1. Installation manual for temperature sensors TD TL from SVM North Node AB The temperature sensors from SVM North Node are delivered two and two in pairs Both sensors must be installed in pipes of the same dimension and symmetrical That means that they must have exactly the same cable length between the sensors and the calculator This is very important for keeping the accuracy in the measurements The sensors are dedicated for mounting in standardised pockets with an inside diameter of 5 2 mm TL045 or direct into the flow TDA26 and TL045 with mounting kit Any extra insulation of the sensor head beyond that for the piping is not needed If one sensor is failing both temperature sensors must be replaced with new ones The temperature sensors shall then be connected to the sensor terminals in the calculator marked Pt100 Pt500 and then a symbol for high temperature forward and low temperature return Hereafter the temperatures and the temperature difference can be read on the display Sealing of the temperature sensors can be done partly with a sealing thread between the lid and the bottom of the sensor head partly between the head and the locker screw in the pocket
Download Pdf Manuals
Related Search
Related Contents
Fireboss Parts Manual INSTALLATION MANUAL Bosch_2000 WB-B2B – A WEB BEA WebLogic Adapter for Siebel User Manual User Manual - Viper Medical MRI Kits User Manual Neuroelectrics serie md english central air conditioner split system with ele マリンボーチライ トの装着レ Dimplex DFP20L-1424RA Use and Care Manual Shure BETA 27 microphone Copyright © All rights reserved.