1. SPL OUZON Sole Phase Logger User Manual Rev 1 0 Dec 2003 Go M AT INSTRUMENTS Wavecom Instruments PTY LTD 45 Charles St Norwood South Australia 5067 PH 61 8 8331 8892 FAX 61 8 8331 3648 EMAIL admin wavecom com au WWW Wavecom com au INSTRUMENTS Specification BANDWIDTH Measurement VOLTAGE Measurement CURRENT Measurement POWER Measurement VA Measurement POWER FACTOR Measurement FREQUENCY Measurement KW HR Measurement SAGS SWELLS AVERAGING MAX MIN POWER SUPPLY SAMPLING SPEED MEMORY MEMORY CAPACITY ANALOGUE INPUTS DISPLAY COMMUNICATIONS PORT BAUD RATE CLOCK CALENDAR 30 Hz TO 2KHz Accuracy 0 5 reading 1 VAC TO 280 VAC RMS Accuracy 0 5 reading 10mA TO 1A RMS Scaleable 10mA TO 5A RMS Scaleable 5mV TO 200mV Scaleable Accuracy 0 5 reading 5 W TO 400 KW Accuracy 0 5 reading 0 TO 10000 VA Accuracy 0 5 reading 0 3 TO 1 000 Accuracy 001 30 Hz to 2KHz Accuracy 0 5 40000 KW Hrs 0 280 Vac minimum 1 Cycle Measures Duration of SAG or SWELL Stores 2000 events 0 5 sec to 60 min TRMS Values stored for each measurement 40 VAC 280 VAC UP TO 10 KS s 8 M BIT Standard 72K DATA POINTS 2 CH 12 BITS 2 X 16 CHARACTER BACK LIT RS232 9 6K 19 2K 38 4K 54K YEAR MONTH DAY HOUR MIN SEC POWER CONSUMPTION 1 WATT PROTECTION RATING 600VAC 100KA Fuse DIMENSIONS 225H X 110W X 90DMM WEIGHT 1K
2. 00 90 4 1 2 00 94000 2250 19 6 1 3600 72000 3000 100 8 2 Site ID Up to 8 Characters can be entered Letters from A Z and Number Digits O0 9 using the Up starts at A through to Z then 0 9 DWN starts at 9 0 then Zto A Holding the Up or DWN key for 1 sec will enable fast scrolling Calibration Software Setup Install CD into drive select RUN from the Start Menu selection bar Select SPL D disks setup exe to begin installation D Drive being your CD When prompted install program into desired directory or folder Create new name of file or folder if you wish Follow prompts to complete installation When complete installation click on application name in PROGRAM menu bar name is called SPL20 A splash screen will appear with the main Data logger terminal page Check Connection settings and ensure power is on in the logger Allow default of terminal settings answer selected comms port and IRQ Set logger Standard default settings 9600 n 8 1 Baud 9600 Parity N Bits 8 Stopbits one Serial Comms Port Default to 2 Press ok to accept
3. G excluding clamps OPERATING TEMP 0 TO 50 DEG C ENCLOSURE RATING IP 61 upto 67 depending on Clamp and Comms connections used INPUT CONNECTORS 4MM BANANA IP64 DIN OPTIONAL SPL Hardware Operation The SPL has been designed for simple field and Office compatibility The SPL keyboard allows the user to enter all required operation parameters in the field without the requirement of a PC The Menu Control is Simple when the unit is plugged in it is turned on and ready for operation and will continue to log at the setting already programmed previously or at factory default settings The unit will splash up on the display Unit Wavecom SPL and Firmware version Number perform a memory test and be in operation within 2 seconds Displaying main menu If left in an alternate display the SPL will default to the main display after 2 minutes turning back light off also 1 34A 98 PF The Back light defaults to OFF unless a key is pressed DISPLAY SCREEN MENU Going Down in the Menu Using Key Amps Mode 1 1A Range This window displays the settings of the current input device and what its CT ratio is SAG SWELL H 0 L 0 COUNT Start Log Delay 00 00 0000 00 00 This Display if set at O or at any expired date and time will enable the logger to log as soon as it powered up To set start delayed logging time see Setup Menu Start delay time If the date and time is set to a future date time setting the
4. n logger will not log until that time has arrived Memory 0 full Avg Period 5 m This display shows the user what percentage of the memory is used When displaying 99 the memory is full and all 4096 pages of memory are used The unit will need to be downloaded and cleared prior to logging more data The average period is the time interval the sampling is average over The unit collects the data for say 5 minutes as shown in above Sample and averages all temporary accumulated data and stores the averaged value with date and time stamp Site ID Wavecom V x1 A x1 This Display shows the user Site Identification this input is optional But recommended for tracing where unit was located for testing V x1 shows the user if any Voltage multipliers or VT are used This can be seen on the main display if a VT is used the Volts reading will display KV values if ratios are high enough A x1 shows the user if any Current multipliers or CT are used This can be seen on the main display if a CT is used the Amps reading will display KA values if ratios are high enough Max 50 2Hz Min 49 6Hz This Display shows the user what the Maximum and Minimum Frequencies measured during the time of recording To reset these values to zero the user must Reset MAX amp MIN Values in setup Menu Max 100PF Min 49PF This Display shows the user what the Maximum and Minimum Power Factors measured during the time of recording To reset these
5. ock Key board Setup Logger Confirm Press to confirm Setup menu SPL Setup Mode Use Up and Down This prompts the user to use the Up and DWN Keys to select function the User wishes to get to and Change Once in this mode and left without any keystrokes for 2 minutes the SPL will change back to the MAIN DISPLAY screen resetting into normal operation mode Using the Key the menu flows as following Change Amps Mode Enter Up or Dwn Press to confirm Setup menu Amps Input 1A Use Up and Dwn Pressing UP or DWN Key will give the Choice of 3 settings 1A 5A 200mV Amps Input 5A Use Up and Dwn Amps Input 200mV Use Up and Dwn Select input option required press to confirm selection Amps Input 5A Done The Flash screen confirms the entry with DONE Then resets to the top of setup menu allowing user to change the next setting or Pressing menu to opt back to logging MAIN DISPLAY by Pressing MENU button Set Amps Ratio Enter Up or Dwn Pressing UP or DWN Key will give the Choice of 24 Ratio settings 1 2 5 10 12 20 26 30 32 40 50 100 105 150 200 240 320 400 500 600 700 800 900 1 000 Select ratio setting to match CT Select input option required press to confirm selection Set Amps Ratio Confirm Amps Ratio 20 Done The Flash screen confirms the entry with DONE Then resets to the top of setup menu allowing user to change the next setting or Pressing menu to o
6. pt back to logging MAIN DISPLAY by Pressing MENU button scroll Down Menu Using Key Until Un Lock Keypad Enter Up or Dwn To unlock Keyboard press menu key to display Setup Logger No Press Menu Then hold the DWN amp ENT together for 3 seconds and scroll to Un Lock Keypad Confirm Once the keypad is locked the SPL will only display the MAIN Display and the SETTING Displays The key lock takes effect when the setup program is exited Un Lock Keypad Keypad Locked Unlocking the Keypad The user must hold the DWN key then the ENT Key together for 3 seconds The Lock system remains locked until the above process is reversed Defaults Amps Mode 1 1A Amp Start Log Delay 00 00 0000 00 00 Memory 0 Full Avg Period 60 minutes log data every 60 Minutes Site ID Norwood Volts Ratio x1 Amps Ratio x 1 This also clears all Memory and resets Max amp Mins Logger Memory The datalogger has standard memory capacity of approx 72000 this is stored in date time This can be upgraded to 144000 if required The keyboard can erase the Logger this can only be done in the setup menu Storage Rate SEC Hours Storage Days Storage Months Storage Years Storage 0 5 10 0 41 1 20 0 83 2 40 1 6 5 100 4 16 10 200 8 3 20 400 16 6 30 600 29 0 83 0 06 60 1200 50 1 6 0 1 120 2400 100 3 3 0 2 300 6000 200 8 3 0 6 600 12000 900 16 6 1 3 900 18000 750 25 2 0 1200 24000 1000 33 3 2 1800 36000 15
7. values to zero the user must Reset MAX amp MIN Values in setup Menu 9 Max 1 3KA Min 1 45A This Display shows the user what the Maximum and Minimum Current measured during the time of recording To reset these values to zero the user must Reset MAX amp MIN Values in setup Menu 9 Max 247V Min 217V This Display shows the user what the Maximum and Minimum Voltage measured during the time of recording To reset these values to zero the user must Reset MAX amp MIN Values in setup Menu Date and Time 06 02 2000 13 43 This Display shows the user what the real time is set too The Setup Menu or PC can altar the Date and Time The Time will only update every minute although the system measures and stamps recordings including seconds 12kWh 90 0HZ OkVAh This Display shows the user what the power usage is upto the second reading The value is updated The Frequency is also displayed real time Using the DWN Key again will bring the user to the MAIN DISPLAY screen completing the Display Data Loop SETUP MENU MEN KEY Pressing the menu key enables the user to toggle between the MAIN DISPLAY and SETUP MENU DISPLAY Setup Logger No Press Menu Pressing the MENU key twice will acknowledge the setup menu is not required If pressed once the above display will be displayed Press key and the display will ask for confirmation if keyboard is not locked If Keyboard Locked See Lock Unl