1. Recommended Cable type Cores Max Distance TDSi IR Reader Belden 9729 4 140m FBOS2P24 4 100m 0S2P22 Alpha 5902 Belden 4 60m 9502 OS4C24 Alpha 5094 BICC 4 40m H8123 Screened Alarm Cable 8 Up to 30m Magnetic Stripe Reader Belden 9730 6 60m Belden 9503 6 25m OS6C24 Alpha 5096 BICC 6 20m H8124 Screened Alarm Cable 8 Up to 30m Indala Proximity Belden 9730 150m Reader amp TDSi eXprox reader Belden 9503 60m OS6C24 Alpha 5096 BICC 6 50m H8124 Screened Alarm Cable 8 Up to 30m Keypad Belden 9729 4 140m FBOS2P24 4 100m 0S2P22 Alpha 5902 Belden 4 60m 9502 OS4C24 Alpha 5094 BICC 4 40m H8123 Screened Alarm Cable Up to 20m RS232 Communications Belden 9534 or 7 0 2mm 15m Screened RS485 Communications Belden 9729 1200m FBOS2P24 900m 0S2P22 Alpha 5902 Belden 530m 9502 OS4C24 Alpha 5094 BICC 4 400m H8123 Screened Alarm Cable 300m Inputs 7 0 2mm Screened 300m Relays 7 0 2mm or 16 0 2mm 2 Dependant on load Screened and cable choice 6656 0396 Issue 1 page 9 Basic Installation Basic Installation Installation do s and don ts It is vital to observe anti static precautions when working inside the ACU cabinet Solder and tape all connections DO NOT use crimps or B connectors or wire nuts or punch down blocks Each ACU must be grounded to a good mains ground This can be achieved via the ground wire cable shield from the power supply or by a sepa
2. I ACCESS CONTROL Installation manual 6656 0396 Issue 1 Supplier information eXcel is designed and manufactured by TDSi Ltd Sentinel House Nuffield Road Poole Dorset BH17 ORE England Telephone Within UK 01202 666222 International 44 1202 666222 Fax Within UK 01202 679730 International 44 1202 679730 E mail info tdsi co uk Web site www tdsi co uk Other supplier information DEALER STAMP Copyright Copyright 2003 Time and Data Systems International Ltd Poole All rights reserved This document and any software supplied with it may not be reproduced in any form or by any means in whole or in part without prior written consent of the copyright owners Policy Time and Data Systems has a policy to continuously improve its products Therefore the company reserve the right to change specifications colours or prices of its products at any time without prior notice Limitation of liability In no event shall seller be liable to buyer whether in contract or in tort or under any other legal theory for lost profits or revenues loss of use or similar economic loss or for any indirect special incidental consequential or similar damages arising out of or in connection with the sale delivery non delivery servicing use maintenance condition or possession of any and all of the system or software or for any claim made against buyer by any other party even if seller has been advi
3. from the RS485 converter PC to MA 45 PC 9 way PC 25 way MA 45 25 way Function 2 3 3 Receive 3 2 2 Transmit 5 7 7 Ground MA 45 to eXcel MA 45 5 way eXcel terminal Function 1 2 RS485 Rx A 2 1 RS485 Rx B 3 4 RS485 Tx A 4 3 RS485 Tx B 5 No connection eXcel chassis Cable screen MA 45 switch settings 51 53 52 MAM AAA vijve 5 m MM 4 vi v viv v orn i 123 45 6 7 8 340 V 1234 115 S3 settings S2 settings 1 ON 1 ON 2 ON 2 ON Baud rate Terminated 4 Wire 3 ON 3 OFF 5 ON AJLON 10 bit word 5 OFF 6 OFF 4 wire 7 OFF RTS control 8 n a not used eXcel4 switch settings All switches OFF DOWN 6656 0396 Issue 1 page 17 Basic Installation One or more units over Ethernet using TCP IP eXcel features a built in Ethernet port called Xport with an RJ 45 socket which is suitable for 10Mb and 100Mb networks An eXcel can also be directly to a computer using a crossover cable In an installation with more than one eXcel all of the units can be connected using their Ethernet ports Alternatively some of the eXcel units can be connected to other eXcel units via their RS485 ports If you are connecting to an existing network Establish with the network administrator e the IP address of the computer s that will be running
4. OV 46 Door 3 Lock relay n c 47 Door 3 Lock relay pole Relay 3 1 2 or 3 door configuration 48 Door 3 Lock relay n o 49 Door 3 Door Sense Input 5 2 or 3 door configuration 50 OV for Door Sense and Egress 51 Door 4 Egress Input 6 2 or 3 door configuration 52 Door 4 Lock relay n c 53 Door 4 Lock relay pole Relay 4 1 2 or 3 door configuration 54 Door 4 Lock relay n o 55 Door 4 Door Sense Input 7 2 or 3 door configuration 56 OV for Door Sense and Egress 57 Door 4 Egress Input 8 2 or 3 door configuration page 26 6656 0396 Issue 1 Compliance Notices Commissioning and Trouble Shooting Compliance with CE regulations CE The equipment is designed tested and declared to conform to the following CE directives 89 336 EEC EMC Directive 93 68 EC Low Voltage Directive The equipment has been tested and found to comply to the following EMC amp Safety standards Electromagnetic emission EN 55022 1994 Electromagnetic emission EN 50081 1 1992 Electromagnetic immunity EN 50082 1995 Electromagnetic immunity EN 50130 4 1995 Safety of IT Equipment EN 60950 Limitations on the intended operating environment The equipment is intended for use in access control applications in a wide range of configurations It is intended for use with third party equipment attached at the power supply input the reader inputs various control outputs and the data co
5. a faulty connection at one unit could prevent communication with all units Red LED flashing rapidly Normal behaviour by eXcel if eXguard software green LED flashes every 1 reports ACU as off line then data transmitted by 5 seconds eXcel is either not reaching the PC or the eXcel A and B Tx transmit data lines are reversed No LEDs flashing Data transmitted by PC is not reaching eXcel Only RED LED flashing Data transmitted by PC is reaching eXcel but either eXcel serial number has not been entered correctly or the eXcel A and B Rx receive data lines are reversed A diagnostic tool eXmonitor exe is available This will display a list of all units that are capable of communicating correctly and provides a quicker simpler way of troubleshooting The tool is installed automatically in the eXguard program directory but with no shortcut run it directly from the folder 6656 0396 Issue 1 page 23 Commissioning and trouble shooting Final configuration Final configuration involves using eXguard to program the required features into eXcel Please refer to the help system in eXguard for further guidance page 24 6656 0396 Issue 1 Commissioning and Trouble Shooting Connection tables Power and communications eXcel terminal Function Notes 1 RS485 TX A The descriptions A and B are 2 RS485 TX B not always consistent between various manufactur
6. eXguard applications or permissible addresses and subnet masks for those computers e permissible IP addresses for each access control unit that will be connected to the network If you are connecting to a network dedicated to the access control system Make sure that TCP IP protocol is installed on the computer s that will be running eXguard applications Give each computer an IP address in the range 10 0 0 254 10 0 0 253 etc and a subnet mask of 255 255 255 0 Instructions for Ethernet connection Before connecting the Ethernet port to anything re position the 5 dip switches to the ON position up These switches enable the port and provide RS485 end of line termination Connect the eXcel to the network or computer If there is more than one eXcel they can all be connected at this stage but make a note of the UID number of each unit and its location to help you identify which unit is which during setup If required to confirm that the network is connected correctly you can observe the light inside the Ethernet port an amber light means a connection at 10Mb s a green light means a connection at 100Mb s Install and run the Lantronix XPort Installer software in the Extras folder on the Documentation CD supplied with the eXcel and on the eXguard CD Click the Search button this will detect all eXcel4 units in the system and display their automatically assigned IP addresses Note this process m
7. the door sensor inputs 2 Present a card to one of the readers The flashing rate should change to one flash every two seconds 3 Present the card again relays 1 and 2 should be energised for 5 seconds At this stage the eXcel has not been told whether it is a one door or two door installation Note that until the first card is programmed using eXguard ANY card of the correct technology will trigger both relays 4 If an egress button is fitted press it The associated lock should operate for as long as the button is pressed and remain operated for 5 seconds after the button is released Communications set up Make a note of the 12 digit UID of each eXcel unit in the system this is visible through a window in the connection label Once eXguard is started on the PC this information is needed at the time of adding the ACU details into the database For units connected via Ethernet the IP address will also be required Once the required information has been entered you can start or re start eXguard Communications and the computer will start communicating with the ACUs Fault finding communications problems eXguard will indicate if it has failed to communicate with any ACU and the red and green LEDS on the eXcel boards can be used to assist with troubleshooting Note that this type of problem is more easily resolved by disconnecting the RS485 connections from ALL eXcel units and trying to bring them on line one at a time
8. with keypad part number 5002 0317 Mag stripe reader with keypad part number 5002 0316 Digital Microcard reader with keypad part number 5002 0315 eXcel terminal Reader CN1 terminal Function 14 Reader 1 Terminal 4 Data 15 Reader 1 Terminal 3 Clock 16 Reader 1 Terminal 5 LED 12 Reader 1 Terminal 2 5V DC 18 Reader 1 Terminal 1 OV 17 Reader 1 Terminal 6 12V DC 28 Reader 2 Terminal 6 12V DC 25 Reader 2 Terminal 4 Data 26 Reader 2 Terminal 3 Clock 27 Reader 2 Terminal 5 LED 39 Reader 2 Terminal 2 5V DC 29 Reader 2 Terminal 1 OV 28 Reader 3 Terminal 6 12V DC 30 Reader 3 Terminal 4 Data 31 Reader 3 Terminal 3 Clock 32 Reader 3 Terminal 5 LED 39 Reader 3 Terminal 2 5V DC 37 Reader 3 Terminal 1 OV 44 Reader 4 Terminal 6 12V DC 41 Reader 4 Terminal 4 Data 42 Reader 4 Terminal 3 Clock 43 Reader 4 Terminal 5 LED 40 Reader 4 Terminal 2 5V DC 45 Reader 4 Terminal 1 OV page 20 6656 0396 Issue 1 Installing extra features Door sensors Most door sensors have contacts that are closed when the door is closed If fitting one where the opposite is true make the appropriate selection in eXguard If no door sensor is to be fitted then the factory fitted link should be left in place otherwise the on board buzzer will start to sound shortly after powering up eXcelf eXcel terminal Funct
9. 656 0396 Issue 1 page 5 Planning Planning Options to choose before starting Additional to an eXcel ACU and a computer running eXguard software a basic installation requires only card readers and electric lock mechanisms Additional features are available i e door sensor egress input inputs and relays Options for all of these are listed below and factors affecting the choice are explained Card reader Choose an appropriate technology the choice includes infra red Microcard mag stripe proximity hands free and biometrics If there is no pre existing reason for choosing one technology over another e g if the cards have also to be used in an other system such as a time and attendance recorder then the choice of technology will be based on cost of readers cost of cards level of security offered and personal preference Technology Reader cost Card Cost Security Other issues Mag stripe Low Low Low Mis reads are common Readers are usually not weatherproof Cards are easily damaged through accidental erasure of the coding Wiegand Medium Medium Medium Old technology often site specific so long lead times at manufacture Infra red Microcard Medium Medium Medium Small readers mis reads are rare Cards are more secure and more robust than mag stripe Proximity High Medium to High High Easy to use and rapidly growing in popularity as pr
10. ant les limites applicable aux appareils numeriques de la Class B prescrites dans les reglement sur le brouillage radioelectrique edicte par le Ministere des Communications du Canada page 28 6656 0396 Issue 1 Commissioning and Trouble Shooting Safety Notices Product description These notes apply to TDSi eXcel Access Control Units with an internal ACU PSU mains power supply fitted A 230v 50 Hz AC mains supply must be connected to the equipment by a permanently connected wiring installation as described below Rating The TDSi eXcel Access Control Units with an internal AC PSU mains power supply fitted are powered from a 230v 50Hz mains supply amp draw a maximum supply current of 0 4A Safety WARNING Disconnect the mains supply before removing the covers or making connections to the equipment All regulations and requirements MUST be must strictly followed to prevent hazards to life and property both during and after installation and during any subsequent servicing and maintenance Positioning and fixing of equipment The equipment must not be installed out of doors or in damp or exposed conditions To ensure mechanical stability the equipment must be secured using appropriate fasteners or brackets to a wall pillar or other part of the building structure or to associated stable equipment The equipment must not be sited near to sources of heat It is designed for use in ambient temperatures ranging from 0 to 40 degrees C Con
11. ay require several attempts If you do not see all of the expected units keep pressing the Search button and dismissing any error messages At this stage you will not be able to tell which one is which For each unit that has been detected e Select the unit in the list e Observe the UID number of the unit in the list on the right under e mail notification unit name e Click the Assign IP button e Enter a suitable IP address If this is a dedicated network start at 10 0 0 1 then 10 0 0 2 and so on e Click on the OK button and wait for the Xport to re boot and for the new IP address to appear in the list Close the Lantronix Xport Installer Install and run eXguard software and add the eXcel units into the database using the IP addresses assigned in step 4 page 18 6656 0396 Issue 1 Basic Installation connecting one eXcel to another eXcel terminal eXcel terminal Function 2 2 RS485 Rx A 1 1 RS485 Rx B 4 4 RS485 Tx A 3 3 RS485 Tx B 6656 0396 Issue 1 page 19 Installing extra features Installing extra features This section covers the following optional installations Readers with keypads Door Sensors Egress buttons Inputs Relays Readers with keypads The following table covers the most popular reader keypads being supplied currently by TDSi For any other reader keypad combination please refer its own documentation TDSi Proximity reader
12. dy Peripheral mounted on NON METAL surface Peripheral mounted on METAL surface 6656 0396 Issue 1 page 11 Basic Installation How to terminate The following pictures show how the cable screen should be terminated to the ACU chassis This also holds the cable firmly in place while terminating the cable cores If you are not terminating the cable screen to the chassis use a cable tie through the holes to hold the cable in place Before terminating the cable cores have feed the twisted screen braid through the hole nearest the connector Feed the braid round the cable pull the spring towards you and pull the braid down into the gap nearest the chassis Make sure the screen is completely within the spring and that it points away from the connector blocks page 12 6656 0396 Issue 1 Basic Installation Readers This section covers the most popular readers currently supplied by TDSi For any other reader please refer to the documentation that came with the reader Installation of readers with combined keypads is covered in Installing extra features eXprox Proximity readers 5002 0350 5002 0352 0357 Digital IR reader 5002 0372 Mag stripe reader 5002 0360 eXcel Reader connection Colour terminal 14 Reader 1 MAG DATA Yellow 15 Reader 1 MAG CLK White 16 Reader 1 LED Blue 12 Reader 1 5V Green 18 Reade
13. e protection marked FUSE In case of failure FUSE should be replaced with a 3A T Slow blow 20mm Fuse TDSi part number 2021 0034 The Reader Connect PCB is fitted with fuse protection marked F1 In case of failure F1 should be replaced with a 1 6A T Slow blow 20mm Fuse TDSi part number 2021 0036 Lithium battery The Lithium battery is only fitted to the eXcel board For this to be operational jumper J4 needs to be connected The battery will support eXcel memory for a maximum of 10 years in normal environmental conditions The clock chip mounted on eXcel board has it only internal battery which will retain memory to the clock chip for a maximum of 10 years under normal operating conditions 6656 0396 Issue 1 page 29 Safety Notices Board layout Fuse 12v 1A anti surge ES 4 000 S 000 102 didi page 30 mm Ethernet port Communications switches Communications LEDs iiiiiiii Midiiiitit dEdEEEEEER Processor showing UID WSI device 2223122312311 Reset switch tititidiit Memory battery and switch Flash EPROM ENFEETERE ele TTtTEtte 4104 Buzzer Tamper switch under spring 6656 0396 Issue 1
14. ed open from either side Frameless glass doors also require specialist solutions All lock types have their advantages and disadvantages if unsure which type to choose then gather as much information as possible about the door and seek advice from a supplier Magnetic locks Magnetic locks have become very popular as they provide rapid solutions in a wide variety of circumstances often without the need for major surgery to the door frame or pre existing furniture There are two types face to face for outward opening doors and shear locks for inward opening and swing doors These locks are available in a range of strengths and designs Note that some designs will reduce headroom and may have health and safety implications if there is a risk of injury from the metal edges of the mechanism Door sensor A door sensor can serve two purposes e For access control the door sensor provides an extra level of security in the following way If the lock release time is set to say 10 seconds it is quite possible for someone to pass through the door in only two or three seconds after using their card This leaves seven or eight seconds of un expired time during which if no door sensor was fitted the door could still be opened However if a door sensor is fitted then as soon as the door opens the lock release is de energised and the door re locks as it closes e For access monitoring having a door sensor fitted means that all
15. ers To avoid 3 RS485 RX A problems always follow the pin to 4 RS485 RX B pin tables in this manual 5 RS232 OV SG 6 RS232 RX 7 RS232 TX 8 RS232 RTS 9 RS232 CTS 10 12V DC Power supply IN 11 Power supply Ground MA 45 RS232 RS485 converter Connecting one eXcel to another eXcel eXcel 3 3 4 4 1 1 2 2 6656 0396 Issue 1 page 25 Safety Notices Readers and doors eXcel terminal Function Alternate use 12 5V OUT 13 OV OUT 14 Reader 1 MAG DATA 15 Reader 1 MAG CLK 16 Reader 1 LED 17 Reader 1 12V 18 Reader 1 OV 19 Door 1 Lock relay n c 20 Door 1 Lock relay pole 21 Door 1 Lock relay n o 22 Door 1 Door Sense 23 OV for Door Sense and Egress 24 Door 1 Egress 25 Reader 2 MAG DATA 26 Reader 2 MAG CLK 27 Reader 2 LED 28 Reader 2 amp 3 12V 29 Reader 2 amp 3 OV 30 Reader 3 MAG DATA 31 Reader 3 MAG CLK 32 Reader 3 LED 33 Door 2 Lock relay n c 34 Door 2 Lock relay pole Relay 2 1 2 or 3 door configuration 35 Door 2 Lock relay n o 36 Door 2 Door Sense Input 3 1 2 or 3 door configuration 37 OV for Door Sense and Egress 38 Door 2 Egress Input 4 1 2 or 3 door configuration 39 5V OUT 40 5V OUT 41 Reader 4 MAG DATA 42 Reader 4 MAG CLK 43 Reader 4 LED 44 Reader 4 12V 45 Reader 4
16. ices come down Most cards are passive i e contain no battery and therefore have an unlimited life Hands free High High High Can read at unwanted times e g walking down corridors past doors Most cards are active i e contain a battery and therefore have a limited life Smart Card e g Mifare High High High Can be useful where several different systems are installed and only one card per person is wanted Card security the risk of copying is not a single issue It involves the need for time equipment money and special material It also includes the risk of the copying being detected TDSi supplies a wide range of readers suitable for use with eXcel Other manufacturers readers MAY work if the interface meets the following specifications but this cannot be guaranteed please contact your supplier for guidance Mag stripe Track 2 ABA format the last 8 digits preceding the first field separator will be read as the card number Wiegand 26 bit standard format 7 bits for the 3 digit site code 15 bits for the 5 digit card number and 2 parity bits eXcel will concatenate the site code and card number to give an 8 digit card number eXcel does not limit the range of site codes that can be used page 6 6656 0396 Issue 1 Planning Card reader with keypad Security is enhanced if a person is required to enter a personal identification nu
17. ion 22 Door 1 Door sense input 23 Door 1 Door sense OV 36 Door 2 Door sense 37 Door 2 Door sense OV 49 Door 3 Door sense input 50 Door 3 Door sense OV 55 Door 4 Door sense 56 Door 4 Door sense OV Egress buttons Most egress buttons have contacts that are closed when the button is pressed If fitting one where the opposite is true make the appropriate selection in eXguard eXcel terminal Function 23 Door 1 Egress OV 24 Door 1 Egress input 37 Door 2 Egress OV 38 Door 2 Egress input 50 Door 3 Egress OV 51 Door 3 Egress input 56 Door 4 Egress OV 57 Door 4 Egress input 6656 0396 Issue 1 page 21 Installing extra features Inputs eXcel terminal Function Only available in the following configurations 36 Input 3 37 OV for Inputs 3 amp 4 1 Door 38 Input 4 49 Input 5 50 OV For inputs 5 amp 6 1 or 2 Door 51 Input 6 55 Input 7 56 OV For inputs 7 amp 8 1 2 or 3 Door 57 Input 8 Supervision options eXcel can detect and report tampering with an input if one of the two configurations below is used The two options are referred to as US and UK because of the countries in which each type is most prevalent The resistor s should be installed as close to the switch as possible to provide maximum protection To ACU 2K2 E d 10k 1 resistor supervision US for short 2 resistor supervision UK for short circu
18. it tamper detection circuit and open circuit tamper detection Relays Note that relays are limited to 30V 2A non inductive load Any load that exceeds this MUST be controlled using a suitable separate relay If the load is of an inductive nature motors bells locks relays etc then the load MUST have a suppressor fitted in the same way as for a lock eXcel terminal Function Only available in the following configurations 33 Relay 2 n c 1 Door 34 Relay 2 pole 35 Relay 2 n o 46 Relay 3 n c 1 or 2 Door 47 Relay 3 pole 48 Relay 3 n o 52 Relay 4 n c 1 2 or 3 Door 53 Relay 4 pole 54 Relay 4 n o page 22 6656 0396 Issue 1 Commissioning and Trouble Shooting Commissioning and Trouble shooting Connect the memory battery using the jumper on the eXcel board Testing the installation The installation can be tested without using the computer by doing the following 1 Apply power to the eXcel The LED on the reader s should start flashing at about two flashes per second If a door sensor is fitted to Door 1 the on board buzzer may sound after 15 seconds If this happens it is because the ACU thinks the door is open and is signalling that the door has been left open too long If the door is in fact closed this can be corrected once eXguard software is talking to eXcel Temporarily silence the buzzer by opening the door or replacing the factory fitted link across
19. mber PIN after presenting a card This makes it less likely that a lost or stolen card can be used TDSi supplies a range of readers with integrated keypads suitable for use with eXcel Other manufacturers readers MAY work if the interface meets the following specifications but this cannot be guaranteed please contact your supplier for guidance Mag stripe Track 2 ABA format the last 8 digits preceding the first field separator will be read as the card number Each key press is transmitted as a 1 digit card number Wiegand 26 bit standard format 7 bits for the 3 digit site code 15 bits for the 5 digit card number and 2 parity bits eXcel will concatenate the site code and card number to give an 8 digit card number eXcel does not limit the range of site codes that can be used Each key press is transmitted as a 1 digit card number Lock The choice of lock depends firstly on the door electric strikes or bolts magnetic locks turnstiles or barriers are all options depending firstly on the architecture and secondly on the required resistance to attack As the lock is normally located on the edge of the door furthest from the hinge double doors represent a special case unless one door is fixed closed during normal operation i e it is normally opened only for emergencies or to allow large objects to pass through Another special case is a door that swings i e opens both inwards and outwards so it can be push
20. md eenden I alde eid atd edn dal eedt 21 Egress buttons casenr YA send ee aante aaron in ade 21 Inputs aan nn RM AR ne wine a Ven ae nee UK ie isle en Ve AT AES 22 BIEN Ae 22 Commissioning and Trouble shooting sssssnssnsnsnnsnennenennenennenennenennenennenennenen 23 Testing the installation ica verderen ette A Reed nera en anna enne daan rasta 23 COMMUNICATIONS SEL Up ierre viec leali ic Wel urk da re Deb aan 23 Final configuration o ie det Mee ii A erat ee rt da me er 23 Connection tables nsansannannsnnsnnsnnnnnsnnsnnennennennennennennennennnnnnnnnnnnnnnsnnennennennene 25 Compliance with CE regulations sisi 27 FCC Regulations Notice ns tnv eyed ite tr ndn i CUR d ee RE an dau 28 CSA EMC NOCO notre eek ten Mean dad ere eat name a 28 Safety NOtICGs 5 11 2 22 029025 24 RARA SORS RURORA UAR ones SER RERUM RAD IS send essai ee iiion 29 Board layout Seer Perper per er err rerr errr iridata 30 6656 0396 Issue 1 page 3 Introduction Introduction System capabilities eXcel is a four door access control unit ACU that is administered by a computer PC running TDSi s eXguard software More than one controller can be administered simultaneously from one or more computers and TDSi manufacture several controller types besides eXcel that can co exist in a single system The software is used to monitor events and to program ACUs with card numbers access rules and other parameters such as input and relay func
21. mmunications ports Such third party equipment and all cabling must be of suitable design and installation to ensure that the overall system complies with the requirements of the EC EMC directive The equipment in OEM Module form complies with the RFI emission and immunity and electrical transient immunity regulations Compliance with the ESD regulations will be the responsibility of any installer that mounts the OEM module in an alternative outer case Guidance notes for the installation and use of TDSi equipment must be strictly followed Due to the wide range of access control products TDSi notes cannot cover all possible type and combinations of equipment that may be assembled to form a total system TDSi exercise due diligence to ensure that its equipment is suitable for use in the stated applications but ultimate responsibility for the compliance of a complete system must rest with the prime contractor at a site where local conditions may require additional EMC precautions to be taken 6656 0396 Issue 1 page 27 Safety Notices FCC Regulations Notice This device complies with Part 15 Class B of the FCC Rules Operation is subject to the following two conditions a This device may not cause harmful interference b This device must accept any interference received including interference that may cause undesired operation WARNING Changes or modifications to this unit not expressly approved by the party respo
22. necting a permanently wired mains supply to the equipment Ensure that the mains supply is SWITCHED OFF before starting any wiring Wiring should be in accordance with the current I E E regulations or the appropriate standards in your country and should be performed by a properly qualified electrician For permanently connected equipment a readily accessible disconnect device shall be incorporated in the fixed wiring Wiring should be via a switched fused spur with a 3A fuse UK rating and should use approved 3 core mains cable of minimum cross section area 0 75 sq mm The installation MUST be provided with a double pole isolator switch with a contact separation of at least 3mm The Earth wire into the terminal block should be left longer than the L amp N wires so that it is pulled out last if the cable is strained Connecting signal wiring to associated equipment The TDSi eXcel Access Control Units with an internal AC PSU mains power supply fitted must be connected to other equipment forming part of an overall control system using signal wiring connections made with screened cable with the screen securely connected to an earth point at the controlled equipment end and at earth points within the eXcel equipment Where individual remote equipment is locally earthed it is permissible to disconnect the cable screen earth connection at one end of the cable Internal fuse rating The low voltage DC Regulator PCB in eXcel is fitted with fus
23. nsible for compliance could void the user s authority to operate this equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the manufacturer s instructions may cause interference harmful to radio communications There is no guarantee however that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures e Reorient or relocate the receiving antenna e Increase the separation between the equipment and receiver e Connect the equipment into an outlet on a circuit different from that to which the receiver is connected e Consult the dealer or an experienced radio TV technician for help CSA EMC Notice This digital apparatus does not exceed the Class B Limits for radio frequency emissions from digital apparatus set out in the radio interference regulations of the Canadian Department of Communications Le present appareil numerique n emet pas de bruits radioelectriques depass
24. ocal ground If the peripheral is metal cased then the ground wire can be connected to the metal case When using RS485 communications attention must be paid to the special earthing requirements detailed in the section titled Communications In addition to these general principles it is vital to follow the specific requirements for installing peripheral equipment readers lock releases etc These requirements are explained in the relevant places of this manual Please note that in all recommendations for wire minimum gauge requirements are listed It is the responsibility of the installing company to follow all local and national electrical codes as they apply Never install any access control system until approval has been obtained from local fire authority In particular note that the use of an exit egress button may not be legal Single action exit may be required The use of shielded cable and adherence to correct grounding procedures is necessary for every connection to the controller page 10 6656 0396 Issue 1 Basic Installation Terminating screened cable at the ACU It may or may not be necessary to terminate cable screens at the ACU end The following diagrams show when it is necessary and how to do it to maximise the effectiveness of the screening When to terminate The following two diagrams show correct methods of grounding cable shields where the peripheral equipment may or may not be connected to ground alrea
25. occurrences of the door opening and closing can be monitored Also a relay can be set to operate and thereby sound an alarm if a door opens when it shouldn t i e the access control system had not released the lock or stays open for too long Note that the output from monitored mag locks is not suitable for either of these functions Egress button An Egress button allows people through a door from the secure area to a less secure area without the use of a card or PIN Pushing the button causes the lock to be released just as if a card had been entered i e for the pre programmed lock release time 6656 0396 Issue 1 page 7 Planning This is sometimes used as a reception button where someone inside the building can let someone else in More commonly the egress button permits a person to exit the building or room Although certain types of door lock mechanisms permit egress by turning the handle on the inside this may be detected by the ACU as a door forced situation In other words the door has opened but no card or PIN was used Installing an egress button bypasses this problem Note that fire regulations may also require people to be able to exit an area without depending in any way on electrical systems Door Ajar Sounder An access control system is useless if the door is propped open If a door sensor is fitted then a sounder can be used to alert anyone in the vicinity that this has happened Loud bu
26. ock requires more than 1A pull in current substitute a separate relay for the lock release shown in the diagram above and use this to switch a separate power supply Communications Single ACU over RS232 Most computers these days use 9 way connectors for serial communication ports but we ve included the connections for 25 way connectors as well PC 9 way PC 25 way eXcel terminal PC Function 2 3 7 Receive 3 2 6 Transmit 5 7 5 Ground no connection no connection 8 RTS no connection no connection 9 CTS If necessary a USB to serial adaptor may be used to add a serial port to a computer However the use of multi port adaptors is not recommended because data can be lost due to increased load on a single USB port page 16 6656 0396 Issue 1 Basic Installation One or more units over RS485 This requires the use of an RS232 to RS485 converter TDSi supply a suitable product Westermo MA 45 and the following wiring instructions relate to this converter Other manufacturers converters MAY work if the interface meets the international standards for RS485 but this cannot be guaranteed please contact your supplier for guidance IMPORTANT When connecting more than one unit using RS485 the cable must be run from unit to unit as a daisy chain Multi drop or star cable runs are not suitable for RS485 applications However it is permissible to have the cable run in two directions
27. r 1 OV Black 17 Reader 1 12V Red 28 Reader 2 12V Red 25 Reader 2 MAG DATA Yellow 26 Reader 2 MAG CLK White 27 Reader 2 LED Blue 39 Reader 2 5V Green 29 Reader 2 OV Black 28 Reader 3 12V Red 30 Reader 3 MAG DATA Yellow 31 Reader 3 MAG CLK White 32 Reader 3 LED Blue 39 Reader 3 5V Green 29 Reader 3 OV Black 44 Reader 4 12V Red 41 Reader 4 MAG DATA Yellow 42 Reader 4 MAG CLK White 43 Reader 4 LED Blue 40 Reader 4 5V Green 45 Reader 4 OV Black 6656 0396 Issue 1 page 13 Basic Installation Indala Proximity Reader 5002 0133 eXcel Reader connection Colour terminal 14 Reader 1 Wiegand 0 Green 15 Reader 1 Wiegand 1 White 16 Reader 1 LED Brown 18 Reader 1 OV Black 17 Reader 1 12V Red 28 Reader 2 12V Red 25 Reader 2 Wiegand 0 Green 26 Reader 2 Wiegand 1 White 27 Reader 2 LED Brown 29 Reader 2 OV Black 28 Reader 3 12V Red 30 Reader 3 Wiegand 0 Green 31 Reader 3 Wiegand 1 White 32 Reader 3 LED Brown 29 Reader 3 OV Black 44 Reader 4 12V Red 41 Reader 4 Wiegand 0 Green 42 Reader 4 Wiegand 1 White 43 Reader 4 LED Brown 45 Reader 4 OV Black page 14 6656 0396 Issue 1 Basic Installation Locks The following instructions assume that the lock s will be powered from the built in power supply this is subject to a maximum peak current of 1A per lock If a separate power supply is used modify the wiring accordingly IMPORTANT A suppres
28. rate wire to mains ground All cable runs must be in shielded cable The shield of each cable must be grounded at one end and at one end only This will usually be at the ACU chassis plate However if the peripheral equipment is grounded then the shield of the cable must be grounded at the peripheral end and not at the ACU end Cable runs must be at least 6 feet 2 metres long This allows induced static to dissipate before it reaches the electronics The braid of the cables or the drain wire or ground wire must be terminated to the spring earthing clamps which are mounted to the chassis plate unless the peripheral is connected to ground see below The pig tails of the screened cable should be kept as short as possible to reduce the radiating length The lengths of un shielded wire should be kept to an absolute minimum This will reduce the chances of noise pick up They must not be allowed to protrude into the area of the electronics Where metal cased peripheral equipment lock release card reader etc is to be mounted on a metal surface e g a metal doorframe ensure that the metal surface is grounded and that the cable ground wire is connected at the peripheral end The cable ground wire must not be connected at the ACU end Where peripheral equipment lock releases card reader s etc is to be mounted on a non metal surface the peripheral must not be grounded independently and the ground wire must not be taken to a l
29. sed of the possibility of such claim In no event shall seller s liability under any claim made by buyer exceed the amounts paid for the system and the use of the software in respect of which such claim is made page 2 6656 0396 Issue 1 Table of Contents Supplier informatiOn ensansansensennsnnnnnnnnsnnnnnsnnsnnennennennennennnnnnnnnnnannsnnsnnennennennene 2 Table Of Contents 5sisssssss erasegcensassiencesegeenese Aeee ERE ere en anna aiar 3 Introduction p M 4 System capabilities riri Ere erra el Ve E EE menant ela 4 Teclinical specificatlon tir tenen lates are Ee ERE tues dean ae en en 5 Planning uussssunsnsnssnensanensenensnnensnnensneensnnensnennsnennenennensnsenenssnenssnensnnennenensnnensnennnnen 6 Options to choose before starting sisi 6 Cable specifications eden aped Ai 9 Basic Installation i tvesrenssenrdeanwennnabinaendendwaenwandsenstandveernengnsnntnaidenhmdndeaandaaddesned 10 Installation do s and don ts UE a dennen neen eneen 10 Terminating screened cable at the ACU enen ennen en eee neta eens teeta 11 Readers nn RR eenden denn ed neede dead TRE Kadan es tees 13 Kel CT 15 COMMUNICATIONS reece oy viene en ee led ee eu VER EN ee 16 Installing extra featur sS sssssssnsnsnnsnsnnsnennenennenensenennenennenennenennenennenennensnnenen 20 Readers with Keypads ins iii verande recte stuwen herten denn dins at de ror Ee Tae S 20 DOOR Sensors a
30. sor MUST be fitted at the lock TDSi supplies a suitable suppressor part number 5002 0095 or a diode capacitor combination or MOV device Metal Oxide Varistor may be used Fail locked This kind of lock requires power to unlock eXcel terminal Lock connection 20 Door 1 Lock relay pole 21 Door 1 Lock relay n o 34 Door 2 Lock relay pole 35 Door 2 Lock relay n o 47 Door 3 Lock relay pole 48 Door 3 Lock relay n o 53 Door 4 Lock relay pole 54 Door 4 Lock relay n o Fail open This kind of lock is locked when power is applied eXcel terminal Lock connection 19 Door 1 Lock relay n c 20 Door 1 Lock relay pole 33 Door 2 Lock relay n c 34 Door 2 Lock relay pole 46 Door 3 Lock relay n c 47 Door 3 Lock relay pole 52 Door 4 Lock relay n c 53 Door 4 Lock relay pole Power supply for locks The built in power supply if fitted has two outputs which can supply a maximum peak current of 1A per output DO NOT combine the two supplies to provide extra current eXcel terminal Lock connection P3 Lock supply A 12V DC P4 Ov P5 Lock supply B 12V DC P6 ov 6656 0396 Issue 1 page 15 Basic Installation Lock release Suppressur Ta eXcel lock relay Gable screen must NOT be connected to ACU chassis if lock is grounded To Power Supply Gonnect cable screen to lock casing it passible If the l
31. tions The software does not need to be running continuously as ACUs hold all the information they need to provide the security features that have been set up When eXcelf is used as a two door controller four inputs and two relays become spare and may be used for monitoring and control of other equipment Feature Four door Two door configuration configuration Maximum number of 1 2 readers per door readers may have associated keypads Egress inputs Door sensor inputs Spare Inputs Spare Relays o o s A NI AININ Card capacity with eXguard Lite 5 000 Card capacity with eXguard Pro 18 000 Anti pass back with eXguard Lite Timed Anti pass back with eXguard Pro Timed or True Mantrap Yes Time groups 64 Card expiry by date Yes page 4 6656 0396 Issue 1 Introduction Technical specification Case dimensions cm 38 x 33 x 14 Environment Temperature 10 C to 40 C Humidity 0 95 rh non condensing Power 230V AC version Input 200 240V AC 80VA max Output 12V DC 1A for ACU 2 x 12V DC 1A for locks 2 x 13 6V for standby batteries Power 110V AC version Input 100 120V AC 80VA max Output as for 240V AC version Power 18V AC version Input 14 18V AC 80VA max Output as for 240V AC version Power 12V DC version Input 12V DC 500 mA max Relays Form C changeover rated at 30V 2A 6
32. zzers are very effective at persuading people not to do this in the first place eXcel has an on board buzzer that is used for this purpose but this can be disabled and an external sounder can be connected to a spare relay Inputs eXcel when used in a two door configuration has 4 spare inputs which can be used to monitor other equipment Every instance of an input going open circuit and closed circuit is logged by eXguard and can be reported on An input can also trigger a spare relay All inputs are suitable for use with supervision resistors which provide a means of detecting tampering 1 resistor supervision allows detection of a short circuit while 2 resistor supervision allows detection of both open and short circuit tampering Relays eXcel when used in a two door configuration has 2 spare relays which can be used in various ways to control another piece of equipment for example lighting heating or a sounder A relay can be triggered by one of the following e Input e Control card e Manual command e Time schedule page 8 6656 0396 Issue 1 Cable specifications Always use suitable cable Access control systems differ from intruder alarm systems in that reader and communications cables carry high speed data signals that can become distorted or corrupted if inadequate cable is used The following table lists suitable cable specifications for each type of equipment Planning

Download Pdf Manuals

image

Related Search

Related Contents

  House of Fara HT18 Instructions / Assembly  LG-E410f  グリーン調達基準書 - 中島オールプリシジョン株式会社  Microlife FH 422  INVISIO S10 Brochure.indd - Marlborough Communications Limited  svm 25 user manual in original  MSI R7870 Twin Frozr 2GD5/OC AMD Radeon HD7870 2GB  Sony DVP-K370 User's Manual  VOUS AVEZ CHOISI L`ABBAYE AUX DAMES  