Home

USER MANUAL - Kompleksmedia.pl

image

Contents

1. EEG Connecting the Multiple EBMs in rack form 1 Connect Earth line between UPS and the first EBM and then connect Earth Line between the first EBM and the second EBM Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below And then connect the battery terminal D from the first EBM to the battery terminal E from the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel R P POmer Waker Note Three or more EBMs can be connected to the UPS in the same way as shown above Note After connect the EBMs please do not forget to set the number of EBMs on LCD please refer to chapter 7 Setting by LCD module for setting method If use the nonstandard EBMs please call local dealer or distributor for setting method 1 2 Operation Do not disconnect the mains cable on the UPS or the building wiring socket grounded shockproof socket during operation as this would remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets or output terminal block even if the UPS is not connected to the building wiring socket In
2. 240 208 Press Enter button to confirm the output volt what you want LOAD Tri ja e Le LG bal Vac ER h INPUT OUTPUT Exit the setting mode to short touch the Enter button continue setting to press Select button if no any pressing on the Select or Enter button lasting for more than 10 seconds the setting mode exit automatically The output frequency string OPF Bypass status string bYPA operating mode string MOdE EBM string EbM Load segment string LS1 and LS2 would be presented circularly The only one voltage value could be selected in 208V 220V 230V 240V at any time The only one frequency value could be selected in 50Hz 60Hz at any time Bypass status could be selected in 000 or 001 Here 000 means Bypass Disable 001 means Bypass Enable The UPS would turn to bypass mode in several seconds after 28 R P POmer Waker Bypass Enable is selected and turn to no output mode in several seconds after Bypass Disable is selected Operating mode could be selected in UPS ECO CVF Here UPS means the normal inverter mode ECO EN means the high efficiency mode and CVF means the converter mode The mode change would be active only after the UPS is turned on The number of EBM could be selected in 000 to 009 Here 000 means no EBM connect
3. 2 U POWETWAKEL USER MANUAL On Line UPS 1000VA 1500VA 2000VA 3000VA Uninterruptible Power Supply System e U PowerWalker CONTENT USER MANU AL coccccdccccccctstacecasccesacetcansucsdoestsavesastedsiacadetucetatutesazcssaneez cee 1 1 Safety and EMC Instructions EE 1 E a Wl EE E Le NEE 1 LZOPOMIO ez ak Ek GREG e KASE e Jl EE SBE 9 1 3 Maintenance servicing and Tous 10 1 4 Transport srs sat oz Eo ieee eben 13 SPORO AE kad kob 13 1 6 StandardS sessneesnneeeieeeteettrtrtretttttttttttntttnnttrnnttnnttnntEnnEnnnE Ennen Enee 14 2 Description of Commonly Used Symbols 1111111211 111211112 15 Ride Lk TO d i us anaiai w EEEE 16 4 Panel Description season a aaa aaa 17 5 Connection and Operation s snssnnsssnnsazenanenaaznnazenana 19 E le EE 19 EE 19 5 3 ee GE 21 5 4 Turn on the UP 21 5 5 Test funwct na A A A AAA A A A AAAA 21 ROU Te E e BI 22 5 7 Audible alarm mute TIunchon 22 5 8 Operation procedure of external battery for long backup time model S le EE 22 6 Operating Mode for All Models ssmersseeuasanenasone 24 Gel LING MOJE eene 24 EE KEE 25 6 3 Bypass e E 25 6 4 NO output MOJE as AGES aai a 26 6 5 EPO Emergency Power Off GROW AGI kk aa 26 6 6 ECO mode Economy mode siesta eects 26 6 7 Converter mode 27 6 8 Abnormal mode 27 7 Setting by LCD Module acid ia ada kiki 28 8 Trouble Shooting uasawswczwiwiczciwwadawa wnika 3
4. 000000000000000000 OO0000000000000000 ooo000000000000000000 K D oo0o0o000000000000000 00 oooo0oo0o0000000000000 0 ooooo0o000000000000000 V e 00 000000000000000000 COO0000 0000000000000 oooooooooooooooooooo L o0o000000000000000000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o 000 0 0 00 000 0000 000 eo 0 0 0 0 0_0 0 0_0 0 0 0_0 0 0 0 0 0 0 36V amp 48V amp 72V EBM rear panel 40 o 0o 0 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 OOO0000 0000000000000 ooo0000000000000 ooo
5. UPS is running in battery mode the buzzer beeps once every 4 seconds If the ON button on the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Press the ON button once again for more than 1 second to resume the alarm function C2 m The Battery mode 6 3 Bypass mode The LCD display in bypass mode is shown in the following diagram The information about the utility power the battery level the UPS output and the load level could be displayed The UPS will beep once every 2 minutes in bypass mode The bYPA string indicate the UPS is working in the bypass mode OUTPUT The Bypass mode 25 e B U PowerWalker The UPS does not have the backup function when it is in bypass mode The power used by the load is supplied from the utility power via internal filter 6 4 NO output mode EI The LCD display in No output mode is shown in the following diagram The information about the utility power the battery level the UPS output and the load level could be displayed The STbY string indicates the UPS is working in the No output mode KA The No output mode 6 5 EPO Emergency Power Off It is also called RPO Remote Power Off On LCD display the mode string is EPO It is a special status in which the UPS would shut the output off and alarm The UPS could not be turned off by pressing OFF button on the pan
6. connected with load Battery Information Load Inform ation It indicates the battery capacity Every grid represents the capacity of 20 It indicates the load level Every grid represents the level of 20 Mode Fault Warning Information d sj LE ZZ d IS ZU Sz gt 3 SS b kb D p kb b p It Indicates the operating mode or Fault kind or Warning kind several warning kinds at the same time could be displayed alternately It indicates the UPS is in setting mode It indicates the UPS is in Fault mode or has some warnings 18 R P POmer Waker 5 Connection and Operation The system may be installed and wired only by qualified electricians EN in accordance with applicable safety requlations When installing the electrical wiring please note the nominal amperaae of vour incoming feeder 5 1 Inspection Inspect the packaging carton and its contents for damage Please inform the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to prevent it from being switched back on again 5 2 Connection 1 UPS Input Connection If the UPS is connected via the power cord please use a proper socket with protection against electric current the user can refer to below table If the UPS is connected via wires it i
7. is necessary The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible Place cables in such a way that no one can step on or trip over them Assure to connect the UPS and external battery pack with the earth reliably Do not block ventilation openings in the UPS s housing Ensure the air vents on the front and rear of the UPS are not blocked Allow at least 25cm of space on each side In case smoke is found coming out from the device please cut off the power supply quickly and contact the distributor An appropriate disconnect device as short circuit backup protection should be provided in the building wiring installation Please see the disconnect device specification in chapter 5 2 Do not keep or use this product in any of the following environments o Any area with combustible gas corrosive substance heavy dust R U POmer Waker standing water or running water o Any area with extraordinarily high or low temperature above 40 C or below 0 C and humidity of more than 90 EN o Any area exposed to direct sunshine or near any heating apparatus Maximum ambient temperature rating is 40 o Any area with serious vibrations o Outdoor e In the event that there is fire occurring in the vicinity please use dry power extinguishers The use of liquid extinguishers may give rise to the danger of electric shock 1 1 1 Inspection of Unit Inspect the UPS upon receiving If the U
8. order to fully disconnect the UPS first press the OFF button to turn off the UPS then disconnect the mains lead Ensure that no liquid or other foreign objects can enter the UPS Do not remove the enclosure This system is to be serviced by qualified service personnel only Remove the protective panel only after disconnecting the terminal connections e B U PowerWalker Use No 12 AWG for 3KS input wire 90 C copper wire and 4 4 Ib in Torque force when connecting to terminal block Use No 10AWG for all models battery wire 90 C copper wire and Anderson PP45 connectors for user s external battery cabinet 1 3 Maintenance servicing and faults 10 The UPS operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel Caution risk of electric shock Even after the unit is disconnected from the mains power supply building wiring socket components inside the UPS are still connected to the battery which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals Batteries must be replaced only by qualified personnel Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Verify that no vo
9. polarity of EPO EPO is Normally close as default setting e NO Normally the EPO connector is open on the rear panel Once the connector is closed with a wire the UPS would stop the output until the EPO status is disabled Disable the EPO status Enable the EPO status 20 R P POmer Waker e NC Normally the EPO connector is closed with a wire on the rear panel Once the connector is open the UPS would stop the output until the EPO status is EI disabled Enable the EPO status Disable the EPO status 5 3 Battery charge Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours You may use the UPS system directly without charging it but the stored energy time may be shorter than the nominal value specified 5 4 Turn on the UPS 1 With utility power connecting Press I button continuously for more than 1 second to turn on the UPS the UPS will get into the inverter mode the LCD screen will indicate the state of the UPS 2 Without utility power connecting If UPS is cold start without utility power connecting user need to push I button twice first pushing I button is for UPS to get power LCD screen show INIT And second pushing I button continuously for more than 1 second is for UPS to turns on the UPS will get into the inverter mode In fact the two pushing I button is to make further sure user operation for turning on
10. rack space EI Use the following procedure to install UPS in a rack 1 Align the mounting ears with screw holes on the side of the UPS and tighten the screw 2 Assemble the rack rails with the rack mounting 3 Slide in the UPS into the rack rail and lock it in the Rack mounting 4 Tighten the screw and then the load can be connected 1 1 4 EBM Installation Optional e Connecting the EBM in Tower form 1 Slide down the UPS and EBM vertically and place two UPS stands with the extend part at the end of the tower 2 Tighten the screw on the metal sheet for stabilization Connect the Earth line from UPS port A to EBM port B 4 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C ao e B U PowerWalker on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel ZZZZZZZA e Connecting the EBM in a rack form 1 Using the same method as assembling UPS in a rack form assemble EBM into the rack mounting on the top or bottom of the UPS EN 2 Connect the earth line from UPS port A to EBM
11. to clear it Moreover the alarm will be enabled when the battery is low to remind you to shutdown the load soon If the alarm is too annoying in bypass mode you may press button continuously for more than 1 second to clear it The action doesn t affect the warning and fault alarm If all alarm is too annoying you can short touch I button all alarms are disable if alarms need to be resumed short touch I button again 5 8 Operation procedure of external battery for long backup time model S model 1 Use the battery pack with voltage 36VDC for 1KS 12Vx3 batteries 48VDC for 1 5KS 2KS 12Vx4 batteries 72VDC for 3KS 12Vx6 batteries Connection of batteries more than or less than required will cause abnormality or permanent damage 2 One hard wiring type battery terminal on the rear panel is used for connecting the battery pack 22 R P POmer Waker 3 The battery connection procedure is very important Any incompliance may result in the risk of electric shock Therefore the following steps must be strictly complied with EN 4 lt Make sure the mains input is cut off if there is a battery breaker then turn it off first QI Remove front panel connect the battery via Anderson PP45 connectors Prepare the battery cable which should be able to carry the current of gt 50A for all models the cross section area should be great than 4 mm for all model And battery wire color
12. 0 9 Eu ue 32 _ desse CERN 32 oaz 8 GE 32 9 3 Battery REPIACO aaa AR A deen av eve dee ee ee 32 EN 10 Technical Data eessen 33 10 1 Electrical SpeCiHiCatiON esses AE A A AA 33 10 2 Operating Environment uassaccaccicaskccciaki k ia a kiki 33 10 3 Typical backup time Typical values at 25 in minutes 33 10 4 Dimensions and weights AAA 34 11 Communication Port eegeeugeeetoesgetetegegedegeeggeegtegeteeeeeeeeedeeegeediegegegg 35 11 1 RS 232 and USB communication ports ken 35 RE 35 11 3 USB p l ek ee AL LL 36 11 4 Installing a Serial Network Management Card optional 36 11 5 Dry Contact pott accccccccccensdaiedatcdenatidedateneieneiatenetasedasiantasieaaceheantacs 36 12 Software Installation csccssscssseseeeseeesseeseesseeesseeeseessenesseeeseees 38 Appendix Rear panel cccssecsesecsseeeessneseseeeessneeenenereseeesssnenenenenesnee 39 VALE ML 1 Safety and EMC Instructions SAVE THESE INSTRUCTIONS This manual contains important instructions for EN models PowerWalker VFI 1000 1500 2000 3000RT LCD that should be followed during installation and maintenance of the UPS and batteries Please read carefully the following user manual and the safety instructions before installing the unit or using the unit 1 1 Installation e This product is specially designed for PCs and it is not recommended for use in any life supporting system and other specific im
13. Over temperature fault OVTP Inverter temperature high TEPH Inverter voltage low INVL Ambient temperature high AMbH Inverter voltage high INVH Battery open bOPN Bus voltage over bUSH Overload OVLD Bus voltage Low bUSL EPO EPO Bus voltage unbalance bUSE Battery fault bATF Bus short bUSS NTC open NTCO If the UPS system does not operate correctly please attempt to solve the problem using the table below No indication no No input voltage Check building wiring socket outlet warning tone even and input cable though system is connected to mains power supply Display Mode Inverter not switched on Press On Switch I string STbY in LCD even though the power supply is available Display Mode Mains power supply has Switching to battery mode string DATT in LCD failed or Input power automatically and audible alarm and or frequency are out Check input power source and inform sounding every 1 beep of tolerance dealer if necessary in every 4 seconds Emergency supply Batteries not fully charged Charge the batteries for at least period shorter than batteries defect 5 8 hours and then check capacity nominal value If the problem still persists consult your dealer Check if the fan is running Battery over voltage Battery is over charged Stop charging to battery automatically and after the battery voltage is normal and the mains is normal charge automatically again 30 EE PowerWal
14. PS is apparently damaged during the shipment please keep the box and packing material in original form for the carrier and notify the carrier and dealer immediately 1 1 2 Unpacking the Cabinet To unpack the system 1 Open the outer carton and remove the accessories packaged with the cabinet 2 Carefully lift the cabinet out of the outer carton and set it on a flat stable surface 3 Discard or recycle the packaging in a responsible manner or store it for future use 1 1 3 UPS Setup All model series are designed for tower and rack purpose They can be installed into a 19 inches equipment rack Please follow the instruction for Tower Setup and Rack Mount Setup e Tower setup This series of UPS can be placed horizontally and vertically As a tower configuration it is provided with the optional UPS stands to stabilize the UPS when the UPS is positioned in vertical The UPS stand must be attached to the bottom of the tower Use the following procedure to install UPS in UPS stands 1 Slide down the UPS vertically and put two UPS stands at the end of the tower 2 Place down the UPS into two stands carefully O U PowerWalker 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel 20 P POmer Waker Rack mount setup The series can be installed in 19 inches racks Both the UPS and external battery enclosure need 2U of
15. SNMP slot RS232 Modem Network Surge Protection Earth Line Port z o O 0O VJO OO R O N e le ZZ Ia ZER o an e 1000VA 1500VA 2000VA Standard amp 1000VA 1500VA Super charger model rear panel e ome wf pell 8 2000VA Super charger model rear panel 39 e B U PowerWalker DI o o 250V 15A RS232 e E USB DRY OUT 8 e 3000VA Standard model rear panel e o 250V 16A mz EL EJ LS2 AC OUTPUT 250V 10A 151 AC OUTPUT 250V 10A ce oryn ZN il INTELLIGENT SLOT oryout gt CO SI CO SI MCK 3000VA Supper charger model rear panel The EBM rear panel description table and picture are shown as below No Function 36V amp 48V amp 72V EBM 1 Earth Line Port 1 0 0
16. UPS the LCD screen will indicate the state of the UPS Note The default setting for bypass mode is no output after UPS is connecting utility power and breaker is turned on This can be configured by monitoring the LCD panel or firmware 5 5 Test function 1 Real time detection UPS could do real time detection when battery connected or disconnected If the battery connection status is changed in floating mode UPS will detect the 21 e U PowerWalker change within 30 seconds in resting mode UPS will detect the change within 3 minutes 2 Manual test Test the function of the UPS system by pressing the On Switch I for more E than 1 second the UPS would detect whether the battery is connected or the battery is low immediately Also the UPS could do the test automatically and periodically the period time could be set by user the default value is 7 days 5 6 Turn off the UPS 1 In Inverter Mode Press button continuously for more than 1 second to turn off the UPS the UPS will get into no output or bypass mode At this time the UPS might has output if bypass is enabled Disconnect the utility power to turn off the output 2 In Battery Mode Press button continuously for more than 1 second to turn off the UPS the UPS will be turned off completely 5 7 Audible alarm mute function If the alarm is too annoying in battery mode you may press I button continuously for more than 1 second
17. al dealer or distributor immediately 1 3 4 Replacing UPS Internal Batteries Follow the steps and Charts as below to replace batteries 1 Take off the LCD box and remove the screws 2 Slide and Pull the front panel leftward and then take it off 3 Disconnect the cable from the UPS and battery pack 4 Remove the right inner battery bracket 5 Pull the battery pack out onto flat area 6 Install new battery pack into UPS 7 Screw up the battery bracket and reconnect the battery cable A and B 8 Re install the front panel back to UPS 12 R P POmer Waker 1 3 5 Testing New Batteries For a battery test please check e The batteries must be fully charged EN e The UPS must be in Normal mode with no active alarms e Don t take on off the load To test batteries 1 Connect the UPS to utility power for at least 48 hours to charge the batteries 2 Press and hold the T button 1 second to start the battery test on line mode or HE mode The status display string shows TEST 1 3 6 Recycling the Used Battery A Warning e Never dispose the batteries in a fire It may explode e Do not open or mutilate the batteries Released electrolyte is harmful to the skins and eyes It may be toxic A battery can present a risk of electrical shock and high short circuit current To recycle properly the used battery please do not discard the UPS battery pack and batteries into the trash bin Please follow
18. ation on your PC Connected by USB to a PC or notebook the Software enables communication between the UPS and the computer The UPS software monitors the status of the UPS shuts down the system before the UPS is exhausted and can remotely observe the UPS via the Network enabling users to manage their system more effectively Upon AC failure or UPS battery low UPS takes all necessary actions without intervention from the system administrator In addition to automatic file saving and system shut down functions it can also send warning messages via pager e mail etc eUse the bundled CD and follow the on screen instructions to install the software WinPower Enter the following serial No to install software 511C1 01220 0100 478DF2A e After the software is successfully installed the communication with UPS has been established and an green icon will appear in the system tray FB asam eDouble click the icon to use the monitor software as above eYou can schedule UPS shutdown start up and monitor UPS status through PC Detail instructions please refer to the e manual in the software A Check www powerwalker com winpower html from time to time to get the latest version of monitoring software 38 O VATA MLL Appendix Rear panel The UPS rear panel description table and pictures are shown as below Function 1000VA amp 1500VA amp 2000VA amp 3000VA AC Output EPO Dry in Communication Port USB Port AC Input Dry out
19. be shown when the load or the UPS output is short The LCD display is shown in the following diagram OUTPUT 27 R U PowerWalker 7 Setting by LCD Module The output voltage frequency Bypass status and operating mode in No output mode or Bypass mode Two Load segments in output mode The number of EBM in all mode could be set directly through LCD module The Gi output voltage could be set to 208V 220V 230V and 240V The output frequency could be set to 50Hz and 60Hz The bypass state could be set to enable and disable The operating mode of UPS could be set between the Line mode ECO mode and Converter mode The number of EBM could be set to 0 to 9 Two Load segments could be set to on and off In bypass or no output mode pressing the Enter button on the LCD panel for more than one second to enter setting mode The LCD display is shown in the following diagram The string OPV indicates that the current setting is output voltage 230Vac indicates the current default output voltage is 230Vac if you want to set output voltage press the Enter button for more than one second a flickering string 208 would be shown if the Enter button is pressed again the string 208 turn to flickerless the output volt is changed to 208V if the Select button is pressed for more than one second the next flickering string 220 appear the order of flickering string is 208 220 230
20. ed Load segment 1 could be selected in 000 or 001 Here 000 means load segment 1 off 001 means load segment 1 on Load segment 2 is the same as Load segment 1 m Here is a example for changing the Operating mode from normal mode to converter mode through the LCD panel 4 5 Imm Ria Lk bal Vac 1 md hd Vac fo tee ee NAP TD IC ye LL 7 q a 230 kd hdd i LL Livac OUTPUT LI Step 3 bYPA after pressing the Select button Step 4 MOdE after pressing the Select button press the Enter button to set mode then UPS flickering I METAL III LOAD A U h I B 770 LL hal Vac I egr L MEW OUTPUT OUTPUT Step 5 ECO flickering after pressing Step 6 CVF flickering after pressing the button the Select button Select again Press the Enter button to make sure to change the mode Short touch Enter button to exit setting mode 29 e B U PowerWalker 8 Trouble Shooting If the UPS system does not operate correctly check the operating status on the LCD display Warning String Fault String Gi Site fail SITE Inverter short SHOR Fan fail FANF Overload fault OVLD Battery over voltage over charged HIGH Inverter soft start fail ISFT Battery low bLOW Bus soft start fail bSFT Charge fail CHGF
21. ed on the top of the UPS so as to avoid such dangers as electric shock e Do not dispose of battery or batteries in a fire The battery may explode e U PowerWalker Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic Icon on the rating label stands for phase symbol A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries Remove watches rings or other metal objects from the hand Use tools with insulated handles Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When replacing batteries replace with the same type and number of the sealed lead acid batteries This pluggable type A equipment with battery already installed by the supplier is operator installable and may be operated by laymen During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole of the battery when maintenance or service work inside the UPS
22. el only after releasing EPO status by turning off the EPO switch 6 6 ECO mode Economy mode It is also called high efficiency mode In ECO mode on LCD display the mode sting is ECO After the UPS is turned on the power used by the load is supplied from the utility power via internal filter while the utility power is in normal range so the high efficiency could be gained in the ECO mode Once the mains is loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc 2 It is attention that the transfer time of UPS output from ECO mode to battery mode is less than 10ms But it is still too long for some sensitive load 26 Q PowerWatker 6 7 Converter mode In converter mode on LCD display the mode string is CVCF The UPS would free run with fixed output frequency 50Hz or 60Hz in ml converter mode Once the mains is loss or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc 2 The load should be derating to 70 in converter mode 6 8 Abnormal mode In abnormal mode such as Bus fault etc the corresponding fault string would be shown to indicate the operating mode of the UPS and the background light become red For example SHOR would
23. hen the discharging time is less than 50 of specified after full charged the battery may need to be replaced Please check the battery connection or contact your local dealer to order new battery A WARNING e Turn off the UPS and disconnect the utility power cord from the wall outlet e Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries e Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Wear rubber gloves and boots 5 Disconnect the charging source prior to connecting or disconnecting battery terminal e When replacing batteries replace with the same type and number of batteries or battery packs Contact your service representative to order new batteries e Do not dispose of battery in a fire Batteries may explode when exposed to flame e Proper disposal of batteries is required Refer to your local codes for disposal requirements e Do not open or mutilate the battery Released toxic electrolyte is harmful to skin and eyes 11 e U PowerWalker Note If you are not qualified service personnel to replace the battery do not attempt to open the battery cabin Please call loc
24. ible power supply incorporating double converter technology It provides perfect protection specifically for Novell Windows NT and UNIX servers E The double converter principle eliminates all mains power disturbances A rectifier converts the alternating current from the socket outlet to direct current This direct current charges the batteries and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains voltage In the event of power failure the maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model No on the rear panel of the UPS Model No Model No 5 Banded 5KS Extended backup 2KS time 3KS S Model Extended backup time 16 R P POmer Waker 4 Panel Description LCD Screen TEA A A l IS U ON Button OFF Button Select Button Enter Button Alarm Silence E The Display Panel Switch Function ON Button Turn on UPS system By pressing the ON Button I the UPS system is turned on Deactivate acoustic alarm By pressing this Button an acoustic alarm can be deactivated in the battery mode By short touch this Button all acoustic alarms can be deactivated in all m
25. is recommended as following GND Red wire Green Yellow wire Black wire 6 The red wire is connected to the terminal of the battery The black wire is connected to the terminal of the battery Note the green yellow wire is grounded for protection purpose 7 Make sure the wires are fasten install the terminal block cover on the rear panel of the UPS 8 Connect the UPS to the load Then turn on the mains switch or connect the power cord of the UPS to utility power supply the battery would start to be charged A Caution A DC breaker must be connected between the UPS and external battery Caution The output sockets of the UPS system may still be electrically live even if the power supply system has been disconnected or the Bypass switch is on OFF position 23 R U PowerWalker 6 Operating Mode for All Models The different string could be displayed on the LCD screen corresponding to their own operating modes and they are illustrated as the following table At any time only one normal operating string or fault string is presented But the E warning even several warnings could appear in a certain normal operating mode at one time And the normal operating mode string and the warning string would be shown circularly Once one fault is come forth then all previous warnings would not be shown again but only the fault string is presented Normal operating mode Code No out
26. ker Battery low Battery voltage is low When audible alarm sounding every second EE is almost empty Charge fall fail Notify deale ss dealer EN high UPS is too high check the ambient temperature high is too high Battery open Battery pack is not Check the battery bank is connected connected correctly to the UPS Check the battery breaker is turn on Battery fault Battery may need to be Notify dealer replaced Overload Overload Check the loads and remove some non critical loads Check whether some loads are failed Site fail Phase and neutral Rotate mains power socket by 180 conductor at input of UPS or connect UPS system system are reversed EPO function is enabled _ Turn off the EPO switch Bus fault Low high UPS internal fault Notify dealer Unbalance soft start Inverter UPS internal fault Notify dealer fault Low high soft start Over temperature fault Over temperature Check the ventilation of the UPS check the ambient temperature and ventilation NTC open UPS internal fault Notify dealer Inverter short Output short circuit Remove all the loads Turn off the UPS Check whether the output of UPS and loads is short circuit Make sure the short circuit is removed and the UPS has no internal faults before turning on again Please have the following information at hand before calling the After Sales Service Department Model number serial number Date on which the problem occurred LCD displa
27. l values 36 _ Powerttalher The following figures show schematic of the dry out in contacts Dry out Normally open Activated close Al remeron Normally open Activated by pulse signal trigger EPU Dry in contact schematic The following table shows the options for the dry out in contacts Dry out signal Description Summary Alarm Activated when any warning happens On Battery Activated when the UPS operates on battery Battery Low Activated with the oLOW alarm UPS ok Activated when the UPS has no alarms and no fault On Bypass Activated when the UPS has bypass output Dry in signal Description UPS On Off One second pulse activate if active the UPS turns off when UPS is on inverter the UPS turns on when UPS is not on inverter It is the same as a remote button to control UPS On Off status 37 e B U PowerWalker 12 Software Installation WinPower is UPS monitoring software featuring user friendly interface to monitor and control your UPS This unique software provides complete power protection for computer system while power failure With the E software users can monitor any UPS status on the same LAN Furthermore a UPS can provide security protection for more than one computer on the same LAN at the same time such as shutting down system in security saving application data and shutting down the UPS when power fails Software Install
28. ltage is present before servicing Batteries have a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures necessary when working with batteries remove all jewellery wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries replace with the same quantity and the same type of batteries Do not attempt to dispose of batteries by burning them It could cause explosion Do not open or destroy batteries Effluent electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards Do not dismantle the UPS except the qualified maintenance personnel R P POmer Waker 1 3 1 UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system EI with a vacuum cleaner For long battery life keep the UPS at an ambient temperature of 25 77 F 1 3 2 Storing the UPS and Batteries When the UPS is intended to store for a long period recharge the battery every 6 months by connecting the UPS to utility power The batteries charge to 90 capacity in approximately 4 hours However it is recommended that the batteries charge for 48 hours after long term storage 1 3 3 Time to Replace Batteries W
29. n it off first Disconnect the battery cable carefully and make sure no any exposed wires can be touched Reconnect the new batteries to the UPS by following section 5 8 Then turn on the battery breaker and press the ON switch to make the UPS do the battery test check whether the battery information is normal 32 R U POmer Waker 10 Technical Data Specyfikacja elektryczna WEJ CIE Model No 1000VA 1500VA 2000VA 3000VA Phase 1 20 Model No 1000VA 3000VA Power rating 3KVA 2 7kW Voltage Frequency Wave form Srodowisko pracy Ambient Temperature 0 C to 40 C Operating humidity Altitude lt 1000m 33 io a hee ee Ea Dane fizyczne Case EBM Case Net weight kg Model 1000 1000S 1500 1500S 2000 20005 3000 3000S Dimension mm W xH xD Eo W mm LE x H x D 438X86 5x436 438X86 5x608 72V 34 R P POmer Waker 11 Communication Port 11 1 RS 232 and USB communication ports EN To establish communication between the UPS and a computer connect a computer to one of the UPS communication ports by using an applicable communication cable A NOTE Only one of the communication ports can be active at one time The USB port has priority over the RS 232 port When a communication cable is installed the power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power envi
30. ode Do the battery test By pressing this Button the UPS can do the battery test in the Line mode or ECO mode or Converter mode OFF Button When mains power is normal the UPS system switches to No output or Bypass mode by pressing OFF Button abe and the inverter is off At this moment if Bypass is enabled then the output sockets are supplied with voltage via the bypass if the mains power is available Deactivate acoustic alarm By pressing this Button an acoustic alarm can be deactivated in the bypass mode Release the UPS from fault mode and EPO status Select Button The output voltage frequency Bypass disable enable and operating mode in No output or Bypass mode Two Load Enter Button segments in output mode The number of EBM in all mode could be selected by pressing Select Button and confirmed by pressing Enter Button 17 e U PowerWalker The LCD Display Display Function Display Function Input Information Output Information It indi i GOT Hz It indicates output oo DIr t indicates input GOD vec p voltage frequency value which are displayed alternately voltage frequency value which are displayed alternately ES It indicates the input is connected with mains and the input power is supplied from the mains It indicates the Output plug 123 It indicates the Number of the input supplied from the mains 123 It indicates the Number of the output
31. portB Take off the LCD box and unscrew the internal screws 4 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel 5 After installing the UPS into rack the load can then be connected to UPS Please make sure the load equipment is turned off before plugging all loads into the output receptacle a Unscrew e Connecting the Multiple EBMs 1000VA 1500VA 2000VA and 3000VA UPS include external battery port that allows users to connect multiple EBM in order to provide additional backup time Follow the procedure to install multiple EBM as below e B U PowerWalker Connecting multiple EBMs in Tower form 1 Connect Earth line between UPS and the first EBM and then connect Earth Line between the first EBM and the second EBM 2 Take off the front panel and connect the battery terminal A from UPS to EBM terminal B shown as below And then connect the battery terminal D from the first EBM to the battery terminal E from the second EBM Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel ai ua fa dl gji au af came
32. portant equipment e Do not connect household or other appliances or items of equipment which would overload the UPS e g laser printers hair dryers etc to the UPS output e This unit intended for installation in a controlled environment temperature controlled indoor area free of conductive contaminants e Condensation may occur if the UPS is moved directly from a cold to a warm environment The UPS must be absolutely dry before being installed Please allow an acclimatization time of at least two hours e Risk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel e The utility power outlet shall be near the equipment and easily accessible To isolate UPS from AC input remove the plug from the utility power outlet e If UPS is to be stored for a long time it is recommended to recharge the batteries by connecting the utility power to UPS switch ONT once a month for 24 hours to avoid a full battery discharge e Please do not use the UPS in excess of the rated load capacity e The UPS contains large capacity batteries So the shell shall not be opened otherwise such dangers as electric shock will be caused If any internal overhaul or replacement of the battery is required please contact the distributor e The internal short circuiting of the UPS will lead to dangers such as electric shock or fire therefore no water containers such as a water glass shall be plac
33. put mode STbY Bypass mode bYPA Line mode LINE Battery mode bATT Battery test mode TEST ECO mode ECO Converter mode CVCF 6 1 Line mode The LCD display in Line mode is shown in the following diagram The information about the utility power the battery level the UPS output and the load level could be displayed The LINE string indicates the UPS is working in Line mode ee 4 LNE vh l int op t s S 1 I Da Gin m The Line mode If output overloaded alarm will keep twice every second You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 90 of its nominal power capacity 24 Oo U POmer Waker Note Please follow the following steps to connect the generator e Activate the generator and wait until the operation is stable before supplying power of the generator to the UPS be sure that the UPS is in idle mode EI Then turn on the UPS according to the start up procedure After the UPS is turned on then the loads can be connected to the UPS one by one e The power capacity of the AC generator should be at least twice of the UPS capacity 6 2 Battery mode The LCD display in battery mode is shown in the following diagram The information about the utility power the battery level the UPS output and the load level could be displayed The bATT string indicates the UPS is working in the battery mode When the
34. ronment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment 11 2 RS 232 port The RS 232 port is available for UPS monitoring control and firmware updates To establish communication between the UPS and a computer connect one end of the serial communication cable that comes with the UPS to the RS 232 port on the UPS Connect the other end of the serial cable to the RS 232 port on a computer The cable pins for the RS 232 communication port are identified in the following illustration RS 232 communication port pin assignments Pin Signal name Function DI USTOM the UPS Unused Not applicable Tx Transmit to external device Out Rx Receive from external device In Unused Not applicable Signal common O O JO O AOIN GND tied to chassis Not applicable Unused Not applicable Unused Not applicable Unused Not applicable Unused Not applicable 35 E U PowerWalker 11 3 USB port The UPS can communicate with a USB compliant computer by using HID compatible power management software To establish communication between the UPS and a computer connect the USB cable that comes with the E UPS to the USB port on the UPS Connect the other end of the USB cable to the USB port on a computer 11 4 Installing a Serial Network Management Card optional Each UPS has one available communication bay which support
35. s recommended to select the 2 5mm wire and the GND terminal should be grounded first The UPS System has no input breaker on the standard cabinet When installing the UPS the user needs to connect the external breakers and protective components in the input terminals It is recommended to select the NFB Non Fuse Breaker instead of the traditional combination kit including breaker and fuse When selecting the NFB the user can refer to below table UPS INPUT NFB amp Power Cord amp Socket VOLTAGE CURRENT 1K S 300Vac 10A Model No 1 5K S 300Vac 12A 300Vac 16A 300Vac 20A 19 E U PowerWalker 2 UPS Output Connection The output of the UPS is IEC socket types Simply plug the load power cord to the output sockets to complete connection Use one cord for every 5A load Model No Output Socket pcs 1K S 1 5K S 2K S 8 IEC320 C13 3K S 8 IEC320 C13 1 C19 The wiring configuration is shown as the following procedure UPS power section a Remove the small cover of the terminal block b Use 2 5mm wires for wiring configuration c Upon completion of the wiring configuration please check whether the wires are securely L N PE affixed d Put the small cover back to the rear panel Output Connection diagram A Caution Do not connect equipment which would overload the UPS system e g laser printers 3 EPO Connection User can select the
36. s the optional Serial Network Management Card After you install a Serial Network Management Card you can connect an environmental monitoring probe to the UPS Note You do not have to shut down the UPS before you install a communication card To install the Network Management Card complete the following steps 1 Locate the UPS communication bay 2 Remove the two screws that secure the communication bay cover to the UPS and save the screws 3 Insert the Serial Network Management Card into the slot on the UPS 4 Secure the Serial Network Management Card to the UPS with both screws For more information about the Serial Network Management Card see the Serial Network Management Card User s Guide 11 5 Dry Contact port The UPS incorporates build in single programmable relay output with potential free contact for remote alarm indication Dry out port And incorporates single signal input Dry in port See figure in the UPS rear panel for the locations of the ports The relay output can be configured by protocol command setting the default output contact is Summary Alarm The signal input to control UPS On Off status does not need to be configured its function is the same as one button to control UPS On Off status Note The relay output contact must not be connected to any utility connected circuits Reinforced insulation to the utility is required The relay output contact has a maximum rating of 30Vac 1A and 60Vdc 2A norma
37. y status Buzzer alarm status Utility power condition load type and capacity environment temperature ventilation condition 5 The information battery capacity quantity of external battery pack if the UPS is S model 6 Other information for complete description of the problem Pn 31 e B U PowerWalker 9 Maintenance 9 1 Operation The UPS system contains no user serviceable parts If the battery service life EJ 3 5 years at 25C ambient temperature has been ex ceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged every three months for 1 2 hours You should shorten the charging intervals to two months at locations subject to high temperatures 9 3 Battery Replace If the battery service life has been exceeded the batteries must be replaced Battery replacement should be performed only by qualified personnel It recommends to shut off the UPS completely before the replacement If there is a battery breaker then turn it off first Disconnect the battery cable carefully and make sure no any exposed wires can be touched Reconnect the new batteries to the UPS by following section 5 8 Then turn on the battery breaker and start the UPS If it needs to replace the batteries while the UPS is running make sure the UPS would not shut down during the replacement If there is a battery breaker then tur
38. your local laws and regulations you may contact your local recycling waste management center for further information to dispose properly of the used UPS battery pack and batteries 1 4 Transport Please transport the UPS only in the original packaging to protect against shock and impact 1 5 Storage The UPS must be stockpiled in the room where it is ventilated and dry 13 E U PowerWalker 1 6 Standards Safety IEC EN 62040 1 1 E EMI Conducted Emission Category C1 Radiated Emission Category C1 Harmonic Current Voltage Fluctuation and Flicker Level 3 Level 3 Level 4 Level 4 Level 3 Level 3 Voltage Dips Low Frequency Signals 14 R P POmer Waker 2 Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual It is advisable to EI familiarize yourself with them and understand their meaning Symbol and Explanation Symbol Explanation Symbol Explanation Alert you to pay F A special attention Protective ground A ale E of Alarm silence Turn on the UPS KAN Overload indication O Turn off the UPS m H Battery Idle or shut down d the UPS a Recycle Alternating current Do not dispose with Om source AC ordinary trash e Direct current source DC 15 E U PowerWalker 3 Introduction This On Line Series is an uninterrupt

Download Pdf Manuals

image

Related Search

Related Contents

Manuale Tecnico - A42R2  Kingston Technology HyperX Memory modules KHX1800C8D3K2/2G  社団法人 埼玉デザイン協議会 平成22年度改訂事業報告書  Focal Little Bird Pack 2.1  View &  FM/AM CD Clock Radio  Manual - Pyramid Technical Consultants  TraTores agrícolas  Mode d`emploi  

Copyright © All rights reserved.
Failed to retrieve file