be as
5. 6AWG for Canada wire A lug for bonding 2 for Canada is provided on the outside bottom of the ECOMMAND 4 enclosure Circuit Breaker Installation and Wiring Circuit breakers are to be supplied by the installer Refer to the circuit breaker chart below for a list of suitable circuit breakers that can be used Follow the code and the circuit breaker manufacturer s rating requirements regarding the size and temperature rating for wiring Note that some pool equipment may be required to be connected to ground fault circuit breakers check local and NEC CEC codes SUITABLE LISTED BREAKERS Tightening Manufacturer _ Single Double Twin Quad GFCB Filler Plates Tordue awnee or or or or or ot an General Purpose Outlet If desired a duplex receptacle with weatherproof cover supplied by installer may be installed in the knockouts on the lower right side of the ECOMMAND 4 enclosure Per code the receptacle should be a GFCI type Alternatively connect a standard receptacle to a GFCB ECOMMAND 4 Control Power The ECOMMAND 4 requires 120VAC 2A power to operate the control logic circuits This power should be connected to a circuit breaker rated at 125 of the intended load or the next higher size available Factory p Prewired 120 2VA Field Wired High Voltage 120 240V Pool Equipment AlLECOMMAND 4 relays are double pole they make break both legs of 240V circuits and are rated at 3HP 30A at 240V 142H
6. Lights Pump Speed This is the speed of the pump when the Lights output is on The choices are the Settings Menu speed and a speed that is unique to the Lights output only The default selection is Settings Menu This is the speed of the pump that has been selected in the Settings Menu for normal filter operation If an alternate speed is desired when the Lights output is on push or and select from Lowest to Highest in 5 increments NOTE The configuration parameters for the Aux2 output are the same as shown below for Aux Aux1 Config to view change Aux1 Function Manual On Off for manual on off countdown timer and timeclock functions Aux1 Relay Standard Push to access Aux options lt gt Move to previous next configuration menu Rotates between Manual On Off default Countdown Timer Low Speed Filter Timeclock Solar and Super Chlorinate lt gt Move to next menu item Toggle between Standard default and Dimmer lt gt Move to next menu item or previous next configuration menu for all functions except dimmer relay solar super chlorinate and low speed Aux1 Interlock Disable Toggle between Enabled and Disabled default Aux1 Interlock lt gt Move to next menu item for all functions except dimmer relay super chlorinate and low speed Aux1 Freeze Disable Toggle between Enabled default and Disabled Aux1 Freeze lt gt Move to previous next c
7. Rotates between 1 speed default 2 speed and variable speed options 1 Speed lt gt Move to next menu item if Variable Speed is selected i Lowest Speed Adjust the lowest speed desired for variable speed operation 10 lt gt Move to next menu item if Variable Speed is selected i Highest Speed Adjust the highest speed desired for variable speed operation 100 lt gt Move to next menu item Freeze Protect Toggle between Enabled default and Disabled Freeze Protection Enabled lt gt Move to next menu item or previous next configuration menu if Freeze Protect is enabled and 1 speed Filter is not selected Freeze Protect Toggle between high speed default and low speed High Speed lt gt Move to next menu item if Freeze Protect is enabled Freeze Temp Adjust the desired freeze protection temperature 33 F 42 F 38 F lt gt Move to previous next configuration menu ai Filter Pump For 2 speed pumps When a 2 speed pump is configured one of the AUX relays must also be configured to control the low speed motor winding on the pump Refer to the appropriate sections in the Installation manual for specific information regarding the control logic for 2 speed and variable speed pump operation For the Hayward Tristar variable speed pump The Filter relay is used to supply input power to the VSC pump control The relay will be on when the filter pump
8. Equipment iicsc cseciccnccnninincn 7 Low getcoucete lea a8 eeeeeeeeete remanent aren oem eee ere ee ete 8 4 Configuration Configuration BAC IN isesis esses et seusacdats assener oeiee 14 5 System Startup Before StartUp scis osiers gee eer ere tire er ean eer ret re feet S Caan oeretiee 24 and Checkout Heater Checkout isisisi iranata eee 24 Seice ModE rn ter er ne te nen nerve ee ier aE KTERE 25 6 Warranty ECOMMAND 4 Limited Warranty 2 ccccceeeeeeeeeeeeeees 28 Introduction Before You Begin What s Included Before attempting to install the ECOMMAND 4 system check that the following components have been included in the package ECOMMAND 4 Electronics Unit 3 Temperature sensors with 15 ft Sm cable hose clamp 2 Goldline GVA 24 actuators HPC 4 ACT HPC 4 ACT RC only 1 Goldline AQL2 BASE RF AQL2 SS RF remote control HPC 4 RC HPC 4 ACT RC only What s NOT Included Some of the additional items that you may need to complete an installation include Circuit breakers None are included with control see page 6 and inside of door for suitable breakers Wire 4 conductor cable electronics unit to external chlorination Wire conduit for 100A service from main panel to ECOMMAND 4 Wire conduit for filter pump and other high voltage loads Wire for bonding Miscellaneous Mounting hardware screws etc for mounting ECOMMAND 4 Valves use standard Hayward Pentair Compool or Jandy valves Additional valve actu
9. Low Speed Filter Timeclock Solar ang Super Chlorinate Manual On Off lt gt Move to next menu item for manual on off countdown timer and timeclock functions Lights Relay Toggle between Standard default and Dimmer Standard lt gt Move to next menu item or previous next configuration menu for all functions except dimmer relay solar super chlorinate and low speed Lights Interlock Toggle between Enabled and Disabled default Lights Interlock Disable lt gt Move to next menu item for all functions except dimmer relay super chlorinate and low speed f f Lights Freeze Toggle between Enabled and Disabled default Lights Freeze Disable lt gt Move to next menu item or previous next configuration menu only if filter pump is set to variable and relay type is set to standard Lights Pump Spd Select between Settings Menu default and the desired pump speed lt gt Move to previous next configuration menu Lights Function Although designated as the Lights output the function of the lights relay is similar to the aux 1 and aux2 relays If pool lights are wired to the lights relay some options including Solar function Low Speed of a 2 Speed Filter Pump Lights Interlock and Lights Freeze Protection will not be necessary and should be disabled If no pool lights are used the lights relay can be used to control other pool devices that may require these options The function of each option is shown below
10. Stripe gt Pool Spa an Drawing is for digital amp gt Air OE f Light Blue IS Solar heater If heater is a 4 gt Heater millivolt analog run red wires from Fireman s Switch to heater relay RAYPAK RP2100 STA RITE Heater 1 Turn power off to heater 2 Remove upper jacket and open the control box 3 Remove the jumper for the fireman s switch 4 Wire to the ECOMMAND 4 using wire rated for 105 C minimum Transformer Fireman s Switch _ D Operating Control zaze 8 8 S gt Pool Spa 8 I gt air S gt Solar Terminal X gt Heater Board lo S STA RITE 11 Hayward Variable Speed Filter Pump Refer to the diagram below for proper low voltage communica tion wiring between the ECOMMAND 4 and the Hayward Tristar Variable Speed Control VSC Connect screw terminals 1 to 1 2 to 2 etc VSC Use four conductor cable typically phone cable for communications connection between the VSC and the ECOMMAND 4 The maximum wiring distance is 500 feet 160 meters Note that the terminals on both the VSC interface board and the ECOMMAND 4 main board are numbered The terminal connec tions should be matched between both terminal blocks connect 1 to 1 2 to 2 etc The communications cable should be routed thr
11. correctly for remote control operation tefer to the heater manual and also Heater Control page 8 e Heater is turned on Kill Switch is in the ON position e Ifaheater bypass valve is installed check that water is flowing through the heater e The heater temperature setting is set as high as possible usually 104 F 40 C Also note that some heat pumps actually have be set to the lowest possible temperature 24 3 Once the heater is running you can verify the heater cooldown feature optional see Configuration Menu Heater Config is operating properly e Press the Filter button once for 2 speed pumps this may require 2 pushes of the Filter button e The heater should turn off Heater LED off and the Filter LED will flash to indicated heater cooldown is active e The display will periodically indicate that the filter pump is on for heater cooldown and show the minutes remaining e The pump will automatically turn off at the end of the 5 minute heater cooldown period For more detailed instructions on control and operation of the ECOMMAND 4 system refer to the Operation Manual Service Mode Service mode disables all automatic control operation and is intended to be used when servicing the pool system To enter service mode push the SERVICE button once on the main unit keypad This will initially turn all outputs off and then allow you to turn outputs on off manually a
12. position of the pool spa suction valve the proper temperature setting will be used Heater Cooldown This feature ensures that the heater cools down before water circulation is stopped When enabled the ECOMMAND 4 will continue to run the filter pump for 5 minutes after the heater turns off During this period the filter pump LED will flash and also a Heater Cooldown X XX remaining message will scroll on the display When the filter pump is running and the heater is on Pressing the Filter button once will cause the heater to turn off but the filter pump will continue to run for heater cooldown filter LED flashing and message on display Pushing the filter button a second time will override the heater cooldown operation and turn the filter pump off 17 Solar Config to view change Solar Disabled if Solar is enabled Solar Extend Disabled if Solar is enabled Solar Priority Disabled if Solar is enabled and Heater Extend If Enabled the filter extend logic keeps the filter pump running beyond the normal turn off time until the pool or spa is heated up to the desired temperature setting see Settings Menu Heater extend will NOT cause the filter pump to turn on it will only delay the turn off time when the heater is operating Allow Low Speed This menu only appears if the filter is configured for 2 speed or variable speed operation During default operation high speed mode is us
13. previous next configuration menu Pool Spa Setup If Pool Only or Spa Only are selected then the pool spa valves are not needed and pushing the POOL SPA button on the display keypad will have no effect If Pool and Spa is selected then the pool spa suction and return valve actuators should be connected to the ECOMMAND 4 Pressing the POOL SPA button on the display keypad will allow the homeowner to alternate between pool and spa operation For more information on Pool and Spa refer to the Plumbing section on pages 8 Spa CountDn This menu will appear only if Pool Spa Setup is set to Pool and Spa This setting is the time after you manually switch the Pool Spa valves to Spa Only until the ECOMMAND 4 automatically returns the valves to their previous positions It is programmed in increments of 5 minutes from Manual On Off 0 minutes to 21 00 21 hours The filter is forced on during this time period Spa Spillover When spa spillover is Enabled and Pool and Spa the homeowner will be able to rotate through Pool Only both suction and return valves switched to pool Spa Only both suction and return valves switched to spa and Spillover suction valve switched to pool and return valve switched to spa by successive presses of the Pool Spa button Filter Operation If Spa Spillover is selected the ECOMMAND 4 will automatically switch the pool sp
14. the solar panels to be purged Interlock is not available for solar or super chlorinate Valve3 Freeze Protection This function protects the pool and plumbed equipment against freeze damage If Freeze Protection is enabled and the AIR temperature falls sensor falls below the selected freeze temperature threshold the ECOMMAND 4 will turn on the valve to allow circulation of the water IMPORTANT this only enables operation of the valve3 output during freeze see the Filter Pump Config menu to enable freeze protection for the main circulation system 22 All Timeclocks 7 da Units F and PPM Time Format 12 hour AM PM Reset Config to Valve3 Pump Speed This is the speed of the pump when the Valve3 output is on The choices are the Settings Menu speed and a speed that is unique to the Valve3 output only The default selection is Settings Menu This is the speed of the pump that has been selected in the Settings Menu for normal filter operation If an alternate speed is desired when the Valve3 output is on push or and select from Lowest to Highest in 5 increments Toggle between 7 day default and Weekend Weekday time options lt gt Move to previous next configuration menu This selection affects ALL of the timeclock logic in the ECOMMAND 4 If 7 day is selected each timeclock will have one set of turn on turn off settings that operate every day of the week If Weekend Weekday
15. ACT RC The ECOMMAND 4 is compatible with AQL2 SS RF wireless remote control only The AQL2 SS RF is a waterproof portable remote control that is designed to be used in and around the pool spa area The AQL2 SS RF floats and can be left in the water for easy access A single AQL2 BASE RF Base Station must be installed on the ECOMMAND 4 in order to use this remote control The maximum distance between the wireless remote and the base station on the ECOMMAND 4 main control unit is 400 feet 120m line of sight or 200 feet 60m through walls etc Ifin doubt about the distance test operation before installing the remote All wireless models require the user to run the Teach Wireless routine in the Settings Menu This information can be found in the ECOMMAND 4 Operation Manual Optional Base Station included with HPC 4 RC HPC 4 ACT RC The AQL2 BASE RF optional base station must be installed if the AQL2 SS RF is used To install the base station remove the knockout on the upper left side of the ECOMMAND 4 main control unit insert the base station and then tighten the nut from the inside Also refer to the Base Station manual and the diagram on page 13 Optional Valve Actuators included with HPC 4 ACT HPC 4 ACT RC For optional actuators used with the ECOMMAND 4 note that the internal cams in the actuator may also have to be adjusted depending on the way the actuator is mounted on the valve and the desired valve action RETURN SUCTION
16. E FOR ANY CONSEQUENTIAL SPECIAL OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER INCLUDING BUT NOT LIMITED TO PERSONAL INJURY PROPERTY DAMAGE DAMAGE TO OR LOSS OF EQUIPMENT LOST PROFITS OR REVENUE COSTS OF RENTING REPLACEMENTS AND OTHER ADDITIONAL EXPENSES EVEN IF THE SELLER HAD BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES SOME STATES DO NOT ALLOW THE EXCLUSION OF LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU NO WHOLESALER AGENT DEALER CONTRACTOR OR OTHER PERSON IS AUTHORIZED TO GIVE ANY WARRANTY ON BEHALF OF GOLDLINE THIS WARRANTY IS VOID IF THE PRODUCT HAS BEEN ALTERED IN ANY WAY AFTER LEAVING THE FACTORY 28 ECOMMAND 4 Programming Flow Chart default menu day and time water temperature air temperature chlorinator settin E denotes conditional items salt level reason pump is running not scheduled reason hi speed is running not scheduled countdown time remaining heater control status system manual off check system error filter speed settings menu spa heater1 temperature pool heater1 temperature spa solar temperature pool solar temperature superchlorinate spa chlorinator setting pool chlorinator setting spa high low speed pool high low speed day and time backlit display light beeper teach wireless remote wireless channel timersmenu__ pool filter pump1 or hi speed pool fil
17. ED WATER FEATURE IN FLOOR oS H CLEANER POP UP M SKIM OVERFLOW RETURN j SPILLOVER JET VALVE PUMP WATER WATER e POOL mon FEATURE FEATURE MAIN POP UP DRAIN enery Q Q O SUCTION SAVER NON BOOST CLEANER PRESSURE e PRESSURE PRESSURE CLEANER POP UP CLEANER CLEANER Some important notes regarding the ECOMMAND 4 control of Standard Pool Spa systems In Pool Spa Config select 1 2 3 The ECOMMAND 4 can be programmed to accommodate spa spillover if desired A conventional heater gas or heat pump and solar can be used to heat both the pool and the spa If the chlorinator cell is plumbed prior to the pool spa return valve then both the pool and the spa can be chlorinated only when optional external chlorination is used The water sensor should be installed prior to any heater or solar and will display either the pool or the spa temperature depending on the current operation of the pool The temperature will only be displayed when the filter pump is running If any water feature or pressure side cleaner boost pumps are used be sure to enable the interlock feature see Configuration Menu for details to ensure that the pumps operate only when the filter pump is on and the system is in the pool only operating mode The plumbing diagram above is intended to be used as a general guideline and is not a complete plumbing schematic for the pool The air sensor must be installed if the freeze protection feat
18. Hayward ECOMMAND 4 Automation Installation Manual for models HPC 4 HPC 4 ACT HPC 4 RC HPC 4 ACT RC HAYWARD Poo Products One Source ver y pool www haywardnet com IMPORTANT SAFETY INSTRUCTIONS When using this electrical equipment basic safety precautions should always be followed including the following READ AND FOLLOW ALL INSTRUCTIONS N WARNING Disconnect all AC power during installation N WARNING Water in excess of 100 degrees Fahrenheit may be hazardous to your health N WARNING To reduce the risk of injury do not permit children to use this product unless they are closely supervised at all times A green colored terminal marked Earth Ground is located inside the wiring compartment To reduce the risk of electric shock this terminal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment A wire connector is provided on this unit to connect a minimum 8 AWG 8 4 mm2 solid copper conductor between this unit and any metal equipment metal enclosures of electrical equipment metal water pipe or conduit within 5 feet 1 5m of the unit to connect the equipment assembly or spa to a circuit protected by a ground fault circuit interrupter One bonding lug for US models two for Canadian models is provided on the external surface To reduce the risk
19. P 30A at 120V Refer to the diagram below for typical relay wiring I ce A 2 P m VAC O 120 VAC 120 VAC Load Load Load Wiring relays for 240 VAC Wiring relays for 120 VAC Wiring GFCB for 120 VAC Pool Equipment Pool Equipment Pool Equipment G warnina Do not use the ECOMMAND 4 to control an automatic pool cover wimmers may become entrapped underneath the cover Two speed filter pump Requires 2 relays FILTER plus one of the AUX relays for proper operation of both speeds IMPORTANT Be sure to follow the wiring diagram below AND to configure the control logic according to the instructions on page 14 Lo Speed 2 Speed Hi Speed f Common Filter Ground Pump S S 16 S Lights A ground fault circuit breaker must be used to supply power for high voltage pool spa lighting Low voltage lights will require an external transformer For lighting systems that have both a light source and color wheel connect the light source to the Lights relay a
20. a suction and return valves to spillover at the start of the programmed pool filtering time period or when the super chlorinate function is turned on The valves will remain in this position for the remainder of the super chlorinate period This option is usually preferable because both the pool and spa water will be filtered and sanitized 15 If Pool Only is selected then the ECOMMAND 4 will switch the pool spa valves to the pool only position at the start of the programmed pool filtering time period or when the super chlorinate function is turned on This may be desirable on some systems with in floor cleaners because it allows the cleaner to operate all the time the pool is being filtered and or the super chlorinate is running V1 Aux1 V2 Aux2 This menu appears only if the Pool Spa Setup is Pool Only or Spa Only When enabled Valve 1 return will follow the Aux output and Valve 2 suction will follow the Aux2 output When disabled default the return and suction pool spa valves function normally Filter Off Valve Change This menu appears only if Pool Spa setup is set to Pool and Spa Std When enabled default the filter pump will shut off for 35 seconds whenever the Pool Spa valves are turning The pump will NOT shut off when a heater is in Heater Cooldown mode Filter Config Push to access pump options to view change _ lt gt Move to previous next configuration menu Filter Pump 4
21. ard Valve3 Pump Spd Select between Settings Menu default and the desired pump speed Settings Menu lt gt Move to previous next configuration menu Valve3 Function Timeclock default the valve turns on off at the times set for the valve3 timeclock in the Timers Menu see Operations Manual Solar the valve operates when the filter pump is running and solar heat is available and the water is less than the desired temperature setting Solar heating must be enabled in the Solar Config menu for proper operation to occur In Floor Cleaner the valve switches the water returning to the pool between the in floor cleaner and the normal return jets which facilitate efficient surface skimming The valve will operate the in floor cleaner for the first half of each clock hour and then switch to the jets skimming for the last half of the hour Valve3 Filter the valve operates whenever the Filter relay is on Valve3 Lights the valve operates whenever the Lights relay is on Valve3 Aux1 the valve operates whenever the Aux relay is on Valve3 Aux2 the valve operates whenever the Aux relay is on Valve3 Interlock If Enabled this feature will override the function timeclock or in floor cleaner selected above and turn the valve off when the filter pump is off first 3 minutes of filter pump operation allows the pump to prime and get water flowing or for the first 3 minutes after solar turns on allows air in
22. ators Accessory Products Order Separately AQL2 SS RF Wireless Spa Side Remote Control Included with HPC 4 RC HPC 4 ACT RC AQL2 BASE RF Base Station required if using AQL2 SS RF Included with HPC 4 RC HPC 4 ACT RC AQL DIM Light Dimmer Relay GVA 24 Valve Actuator V amp A xx Valve amp Actuator xx 1P 1 5 pos seal 2P 2 pos seal Included with HPC 4 ACT HPC 4 ACT RC Installation Steps Details on each installation step are presented on the following pages 1 Mounting the equipment page 2 ECOMMAND 4 main unit High Voltage pool equipment Temperature sensors Low voltage wiring temperature sen Optional Remote Control sors heater etc Optional Base Station Valve actuators if applicable 4 ECOMMAND 4 configuration page 14 2 Plumbing page 4 5 System Startup and checkout page 24 General Pool Equipment 3 Electrical Wiring page 6 Main service Grounding and bonding Circuit breakers ECOMMAND 4 control power 1 Mounting the Equipment ECOMMAND 4 Control Center The ECOMMAND 4 is contained in a raintight enclosure that is suitable for outdoor mounting The control must be mounted a minimum of 5 ft 2 meters horizontal distance from the pool spa or more if local codes require The Control Center is designed to mount vertically on a flat surface with the knock outs facing downward Because the enclosure also acts as a heat sink disperses heat from inside the box it is important not to b
23. ed whenever the heater is on If Allow Low Speed is enabled low speed will be allowed even if the heater is on Push to access solar options lt gt Move to previous next configuration menu Toggle between Enabled and Disabled default Solar lt gt Move to next menu item or previous next configuration menu Toggle between Enabled and Disabled default Solar Extend lt gt Move to next menu item Toggle between Enabled and Disabled default Solar Priority lt gt Move to next menu item 1 speed Filter is not selected Allow Low Speed Disabled Toggle between Enabled and Disabled default lt gt Move to next menu item or previous next configuration menu Solar If the solar control logic is Enabled several additional steps must be taken to ensure proper operation of the solar system If the solar is operated by a valve then the Valve3 output must be setup for solar logic page 22 If the solar is operated by a pump then one of the AUX relays must be set up for solar logic page 20 Also the solar temperature sensor must be installed This sensor is typically mounted near the collector array and is used to sense whether sufficient solar heat is available If solar is Enabled the valve or solar pump relay will turn on when the water temperature is less than the desired temperature setting AND the solar sensor is hotter than the water The desired temperature is in the Settings Menu
24. enu in the Operation manual If disabled default all displays relating to the chlorinator will be suppressed When the chlorinator is enabled the ECOMMAND 4 will automatically detect and control any Aqua Rite Swimpure s that is installed in the system see page 13 Display Allows for the display of salt default or mineral values 14 Pool Spa Config Push to access Pool Spa options to view change _ lt gt Move to previous next configuration menu Pool Spa Setup otas pemeen Pool Only default Spa Only and Pool and Spa lt gt Move to next menu item if Pool and Spa is selected Spa CountDn Adjust time setting Manual On Off 0 05 0 10 0 15 default is 4 00 00 30 lt gt Move to next menu item if Pool and Spa is selected Spa Spillover Toggle between Enabled and Disabled default Spa Spillover Enabled lt gt Move to next menu item or previous next configuration menu if Pool and Spa is selected and if Spa Spillover is enabled Filter Operation Toggle between Pool Only default and Spa Spillover options Spa Spillover lt gt Move to previous next configuration menu if Pool Only or Spa Only is selected V1 Aux1 V2 Aux2 Toggle between Enabled and Disabled default Disabled lt gt Move to previous next configuration menu if Pool and Spa is selected Filter Off Valve Toggle between Enabled default and Disabled Change Enabled _ lt gt Move to
25. h Thermostat 1L Heater Ignition Valve Laars Heaters 1 Turn power off to heater 2 Remove factory jumper from terminal block 3 Wire ECOMMAND 4 to the heater as shown 4 Ensure toggle switch is in the ON position 5 Set heater thermostats to maximum position N to limit switches 8 8 remove jumper 8 gt Poovspa S ai C gt Solar white gt Heater A 5 e Y white oO gt o Oo Fusible Link Hayward Heaters Refer to the instructions in the heater manual for 2 wire Remote Thermostat operation under Remote Control Connections and the diagram below 1 Turn off power to heater 2 Wire ECOMMAND 4 to terminals 1 amp 2 see diagram 3 Leave jumper attached to terminals 4 amp 5 4 Move BYPASS dipswitch on heater circuit board to ON position up 5 Turn heater power back on 6 Switch heater to either Pool or Spa it doesn t make any difference which is selected the ECOMMAND 4 will take control 7 Heater display should be bO for bypass On 8 Heater will fire whenever ECOMMAND 4 requests when ECOMMAND 4 Heater LED is illumi nated Dipswitch located on heater R circuit board S gt Poovspa gt Air gt Solar PK fo gt Heater w R A BK L R Do not remove jumper Terminal block located at electrical junction bo
26. lock the four sides of the control Do not mount the ECOMMAND 4 inside a panel or tightly enclosed area When selecting a location note that the standard cables supplied with the temperature sensors and valve actuators if applicable are all 15 ft Sm long Temperature Sensors Three sensors are included with the ECOMMAND 4 A water sensor and an air sensor must be installed at all times for proper operation A solar sensor is required if the solar function is enabled Water Sensor This sensor is used to measure the pool spa temperature and is installed in the filtration plumbing after the filter but before either the solar or conventionally fueled heaters refer to the plumbing overview diagram 1 Drill a 3 8 10mm diameter hole in the PVC piping and remove all chips and burrs 2 Insert sensor until O ring collar sits flush on the hole 3 Position hose clamp over the sensor and gently tighten until O ring makes an adequate seal Do not overtighten 4 For maximum temperature accuracy cover the sensor and 3 6cm of pipe on either side with insulation and white paint Air Sensor Mount the air sensor outdoors AN IMPORTANT Mount the air sensor out of direct sunlight Solar Sensor For solar applications mount the sensor near the solar collector array so that it is exposed to the same sunlight as the collectors Use additional cable 20 AWG if necessary Optional AQL2 SS RF Remote Control included with HPC 4 RC HPC 4
27. mming flow chart on the back cover of this manual for a listing of the available menus and the items included in each menu Settings Menu Heater and or solar thermostat settings Chlorinator settings if applicable Day and Time Timers Menu Timeclock and or Countdown timer settings Heater Checkout Follow these instructions to verify that the ECOMMAND 4 is properly controlling the heater 1 Check that the ECOMMAND 4 is calling for the heater to turn on as indicated by the Heater LED being illuminated If the Heater LED is illuminated go directly to step 2 if not then check the follow ing e The heater is enabled Configuration Menu Heater Config e The heater temperature setting is at least 2 F greater than the water temperature Settings Menu Pool Heater amp Spa Heater e The filter pump is running e Ifthe pool has solar heat and the solar priority feature is enabled Configuration Menu Solar Config then solar must be off in order for the heater to fire The easiest way to force solar off is to go to the Settings Menu Pool Solar amp Spa Solar and temporarily lower the temperature settings below the current water temperature 2 Check that the heater is running If not then check e Power is supplied to the heater e The ECOMMAND 4 control output is properly connected to the heater control see Heater Control wiring page 8 e Some heaters also have internal switches or jumpers that have to be set
28. n at during freeze protection operation Select high default or low speed operation Freeze Protection Temperature Select the temperature to be used for freeze protection Temperature is adjustable from 33 F 42 F 1 C 6 C 38 F 3 C is default This threshold will be used for all outputs that have freeze protection enabled Heater1 Config Push to access heater options to view change_ lt gt Move to previous next configuration menu Toggle between Enabled and Disabled default Heater 1 Disable lt gt Move to next menu item or previous next configuration menu if Heater1 is enabled Heater1 Cooldown Toggle between Enabled and Disabled default Heater 1 Cooldown Disabled lt gt Move to next menu item if Heater1 is enabled Heater1 Extend Toggle between Enabled and Disabled default Heater 1 Extend Disabled lt gt Move to previous next configuration menu if Heater1 is enabled and 1 speed filter pump is not selected Toggle between Enabled and Disabled default Disabled lt gt Move to next menu item or previous next configuration menu Heater1 If the heater is Enabled the heater relay will turn on when the water temperature is less than the desired temperature setting and the filter pump is running The desired temperature is in the Settings Menu If applicable the homeowner will be prompted to enter separate pool and spa settings Depending on the
29. nd then connect the color wheel to one of the AUX outputs Hayward Variable Speed Filter Pump Proper installation of the Hayward TriStar Variable Speed Control VSC includes high voltage input wiring communication wiring and menu configuration settings Refer to the following diagram for proper input wiring to the VSC Wiring from the 220V breaker must connect through the ECOMMAND 4 s Filter relay The Filter relay is used to supply input power to the VSC pump control The relay will be on when the filter pump output is on When the filter pump output is off the relay will be off Note that when the filter pump relay is off power off to the VSC the ECOMMAND 4 will not display errors or diagnostics for the pump The filter pump relay must be on for diagnostic function 220 VAC input power to VSC Low Voltage Wiring Valve Actuators The ECOMMAND 4 can control up to three automatic valve actuators Two of the valve outputs are dedicated to the pool spa suction Valve2 and return Valve1 valves Valve3 is for general purpose use solar water feature in floor cleaner etc For installations with solar heating Goldline offers the AQ SOL KIT xx solar kit that contains a valve actuator and extra temperature sensor The xx indicates the valve type from the 3 choices below 1P 1 5 Positive Seal 2P 2 Positive Seal The ECOMMAND 4 is compatible with standard valve actuator
30. of electric shock connect the local common bonding grid in the area of the swimming pool spa or hot tub to these terminals with an insulated or bare copper conductor not smaller than 8 AWG US 6 AWG Canada e All field installed metal components such as rails ladders drains or other similar hardware within 3 meters of the pool spa or hot tub shall be bonded to the equipment grounding bus with copper conductors not smaller than 8 AWG US 6 AWG Canada SAVE THESE INSTRUCTIONS Table of Contents Introduction Before You a c eeeremeter artnet erediens en eeina keat 1 Installation Steps mere nae nner tore ener enr nent eure nn Sehr eran err 1 1 Mounting EGOMMAND 4 Control Cente tigecescivesiesaeere mie meterennss 2 Equipment Temperature SSIS OS ec cec ras tea cecccsceccecst ais cheese aeaec pacts eaeedeteks 2 Optional Wireless Remote Conttrol ccceceeeeeeeeees 2 Optional Base Slant axsscatitscepcvasieseceresciacaapivteaceiseeeeeetend 3 Optional Valve ACUAIONS cess oncesieseesesvesciurettvectiiteieeccrinelaucne 3 2 Plumbing Pl mbingConfig ratoi sosisini ve sauceezttxeciclaceacatiateuetenens 4 3 Electrical Mam SUI Sah ens case eenei aeaa eae eek ete 5 Wiring Groundingiand Bonding sereisas 5 Circuit Breaker Installation and Wiring cccseeeeeeees 6 General Purpose OUM Sinn cicsacceckeic ci netmepeceeueital 6 ECOMMAND 4 Control PoWel c cecceeseeeeeesseseeeeeeees 6 High Voltage Pool
31. oldline authorized warranty service center For more information on authorized service centers please contact the Hayward Goldline Technical Service Support Center 61 Whitecap Road North Kingstown RI 02852 or visit the Goldline web site www goldlinecontrols com WARRANTY EXCLUSIONS 1 Material supplied or workmanship performed by others in process of installation Damage resulting from improper installation including installation on pools larger than the product rating Problems resulting from failure to install operate or maintain the product s in accordance with the recommendations contained in the owners manual s Problems resulting from failure to maintain pool water chemistry in accordance with the recommendations in the owners manual s Problems resulting from tampering accident abuse negligence unauthorized repairs or alternations fire flood lightning freezing external water degradation of natural stone used in or immediately adjacent to a pool or spa war or acts of God DISCLAIMER THE EXPRESS LIMITED WARRANTY ABOVE CONSTITUTES THE ENTIRE WARRANTY OF GOLDLINE WITH RESPECT TO ITS POOLAUTOMATION AND CHLORINATION PRODUCTS AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE IN NO EVENT SHALL GOLDLINE BE RESPONSIBL
32. onfiguration menu only if filter pump is set to variable and relay type is set to standard Aux1 Pump Spd Settings Menu J gt Select between Settings Menu default and the desired pump speed lt gt Move to previous next configuration menu WARNING Do not use the ECOMMAND 4 to control an automatic pool cover wimmers may become entrapped underneath the cover 20 Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed There is no automatic control logic Countdown Timer the aux relay will turn on when the AUX button is pressed and then will turn off automatically after a programmed time see Timers Menu Operation Manual The AUX button can also be used to turn the output off Low Speed of a 2 speed Filter Pump the ECOMMAND 4 will operate the aux relay whenever the low speed operation of the filter pump is required It is very important that the 2 speed filter pump option be selected under the Filter Config Menu for proper operation Timeclock the aux relay will turn on and turn off at the times set for the aux timeclock in the Timers Menu The AUX button can also be used to turn the output on and off Solar the aux relay operates a solar booster pump which will turn on when the filter pump is running and solar heat is available and the water is less than the desired temperature setting It is important to note that Sola
33. ough the knockout hole on the left side of the VSC enclosure and a watertight fitting should be used to keep water and debris out of the opening The communications cable should also be routed away from the ECOMMAND 4 and VSC power connections if possible VSC Pump Address Setting The VSC address must be set to 001 when using the VSC with the ECOMMAND 4 Refer to the TriStar Pump Owner s Manual IS3220VSC and Hayward document IS3220VSCAQLL for specific instruc tions on setting the pump address Temperature Sensors The ECOMMAND 4 utilizes 10K ohm thermistor type sensors Three sensors water temperature air temperature and solar temperature are included If the ECOMMAND 4 is being used to control a solar heating system the solar sensor is required The sensors are provided with a 15 ft cable If a longer cable is required contact the Goldline service dept for information on suitable cable types and splices See page 6 and the diagram below for installation information POOL SPA SENSOR AIR gt Pool Spa SENSOR oe gt Solar SOLAR SPA A D SENSOR y e e gt 12 Base Station Plug in the pigtail connector from the wireless base station into the wireless connector on the main PCB inthe ECOMMAND 4 control unit Connector for Base Receiver AQL2 BASE RF Base Receiver Main PCB Tighten nut
34. output is on When the filter pump output is off the relay will be off On off and speed is controlled by commands sent to the pump Lowest Speed This is the lowest speed that the variable speed pump is allowed to run at It is used as the lower limit in the Low Speed Settings Menu Set lowest speed from 10 default to 50 16 Highest Speed This is the highest speed that the variable speed pump is allowed to run at It is used as the upper limit in the High Speed Settings Menu Also this is the speed that the pump will run at during the first 3 minutes of operation anytime the pump has been off for more than 30 seconds Set highest speed from 20 to 100 default Freeze Protection Freeze protection is used to protect the pool and plumbed equipment against freeze damage If freeze protection is enabled and the AIR temperature sensor falls below the freeze threshold see below the ECOMMAND 4 will turn on the filter pump to circulate the water If Pool and Spa is selected in the Pool Spa sub menu see page 22 the valves will also alternate between the pool and spa every 30 minutes and the filter pump will turn off while the valves are turning The chlorinator will not operate if freeze protection is the only reason the pump is running Freeze Protection Speed This menu only appears if freeze protection is enabled and the pump is configured for 2 speed or variable speed pump operation This is the speed that the pump will ru
35. perature sensor falls below the selected freeze temperature threshold the ECOMMAND 4 will turn on the aux relay to circulate the water IMPORTANT this only enables operation of the AUX output during freeze see the Filter Pump Config menu to enable freeze protection for the main circulation system Aux1 Pump Speed This is the speed of the pump when the Aux output is on The choices are the Settings Menu speed and a speed that is unique to the Aux output only The default selection is Settings Menu This is the speed of the pump that has been selected in the Settings Menu for normal filter operation If an alternate speed is desired when the Aux output is on push or and select from Lowest to Highest in 5 increments 21 Valve3 Config Push to access Valve3 options to view change J lt gt Move to previous next configuration menu i Rotates between Timeclock default Solar In floor Cleaner AANEREN Filter Lights Auxt and ies plai lt gt Move to next menu item for all functions except solar and super chlorinate Valve3 Interlock Toggle between Enabled and Disabled default Valve3 Interlock Disabled lt gt Move to next menu item for all functions except super chlorinate Valve3 Freeze Toggle between Enabled and Disabled default Valve3 Freeze Disabled lt gt Move to previous next configuration menu only if filter pump is set to variable and relay type is set to stand
36. r Control must be enabled in the Solar Config menu for proper operation to occur Super Chlorinate if Chlorinator is enabled this option allows the user to start a Super Chlorinate cycle when the Aux button is pressed rather than using the Settings Menu Note that only one button can be assigned to this function Aux1 Relay This feature allows the user to select either Standard default or Dimmer type relay for the Aux output The optional AQL DIM dimmer kit must be installed if Dimmer is desired When Dimmer is selected and the Aux output is manually turned on the and buttons adjust the level from 20 to 100 default The level is saved for the next time the aux output is turned from off to on Aux1 Interlock If Enabled this feature will override the function Manual On Off Countdown Timer Timeclock selected above and turn the aux off when filter pump is off first 3 minutes of filter pump operation allows the pump to prime and get water flowing when the pool spa suction return valves are in any position other than pool only or for the first 3 minutes after solar turns on allows air in the solar panels to be purged Interlock is not available for solar low speed filter pump super chlorinate or dimmer Aux1 Freeze Protection This function protects the pool plumbing and equipment against freeze damage If Freeze Protection is enabled and the AIR tem
37. s option is selected then the user can enter one set of turn on turn off times for the weekend fixed as Saturday Sunday and another set of turn on turn off times for weekdays Monday through Friday Toggle between 12 hour AM PM default and 24 hour time format options lt gt Move to previous next configuration menu Toggle between F and PPM default and C and g L Metric options lt gt Move to previous next configuration menu Initiate reset of all configuration parameters Default __ Press J lt gt Move to previous next configuration menu config not reset Are you sure to proceed Config reset Confirmed Reset all configuration parameters lt gt Move to previous next menu config not reset lt gt Move to previous next configuration menu Use this function to erase all previous system configuration and reset all configuration parameters back to the factory default values This function is NOT reversible be careful 23 5 System Startup and Checkout Before Startup Before starting the ECOMMAND 4 for the first time be sure that the following items have been com pleted 1 Properly rated circuit breakers are installed in the ECOMMAND 4 subpanel 2 All wiring is performed according to NEC and local codes 3 The ECOMMAND 4 is properly grounded and bonded 4 The ECOMMAND 4 is properly configured to control all desired functions Program Automatic Operation Refer to the progra
38. s manufactured by Hayward Pentair Compool and Jandy See diagram on page 5 for the location of valve connectors Heater Control The ECOMMAND 4 provides a set of low voltage dry contacts that can be connected to most gas heaters or heat pumps with 24V control circuits Refer to the diagram on the following page for a generic connection The manuals supplied with most heaters also include specific wiring instructions for connecting the heater to an external control usually identified as 2 wire remote control For millivolt or line voltage heaters contact Goldline Tech support 908 355 7995 Refer to the diagrams and the information on the following pages for more details on the connection to several popular heaters Generic Heaters 1 Wire heater to 120 240V power source per the instructions in the heater manual The ECOMMAND 4 does NOT control the power going to the heater 2 Wire the ECOMMAND 4 dry contact heater output per the diagram below Many internal parts of the heater can get very hot see the heater manufacturer s recommendations on the minimum temperature rating for wires If no guidance is given use 105 C rated wire Set any ON OFF switch on the heater to ON 4 Set the thermostat s on the heater to the maximum hottest setting nad N S 8 gt Pool Spa Ts C _ S gt Solar I gt Heater gt A e D Y amp Kill Switc
39. signed to this function Lights Relay This feature allows the user to select either Standard default or Dimmer type relay for the Lights output The optional AQL DIM dimmer kit must be installed if Dimmer is desired When Dimmer is selected and the Lights output is manually turned on the and buttons adjust the level from 20 to 100 default The level is saved for the next time the lights are turned from off to on Lights Interlock If enabled this feature will override the function Manual On Off Countdown Timer Timeclock selected above and turn the lights relay off when filter pump is off first 3 minutes of filter pump operation allows the pump to prime and get water flowing when the pool spa suction return valves are in any position other than pool only or for the first 3 minutes after solar turns on allows air in the solar panels to be purged Interlock is not available for solar low speed filter pump super chlorinate or dimmer Lights Freeze Protection This function helps protect equipment that is wired to the lights relay against freeze damage If Freeze Protection is enabled and the AIR temperature sensor falls below the selected freeze temperature threshold the ECOMMAND 4 will energize the lights relay IMPORTANT this only enables operation of the lights relay during freeze see the Filter Pump Config menu to enable freeze protection for the main circulation system
40. t the main display only In service mode the buttons on the optional spa side remote will turn outputs off but will not turn any output on Heater control outputs and solar control outputs are prevented from turning on if the water temperature exceeds 104 F 40 C Pushing the SERVICE button again will enter a timed service mode Service operation as described above will continue for 3 hours then automatically return to normal operation Push the SERVICE button once more to exit out of Service mode 25 26 27 LIMITED WARRANTY effective 01 01 09 Goldline warrants its Aqua Rite Aqua Rite Pro Aqua Logic Pro Logic and E Command products to be free of defects in materials and workmanship under normal use and service for a period of three 3 years This warranty is applicable from the initial date of installation on private residential swimming pools in the US and Canada The warranty is not transferable and applies to the original owner only Aqua Trol commercial installations installations outside of the US and Canada accessory products and replacement parts are covered under the terms of the warranty for a period of one 1 year Proof of purchase is required for warranty service If written proof of purchase is not provided the manufacturing date code will be the sole determinant of the date of installation of the product To obtain warranty service or repair please contact the place of purchase or the nearest G
41. te through the Configuration Menu and input various information For more detailed information about using the ECOMMAND 4 menu system refer to the Operation Manual To access the Configuration Menu Press repeatedly until Configuration Menu is displayed Menu Locked lt gt Press BOTH buttons SIMULTANEOUSLY for 5 seconds to unlock Configuration Men ocd lt gt Move to configuration menu items NOTE The configuration menu automatically locks after 2 minutes of no buttons being pressed to prevent unauthorized people from changing the control logic inadvertently and possibly damaging the pool equipment or causing a call back to fix the configuration Configuration Menu Items Each item needs to be programmed and may contain additional sub menu items Refer to the following pages for information on programming Chlor Config Push to access Chlorinator option to view change_ lt gt Move to next configuration menu Ext Chlorinator Toggle between External Chlorinator Enabled and Disabled default Enabled lt gt Move to next menu item Display Toggle between Display Salt default and Minerals Salt lt gt Move to previous next configuration menu Chlorinator If the optional external chlorinator is enabled requires the use of a Goldline Aqua Rite or Hayward Swimpure chlorinator the ECOMMAND 4 will automatically chlorinate both the pool and spa according to the desired output setting see Settings M
42. ter pump2 or lo speed spa lights aux1 aux2 valve3 superchlorinate diagnostic menu H salt level M water sensor air sensor solar sensor main software revision display software revision filter bridge vsc software revision RE base software revision configuration menu LH chlorinator pool spa 1 filter heater1 solar lights aux aux2 valve3 7 day or weekend weekday timeclock 12 hour or 24 hour time format M F or C reset to default HAYWARD 620 Division St 092419A Elizabeth NJ 07207 Copyright 2008 Goldine Controls
43. ure is enabled for the filter valves or aux outputs or if the chlorinator is enabled 4 3 Electrical Wiring Wireless Base Receiver Connector External Chlorinator Display Keypad requires Aqua Rite Sensor Input Heater Output Valve Connector High Voltage Relays Subpanel Control Power Input The ECOMMAND 4 Control Center requires both high and low voltage connections Low voltage connections will be made to actuators sensors remote keypad etc High voltage connections will be made to pumps lights etc as well as providing direct input power to the Control Center Always Ensure that Power is disconnected prior to doing any wiring Follow all local and NEC CEC if applicable codes Use copper conductors only Main Service Power to the Circuit Breaker Subpanel The ECOMMAND 4 circuit breaker subpanel is rated for 100A service Run properly rated conductors L1 L2 N and ground from the primary house electrical panel to the main power connections on the ECOMMAND 4 circuit breaker base The connection at the main house panel should be to a 240VAC circuit breaker rated at 100A maximum Grounding and Bonding Connect a ground wire from the primary electrical panel to the ECOMMAND 4 ground bus bar Also ground each piece of high voltage 120 or 240 VAC equipment that is connected to the ECOMMAND 4 control relays or circuit breakers The ECOMMAND 4 should also be connected to the pool bonding system by an 8AWG
44. x Pentair Purex MiniMax 1 Turn power off to heater 2 Remove factory installed jumper from the Ext Switch connector 3 Wire the ECOMMAND 4 to the Ext Switch connector as shown below 4 The wires to the ECOMMAND 4 must be separated from any line voltage wires Failure to follow NN these instructions may cause erratic operation of the heater Set the Power Thermostat Select switch to either Pool or Spa Set the Pool and Spa thermostats to their maximum settings Remove gt Pool Spa Factory Jumper gt Air gt Solar gt Heater DODDDDOD7 OAO o fooo000 9 0 o o o o 0 MINIMAX 0 Switch o Ooo fe Raypak RP2100 Pool Spa Heater 1 Turn power off to heater 2 Push the mode button to spa mode 3 Set the temperature to the maximum 4 Push the mode button to OFF 5 Lastly plug the prewired connector in the P7 position on the board IMPORTANT The heater will display OFF when it is being remotely controlled by the ECOMMAND 4 Some homeowners see the OFF display and thinking this is a mistake change the mode to POOL or SPA which then disables the remote control by the ECOMMAND 4 To prevent this Remove the heater touch pad connector P5 which will disable the touchpad Orange Black Stripe Black Orange