        dIXEL Operating Instructions - Emerson Climate Technologies
         Contents
1.     Through    Prg    button is possible to modify the parameters map of active section  These  parameters influence the behaviour of single section     5  PARAMETERS PROGRAMMING FOR SECTION  5 1 HOW TO MODIFY SECTION PARAMETERS    To modify the parameter value work in the following manner    1  enter in programming mode  by pressing    Prg    for 3 seconds    2  slide the parameters list with A or w arrows until you display the code of  parameter    3  Press  SET    key and display the value    4  With a or v you modify the value    5  Press Set to store parameter and to go to next label     Quit  Press SET   a   when view a label or wait 15 seconds without press a key     Note  the new value is stored even if you go out from modification procedure after  timeout interval is terminated    SECTION PARAMETERS    Set point  it allows to modify the Set Point   200   600  C    328   999  F   Temperature probe presence   Yes or No  it permits to disable the input  probe to use only digital input   Maximum temperature alarm setting   0 200  C or 0 360  F  when  SET ALU temperature is reached and after the ALd delay time the HA alarm  is enabled   Minimum temperature alarm setting   0 200  C or 0 360  F  SET ALL  temperature is reached and after the ALd delay time  the LA alarm is  enabled    Temperature alarm delay   0 120 min  time interval between the detection  of an alarm condition and the corresponding alarm signalling    Thermostat probe calibration    12 0 12 0  C   21 21  F
2.    Pr1    label  then    1  Press and release    Section    key  it ll show the first label of the global parameters  map  dAQ     2  move in menu using Up or Down arrows keys until you display the label that you  want to modify    3  Press    Set    key to display the parameter value    Modify the parameter value through Up or Down arrows    5  Press    Set    to store parameter and to go to next label  If the value of parameter is  modified it ll blink for three seconds    6  Togo out from programming mode  you press    Set   Up    when a parameter label  is showed or you return to function menu and wait 15 seconds     a    GLOBAL PARAMETERS    Delay of temperature alarm at start up   0   23h 50min  time interval  between detection of alarm condition and alarm signalling after power on   This delay is counted also when digital input configured as oFF is disabled   Alarm delay at the end of defrost   0   120 min  Time interval after defrost  before alarm signalling    Resolution  for   C    in   1  C  de   0 1  C  it allows visualisation with  decimal point    Measurement unit    C   Celsius    F   Fahrenheit   Probe input configuration  P2F   PT100 2 wires  P3F  PT100 3 wires  Parameters map   read only  it shows the original code of the dixell  parameter map    Release Software read only      4 6 EXIT  There are two possibility to go out from menu     e By pressing Section button on    out    label  e If you don   t press keys for 15 seconds    Section Menu      PRG    Key
3.   allows to adjust  possible offset of the thermostat probe    Digital input polarity  cL   D I  is active if voltage is present  oP   D I  is  active if voltage isn t present  nP   D I  not used    1592010250 XJP40D GB r1 0 05 06 06 doc    Operating Instructions          Digital input operating mode  StA   State  ALL   Alarm  dFr   defrost   oFF   if digital input is enabled the section goes to Standby   Time interval delay for digital input alarm  0 120 min      Serial Address  1 247   Identifies the instrument address when connected  to Mod BUS compatible monitoring system     6  ALARM MANAGEMENT    The alarm control is disabled when     e the sections aren t active or aren t enabled     during dAo interval at power on and as soon as digital input configured as  OFF is disabled    e if digital input is configured at defrost and it is active    e during EdA interval after defrost end       The type of managed alarms are reassumed in the following table       Mess    Causes                 C sSCSCSC S SCS  High temperature alarm  Low temperature alarm    i  ae Probe fault in active section       EE      Communication error with internal EEPROM       N B   Every alarm stops automatically when the alarm situation is finished     6 1 COPY FUNCTION    To facilitate module programming operations  its possible to copy the parameter list  from    work section    to another     1  Enter the section menu     Section    key     2  Slide using    UP    and    DOWN    keys the list of s
4.  permits to decide if you   want to use unique serial address to manage all sections or if you want to use different   serial address for each section    The Adr parameter permits to do this choice    e By setting the same Adr parameter value for each section  you use unique  address for all sections    e By setting different Adr parameter for each section  you use a serial address for  each section   All alarms  the states and the data measured by the modules XJP can be sent by RS485   serial to ModBUS RTU compatible monitoring system     N B   With XWEB series unique addressing system must be used  By default the  unique addressing system is used  so at first time that new section is created it  gets the same address of the previous section     11  TECHNICAL DATA   Housing  self extinguishing ABS   Case  4 DIN modules 70x85 mm  depth 61mm   Mounting  DIN RAIL mounted in an omega din rail   Connections  Screw terminal block  lt  2 5mm  wiring   Power Supply  230Vac   10  50 60Hz  opz  110Vac   10  50 60Hz  24Vac   10   50 60Hz    Power absorption  3VA max   Display  through KB1 PRG  Three digits  LED red  height 14 2 mm  Analog inputs  4 PT100 probes 2 or 3 wires   Inputs  4 main supply digital inputs   RS485 Output  RS485 serial output with ModBUS RTU protocol  Data Storage  on the non volatile memory EEPROM    Operating temperature  0 60   C   Storage temperature   30 85   C   Relative humidity  20 85   no condensing    Measuring and regulation range   200    600   C   Res
5.  ready to operation of UPLOAD  Removing the  keyboard and inserting the    Hot Key    within 30 sec the UPLOAD will start  During this  phase  the two Led  RED and GREEN  are turned on fixed     At the end of the data transfer phase the module displays one of the following  messages     Only Green Led   ON    right programming   Only Red Led  ON   failed programming     After removing the    Hot Key    the instrument waits 30sec before restarting normal  regulation  If another    Hot key    is plugged in  the UPLOAD will be done again     8  INSTALLATION AND MOUNTING    XJP modules shall be mounted on omega DIN RAIL  The ambient temperature range  allowed for correct operation is 0   60   C  Avoid places subject to strong vibrations   corrosive gases  excessive dirt or humidity  The same recommendations apply to  probes  Let air circulate by the cooling holes     XJP40D 2 3    dixell  9  ELECTRICAL CONNECTIONS    Operating Instructions    1592010250       The instruments are provided with screw terminal block to connect cables with a cross  section up to 2 5 mm   Before connecting cables make sure the power supply complies  with the instrument s requirements  Separate the input connection cables from the power  supply cables  from the outputs and the power connections  Do not exceed the  maximum current allowed on each relay  in case of heavier loads use a suitable external  relay     10  SERIAL COMMUNICATIONS    Factory serial address configuration is Adr_0 1  The instrument
6. Operating Instructions      1592010250       XJP40D    ACQUISITION MODULE       1  General warning 1  2  General description 1  3  Programming keyboard  KB1 PRG  1  4  Main functions 1  5  Parameters programming for section 2  6  Alarm management 2  7  X REP  amp  KB1 PRG  amp  HOT KEY 2  8  Installation and mounting 2  9  Electrical connections 3  10  Serial communications 3  11  Technical data 3  12  WIRING Connections 3  13  Default values 3    1  GENERAL WARNING    1 1 Z  PLEASE READ BEFORE USING THIS MANUAL    e This manual is part of the product and should be kept near the instrument for easy  and quick reference    e The instrument shall not be used for purposes different from those described  hereunder  It cannot be used as a safety device    e Check the application limits before proceeding     1 2 IAN SAFETY PRECAUTIONS    e Check the supply voltage is correct before connecting the instrument    e Do not expose to water or moisture  use the controller only within the operating  limits avoiding sudden temperature changes with high atmospheric humidity to  prevent formation of condensation   e Warning  disconnect all electrical connections before any kind of maintenance    Fit the probe where it is not accessible by the End User  The instrument must not   be opened    In case of failure or faulty operation send the instrument back to the distributor or to      Dixell S p a      see address  with a detailed description of the fault    Consider the maximum current which 
7. can be applied to each relay  see Technical   Data     Ensure that the wires for probes  loads and the power supply are separated and far   enough from each other  without crossing or intertwining    In case of applications in industrial environments  the use of mains filters  our mod    FT1  in parallel with inductive loads could be useful     2  GENERAL DESCRIPTION    The XJP40D in DIN RAIL format is an acquisition module able to read up to 4  temperature via PT100 probes and is provided of 4 digital inputs at supply voltage   PT100 probes with 2 or 3 wires can be used through configuration of instrument  parameter  Every XJP40D can have up to 4 sections  More precisely  it   s possible to  subdivide the instrument resources in 4 parts independent  with autonomous parameters  and so with unique or different serial address     Through RS485 serial output it can be integrated in a monitoring systems created by  Cixell or in whichever Modbus RTU compatible system  It   s programmable through  useful Hot Key or through KB1 PRG and it   s possible to link it to X REP display to view  the temperature values of probe linked to active section     3  PROGRAMMING KEYBOARD  KB1 PRG         v  DOWN   During programming mode they slide the  labels of parameters or they change the    Ol 2    values displayed  By pressing and holding  one of these buttons during modifying  procedure  values change faster        PRG  Displaying active section  by  pressing and releasing this key the  name 
8. ections until the label of section to  program is displayed    3  By pushing    COPY    key until the code of the section flashes  the parameter list of the     work section    is pasted in the new section     7  X REP  amp  KB1 PRG  amp  HOT KEY    The XJP has a connector on the front to connect the programming keyboard KB1 PRG  which can be used to program the modules  to connect the X REP to display the input  status or the    Hot Key        7 1 USE OF THE PROGRAMMING HOT KEY    7 1 1 Download from the Hot Key to the module    If the programming key is plugged in  when the instrument is switched ON  the  automatic DOWNLOAD of the parameters list from the    Hot Key    to the instrument will  start  During this phase  RED and GREEN LEDs are turned on fixed     At the end of data transfer phase the module displays one of the following messages     Green Led   ON   right programming   RedLed  ON   failed programming     If the programming has failed  the instrument has to be switch OFF and ON to repeat the  operation or to start the normal regulation   The normal regulation start if you remove the     Hot Key         7 1 2 Upload from the module to the    Hot key       The module can UPLOAD the parameters list from own E2  internal memory  to the Hot  Key     The programming keyboard has to be connected and the module switched ON  During  the normal displaying  push    COPY    key for up to 3 seconds until the label  uPL  will  appear     Pressing    SET    key  the module is
9. ion    button you can modify the global section parameters  while with    Prg     button you can modify the specific section parameters     Global menu      SECTION    Key    The    Section    key allows the sections administration  up to four sections  in which the  instrument can be divided  moreover it   s possible to display the measured value from  input of active section  With    Section    it s possible to modify the number of sections and  the parameters of global map     In the following table there is the complete list of labels of global menu     Label   Description  It contains the number of enabled sections    The states of section    General parameters  Quit to menu       Where with SE  indication it   s intended that if there are four active sections  on global  menu we will have 4 labels  SEO  SE1  SE2  SE3 one for each section     4 1 HOWTO ENTER MENU     1  you enter in section menu by pressing and releasing the    Section    button   Immediately the display shows the label Snc  First label of the list     2  Through Up or Down arrows you can move ahead or behind cyclically into menu     4 2 HOWTO MODIFY THE NUMBER OF SECTIONS SNC    You enter in section menu and immediately you ll view the Snc label     1  By pressing and releasing    Section    button  it ll appear the number of enabled  sections  With Up or Down arrows you can modify the number of sections     2  By pressing and releasing another time    Section    key  you store the number of  sections a
10. nd you return in main visualisation  By pressing key  number will blink for  3 seconds      3  If the number of section isn   t modified by pressing    Section    button you view the  label SEO  label after Snc      N B   The sections number is able to be modified in order to number of active sections   For example  if the fourth section is active  Se3  the number of sections is always at  least four  if the second section is active  Se1   the number of sections is always at least  two     4 3 DISPLAYING MEASURED VALUES    When you have finished the configuration of the number of section     Section    menu  shows a number of labels equals to number of active sections     1  By pressing and releasing    Section    key on the label    SE     you can view the  temperature measured by probe relative to section while the functional state of  digital input is monitored by D I 1 dot with delay did     2  By pressing and releasing    Section    key you ll go to SE  1 label    XJP40D 1 3    dixell    1592010250       3  Ifyou don   t press a key for 15 seconds you ll return to main visualisation     4 4 ACTIVATION OF WORKING SECTION    To enable a section  you display a label that represent it and you press    Section    key for  3 seconds  by default active section is Se0      N B   By entering in programming mode you view always the active section parameters     4 5 HOWTO MODIFY THE GLOBAL PARAMETERS MAP    PR1       You enter in Section menu and slide the labels until you display 
11. of active section is  displayed  Parameters access  by  pressing and holding the key for 3  seconds the instrument enters in  programming menu of active  section        1592010250 XJP40D GB r1 0 05 06 06 doc    SET  Displaying and modify SET POINT  by pressing and releasing the key  the  instrument displays value of set point for 5 seconds  By pressing and  holding this button at least for 3 seconds you can modify the SET value     SECTION  Section menu access  by pressing and releasing this key you enter in  section menu  One instrument can have up to 4 section  par  1      COPY  It permits to copy total configuration of one section into another section   During normal operation it allows the data upload from module to    Hot  Key        3 1 ABOUT LED    The display always shows the active section  either via remote keyboard or via the X   REP  There are three different colour LEDs  in the following table are presented the  States it can be displayed     State of Led  Function S  RX TX in progress    The module receive but not transmit  It s absent the serial communication       Green ON Power supply is present    Red   ON  Aa o    N B  Section 7 1    LEDs states displayed during Hot Key usage     4  MAIN FUNCTIONS   The instrument is provided with two type of parameters map     The global parameters map    The section parameters map    Modification of global parameters map influence all active sections  while every section  has one independent section map    Through    Sect
12. olution  0 1   C 01  C or 1   F   Precision a 25  C   0 5   C   1 digit    1592010250 XJP40D GB r1 0 05 06 06 doc             12  WIRING CONNECTIONS    HOT KEY  remote display keyboard           a                Input Input2 Input3 Input4 RS485 Powe Supply  230Vac 230Vac 230Vac 230Vac 230Vac    Pt100 2 wires  connect to not dashed terminal  24 110Vac Power Supply  connect to 23 24 terminals    13  DEFAULT VALUES    13 1 GLOBAL PARAMETERS    dAo Delay of temperature alarm at start up 0   23h50       EdA Alarm delay at the end of defrost 0      120         EGA     in   integer   dE    CIF    Pt  EL      P2F 2 wires   P3F 3    Input probe configuration Wires    rEL Release Software    13 2 SECTION PARAMETERS    Range  Set Point  200   600  C    328   999  F  Temperature probe presence    g  ALU Maximum temperature alarm 0   200  C   0   360  F  setting  ALL Minimum temperature alarm 0   200  C   0   360  F  setting  ALd Temperature alarm delay 0      120     ee   cL   closed   oP   open  nP   not  Digital input configuration Sta   state   ALL   alarm dEr    defrost   oFF   Standby  Time interval delay for digital i  Adr 1      0       120     input alarm    Adr   Serial Address    Set    EA  Ald      Ot   Thermostat probe calibration  12  C     20  F    dixell s p a     Z    Via dell    Industria  27   32010 Pieve d Alpago  BL  ITALY    tel   39   0437   98 33   fax  39   0437   98 93 13  http   www dixell com E mail  dixell dixell com       XJP40D 3 3    
    