SLTA-10 Adapter User's Guide

image

Contents

1. README TXT A description of the sample host application HA EXE An executable version of the sample host application for DOS The SLTA 10 Adapter DOS network driver must be installed to run this application HA C The main program for the example NI_MSG C A general purpose network interface library that can be used with any host application APPLCMDS C Functions to handle application layer network variable commands NI_CALLB C The host bound network management dispatcher APPLMSG H Application message handler function prototypes HA_COMN H The HA common declarations NI_CALLB H The definitions for the network management dispatcher APPLMSG C Functions to handle application network variable and explicit messages HAUIF C Command line user interface for the example IOCTL C 1 O control function for Microsoft C LDVINTFC C Device interface driver LDVINTFC H Include file for device driver interface NI_MSG H Definitions for network interface message structures NI_MGMT H Definitions for network management message structures used by the example SLTA 10 Adapter User s Guide 46 HAUIF H Definitions for the host application example user interface AKEFILE A make file script for Borland C MSOFT MAK A make file script for Microsoft C HA_V3 XIF An external interface file which may be used to bind the example with LonBuilder HA_TEST NC A Neuron C program which may be loaded intoa Neu
2. See Moden Compatibility later in this chapter for additional sample modem configuration strings typedef struct byte sub_code always 1 byte app_command value 10 byte total_size of the data string byte offset for incremental writes char cfg_string ANM_install_cfgs_request This message uses the EEPROM pool to store the modem configuration string See the section on EEPROM String Pool Managenent above for details Install Hangup String MIP mode only This message installs a hang up string which is used to terminate a connection if the DTR control fails to do so The default setting for this string is ATHO This particular sequence is useful for Hayes modems or other modems that have licensed the use of the Guard Time feature from Hayes Corporation Some so called H ayes compatible modems use other sequences A 1 5 second pause followed by the string followed by another 1 5 second pause will cause a Hayes compatible modem to enter its command state if it is in the connected state The command ATHO causes the modem to hang up typedef struct byte sub_code always 1 byte app_command value 11 byte total_size of the data string byte offset for incremental writes char hups_string ANM_install_hups_request This message uses the EEPROM pool to store the hang up string See the section on EEPROM String Pool Management above for details SLTA 10 Adapter Use
3. Table 3 Power Supply Characteristics Country or Nominal Input Inout range Frequency Input Connector Echelon Region Voltage nominal 10 Model USA Canada 120 VAC 108 132 VAC 60 Hz 2 prong NEMA 1 15P 78010 Continental 230 VAC 207 253 VAC 50 Hz 2 prong Euro Plug 78020 Europe U K 230 VAC 207 253 VAC 50 Hz 3 prong U K Plug 78030 Japan 100 VAC 90 110 VAC 50 60 Hz 2 prong NEMA 1 15P 78040 SLTA 10 Adapter User s Guide 22 Table 4 provides the specifications for power inputs to the SLTA 10 Adapter The barrel connector input J 2 is a standard female power plug with a 2 1 mm inside diameter and 5 5 mm outside diameter LZR Electronics part number HP 114A Radio Shack catalog number 274 1569 or equal A surge protector may be required between the AC mains and the power supply as neither the power supply nor the SLTA 10 Adapter include surge protection Power supply jack J 3 provides screw terminals via a Weidmuller PN 11261 input connector provided for connection to a 9 30VAC DC power supply Table 4 Two Prong SLTA 10 Adapter Power Supply Requirements Power Minimum Nominal Absolute Maximum Unregulated 9 VDC 12 VDC 30 VDC DC Unregulated 9 VAC 24 VAC 30 VAC AC When power is connected the yellow service LED will briefly flash and the green power indicator LED will turn on Once an SLTA 10 Adapter is powered and configured the service LE
4. The UNIX network driver uses the UNIX serial port driver for all low level serial 1 O and interrupt support This simplifies the driver and also simplifies porting between different versions of UNIX The serial device is opened by the 1dv_open function and closed by the ldv_close function Data are read from and written to the serial device using the UNIX read andwrite system calls SLTA 10 Adapter User s Guide 79 The UNIX network driver includes a 1dv_post_events function that should be called periodically from the client application in order to assure that the SLTA 10 Adapter traffic is being processed The DOS network driver serial I O functions are implemented by MSD_STO C MSD_UART H and MSD_TROQC ASM These files may all be replaced as long as the required serial I O functions in MSD_STO cC are provided The definitions of the UART registers arein MSD_UART H The DOS serial I O interrupt service routines are in MSD_IROC ASM The DOS network driver uses the DOS system timer tick interrupt vector 0x1C and the serial I O device interrupt for the relevant COM port to perform background processing of the serial network interface The driver hooks into these interrupt vectors and executes driver code whenever the LON n device is opened Flags internal to the driver prevent the interrupt code thread from interfering with the normal application foreground execution of functions within the driver The smip_int_main function in
5. you may want to use a unique unused IRQ for that port Many serial ports and internal modems allow the selection of a non standard IRQ such as RQ2 or IRQ5 Enables communications interrupt chaining Some PCs may incorporate up to four serial ports If supported by the serial hardware COM1 and COM3 may share the same interrupt as do COM2 and COMA4 This option may enable the driver to support the shared interrupt by chaining to the interrupt vector that was in place when the driver was loaded This option is not necessary if your system does not use COM3 or COM4 or if COM3 or COM4 use a different interrupt request number When installing two SLTA 10 Adapter network drivers on a system on COM 1 and COM3 or COM2 and COM4 with the same interrupt request number the last installation of the driver should use this option Hereis an example of a coNFIG Sys file entry for such a system DEVICE C LONWORKS BIN LDVSLTA SYS B38400 A P1 DEVICE C LONWORKS BIN LDVSLTA SYS B38400 A P3 C Table 14 Hardware Configurations COM Ports Device I O Address Interrupt May be changed with the U option Defines the flush retry count in 55ms intervals This value is used in error states for re transmitting requests and for terminating receive flushes when input errors occur Normally this option should not be specified Includes a delay of lt nnn gt microseconds when transmitting downlink This
6. The UNIX network driver is a source library that uses the UNIX serial device driver It also supports the ldv_open ldv_read ldv_write and 1ldv_close functions Implementing an SLTA 10 MIP Mode Network Driver The network driver manages the physical interface with the SLTA 10 Adapter implements the network interface protocol performs flow control manages input and output buffers and provides a read write interface to the host application Figure 31 illustrates how the network driver fits into the host application architecture SLTA 10 Adapter User s Guide 78 Host Application Host Application Driver services open close ioctl read write Output Buffers Input Buffers Downlink Flow Control Uplink Flow Control l Buffer Request Protocol XON XOFF Protocol Network Driver Host Interface Transport Protocol Reliable or None Interface Link Protocol ALERT ACK or Buffered ae a a Physical Layer Interface EIA 232 SLTA 10 Network Interface LONWORKS Network Figure 30 Host Application Architecture To implement an SLTA 10 MIP mode network driver for a host other than DOS Windows or UNIX follow these steps 1 Implement and test low level serial I O Serial O may be performed directly to the host s UART as is done in the DOS network driver or may be performed by a serial 1 0 driver on the host as is done by the UNIX network driver Serial I O should be interrupt driven for better performance
7. This and other cables used with the SLTA 10 Adapter are described in detail in the chapter Attaching the SLTA 10 Adapter to a PC Most PC serial I O ports have a 9 pin male DB 9 connector although some have a 25 pin male DB 25 connector Most serial O ports are hard wired as DTE devices If connecting to a PC or modem equipped with a DB 9 connector then use a straight through cable with one end terminated with a DB 9 male connector and the other end with a DB 9 female connector Plug the male end into the SLTA 10 Adapter and the female end into the serial I O port Table 5 PC DB 9 to DB 9 Connection Signal Name PC Connector Cable DB 9 Cable DB 9 SLTA DCE DB 9 Male Female Male DB9 Female RxD Pin 2 Pin 2 Pin 2 Pin 2 TxD Pin 3 Pin 3 Pin 3 Pin 3 Signal Ground Pin 5 Pin 5 Pin 5 Pin 5 SLTA 10 PC DTE il DCE DB 9 DB 9 female end male end Figure 5 DB 9 to DB 9 Connection SLTA 10 Adapter User s Guide 26 If using a PC or modem equipped with a DB 25 connector then use a cable equipped on one end with a DB 25 female connector and a DB 9 male connector on the other end Plug the male DB 9 connector into the SLTA 10 Adapter and the female DB 25 connector into the PC Table 6 PC 25 Pin to DB 9 Connection Signal Name PC Connector Cable DB 25 Cable DB 9 SLTA DCE DB 25 Male Female Male DB 9 Female RxD Pin 3 Pin 3 Pin 2 Pin 2 TxD Pin 2 Pin 2 Pin 3 Pin 3 Sig
8. for piecemeal writes char dir_string ANM_install_dir_request See the section on EEPROM String Pool Managenent above for details on the EEPROM string pool Dial From Directory Using one of the directory entries specified by dir_num dial out to a remote host and establish a connection Based on the mode argument the directory string may be sent to the modem and the SLTA 10 Adapter enters the CALL_IN_PROCESS state Connection progress may then be checked periodically by interested nodes using the Connection Status Query message The mode parameter is used to control the connection state of the SLTA 10 Adapter The values for this parameter are 1 Initiate a dial out connection If the SLTA 10 Adapter is already currently connected preserve that connection and ignore the message The SLTA 10 Adapter s connection status changes from IDLE to CALL_IN_PROCESS unless the connection is already made in which case the state stays at CONNECTED The dial out prefix is sent first 2 Sameas 1 but disconnect hang up if currently connected before initiating the new connection typedef enum DIAL_OUT 1 HANGUP_DIAL_OUT 2 STR_mode typedef struct byte sub_code always 1 byte app_command value 7 STR_mode mode byte dir_num value 0 7 for MIP 0 4 for NSI ANM_dial_dir_request If the directory entry does not exist the response to this message will indicate a failure A successful
9. parameter can be used to pace the rate at which bytes are transmitted downlink to the SLTA 10 Adapter and may be required for high performance network management tools such as LonMaker The delay is executed following the transfer of each data byte to the host s UART and only after the first 15 bytes have been sent Since the SLTA 10 Adapter employs a 16 byte deep FIFO buffer in its UART the first group of bytes sent do not need to be paced SLTA 10 Adapter User s Guide 70 Z The pacing delay will have no effect unless it is greater than the actual period it takes to transmit a single byte at the given serial bit rate The time taken to transmit a byte is 173 us at 57 600 bps and 86 us at 115 200 bps This option should be used at 115 200 bps if messages greater than 16 bytes are to be transmitted A value of W120 is suggested This option is not required at the serial bit rate of 38 400bps or slower By default the SLTA 10 MIP mode firmware disables network communications after a reset by entering a FLUSH state This state causes the SLTA 10 Adapter to ignore all incoming messages and prevents all outgoing messages even service pin messages The SLTA 10 MIP mode network driver for DOS automatically enables network communications when the SLTA 10 Adapter is opened and when it receives an uplink message from the SLTA 10 Adapter indicating that it has been reset However the host application itself must explicitly enable network communic
10. the default or a Hangup operation For example a host application that needs to communicate with a remote SLTA 10 Adapter can be invoked from a DOS batch file with preceding and subsequent calls to HCU Prior to invoking the application HCU is called to connect to the remote SLTA 10 Adapter Following execution of the host application HCU is called to disconnect from the remote SLTA 10 Adapter Ddevname To select anon default device name where devname is the device name default LON1 Ppassword Toindicate a password where password is a string of up to 8 characters which will be sent downlink to the remote SLTA 10 Adapter once the connection is made Each character in the password string may be any eight bit value Non printable characters may be represented by hex or octal values in the same format as for C strings such as x10 or 020 Tnnn To select a non default connection wait time of nnn seconds the default is 60 seconds This value limits the period for which HCU will wait for a connection to be completed Bbps To change the LDVSLTA network driver serial bit rate The default is the current setting of the network driver This controls the link rate between the host computer and the modem The acceptable values for the bps value are the same as those available on the SLTA 10 Adapter 1200 2400 9600 14400 19200 38400 57600 and 115200 N To enable the buffered link protocol and disable the ALERT ACK link pr
11. 3 51 does not include the 32 bit TAPI services used by the SLTALink Manager software Upon invocation of the SLTALink Manager software SLTALINK EXE the main screen appears shown in figure 18 SLTA 10 Adapter User s Guide 50 Figure 18 Wena Mai Qh SLTALink Manager Of x Screen Link Line Devices Help _ slezle a 2 Establishing a Communicat ions Line for Dialing in to a Network G 3 T0 TO WM ta m Selected link Local SLTA 10 Idle a communications line is the first task to be completed Figure 19 displays the message that appears when Dialing Preferences is chosen from the Line menu This message will only appear when telephony information has not been provided This case usually occurs if the computer has never been configured to use a modem Fig Oi SLTALink Manager OF x ur Link Line Devices Help e JE 19 j lja a 3 Configuration information relating to Telephony services appears to be corupt 7 This could be the first time you have used the Telephony services me Us e Message SLTA 10 Adapter User s Guide 51 This message in figure 19 may not be visible due to being covered by the SLTALink Manager Dialing Preferences window Moving the Dialing Preferences window should reveal the message if it exists This leftmost window shown in figure 20 will display 22 for the Dialing from indicator if there has been no dialing location created chosen Dialin
12. 4 must bein the buffered protocol state UP position When using this protocol the link layer header contains a length byte followed by a one s complement of the length byte These values are always validated by the receiver before accepting the rest of the message Following the length bytes is the network interface command See Appendix D of the Host Application Programmer s Guide for a description of the command byte structure If the message contains a data field it follows the command byte Finally a checksum terminates the sequence Sender Receiver ALERT 01 Link Layer Header network interface Me command Figure 32 SLTA 10 Adapter Buffered Link Protocol The length byte value describes the length of the network interface command byte plus the length of the data field This value will always be at least 1 The checksum is a two s complement of the sum of the command byte and all of the bytes in the data field if it exists Checksum errors detected by the host will cause an error to be reported to the application and checksum errors detected by the SLTA 10 Adapter will cause the message to be ignored This protocol is used when the host is capable of accepting asynchronously occurring input data without losing characters The host is also relieved of the obligation of responding to an ALERT character within 50 ms This protocol may therefore be used by an application level handler calling an interrupt driven buffered
13. Adapter to dial out and always have that SLTA 10 Adapter connect to the same remote PC Make sure that the NSI EEPROM is configured correctly See figure 27 e IfLNS is connected to the network through modems dedicate one SLTA 10 Adapter in the network to handle dial out and dial in with this PC that has the NSS server Make sure that the NSI EEPROM is configured correctly See figure 28 SLTA 10 Adapter User s Guide 62 e Several PCs can share one SLTA 10 Adapter as long as the calls are all initiated on the remote PC hosts i e dial in only and each remote LNS application removes the bound connections to its host before terminating See figure 29 Host Monitoring Application Remote LCA Driver Interface SLTALink Manager and Network Driver Modem Dial out Modem Null Modem Cable SLTA 10 Adapter Transceiver Interface LNS Server LonWorks Devices Figure 27 Dedicated SLTA 10 Adapter using Dial out SLTA 10 Adapter User s Guide 63 Host Monitoring Application LNS Server Driver Interface SLTALink Manager and Network Driver Modem Dial in and Dial out to the LNS Server Modem Null Modem Cable SLTA 10 Adapter Transceiver Interface LonWorks Devices Figure 28 Dedicated SLTA 10 Adapter hosting the NSS SLTA 10 Adapter
14. C SLTA 10 Adapter User s Guide ECHELON Corporation 078 0160 01B Echelon LON LONWORKS LONMARK Neuron 3120 3150 LonBuilder NodeBuilder LonTalk and LonManager are trademarks of Echelon Corporation registered in the United States and other countries LonMaker and LonSupport are trademarks of Echelon Other brand and product names may be trademarks or registered trademarks of their respective companies Neuron Chips Serial LonTalk Adapters and other OEM products were not designed for use in equipment or systems which involve danger to human health or safety or a risk of property damage and Echelon assumes no responsibility or liability for use of the Neuron Chips or Power Line products in such applications Parts manufactured by vendors other than Echelon and referenced in this document have been described for illustrative purposes only and may not have been tested by Echelon It is the responsibility of the customer to determine the suitability of these parts for each application ECHELON MAKES AND YOU RECEIVE NO WARRANTIES OR CONDITIONS EXPRESS IMPLIED STATUTORY OR IN ANY COMMUNICATION WITH YOU AND ECHELON SPECIFICALLY DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written
15. Indicator Switch LED Block Transceiver Section J3 Power Input J1 J2 Network Power Input Connector SLTA 1 ECHELON 1996 Figure 4 SLTA 10 Adapter Without Enclosure Component Side View from Top Switches Indicators and Connectors ESD Waming This product contains components which are sensitive to static electricity Before installing or removing the network or serial cables touch earth ground with your hand to discharge any static electricity which may have accumulated SLTA 10 Adapter User s Guide 20 Table 2 describes the external connections and switches LE Ds on the SLTA 10 Adapter Table 2 SLTA 10 Adapter Interfaces Service Button S2 Pressing this switch grounds the service request pin on the Neuron Chip within the SLTA 10 Adapter While this switch is pressed the service LED should light to maximum intensity If Switch 3 the Network Disable switch on the switch block S1 is in the ON up position the service LED will light but no service message will be sent if after power up but before an application has configured the SLTA 10 Adapter Service LED Yellow LED Indicates that either the Service Button is being DS1 pressed or if not The SLTA 10 firmware has detected an unrecoverable error and or the node is Applicationless Reboot the SLTA 10 Adapter from another network interface on the channel blinking Node is unconfigured off Node is configured or there is no power Check LE
16. Installation Overview engineering bulletin number 005 0006 01 Unique installation requirements of host applications are described in Chapter 3 of the LONWORKS Host Application Programmer s Guide Installing with LNS With LNS the SLTA 10 Adapter is initialized automatically as part of the system open Prior to the system open the application selects the desired network interface See the Chapter 3 Initializing and Terminating LCA Applications in the LCA Object and Data Seve Programmer s Guide for code fragments Installing with the LonBuilder or NodeBuilder Tools An SLTA 10 Adapter node can be installed on a development network using the LonBuilder Network Manager Chapter 6 of the LonBuilder User s Guide describes how to define and install nodes in a development network using the LonBuilder Network Manager A prerequisite to creating application node target hardware and node specifications is to define the channels that will be included in the network as defined under Defining Channds in Chapter 10 of the LonBuilder User s Guide Select the standard transceiver type compatible with the transceiver on your SLTA 10 Adapter node SLTA 10 Adapter User s Guide 93 When creating a hardware properties definition for a custom node to represent the SLTA 10 Adapter node set the input clock rate to 1OMHz Then create a hardware definition for the custom node specifying these hardware properties The SLTA 10 Adapter will not accept an incorrect c
17. MIP mode EEPROM pool This allows flexible utilization of the SLTA 10 Adapter s MIP mode EEPROM space The MIP mode pool consists of 21 blocks each with 9 bytes of data storage space A string occupies one or more blocks For the SLTA 10 NSI mode the EEPROM pool consists of the following strings e Uptofive dial out directory entries These may be used by index to initiate a dial out connection and may contain any combination of AT commands and numbers e One modem initialization string This string is used to initialize the modem as required e Onedial out prefix string This string is sent as a prefix to any dial out operation to specify the modem dial command and to indicate whether tone or pulse dialing should be used e An 8 byte dial in password string e A 1 byte code that enables an auto dial out on a network variable message e A 1 byte code that enables an auto dial out on a NSI message e A 1 byte code that enables callback EEPROM storage and allocation for these strings is managed by the NSI mode EEPROM pool This allows flexible utilization of the SLTA 10 Adapter s NSI mode EEPROM space The NSI mode pool consists of 8 blocks each with 12 bytes of data storage space A string occupies one or more blocks The NSI mode EEPROM pool does not require the exclamation point translated to a carriage return in the dial directories whereas it is required in the MIP mode EEPROM pool In addition the NSI mode EEPROM pool doe
18. SLTA 10 Adapter User s Guide 109 109 110 110 110 111 113 114 115 116 116 117 119 120 120 120 120 121 121 123 124 125 126 127 128 10 Chapter 1 SLTA 10 Adapter Overview The SLTA 10 Serial LonTalk Adapter Models 73351 73352 and 73353 is a network interface that enables any host processor with an ElA 232 serial interface to connect toa LONWORKS network The SLTA 10 Adapter extends the reach of LONWoRKS technology to a variety of hosts including desktop laptop and palmtop PCs workstations embedded microprocessors and microcontrollers The SLTA 10 Adapter has two modes of operation NSI and MIP modes The SLTA 10 NSI mode is compatible with LNS based applications The SLTA 10 MIP mode is compatible with legacy applications based on the LonManager API or the HA host application software The SLTA 10 MIP mode is a replacement for the SLTA 2 Serial LonTalk Adapter An externally accessible DIP switch determines the mode of operation SLTA 10 Adapter User s Guide 11 Introduction The SLTA 10 Adapter is the latest addition to the SLTA product family It is an ElA 232 formerly RS 232 compatible serial device that allows any host with an El A 232 interface and proper software to communicate with a LONWORKS network An SLTA 10 Adapter enables the attached host to act as an application node on a LONWORKS network When used with a PC host and the LNS Developer s Kit for Windows software the SLTA 1
19. Some modems cannot handle being sent an entire configuration string following these first two characters during this link rate sensing phase One way to accommodate these modems is to add an extra AT command followed by a delay to the front of the configuration string For example AT ATEQ amp C1 amp D2S0 1 This will allow the modem time to become fully synchronized with the new link bit rate before sending any actual command strings to the modem SLTA 10 Adapter User s Guide 121 SLTA 10 Adapter User s Guide 122 Appendix A This appendix describes the function and use of the LONWoRKS DLL interface software provided with Echelon s Connectivity Starter Kit Microsoft Windows 3 1x supports access to DOS drivers through an interface layer called DOS Protected Mode I nterface DPMI This interface standard defines the requirements to switch the processor between protected Windows and Real DOS mode operation and also the mechanisms for proper data transfer between code running in these operating environments Using DPMI the same driver may be used in DOS Windows 3 1x and Windows 95 without modification The DPMI layer that allows access to the LDVSLTA SYS and other DOS drivers provided by Echelon is contained in the Windows 3 1x DLL WLDV DLL This DLL is part of the LonManager API for Windows and the LonManager DDE Server It is also supplied on the Windows 3 1x DLL diskette The LonManager API provides high level fu
20. User s Guide 64 Host Monitoring Application Remote LCA Driver Interface SLTALink Manager and Network Driver Modem Ss Dial in Host Monitoring Application Remote LCA Driver Interface SLTALink Manager and Network Driver Modem a Modem Null Modem Cable SLTA 10 Adapter LNS Server Transceiver Interface LonWorks Devices Figure 29 Shared SLTA 10 Adapter using Dial in SLTA 10 Adapter User s Guide 65 SLTA 10 Adapter User s Guide 66 Chapter 8 Using the DOS Driver with SLTA 10 MIP Mode This chapter describes the DOS network driver supplied with the Connectivity Starter Kit The DOS network driver provides a device independent interface between a DOS or Windows 3 1x host application and the SLTA 10 Adapter in MIP mode The driver is configurable to use one of four PC AT serial ports COM1 through COM4 at one of eight serial bit rates Skip this Chapter if you are using the SLTA 10 NSI mode SLTA 10 Adapter User s Guide 67 Installing the SLTA 10 MIP Mode Driver for DOS TheDOS driver is supplied on the floppy disketteindluded with the Connectivity Starter Kit Thelatest version of this driver may be obtained from the E chdon web site The SLTA 10 MIP mode network driver for DOS is installed by adding a DEVICE comm
21. User s Guide 31 Network Disable Switch3 CFG1 Network Disable On Network Enable default Disable Off Figure 13 SLTA 10 Adapter Network Switch 3 CFG1 Switch 3 CFG1 enables down position or disables up position network communications after reset If disabled the SLTA 10 Adapter will not be able to communicate on the network after a reset until it receives an niFLUSH_CANCEL command from the host The SLTA 10 Adapter prevents network communications by entering a FLUSH state This state causes the SLTA 10 Adapter to ignore all incoming network messages and prevents all outgoing network messages even service pin messages In the disabled state if the service pin is pressed the service LED will light but no service message will be sent This FLUSH state is provided to prevent any other network management tools from performing network management functions on the SLTA 10 Adapter before the SLTA 10 Adapter s host has a chance to perform any of its own network management functions This state is canceled with the niFLUSH_CANCEL command from the host An SLTA 10 Adapter network driver may automatically enable network communications when the SLTA 10 Adapter is opened For example by default the DOS network driver enables network communications by automatically sending the niFLUSH_CANCEL command when the SLTA 10 Adapter is opened and when it receives an uplink message from the SLTA 10 Adapter indicating that it has been
22. an orange two conductor block type Use the 2 pin conductor that comes with the SLTA 10 Adapter to connect to the twisted pair network If connecting to a network which currently has an RJ 45 type connector only the wires attached to pins one 1 and two 2 of the RJ 45 connector are needed These are the wires that need to be stripped inserted and screwed into the SLTA 10 Adapter terminal block J 1 See figure 9 for a diagram of the RJ 45 Terminal Block Figure 9 RJ 45 Terminal Block SLTA 10 Adapter User s Guide 28 Chapter 4 Hardware Configuration This chapter describes how to install and configure an SLTA 10 Adapter SLTA 10 Adapter User s Guide 29 Configuring the SLTA 10 Adapter Hardware There are eight configuration switches on the SLTA 10 Adapter s switch block S1 These inputs are read by the SLTA 10 firmware to configure or enable features Figure 10 shows the factory default settings for the SLTA 10 Adapter Changes to the switch configurations will not occur until the power is cycled on the SLTA 10 Adapter The switches are read immediately after a power reset The NSI switch selects between the legacy SLTA 10 MIP mode and a serial Network Services Interface NSI mode i om ON up HTE A _ 1234567 8 b Y N gt OFF down Figure 10 SLTA 10 Adapter Default Switch Settings Configuration Options Interface Link Protocol Control Switch1 CFG3 Buffered Link Protocol ALERT ACK Li
23. create a separate link for each SLTA 10 Adapter Each link then stores the Remote Identifier of its SLTA 10 Adapter after the first connection Upon connection the appropriate application and command line arguments stored in the link get launched A second viable approach is to create a generic link that uses the wild card as a Remote Identifier to launch a generic application using command line arguments to specify the appropriate network or database and device driver name These arguments are available and described above under Invoking an Application Note if the device driver information used in the application does not match the device driver name being used by the link the newly launched application can open a second device driver which may result in an attempt to dial in to the network Since the modem is still presumably in use with the original dial out call to the host PC the second call will fail The result is a system level failure Dial In Dial Out These scenarios are the combinations and permutations of the above However it needs to be pointed out that not all dial in strategies can co exist with all dial out strategies For example if the dial out strategy involves having the SLTALink Manager match the incoming call to the wild card Remote Identifier and if the dial in strategy requires a separate link for each SLTA 10 Remote Identifier then it is possible that a call initiated from the network will be received by the SLTA
24. following naming conventions are used to identify the type of device driver being used LONn DOS Device Driver named Lonn where nisa number from 1 to 9 handle short far Pointer to an integer in which the open function will return a handle to be used to identify this device in other driver functions SLTA 10 Adapter User s Guide 126 Idv_read Purpose Retrieves an available message from the network interface hardware The function returns immediately when no messages are available An error is returned when the next available message is longer than the specified buffer length Syntax include lt ldv h gt short ldv_read short handle See Also ldv_write Returns LDV_OK LDV_NO 0 T_OF P EN 3 LDV_D EVICE ERR 4 LDV_NO_MSG_AVAIL 6 LDV_INVALI Parameters handle msg_p len D_BUF_LEN 9 hort n void far short SLTA 10 Adapter User s Guide void far msg_p short len Message read and placed in the buffer pointed to by msg_p Invalid handle or device not open Error occurred accessing device No message available Invalid buffer length Device identifier returned by 1dv_open Pointer to the buffer into which the message will be placed Length of buffer in bytes 127 Idv_write Purpose Delivers a message to the network interface hardware Syntax include lt ldv h gt short ldv_write short handle void
25. host mode When this timeout occurs the SLTA 10 Adapter discards the downlink buffer and returns to the NORMAL state If the reliable transport protocol is enabled the SLTA 10 Adapter also sends a NACK byte after this timeout SLTA 10 Adapter User s Guide 85 Uplink Message Life The uplink message life is the maximum allowable period between the SLTA 10 Adapter sending an ALERT byte to the host and the host responding with an ALERT ACK byte This period is 100ms in local host mode and 1 second in remote host mode When this timeout occurs the SLTA 10 Adapter will resend the ALERT byte This process is repeated until 3 seconds have elapsed after which the uplink message is discarded This timeout only applies to the ALERT ACK link protocol and is not used for the buffered link protocol ACK NACK Receive Timeout When using the reliable transport protocol the SLTA 10 Adapter will wait for the ACK or NACK byte to be sent downlink following the end of the uplink transmission of a message This period is 1 second after which the SLTA 10 Adapter will re send the uplink message Uplink Timeout Message Retry Count When using the reliable transport protocol the SLTA 10 Adapter will re send uplink messages whenever the ACK NACK timeout period has elapsed This retry process is limited to 5 retries after which the uplink message is discarded There is no retry limit applied to resends due to the reception of the NACK byte Session Layer Protoc
26. is chosen from the Line menu Only one line or modem can be monitored at a given time by the SLTALink Manager software However multiple modems may be used for dialing into a network concurrent with monitoring the one modem SLTA 10 Adapter User s Guide 53 Monitor Line Figure 23 SLTALink Manager Monitor Line Window The option list box will display the list of modems which have been set up for use on this computer The list can be created modified by using the Windows Modem Control Panel Select the line modem to be used for incoming calls then click OK Establishing Remote and Local Network Sites Choosing Select Action from the Link menu will display a screen similar to the screen shown in figure 24 Figure 25 shows the default local setup SLTAL ink Ss election Local SLT4 10 Local COM1 Figure 24 Completed SLTALink Selection Window Local SLTA 10 Figure 25 Default SLTALink Selection SLTA 10 Adapter User s Guide 54 Select Local SLTA 10 and click Edit This action will present a window allowing the ability to customize the connection including changing it from Local to Remote or modifying the name Name of Link The name of the link should be fairly verbose and or something easy to understand This is the descriptor for the connection and location Remote Identifier The Remote dentifier is used to identify a specific link when a dial in to the computer occurs It represents the remo
27. it to pick up and connect when dialed up Set the modem s SO register to a non zero value Modems Will Not Connect This is an unusual case with current modems which utilize modulation scheme fallbacks and error control negotiation fallbacks One rule for modem modulation speed configuration is that if your modem can be configured to connect at the speed of the last AT command do so Also be sure that the modems connect carrier Register S7 wait time is sufficient Start with 60 seconds SLTA 10 Adapter to Host Link Fails Completely This can be observed as repeated retries at the link layer when the first actual downlink or uplink transfer is attempted This can be due to any of the following conditions in order of likelihood e Mismatched network interface link protocols One end is using the ALERT ACK link protocol and another is using the buffered link protocol These settings are determined on the SLTA 10 Adapter by Switch1 CF G3 and in the host by network driver switches The ALERT ACK link protocol should be used OF F down position for Switch1 CF G3 on the SLTA 10 Adapter e Using the Host Connect Utility in the wrong network interface link protocol HCU can and may modify the current configuration of the DOS network driver Ensure that the command line switches for the HCU maintain the desired network interface link protocol and serial bit rate settings For example you may have used the N option with the DOS device driver b
28. mask defining which of the driver modes is to be changed and the mode_aux field specifies bits defining the new states of those modes It is possible to set more than one of the modes by OR ing the following bit masks together 0x0001 Enables modem support 0x0002 Allows modem responses to host same as the Q option SLTA 10 Adapter User s Guide 74 0x0004 Forces direct modem mode In this mode the network driver is communicating directly with the modem 0x0010 Enables the buffered link protocol and disables the ALERT ACK link protocol same as the N option 0x0020 Enables the reliable transport protocol The m option corresponds to 0x0021 Sub command 2 is used to set the state of the DTR line In this case the DTR signal is enabled on if the mode field is true Sub command 3 is used to set the serial bit rate of the serial interface The mode field determines the new bit rate as follows 0 14 400 1 1 200 2 2 400 3 9 600 4 19 200 5 38 400 6 57 600 7 115 200 Using the SLTA 10 MIP Mode under Microsoft Windows 3 1x In order to use the SLTA 10 MIP mode network driver for DOS under Microsoft Windows 3 1x an interface based on the DOS Protected Mode Interface DPMI must be provided This type of interface in the form of Windows DLL software is supplied with the Connectivity Starter Kit as well as with the LonManager API for Windows and LonM anager DDE Server The interface software is called WLDV DLL See Appendix A
29. network no longer requires the host application to be up and running When the host application receives this network variable it should enter a shut down routine This approach places the responsibility on the network to determine when the host application is needed and requires a hook in the monitoring application but provides a level of automation when dial out is used The third approach is the most blunt In this scenario the remote host application terminates itself either after completing a series of actions or based on a timer We do not recommend this scenario for the general scenario but it has certain appeal for some applications For example a connection may be established through dial in or dial out based on a timer The host application could then take a series of measurements from the network log them to a file and then terminate itself Monitoring Missing Messages after a Dial Out In general the message that triggers a dial out from the SLTA 10 on the network to a remote PC host is lost When a network variable update is sent to the SLTA 10 Adapter and no phone connection is currently up and running the SLTA 10 Adapter is typically configured to dial out to the host On the remote PC host the incoming call is answered by the SLTALink Manager application The SLTA 10 Adapter User s Guide 61 SLTALink Manager then reads the Remote dentifier in the SLTA 10 Adapter and searches through all the s10 files for a match T
30. of RAM for buffers The following tables summarize the memory usage of the default configurations for the respective two firmware versions resident on the SLTA 10 Adapter The tables also list the maximum size of the buffer memory pool If the SLTA 10 Adapter is configured to use more bytes than are available in the pool it will behave erratically since the RAM is used by the SLTA 10 firmware Table 11 SLTA 10 Adapter Default EEPROM Configuration Configuration Parameters nal State Explicit addressing Network variable processing Program ID string SLTA10 Mip Mode 80 00 01 01 03 00 xx 3C NSI Mode Table 12 SLTA 10 Adapter MIP mode Default Buffer Configuration MIP mode Buffer Parameter Default Count Default Size Default Total in Bytes Bytes Receive varsastonbufers 6 n w Total byes usediorbuers J m SLTA 10 Adapter User s Guide 36 The NODEUTIL node utility application available on Echelon s web site can be used to modify the MIP mode buffer configuration from aPC host Seethe README TXT file included with NODEUTIL for details By default the SLTA 10 NSI mode program ID consists of 8 bytes of program identification information 80 00 01 01 03 00 xx 3C where xx is determined by the transceiver being used The host application must change this program ID to indicate its application This is done automatically in LNS by the LCA Object Server If not using the LCA Object Server the host applicatio
31. pass any new data to the host and the input application buffers in the SLTA 10 Adapter will start to fill up Once that occurs messages will be lost possibly causing incoming LonTalk transactions to be retried and eventually causing the sender of the message to receive a failure indication Serial Bit Rate Options Bnnnnnn A Sets the serial bit rate to lt nnnnnn gt The available serial bit rates are listed below Available serial bit rates are 1200 2400 9600 14400 19200 38400 57600 115200 This rate represents the serial bit rate between the PC and the SLTA 10 Adapter when using a direct serial connection and between the PC and the modem when using a remote connection For remote connections the PC to modem serial bit rate telephone line speed i e modem to modem serial bit rate and the modem to SLTA 10 Adapter serial bit rate may be different The PC to modem serial bit rate is controlled by the network driver on the PC using the B option the telephone line speed is selected by the modems based on modem configuration and the modem to SLTA 10 Adapter serial bit rateis controlled by the hardware configuration of the SLTA 10 Adapter as described in Chapter 4 autobaud cannot be used in this configuration For local connections with the SLTA 10 Adapter Autobaud option disabled the serial bit rate specified by this driver option must match the rate specified by the configuration switches If you are using the d
32. reset If the host application needs to configure the SLTA 10 Adapter before enabling network communications the z option on the DOS network driver command line must be used to leave network communications disabled after the SLTA 10 Adapter is opened When the z option is specified and CFG1 is set to Network Disable On the host application itself must explicitly send the nifFLUSH_CANCEL command after reset The Windows NT network driver does not provide a z option When using the Windows NT network driver network communication will proceed without any action by the host application if Switch3 CFG1 is in the Network Enable position Otherwise if Switch3 CF G1 is in the Network Disable On position the host application must explicitly send the niFlush_CANCEL command If CFG1 is set to Network Enable down position the SLTA 10 Adapter will enable network communications after a reset by going directly to the NORMAL state thus allowing communications without requiring the niFLUSH_CANCEL command SLTA 10 Adapter User s Guide 32 If the SLTA 10 Adapter is used with a modem and the application requires the SLTA 10 Adapter to dial out to a host in response to a message from the network then CF G1 must be set to Network Enabled If the modem is set to receive incoming calls only then the host can disable the FLUSH state after the connection is established in which case CF G1 can be set to either position Table 9 summarizes these
33. string arguments If you areincluding space in an argument you must enclose the string in double quotes or else the DOS command line interpreter will view the spaces as argument delimiters A filename may be used as a source of the string arguments The filename should be preceded by the e character and may be any full pathname The structure of the file should be a series of text lines where each line is a separate string argument Command line strings and filename arguments may be intermixed Theory of Operation Upon execution HCU will open the network driver set the driver s operational mode to modem support on force direct mode on disables any SLTA 10 Adapter network interface protocols enabling communications with the modem itself modem responses on enables modem responses to be passed to the host and reliable transport protocol on If a serial bit rate has been indicated this also is set within the driver Next if the HCU hangup operation is selected HCU will drop DTR for 500ms See Using the SLTA 10 Adapter with a Modem Chapter 11 Next all string arguments are sent to the modem Acceptable modem responses to these strings are OK Or ERROR Next if the HCU connection operation is selected HCU will wait for the connection to be established This wait will be terminated by one of the following conditions e A response from the modem indicating either success or failure These responses may be one of the foll
34. the DOS network driver services the serial port connected to the network interface The function tick_int_main services the timer tick interrupt every 55 msec Both network drivers are fully buffered for both outgoing and incoming messaging Read and write functions work with circular buffers within the driver The host interrupt service routine handles the other ends of these buffer queues Both network drivers only support a single set of output buffers An elaboration on this design could implement a set of priority output buffers The write function could determine into which of the two buffer sets to place messages and the driver service function could service the priority buffers first 2 Implement and test timer support functions Timer support may be provided by a hardware timer as is done in the DOS network driver by a system service as is done in the UNIX network driver or by implementing a background software task The UNIX network driver uses a once per second signal that is handled by the second_service function The DOS timer functions are implemented by MDV_TIME C and MDV_TIME H 3 Implement and test the host side of the network interface protocol The network interface protocol is implemented by the rx_process andtx_process functions in the UNIX driver and by the functions in MSD_TXRX C for the DOS network driver 4 Implement and test raw modem I O if you need to support a modem interface Raw I O manages the ser
35. the appropriate queue value niTo niTQ_P niNTQ niNTQ_P The data portion of the interface buffer is not sent with the buffer request This puts the SLTA 10 Adapter inthe OUTPUT QUEUE REQUESTED State 3 If an output buffer is not available the SLTA 10 Adapter responds with a niNAck OxC1 command The SLTA 10 Adapter returns to the NORMAL state and the driver starts again at step 2 4 When an output buffer is available the SLTA 10 Adapter responds with a niack 0xC0 command The SLTA 10 Adapter is now in the OUTPUT QUEUE ACKNOWLEDGED state While in this state the network driver can only transfer downlink LonTalk messages uplink source quench commands niPUPXOFF uplink source resume commands niPUPXON or reset commands niRESET since the SLTA 10 Adapter is waiting for a message in this state All SLTA 10 Adapter User s Guide 87 other network interface commands sent downlink will be ignored and will return the SLTA 10 Adapter to the NORMAL state 5 Upon receiving the niAck acknowledgment the network driver transfers the entire interface buffer to the SLTA 10 Adapter This buffer has the same command and queue value sent in step 2 and also contains the data and checksum Upon completion of this transfer the SLTA 10 Adapter returns to the NORMAL state The network driver must preserve the continuity of the type of buffer request and the type of message sent downlink F
36. the modem string sent with this message The string must be null terminated If a large string needs to be sent to the SLTA 10 Adapter use a series of these requests with a single carriage return in the last string Note that many modems have a limited input buffer size typically 32 to 80 bytes The mode parameter is used to control the connection state of the SLTA 10 Adapter The values for this parameter are O0 Make no change to the SLTA 10 Adapter s modem connection state Send only if not CONNECTED Otherwise respond with a failed status 1 Initiate a dial out connection If the SLTA 10 Adapter is already currently connected preserve that connection and ignore the message The SLTA 10 Adapter s connection status changes SLTA 10 Adapter User s Guide 103 from IDLE to CALL_IN_PROCESS unless the connection is already made in which case the state stays at CONNECTED Thedial out prefix is sent first 2 Sameas 1 but disconnect hang up if currently connected before initiating the new connection Modem Response Query ASCII strings received from the modem when the SLTA 10 Adapter is not connected to a host will be buffered and may be read back by a node via this message The storage for this string is limited and so it will contain only the first 16 characters received from the modem in the disconnected state Executing the Send Modem String message will always clear this buffered string It will
37. to dial up a remote SLTA 10 Adapter change the configuration string hang up and reconfigure the modem Install Password This message stores a dial in password in EEPROM The default setting for this string is a null string which results in no password requirement by the SLTA 10 Adapter Any node on the network may change the password but an external host must have already connected and used the existing password in order to change it unless it was blank Any installed SLTA 10 Adapter should use a password otherwise an intruder might change the password to another setting The password string is limited to 8 characters and may be any sequence of non zero eight bit values The string must be null terminated typedef struct byte sub_code always 1 byte app_command value 9 char passwd_string 8 ANM_install_passwd_request If a password is installed in the SLTA 10 Adapter the host must issue the niPASSWD network interface command to the SLTA 10 Adapter after the connection is established The code for this command is OxE4 and it should be followed by up to eight password characters null terminated For details on sending network interface commands see the LONWORKS Host Application Programmer s Guide If modem support is selected a password is present in the SLTA 10 Adapter s configuration and the connection state changes from IDLE to CONNECTED the SLTA 10 Adapter will not process any other network interface comma
38. tool then the network management application itself normally configures the network interface For example a network management application based on LNS will configure the network interface in this case a SLTA 10 Adapter in NSI mode when the network interface device is opened Also a network management application based on the LonManager API or the LonMaker installation tool will configure the network interface when the network interface device is opened In this case the PC running the network management application sends a local message to the SLTA 10 Adapter to change its state to configured Alternatively the SLTA 10 Adapter may be installed in a network by some other network management tool In this case the network management tool sends a message to the SLTA 10 Adapter across the network to change its state and to assign it an address Once the SLTA 10 Adapter is in the configured state it will retain that state and its address assignment across power cycles because that information is stored in the internal EEPROM However if Switch3 CF G1 is set to Network Disable the FLUSH state must be canceled each time the SLTA 10 Adapter is reset If the host application attempts to send a message while the SLTA 10 Adapter is in the FLUSH state the SLTA 10 Adapter will return a failed response for acknowledged messages and a success response for unacknowledged messages The message will not be sent in either case If the host application att
39. values e Modem configuration string e Hangup string e Dial prefix string All dial out directory entries typedef struct byte sub_code always 1 byte app_command value 16 ANM_clear_eepool_request Install NVConnect NSI mode only This message writes the NVConnect byte A value of OxFF the default will disable this feature When this feature is enabled the SLTA 10 Adapter initiates a dial out when it receives a network variable update typedef struct byte sub_code always 1 byte app_command value 17 byte NVConnect two 4 bit fields ANM_install_nvconnect SLTA 10 Adapter User s Guide 109 Install NSIConnect NSI mode only This message writes the NSTConnect byte A value of OxFF the default will disable this feature When this feature is enabled the SLTA 10 Adapter initiates a dial out when it receives an AddMyNSI message typedef struct byte sub_code always 1 byte app_command value 18 byte NSIConnect two 4 bit fields ANM_install_nsiconnect Install CallbackEnable NSI mode only The CallbackEnable configuration byte is written as a Boolean value using this command A valus of zero the default will disable the callback configuration When this feature is enabled and a remote host dials in to the SLTA 10 Adapter the SLTA 10 Adapter terminates the call and initiates a dial out using the address entry requested by the initial dial in typede
40. with host selection enabled so the data field of the buffer is either an unprocessed network variable or an explicit message SLTA 10 Adapter User s Guide 89 SLTA 10 Adapter User s Guide 90 Chapter 10 Initialization and Installation This chapter describes initializing communicating with and installing the SLTA 10 Adapter as a network node SLTA 10 Adapter User s Guide 91 Initializing an SLTA 10 Adapter After an SLTA 10 Adapter and its host processor are powered the host application must initialize the SLTA 10 Adapter When an SLTA 10 Adapter is initially powered up or reset it disables network communications by entering the FLUSH unconfigured state unless the Switch3 CF G1 input is set to Network Enable The FLUSH state prevents the SLTA 10 Adapter from responding to network management messages before the host application has initialized the SLTA 10 Adapter The unconfigured state prevents the SLTA 10 Adapter from responding to application messages before the node has been installed in a network The host application will not be able to send or receive application messages until after it cancels the FLUSH state and the SLTA 10 Adapter leaves the unconfigured state An SLTA 10 Adapter leaves the unconfigured state when it is installed in a network and assigned an address in one or two domains on that network There are two ways this can happen If the SLTA 10 Adapter is used as a network interface for a network management
41. 0 Adapter can be used to build sophisticated network management monitoring and control tools for LONWORKS networks The SLTA 10 adapter also can be used with legacy host applications such as the LonManager LonMaker installation tool LonManager DDE Server or applications based on the LonManager API An SLTA 10 Adapter can be connected to the host through a pair of modems and the telephone network allowing the monitoring control or network management computers to be remote from the network The SLTA 10 Adapter can be set up to answer incoming calls from a remote host In addition any node on the local network can initiate a telephone call to a remote host computer A new feature available only in the SLTA 10 NSI mode see below allows the SLTA 10 Adapter itself to initiate a phone call to a remote host computer Figure 1 illustrates a typical node based on an SLTA 10 Adapter Chapter 11 Using the SLTA 10 Adapter with a Modem shows an SLTA 10 Adapter connected to a host through the telephone network Host Host Application LNS or LonManager Software optional Driver Interface Network Driver EIA 232 Interface SLTA 10 Network Adapter Network Interface Transceiver Interface LONWORKS Network Figure 1 SLTA 10 Adapter Node Architecture with Local Host SLTA 10 Adapter User s Guide 12 Two Modes of Operation SLTA 10 NSI and MIP Modes The SLTA 10 Adapter provides both the network services inte
42. D EIA 232 Data Port Connector for the EIA 232 Serial I O port J5 Standard DB9 female connection Network Connector Orange connector for attachment to a twisted A pair channel The mating plug provided is Two Position Weidm ller PN 135606 J1 SLTA 10 Adapter User s Guide Interface Unregulated AC DC Power Input Two Position J3 Unregulated AC DC Power Input Barrel Connector J2 Power Indicator LED DS2 Connecting Power Function Black connector for the power input The mating plug provided is Weidmuller PN 125911 Female 2 1 mm inside diameter and 5 5 mm outside diameter barrel input connector For use with Echelon power supplies models 78010 78020 78030 and 78040 Green LED Indicates presence of input power to the SLTA 10 Adapter Once the SLTA 10 Adapter is physically attached to the desired channel power must be supplied via one of the power input connectors The SLTA 10 Adapter may be ordered with a plug in power supply or may be used with any 9 30VAC DC supply Four plug in power supply options are available for the SLTA 10 Adapter depending on the country in which the SLTA 10 Adapter is used USA Canada United Kingdom Continental Europe or J apan The output voltage of these supplies is a nominal 9VDC at 500mA Power consumption is typically lt Watt independent of input voltage Table 3 describes the basic characteristics of the four power supply types
43. D will remain off unless the service request switch is pressed Note Do not attempt to power an SLTA 10 Adapter simultaneously from J P2 and J P3 Mechanical insertion of a connector into P2 disables theinput to P3 SLTA 10 Adapter User s Guide 23 SLTA 10 Adapter User s Guide 24 Chapter 3 Cabling and Connections This chapter demonstrates how to attach the SLTA 10 Adapter to a LONWORKS network a PC and a modem SLTA 10 Adapter User s Guide 25 Attaching the SLTA 10 Adapter El A 232 devices are configured as either Data Circuit terminating Equipment DCE or as Data Terminal Equipment DTE A DCE device connects toa DTE device unless a null modem cable is used Using a null modem cable a DCE device connects to a DCE device and a DTE device connects toa DTE device The SLTA 10 Adapter is a DCE device The standard configuration for a PC AT ElA 282 serial I O port isa DTE device PCs usually take the terminal role in communications Modems should always be DCE devices To connect an SLTA 10 Adapter to a PC simply connect one end of the serial cable to the SLTA 10 Adapter and the other end of the cable to the PC s serial port To connect an SLTA 10 Adapter to a modem a special null modem cable must be used Note that a standard off the shelf null modem cable will not work in this configuration Echelon offers the Model 73380 SLTA 10 Null Modem Cable which is a DB 9 male to DB 25 male null modem cable
44. EST msg_out data 0 1 sub code for SLTA 10 msg_out data 1 app_command specific command msg_out data 2 additional parameters msg_send SLTA 10 Adapter User s Guide 100 when msg_fails SLTA_tag SLTA 10 Adapter did not respond to the message when msg_succeeds when resp_arrives SLTA_tag SLTA 10 Adapter did respond to the message if resp_in code 0x3D command executed successfully Certain SLTA 10 Adapter network management messages which are designed to send a command string directly to the modem will fail if the connection status is CONNECTED This applies to the following messages Send Modem String Dial From Directory and Configure Modem The telephone connection must be broken and the SLTA 10 Adapter returned to the IDLE state for these messages to be issued Many of these network management messages for example the Install messages may be sent to the SLTA 10 Adapter from the host computer via the telephone link if the SLTA 10 Adapter is in the CONNECTED state In this case they should be sent using the niNETMGMT network interface command so that they are addressed to the SLTA 10 Adapter itself Structures are defined in the file SLTA_ANM H for each of the application commands and include the sub_code and app_command fields as well as any additional parameters for the specific application command If the response contains data other
45. Link Manager and will be matched with the link created for the dial in case The correct application may not be launched and a system level failure may occur SLTA 10 Adapter User s Guide 59 Callback The SLTA 10 Adapter callback functionality works as follows A call is initiated from some remote PC to an SLTA 10 Adapter on a network which must have its NSI mode EEPROM configured to require callback See Chapter 11 for more information on configuring the SLTA 10 s EEPROM The SLTA 10 Adapter answers the remote PC identifies to the SLTA 10 Adapter one of the SLTA 10 Adapters directory entries to use for the callback An SLTA 10 configured to require a callback will not accept any other direction from the host at this time The original call is terminated and the SLTA 10 Adapter calls the phone number indicated in its directory Note this does NOT need to be the phone number of the original remote PC that initiated the call Typically the SLTALink Manager on the remote host dialed answers the call and launches the appropriate application Several possible system level failures include e Theoriginal remote host expects to receive the callback but the directory index reflects the phone number of another remote host e Theoriginal remote host application opens an LNS database and initiates the first call The callback is directed back to the original remote host PC The SLTALink Manager on this PC receives the callback just like any other
46. MHz for all transceiver types the SLTA 2 operates at 5MHz or 10MHz depending on transceiver type In addition the SLTA 10 configuration DIP switches are externally accessible The SLTA 10 enclosure has been improved to allow wall mounting without requiring a bracket The SLTA 2 and the SLTA 10 MIP mode use the same drivers and link layer protocol The SLTA 10 Adapter Configurations The SLTA 10 Adapter is available with the following transceiver and power supply options e Transceivers The SLTA 10 Adapter is available with three LONWORKS channel options TP FT 10 TP XF 78 and TP XF 1250 The FTT 10A 78kbps free or bus topology TPT XF 78 78kbps bus topology and TPT XF 1250 1 25Mbps bus topology transceivers all use transformer isolated differential transmission e Power supply 9V plug in power supplies are available in U S Canada Model 78010 U K Model 78030 continental European Model 78020 and J apanese Model 78030 configurations Plug in power supplies are sold separately Alternately screw terminals are supplied for use with a 9 to 30VAC DC power sources Software Availability The SLTA 10 Adapter is not shipped with software Software for the SLTA 10 NSI mode is available on the LNS Developer s Kit for Windows CD version 1 5 and higher in the Connectivity Starter Kit Model 58030 01 or from the Developer s Toolbox of the Echelon web site www echelon com Software for the SLTA 10 MIP mode is distrib
47. SD_RAW C Direct serial 1 0 modem processing SD_SEGD ASM Defines data segment register for driver SD_SIO C PC AT UART interface processing SD_TXRX C Single byte link layer processing SD_UART H Defines PC AT UART registers e External Interface Files External interface files included for use by network management tools are contained in the SLTA directory External interface files are included for the transceivers available for the SLTA 10 Adapter See Binding toa Host Nodein Chapter 3 of the LONWORKS Host Application Programmer s Guide for a description of how to use these files to bind to an SLTA 10 Adapter node Appendix B of the LONWORKS Host Application Programmer s Guide provides a detailed description of how to modify these files to incorporate network variables SLTA 10 Adapter User s Guide 45 and message tags These interface files are provided in version 3 formats External interface files in version 3 format are contained in the SLTA2 XxIF_v3 directory The SLTA directories contain at least the following files NSLTA125 XIF For SLTA 10 Adapter with a TP XF 1250 transceiver NSLTA78K XIF For SLTA 10 Adapter with a TP XF 78 transceiver NSLTAFT1 XIF For SLTA 10 Adapter with a TP FT 10 transceiver e Sample Host Application A sample host application is contained in the HA directory See Appendix A of the LONWORKS Host Application Programmer s Guide for a description of the example The following files are included
48. T for network management commands to be executed by the SLTA 10 Adapter itself and nicomm for messages to be sent out on the network including network variables explicit messages and network SLTA 10 Adapter User s Guide 86 management messages addressed to other nodes For these two commands a buffer request protocol is used to ensure that the SLTA 10 Adapter has a free application buffer for the data The network driver must first request an output buffer before sending the interface buffer The network driver must hold the buffers in an output queue until the SLTA 10 Adapter is ready to receive them The network driver takes the SLTA 10 Adapter through 3 states to request a buffer and send the interface buffer Figure 34 summarizes the downlink state transitions Receive niCOMM or nINETMGMT Receive niFLUSH_CANCEL Out Queue Requested Output Buffer not send niNACK Available Output Buffer Available Receive niCOMM or niINETMGMT message send niACK Out Queue Ack d Note niNETMGMT commands are allowed in the Flush state Figure 34 SLTA 10 Adapter Downlink Flow Control States Following is the sequence of events for transferring an ni COMM or niNETMGMT Command downlink to the SLTA 10 Adapter 1 TheSLTA 10 Adapter is initially in the NORMAL state 2 Thenetwork driver requests an output buffer by sending a link layer header see figures 31 and 32 with a niCoOMM or niNETMGMT command and
49. adds an ACK NACK transport protocol to the network interface protocol A sequence number is also added to the link layer header This protocol can therefore recover from checksum errors on the host to SLTA 10 Adapter link The reliable transport protocol is enabled on the SLTA 10 Adapter with the Remote H ost option selected by the Switch2 CF G2 input as described in Chapter 4 The reliable transport protocol is enabled on the DOS network driver with the m option as described in Chapter 8 The reliable transport protocol is not supported by the UNIX network driver The link layer header contains an ALERT 0x01 byte a sequence number and a length byte followed by a one s complement of the length byte These values are always validated by the receiver before accepting the rest of the message Following the length bytes is the network interface command See Appendix D of the Host Application Programmer s Guide for a description of the command byte structure If the message contains a data field it follows the command byte Finally a checksum terminates the sequence The ALERT ACK link protocol should be used with remote hosts With this protocol the sender will start the sequence by transmitting the ALERT byte When this byteis received by the receiver that device responds by transmitting the ALERT ACK byte value FE hex This low level handshaking process prevents the sender from transmitting the rest of the sequence before the receiving device
50. al Fax Modem with Simultaneous Voice and Data 33 6 modem with the US Robotics 28 8 Faxmodem with Personal Voice Mail an incompatibility in communication occurs Testing the two modems via Hyperterminal reveals that the CD signal Carrier Detect gets trampled on SLTA 10 Adapter User s Guide 111 SLTA 10 Adapter User s Guide 112 Chapter 12 Using the Host Connect Utility with the SLTA 10 MIP Mode The Host Connect Utility or HCU is a standalone DOS utility designed to dial out and make a connection to a remote SLTA 10 Adapter in MIP mode This utility may be used prior to executing an application based on a LonManager product or may be called directly from such a product The source code for HCU is supplied with the Connectivity Starter Kit so that it may be used as a model for host applications that need to establish connections directly with a remote SLTA 10 Adapter as well as host applications on platforms other than PCs running DOS The features provided by this program are e Dial Out or Hangup Operations e User Defined Modem Strings Used for Initialization or Dialing e Modem Control via the LDVSLTA Network Driver Skip this Chapter if you are using the SLTA 10 NSI mode SLTA 10 Adapter User s Guide 113 HCU Usage The command line arguments for HCU are HCU options stringl string n filename The optional options arguments may include C Or H To indicate to HCU that this is a Connection operation
51. and may be associated with a host application The link information is stored in a s10 file located by default inthe c lonworks bin sltal0 folder The SLTALink Manager application can associate a link with a LON device name and then interface with the SLTA 10 NSI mode driver for Windows NT The SLTALink Manager handles automatically dialing in to the network from the PC host providing the ability for applications with no knowledge of modems or phone numbers to run remotely through a pair of modems The SLTALink Manager s GUI can be used to connect or disconnect to a remote SLTA 10 Adapter In addition the SLTALink Manager has a simple programmatic way to interact with the SLTA 10 driver for Windows NT This programmatic interface allows an application to send down a particular phone number for an SLTA 10 Adapter to dial or to send down certain commands such as hang up Finally the SLTALink Manager includes many diagnostic functions The SLTA 10 Adapter Link Manager software is used to control a remote SLTA 10 via a set 2 of modems by using the Telephony Application Programming Interface TAPI services which are built into the Windows NT 4 0 operating system When attached directly toa PC SLTA 10 Adapters use so called local links In this case the SLTALink Manager software interacts with the Windows NT driver and configures the necessary parameters NOTE Remote SLTA 10 Adapters cannot be used with Windows 3 51 because Windows
52. and to the DOS conf IG sys file Edit the conFIG sys file to indude the line DEVICE C LONWORKS BIN LDVSLTA SYS options Substitute your drive and directory name if other than c LONWORKS BIN Reboot the PC after adding this line to load the driver For example the following command would be used with a locally attached SLTA 10 Adapter in MIP mode installed on COM2 as device LON1 running at 115 200 bps with autobaud enabled DEVICE C LONWORKS BIN LDVSLTA SYS P2 D1 B115200 Warning The A option must be present in the conF IG sys entry if the SLTA 10 Adapter AutoB aud Switch5 AB is in the Enabled UP position or the SLTA 10 Adapter will not function correctly The A option also may belet in the conF IG Sys entry if the SLTA 10 Adapter Autobaud switch is in the disabled default DOWN position The available options for the SLTA 10 MIP mode network driver for DOS are described in the following sections Buffer Options Onn Sets the number of output downlink buffers within the driver to lt nn gt The buffer sizes within the driver are pre set to accommodate 255 byte packets The SLTA 10 Adapter in MIP mode has application output buffers that may be increased to as large as 255 bytes There must be at least 2 buffers and the maximum allowed number for lt nn gt is limited by the size of the buffer 258 times the total number of input and output buffers within the driver The entire buffer space plus t
53. antage of these system solutions is that they do not scale well to monitoring multiple networks on one PC Theresult is many applications continually and concurrently running on the same PC Also one possible system failure to avoid is that the SLTALink Manager settings may result in multiple copies of the host applications By default the SLTA 10 NSI mode will terminate a phone call after three minutes with no traffic going across the modems As with the application controlled hang up and the manual disconnect in the SLTALink Manager this scenario does not result in the application terminating This scenario therefore carries the same advantages and disadvantages as those described in the previous paragraph Monitoring Application Termination Strategy There are three strategies for terminating the remote LNS monitoring application The first strategy is to require user intervention to shut down or terminate the application No special software must be written for this case For the dial in to a network scenario when the call is user initiated the user is presumably available to shut down or terminate the application In the dial out case the requirement of user intervention to terminate the application means that every call from a network is seen by an user If the network is sending alarms user intervention is highly desirable The second approach requires a node on the network to send a network variable update to the host when the
54. ations if the z option is specified and the Switch3 CF G1 input is set to Network Disable UP position See Chapter 4 for more information Host applications which need to configure the SLTA 10 Adapter prior to enabling network communications should use this option This option should not be used with the LonManager API LonManager LonMaker or the LonManager DDE Server More information about the nif LUSH_CANCEL message is provided in the LONWORKS Host Application Programmer s Guide Network Interface Protocol Options F M Enables the full interrupt mode of the driver If this option is not specified the driver will disable interrupts for the duration of each link layer transfer This ensures that no data will be lost due to other system interrupts and is acceptable at high serial bit rates The driver will use interrupts for the first byte of each uplink interface buffer When the uplink interrupt is received the driver reads the rest of the message without interrupts via polled I O Interrupts are disabled during the uplink transfer This assures that no other system interrupts will occur resulting in lost uplink data frames Downlink transmissions are sent directly via polled I O of the serial port from the write function call The host write functions will not return until the message has been sent downlink When using the ALERT ACK link protocol interrupt latency is not a problem since the SLTA to host protocol includes an acknowl
55. current month day year and hh mm ss is the current time All modem responses are also displayed SLTA 10 Adapter User s Guide 117 Table 17 HCU Progress Strings devname No such file or Indicates that HCU could not open the device devname directory or Not ready reading device devname Dialing or Hanging up Indicates the HCU operation Device initialization error Indicates a problem with initializing the network driver devname Could not open file filename Indicates a problem with opening the string argument file Password Format error abort Indicates there was a problem interpreting the password argument Modem Response Timeout Indicates that the modem did not respond to a command string DCD state test error devname Indicates a problem communicating with the network driver Connect timeout devname Indicates that the connection was not established within the connection timeout period User Abort Indicates that the connect wait process was aborted by the user Connected Indicates the status of the connection If the message or Connection Failed Connection Failed appears following what appears to bea successful modem connection there may be a problem with the DCD signal from the modem Downlink Password Failure Indicates a problem sending the password command downlink to the SLTA 10 Adapter The connection may have been broken unexpectedly Password Validation Fail Indicates that the remote SLTA 10 Adapter has res
56. d for example in the command string which causes the modem to hang up When dialing out Hayes AT compatible modems use the comma character to insert delays between portions of a dial command the comma character should continue to be used for dialing out DTE Connections In addition to the basic three wire connections Transmit Data TXD Receive Data RXD and Signal Ground there are two additional signals that must be connected Data Carrier Detect DCD and Data Terminal Ready DTR The modem must also be configured to use these signals DCD is used by the SLTA 10 Adapter to determine that a connection has been made and DTR is used to terminate a connection by hanging up Note that many modems default to ignore these two signals and must be configured to enable them The following AT command enables these two signals on many modems AT amp C1 amp D2 CR SLTA 10 Adapter User s Guide 98 Network Management Messages Network management messages are used to configure the operation of the network as opposed to delivering application data during operation of the network All LONWORKS nodes respond to the standard network management messages as described in Appendix B of the Neuron Chip Data Book For nodes based on the SLTA 10 Adapter additional network management messages are defined to configure and control the SLTA 10 Adapter The message codes for network management messages are reserved and therefore applications need not be co
57. dapter User s Guide 39 SLTA 10 NSI Mode Software Overview The SLTA 10 Adapter is not shipped with any software The Windows NT driver and SLTALink Manager software are supplied in the Connectivity Starter Kit and as part of the LNS Developer s Kit for Windows The SLTA 10 NSI mode set up installs three pieces of software e theSLTA 10NSI mode Windows NT Driver e a stub driver to run legacy DOS and Windows 3 1x applications and e theSLTALink Manager software The SLTA 10 Adapter includes firmware that moves the upper layers of the LonTalk Protocol from the Neuron Chip within an SLTA 10 Adapter and onto a host processor This firmware allows the SLTA 10 Adapter to be used by a host application to send and receive LonTalk messages The firmware in the SLTA 10 Adapter is loaded in ROM and cannot be reprogrammed Using the SLTA 10 NSI mode the host application may be one of two types The first type of host application is an LNS based application developed with the LNS Developer s Kit for Windows The second type of application is a legacy DOS or Windows 3 1x application these applications make use of the stub driver declared in the config nt file which in turns accesses the Windows NT driver Echelon does not support 32 bit Windows applications that are not based on the LNS software accessing the Windows NT driver Windows NT Software Installation Procedure Prior toinstallation ensure that the computer is running the Wind
58. ded the VDD is installed which would be LONn Al D Expands to the remote identifier This is expressed as either a quoted ASCII string or as a series of hexadecimal numbers if the identifier contains non ASCII data RESULT Expands to an unquoted word that represents the success or fail reason of the connection The startup application will be launched when a dial in occurs for this link or optionally when a manual connection is made to the link It will not start up if the link is connected to due to an auto connect case Enabling a Callback If a remote SLTA 10 adapter has callback enabled then it will expect a callback command whenever someone dials in to it Check the Enable box if you need to enable the callback feature The callback command includes a directory index that points to a phone number stored in the remote SLTA 10 adapter If callback is enabled then one of the remote directory numbers Address 1 though Address 5 can be select to be used to call the host back See Characteristics of a Well Designed System below for a description of how to successfully implement callback SLTA 10 Adapter User s Guide 56 Diagnostics A number of Diagnostic and testing services are provided via the Diagnostic Screen accessed through the Devices menu see figure 26 The Test button retrieves status and error counts from the SLTA 10 Adapter The Service button will cause the SLTA 10 Adapter to broadcast a s
59. dressed to the SLTA 10 Adapter s NSI mode results in a call being initiated Second if the interface adapter is not an SLTA 10 Adapter in NSI modem using modems or there are no explicitly bound network variables to the host application then at the LNS application s termination any host network variables and their connections are removed from the LNS database and the other nodes in the network In addition if the interface does not host the LNS database upon termination of the LNS application the interface is deconfigured The second behavior described would be desirable in the event that multiple remote host PCs needed to be able to dial in to the same network As long as no explicitly bound network variables were left when the host applications terminated then several remote PCs could share one SLTA SLTA 10 Adapter User s Guide 60 10 Adapter Note this assumes that the NSS engine exists somewhere on the network and is not located on one of the remote PCs sharing the single SLTA 10 Adapter Both an application controlled hang up using the SLTALINK EXE programmatic interface and a manual disconnect in the SLTALink Manager will terminate the phone call however neither results in the termination of the host application In these scenarios the host application remains running as the call can be re established by the host application itself by a manual connect in the SLTALink Manager or a dial out initiated on the network The disadv
60. during the execution of your host application use the source code of HCU as a guide When function code 2 is used argdx points to the direct_calls structure defined for all LONWORKS standard network drivers for DOS If argcx is 13 the size of the standard direct calls structure then three direct entry point addresses are returned as usual If argcx is 4 the size of the structure ioct 1_get_dcd_s then the state of the modem s DCD lineis returned as a TRUE Or FALSE value Note that the status field is 16 bits in this structure but 8 bits in the direct calls structure struct ioctl_get_dcd_s unsigned ioctl_stat 16 bit status unsigned dcd_state Data Carrier Detect TRUE or FALSE lt Function code 3 is used when the application wishes to write information to the driver For the SLTA 10 Adapter driver argdx points to the following structure and argex is its size struct ioctl_o_info_s unsigned ioctl_stat 16 bit status unsigned sub_command use enum sub_command unsigned mode unsigned mode_aux enum sub_command SUBC_set_opt by set driver options SUBC_set_DTR 32 set DTR line SUBC_set_baud 3 set serial bit rate There are three sub commands used to set the various modes of the driver the state of the DTR Data Terminal Ready line to the modem and serial bit rate of the serial interface When sub command 1 is used the mode field in the structure is a bit
61. e automatic dial out initiation techniques In LNS 1 0 or 1 01 when an LNS host application is terminated all host network variables and connections to these variables are removed from the LNS database One way the SLTA 10 Adapter can initiate a phone call or automatically dial out is based on a network variable update being sent to the SLTA 10 Adapter Since the termination of the application on the PC host results in the removal of all network variable connections to the host no network variable update can be sent to the SLTA 10 Adapter Thus one of the two mechanisms that support automatic dial out is unavailable LNS 1 0 and 1 01 have no special knowledge of whether the SLTA 10 Adapter is remotely connected through a pair of modems However LNS 1 5 automatically detects that the SLTA 10 Adapter is remote at commissioning Using a remote SLTA 10 Adapter affects the default system behavior by allowing the system to function as desired Upon termination of an application based LNS 1 5 the LNS host API will determine if the NSI uses modems and if there are any explicitly bound network variables on the host If both of these conditions are met LNS does not remove the connections or host network variables In addition LNS leaves the SLTA 10 Adapter configured Thus LNS 1 5 fully supports the SLTA 10 Adapter accessed through a modem configuration In summary LNS 1 5 fully supports using the SLTA 10 Adapter with modems LNS 1 0 and 1 01 do not supp
62. e hardware FIFO buffer Another suspect in this area can be a disk caching program These programs also perform services under the DOS tick interrupt such as flushing data onto the disk drive which can postpone serial O interrupts for lengthy periods e Modem serial bit rate overrun For example if the SLTA 10 Adapter serial bit rate is set to 38 400 bps and the modem telephone line speed is set to 2 400 bps the modem will likely be overrun by sending it data faster than it can transmit it This can occur since no flow control schemes can be used to restrict the rate that data is sent to the modem In general set the modem link rate equal to the telephone line speed In certain cases it will be acceptable to exceed the telephone line speed for instance with a 14 400 bps V 32bis modem with data compression enabled it may be possible to run the modem link at 19 200 bps e Full duplex FIFO overrun This is caused by excessive full duplex traffic when using the buffered link protocol The ALERT ACK link protocol should be used instead SLTA 10 Adapter Sends Modem Configuration String But It Has No Effect Most modems will determine the serial bit rate based on the assumption that the first two characters sent to them while in the command mode are the characters AT This means that a type of bit rate detection is being performed when these characters are sent to the modem If the modem has been power cycled it will need to repeat this process
63. e may be used to check the type of interface product that the node is running The value returned for the SLTA 10 Adapter is a 1 Application nodes will respond with a failed code of Ox1D returned for this or any message where the request message code is 0x7D typedef struct byte sub_code always 1 byte app_command value 1 ANM_product_query_request typedef struct byte product for SLTA 10 Adapter 1 ANM_product_query_response Send Modem String This message is typically used to send AT command character strings to the modem from another node on the local network This provides full control of the modem and its internal control registers and settings Normal use of this feature is to dial out to a number that is not in the telephone directory of the SLTA 10 Adapter or to change or set modem control registers and options This puts complete control of the modem in the hands of any application node on the network The message definition is typedef enum NO_CHANGE 0 DIAL_OUT 1 HANGUP_DIAL_OUT 2 STR_mode typedef struct byte sub_code always 1 byte app_command value 2 STR_mode mode char modem_string ANM_send_str_request The length of modem_st ring is limited to the application and network buffer sizes within the SLTA 10 Adapter node and the node which is communicating with it The SLTA 10 Adapter as shipped has buffers sizes allowing for a maximum of 46 characters in
64. e that the packet throughput of the SLTA 10 Adapter is substantially reduced when using a modem because of the overhead associated with modem support SLTA 10 Adapter Connection States When the SLTA 10 Adapter is operating in the remote host mode several internal states or connection states will control its behavior e The IDLE state is entered after power up reset In this state any uplink bound messages are ignored since the SLTA 10 Adapter is not connected to a host The IDLE state is also entered whenever the telephone connection is broken and the modem drops the DCD Data Carrier Detect line e TheCALL_IN_PROCESS state is entered once a connection is initiated by a node on the network connected to the SLTA 10 Adapter In this state uplink traffic is still discarded while the SLTA 10 Adapter monitors the modem for connection completion or connection failed events to occur e The CONNECTED state is entered once the connection is complete The normal network interface protocol resumes between the SLTA 10 Adapter and the remote host This state may be entered as a result of a node on the local network initiating a call or as a result of a remote host calling up this SLTA 10 Adapter e The FAILED state is entered if the connection process failed This state is operationally the same aS IDLE The connection state of the SLTA 10 Adapter is preserved across software resets allowing normal network management resets t
65. ed with Windows NT 3 51 because Windows NT 3 51 does not include the 32 bit TAPI services used by the SLTALink Manager software Skip this Chapter if you are using the SLTA 10 MIP mode SLTA 10 Adapter User s Guide 49 Software Overview The SLTALink Manager is sophisticated software that compliments the SLTA 10 Adapter NSI mode firmware in many various ways The SLTALink Manager is a standalone application that can monitor a modem line answer an incoming phone call associate the incoming call s SLTA 10 Adapter and hence its network with a LON device and then launch a pre determined application for that particular network or SLTA 10 Adapter Combined with a well designed system architecture and a well designed LNS host application the SLTALink Manager lets a LONWORKS network establish a connection to a remote PC through a pair of modems based on an event that occurs locally to the network The SLTALink Manager provides a graphical user interface for the creating editing and diagnosing of links Each link represents a particular SLTA 10 Adapter and its network A link identifies several important aspects of the set up including the type of connection a remote connection via modems or a local direct connection the COM port the SLTA 10 Remote Identifier see below the baud rate of the serial port on the SLTA 10 Adapter and the dial in password if any In addition the link indicates if a security callback is required
66. edgment of the start of the message The driver employs timeouts in order to prevent lockout of the write function and timeouts for clearing various states of the transmitter receiver when line errors occur When operating at lower serial bit rates it becomes less desirable to disable interrupts for long periods The trade off with using the full interrupt mode is that other system interrupts may cause loss of data in the serial port s UART If the F option is specified the driver uses interrupts for every uplink and downlink byte transferred Downlink messages are buffered from the device write function and are sent downlink under interrupt control Uplink messages are received under interrupt control and are buffered also This option should be used for serial bit rates of 9 600 bps or slower Enables modem support and the reliable transport protocol This option must be specified if the host is to communicate with the SLTA 10 Adapter via a modem connection The SLTA 10 Adapter must be configured with SLTA 10 Adapter User s Guide 71 Switch2 CF G2 input in the Remote Host setting UP position When connected the selected SLTA 10 Adapter and Host network interface link protocol is in effect When disconnected the only allowable link layer traffic is of the modem direct type where ASCII strings are being exchanged between the host and the modem for example AT commands to dial out Any other network interface traffic is not allowed w
67. efault hardware configuration autobaud disabled the autobaud option A does not need to be enabled Enables the autobaud feature This provides the autobaud sequence whenever the driver is opened The default setting for the driver is Autobaud Disabled If the Autobaud input on the SLTA 10 Adapter hardware is enabled then this option must be specified As described in Chapter 4 the default setting for the AB switch on the SLTA 10 Adapter is disabled so the a option does not need to be specified with the default hardware configuration This option may not be used with the modem support m option DOS Device Options Pn Dn Sets the serial port to lt a gt where lt n gt is 1 4 for COM1 COM4 The default is COM 1 Defines the device unit number as lt n gt where lt n gt is between 1 and 9 so that the DOS device nameis LON1 through LON9 The default is 1 for LONT This option can be used to support multiple network interfaces on a single PC For example this device name is passed as a parameter to SLTA 10 Adapter User s Guide 69 Un C Timing Options Rnn Wnnn 1xt_open when using the LonManager API When invoking the sample host application HA the device may be specified with the D option for example HA DLON2 Sets the serial port interrupt request number IRQ to a non standard value lt n gt where lt n gt is between 1 and 7 If the serial port in use is COM3 or COM4
68. eived by the receiver that device responds by transmitting the ALERT ACK byte value FE hex This low level handshaking process prevents the sender from transmitting the rest of the sequence before the receiving device is ready Once the ALERT ACK byte is received by the sender it sends the rest of the message without any other interactions SLTA 10 Adapter User s Guide 81 Sender Receiver ALERT 01 ALERT ACK FE Link Layer Header length not_length network interface comman data checksum Figure 31 SLTA 10 Adapter ALERT ACK Link Protocol The link layer header contains a length byte followed by a one s complement of the length byte These values are always validated by the receiver before accepting the rest of the message Following the length bytes is the network interface command See Appendix D of the H ost Application Programmer s Guide for a description of the command byte structure If the message contains a data field it follows the command byte Finally a checksum terminates the sequence The length byte value describes the length of the network interface command byte plus the length of the data field This value will always be at least 1 The checksum is a two s complement of the sum of the command byte and all of the bytes in the data field if it exists Checksum errors detected by the host will cause an error to be reported to the application and checksum errors detected by the SLTA 10 Adapter will cause t
69. ement command The Attach command performs this function for an SLTA 10 Adapter attached to the PC with DOS based LonManager LonMaker installation tool the Install command performs this function for SLTA 10 Adapters in application nodes Calling the 1xt_install_node function in the LonManager API performs this function for nodes across the network the LonManager API 1xt_open function installs the network interface itself See below for details with the LCA Object Server of LNS 4 Change the state of the network interface to configured This may be done by a network management tool across the network or may be done directly by the host application by sending the Set Node Modenetwork management message The LonMaker Attach command performs this function for an SLTA 10 Adapter attached to the PC with LonMaker the LonMaker Install command performs this function for SLTA 10 Adapters in application nodes Calling the 1xt_install_node function in the LonManager API changes the mode of other nodes across the network the LonManager API 1xt_open function changes the mode of the network interface itself See below for details with the LCA Object Server of LNS Installing an SLTA 10 Adapter on a Network An SLTA 10 Adapter attached to a network appears as a standard LONWORKS node to other nodes on the network The SLTA 10 Adapter node is logically installed on a network with a network management tool Installation scenarios are described in the LONWORKS
70. empts to send a message while the SLTA 10 Adapter is in the NORMAL unconfigured state the SLTA 10 Adapter will always return a success response even though the message will not be sent To initialize an SLTA 10 Adapter follow these steps for more detail see the LONWORKS Host Application Programmer s Guide 1 Reset the SLTA 10 Adapter from the host application by sending the niRESET command If installed correctly the SLTA 10 Adapter will respond with an uplink niRESET message upon completion of the reset The first message from an SLTA 10 Adapter after power up will also bean uplink niRESET message informing the host that the SLTA 10 Adapter has reset 2 Cancel the FLUSH state in the SLTA 10 Adapter LNS applications automatically handle this and it is done automatically by the SLTA 10 MIP mode DOS network driver after an open command or uplink niRESET if the z flag is not specified The FLUSH state can be manually SLTA 10 Adapter User s Guide 92 canceled by sending the niFLUSH_CANCEL message The FLUSH state can also be disabled by a configuration switch on the SLTA 10 Adapter as described earlier in this chapter 3 Install the network interface in one or two domains using the Update Domain network management message This may be done by a network management tool across the network or may be done directly by the host application by sending the Update Domain message as a local network manag
71. ervice pin message on the network The reset button causes a reset of the Neuron Chip in the SLTA 10 Adapter but does not clear the Neuron Chip s system image LON1 Diagnostics Ed OK i A comm Service Reset Node State Configured LonYorks SLTA 10 Device Driver Version 1 00 Network Interface Node Status 00000 TE Timeouts 00000 Lost APP Messages 00000 Missed NET Messages 00000 Node State Configured Most recent error 0 Reset Cause Restart Internal Some buttons are left for future releases of additional features Figure 26 Diagnostic Screen The SLTALink Manager Programmatic Interface The SLTALink Manager executable SLTALINK EXE provides for a command line invocation Once the SLTALink Manager is up and running a program can connect to a known link by executing SLTALINK EXE with a command line argument C lonworks bin sltalink exe Remote Quotes generally are needed since the link name can have embedded spaces Another form will disconnect the specified link C lonworks bin sltalink exe Remote D Another form allows a phone number override C lonworks bin sltalink exe Remote 1 415 867 5309 Another form allows a password override C lonworks bin sltalink exe Remote P passwd SLTA 10 Adapter User s Guide 57 The P and options may be combined Note that
72. f struct byte sub_code always 1 byte app_command value 19 byte NSIConnect Non zero enables callback ANM_install_callbackenable Report SLTAEE NSI mode only This command will result in a response that includes the address of the SItaEE data the revision of the data structure and its length This information can be used to read back any portion of the structure for analysis and deconstruction typedef struct byte sub_code always 1 byte app_command value 20 ANM_report_sltaee The response is typedef struct word abs_address 16 bit absolute address of structure byte version currently 1 byte length ANM_report_sltaee_resp SLTA 10 Adapter User s Guide 110 Modem Compatibility The SLTA 10 Adapter has been tested with the following modems Best Data Smart One external modem 33 600 bps Data Fax modem Diamond SupraExpress 336e external faxmodem Hayes Accura 336 external fax modem US Robotics Sportster Voice external 28 8 faxmodem Synchronous communication should be disabled when synchronous modems are connected at lower serial bit rates less than 4800 bps Alternatively data compression can be disabled at lower bit rates For example two V 42 or V 32bis modems connected at 2400 bps will have very low throughput due to the slow serial bit rate XON XOF F flow control should always be disabled in the modem with the SLTA 10 Adapter When using the Hayes Accura extern
73. far msg_p short len See Also ldv_read Returns LDV_OK 0 Message written successfully LDV_NOT_OPEN 3 Invalid handle or device not open LDV_DEVICE_ERR 4 Error occurred accessing device LDV_NO_BUFF_AVAIL 7 No message buffers available Parameters handle short Device identifier returned by 1dv_open msg_p void far Pointer to buffer containing the message to be delivered to the network len short Length of outgoing message in bytes SLTA 10 Adapter User s Guide 128
74. for information on using the Windows 3 1x DLL directly SLTA 10 Adapter User s Guide 75 SLTA 10 Adapter User s Guide 76 Chapter 9 Creating an SLTA 10 MIP Mode Driver This chapter describes the process of building a network driver for a host that is to be connected to an SLTA 10 Adapter in MIP mode This chapter also includes a description of the network interface protocol for the SLTA 10 MIP mode The network interface protocol defines the format of the data passed across the El A 232 interface and varies depending on the configuration of the SLTA 10 Adapter and the network driver If aLONWoRKS standard network driver is used the format of the data passed between the driver and the application is defined by the network driver protocol and is independent of the network interface protocol the driver is responsible for providing the necessary translations This chapter will therefore be of interest only to those needing to develop a network driver for a host other than DOS Windows or UNIX Skip this Chapter if you are using the SLTA 10 NSI mode SLTA 10 Adapter User s Guide 77 Purpose of the Network Driver The network driver provides a hardware independent interface between the host application and the network interface By using network drivers with consistent calling conventions host applications can be transparently moved between different network interfaces For example the standard SLTA 10 MIP mode DOS network drive
75. func void far argdx int argcx e handle is an integer returned by an earlier successful call to open specifying the LONWORKS network driver LONn to be opened e func is the value 2 meaning that the application is reading information from the driver For LONWORKS standard DOS network drivers the information returned is the network interface direct call structure SLTA 10 Adapter User s Guide 73 e argdx isa pointer toa caller declared structure that will contain the direct entry points into the driver See the structure direct_calls in the file NI_mMSG c in the supplied example host application for usage e argcx is the size of the structure Function code 2 is supported by network drivers for DOS to return three direct entry points into the driver code The network driver for the SLTA 10 Adapter supports an additional option to function code 2 as well as function code 3 which is used to manage the modem control state of the driver These options are not used when the SLTA 10 Adapter is connected directly to a host They are provided primarily for use while establishing communications with a remote host For example the host connect utility H CU described in Chapter 11 of this manual uses these functions Host applications that only communicate to the SLTA 10 Adapter via an already established telephone connection do not need to concern themselves with these functions If you wish to establish or take down telephone connections
76. g Preferences 21x Dialing from The Office Use Dialing Properties to modify how your calls are dialed Dialing Properties Figure 20 SLTALink Manager Dialing Preferences Window Clicking on Dialing Properties will bring up the Windows Location Information window figure 21 if the Dialing from indicator reads or if TAPI information has been previously entered as shown in figure 20 as Dialing from The Office the Windows Dialing Properties window figure 22 will be displayed instead The Dialing Properties window is a tabbed subset of the Windows Telephony Control Panel Location Information x Please provide information about your current location so that your calls can be dialed correctly What country are you in now What area or city code are you in now IF you dial a number to access an outside line what is it The phone system at this location uses Tone dialing Pulse dialing Figure 21 Windows Location Information Window SLTA 10 Adapter User s Guide 52 Dialing Properties HEMOSE United States of America v E E Plejni s Biir eie Bi f i Figure 22 Windows Dialing Properties Window Establishing a Communications Line for Calls Dialed out to the PC The next step is to select a line modem to monitor for incoming calls Figure 23 shows the Monitor Line window that is displayed when Monitor for SLTA dial in
77. g will start at LON1 This may conflict with other LonWorks network interfaces if they exist Eam Figure 17 LONWORKS Device Naming Convention Clicking the Next button concludes installation At the prompt to restart the computer remove the SLTA 10 NSI mode installation diskette and restart the computer Note that the Windows operating system will not recognize the SLTA 10 adapter until the computer is restarted Windows NT Software Installation Results The Windows NT installation software loads a selection of new files and updated Echelon files to different locations on the PC s hard drive The function and location of these files can be found in readme txt SLTA 10 Adapter User s Guide 41 SLTA 10 Adapter User s Guide 42 Chapter 6 The SLTA 10 Mip Mode Software This chapter describes the SLTA 10 MIP mode software shipped with the Connectivity Starter Kit Model 58030 01 and on the Echelon web site at www echelon com This software is basically an updated version of the SLTA 2 adapter software There is no 32 bit Windows driver available for the SLTA 10 MIP mode Skip this Chapter if you are using the SLTA 10 NSI mode SLTA 10 Adapter User s Guide 43 SLTA 10 MIP Mode Software Overview The SLTA 10 Adapter is not shipped with any software The SLTA 10 MIP mode software and drivers are supplied in the Connectivity Starter Kit and must be ordered separately The software includes ANSI C source code f
78. he SLTALink Manager application then typically launches the application listed in the link with optional command line arguments available for example to open the correct LNS database with the correct device name The process of opening the LNS application results in the buffers of the SLTA 10 Adapter being over written thus the original message is lost Since this message network variable update is by definition important enough to warrant establishing a connection to the host a system strategy is required so that this data reaches the host The two basic system strategies are 1 to have the node on the network continue to send out the network variable update until the host application sends a message to the node telling it to stop or 2 to have the host application seek out the information upon being launched The first approach places the burden on nodes in the network the second approach places the burden on the host application The first is more direct and is likely to result in the information getting to the host more quickly The second approach has the primary advantage that no special Neuron Chip application code is required also since the call initiation and host application launch may require minutes the time it takes the host application to poll several network variables is not significant In the best scenario upon being launched the host application would first check with a datalogging node on the network that records alarms and a
79. he driver code itself cannot exceed 64K bytes The size of the driver code itself is 9K bytes The number of output buffers required is determined by the characteristics of the host application If the host application always waits for an outgoing message completion before sending another message then only two buffers are required If the host application is set up to overlap transactions more buffers may be required In this case greater parallelism may be achieved at the expense of host application code complexity Inn Sets the number of input uplink buffers within the driver to lt nn gt The buffer sizes within the driver are pre set to accommodate 255 byte packets The SLTA 10 Adapter has application output buffers may also be increased to as large as 255 bytes There must be at least 2 buffers and the maximum allowed number for lt nn gt is limited by the size of the buffer 258 times the total number of input and output buffers within the driver The entire buffer space plus the driver code itself cannot exceed 64K bytes The number of input buffers required is determined by the expected incoming traffic and the capability of the host application to process it If the incoming traffic is bursty more input buffers are required If the application cannot process incoming SLTA 10 Adapter User s Guide 68 traffic fast enough the input buffer pool will fill up with unprocessed packets In that case the SLTA 10 Adapter will not be able to
80. he message to be ignored The SLTA 10 Adapter places the following requirements on the rate of the received serial data stream When receiving the maximum wait period for the length byte following the transmission of the ALERT ACK byte is 100ms or 1 second when attached to a modem All subsequent bytes received must occur within 100ms after the previous byte otherwise the SLTA 10 Adapter receive process will abort Likewise the SLTA 10 Adapter uses a wait period of 100ms or 1 second when attached to a modem before aborting for the reception of the ALERT ACK when transmitting a message If the ALERT ACK is not received in time the SLTA 10 Adapter repeats the process by transmitting another ALERT byte The SLTA 10 Adapter cannot support a full duplex communications process between it and the host The network driver included with the SLTA 10 Adapter takes this into account Data frames transmitted to the SLTA 10 Adapter while it is in the process of sending uplink messages will be lost if more than 16 bytes are sent to the SLTA 10 Adapter SLTA 10 Adapter User s Guide 82 Buffered Link Protocol The DOS network driver uses the buffered link protocol when the N option is specified See Chapter 8 for a description of this option The UNIX network driver uses the buffered link protocol if the alert_ack_prtcl variable is set to FALSE in the source code this is the default The Switch1 CF G3 input of the SLTA 10 Adapter as described in Chapter
81. hen the host wishes to send data to the SLTA 10 Adapter The buffered link protocol up position is designed for host computers and applications that can accept and buffer back to back serial data without losing characters For example most real time operating systems and dev tty drivers in UNIX systems have this capability In this case the SLTA 10 Adapter simply sends the uplink message without any handshake with the host The SLTA 10 Adapter does not support hardware handshake or XON XOFF software flow control when directly attached to a host If the buffered link protocol option is enabled up position the buffered protocol is also used when the host wishes to send data to the SLTA 10 Adapter The buffered link protocol should not be used when CF G2 is set to the Remote Host state up position See Buffered Link Protocol in Chapter 9 for additional application restrictions when using the buffered link protocol Modem Support Switch 2 CFG2 Remote Host modem Local Host default Figure 12 SLTA 10 Adapter Host Switch2 CFG2 Switch2 CF G2 controls the use of the SLTA 10 Adapter with a modem If the SLTA 10 Adapter is connected directly to a host then CF G2 should be set to the Local Host state down position This is the SLTA 10 Adapter default If the SLTA 10 Adapter is connected to a modem then CF G2 must be set to the Remote Host state up position and CFG3 must be set to ALERT ACK down position SLTA 10 Adapter
82. hen disconnected from the SLTA 10 Adapter Calls to the read function will result in no network interface data messages LDV_NO_MSG_AVATIL and any call toa write function that needs to communicate with the SLTA 10 Adapter via the modems will result in a No Output Buffers Available error LDV_NO_BUFF_AVAIL Once the connection is made normal network interface traffic may resume This option also enables the reliable transport protocol This protocol includes the addition of a message sequence number and the end of message ACK NACK code See Chapter 4 for a description of this protocol N Disables the ALERT ACK network interface link protocol and enables the buffered network interface link protocol Network interface messages are sent without waiting for the ALERT ACK response Both sides of the interface the SLTA 10 Adapter and the driver must have the same setting This option should not be used with the m option Q Allows modem responses to be sent uplink to the host When the telephone link is disconnected these messages are ASCII strings with the network interface command type niDRIVER 0xF 0 If Q is specified the host application must be able to handle messages such aS NO CARRIER that might come from the modem itself if problems occur in the connection X Disables the buffer request protocol When this option is enabled the driver requests the buffer count from the SLTA 10 Adapter using the niSBUFC 0xE7 command whene
83. ial interface to the modem when the modem is not connected to a host and is used for modem initialization and control The raw I O interface is implemented in MSD_RAW cC for the DOS network driver and is not implemented in the UNIX network driver 5 Implement and test the buffer request states buffer management and read write interfaces These functions are implemented by MSD_EXEC c for the DOS network driver The read write interface is implemented in the 1dv_read and 1dv_write functions for the UNIX network driver The following files are unique to a DOS driver and would probably not be used in a port to another host MSD_DRVR H MSD_DIFC C MSD_FRST C MSD_LAST C MSD_SEGD ASM SLTA 10 Adapter User s Guide 80 Network Interface Protocol The network driver implements the host side of the network interface protocol providing an easy to use and interface independent read write interface to the host application The network interface protocol is a layered protocol that includes the following layers e Presentation Layer Defines packet formats for network variables and explicit messages This is the only layer visible to the host application The remaining layers are managed by the network driver e Session Layer Manages flow control buffer requests and grants e Transport Layer Ensures end to end reliability between the host and the SLTA 10 Adapter e Link Layer Controls access to the serial link e Physical Layer ElA 232 i
84. idestep the downlink buffer request protocol In this case the complete message is sent downlink without any buffer request step If the SLTA 10 Adapter has a free output buffer then the message will be transferred into the SLTA 10 Adapter successfully If not there will be no indication and the message will be lost The exception to this case is when using the transport layer protocol in which case the SLTA 10 Adapter will send the NACK tothe host which should force the host to re send the message Otherwise in order to use this feature successfully the host driver must manage the number of available output buffers within the SLTA 10 Adapter This feature has been added to the DOS driver for the SLTA 10 Adapter SLTA 10 Adapter User s Guide 88 Presentation Layer Protocol The network driver exchanges LonTalk packets with the host application at the presentation layer The LonTalk packet enclosed in a command of type nicomM or niNETMGMT is described in detail in the Host Application Programmer s Guide It is summarized here for convenience ExpMsgHadr Message or Header NetVarHdr size 3 SendAdarDtl or Network RevAddrDtl Address or size 11 RespAddrDtl nee Data i size ExplicitMsg vares l Figure 36 Application Buffer Format The SLTA 10 firmware is configured with explicit addressing enabled and therefore the 11 byte network address field is always present in an uplink or downlink buffer The firmware is also configured
85. imal operation of both HCU and for SLTA 10 Adapter to host phone links These should be included in the string arguments to HCU if they are not the modem defaults When possible the corresponding AT command is included e Command echo enabled 1 This is a personal preference and will result in modem commands being included in the HCU display SLTA 10 Adapter User s Guide 116 e Send modem responses enabled Q0 This causes the modem to respond to commands sent to it with a result code e Word responses v1 The modem result codes will be expressed as full word codes alphabetical rather than as numerical codes e Full response set x4 or x2 This will include the Busy and NO DIALTONE responses which will expedite the process when these cases occur e Data Carrier Detect signal DCD reflects carrier state amp c1 e DTE flow control disable S58 0 for Telebit modems K0 for Hayes modems If your modem uses software XKON XOF F flow control you must disable it since the SLTA 10 Adapter link layer is a binary one e Auto answer enabled s0 1 If you need your Host modem to answer to an incoming call from a remote SLTA 10 Adapter and modem you will need to enable this feature Status and Error Reporting HCU will print its progress to the standard output device which defaults tothe CRT screen The format of this display is HCU mm dd yy hh mm ss progress string where mm dd yy isthe
86. ing Call Initiation The four scenarios for call initiation are dial in to the network only dial out to the remote PC only dial in dial out and callback Dial In to the Network Only In the most straight forward case a user launches an application The application opens the driver which is associated with a particular link The SLTALink Manager application dials the phone number in the link or the phone number the application passes down to the SLTALink Manager perhaps to a generic link and establishes the connection Similarly the user could select the link from within the SLTALink Manager and cause a manual connection At this point either the SLTALink Manager would launch the pre determined application from the information stored in the link file or the user could manually launch the application In all of these cases the user is assumed to initiate the call The user could be a human operator or another application that initiates a dial in based on a clock for example For the dial in only scenario the system strategy issues primarily have to do with associating the link or phone number with the application Where there are only one or two links this is very easy When one PC host can be connected to many different networks we offer two standard solutions The first is to have the user navigate the SLTALink Manager s GUI Under the Link menu the Select item lists approximately 40 links of the 1000 possible The second solut
87. ion is a SLTA 10 Adapter User s Guide 58 monitoring application that programmatically interacts with the SLTALink Manager to send down the appropriate phone number perhaps to a generic out going link Dial Out to the Remote PC Only The three common approaches for initiating a dial out are sending a network variable update to the SLTA 10 Adapter sending an AddMyNSI message to the SLTA 10 Adapter or sending an explicit message from a Helper Dialer node on the network In the first case the remote host application needs to have an explicitly bound input network variable and the SLTA 10 Adapter s NSI mode EEPROM must be configured correctly See Chapter 11 for more information on configuring the SLTA 10 s EEPROM Seealso Call Termination below In the second case the remote host PC is assumed to have the NSS engine and a second NSI on the network perhaps a service technician with a laptop running a PCC 10 card is required to send the AddMyNSI message Also SLTA 10 Adapter s NSI mode EEPROM must be configured correctly See Chapter 11 for more information on configuring the SLTA 10 s EEPROM In the third case a custom Neuron Chip application must be written All three cases could be used with the same SLTA 10 Adapter In the dial out only case besides the call initiation the SLTALink Manager must be able to launch the appropriate application with the correct database and device driver name One system solution is to
88. is ready Once the ALERT ACK byte is received by the sender it sends the rest of the message without any other interactions The length byte value describes the length of the network interface command byte plus the length of the data field This value will always be at least 1 The checksum is a two s complement of the sum of the command byte and all of the bytes in the data field if it exists If the receiver receives a message in sequence with a valid checksum it responds with an ACK 0x06 Otherwise it responds with a NACK 0x15 requesting a retransmission SLTA 10 Adapter User s Guide 84 Sender Receiver ALERT 01 ALERT ACK FE Only transmitted with sequence number ALERT ACK link Link Layer protocol Header length not_length network interface command data checksum ACK or NACK ACK 0x06 NACK 0x15 Figure 33 SLTA 10 Adapter Reliable Transport Protocol SLTA 10 Adapter Timing Data Certain aspects of the SLTA 10 Adapter link and transport layer protocols implement fail safe timeouts in order to control the time spent waiting for protocol states to change when errors occur Downlink Byte to Byte Receive Timeout The downlink byte to byte receive timeout is the maximum allowable period between the end of a single byte data frame sent downlink to the SLTA 10 Adapter to the end of the next single byte data frame sent downlink tothe SLTA 10 Adapter This period is 100ms in local host mode and 1 second in remote
89. is recognized correctly and will respond with an ALERT ACK character hex FE when it selects the matching serial bit rate The SLTA 10 Adapter DOS network driver sends this sequence automatically if the autobaud option A is specified The default for an SLTA 10 Adapter is Autobaud Disable Autobaud Enabled Autobaud Disabled default Baud Determined by Switches 6 7 and 8 Figure 15 SLTA 10 Adapter Autobaud Switch 5 AB If the A option is specified for the DOS network driver the driver sends the autobaud sequence every time the driver is opened However if the AB option is enabled the driver must re send the autobaud sequence every time the SLTA 10 Adapter cycles power For the Windows NT network driver thereis no a option Using the Windows NT driver the autobaud sequence is attempted following power up if Autobaud Enabled is selected otherwise the default autobaud will not be attempted Serial Bit Rate Switches 6 8 BAUDI2 0 Switches 6 to 8 named BAUD 2 0 are used to set the SLTA 10 Adapter serial bit rate This setting is only used if autobaud operation is disabled There are eight available bit rates The SLTA 10 Adapter is configured for 38 400 bps with autobaud disabled by default All data are transmitted using 1 start bit 8 data bits no parity bits and 1 stop bit The B option is used to specify the serial bit rate to the DOS network driver For the Windows NT network driver there is no B op
90. lock rate or hardware properties This may occur for example if you specify default_hw_props instead of the correct one Toinstall the SLTA 10 Adapter in a LonBuilder network using the service pin you must either connect the SLTA 10 Adapter to a host and open the network driver for example by running HA or else set Switch3 CF G1 to the Network Enable state When installing the SLTA 10 Adapter node the channel definition must match the transceiver on the SLTA 10 Adapter If it does not the SLTA 10 Adapter will not accept the new values A No response is required tothe prompt Do you want to install communications parameters DONOT usethe Yes responsetotheprompt Do you want to install communications parameters unless the channad and hardware definitions are compatible with thetransceiver and input clock on the SLTA 10 Adapter When defining the application image the App Image Origin field should be set to Interface File andtheApp Image Name should be set to the name of an external interface file XIF created as described under Binding to a Host Nodein Chapter 3 of the LONWORKS Host Application Programmer s Guide WARNING This is NOT the default setting for the App Image Origin If you specify a Neuron C sourcefileas the App Image Origin theSLTA 10 Adapter may be rendered unusable If the SLTA 10 Adapter is accidentally configured with the wrong communication parameters it may be rebooted with the NODEUTIL application available o
91. lso the system state mode or health information Monitoring LNS Application Design Issues A well designed LNS monitoring application using the SLTA 10 Adapter through modems should use the correct version and layer of LNS should handle initialization of the application with the correct LNS database and device driver name and should have a phone call session termination and an application termination strategy The remote monitoring application is based on LNS Object Server of LNS 1 5 or higher Applications based on the LNS 1 0 and LNS 1 01 do not behave well by default and do not allow for certain dial out scenarios Applications written at the NSS layer are not supported for use with the SLTA 10 Adapter across a pair of modems The remote monitoring application should open the correct LNS database with the correct device driver Specifically the mapping of the Remote ID to the LNS database should be handled by the application We suggest using the command line arguments with the information available from the SLTALink Manager Note LNS capacity keys may need to be hard coded in the monitoring application Finally the LNS application needs to implement a termination strategy that meets the needs of the application and the system Good Practices Schemes that Work Use these guidelines to avoid the system level failures detailed above e When expecting the SLTA 10 Adapter to dial out from the network to a remote PC dedicate one SLTA 10
92. n Echelon s web site See the README TXT file included with NODEUTIL for a description See the NodeBuilder User s Guide for information on creating an SLTA 10 Adapter node using the NodeBuilder tools The Application mage Type for an SLTA 10 Adapter must be set to External The Application mage file name should be set to the name of an external interface XI F file Installing an SLTA 10 Adapter with LonManager API the DOS based LonManager LonMaker Installation Tool or DDE Server When an SLTA 10 Adapter is used as a network interface for a host application based on the LonManager API these installation steps are automatically handled by the LonM anager API 1xt_open function call When an SLTA 10 Adapter is used as a network interface for a network management PC running LonMaker or a LonManager API based application these installation steps are automatically handled by the LonMaker Attach command or the LonManager API 1xt_open function call When an SLTA 10 Adapter is used as a network interface for a control and monitoring PC running the LonM anager DDE Server these installation steps are automatically handled by the DDE Server SLTA 10 Adapter User s Guide 94 Chapter 11 Using the SLTA 10 Adapter with a Modem This chapter describes the operation of the SLTA 10 Adapter when a remote host computer is connected via a pair of modems to the SLTA 10 Adapter In this set up any node on the network may req
93. n needs to send local write memory network management messages to change the program ID SeetheLNS Host API Programmer s Guide for further information Table 13 SLTA 10 Adapter NSI mode Default and Minimum Buffer Configuration NSI mode Buffer Parameter Default Count Default Size Default Total in Bytes Bytes FTranemitvansastn butes 2 s Networcinputbutes 2 e e Network ouput ouies 2 e e ee rm rm w ow rm z Priority net output buffers Total bytes used for buffers Note Itis very important that the LNS application changetheSLTA 10 Adapter s NSI mode program ID TheNetwork Services Serve NSS uses the program ID asa uniqueidentifier of a device s external interface Thefirst device encountered by the NSS with a given program ID defines the external interface for all devices with that program ID To ensurethat the NSI mode SLTA 10 Adapter s unique external interface is recognized by the NSS it must given a unique program ID SLTA 10 Adapter User s Guide 37 SLTA 10 Adapter User s Guide 38 Chapter 5 The SLTA 10 NSI Mode Software This chapter describes the Windows NT software used with the SLTA 10 NSI mode This software is available in the Connectivity Starter Kit Model 58030 01 as part of the LNS Developer s Kit for Windows Model 34303 versions 1 5 and higher and on the Echelon web site at www echelon com Skip this Chapter if you are using the SLTA 10 MIP mode SLTA 10 A
94. nal Ground Pin 7 Pin 7 Pin 5 Pin 5 SLTA 10 PC DTE i DCE DB 25 DB 9 female end male end Figure 6 PC 25 Pin to DB 9 Connection Attaching the SLTA 10 Adapter to a Modem You must use the specific null modem cable described below to attach the SLTA 10 Adapter toa modem Table 7 DCE Modem to SLTA 10 Adapter Connection DB 9 to DB 9 Modem Signal Cable DB 9 Null Cable DB9 Male SLTA 10 DCE Name Male Modem DB 9 Female RxD Pin 2 Pin 2 Pin 2 3 Pin 3 TxD Pin 3 TxD Pin 3 Pin 3 Pin 3 2 Pin 2 RxD Pin 2 DCD Pin1 Pin 1 Pin 1 4 Pin 4 DTR Pin 4 DTR Pin 4 Pins 4 amp 7 Pins Pin 6 DSR Pin 6 RTS Pin 7 4 7 6 GND Pin 5 Pin 5 Pin 5 5 Pin 5 GND Pin 5 DB 9 male end Null Modem SLTA 10 DB 9 male end Figure 7 DCE Modem to SLTA 10 Adapter Connection DB 9 to DB 9 SLTA 10 Adapter User s Guide 27 Table 8 DCE Modem to SLTA 10 Adapter Connection DB 25 to DB 9 Modem Signal Cable DB 25 Cable DB9 Male SLTA 10 DCE Name Male DB 9 Female RxD Pin 3 Pin 3 Pin 3 TxD Pin 3 TxD Pin 2 Pin 2 Pin2 RxD Pin 2 DCD Pin8 Pin 8 Pin 4 DTR Pin 4 DTR Pin 20 Pins 20 amp 4 Pin 6 DSR Pin 6 RTS Pin 4 GND Pin 7 Pin 7 Pin 5 GND Pin 5 DB 25 Null DB 9 male end Modem male end Figure 8 SLTA 10 Adapter Null Modem Cable DB 25 to DB 9 Attaching the SLTA 10 Adapter to a Network The network connector for the SLTA 10 Adapter is
95. ncerned about possible conflicts in the choice of message codes The additional SLTA 10 Adapter network management messages use the reserved message code 7D hex The first data byte is used as a sub code and is 01 hex to indicate an SLTA 10 Adapter function The second data byteis a specific application command code Table 16 summarizes the network management messages specific to the SLTA 10 Adapter Table 16 SLTA 10 Adapter Network Management Messages Message Code Message Sub Application Function code Command 0x7D 1 1 Product Query 0x7D 1 2 Send Modem String 0x7D 1 3 Modem Status Readback 0x7D 1 4 Modem Response Query 0x7D 1 5 Connection Status Query 0x7D 1 6 Install Directory Entry 0x7D 1 7 Dial From Directory 0x7D 1 8 Hang up 0x7D 1 9 Install Password 0x7D 1 10 Install Modem Configuration String 0x7D 1 11 Install Hangup String 0x7D 1 12 Install Dial Prefix 0x7D 1 13 Install Hangup Timer 0x7D 1 14 Configure Modem 0x7D 1 15 Request Release Modem 0x7D 1 16 Clear EEPROM Pool 0x7D 1 17 Install NV Connect 0x7D 1 18 Install NSI Connect 0x7D 1 19 Install Callback Enable 0x7D 1 20 Report SLTA EEPROM contents These network management messages may be sent from any node on the network to the SLTA 10 Adapter If an application node wishes to send modem control network management messages to the SLTA 10 Adapter it does so using explicit messaging See Chapter 4
96. nctions for network installation maintanence monitoring and control The LonManager DDE Server provides a simple Dynamic Data E xchange DDE interface for other client Windows applications to access toa LONWORKS based network for monitoring and control Programs specify a logical network driver name when first requesting access to the network The WLDV DLL supports simultaneous access toa maximum of eight 8 DOS drivers The functions provided by WLDV DLL are described in the following section SLTA 10 Adapter User s Guide 123 Idv_close Purpose Terminates access to the network interface hardware Syntax include lt ldv h gt short ldv_close short handle See Also ldv_open Returns LDV_OK 0 Device closed successfully LDV_NOT_OPEN 3 Invalid handle or device not open Parameters handle short Device identifier returned by 1dv_open SLTA 10 Adapter User s Guide 124 Idv_get_version Purpose Returns the current version of the driver DLL as a text string Format of the version string is M mml sss where M is the major release number mm is the minor release number and sss is an option sub release number All numbers are decimal Using this function allows your application to verify that a compatible version of the driver WLDV DLL is loaded Syntax include lt ldv h gt const char far ldv_get_version void See Also None Returns char far Character pointer to
97. nds until the correct password is sent downlink If the password is correct the SLTA 10 Adapter will respond with the niAck code Otherwise the SLTA 10 Adapter will respond with the niNACK code Install Modem Configuration String Whenever the SLTA 10 Adapter is either powered or reset the connection state is not CONNECTED or is commanded to by the Configure M odem message the SLTA 10 Adapter will send its modem SLTA 10 Adapter User s Guide 106 configuration string to the modem This string is stored in EEPROM and may be changed by this message The default setting for this string is ATE0 amp C1 amp D2S0 1 The commands specified in this string are e E0 isthe AT command to disable local echo of characters received by the modem e amp C1 isthe AT command to enable the Data Carrier Detect DCD output of the modem which is active when the modem detects the carrier signal of another modem on the line e amp D2 isthe AT command to enable the Data Terminal Ready DTR input of the modem The modem will hang up enter command state and disable auto answer when it detects an on to off transition of the DTR input e 0 1 isthe AT command to set register SO to 1 meaning that the modem should auto answer incoming calls on the first ring This option should be used if remote hosts will be dialing in to the SLTA 10 Adapter Use so 0 if the SLTA 10 Adapter will only be used for dialing out to remote hosts
98. ng out to a remote SLTA 10 Adapter requires running the DOS program HCU EXE in a session prior to running the Windows API application The HCU source code is available from Echelon for integration into a DOS application When using HCU with the Windows 95 operating system use the following procedure e Start Windows 95 e Start a DOS box Makethe DOS box a small window e Run HCU in the DOS box e After the message successfully connected and the DOS prompt appears EXIT type c gt exit DOS box e Then run the application Usage Examples To connect at 9600 bps with a modem initialization string included in the process HCU b9600 pSLTA_2 0 ATM1E1S8 1 ATDT9 555 1234 It is important to remember to include the carriage return at the end of each command string argument To hangup HCU h ATHO which includes the Hayes AT command mode escape sequence The following is a DOS batch file which will make the connection using a script dial cmd execute a host program hostapp exe and then hangup echo off hcu b9600 pSLTA_2 0 dial cmd if not errorlevel 1 hostapp exe heu h atho If using a Windows based network management application a connection can be created by using HCU and then closing the DOS box before initializing the connection with 1xt_open Suggested Modem Configurations Following is a list of configuration settings that are suggested for opt
99. ng with LNS Installing with the LonBuilder or NodeBuilder Tools Installing an SLTA 10 Adapter with LonManager API the DOS based LonMamager LonMaker Installation Tool or DDE Server Using the SLTA 10 Adapter with a Modem Overview SLTA 10 Adapter Connection States Command Set Assumptions Translated Characters DTE Connections Network Management Messages EEPROM String Pool Management Product Query Send Modem String Modem Response Query Connection Status Query Install Directory Entry Dial From Directory Hang up Install Password Install Modem Configuration String Install Hangup String MIP mode only Install Dial Prefix Install Hangup Timer Configure Modem Request Release SLTA SLTA 10 Adapter User s Guide Clear EEPROM Pool Install NVConnect NSI mode only Install NSI Connect NSI mode only Install CallbackE nable NSI mode only Report SLTAEE NSI mode only Modem Compatibility 12 Using the DOS Host Connect Utility with the SLTA 10 MIP Mode HCU Usage Theory of Operation Usage Examples Suggested Modem Configurations Status and Error Reporting 13 Modem Troubleshooting Troubleshooting a Modem Link SLTA 10 Adapter and Modem Do Not Answer or Pick Up Modems Will Not Connect SLTA 10 Adapter to Host Link Fails Completely SLTA 10 Adapter to Host Link Fails Partially SLTA 10 Adapter Sends Modem Configuration String But It Has No Effect Appendix A Windows DLL Idv_close Idv_get_version Idv_open Idv_read Idv_write
100. nk Protocol default Figure 11 SLTA 10 Adapter Link Protocol Switch1 CFG3 Switch1 CF G3 controls the network interface link protocol used between the SLTA 10 Adapter and a local host when in MIP mode For NSI mode leave this switch in the default position Two link protocols are available for the SLTA 10 MIP mode the SLTA 10 Adapter ALERT ACK link protocol and the buffered link protocol The ALERT ACK link protocol is designed for host computers that cannot accept asynchronously occurring streams of serial data at high speed For example a PC running DOS or Windows SLTA 10 Adapter User s Guide 30 cannot guarantee receipt of all characters in an input stream appearing back to back on a COM port ALERT ACK link protocol down position is the default setting for the SLTA 10 Adapter When the SLTA 10 Adapter uses the ALERT ACK protocol and it wishes to send data to the host it first sends a single ALERT character hex 01 The host then responds with an ALERT ACK character hex FE to indicate its readiness to accept the rest of the data The ALERT ACK protocol places timing requirements on the host and if these timing requirements are violated a driver error occurs After the host network driver has sent the ALERT ACK character it enters a tightly controlled loop for accepting the remaining characters usually with interrupts disabled If this option is enabled switch in down position the ALERT ACK protocol will also be used w
101. normal dial out call and launches the application contained in the link At this point there may be two copies of the application open Depending on sharing configuration the second application may fail because appropriate LNS database in already opened To prevent these failures Echelon recommends that the initial call should either be a manual connection from within the SLTALink Manager or the initial call should originate from a dummy application that terminates itself without opening the LNS databases Call Termination The four scenarios for call termination include termination of the host application application controlled hang up a manual disconnect in the SLTALink Manager and time out In all of these cases the important system level issues involve making sure that the termination strategy is compatible with the call initiation strategy The behavior of an application at termination is not always known By default applications based on the Object Server of LNS 1 5 and higher should exhibit two types of behavior First if the interface adapter is an SLTA 10 Adapter in NSI modem using modems and there are explicitly bound network variables to the host application then at the LNS application s termination the host network variables and their connections should not be removed from the LNS database This behavior facilitates the use of the first case described under Dial Out to the Remote PC Only where a network variable update ad
102. not be cleared when the modem disconnects aiding in diagnosis of connection problems typedef struct byte sub_code always 1 byte app_command value 4 byte max_length limits the size of the response ANM_modem_response_query_request typedef struct char response null terminated string ANM_modem_response_query_response Connection Status Query The SLTA 10 Adapter s connection status may be polled with this message Most modems may be configured with various time outs for the different stages of establishing a connection Consult your modem s documentation for details typedef struct byte sub_code always 1 byte app_command value 5 ANM_connect_state_request typedef enum IDLE 0 FAILED 1 CALL_IN_PROCESS 2 CONNECTED 3 CONN_state typedef struct CONN_state connection_state ANM_connect_state_response Install Directory Entry This message stores a dial out directory entry in the SLTA 10 Adapter s EEPROM string pool Up to 5 dial out entries can be stored in the SLTA 10 NSI mode EEPROM pool up to 8 can be stored SLTA 10 Adapter User s Guide 104 in the SLTA 10 MIP mode EEPROM pool The entries are numbered 0 to 4 or 0 to 7 as specified by the dir_nunm field typedef struct byte sub_code always 1 byte app_command value 6 byte dir_num value 0 7 for MIP 0 4 for NSI byte total_size of the data string byte offset
103. nterface The physical layer is defined by the EIA RS 232 standard The link transport session and presentation layers are described in the following sections Link Layer Protocol The default interface link layer protocol is the ALERT ACK protocol This protocol may be used when the host is a microcontroller or microprocessor such as a PC running DOS or Windows The alternative interface link protocol is the buffered protocol This protocol is used with computer hosts that can asynchronously buffer an entire packet All data are transmitted using 1 start bit 8 data bits no parity bits and 1 stop bit ALERT ACK Link Protocol The DOS network driver uses the ALERT ACK link protocol by default i e the N option is not specified See Chapter 8 for a description of the network driver options The UNIX network driver uses the ALERT ACK link protocol if the alert_ack_prtcl variable is set to TRUE in the source code this is not the default The Switch1 CF G3 input of the SLTA 10 Adapter as described in Chapter 4 must be in the ALERT ACK state DOWN position When using this protocol all transfers between the SLTA 10 Adapter and the host consist of serial data streams that start off with the link layer header sequence described in figure 31 Whenever one device either the SLTA 10 Adapter or the host needs to send a command or message the sender starts the sequence by transmitting the ALERT byte value 01 hex When this byte is rec
104. o occur without breaking the connection The SLTA 10 Adapter will not preserve the connection state after it has been through a power reset SLTA 10 Adapter User s Guide 97 Command Set Assumptions The SLTA 10 Adapter uses the following strings received from the modem to interpret the connection state These strings are consistent with all Hayes AT compatible modems operating in the word response mode alphabetic responses CR is the hex OD character CONNECT any text CR BUSY CR VOICE CR No any text CR ERROR CR The CONNECT string may be and typically is followed by other informative text such as connection serial bit rate or error correction methods in use These other four states indicate a failure to make the connection Translated Characters All strings that are sent specifically to the modem as commands by the SLTA 10 Adapter are scanned for certain characters by the SLTA 10 firmware These characters are then translated into specific functions or characters unless they are preceded by a backslash The characters are The tilde will cause the SLTA 10 Adapter to pause 500ms before sending the next character to the modem The tilde itself is not sent The exclamation point will cause the SLTA 10 Adapter to send a carriage return 0x0H to the modem The exclamation point itself is not sent The tilde is provided for users familiar with existing modem packages It can be use
105. of the Neuron C Programmer s Guide for details on explicit messaging The message should be delivered using SLTA 10 Adapter User s Guide 99 request response service and the message code for modem control messages is always 7D hex The data portion of the message always begins with a sub code value of 1 indicating that the message is addressed to an SLTA 10 Adapter followed by an application command byte indicating which modem control command this is This is followed by parameters specific to the application command These messages may be sent by a Neuron C based node a node based on the Microprocessor Interface Program MIP or a node based on another SLTA 10 Adapter See the supplied Neuron C program DIALOUT NC for an example of an application that sends a message to an SLTA 10 Adapter to cause it to dial out using an attached modem The example GIZSETUP NC sends messages to an SLTA 10 Adapter to configure its modem strings using a Gizmo I O module as the user interface A node can send these messages using either implicit or explicit addressing When implicit addressing is used a network management tool binds the output message tag in the node wishing to send the message to the SLTA 10 Adapter as the destination When explicit addressing is used the node wishing to send the message must explicitly insert the destination address in the outgoing message Note that the SLTA 10 Adapter will be unable to receive any messages including the
106. oking an Application Enabling a Callback Diagnostics The SLTALink Manager Programmatic Interface Using the DOS Stub Driver Characteristics of a Well Designed System Call Initiation Dial In to the Network Only Dial Out to the Remote PC Only Dial In Dial Out Callback Call Termination Monitoring Application Termination Strategy Monitoring Missing Messages after a Dial Out Monitoring LNS Application Design Issues Good Practices Schemes that Work Using the DOS Driver with SLTA 10 MIP Mode Installing the SLTA 10 Mip Mode Driver for DOS Buffer Options Serial Bit Rate Options DOS Device Options Timing Options Network Interface Protocol Options Calling the Network Driver from a Host Application Using the SLTA 10 Adapter Driver under Microsoft Windows 3 1x SLTA 10 Adapter User s Guide 9 10 11 Creating an SLTA 10 MIP Mode Driver Purpose of the Network Driver Example Network Drivers Implementing an SLTA 10 MIP Mode Network Driver Network Interface Protocol Link Layer Protocol ALERT ACK Link Protocol Buffered Link Protocol Transport Layer Protocol SLTA 10 Adapter Timing Data Downlink Byte to Byte Receive Timeout Uplink Message Life ACK NACK Receive Timeout Uplink Timeout Message Retry Count Session Layer Protocol Downlink Buffer Request Protocol Uplink Flow Control Protocol Presentation Layer Protocol Initialization and Installation Initializing an SLTA 10 Adapter Installing an SLTA 10 Adapter on a Network Installi
107. ol The network interface link and transport protocols described above are used for all host to SLTA communications Layered on top of these protocols is a downlink buffer request protocol and an uplink flow control protocol Downlink Buffer Request Protocol The network driver receives application buffers from the host application translates them to interface buffers and passes the interface buffers to the SLTA 10 Adapter There are two types of downlink commands from the host to the SLTA 10 Adapter commands that can be executed directly by the SLTA 10 Adapter and commands that need to be buffered in the SLTA 10 Adapter Downlink commands that are executed directly by the SLTA 10 Adapter are niRESET niFLUSH CANCEL niONLINE niOFFLINE niFLUSH niFLUSH_IGN niPUPXOFF niPUPXON niSLEEP and niSSTATUS See the Host Application Programmer s Guide Appendix D for a description of these commands TheniSStatus command when sent downlink will cause the SLTA 10 Adapter to respond with a niSStatus command plus one byte of data In MIP mode this byte of data contains the settings of configuration switches with BAU DO being the least significant bit In NSI mode this byte of data contains 011 in the least significant bits followed by the XID information making the SLTA 10 Adapter NSI mode consistent with the PCNSI Adapter Downlink commands that are buffered in the SLTA 10 Adapter are niNETMGM
108. om application as described in the LONWORKS Host Application Programmer s Guide The host application may also be a network management or monitoring application based on the LonManager API LonManager LonMaker installation tool or LonManager DDE Server The firmwarein an SLTA 10 Adapter is fixed in ROM and cannot be reprogrammed Installing the SLTA 10 MIP Mode Adapter Software The SLTA 10 Adapter software is supplied in the Connectivity Starter Kit as a diskette The SLTA 10 DOS driver operates under DOS Windows 3 1x and Windows 95 operating systems To install the SLTA 10 Adapter software follow these steps 1 Place the diskette in one of the disk drives of your PC This will typically bethea or B drive Under the Windows 95 operating system open a DOS console 2 Start the automatic installation procedure by entering A INSTALL ENTER Substitute your disk drive name for the a if you are using a different drive 3 You will be asked to enter the name of your LONWORKS installation directory C LONWORKS is the default The SLTA 10 Adapter software will be installed in the sLTA sub directory of your LONWORKS directory with the exception of the DOS network driver LDVSLTA SyS This file will be installed in the BIN sub directory of your LONWORKS directory To install the DOS network driver into your CONFIG SYS file follow the instructions in Chapter 8 SLTA 10 Adapter User s Guide 44 The SLTA directory will con
109. options Table 9 SLTA 10 Adapter Network Disable Switch Configuration Network DOS Driver When SLTA 10 Adapter Disable Z Option Enables Network Input Communications Disabled Specified Host application up position command Disabled Not specified Opening network driver up position default Enabled Don t care Immediately after reset default down position Serial Network Services Interface Switch4 NSI NSI Mode Firmware default MIP Mode Firmware Figure 14 SLTA 10 Adapter Firmware Switch 4 NSI The SLTA 10 Adapter has an SLTA 10 NSI mode firmware switch which is Switch4 NSI Itis factory set in the up position for use of the SLTA 10 NSI mode firmware The down position is for the MIP mode firmware SLTA 10 Adapter User s Guide 33 Autobaud AB The switch 5 labeled AB on the SLTA 10 Adapter is used to select automatic baud rate detection the autobaud feature Autobaud must not be used when the SLTA 10 Adapter is used with a modem When autobaud is enabled the SLTA 10 Adapter matches the serial bit rate of a local host When powered the SLTA 10 Adapter looks for a 0 byte from the host The SLTA 10 Adapter cycles through all the serial bit rates until a 0 is recognized Toinitialize the SLTA 10 Adapter the host must transmit eight binary zeroes or ASCII NU Ls spaced at least 50ms apart The SLTA 10 Adapter will try all of its bit rates until the zero character
110. or HA a sample host application for MS DOS that can be used as a basis for a user developed host application on other host platforms This application provides examples of sending and receiving network variable messages as well as allowing a node based on an SLTA 10 Adapter to be installed and bound by a network management tool such as the LonManager LonMaker Installation Tool or the LonBuilder network manager A network driver for DOS permits the SLTA 10 Adapter to be used with DOS applications Source code for a DOS network driver is provided as a basis for a user developed network driver for other hosts or operating systems On a separate diskette DLL software is provided to make it easier to use the network driver under the Microsoft Windows 3 1x operating system An executable program and source code is also provided for a Host Connection Utility HCU which may be used to initiate and terminate the host to SLTA 10 Adapter connection when the SLTA 10 Adapter is used with a remote host An example written in Neuron C is also provided as a basis for user developed nodes on a LONWORKS network that need to initiate outgoing calls toa remote host The SLTA 10 Adapter includes firmware that moves the upper layers of the LonTalk Protocol off the Neuron Chip within an SLTA 10 Adapter onto a host processor This firmware allows the SLTA 10 Adapter to be used by a host application to send and receive LonTalk messages The host application may be a cust
111. or example if the network driver sends the nicOMM niTQ_P command requesting a priority output buffer and follows this with a message transfer with the non priority niCOMM niTQ command the SLTA 10 Adapter will incorrectly store the message in a priority output buffer the type originally requested Uplink Flow Control Protocol Uplink traffic may be incoming LonTalk messages output buffer request acknowledgments completion events or local commands The network driver translates the interface buffers to application buffer format and stores the buffers in a queue until the host application is ready to read them There is no buffer request protocol for uplink traffic The network driver is normally assumed to have sufficient buffers The network driver can suspend or resume uplink traffic when no network driver input buffers are available by sending the Uplink Source Quench niPUPXOFF command to the SLTA 10 Adapter This prevents the STLA from sending any LonTalk messages uplink When the network driver senses that network driver input buffers are available it sends the Uplink Source Resume niPUPXON command to resume uplink transfers Figure 35 summarizes the uplink state transitions Node Reset Receive niPUPXOFF Receive lt gt niFLUSH_CANCEL gt Receive niPUPXON Note Responses to niINETMGMT and niSSTATUS commands are allowed in the Flush state Figure 35 SLTA 10 Adapter Uplink Flow Control States The host may chose to s
112. ort the use of the SLTA 10 with modems although direct connect interfaces are supported Note A remote via modems LNS Server requires a dedicated SLTA 10 Adapter Thus some networks may require multiple SLTA 10 Adapters one for the remote LNS Server and others to allow access for other PCs SLTA 10 Adapter User s Guide 15 TAPI Compatibility The SLTALink Manager software uses TAPI release 1 3 or higher This is supported in Windows NT 4 0 but not in Windows NT 3 51 Thus Windows NT 3 51 does not support the use of the SLTA 10 Adapter with modems however Windows NT 3 51 does support a direct connect interface SLTA 10 Adapter User s Guide 16 Chapter 2 SLTA 10 Adapter Hardware This chapter provides a physical description of the SLTA 10 Adapter SLTA 10 Adapter User s Guide Mechanical Description Figures 2 and 3 show the SLTA 10 Adapter in its enclosure Figure 4 shows the SLTA 10 Adapter board without an enclosure 5 44 138 12 4 00 se ALL DIMENSIONS ARE IN INCHES WIH EOUN mm DIMENSIONS IN BRACKETS Figure 2 SLTA 10 Adapter Enclosure SLTA 10 Adapter User s Guide 18 Figure 3 shows a 1 1 view of the enclosure and may be used as a mounting template Figure 3 SLTA 10 Adapter Enclosure Keyhole View Mounting Slots SLTA 10 Adapter User s Guide 19 Component Side View S2 Service Button J5 DS1 EIA 232 Service Data Port LED S1 DS2 Config Power
113. otocol This option is not recommended for connection operations X To exit HCU with the network driver s modem support mode disabled Use with the H option to disconnect from a remote SLTA 10 Adapter for subsequent connection to a local SLTA 10 Adapter All options must precede string arguments on the command line when evaluated from left to right The string arguments are modem command strings typically Hayes compatible AT commands These strings are sent directly to the modem For details of the allowable commands see the documentation supplied by your modem manufacturer If more than one string is included HCU will wait for the oK response from the modem before sending the next string This requires that word alphabetic modem responses are enabled in the modem If the ok response does not appear within 4 seconds HCU will stop waiting and proceed to the next string In most cases the command string arguments need to be terminated with a carriage return The carriage return is represented by the character HCU will interpret the character by sending a carriage return 0x0D to the modem HCU will also interpret the character by pausing 500ms If either of these characters themselves need to be sent to the modem they can be SLTA 10 Adapter User s Guide 114 escaped with a leading backslash or HCU does not send implied carriage returns at the end of each string Spaces may be included in the
114. ovided it is not in the CONNECTED state See the Install Modem Configuration String message for further details If the modem is in the CONNECTED state the failed status will be returned typedef struct byte sub_code always 1 byte app_command value 14 ANM_modem_config_request SLTA 10 Adapter User s Guide 108 Request Release SLTA This message may be used to grant ownership access of the SLTA 10 Adapter to any node on the local network In a design where there may be more than one network node that wishes to control the SLTA 10 Adapter s connection states Request Rel ease provides a method of managing this control In this case a node will request the SLTA 10 Adapter and the response to this request will be successful code 0x3D if access was granted or failure code 0x1D if it was denied At the end of such a session the node which was granted ownership must release the SLTA 10 Adapter allowing other nodes access to it This process only works if all nodes employ this mechanism The request state is not preserved across resets of the SLTA 10 Adapter typedef struct byte sub_code always 1 byte app_command value 15 boolean reg_rel TRUE if request FALSE if release ANM_request_slta_request Clear EEPROM Pool This message will clear the entire EEPROM pool usage and will remove the following configurable strings The strings will be set to null strings not their default
115. owing CR is the carriage return Ox0D character The following indicates a successful connection CONNECT any text CR These indicate a failed connection No any text CR Busy CR VOICE CR e Any keyboard action This will abort the HCU process Once the connection is considered made HCU will process any additional modem responses for a few seconds It will then change the operational mode of the network driver to force direct mode off and modem responses off If this is a connection operation the selected network interface protocol is enabled If the Xx option is specified modem support is disabled Finally if the user has indicated that a password is to be used HCU will send the password command plus the password to the remote SLTA 10 Adapter and wait for a response If the response does not appear within five seconds or if the response is not an acknowledgment the process is repeated up to two additional times HCU will exit with a status of zero if the connection or hangup was successful Otherwise the exit status will be 1 Upon successful exit the network driver state will be set to modem responses off This implies that if the connection is broken during the course of a host application execution the network driver will not start sending modem responses back to the host application since it may not know how to handle them SLTA 10 Adapter User s Guide 115 If operating under Microsoft Windows 3 1x diali
116. ows NT Operating System version 3 51 or higher for a direct connect interface version 4 0 or higher for use with modems The SLTA 10 software cannot be installed from DOS or a DOS shell nor can it be installed on Windows 3 1 or Windows 3 11 or Windows 95 1 Before installing the software make sure that you have logged in as Administrator 2 Close all open programs 3 Insert the installation diskette into the PC 4 Click the Start button on the Windows task bar and select the run command If using with Windows NT 3 51 Within Program Manager choose the Run command from the File menu 5 When prompted for a program name enter the following A SETUP EXE If necessary replace A with the drive letter which corresponds to the drive containing the SLTA 10 NSI mode installation diskette 6 When prompted click the button marked Next gt SLTA 10 Adapter User s Guide 40 When prompted for a destination directory enter the desired installation directory By default this directory is c lonworks unless previous LONWORKS products have been installed and have registered a different path in the Windows Registry The path may be modified using the Browse button The next screen presented is shown in figure 17 This will determine the LONWORKS naming convention used for the SLTA 10 adapter You may specify a numeric base for the device name If you do not then by default the device namin
117. pendix A describes the Windows 3 1x DLL files for use with the SLTA 10 Adapter SLTA 10 Adapter User s Guide Related Manuals The following Echelon documents are suggested reading for more information The LCA Object and Data Server Programme s Guide describes how to write a 32 bit Windows host application and installation tool that can be used with the SLTA 10 NSI mode The LONWORKS Host Application Programmer s Guide describes how to write a host application that can be used with the SLTA 10 MIP mode The LonBuilder User s Guide describes how to develop LONWORKS applications with the LonBuilder Developer s Workbench The NodeBuilder User s Guide describes how to develop LONWORKS applications with the NodeBuilder Development Tool Both Motorola and Toshiba have authored Neuron Chip databooks containing specifications and literature that describe the architecture of the Neuron Chip Web Access Engineering bulletins and data sheets supporting this product are available on the Echelon Web site General information regarding Echelon its business and its products also are located on the site at http www echelon com SLTA 10 Adapter User s Guide 5 SLTA 10 Adapter User s Guide Contents Preface Content Related Manuals Web Access 1 SLTA 10 Adapter Overview Introduction Two Modes of Operation SLTA 10 NSI and MIP Modes SLTA 10 NSI Mode Features SLTA 10 MIP Mode Versus the SLTA 2 The SLTA 10 Adapte
118. permission of Echelon Corporation Printed in the United States of America Copyright 1996 1997 by Echelon Corporation Echelon Corporation 4015 Miranda Avenue Palo Alto CA 94304 USA SLTA 10 Adapter User s Guide Preface This document describes how to use the SLTA 10 Serial LonTalk Adapter to connect a host processor with an EIA 232 formerly RS 232 serial interface to a LONWORKS network SLTA 10 Adapter User s Guide 3 Content This manual provides detailed information about the hardware and software for the SLTA 10 Adapter Chapter 1 introduces the SLTA 10 Adapter and provides a quick overview Chapter 2 describes the SLTA 10 Adapter hardware Chapter 3 describes how to attach an SLTA 10 Adapter Chapter 4 describes the configuration switches of the SLTA 10 Adapter Chapter 5 describes the software for the SLTA 10 NSI mode Chapter 6 describes the software for the SLTA 10 MIP mode Chapter 7 discusses using the Windows NT network driver and the SLTALink Manager software with the SLTA 10 NSI mode Chapter 8 discusses using the DOS network driver with the SLTA 10 MIP mode Chapter 9 discusses creating an SLTA 10 MIP mode network driver for any host Chapter 10 describes initilization and installing as a node Chapter 11 discusses using an SLTA 10 Adapter with a modem Chapter 12 describes the DOS Host Connect Utility HCU for use with the SLTA 10 MIP mode Chapter 13 is a troubleshooting section Ap
119. ponded to the password command with a negative acknowledgment Y ou are probably using the wrong password Password Validation Complete Indicates a successful password command transfer with the remote SLTA 10 Adapter and that HCU has successfully communicated with the remote SLTA 10 Adapter Downlink Password Timeout Indicates no password acknowledgment or negative acknowledgment was received Either the remote SLTA 10 Adapter is not operational or the SLTA 10 Adapter link layer protocol does not match or there is a problem with transferring binary data across the modem connection Hangup Failed Still Indicates HCU still thinks that the connection is made following Connected a hangup This could be the result of a persistent DCD ON level SLTA 10 Adapter User s Guide 118 Chapter 13 Modem Troubleshooting This chapter provides solutions to problems that may arise with a modem attached to an SLTA 10 Adapter SLTA 10 Adapter User s Guide 119 Troubleshooting a Modem Link A Host Modem Modem SLTA 10 Adapter configuration has many user selected options including the choice of modems configuration of the modems the operating system of the host the network interface link protocol and the serial bit rates of both the host modem link layer and the SLTA 10 Adapter modem link layer SLTA 10 Adapter and Modem Do Not Answer or Pick Up The modem attached to the SLTA 10 Adapter must be configured to auto answer if you want
120. pter When the network driver is opened with the DOS open call it establishes communications with the SLTA 10 Adapter The network driver returns an error if this fails for example if the SLTA 10 Adapter is disconnected powered down or configured incorrectly If the open call succeeds the driver enables network communications by clearing the SLTA 10 Adapter FLUSH state if configured to do so The DOS read call is defined to return the number of bytes read from the device Some LONWORKS standard network drivers return 0 if there are no uplink messages available DOS reports this as an end of file condition and prevents further reads from succeeding However the SLTA 10 Adapter driver returns a length of 2 and sets the first byte of the caller s buffer the cmd queue byte to 0 to indicate that there is no uplink message available Normally the DOS read and write calls are not used with LONWORKS standard network drivers This is because any error from the network interface will display the familiar Abort Retry Fail error message from DOS unless the caller has installed a critical error device handler Therefore DOS applications using a network device typically call direct entry points into the driver This also allows more detailed error status to be returned to the application The addresses of these entry points are obtained by calling the ioct1 function of the driver This function call is used as follows int ioctl int handle int
121. r s Guide 107 Install Dial Prefix The default setting for this string is ATDT This string is sent as a prefix for any dial out operations This particular sequence instructs the modem to dial using Touch Tone DTMF signaling If pulse dialing is required the prefix should be set to ATDP typedef struct byte sub_code always 1 byte app_command value 12 byte total_size of the data string byte offset for incremental writes char dpre_string ANM_install_dpre_request This message uses the EEPROM pool to store the dial prefix See the section on EEPROM String Pool Management above for details Install Hangup Timer The hangup timer is controlled by an eight bit valuein EEPROM The default setting for this value is zero which results in no hangup timer action If the hangup timer is a non zero value the SLTA 10 Adapter will hang up and break a connection if in the CONNECTED state when the number of minutes specified by t imer_value have elapsed and no uplink or downlink activity has occurred The default value for this timeout is zero meaning that the phone connection will remain active indefinitely even if there is no activity on the link typedef struct byte sub_code always 1 byte app_command value 13 byte timer_value ANM_install_hangt_request Configure Modem This message will cause the SLTA 10 Adapter to send its Modem Configuration String to the modem pr
122. r together with the Windows 3 1x DLL software allows DOS and Windows 3 1x applications such as those based on the LonManager API to be debugged using the network driver for the LonBuilder Development Station These applications can later be used with the network driver for the SLTA 10 Adapter without modifying the host application A LONWORKS standard network driver must supply the functions defined under Network Driver Services in Chapter 4 of the LONWORKS Host Application Programmer s Guide The Windows 3 1x DLL software is described in Appendix A Example Network Drivers The Connectivity Starter Kit includes source code for an example DOS network driver the Echelon web site contains source code for an example UNIX network driver The DOS driver is used for both DOS and Windows 3 1x applications See the comments in the source code of the network drivers for an explanation of how the network drivers work These drivers can be used as templates for a LONWORKS standard network driver The DOS network driver is compatible with the LonM anager APIs for DOS and Windows the LonManager LonMaker installation tool and the LonManager DDE Server A sample host application for DOS is also supplied The functions ldv_open ldv_read ldv_write and ldv_close forma suitable operating system independent definition for the network driver These functions support multiple network interfaces and hide the DOS specific aspects of the DOS network driver
123. r Configurations Software Availability LNS 1 0 1 01 and 1 5 Compatibility TAPI Compatibility SLTA 10 Adapter Hardware Mechanical Description Switches Indicators and Connectors ESD Warning Connecting Power Cabling and Connections Attaching the SLTA 10 Adapter Attaching the SLTA 10 Adapter toa PC Attaching the SLTA 10 Adapter to a Modem Attaching the SLTA 10 Adapter to a Network Hardware Configuration Configuring the SLTA 10 Adapter Hardware Configuration Options Interface Link Protocol Control Switch1 CF G3 Modem Support Switch2 CF G2 Network Disable Switch3 CF G1 Serial Network Services Interface Switch4 NSI Autobaud AB Serial Bit Rate Switches 6 8 Baud 2 0 Configuring the SLTA 10 Adapter Software The SLTA 10 NSI Mode Software SLTA 10 NSI Mode Software Overview Windows NT Software Installation Procedure Windows NT Software Installation Results SLTA 10 Adapter User s Guide 6 The SLTA 10 MIP Mode Software SLTA 10 MIP Mode Software Overview Installing the SLTA 10 MIP Mode Adapter Software Installing the Windows 3 1x DLL Software Other Drivers Using the Windows NT Driver and SLTALink Manager with SLTA 10 NSI Mode Software Overview Establishing a Communications Line for Dialing in toa Network Establishing a Communication Line for Calls Dialed out to the PC Establishing Remote and Local Network Sites Name of Link Remote dentifier Link Type Configuring the Modem Line SLTA Password Inv
124. response to this message indicates that the SLTA 10 Adapter has sent the dial out command to the modem not that the modem has successfully dialed The Connection Status Query message should be sent to determine whether a successful connection has been established Hang up This message causes the SLTA 10 Adapter to pulse the EIA 232 DTR signal Data Terminal Ready low for 500ms If the DCD signal is still ON following this step then the SLTA 10 Adapter SLTA 10 Adapter User s Guide 105 will send the hangup string see below if it is not a null string This will terminate the connection and the SLTA 10 Adapter enters the IDLE state The response will not be sent until this process is complete Therefore the transaction timer for this message should be set to at least 768ms if it is sent from a node on the network If this message is sent from a remote host no response should be expected since the connection will have been broken before the response can be sent typedef struct byte sub_code always 1 byte app_command value 8 boolean if config ANM_hangup_request If the SLTA 10 Adapter is forced to send the hangup string and this string does not exist in the EEPROM configuration the response to this message will indicate a failure If the if_config byte of this message is non zero the SLTA 10 Adapter sends the configuration string to the modem following the hangup process This provides a remote host with the ability
125. rface NSI mode functionality for use with LNS compliant applications and network interface functionality MIP mode for use with LonM anager API based applications There are two separate firmware images in the SLTA 10 Adapter The two separate images have different link layer protocols different network drivers different buffer capacity and different functionality The two modes of operation are the SLTA 10 NSI mode and the SLTA 10 MIP mode The mode of operation is controlled by an externally accessible DIP switch at power up Table 1 illustrates the differences between the SLTA 10 NSI mode the SLTA 10 MIP mode and the SLTA 2 Table 1 SLTA 10 NSI and MIP Modes and SLTA 2 Feature Comparison NSI Mode MIP Mode Supports LNS applications VES NOT NO applications Windows 95 Windows 3 1x Windows 3 1x planned SLTALink Manager HCU DOS HCU DOS connections via modems TAPI application application with application with source code source code Who initiates calls from a remote SLTA 10 itself Helper Dialer Helper Dialer node Input power options 9 30VAC or DC 9 30VAC or DC wall mount supply supply supply Configuration Switches Externally Externally Internally accessible accessible accessible Network Connector Color coded Color coded RJ45 removable screw removable screw terminals terminals Weidmuller Weidmuller Processor Input Clock 10 MHz 10 MHz 5 MHz 10MHZ for TP XF 1250 Bracket Required Transceiver
126. ron emulator and bound to the sample host application for testing DISPLAY H A Neuron C include file to drive the Gizmo 2 I O module for the test example e Host Connect Utility A sample host connection utility is contained in the Hcu directory with source code See Chapter 12 for details The files supplied are HCU EXE Executable file for the Host Connection Utility HCU_MAIN C The main C source program HCU CFG Configuration file for Borland C AKEFILE Make file script for Borland C SD_DRVR H Driver definition include file e Neuron C Connection Example A sample Neuron C program is contained in the NC_APPS directory This program shows how a node on a network connected to the SLTA 10 Adapter can dial out and connect to a remote host computer The files supplied are DIALOUT NC Neuron C source program to dial out with the SLTA 10 Adapter GIZSETUP NC An example Neuron C program for configuring the SLTA 10 Adapter Configures the EEPROM directories of an SLTA 10 Adapter using the Gizmo 2 O module as the user interface SLTA_ANM H Definitions of SLTA specific network management messages Installing the Windows 3 1x DLL Software A second diskette labeled LONWORKS Network Driver Interface for Windows 3 1x contains the 16 bit Windows Dynamic Link Library DLL files These files may be used when developing a host application to run under Microsoft Windows 3 1x The file WLDV DLL sho
127. s established the host computer communicates transparently with the network as though the SLTA 10 Adapter were attached locally SLTA 10 Adapter User s Guide 96 In NSI mode the SLTA 10 Adapter can be configured to initiate the connection with the host PC when LNS network management messages and or network variable updates are addressed to the SLTA 10 Adapter Alternatively another node on the local network can command the SLTA 10 Adapter to initiate the connection In MIP mode the SLTA 10 Adapter cannot itself initiate any connection it must be commanded to do so by another node on the local network or else by the modem s detection of an incoming call This means for example another node on the local network must initiate the dialing procedure when an alarm is detected that needs to be reported to the host Once a connection has been established however any node on the local network can communicate with the host by addressing messages to the SLTA 10 Adapter In order to support the modem functions the SLTA 10 Adapter Switch2 CF G2 input must be set to the Remote Host state UP position Switch1 CF G3 should be set to the default ALERT ACK link protocol DOWN position This automatically enables the reliable network interface transport protocol See Chapter 4 for details of the configuration inputs See Chapter 7 for using the SLTALink Manager with the SLTA 10 NSI mode or Chapter 8 for SLTA 10 MIP mode DOS network driver options Not
128. s not require a null terminator on exact sector size strings In the MIP mode EEPROM pool if a string winds up ending on the last byte of a sector a subsequent sector is required to hold the null terminator The network management functions that install these strings allow incremental EEPROM writes and indude a total_size field Incremental writes allow long strings to be installed without the requirement of large buffer sizes on the SLTA 10 Adapter If the total_size field is greater than the amount of EEPROM storage space available then the network management message response will indicate a failed status In all cases the strings should include a null terminator The offset field in the install messages indicates the starting point in the complete string of the current string piece to be installed The first byte of the complete string is at offset zero If the offset is such that the string piece would not fit in the allocated total size for the string the total size for that string is automatically extended if space is available All pieces of a string should specify the same value for total_size Otherwise it means that you are starting over with a new string Once a particular string has been installed in the pool it may be deleted by re installing it with a total size of 0 Alternatively the Clear EEPROM Pool message may be issued to clear the whole EEPROM string pool Product Query SLTA 10 Adapter User s Guide 102 This messag
129. se network management messages if network communications is disabled i e it is in the FLUSH state This will normally be the case if it is not connected to a host Therefore in order to be able to dial out and connect to a host the SLTA 10 Adapter must be configured to initialize with network communications enabled i e the NoRMAL state with the CFG1 input See Chapter 4 for more details The messages should be sent with request response service and the response code should be checked to see if the message was executed correctly it will be Ox3D if there was no error and Ox1D if there was Possible failure conditions are noted under each message Some of these network management messages return data to the sender in the response structure as noted below Note that some of these messages cause one or more bytes of EEPROM in the SLTA 10 Adapter to be written Each byte of EEPROM takes 20ms to write and the response is not sent by the SLTA 10 Adapter until after the command is executed This time should be taken into account when setting the transaction timer tx_timer in the message tag connection for implicit addressing or in the destination address for explicit addressing If the LonBuilder or LonM anager API binder is used to create the connection the transaction timer may be explicitly specified Example msg_tag SLTA_tag when msg_out code 0x7D network mgmt msg code msg_out tag SLTA_tag msg_out service REQU
130. serial device driver Drivers with these characteristics are typically provided with real time operating systems such as VRTX or time sharing operating systems such as UNIX or VMS In this case these drivers should be set up for binary data communications without software flow control SLTA 10 Adapter User s Guide 83 The buffered link protocol should not be used when the SLTA 10 Adapter is attached to a modem The buffered link protocol can only be used on multitasking operating systems such as UNIX if the host application executes often enough to empty any incoming buffers For example if the SLTA 10 Adapter is receiving 70 packets per second and each packet is 25 bytes the host will receive 1750 bytes per second If the host has a serial input buffer of 256 bytes the buffer will fill within 150 milliseconds if the host application is preempted If the host application is preempted for longer than 150 milliseconds incoming data will be lost due to lack of serial buffer space In this case the ALERT ACK protocol should be used or the buffer space increased to handle the worst case traffic during the maximum preemption period Transport Layer Protocol When used with a local host the SLTA 10 Adapter assumes a reliable connection and does not use a transport layer protocol When used with a remote host the SLTA 10 Adapter assumes that the link may not be reliable and enables the reliable transport protocol The reliable transport protocol
131. tain the following files e Read MeFile The README TXT file includes a list of all the files on the distribution disk and also includes any updates to the documentation that occurred since the SLTA 10 Adapter documentation was printed e DOS Network Driver Sources The SLTA 10 Adapter DOS network driver source code is contained in the LDVSLTA directory These files can be used as the basis for creating drivers for hosts other than PCs running DOS see also the UNIX network driver sources See Chapter 8 for a description of the SLTA 10 Adapter DOS network driver and Chapter 9 for a description of how to write an SLTA 10 Adapter network driver for other hosts See Chapter 4 of the LONWORKS Host Application Programmer s Guide for a description of the services that must be supplied by a LONWORKS network driver The source files to build the DOS driver are LDVSLTA CFG Configuration file for Borland C MAKEFILE Make file script for Borland C DV_TIME C Code to manage the PC timer MDV_TIME H External interface definitions for the timer handler SD_DEFS H Data structure and literal definitions MSD_DIFC C DOS driver interface functions SD_DRVR H DOS driver interface and literal definitions SD_EXEC C Main open close read and write processing SD_FRST C Module to be linked first in the network driver SD_IROC ASM Serial I O interrupt procedure SD_LAST C Module to be linked last in the network driver M
132. te SLTA 10 Adapter in a 12 byte string of characters or hexadecimal numbers This value here should match the value stored in the remote SLTA 10 Adapter It can be entered here as a string in single quotes or as a series of hexadecimal numbers separated by dashes If this field is blank or all zeroes 00 00 00 00 00 00 00 00 00 00 00 00 then the Remote Identifier will be captured and stored here the next time this connection is made If this field is all FFs FF FF FF FF FF FF FF FF FF FF FF FF then any Remote Identifier will be accepted The identifier will not be stored on the PC This is known as the wildcard Remote Identifier The question mark is also accepted as the wildcard Remote Identifier The SLTALink Manager software translates to all FFs The Update dentifier checkbox indicates that the remote identifier will be read from the SLTA 10 Adapter by the SLTALink Manager and the new value will be stored in the s10 file the next time this link is used The SLTALink Manager software allows a user to create two links with different names but the same Remote Identifier However when a network dials out to a PC with multiple links each with the Remote dentifier the user has no control over which link is selected which could result in undesired behavior Link Type The type of link specifies whether the SLTA 10 is directly connected to the PC Local or if the SLTA 10 is at a different location and must be accessed
133. text string containing the WLDV DLL version number Parameters None SLTA 10 Adapter User s Guide 125 Idv_open Purpose Initializes the network interface hardware for access by a Windows application A Windows application can open multiple network interfaces In the case of DOS drivers this is done by loading multiple drivers in conFic sys Initialization required to prepare the SLTA 10 Adapter is performed by this function Different drivers and hardware interfaces could require different initialization and configuration requirements Each driver must provide its own mechanism for providing these services In the case of DOS device drivers this is assumed to be command line options specified at the time the driver is loaded Note A driver should only allow itself to be opened once If the driver is already open it should return the error value 2 Syntax include lt ldv h gt short ldv_open char far device_id_p short far handle See Also ldv_close Returns LDV_OK 0 Device successfully opened LDV_NOT_FOUND 1 Hardware does not exist or is not accessible LDV_ALREADY_OPEN 2 Device already open LDV_DEVICE_ERR 4 Error occurred accessing device LDV_INVALID_DEVICE_ID 5 Invalid device ID LDV_NO_RESOURCES 8 No device handles available Parameters device_id_p char far Pointer toa character string identifying the network interface hardware device to be accessed The
134. than the response code a structure for the returned data is also defined EEPROM String Pool Management The SLTA 10 Adapter s EEPROM is used to store a number of varying length configurable strings which are used to control the modem These strings can be set by sending network management messages to the SLTA 10 Adapter either from the modem side or the network side Since the strings are varying in length and the EEPROM space is limited a pool management system is used to optimize the usage of EEPROM The SLTA 10 MIP mode EEPROM string pool and the SLTA 10 NSI mode EEPROM pool are different Changing the mode DIP switch and cyding power will destroy the EEPROM pool For the SLTA 10 MIP mode the EEPROM pool consists of the following strings e Uptoeight dial out directory entries These may be used by index to initiate a dial out connection and may contain any combination of AT commands and numbers e Onemodem initialization string This string is used to initialize the modem as required e Onemodem hang up string This string is used to hang up the modem and break the connection when DTR control does not function e Onedial out prefix string This string is sent as a prefix to any dial out operation to specify the modem dial command and to indicate whether tone or pulse dialing should be used SLTA 10 Adapter User s Guide 101 e An 8 byte dial in password string EEPROM storage and allocation for these strings is managed by the
135. the phone number is in the form of a canonical number This is defined as a country code followed by a space followed by an area code or city code enclosed in parenthesis followed by a space and the rest of the phone number TAPI will take this and decide how to translate it before the dial out based on your dialing preferences Even if the call is local the number should include the area code city code This is the same format as the number that appears in the link selection dialog under the Port Number column Using the DOS Stub Driver The DOS stub driver which is added as part of the install allows DOS and Windows 3 1x applications to run on top of the SLTA 10 driver for Windows NT The following line is required in the CONFIG NT file that is loaded on startup DEVICE SystemRoot system32 PCLTDOS SYS Dn This makes the device LONn available for DOS applications When LONn is opened by an application and the SLTALink Manager has been configured to associate LONn with a particular link the SLTALink Manager will auto connect to the SLTA 10 Adapter locally or remotely That is the SLTALink Manager automatically dials in to the network defined by the link if required Characteristics of a Well Designed System Well understood strategies used with the SLTA 10 Adapter and the SLTALink Manager for the following system functions are essential for reliable system design Call Initiation Call Termination and Monitor
136. tion When using the Windows NT driver the serial bit rate is configured using the SLTALink Manager as explained in Chapter 7 SLTA 10 Adapter User s Guide 34 default 38 400 bps Figure 16 SLTA 10 Adapter Serial Baud Rate Switches 6 7 and 8 BAUD 2 0 Table 10 SLTA 10 Adapter Autobaud Switch Configuration Autobaud BAUD Switches A Option on B Option on DOS Driver Switch DOS Driver down Specifies actual Don t care Specifies actual serial bit baud rate rate Must match switch position selected baud rate up Don t care Must be specified Specifies actual baud rate position SLTA 10 Adapter User s Guide Configuring the SLTA 10 Adapter Software The types of messages passed between the host and the SLTA 10 Adapter are determined by EEPROM configuration options These options are described under Network Interface Configuration Options in Chapter 3 of the LONWORKS Host Application Programmer s Guide The Network Disable Option affects whether or not the SLTA 10 Adapter can send and receive application messages The buffer configuration parameters can be changed at any time by sending Write Memory network management messages to the SLTA 10 Adapter either from a host using local network management messages or over the network from a network management tool See the Neuron Chip Data Book Appendix A for details of the data structures within the Neuron Chip that control the partitioning
137. uest the SLTA 10 Adapter to initiate a dial out operation to connect to the host In addition if the SLTA 10 Adapter is functioning in NSI mode the SLTA 10 Adapter itself may be configured to initiate a dial out operation to connect to the host The SLTA 10 Adapter can storea telephone directory of commonly called numbers as well as accept commands to dial any other number The SLTA 10 Adapter may also be configured to accept incoming calls and connect the network to the host Incoming callers may optionally be required to provide a password before the SLTA 10 Adapter will connect them to the network SLTA 10 Adapter User s Guide 95 Overview The SLTA 10 Adapter network interface may be attached to the host processor using modems and the switched telephone network Figure 37 illustrates this option Host Host Application LNS Software optional Driver Interface Network Driver EIA 232 Interface Telephone Network via null EIA 232 modem Interface Network SLTA 10 Interface Network Adapter via built in transceiver LONWORKS Network Figure 37 Using the SLTA 10 Adapter with Modems When the SLTA 10 Adapter is configured for modem support it will respond to special network management messages that cause it to communicate with the attached modem The modem used must support the Hayes standard AT command set allowing it to dial out auto answer incoming calls and set various parameters Once a connection i
138. uld be copied to your Windows directory typically c WINDOWS The files LDV H and LON H SLTA 10 Adapter User s Guide 47 should be copied to a directory in the include file search path of your C compiler The file WLDV LIB should be copied to a directory in the library search path of your application linker See Appendix A for information on using the Windows DLL Other Drivers A UNIX network driver and source code for the SLTA 10 MIP mode is available on the Echelon web site http Awww echelon com Chapter 9 discusses creating a SLTA 10 MIP mode driver for any host SLTA 10 Adapter User s Guide 48 Chapter 7 Using the Windows NT Driver and SLTALink Manager with SLTA 10 NSI Mode This chapter describes the SLTALink Manager software which establishes and configures local and remote links from the host PC to the SLTA 10 Adapter in NSI mode A remote link requires a pair of modems one attached to the SLTA 10 Adapter and the other attached to the host PC The SLTALink Manager software controls a remote SLTA 10 via modem through Windows Telephony Application Programming Interface TAPI services under Windows NT 4 0 or later The SLTALink Manager determines when a standard driver open call in a host application requires dialing and handles these cases Thus the host application does not need to know if the network services interface is a local SLTA 10 or a remote SLTA 10 Adapter NOTE Remote SLTA 10 Adapters cannot be us
139. ut did not use the N switch with HCU e Using XON XOFF flow control in your modem Since the SLTA 10 Adapter network interface protocol is a binary one this configuration will interfere with or lock up your modem Be sure that this feature is disabled in your modems SLTA 10 Adapter to Host Link Fails Partially This can be observed as retries at the link layer when certain downlink or uplink transfers are attempted This can be due to any of the following conditions in order of likelihood e Extreme case delays in either the modem or the connection In this case the DOS network driver s calculated timeout values are too short Increase the basic timeout value for the driver using the Rnn option Start with 10 for nn and go up SLTA 10 Adapter User s Guide 120 e Use with Microsoft Windows 3 1x particularly at higher serial bit rates 9600 or greater This is always a problematic case The priority of the serial I O interrupts for PC ATs is always lower than the DOS tick interrupt which is used by Windows to perform many multi tasking services During these services the serial I O interrupts may not be serviced in time resulting in lost uplink data One solution is to lower the serial bit rate Another solution may be to replace the PC AT s UART with the 16550 UART which has a 16 byte FIFO buffer built into it This only works for external modem configurations and will add about 16ms of interrupt headroom at 9600 bps because of th
140. uted in the Connectivity Starter Kit Model 58030 01 and from the Developer s Toolbox of the Echelon web site SLTA 10 Adapter User s Guide 14 LNS 1 0 1 01 and 1 5 Compatibility When the SLTA 10 Adapter is connected directly to the PC host i e no modems the SLTA 10 Adapter uses a direct connection For a direct connection the SLTA 10 Adapter behaves like any other NSI such as the PCLTA 10 Adapter or the PCC 10 PC Card In this case an SLTA 10 Adapter may be used without issue with applications based on LNS 1 0 1 01 or 1 50 The SLTA 10 Adapter is also designed so that a PC host can be connected to the network through a pair of modems and the telephone network In this scenario the PC is a remote host When the PC initiates the phone call to the SLTA 10 Adapter the remote host is said to dial in to the network When the SLTA 10 Adapter initiates a call to the PC the SLTA 10 is said to dial out to the remote host Once the phone connection is established the application running on the remote host can perform network management monitoring or control activities Applications based on LNS 1 0 or 1 01 do not have full functionality with respect to the SLTA 10 Adapter and modems because LNS 1 0 and 1 01 have default system behavior that is incompatible with using the SLTA 10 Adapter through modems For instance an application based on LNS 1 0 and 1 01 terminates i e shuts down in a manner that interferes with one th
141. ver the interface is opened or when the interface is reset and reports an niRESET to the host The driver keeps track of the number of available output buffers in the SLTA 10 Adapter by examining both uplink and downlink messages This option prevents the use of one message type A local network management command not using a request response service Normally this type of message is not used One exception could be the set Node Mode Reset command which would result in the node resetting and the buffer management recovering on its own anyway Otherwise if this type of message is used no uplink response would occur and the driver could not track the fact that a new output buffer has been made available SLTA 10 Adapter User s Guide 72 Table 15 Configuration Switches and DOS Driver Options Input State Driver Option Switch2 CFG 2 Local Host No Transport Protocol not specified Switch2 CFG 2 Remote Host Reliable Transport specified Protocol Switch1 CFG 3 ALERT ACK Link Protocol N not specified Switch1 CFG 3 Buffered Link Protocol N specified Calling the Network Driver from a Host Application The SLTA 10 MIP mode network driver for DOS supports the open close read write and ioct1 DOS calls See Chapter 4 of the Host Application Programmer s Guide for more details When the SLTA 10 MIP mode network driver for DOS is loaded during execution of the CONFIG SYS file it does not attempt to communicate with the SLTA 10 Ada
142. versions available TP FT 10 TP FT 10 TP FT 10 TP XF 78 TP XF 78 TP XF 78 TP XF 1250 TP XF 1250 TP XF 1250 TP RS485 To attach to a modem Special null Special null Internal jumper modem cable modem cable change to become DTE Supports sleep mode Po NOU CUNO VES Message Tag 15 available YES Default Buffer Configuration See Chapter 4 See Chapter 4 See SLTA 2 documentation SLTA 10 Adapter User s Guide 13 SLTA 10 NSI Mode Features The most important new feature of the SLTA 10 NSI mode is the NSI functionality for use with LNS compliant applications Other important features available only in the SLTA 10 NSI mode include SLTA 10 initiated dial out a Windows NT driver a high performance link layer protocol and the SLTALink Manager software These features are not available in SLTA 10 MIP mode The improved hardware form factor applies to both modes of operation and is listed in Table 1 In SLTA 10 NSI mode an SLTA 10 Adapter supports applications based on both the LNS software and the LonManager API SLTA 10 MIP Mode Versus the SLTA 2 In SLTA 10 MIP mode the SLTA 10 Adapter is a replacement for the SLTA 2 Serial LonTalk Adapter with an improved form factor The network connector on the SLTA 10 Adapter is the color coded removable screw terminal Weidmuller instead of the RJ 45 used on the SLTA 2 Adapter The SLTA 10 Adapter input power options include 9 30VAC or DC or a 9V wall mount supply The SLTA 10 Adapter operates at 1O
143. via a set of modems Remote Configuring the Modem Line Clicking on Configure Line will cause the selected modem s property window to appear The property window will reflect the options available to the driver of the modem such as volume control and dial tone detect TAPI services will handle the structuring of the call based on the Location Information see figure 21 SLTA 10 Adapter User s Guide 55 SLTA Password The Password box allows the user to enter the password for a remote SLTA 10 Adapter Up to eight characters may be entered If entered the password will be sent to the remote SLTA 10 adapter when a connection is made The password is not encrypted when stored on host computer Invoking an Application The SLTALink Manager provides a space to enter the startup application for this link This may be a full executable path name or the name of an application that can be found in the system s search path Command line arguments may also added including the special macros for link connection variables LINKNAME Expands to the name of the link enclosed in quotes DEVNAME Expands to the device name used by LONWORKS 32 bit applications to access the logical device This serves the same purpose as DOSNAME does for DOS NSSNAME Expands to the device name used by LonWorks LNS application for SLTA 10s this will be SLTALONn DOSNAME Expands to the DOS device name for the logical device provi